For service or repairs to boiler, call your heating contractor. When seeking information on
boiler, provide Boiler Model Number and Serial Number as shown on Rating Label.
Boiler Model Number
20_PV_I -_ _ _ _
Heating ContractorAddress
8141775R12-3/01
Boiler Serial Number
6_ _ _ _ _ _ _
1
Installation Date
Phone Number
Price - $3.00
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk
levels, or to important information concerning product life.
DANGER
Indicates an imminently hazardous
situation which, if not avoided, will result
in death, serious injury or substantial
property damage.
WARNING
Indicates a potentially hazardous
situation which, if not avoided, could
result in death, serious injury or
substantial property damage.
IX.Repair Parts ............................................... 24
NOTICE
USA boilers built for installation at altitudes greater than 2,000 feet above sea level have
been specially orificed to reduce gas input rate 4 percent per 1,000 feet above sea level
per the National Fuel Gas Code, NFPA 54/ANSI Z223.1, Section 8.1.2 and Appendix F.
Canadian boilers' orifice sizing is indicated on the rating label. High altitude boiler
models are identifiable by the second digit in the model number suffix on the rating
label:
20_PV_I-__2: Less than 2000 ft. elevation
20_PV_I-__4: 2000 ft. and higher elevation, Canada
20_PV_I-__5: 2000 ft. and higher elevation, USA
2
Figure 1: Elevation Views
3
I. Pre-Installation
WARNING
Carefully read all instructions before
installing boiler. Failure to follow all
instructions in proper order can cause
personal injury or death.
A. Inspect shipment carefully for any signs of damage. All
equipment is carefully manufactured, inspected and
packed. Our responsibility ceases upon delivery of
boiler to carrier in good condition. Any claim for damage
or shortage in shipment must be filed immediately
against carrier by consignee. No claims for variances or
shortages will be allowed by Boiler Manufacturer,
unless presented within sixty (60) days after receipt of
equipment.
B. Installation must conform to the requirements of the
authority having jurisdiction. In the absence of such
requirements, installation must conform to NationalFuel Gas Code, NFPA 54/ANSI Z223.1, and/or CAN/
CGA B149 Installation Codes. Where required by the
authority having jurisdiction, the installation must
conform to the Standard for Controls and SafetyDevices for Automatically Fired Boilers, ANSI/ASME
CSD-1.
C. Appliance is design certified for installation on
combustible flooring. The boiler must not be installed
on carpeting.
D. Provide clearance between boiler jacket and
combustible material in accordance with local fire
ordinance. See Figure 2 for minimum clearance from
combustible material for closet installation. For alcove
installation provide top clearance of 27 inches and right
side clearance of 6 inches. Recommended service
clearance is 24 inches from left side, right side and front.
Service clearances may be reduced to minimum
clearances to combustible materials.
E. Install on level floor. For basement installation provide
solid base, such as concrete, if floor is not level or if
water may be encountered on floor around boiler.
F. Install near outside wall for through wall venting. Refer
to Section V: Venting, for vent length limitations.
WARNING
Certified as Category III appliance. Install
vent system in accordance with Section
V: Venting. Do not vent using masonry
chimney, Type B gas vent, or other
Category I venting system.
G. Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during boiler operation
and service (circulator replacement, condensate trap,
control replacement, etc.).
H. Provide combustion and ventilation air in accordance
with applicable provisions of local building codes, or
National Fuel Gas Code, NFPA 54/ANSI Z223.1,
Section 5.3, Air for Combustion and Ventilation, or
Sections 7.2, 7.3 or 7.4 of CAN/CGA B149 Installation
Codes.
WARNING
Adequate combustion and ventilation air
must be provided to assure proper
combustion.
The following guideline is based on the National Fuel
Gas Code, NFPA 54/ANSI Z223.1.
1. Determine volume of space (boiler room). Rooms
communicating directly with space (through
openings not furnished with doors) are considered
part of space.
Figure 2: Minimum Clearances to Combustible
Construction for Closet Installation
Volume [ft³] = Length [ft] x Width [ft] x Height [ft]
4
2. Determine Total Input of all appliances in space.
Round result to nearest 1,000 Btu per hour (Btuh).
3. Determine type of space. Divide Volume by Total
Input.
a. If result is greater than or equal to 50 ft³ per 1,000
Btuh, space is considered an unconfined space.
b. If result is less than 50 ft³ per 1,000 Btuh, space is
considered a confined space.
4. Determine building type. A building of unusuallytight construction has the following characteristics:
a. Direct communication with outdoors. Minimum
free area of 1 square inch per 4,000 Btu per hour
input of all equipment in space.
b. Vertical ducts. Minimum free area of 1 square
inch per 4,000 Btu per hour input of all equipment
in space. Duct cross-sectional area shall be same
as opening free area.
c. Horizontal ducts. Minimum free area of 1 square
inch per 2,000 Btu per hour input of all equipment
in space. Duct cross-sectional area shall be same
as opening free area.
a. Walls and ceiling exposed to outside atmosphere
have a continuous water vapor retarder with a
rating of 1 perm or less with openings gasketed
and sealed, and;
b. Weather-stripping has been added on openable
windows and doors, and;
c. Caulking or sealants applied in joints around
window and door frames, between sole plates
and floors, between wall-ceiling joints, between
wall panels, at plumbing and electrical
penetrations, and at other openings.
5. For boiler located in an unconfined space in abuilding of other than unusually tight construction,
adequate combustion and ventilation air is normally
provided by fresh air infiltration through cracks
around windows and doors.
6. For boiler located within unconfined space in
building of unusually tight construction or within
confined space, provide outdoor air through two
permanent openings which communicate directly or
by duct with the outdoors or spaces (crawl or attic)
freely communicating with the outdoors. Locate one
opening within 12 inches of top of space. Locate
remaining opening within 12 inches of bottom of
space. Minimum dimension of air opening is 3
inches. Size each opening per following:
Alternate method for boiler located within confined
space. Use indoor air if two permanent openings
communicate directly with additional space(s) of
sufficient volume such that combined volume of all
spaces meet criteria for unconfined space. Size each
opening for minimum free area of 1 square inch per
1,000 Btu per hour input of all equipment in spaces,
but not less than 100 square inches.
7. Ventilation Duct Louvers and Grilles. Equip outside
openings with louvers to prevent entrance of rain
and snow, and screens to prevent entrance of
insects and rodents. Louvers and grilles must be
fixed in open position or interlocked with equipment
to open automatically before burner operation.
Screens must not be smaller than ¼ inch mesh.
Consider the blocking effect of louvers, grilles and
screens when calculating the opening size to provide
the required free area. If free area of louver or grille is
not known, assume wood louvers have 20-25 percent
free area and metal louvers and grilles have 60-75
percent free area.
I.Do not install boiler where gasoline or other flammable
vapors or liquids, or sources of hydrocarbons (i.e.
bleaches, cleaners, chemicals, sprays, paint removers,
fabric softeners, etc.) are used or stored.
II. Unpack Boiler
CAUTION
Do not drop boiler. Do not bump boiler
jacket against floor.
A. Move boiler to approximate installed position.
B. Remove all crate fasteners.
C. Lift outside container and remove with all other inside
protective spacers and bracing. Save two of the
wooden slats from the container sleeve for use in
Paragraphs E and F.
D. Remove all boiler hold-down fasteners.
E. Tilt the boiler to one side and slide a wooden slat under
the two raised feet.
F. Tilt the boiler to the other side and slide another
wooden slat under the two raised feet.
G. Slide the boiler forward or backward off the skid using
the two wooden slats as runners.
H. Move boiler to its permanent location.
5
III. Water Piping and Trim
CAUTION
Failure to properly pipe boiler may result in
improper operation and damage to boiler or
building.
A. Design and install boiler and system piping to prevent
oxygen contamination of boiler water.
CAUTION
Oxygen contamination of boiler water will
cause corrosion of iron and steel boiler
components, and can lead to boiler failure.
Burnham's standard warranty does not
cover problems caused by oxygen
contamination of boiler water.
F. Space heating and domestic water heating with Alliance
water heater. Install Alliance water heater as a separate
heating zone. Refer to Alliance Installation, Operating and
Service Instructions for additional information.
G. If boiler is used in connection with refrigeration systems,
boiler must be installed with chilled medium piped in
parallel with the heating boiler using appropriate valves to
prevent chilled medium from entering boiler, see Figure 4.
Also consult I=B=R Installation and Piping Guides.
H. If boiler is connected to heating coils located in air
handling units where they may be exposed to refrigerated
air, boiler piping must be equipped with flow control
valves to prevent gravity circulation of boiler water during
operation of cooling system.
I.Use a boiler bypass if the boiler is to be operated in a
system which has a large volume or excessive radiation
where low boiler water temperatures may be encountered
(i.e. converted gravity circulation system, etc.).
Oxygen contamination sources are system leaks
requiring addition of makeup water, fittings, and oxygen
permeable materials in distribution system. Eliminate
oxygen contamination by repairing system leaks,
repairing fittings, and using nonpermeable materials in
distribution system.
B. Connect system supply and return piping to boiler. See
Figure 3. Also consult I=B=R Installation and Piping
Guides. Maintain minimum ½ inch clearance from hot
water piping to combustible materials.
C. Install Circulator with flanges, gaskets and bolts
provided. Five foot circulator harness allows circulator
to be mounted on supply or return. Connect harness to
circulator and secure any excess conduit.
D. Install Safety Relief Valve. See Figure 3. Safety Relief
Valve must be installed with spindle in vertical position.
Installation of the relief valve must be consistant with
the ANSI/ASME Boiler and Pressure Vessel Code,
Section IV.
WARNING
Safety relief valve discharge piping must be
piped near floor to eliminate potential of
severe burns. Do not pipe in any area
where freezing could occur. Do not install
any shut-off valves.
Install pipe tee between circulator and boiler return along
with second tee in supply piping as shown in Figure 3.
Bypass should be same size as the supply and return lines
with valves located in bypass and supply outlet as
illustrated in Figure 3 in order to regulate water flow to
maintain higher boiler water temperatures.
After the boiler is operational (reference Section VII.
System Start-Up) set by-pass and boiler supply valves to
half throttle position to start. Operate boiler until system
water temperature reaches normal operating range.
Adjust valves to provide 180° to 200°F supply water
temperature. Opening the boiler supply valve will raise
system temperature, while opening the by-pass valve will
lower system supply temperature.
J. A hot water boiler installed above radiation level must be
provided with a low water cut-off device as part of
installation.
K. Oil, grease, and other foreign materials which
accumulate in new hot water boilers and a new or
reworked system should be boiled out, and then
thoroughly flushed. A qualified water treatment chemical
specialist should be consulted for recommendations
regarding appropriate chemical compounds and
concentrations which are compatible with local
environmental regulations.
L. After the boiler and system have been cleaned and
flushed, and before refilling the entire system add
appropriate water treatment chemicals, if necessary, to
bring the pH between 7 and 11.
E. Install Drain Valve in ¾" NPT connection in tee
provided. See Figure 1.
6
Figure 3: Recommended Boiler Piping For Series - Loop Hot Water Heating Systems
Figure 4: Recommended Piping for Combination Heating & Cooling (Refrigeration) Systems
7
IV. Gas Piping
A. Size gas piping. Design system to provide adequate
gas supply to boiler. Consider these factors:
1. Allowable pressure drop from point of delivery to
boiler. Maximum allowable system pressure is ½
psig. Actual point of delivery pressure may be less;
contact gas supplier for additional information.
Minimum gas valve inlet pressure is listed on
rating label.
2. Maximum gas demand. Table 1 lists boiler input
rate. Also consider existing and expected future gas
utilization equipment (i.e. water heater, cooking
equipment).
Table 1: Rated Input
Boiler
Model
Number
Natural Gas LP/Propane
203PV6224¾½
204PV9638½½
Input Rate
[cubic feet per hour]
Gas
Connection
Size
3. Install sediment trap, ground-joint union and manual
shut-off valve upstream of boiler gas control valve
and outside jacket. See Figure 6.
4. All above ground gas piping upstream from manual
shut-off valve must be electrically continuous and
bonded to a grounding electrode. Do not use gas
piping as grounding electrode. Refer to NationalElectrical Code, ANSI/NFPA 70 and/or CSA C22
Electrical Code.
C. Pressure test. The boiler and its gas connection must
be leak tested before placing boiler in operation.
1. Protect boiler gas control valve. For all testing over
½ psig, boiler and its individual shut-off valve must
be disconnected from gas supply piping. For testing
at ½ psig or less, isolate boiler from gas supply
piping by closing boiler's individual manual shut-off
valve.
2. Locate leaks using approved combustible gas
detector, soap and water, or similar nonflammable
solution. Do not use matches, candles, open flames,
or other ignition source.
205PV13052½
206PV16465¾½
3. Length of piping and number of fittings. Refer to
Table 2 for maximum capacity of Schedule 40 pipe.
Table 3 lists equivalent pipe length for standard
fittings.
4. Specific gravity of gas. Gas piping systems for gas
with a specific gravity of 0.70 or less can be sized
directly from Table 2, unless authority having
jurisdiction specifies a gravity factor be applied. For
specific gravity greater than 0.70, apply gravity
factor from Table 4. If exact specific gravity is not
shown choose next higher value.
For materials or conditions other than those listed
above, refer to National Fuel Gas Code, NFPA 54/
ANSI Z223.1, or size system using standard
engineering methods acceptable to authority having
jurisdiction.
B. Connect boiler gas valve to gas supply system.
1. Use methods and materials in accordance with local
plumbing codes and requirements of gas supplier.
In absence of such requirements, follow NationalFuel Gas Code, NFPA 54/ANSI Z223.1 and/or
CAN/CGA B149 Installation Codes.
2. Use thread (joint) compounds (pipe dope) resistant
to action of liquefied petroleum gas.
Figure 6: Recommended Gas Piping
8
Table 2: Maximum Capacity of Schedule 40 Pipe in CFH For Gas Pressures of 0.5 psig or Less
0.3 inch w.c. Pressure Drop0.5 inch w.c. Pressure Drop
½¾11¼½¾11¼
Table 3: Fitting Equivalent LengthsTable 4: Specific Gravity Correction Factors
Nominal Pipe Size
Fitting
½¾11¼
45° Ell0.711.21.6
90° Ell1.62.12.63.5
Tee (As Elbow)3.14.15.26.9
Specific
Gravity
0.501.101.301.07
0.551.041.401.04
0.601.001.501.00
0.650.961.600.97
0.700.931.700.94
Correction
Factor
Specific
Gravity
Correction
Factor
V. Venting
A. General Guidelines.
1. Vent system installation must be in accordance with
National Fuel Gas Code, NFPA 54/ANSI Z221.3,
Part 7, Venting of Equipment; and/or CAN/CGA
B149 Installation Codes, Section 7, Venting Systems
and Air Supply for Appliances; or applicable
provisions of local building codes. Contact local
building or fire officials about restrictions and
installation inspection in your area.
2. This appliance requires a Special Gas Vent. Use Vent
Connector and Vent Terminal in Vent Accessory
Carton provided with boiler (See Repair Parts, Key
No. 8). The product is designed to use Burnham
supplied AL 29-4C® Stainless Steel vent system
components. The following manufacturers offer
similar AL 29-4C® components and are approved for
use with this product: Heat-Fab Inc. - Saf-T-Vent,
0.750.90
0.800.87
Flex-L International Inc., - Star-34, Protech Systems,
Inc. - FasNSeal™, and Z-Flex U. S., Inc. - Z-Vent.
The use of these alternate manufacturer's venting
systems will require adapters to connect to the
Burnham supplied vent connector and vent terminal.
These adapters are not supplied with this unit and
should be obtained from the supplier of the alternate
manufacturer's venting system. See Table 5 for
complete list of Burnham Vent System Components.
WARNING
Do not use this appliance with nonmetallic
vent systems such as Hart & Cooley
Ultravent, Plexco Plexvent, or SelkirkMetalbestos Sel-Vent.
9
Table 5: Burnham Vent System Components
Burnham
Vent System
Component
*Cartoned
Part
Number
3" Dia. Pipe x 1 Ft611601128116135
3" Dia. Pipe x 3 Ft611601018116058
3" Dia. Pipe x 4 Ft**8116176
3" Dia. Pipe x 5 Ft611601118116059
* Complete with Locking Band(s)
* * 6116033 Contains (4) 4 ft. lengths
6116040 Contains (2) 4 ft. lengths
3. Vent length restrictions are based on equivalent feet
of vent pipe (total length of straight pipe in feet plus
5 equivalent feet for each 45° or 90° elbow). Do not
exceed the maximum certified vent length of 25
equivalent feet. The minimum certified vent length is
7 equivalent feet. Do not include vent terminal or
vent connector in equivalent feet calculations.
4. Do not install venting system components on the
exterior of the building except as specifically required
by these instructions.
B. Removal of Existing Boiler. For installations not
involving the replacement of an existing boiler, proceed
to Step C.
When an existing boiler is removed from a common
venting system, the common venting system is likely to
be too large for proper venting of the remaining
appliances. At the time of removal of an existing boiler,
the following steps shall be followed with each
appliance remaining connected to the common venting
system placed in operation, while the other appliances
remaining connected to the common venting system are
not in operation:
(a) Seal any unused openings in the common venting
system.
(b)Visually inspect the venting system for proper size
and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion, and other
deficiencies which could cause an unsafe condition.
(c) Insofar as is practical, close all building doors and
windows and all doors between the space in which
the appliances remaining connected to the common
venting system are located and other spaces of the
building. Turn on clothes dryers and any appliance
not connected to the common venting system. Turn
on any exhaust fans, such as range-hoods and
bathroom exhausts, so they will operate at maximum
speed. Do not operate a summer exhaust fan. Close
fireplace dampers.
(d)Place in operation the appliance being inspected.
Follow the Lighting (or Operating) Instructions.
Adjust thermostat so appliance will operate
continuously.
(e) Test for spillage at the drafthood relief opening after
5 minutes of main burner operation. Use the flame of
a match or candle, or smoke from a cigarette, cigar or
pipe.
(f) After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined above,
return doors, windows, exhaust fans, fireplace
dampers and any other gas burning appliance to
their previous conditions of use.
(g)Any improper operation of the common venting
system should be corrected so the installation
conforms with the National Fuel Gas Code, NFPA
54/ANSI Z223.1. When resizing any portion of the
common venting system, the common venting
system should be resized to approach the minimum
size as determined using the appropriate tables in
Part II in the National Fuel Gas Code, NFPA 54/
ANSI Z223.1.
C. Install Vent Connector.
1. Remove vent connector from vent accessory carton.
2. Remove gaskets, orifice plate and hardware from
blower outlet flange.
3. Assemble orifice plate gaskets, orifice plate, and
vent connector. See Figure 7.
4. Secure vent connector with washers and locknuts.
Figure 7: Vent Connector Installation
10
D. Install Vent Pipe, General.
1. Start at vent connector. Work toward vent terminal.
2. Use ¾ inch pipe strap to support horizontal runs,
maintain vent location and slope, and prevent sags.
Do not restrict thermal expansion movement.
Maximum support spacing is 5 feet.
3. Provide minimum 5 inch clearance to combustible
materials. Use thimble when penetrating combustible
wall.
a. 203PV and 204PV - Single wall thimble, Burnham
Part No. 8116116. Other wall thimble
manufacturers are American Metal Products, Hart
& Cooley, and Metal Fab.
b. 205PV and 206PV - Double wall thimble, Burnham
Part No. 8116115 (accomodates 5" to 8¾" wall
thickness). Another wall thimble manufacturer is
Hart & Cooley.
4. Cut pipe to length using hacksaw with minimum 32
teeth per inch or circular saw with metal abrasive
wheel. Remove bead end only - bell end accepts next
fitting or pipe. Cut must be square with pipe. Scrape
off burrs with sharp edged tool.
Note: If remaining pipe (less bell) must be used,
beaded end of mating pipe/fitting must be crimped.
5. Seal all joints using Dow Corning Silastic 732 RTV,
Dow Corning Silastic 736 RTV, Polybac #500 RTV, or
Sil-bond RTV 4500 (Acetoxy). Do not use other
adhesives or sealants.
6. Procedure for joining pipe and fittings. See Figure 8.
a. Clean pipe or fitting. Remove all dirt and grease.
b. Slip locking band over pipe/fitting bell.
c. Apply continuous ¼ inch bead of sealant around
bead end of pipe/fitting no more than 1/8 inch
from end.
d. Insert pipe/fitting into bell. Smooth sealant for
continuous seal around gap between bead and
bell. Apply additional sealant if necessary.
e. Slip locking band over joint and tighten. Do not
secure joint with sheet metal screws or pop rivets.
E. Horizontal (Through Wall) Vent Installation.
1. Maintain minimum ¼ inch per foot slope in
horizontal runs. Slope pipe down toward vent
terminal.
CAUTION
2. Vent terminal location restricted per following:
a. Minimum 12 inches above grade plus normally
expected snow accumulation level, or 7 feet
above grade if located adjacent to public
walkway. Do not install over public walkway
where local experience indicates condensate or
vapor from Category III appliances creates a
nuisance or hazard.
Figure 8: Typical Joint Detail
b. Minimum 3 feet above any forced air inlet located
within 10 feet.
c. Minimum 4 foot below, 4 foot horizontally from,
or 1 foot above any door, window, or gravity air
inlet.
d. Minimum 4 feet horizontally from, and in no case
above or below, unless a 4-foot horizontal
distance is maintained, from electric meters, gas
meters, regulators and relief equipment.
e. Minimum 12 inches from overhang or corner.
3. Use wall thimble when passing through combustible
outside wall (thimble use optional for
noncombustible wall). Insert thimble through wall
from outside. Secure outside flange to wall with nails
or screws, and seal with adhesive material. Install
inside flange to inside wall, secure with nails or
screws, and seal with adhesive material.
4. For noncombustible wall when thimble is not used,
size opening such that bell with locking band
attached cannot pass through.
5. Join vent terminal to vent pipe. Cut vent pipe to
locate vent terminal 3 inches (minimum) and 6 inches
(recommended) from wall when joined to inside vent
piping. See Figure 9. Vent terminal clearance to vinyl
wall surfaces is 6 inches.
Moisture and ice may form on surfaces
around vent terminal. To prevent
deterioration, surfaces should be in good
repair (sealed, painted etc.)
6. Insert vent pipe through thimble/opening from
outside and join to vent system. Apply sealant
between vent pipe and opening/thimble to provide
weathertight seal.
11
VI. Electrical
Figure 9: Recommendations for Thimble and Wall Penetration
A. General. Install wiring and ground boiler in
accordance with requirements of authority having
jurisdiction, or in absence of such requirements the
National Electrical Code, ANSI/NFPA 70, and/or the
CSA C22.1 Electric Code.
B. Install thermostat. Locate on inside wall approximately
4 feet above floor. Do not install on outside wall, near
fireplace, or where influenced by drafts or restricted air
flow, hot or cold water pipes, lighting fixtures,
television, or sunlight. Allow free air movement by
avoiding placement of furniture near thermostat.
C. Wire thermostat. Provide Class II circuit between
thermostat and boiler. Run wires through grommet in
Jacket Left Side Panel. Set thermostat heat anticipator
to 0.6 amps. See Figure 10.
D. Wire boiler. Boiler is rated for 120 VAC, 60 hertz, less
than 12 amperes. Provide individual branch circuit with
fused disconnect. Connect to black and white wires and
green ground screw. See Figure 10.
E. Alliance water heater (if used). See Figure 10. Also refer
to Alliance Installation, Operating and Service
Instructions.
1. Zoning with Circulators, Domestic Hot Water
Priority. Provide DPDT relay (included with PAL).
Connect coil to Alliance thermostat (prewired with
PAL). Connect normally open contacts (red and
white wires in PAL control harness) to transformer
terminals 'R' and 'Y'. Disconnect yellow circulator
wire. Connect normally closed contacts (violet
wires in PAL boiler harness) to yellow relay wire
and yellow circulator wire.
2. Zoning with Circulators, Nonpriority. Connect
Alliance circulator zone control (or red and white
wires in PAL control harness) to transformer
terminals 'R' and 'Y'.
3. Zoning with Zone Valves. Connect Alliance
thermostat to zone valve. Connect zone valve end
switch to relay terminals 'R' and 'G'. See Paragraph
F.
F. For installations using zone valves provide separate
transformer for zone valve wiring. Consult zone valve
manufacturer for assistance.
12
VII. System Start-up
Figure 10: Wiring Diagram
A. Safe operation and other performance criteria were met
with gas manifold and control assembly provided on
boiler when boiler underwent tests specified in
American National Standard for Gas-Fired LowPressure Steam and Hot Water Boilers, ANSI Z21.13.
B. Fill heating system with water and vent air from system.
Use the following procedure on a Series Loop System
equipped with zone valves. See Figure 3.
1. Close isolation valve in boiler supply piping.
2. Isolate all circuits by closing zone valves or
balancing valves.
3. Attach hose to bib cock located just below isolation
valve in boiler supply piping. Terminate hose in five
gallon bucket at a suitable floor drain or outdoor
area).
4. Starting with one circuit, open zone valve.
5. Open bib cock.
6. Open fill valve. Makeup water line should be located
directly above isolation valve in boiler supply
piping.
8. Open zone valve to second zone to be purged, then
close first. Repeat this step until all zones have been
purged, but always have one zone open. At
completion, open all zone valves.
9. Close bib cock, continue filling system until pressure
gauge reads 12 psi. Close fill valve.
Note: If makeup water line is equipped with pressure
reducing valve, system will automatically fill to 12
psi. Leave globe valve open.
10. Open isolation valve in boiler supply piping.
11. Remove hose from bib cock.
C. Check main burners. See Figure 11. Rear of burner
must be in vertical slot in rear of burner tray. Front of
burner must be seated on orifice.
7. Allow water to overflow from bucket until discharge
from hose is bubble free for 30 seconds.
13
Figure 11: Main Burner Installation
Figure 12: Gas Valve Pressure Tap
D. Prepare to check operation.
1. Obtain gas heating value (in Btu per cubic foot) from
gas supplier.
2. Connect manometer to pressure tap on gas valve.
See Figure 12.
3. For natural gas fired boiler, temporarily turn off all
other gas-fired appliances.
E. Follow Operating Instructions to place boiler in
operation. See Figure 17.
F. Sequence of Operation. See Figure 14. If boiler fails to
operate properly, see Troubleshooting Tree on pages
17-18.
G. Check gas piping and connections between Gas Valve
and Manifold, Orifices and Pilot Tubing. Use soap
solution or other approved method. See Figure 13.
H. Check pilot burner flame. See Figure 15. Flame should
be steady, medium hard blue enveloping 3/8 to ½ inch
of sensing probe.
I.Check main burner flame. See Figure 16. Flame should
have clearly defined inner cone with no yellow tipping.
Orange-yellow streaks should not be confused with true
yellow tipping.
Figure 13: Schematic Pilot and Gas PipingFigure 15: Pilot Burner Flame
Figure 14: Sequence of Operation
14
Table 6: Gas Flow Rate in Cubic Feet per Hour
Figure 16: Main Burner Flame
J. Check thermostat operation. Raise and lower
temperature setting to start and stop boiler operation.
K. Check ignition control module shut-off. Disconnect
igniter/sensor cable from Terminal 9 (SPARK). Gas valve
should close and pilot and main burners should
extinguish.
L. Check low water cut-off (if used). Drain boiler water
2. Observe temperature gauge. When temperature is
indicated, adjust limit to setting below observed
temperature. Main burners and pilot burner should
extinguish and blower stop.
3. Adjust limit to setting above observed temperature.
Ignition sequence should begin.
4. Adjust thermostat to lowest setting. Adjust limit to
desired setting.
N. Adjust gas input rate to boiler (Natural Gas).
1. Adjust thermostat to highest setting.
2. Check manifold gas pressure. Manifold pressure is
listed on rating label. Adjust gas valve pressure
regulator as necessary (turn adjustment screw
counterclockwise to decrease manifold pressure, or
clockwise to increase manifold pressure). If pressure
can not be attained, check gas valve inlet pressure.
If less than minimum gas supply pressure listed on
rating label, contact gas supplier for assistance.
3. Clock gas meter for at least 30 seconds. Use Table 6
to determine gas flow rate in Cubic Feet per Hour.
4. Determine Input Rate. Multiply gas flow rate by gas
heating value.
5. Compare measured input rate to input rate listed on
rating label.
a. Boiler must not be overfired. Reduce input rate
by decreasing manifold pressure. Do not reduce
more than 0.3 inch w.c. If boiler is still overfired,
contact your Burnham distributor or Regional
Office for replacement Gas Orifice.
b. Increase input rate if less than 98% of rating label
input. Increase manifold gas pressure no more
than 0.3 inch w.c. If measured input rate is still
less than 98% of rated input:
i.Remove Main Burners per procedure in
Section VIII: Service.
ii.Remove gas orifices. Drill one (1) drill size
larger (drill size is stamped on orifice, or see
Key No. 4D).
iii. Reinstall gas orifices and main burners.
Measure input rate.
6. Recheck Main Burner Flame.
7. Adjust thermostat to normal setting.
8. Return other gas-fired appliances to previous
conditions of use.
O. Adjust gas input rate to boiler (LP/Propane).
1. Adjust thermostat to highest setting.
2. Check manifold pressure. Adjust gas valve pressure
regulator to obtain 10 inches w.c. manifold pressure.
15
Adjust gas valve pressure regulator as necessary
(turn adjustment screw counterclockwise to
decrease manifold pressure, or clockwise to increase
manifold pressure). If pressure can not be attained,
check gas valve inlet pressure. If less than minimum
gas supply pressure listed on rating label, contact
gas supplier for assistance.
3. Recheck Main Burner Flame
4. Adjust thermostat to normal setting.
P. COMBUSTION CHAMBER BURN-OFF
1. The mineral wool combustion chamber panels
contain a cornstarch based binder that must be
burned out at installation to prevent odors during
Figure 17: Operating Instructions
subsequent boiler operation.
2. Ventilate the boiler room, set the high limit to its
maximum setting, set the thermostat to call for heat.
Allow the boiler to fire for at least an hour or until
the odor from the cornstarch has dissipated.
3. Return the high limit and thermostat to their desired
settings.
Q. Review User's Information Manual and system
operation with owner or operator.
R. Post instructions near boiler for reference by owner and
service personnel. Maintain instructions in legible
condition.
16
TROUBLE SHOOTING GUIDE
SPLIT (SEPARATE) CONTROLS, 24 VOLT OPERATION WITH
ELECTRONIC IGNITION AND INTERMITTENT CIRCULATION
NOTE: 1. Read Sequence of Operation prior to using Trouble Shooting Guide.
See Page 14.
2. Prior to replacing a control, always check for broken wires or loose connectors that
provide power to that control.
17
18
Note: Minimum pilot signal should be 1.0 microamps. Disconnect Pilot Ground wire from Module and connect
DC microammeter between Ground Terminal and Pilot Ground wire.
19
Important Product Safety Information
Refractory Ceramic Fiber Product
Warning:
This product contains refractory ceramic fibers (RCF). RCF has been classified
as a possible human carcinogen. After this product is fired, RCF may, when
exposed to extremely high temperature (>1800F), change into a known human
carcinogen. When disturbed as a result of servicing or repair, RCF becomes
airborne and, if inhaled, may be hazardous to your health.
AVOID Breathing Fiber Particulates and Dust
Precautionary Measures:
Do not remove or replace previously fired RCF (combustion chamber insulation,
target walls, canopy gasket, flue cover gasket, etc.) or attempt any service or
repair work involving RCF without wearing the following protective gear:
1. A National Institute for Occupational Safety and Health (NIOSH)
approved respirator
2. Long sleeved, loose fitting clothing
3. Gloves
4. Eye Protection
•Take steps to assure adequate ventilation.
•Wash all exposed body areas gently with soap and water after contact.
•Wash work clothes separately from other laundry and rinse washing
machine after use to avoid contaminating other clothes.
•Discard used RCF components by sealing in an air tight plastic bag.
First Aid Procedures:
•If contact with eyes: Flush with water for at least 15 minutes. Seek
immediate medical attention if irritation persists.
•If contact with skin: Wash affected area gently with soap and water.
Seek immediate medical attention if irritation persists.
•If breathing difficulty develops: Leave the area and move to a location
with clean fresh air. Seek immediate medical attention if breathing
difficulties persist.
•Ingestion: Do not induce vomiting. Drink plenty of water. Seek
immediate medical attention.
20
VIII. Service
A. General. Inspection and service should be conducted
annually. Turn off electrical power and gas supply while
conducting service or maintenance. Follow instructions
TO TURN OFF GAS TO APPLIANCE. See Figure 17.
CAUTION
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation. Verify
proper operation after servicing.
B. Inspect Housekeeping. Boiler area must be clear and
free from combustible materials, gasoline and other
flammable vapors and liquids. Remove obstructions to
the flow of combustion and ventilation air.
C. Service Low water cut-off (if so equipped). Follow
instructions provided with low water cut-off
D. Inspect Vent System for obstructions in vent pipe, soot
accumulation, deterioration of pipe or joints, and proper
support:
a. If passageways are free of soot and obstruction,
replace canopy, secure and seal using kit
available from Burnham Distributors, Part No.
6111716.
b. If passageways need cleaning, remove burners as
described in Paragraph F below. Using long
handle wire or bristle flue brush and vacuum,
brush flueways thoroughly from top of boiler as
illustrated in Figure 19. Replace canopy and seal
using kit available from Burnham Distributors,
Part No. 6111716.
WARNING
Canopy must be resealed with RTV-732
Silicone Rubber Sealant (500°F Intermittent
Duty).
6. Reinstall jacket top panel, vent pipe and vent
connector in reverse manner. Reconnect electrical
connector to blower.
F. Clean Main Burners and Firebox.
1. Remove vent connector and vent pipe. See Figure
19.
2. Remove all obstructions. Check and clean vent
terminal screens.
3. Remove soot accumulations with wire brush and
vacuum.
4. Replace deteriorated parts.
5. Repair deteriorated joints. See Section V: Venting,
Paragraph D.6.
E. Inspect Boiler Flue Passages for blockage or soot
accumulation. See Figure 19.
1. Disconnect vent connector from blower discharge
flange.
2. Remove sheet metal screws securing Jacket Top
Panel. Lift panel and rotate about relief valve piping
until top of boiler is exposed. If piping or wall
prevent full rotation of top panel for access to
canopy, cut slot into relief valve opening and
remove top panel.
3. Disconnect blower connection from wiring harness
in vestibule.
4. Remove bolts securing canopy to boiler sections.
Cut silastic sealant around base of canopy, pry
canopy from boiler sections and remove canopy/
blower assembly from boiler.
5. Using flashlight, examine all flue passageways.
1. To remove burners for cleaning, changing orifice
plugs, or repairs:
a. Remove jacket Front Panel.
b. Disconnect pilot tubing at gas valve.
c. Disconnect igniter/sensor cable and ground wire
at Ignition Module.
d. Disconnect Flame Rollout Switch wires.
e. Remove Burner Access Panel.
f. Mark Pilot Main Burner location on Manifold.
g. Hold burner on throat. Lift slightly to clear orifice.
Pull burner from combustion chamber. See Figure
11. Pilot Main Burner can only be removed by
lifting at 45° angle after adjacent burner to right is
removed.
2. Brush top of burners with a soft bristle brush. See
Figure 19. Vacuum burners.
3. Check orifices. Drilled passageways must be free of
lint or dirt.
4. Vacuum tip of Pilot Burner.
5. Clean firebox by vacuuming. Exercise care not to
disturb insulation inside base.
6. Install burners by reversing procedure used to
remove burners. Burner with pilot assembly must be
in same location as original installation. See Table 7.
Burners must be properly located on support bracket
21
Table 7: Pilot Burner Location
Boiler
Model
203PV11 & 2
204PV22 & 3
205PV33 & 4
206PV44 & 5
* Main burners numbered left to right as viewed from
front of boiler.
Main Burner with
60° Pilot Bracket *
Pilot Burner Located
Between Main
Burners *
at rear of burner. See Figure 11. Slide burner
over orifice.
7. Reconnect pilot gas supply, igniter/sensor
cable, and ground wire. Reinstall Burner
Access Panel. Reconnect Flame Rollout
Switch wires.
G. Check operation. Follow Paragraphs D through
O from Section VII: System Start-up.
H. Removal or replacement of pilot assembly or
pilot assembly parts. If pilot assembly, sensor or
pilot orifice need replacing, remove main burner
with pilot using procedure described in
Paragraph F.1.
Figure 18: Spark Gap Setting
1. To replace orifice.
a. Disconnect pilot tubing. Pilot orifices
screw into Pilot Burner. Replace with
Honeywell 388146NE (Natural Gas) or
Honeywell 388146KP (LP/Propane).
b. Reconnect pilot tubing and check for
leaks.
2. To adjust or check spark gap between
electrode and hood on Honeywell Q348A
intermittent pilot. See Figure 18.
a. Use round wire gauge to check spark
gap.
b. Spark gap should be 1/8 inch for optimum
performance.
3. To replace complete pilot assembly.
a. Remove two machine screws holding
pilot burner to pilot bracket.
b. Disconnect pilot tubing.
c. Disconnect all other leads to pilot.
d. Select pilot assembly with identical model
number, reconnect leads and pilot tubing.
Resecure to pilot bracket.
4. Reinstall main burner following procedure
described in Paragraph F.
I.Lubrication. There are no parts requiring lubrication by
service technician or owner. Circulator bearings are
water lubricated. Blower motor bearings are factory
sealed.
Figure 20: Procedure for Measuring Fan Suction
Pressure
23
IX. Repair Parts
All Series 2PV Repair Parts may be obtained through your local Burnham Wholesale distributor. Should you require assistance
in locating a Burnham distributor in your area, or have questions regarding the availability of Burnham products or repair parts,
please contact your Burnham Regional Sales Office as listed below.
Burnham Corporation Regional Offices
A. Burnham Corporation - Central & Western Regions
AlabamaA NebraskaA OregonA
AlaskaA NevadaA PennsylvaniaD
ArizonaA New HampshireB Rhode IslandB
ArkansasA New JerseySouth CarolinaA
CaliforniaA
ColoradoACape May, Cumberland,TennesseeA
ConnecticutBGloucester, Mercer,TexasA
DelawareDMonmouth, Ocean, SalemUtahA
Atlantic, Burlington, Camden,
South DakotaA
D
FloridaA
GeorgiaAAll other CountiesC Virginia
HawaiiA New MexicoAArlington,Accomack,Clarke,
IdahoA New YorkFairfax,Frederick,Fauquier,
IllinoisA
IndianaARensselaer, Saratoga,Prince William Counties
IowaASchenectady, Schoharie,All other CountiesA
KansasAWarren, Washington CountiesWashingtonA
KentuckyA
LouisianaA North CarolinaA West VirginiaD
MaineB North DakotaA WisconsinA
MarylandD OhioWyomingA
MassachusettsB
MichiganAJefferson, Lawrence, Meigs,
MinnesotaAMonroe, and Washington
MississippiA
MissouriA
Main Burner Orifice, #55, Green[3] 822708---------------
Main Burner Orifice, 1.25mm, Purple-----[5] 822705[7] 822705[9] 822705
Screw, Self-Tapping Type F, Phillips Pan
Head, 1/4-20 x 1/2", Plated
[4] 80860700
27
Key
No.
Description
203PV204PV205PV206PV
[Quantity] Part Number
5. Pilot Burner and Gas Valve
Pilot Assembly, Natural Gas, Honeywell Q348A1333[1] 8236104
5A
Pilot Assembly, LP Gas, Honeywell Q348A1341[1] 8236107
Pilot Orifice, Natural Gas Honeywell 388146NE
5B
Pilot Orifice, LP/Propane Honeywell 388146KP
5CCompression Nut/Fitting, 1/8" OD x ¼ NPTIncluded with Key No.5A and 5E
5DPilot Tubing, 1/8" OD x 30"[1] 8236110
Gas Valve, ½ x ½, Natural Gas, Honeywell VR8204C6000[1] 81660176
5E
Gas Valve, ½ x ½, LP/Propane, Honeywell VR8204C6018[1] 81660180
(1) For boilers installed in Canada, indicate 'For Canada' when ordering.
(2) For boilers installed in California, indicate 'For California' when ordering.