Burnham 4FH-50 Data Sheet

SERIES 4FH-50
Webster Burner Information 5.0 ratings
Boiler
Size
4FH-63 JB1-02 4FH-78 JB1-03 4FH-92 JB1-03 4FH-107 JB1-03 4FH-127 JB1-03 4FH-154 JB1-03 4FH-180 JB1-05 4FH-209 JB2-10 4FH-240 JB1-07 4FH-277 JB2-10 4FH-311 JB2-10 1 240/60/1 L-H-O LFS L-H-O LFS RM7897C/UV RM7897C/UV RM7897C/UV 2 7" w.c. 28" w.c. 4FH-345
4FH-360 4FH-450 4FH-563
Burner
Model
[3]
JB2-10 1 240/60/1 L-H-O LFS L-H-O LFS RM7897C/UV RM7897C/UV RM7897C/UV 2 9" w.c. 28" w.c.
[3]
JB2-10 1 240/60/1 L-H-O LFS L-H-O LFS RM7897C/UV RM7897C/UV RM7897C/UV 2 9" w.c. 28" w.c.
[3]
JB2-30 3 230/460/3 L-H-O LFS L-H-O LFS RM7897C/UV RM7897C/UV RM7897C/UV 2 9" w.c. 28" w.c.
[3]
JB2-50 5 230/460/3 L-H-O LFS L-H-O LFS RM7897C/UV RM7897C/UV RM7897C/UV
[2]
1/4
120/60/1 On-Off On-Off RM7897C/UV R7284U/Cad RM7897C/UV 1 7" w.c. 14" w.c.
1/3
120/60/1 On-Off On-Off RM7897C/UV R7284U/Cad RM7897C/UV 1 7" w.c. 14" w.c.
1/3
120/60/1 On-Off On-Off RM7897C/UV R7284U/Cad RM7897C/UV 1 7" w.c. 14" w.c.
1/3
120/60/1 On-Off On-Off RM7897C/UV R7284U/Cad RM7897C/UV 1 7" w.c. 14" w.c.
1/2
120/60/1 L-H-O LFS On-Off RM7897C/UV R7284U/Cad RM7897C/UV
1/2
120/60/1 L-H-O LFS On-Off RM7897C/UV R7284U/Cad RM7897C/UV
3/4
120/60/1 L-H-O LFS On-Off RM7897C/UV R7284U/Cad RM7897C/UV
1
240/60/1 L-H-O LFS L-H-O LFS RM7897C/UV R7284U/Cad RM7897C/UV 2 7" w.c. 14" w.c.
3/4
120/60/1 L-H-O LFS L-H-O LFS RM7897C/UV R7284U/Cad RM7897C/UV 2 7" w.c. 14" w.c.
1
240/60/1 L-H-O LFS L-H-O LFS RM7897C/UV R7284U/Cad RM7897C/UV 2 7" w.c. 14" w.c.
Gas and
Gas/#2 Oil
4FH-675 JB3-50 5 230/460/3 L-H-O LFS L-H-O LFS RM7897C/UV RM7897C/UV RM7897C/UV 4FH-827 JB3-50 5 230/460/3 Full Mod Full Mod RM7840L/UV RM7840L/UV RM7840L/UV 3 14" w.c. 28" w.c.
Motor Firing Sequence
1/2
4FH-993 JB3-75
7
230/460/3 Full Mod Full Mod RM7840L/UV RM7840L/UV RM7840L/UV 3 27" w.c. 42" w.c. 4FH-1157 JB3-100 10 230/460/3 Full Mod Full Mod RM7840L/UV RM7840L/UV RM7840L/UV 3 27" w.c. 42" w.c. 4FH-1323 JB3-100 10 230/460/3 Full Mod Full Mod RM7840L/UV RM7840L/UV RM7840L/UV 3H 27" w.c. 42" w.c.
7
4FH-1654 HDRV5-75
1/2
230/460/3 Full Mod Full Mod RM7840L/UV RM7840L/UV RM7840L/UV 3 27" w.c. 42" w.c. 4FH-1985 HDRV5-100 10 230/460/3 Full Mod Full Mod RM7840L/UV RM7840L/UV RM7840L/UV 3 2# 5# 4FH-2315 HDRV7-150 15 230/460/3 Full Mod Full Mod RM7840L/UV RM7840L/UV RM7840L/UV 3 2# 5# 4FH-2645 HDRV7-200 20 230/460/3 Full Mod Full Mod RM7840L/UV RM7840L/UV RM7840L/UV 3 2# 5# 4FH-3075 HDRV9-400 40 230/460/3 Full Mod Full Mod RM7840L/UV RM7840L/UV RM7840L/UV 3 3# 5#
[1] Explanation of Firing Sequences:
[1]
Standard UL Flame Safeguard Gas Train
#2 Oil Gas #2 Oil Gas/#2 Oil
Size
1/4
1
1/2
1
1/2
1
1/2
2
1/2
2
[3]
Min. Pres. Max. Pres.
7" w.c. 14" w.c. 7" w.c. 14" w.c. 7" w.c. 14" w.c.
9" w.c. 28" w.c. 9" w.c. 28" w.c.
Gas and Gas Sequence on Combination Gas/Oil Boilers
On-Off Fixed fire with slow opening gas valve, fixed air. On-Off LFS Low fire start (not proven), high fire run, Lo-Hi-Off gas valve, air control by linkage from motorized gas valve. Full Mod Full modulation with proven low fire start, synchronized fuel/air control by modulating motor.
Oil and Oil Sequence on Combination Gas/Oil Boilers
On-Off On-Off fixed fire, fix air. On-Off LFS Low fire start (not proven), high fire, oil cylinder air control. Reduced input start with by-pass. Full Mod Full modulation with proven low fire start, synchronized fuel/air control by modulating motor. With oil metering valve and oil pressure
regulating valve.
[2] Gas is 1/4 hp and Oil & Combination Gas/Oil is 1/3 hp
[3] Gas trains for models 1654 and larger boilers are Siemens.
October 16, 2012
t
SERIES 4FH-50
Webster Burner Equipment
Equipmen
Control Cabinet Gas, #2 Oil, Gas/#2 Oil NEMA 1A with hinged door.
Control Voltage Transformer Gas, #2 Oil, Gas/#2 Oil Included when burner voltage is greater than 120/60/1.
Motor Starter Gas, #2 Oil, Gas/#2 Oil Contactor with single phase motor, magnetic starter with overload protection with
Fusing Gas, #2 Oil, Gas/#2 Oil Control circuit only.
Ignition Gas and Gas/#2 Oil Gas/Electric pilot.
Signal Lights Gas, #2 Oil, Gas/#2 Oil Power On, Fuel On, Call for Heat and Alarm
Air Flow Safety Switch Gas All models
#2 Oil and Gas/#2 Oil Models 4F-675 and larger. Exception on #2 oil models 4F-63 to 4F-450 with integral
Gas Train Gas and Gas/#2 Oil
Fuel Description
3-phase motor.
#2 Oil Direct spark (4F-63 to 4F-450).
Gas/Electric (4F-563 and larger).
oil pump. UL gas train for minimum inlet pressure indicated on Burner Information table. Shipped unassembled and consisting of the following: Manual shut-off valve. Gas pressure regulator. Manual leak test valve. Automatic gas valve: others (Proof of closure on 4F-675 and larger). Safety gas valve: Metering valve High and Low gas pressure switches:
Diaphragm type with On-Off sequence. Motorized all
Solenoid type.
: 4F-675 and larger.
4F-311 and larger.
Oil Pump #2 Oil and Gas/#2 Oil Integral with burner (4F-63 to 4F-450).
Separate oil pump set with motor and accessories mounted on boiler skid (4F-563 and larger).
Oil Pressure Gauge #2 Oil and Gas/#2 Oil All models.
Pilot Gas Controls Gas, #2 Oil, Gas/#2 Oil All models with gas/electric pilot have manual pilot shut-off valve, high gas pressure
regulator and solenoid gas valve.
Fuel Changeover Gas/#2 Oil Manual switch.
5/02
Loading...