Burnham FD Installation and Operation Manual

0 (0)
DNAGNITAREPO,NOITALLATSNI
ROFSNOITCURTSNIECIVRES
TFARDDECROF"DF"
STINURENRUBRELIOBLEETS
FOR OIL, GAS
OR COMBINATION OIL-GAS FIRING
sserddA
8143401R6-7/03
,reliobnonoitamrofnignikeesnehW.rotcartnocgnitaehruoyllac,reliobotsriaperroecivresroF
.lebaLgnitaRnonwohssarebmuNlaireSdnarebmuNledoMrelioBedivorp
____________DF_______6
rotcartnoCgnitaeH rebmuNenohP
Price - $3.00
1
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning product life.
GNINRAW
nachcihwdrazahafoecneserpsetacidnI
rohtaed,yrujnilanosreperevesesuac
.derongifiegamadytreporplaitnatsbus
.derongifiegamad
NOITUAC
ECITON
nosnoitcurtsnilaicepssetacidnI
ecnanetniamro,noitarepo,noitallatsni
otdetalertontubtnatropmierahcihw
.sdrazahyrujnilanosrep
TABLE OF CONTENTS
INTRODUCTION TO "FD" SERIES STEEL BOILER-BURNER UNITS ...............................................................................3
DIMENSIONS AND RATING DATA.................................................................................................................................4 & 5
FURNACE FLOOR BLANKETS.........................................................................................................................................6 & 7
CERAMIC FIBER WARNING ...................................................................................................................................................8
CLEANING INSTRUCTIONS ....................................................................................................................................................9
BURNER DATA ...............................................................................................................................................................10 & 11
BECKETT BURNER SPECIFICATIONS .......................................................................................................................12 & 13
TANKLESS HEATER PERFORMANCE.................................................................................................................................14
COIL RATINGS.........................................................................................................................................................................15
INDIRECT WATER HEATER OPERATION ..........................................................................................................................16
COMBUSTION AND VENTILATION AIR REQUIREMENTS.............................................................................................16
VENTS—FAULTS AND SUGGESTIONS ..............................................................................................................................17
EXPANSION OR AIR CUSHION TANK ................................................................................................................................18
PIPING—FORCED HOT WATER HEATING ........................................................................................................................19
PIPING—DOMESTIC HOT WATER ......................................................................................................................................20
PIPING—FORCED HOT WATER HEATING AND DOMESTIC HOT WATER.................................................................20
PIPING—DOMESTIC HOT WATER WITH STORAGE TANK ...........................................................................................21
PIPING—RECIRCULATING DOMESTIC HOT WATER SYSTEM .................................................................................... 21
PIPING—MULTI-PURPOSE BOILER APPLICATION .........................................................................................................22
PIPING—MULTIPLE BOILER OPERATIONS (PARALLEL PIPING) ................................................................................22
ORDERING REPAIR PARTS ................................................................................................................................................... 23
JACKET PARTS IDENTIFICATION.......................................................................................................................................23
WARRANTY .............................................................................................................................................................. Rear Cover
rolliwhcihwdrazahafoecneserpsetacidnI
ytreporproyrujnilanosrepronimesuacnac
2
INTRODUCTION TO "FD" SERIES
STEEL BOILER BURNER UNITS
Due to an excellent combination of boiler and burner, the "FD" Series boiler-burner units are capable of developing the optimum in combustion and thermal efficiencies. The burner provides 12½% CO combustion efficiency in excess of 83% on #2 fuel oil. Forced draft operation is accomplished by means of a 3450 RPM motor and blower wheel on the burner and a factory sealed combustion chamber. The commonly used refractory type combustion chamber is not required.
Pressure is produced within the boiler by the "forced draft" operation of the burner eliminating the need for a chimney thus resulting in a substantial savings in building costs. A vent to the outside of the building is the only requirement. Boiler rooms can also be kept to a minimum size since one boiler equipped with a tankless heater can supply all of the heating requirements for comfort heating and domestic hot water.
For optimum performance and serviceability from these units adhere to the following recommendations:
1) Clean boiler flueways (firetubes after removing turbulator baffles) with a 3" OD flue brush, at least once a year and preferably at the end of the heating season, or as may be necessitated to remove all soot and scale. See Page 10 for cleaning instructions.
2) Have burner and controls checked at least once a year. See Pages 14, 15, 21 and 22 and burner manual for burner adjustment specifications.
3) Retain your contractor or a competent service agency to assure that the unit is properly adjusted and maintained.
4) The interior of the venting must be inspected and cleaned before the start of the heating season and should be inspected periodically throughout the heating season for any obstructions. A clean and unobstructed vent is necessary to allow noxious fumes that could cause injury or loss of life to vent safely and will contribute toward maintaining the boiler's efficiency.
for a
2
ECITON
noderiuqerebyamrepmadcirtemorabA
.noitidnoctfardhgihahtiwsnoitallatsni
FLUE DAMPER: The boiler is provided with a breaching damper which
should be secured in the open position for initial start up of the burner. The adjustable damper in the flue collar at the boiler outlet is provided so that if the installer or serviceman desires, he can easily introduce a flow restriction at the boiler outlet and thereby increase the pressure in the firebox. Normally, it is best to leave the damper wide open and to control air flow to the burner entirely by adjustments at the burner inlet. Flue restrictions such as a partially closed damper tend to make starts rougher. Boiler tests were run at 12½% CO2 and 0.1 inches of water stack pressure to demonstrate ample burner air capacity for good performance up to this pressure. Boiler pressure drop does not change measurably at different stack and firebox pressures as long as the burner is adjusted to maintain the same percent CO2.
MINIMUM INSTALLATION CLEARANCES TO COMBUSTIBLE MATERIAL:
FRONT - 48 Inches ABOVE OR TOP - 18 Inches SIDES - 18 Inches VENT CONNECTOR PIPE - 18 Inches REAR - 18 Inches
NOTE:
1. Listed clearances comply with American National Standard ANSI/NFPA 31, Installation of oil burning equipment.
2. FD Series boilers can be installed in rooms with clearances from combustible material as listed above. Listed clearances can not be reduced for alcove or closet installations.
3. For reduced clearances to combustible material, protection must be provided as described in the above ANSI/NFPA 31 standard.
4. Check dimensional data for boiler service recommended clearances.
For additional information consult the service department.
GNINRAW
reliobehtfonoitarepoehtretfaerehtraeya
.evlav
GNINRAW
skcolbgnicalpybreliobtroppustonoD
.reliobehtfosrenroc)4(ruofehtta
ecnotsaeltadnareliobsihtfonoitallatsninopU
wolehtylralucitrap,dekcehcebdluohsslortnoc feiler-ytefasdnalortnoctimilhgih,ffo-tucretaw
.esaberitnerednu
.erutsiomniatnoc
3
detroppusylneveebtsumesabrelioB
elbitsubmocnoreliobetarepotonoD
roolfdeilppusyrotcafatuohtiwroolf
sistsiojdoowrevoetercnoC.dleihs
tonoD.gniroolfelbitsubmocderedisnoc
yamhcihw,sroolfyrnosamnoetarepo
456
FURNACE FLOOR BLANKETS
The furnace floor and the furnace wall below the mud ring are not water backed. These surfaces must be insulated from the intense heat in the furnace. The FD Series boiler now employs precut, refractory ceramic fiber (RCF) blankets to provide this insulation. They are light weight, easy to handle and do not crack like the poured refractory used heretofore.
The blankets must be replaced if they become water logged or lose their thickness or shape for any other reason, such as abuse during firetube cleaning.
BLANKET INSTALLATION
1. Confirm that the blankets are the appropriate size for your FD boiler model using the chart opposite.
2. Unbolt the Burner Mounting Plate from the boiler and set it aside.
GNINRAW
ytefaStcudorPtnatropmIehtdaeR
.gnideecorperofeb8egaPnonoitamrofnI
3. Remove the Burner Mounting Plate Insulation. It may be poured-in-place refractory or precast, lightweight RCF. In either case, it may be reused if removed intact. Replacement, precast, lightweight RCF Burner Mounting Door Insulation is available from Burnham as Part No. 8203401 for Models FD7 through FD30 and as Part No. 8203402 for Models FD38 and FD45.
4. Thoroughly clean any refractory or other insulation out of the furnace.
5. On a flat surface, place the larger diameter 1" thick Bottom Blanket.
6. Lay the smaller diameter 2" thick Top Blanket in the center of the Bottom Blanket. Keep repositioning the Top Blanket until you have equal Bottom Blanket exposure all around the outside edge. See dimension 'C' in the chart opposite and refer to the illustration of blanket placement.
7. Fold the two (2) blankets in half, keeping the Top Blanket centrally positioned on the Bottom Blanket.
8. Slide the folded blankets through the Burner Mounting Plate opening and onto the furnace floor.
9. Unfold the blankets and position the blankets such that the larger diameter 1" thick Bottom Blanket curls up the wall of the furnace by at least 1½" all around the furnace.
It is important that this curled edge of the Bottom Blanket makes contact with the furnace wall all around to protect the furnace wall from overheating below the mudring. Refer to the illustration of correctly installed blankets.
10. Reinsert the Burner Mounting Plate Insulation and seal all gaps and cracks with ceramic caulking. Ceramic caulking is available from Burnham in 10 ounce tubes (Part No. 9056081) and in gallon pails (Part No. 9056982).
11. Reinstall the Burner Mounting Plate. Since neither the blankets nor the ceramic caulk require cure time, the boiler may be returned to service immediately.
7
noitamrofnIytefaStcudorPtnatropmI
tcudorPrebiFcimareCyrotcarfeR
Warning: This product contains refractory ceramic fibers (RCF). RCF has been classified as
a possible human carcinogen. After this product is fired, RCF may, when exposed to extremely high temperature (>1800F), change into a known human carcinogen. When disturbed as a result of servicing or repair, RCF becomes airborne and, if inhaled, may be hazardous to your health.
AVOID Breathing Fiber Particulates and Dust
Precautionary Measures: Do not remove or replace previously fired RCF (combustion chamber insulation,
target walls, canopy gasket, flue cover gasket, etc.) or attempt any service or repair work involving RCF without wearing the following protective gear:
1. A National Institute for Occupational Safety and Health (NIOSH) approved respirator
2. Long sleeved, loose fitting clothing
3. Gloves
4. Eye Protection
Take steps to assure adequate ventilation.
Wash all exposed body areas gently with soap and water after contact.
Wash work clothes separately from other laundry and rinse washing
machine after use to avoid contaminating other clothes.
Discard used RCF components by sealing in an air tight plastic bag.
First Aid Procedures:
If contact with eyes: Flush with water for at least 15 minutes. Seek immediate medical attention if irritation persists.
If contact with skin: Wash affected area gently with soap and water. Seek immediate medical attention if irritation persists.
If breathing difficulty develops: Leave the area and move to a location with clean fresh air. Seek immediate medical attention if breathing difficulties persist.
Ingestion: Do not induce vomiting. Drink plenty of water. Seek immediate medical attention.
8
Loading...
+ 16 hidden pages