Burnham Series 2B, 202, 202X, 203, 204 Installation & Service Instructions Manual

...
DNAGNITAREPO,NOITALLATSNI
ROFSNOITCURTSNIECIVRES
2SEIRES
®
)Bledom(
,reliobnonoitamrofnignikeesnehW.rotcartnocgnitaehruoyllac,reliobotsriaperroecivresroF
.lebaLgnitaRnonwohssarebmuNlaireSdnarebmuNledoMrelioBedivorp
rebmuNledoMrelioB
rebmuNlaireSrelioB
etaDnoitallatsnI
2
rotcartnoCgnitaeH
rebmuNenohP
sserddA
81417032R24-10/08
Price - $3.00
NOTE: The equipment shall be installed in accordance with those installation regulations in force in the area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or local regulations. All wiring on boilers installed in Canada shall be made in accordance with the Canadian Electrical Code and/or local regulations.
The New York City Department of Buildings has approved the Series 2B boiler: Approval No. MEA 96-96-E The City of New York requires a Licensed Master Plumber supervise the installation of this product. The Massachusetts Board of Plumbers and Gas Fitters has approved the Series 2B boiler. See the Massachusetts Board of
Plumbers and Gas Fitters website, http://license.reg.state.ma.us/pubLic/pb_pre_form.asp for the latest Approval Code or ask your local Sales Representative.
The Commonwealth of Massachusetts requires this product to be installed by a Licensed Plumber or Gas Fitter.
Table of Contents
I. Installation Instructions ................... 4
II. Operating Instructions .....................18
III. Trouble Shooting..............................25
IV. Service ..............................................26
V. Repair Part .......................................
29
VI. Appendix
Low Water Cut Off ...........................51
The following dened terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or
to important information concerning the life of the product.
DANGER
Indicates presence of a hazard which will cause severe personal injury, death or substantial property damage if ignored.
WARNING
Indicates presence of a hazard which can cause severe personal injury, death or substantial property damage if ignored.
Indicates presence of a hazard which will or can cause minor personal injury or property damage if ignored.
Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.
CAUTION
NOTICE
FAILURE TO FOLLOW ALL INSTRUCTIONS IN PROPER ORDER CAN CAUSE PERSONAL INJURY OR DEATH. READ ALL INSTRUCTIONS BEFORE INSTALLING.
SERVICE ON THIS BOILER SHOULD BE UNDERTAKEN ONLY BY TRAINED AND SKILLED PERSONNEL.
KEEP BOILER AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
DO NOT PLACE ANY OBSTRUCTION IN THE BOILER ROOM THAT WILL HINDER THE FLOW OF COMBUSTION AND VENTILATING AIR.
2
WARNING
WARNING
WARNING
READ THESE INSTRUCTIONS CAREFULLY BEFORE PROCEEDING WITH THE INSTALLATION OF BOILER. POST INSTRUCTIONS NEAR BOILER FOR REFERENCE BY OWNER AND SERVICE TECHNICIAN. MAINTAIN INSTRUCTIONS IN LEGIBLE CONDITION.
Boiler
Model
Number
202 18-3/4 10-3/4 6-3/8 4 45-5/8 8-1/2 10 [3] 1/2 2.5 3" dia. x 15 ft. 212
202X 20 12 6 4 45-5/8 8-1/2 4-3/4 1/2 3.2 4" dia. x 15 ft. 262
203 20 12 6 4 45-5/8 8-1/2 4-3/4 1/2 3.2 4" dia. x 15 ft. 262 204 23-1/4 15-1/4 7-5/8 5 47-1/8 9-1/8 4-3/4 1/2 4 5" dia. x 15 ft. 306 205 26-1/2 18-1/2 9-1/4 6 48-1/2 9-3/4 5-1/4 1/2 4.7 6" dia. x 15 ft. 354 206 29-3/4 21-3/4 10-7/8 6 48-1/2 9-3/4 5-1/4 1/2 5.5 6" dia. x 15 ft. 414 207 33 25 12-1/2 7 50-1/8 10-3/8 6-5/8 3/4 6.2 7" dia. x 15 ft. 458 208 36-1/4 28-1/4 14-1/8 7 50-1/8 10-3/8 6-5/8 3/4 7 7" dia. x 15 ft. 514 209 39-1/2 31-1/2 15-3/4 8 52 11 7-1/4 3/4 7.7 8" dia. x 15 ft. 550 210 42-3/4 34-3/4 17-3/8 8 52 11 7-1/4 3/4 8.5 8" dia. x 15 ft. 608
[1] 15' chimney height is from bottom of draft hood opening to top of chimney.
[2] Refer to the National Fuel Gas Code for equivalent areas of circular and rectangular ue linings.
Maximum Allowable Working Pressure - 30 PSI (Water Only) [3] 202 only. Dimension 'G' includes allowance for 4" x 3" reducer furnished with boiler. See Figure 8.
A B C D E F G
Dimensions [Inches] Gas
Connection
For Automatic
Gas Valve
Water
Content
[gallons]
Recommended
Vent Size
[1] [2]
Approx.
Shipping
Figure 1
Weight
[lb.]
3
I . Installation Instructions
1. INSPECT SHIPMENT carefully for any signs of
damage. All equipment is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of Boiler to the carrier in good condition. Any
claims for damage or shortage in shipment must be led
immediately against the carrier by the consignee. No claims for variances or shortages will be allowed by Boiler Manufacturer unless presented within sixty (60) days after receipt of equipment.
2. BOILER INSTALLATION must conform to the
requirements of the authority having jurisdiction, or in the absence of such requirements, to:
U.S.A. - National Fuel Gas Code, ANSI Z223.1. When required by the authority having juris-
diction, the installation must conform to ANSI/ASME No. CSD-1.
CANADA - "Installation Codes for Natural and LP Gas
Burning Appliances and Equipment, CAN/ CSA-B149.1.
3. These Gas Boilers are DESIGN CERTIFIED FOR
INSTALLATION ON COMBUSTIBLE FLOORING. DO NOT INSTALL THESE BOILERS ON CARPETING.
NOTICE
Do not drop boiler. Do not bump boiler jacket
against oor.
4. LOCATE BOILER in front of or behind installation
position before removing Crate. Locate on a level oor
as close to chimney as possible. For basement installations, provide a solid base such as concrete, if
oor is not level or if water may be encountered on oor around Boiler.
The boiler shall be installed such that the gas ignition
system components are protected from water (dripping, spraying, rain, etc.) during boiler operation and service (circulator replacement, control replacement, etc.).
DANGER
Do not install boiler where gasoline or other
ammable vapors or liquids, or sources of
hydrocarbons (i.e. bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners, etc.) are used or stored.
5. REMOVE CRATE -
A. Remove all crate fasteners. Lift off outside
container.
B. Remove all screws and brackets securing boiler to
skid.
C. Save two of the wooden slats from the container
sleeve for use in Steps D & E.
D. Tilt the boiler to one side and slide a wooden slat
under the two raised feet.
E. Tilt the boiler to the other side and slide another
wooden slat under the two raised feet.
F. Slide the boiler forward or backward off the skid
using the two wooden slats as runners.
6. Move boiler to permanent position.
7. PROVIDE CLEARANCE and AIR for COMBUS-
TION and VENTILATION.
WARNING
Adequate combustion and ventilation air must be
provided to assure proper combustion.
A. CLEARANCES
1. ALL INSTALLATIONS - Practical service clearances must be considered (see Figure 1). A minimum of 24" (6.0cm) from the left side and front jacket panels is recommended for servicing but may be reduced to minimum shown in Figure 2. Subject to boiler and system piping, left side clearance may be reduced to 1" (2.5cm) if right side clearance is increased to 9" (22.9cm).
2. ALCOVE INSTALLATIONS - An alcove is considered a closet as shown in Figure 2 less front. Height clearance may be reduced to 27" (68.6cm).
3. UNCONFINED SPACE (see denition,
paragraph (B) below) - Height clearance may be reduced to 27" (68.6cm).
B. PROVIDE COMBUSTION AND VENTILATION
AIR in accordance with applicable provisions of local building codes, or: U.S.A. - National Fuel
Gas Code, NFPA 54/ANSI Z223.1, Canada - Natural and Propane Gas Installation Code, CAN/
CSA-B149.1.
1. CLOSET INSTALLATIONS (conned space) in
a building of other than unusually tight construction (see denition below), provide
combustion and ventilation air as shown in Figure 2.
2. Installations other than closet in paragraph (1) : a. Determine volume of space (boiler room).
Rooms communicating directly with space (through openings not furnished with doors) are considered part of space.
4
Figure 2: Minimum Clearances
Volume [ft³](m
3
) = Length [ft](m) x Width
[ft](m) x Height [ft](m)
b. Determine Total Input of all appliances in
space. Round result to nearest 1,000 Btu per hour (Btuh).
c. Determine type of space. Divide Volume by
Total Input.
i. If result is greater than or equal to 50 ft³
(1.4m3) per 1,000 Btuh, space is considered an unconned space.
ii. If result is less than 50 ft³ (1.4m3) per
1,000 Btuh, space is considered a conned space.
d. Determine building type. A building of
unusually tight construction has the following characteristics:
i. Walls and ceiling exposed to outside
atmosphere have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and sealed, and
ii. Weather-stripping has been added on
openable windows and doors, and
iii. Caulking or sealants applied in joints
around window and door frames, between
sole plates and oors, between wall-
ceiling joints, between wall panels, at plumbing and electrical penetrations, and at other openings.
e. For boiler located in a building of other than
unusually tight construction, adequate combustion and ventilation air is normally
provided by fresh air inltration through
cracks around windows and doors.
f. For boiler located
in building of unusually
tight construction, provide outdoor air
through two permanent openings which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely communicating with the outdoors. Locate one opening within 12 inches (30.5cm) of top of space. Locate remaining opening within 12 inches (30.5cm) of bottom of space. Minimum dimension of air opening is
3 inches (7.6cm). Size each opening per
following:
i. Direct communication with outdoors.
Minimum free area of 1 square inch (6.5cm2) per 4,000 Btu per hour input of all equipment in space.
ii. Vertical ducts. Minimum free area of 1
square inch (6.5cm2) per 4,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
iii. Horizontal ducts. Minimum free area of 1
square inch (6.5cm2) per 2,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
g. Ventilation Duct Louvers and Grilles. Equip
outside openings with louvers to prevent entrance of rain and snow, and screens to prevent entrance of insects and rodents.
Louvers and grilles must be xed in open
position or interlocked with equipment to open automatically before burner operation. Screens must not be smaller than ¼ inch mesh.
Consider the blocking effect of louvers,
grilles and screens when calculating the
opening size to provide the required free
area. If free area of louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.
8. CONNECT GAS SERVICE from Meter to gas control
assembly in accordance with Local Piping Codes and requirements of Gas Company, see Figure 1. They may
require piping of larger size than Control Assembly
Connection, especially if run from meter is long or
includes several elbows. (See Figure 1 for size of Gas
Connection to gas control assembly).
5
Table 1: Maximum Capacity of Schedule 40 Pipe in CFH For Natural Gas Pressures of ½ psig or Less
Length
[Feet]
10 132 278 520 1,050 175 360 680 1,400 20 92 190 350 730 120 250 465 950 30 73 152 285 590 97 200 375 770 40 63 130 245 500 82 170 320 660 50 56 115 215 440 73 151 285 580 60 50 105 195 400 66 138 260 530 70 46 96 180 370 61 125 240 490 80 43 90 170 350 57 118 220 460 90 40 84 160 320 53 110 205 430
100 38 79 150 305 50 103 195 400
Table 2: Equivalent Length of Fittings
0.3 Inch w.c. Pressure Drop 0.5 Inch w.c. Pressure Drop
½ ¾ 1 ½ ¾ 1
Table 3: Specic Gravity Correction Factors for
Natural Gas
Nominal Pipe Size
Fitting
½ ¾ 1
45° Ell 0.7 1 1.2 1.6 90° Ell 1.6 2.1 2.6 3.5
Tee (As Elbow) 3.1 4.1 5.2 6.9
This piping is to be supplied by the installer and must
include a trap, a ground joint union and a manual
Specic
Gravity
0.50 1.10 1.30 1.07
0.55 1.04 1.40 1.04
0.60 1.00 1.50 1.00
0.65 0.96 1.60 0.97
0.70 0.93 1.70 0.94
0.75 0.90 --- ---
0.80 0.87 --- ---
Correction
Factor
Specic
Gravity
shutoff valve upstream of the gas control assembly outside of the jacket when codes require, see Figure 1. A pipe thread compound resistant to the action of
liqueed petroleum gases should be applied to all
threaded joints in the gas piping. Pressure testing of the Gas Supply Piping Boiler and its connections is required before placing the boiler in operation.
The boiler and shutoff valve must be disconnected from
the gas supply piping system during any pressure testing at pressures greater than ½ psig (3.5kPa).
A. Allowable loss of pressure to assure a burner
manifold pressure of 3½" (8.9cm) water for natural gas.
B. Supply of gas to be provided in cubic feet.
C. Length of piping and number of ttings. D. Specic gravity of gas. E. Correction factor for specic gravity.
9. BOILER PIPING
The boiler must be isolated from the gas supply piping
system by closing its individual manual shutoff valve
CAUTION
during any pressure testing of the gas supply piping system at pressures equal to or less than ½ psig (3.5kPa).
RECOMMENDED SIZING OF GAS SUPPLY
PIPING TO BOILER FOR NATURAL GAS - shall be such as to provide the required supply of gas without undue loss of pressure between meter and the boiler.
Gas supply piping should be sized in accordance with
the Tables 1, 2 and 3. The following shall be taken into account:
Failure to properly pipe boiler may result in improper operation and damage to boiler or building.
A. CLEARANCES - Hot water pipes do not require
clearance from combustible construction.
B. Install drain valve and safety relief valve as shown
in Figures 1 and 3. Note - Safety relief valve must be in vertical position.
C. Pipe safety relief valve discharge to oor.
Correction
Factor
6
Figure 3: Recommended Water Piping for
Zone Valve Zoned Heating Systems
WARNING
Safety relief valve discharge piping must be
piped near oor to eliminate potential of severe
burns. Do not pipe in any area where freezing could occur. Do not install any shut-off valves.
D. Install circulator with anges, gaskets and bolts
provided. Five foot long circulator harness allows circulator to be mounted on supply or return. Connect harness to circulator and secure any excess conduit.
E. For heating only system piping, see Figure 3.
Consult also I=B=R Installation Guides.
F. For space heating and domestic water heating with
Alliance SL™ water heater (intermittent circulation only); install Alliance SL™ water heater as a
separate heating zone. Refer to Alliance SL™
Installation, Operating and Service Instructions for additional information.
G. If this boiler is used in connection with refrigeration
systems, the boiler must be installed so that the chilled medium is piped in parallel with the heating boiler using appropriate valves to prevent the chilled medium from entering the boiler, see Figure 4. Also consult I=B=R Installation and Piping Guides.
If this Boiler is connected to heating coils located in
air handling units where they may be exposed to refrigerated air, the boiler piping must be equipped
Figure 4: Recommended Piping
for Combination Heating & Cooling
(Refrigeration) Systems
with ow control valves to prevent gravity
circulation of boiler water during the operation of the cooling system.
H. Use a boiler bypass if the boiler is to be
operated in a system which has a large volume or excessive radiation where low boiler water temperatures may be encountered (i.e. converted gravity circulation system, etc.).
Install a pipe tee at the boiler return along
with a second tee in the supply piping as shown in
Figure 3. The bypass should be the same size as the
supply and return lines with valves located in the bypass and supply outlet as illustrated in Figure 3 in
order to regulate water ow to maintain higher
boiler water temperatures.
Set the by-pass and boiler supply valves to a half
throttle position to start. Operate boiler until the system water temperature is at a normal operating range.
Adjust the valves to provide 180° to 200°F supply
water temperature. Opening the boiler supply valve will raise the system temperature, while opening the by-pass valve will lower the system supply temperature.
I. A hot water boiler installed above radiation level
must be provided with a low water cutoff device as part of the installation.
If a low water cut-off is required, it must be
mounted in the system piping above the boiler.
The minimum safe water level of a hot water boiler
is just above the highest water containing cavity of the boiler; that is, a hot water boiler must be full of water to operate safely.
Refer to Section VI for low water cut-off piping and
wiring instructions.
J. If it is required to perform a long term pressure test
of the hydronic system, the boiler should rst be
isolated to avoid a pressure loss due to the escape of air trapped in the boiler.
7
To perform a long term pressure test including the
boiler, ALL trapped air must rst be removed from
the boiler.
A loss of pressure during such a test, with no visible
water leakage, is an indication that the boiler
contained trapped air. K. OXYGEN CORROSION: Oxygen contamination of the boiler water will cause
corrosion of the iron and steel boiler components,
which can lead to failure. As such, any system must
be designed to prevent oxygen absorption in the rst
place or prevent it from reaching the boiler.
Problems caused by oxygen contamination of boiler
water are not covered by Burnham's standard
warranty. There are many possible causes of oxygen
contamination such as:
1. Addition of excessive make-up water as a result of system leaks.
2. Absorption through open tanks and ttings.
3. Oxygen permeable materials in the distribution system.
In order to insure long product life, oxygen
sources should be eliminated. This can be accomplished by taking the following measures:
1. Repairing system leaks to eliminate the need for addition of make-up water.
2. Eliminating open tanks from the system.
3. Eliminating and/or repairing ttings which allow
oxygen absorption.
4. Use of non-permeable materials in the distribution system.
5. Isolating the boiler from the system water by installing a heat exchanger.
10. INSTALL DRAFT HOOD without modication on
outlet of ue collector (See Figure 1). Secure with sheet
metal screws.
WARNING
Do not alter boiler draft hood or place any obstruction or non-approved damper in the breeching or vent system. Flue gas spillage can
occur. ETL certication will become void.
11. INSTALL BLOCKED VENT SWITCH
The blocked vent switch assembly shipped taped to the
top of the boiler includes a power cord and a switch attached to a mounting bracket. The mounting bracket has a three tooth staggered comb stamping at one end with a #10 sheet metal screw in the center tooth.
A. Untape the blocked vent switch assembly from the
top of the boiler and uncoil the power cord.
Figure 6
B. Pinch the black strain relief bushing installed in the
jacket right side panel to dislodge it from the jacket and pull just enough of the black power cord out so the blocked vent switch will reach the near side of the draft hood skirt. Do not pull out more power cord than necessary.
C. Position the mounting bracket (with switch attached)
onto the lower edge of the draft hood skirt by locating the center tooth (with the #10 sheet metal screw) on the outside and the other two teeth inside the draft hood skirt. See Figure 6.
D. Slide the mounting bracket up tight against the
lower edge of the draft hood skirt, so that the #10 sheet metal screw is above the skirt's stiffening rib.
E. Secure the bracket in this position by tightening the
#10 sheet metal screw against the outer surface of the draft hood skirt.
F. Reinsert the excess power cord through the jacket
side panel hole to take the slack out of the power cord running up to the blocked vent switch.
G. Reposition the strain relief bushing around the
power cord at the jacket side panel, pinch the two halves of the bushing together, and snap it back into the hole in the jacket side panel to secure the power cord to the jacket.
H. Be sure the power cord, mounting bracket, and
switch are secure and located as shown in Figure 6.
8
Figure 7: Plug-in Damper Installation
WARNING
Failure to properly install and use this Blocked Vent Switch may result in property damage, personal injury or loss of life.
12. TO MEET FEDERALLY MANDATED
EFFICIENCIES, THIS BOILER MUST BE EQUIPPED WITH A VENT DAMPER.
OPEN THE VENT DAMPER CARTON and remove
the Installation Instructions. READ THE INSTALLA­TION INSTRUCTIONS THOROUGHLY proceeding.
The automatic gas control valve supplied on each Series
2™ boiler provides the redundancy referenced in the vent damper Installation Instructions.
before
CAUTION
Do not use one vent damper to control two heating appliances.
A. The vent damper should be the same size as the
outlet of the Draft Hood. (See Figure 1) Unpack the damper carefully - DO NOT FORCE IT CLOSED! Forcing the damper may damage the gear train and void the warranty. The damper assembly includes a prewired connection harness for use on all 24V Standing Pilot or electronic ignition control systems.
B. Mount the vent damper assembly after the draft
hood, as close to the draft hood as practicable
without modication to the draft hood or vent
damper. (Refer to Figure 7 and to instructions
packed with the vent damper for specic
instructions). This is a must for the wiring harness to
t and the damper position indicator to be visible to
the users.
NOTICE
Provide adequate clearance for servicing.
WARNING
Provide 6" (15.2cm) minimum clearance between damper and combustible construction.
C. Install the 90° BX connector attached to the exible
conduit in the 7/8" knockout on the left side of the jacket. Plug the factory wired Vent Damper Harness
into the polarized receptacle. Install a cable clamp around the exible conduit and attach to the Jacket
top panel. (See Figure 7).
NOTICE
Please refer to the specications, installation
instructions and troubleshooting guide packed in the vent damper carton for complete detailed installation instructions. Also refer to Figure 7 in this manual.
D Continuous Ignition (Standing Pilot) Only. Remove
knockout from vent damper blade.
E. Size 202 Only. Install 4" x 3" reducing tting on
vent damper outlet.
13. INSTALL VENT CONNECTOR from reducing
tting (202 Only), draft hood or damper to chimney, see
Figure 8.
9
Figure 8: Typical Vent Installation
DANGER
Inspect existing chimney before installing boiler. Failure to clean or replace perforated pipe or tile lining will cause severe injury or death.
A. Vent installation shall be in accordance with local
building codes; or the local authority having jurisdiction; or the National Fuel Gas Code, ANSI Z223.1/NFPA 54; or the Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances, ANSI/NFPA 211. Both of the aforementioned standards, ANSI Z223.1 and ANSI/ NFPA 211, specify Type B and Type L double wall
metal vents and re clay tile lined masonry
chimneys as suitable chimney constructions for Category I, draft hood equipped appliances, such as this Series 2™ boiler. Both standards prohibit the use of unlined masonry construction as a chimney, with the exception in ANSI Z223.1/NFPA 54 that "Where permitted by the authority having jurisdiction, existing chimneys shall be permitted to have their use continued when an appliance is replaced by an appliance of similar type, input
rating, and efciency." ANSI/NFPA 211 prohibits
the use of single wall metal vent as a chimney, while ANSI Z223.1 allows it under very restrictive conditions. In Canada refer to the Natural Gas and LP Installation Code, CAN/CSA-B149.1.
B. Do not connect into same leg of chimney serving an
open replace.
C. Inspect chimney for obstructions or restrictions and
remove. Clean chimney if necessary.
D. Vent pipe to chimney must not be smaller than outlet
on draft hood or damper. Although single wall vent pipe may be used, Type B is recommended. The venting system must be arranged so that only the
boiler is served by the damper device. Installation per paragraph 12 complies with this provision.
E. Where two or more appliances vent into a common
vent, the area of the common vent should at least equal the area of the largest vent plus 50% of the area in the additional vents. Do not connect the vent of this appliance into any portion of mechanical draft system operating under positive pressure.
F. Vent pipe should have the greatest possible initial
rise above the draft hood consistent with the head room available and the required clearance from adjacent combustible building structure. Vent Pipe should be installed above the bottom of chimney to prevent blockage.
G. Vent pipe should slope upward from draft hood to
chimney not less than one inch in four feet. Doivent
présenter des tronçons horizontaux dont la pente
montante est d’au moins ¼ po par pied (21 mm/m) entre la chaudière et l’évent. No portion of vent pipe should run downward or have dips or sags. Vent pipe must be securely supported. Les sections
horizontales doivent être supportées pour prévenir le échissement.
H. Vent pipe must be inserted into but not beyond
inside wall of chimney liner. Seal tight between vent pipe and chimney.
I. Do not install non-listed (AGA, CGA, CSA, ETL or
UL) vent damper or other obstruction in vent pipe.
WARNING
14. IF AN EXISTING BOILER IS REMOVED -
When an existing boiler is removed from a common
venting system, the common venting system is likely to be too large for proper venting of the appliances remaining to it.
At the time of removal of an existing boiler, the
following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation:
A. Seal any unused openings in the common venting
system.
B. Visually inspect the venting system for proper size
and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion, and other
deciencies which could cause an unsafe condition.
C. Insofar as is practical, close all building doors and
windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range-hoods and bathroom exhausts, so they will operate at maximum
10
speed. Do not operate a summer exhaust fan. Close
replace dampers.
D. Place in operation the appliance being inspected.
Follow the Lighting (or Operating) Instructions. Adjust thermostat so appliance will operate continuously.
E. Test for spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use the
ame of a match or candle, or smoke from a
cigarette, cigar or pipe.
F. After it has been determined that each appliance
remaining connected to the common venting system properly vents when tested as outlined above, return
doors, windows, exhaust fans, replace dampers and
any other gas burning appliance to their previous conditions of use.
G. Any improper operation of the common venting
system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1 and/or CAN/CSA B149.1, Installation
Codes. When resizing any portion of the common
venting system, the common venting system should
be resized to approach the minimum size as
determined using the National Fuel Gas Code, ANSI Z223.1 and/or CAN/CSA B149.1, Installation
Codes.
Au moment du retrait d’une chaudière existante, les
mesures suivantes doivent être prises pour chaque
appareil toujours raccordé au système d’evacuation commun et qui fonctionne alors que d’autres appareils toujours raccordés au système d’évacuation ne fonctionnent pas:
A. Sceller toutes les ouvertures non utilisées du
système d’évacuation.
B. Inspecter de facon visuelle le système d’évcuation
pour déterminer la grosseur et l’inclinaison
horizontale qui conviennent et s’assurer que le
système est exempt d’obstruction, d’étranglement, de fuite, de corrosion et autres défaillances qui pourraient présenter des risques.
C. Dans la mesure du possible, fermer toutes les portes
et les fenêtres du bâtiment et toutes les portes entre
l’espace où les appareils toujours raccordés au système d’évacuation sont installés et les autres
espaces du bâtiment. Mettre en marche les
sécheuses, tous les appareils non raccordés au système d’évacuation commun et tous les ventilateurs d’extraction comme les hottes de cuisinière et les ventilateurs des salles de bain. S’assurer que ces ventilateurs fonctionnent à la vitesse maximale. Ne pas faire fonctionner les ventilateurs d’été. Fermer les registres des cheminées.
D. Mettre l’appareil inspecté en marche. Suivre les
instructions d’allumage. Régler le thermostat de facon que l’appareil fonctionne de facon continue.
E. Faire fonctionner le brùleur principal pendant 5 min
ensuite, déterminer si le coupe-tirage déborde à
l’ouverture de décharge. Utiliser la amme d’une
allumette ou d’une chandelle ou la fumée d’une cigarette, d’un cigare ou d’une pipe.
F. Une fois qu’il a été déterminé, selon la méthode
indiquée ci-dessus, que chaque appareil raccordé au système d’évacuation est mis à l’air libre de facon
adéquate. Remettre les portes et les fenêtres, les
ventilateurs, les registres de cheminées et les
appareils au gaz à leur position originale.
G. Tout mauvais fonctionnement du système
d’évacuation commun devrat être corrigé de facon
que l’installation soit conforme au National Fuel Gas Code, ANSI Z223.1 et (ou) aux codes d’installation CAN/CSA-B149.1. Si la grosseur
d’une section du système d’évacuation doit être modiée, le système devrait être modié pour
respecter les valeurs minimales des tableaux pertinents de l’appendice F du National Fuel Gas
Code, ANSI Z223.1 et (ou) des codes d’installation CAN/CSA-B149.1.
15. INSTALL A ROOM THERMOSTAT on an inside
wall about four feet above oor. Never install
thermostat on an outside wall or where it will be
inuenced by drafts, hot or cold water pipes, lighting xtures, television, rays of the sun or near a replace.
Keep large furniture away from thermostat so there will be free movement of room air around this control.
Table 4: Wiring Diagrams and Heat Anticipator Settings
Ignition Type Circulation Method
Continuous
(Standing Pilot)
Electronic
If system tends to overheat above thermostat's temperature setting, reduce heat anticipator setting by
0.1 or 0.2 amps. If system tends to shortcycle without reaching desired room temperature, increase heat anticipator setting by 0.1 or 0.2 amps.
Intermittent 0.6 11
Constant/Gravity 1.0 14
Intermittent 0.6 12
Constant/Gravity 1.0 15
Thermostat Heat Anticipator
Setting [Amps]
Wiring
Diagram Figure
11
Heat Anticipator in Thermostat should be set to match
the requirements of the control to which it is connected. See Table 4. If system tends to overheat above the thermostat's temperature setting, reduce heat anticipator setting by .1 or .2 amps. If system tends to short cycle without reaching desired room temperature, increase heat anticipator setting by .1 or .2 amps.
16. INSTALL ELECTRIC WIRING in accordance with
National Electric Code or the Canadian Electrical Code and local regulations. See Figures 11 through 16 for applicable wiring diagram. A separate electrical circuit must be run from the main electrical service with an over-current device/disconnect in the circuit. A service switch is recommended and may be required by some local jurisdictions. When installed, the boiler must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, and/or the CSA C22.1 Electrical Code, if an external electrical source is
utilized.
For zone valve wiring, a separate 24V transformer is
required rather than attempting to use the boiler
mounted control. Consult zone valve manufacturer for
assistance.
17. VENT DAMPER SEQUENCE OF OPERATION.
See Figure 9. A. The Vent Damper is continuously powered at
Terminal 1.
B. When there is a call for heat, the damper relay coil is
energized through Terminal 5 if all limits ahead of the damper are satised.
C. The relay coil closes contacts which energize the
damper motor, causing the damper to open.
D. When the damper blade reaches the fully open
position, power is sent back to the ignition circuit through Terminal 2 and the damper motor is de-
energized.
E. When the call for heat is satised, the damper relay
coil is de-energized - closing contacts which energize the damper motor. This causes the damper
to close. When the damper blade reaches the fully
closed position, the damper motor is de-energized.
POWER FAILURE - The damper blade will stop in
the position it was in when power failed. (Combustion can never take place unless the damper blade is in the fully open position.)
Figure 9: Vent Damper Schematic Wiring Diagram
This boiler contains controls which may cause the boiler to shut down and not restart without service. If damage due to frozen pipes is a possibility, the heating system should not be left unattended in cold weath­er; or appropriate safeguards and alarms should be installed on the heating system to prevent damage if the boiler is inoperative.
Avoid operating this boiler in an environment where saw dust, loose insulation bers, dry wall dust, etc.
are present. If boiler is operated under these conditions, the burner interior and ports must be cleaned and inspected daily to insure proper operation.
12
CAUTION
CAUTION
Figure 11: Wiring Diagram, 24 Volt Standing Pilot and Intermittent Circulation
SEQUENCE OF OPERATION Normal Operation
1. When the thermostat call for heat, the vent damper will open (see paragraphs 17A through 17D). The circulator is started through a relay and at the same
time the gas valve is energized allowing main gas ow and ignition of main burners.
2. Where condensation of ue gas is encountered in boiler ues a reverse acting circulator control should
be installed to stop the circulator before the boiler
water temperature drops to that which ue gas
condensation may occur.
3. After the thermostat is satised the main valve will close and main burner ames will be extinguished.
The vent damper will close (see paragraph 17E).
SAFETY SHUTDOWN
1. High Limit Switch
In the event excessive boiler water temperature is
developed the high limit switch will open interrupting power to the gas valve. The main burners will be extinguished immediately, and the vent damper will close at the same time, but the circulator will continue to operated. Normal operation will be resumed when the boiler water temperature drops to a point where the high limit switch closes.
2. Blocked Vent Switch In the event excessive blockage in the vent system is
developed the blocked vent switch will open interrupting power to the gas valve. The main burners will be extinguished immediately, the circulator will continue to operate, and the vent damper will remain open until the thermostat is turned off. The source of blockage must be corrected by trained and skilled personnel from a
qualied service agency before resetting switch.
3. Flame Rollout Switch In the event excessive blockage in the boiler section
ue passageways is developed the ame rollout
switch will open interrupting power to the gas valve. The main burners will be extinguished immediately, the circulator will continue to operate and the vent damper will remain open until the thermostat is
turned off. If the ame rollout switch is activated do
not attempt to place the boiler in operation. The
source of blockage must be corrected and the ame
rollout switch replaced by trained and skilled
personnel from a qualied service agency.
4. Pilot
The thermocouple proves pilot ame and in the
absence of such within 45-90 seconds causes the combination gas valve, which is equipped with a
100% shut-off provision, to be de-energized, thus, preventing main gas or pilot gas ow.
13
Figure 12: Wiring Diagram, Electronic Ignition (EI), Intermittent Circulation
SEQUENCE OF OPERATION NORMAL OPERATION
1. When the thermostat calls for heat, the relay is
energized. The circulator starts and the vent damper
opens (see Paragraphs 17A through 17D). When the damper blade reaches the fully open position, the
ignition module is energized opening the pilot valve and energizing the igniter to ignite the pilot burner.
2. Sensor proves presence of pilot ame. Main valve
opens to ignite main burners.
3. The burners and circulator will operate
simultaneously until the thermostat is satised.
4. After thermostat is satised, ignition module is de­energized, extinguishing pilot and main ame. Vent
damper closes (see paragraph 17E).
SAFETY SHUTDOWN
1. Limit: Automatically interrupts main burner operation when water temperature exceeds set point. Maximum allowable temperature is 250°F. Normal operation resumes when water temperature falls below set point.
2. Blocked Vent Switch: Automatically interrupts
main burner operation when excessive vent system blockage occurs. Control is a multiple use device. If blocked vent switch is activated do not attempt to place boiler in operation. Correct source of blockage and reset blocked vent switch.
3. Flame Roll-out Switch: Automatically interrupts
boiler operation when ames or excessive heat are
present in vestibule. Control is single use device. If
ame roll-out switch is activated do not attempt to
place boiler in operation. Correct source of blockage
and replace ame roll-out switch.
4. Igniter/Sensor: senses pilot ame and causes
ignition module to turn off main burner and pilot
burner gas ow should pilot burner ame
extinguish. Five to six minutes after shutdown, ignition module restarts ignition sequence.
5. For Electronic Ignition Trouble Shooting Guide, see Page 25 of this manual.
14
Figure 13: Wiring Diagram, 24 Volt Standing Pilot with Continuous or Gravity Circulation
SEQUENCE OF OPERATION NORMAL OPERATION
1. When the thermostat call for heat, the vent damper will open (see paragraphs 17A through 17D). The
gas valve is energized allowing main gas to ow and
operation of the main burners.
2. Where condensation of ue gas is encountered in boiler ues a reverse acting circulator control should
be installed to stop the circulator before the boiler
water temperature drops to that which ue gas
condensation may occur.
3. After the thermostat is satised the main valve will close and main burner ames will be extinguished.
The vent damper will close (see paragraph 17E). If the boiler is so equipped, circulator will continue to run.
SAFETY SHUTDOWN
1. High Limit Switch: In the event excessive boiler water temperature is developed the high limit switch will open interrupting power to the gas valve. The main burners will be extinguished immediately. Normal operation will be resumed when the boiler water temperature drops to a point where the high limit switch closes.
2. Blocked Vent Switch: In the event excessive blockage in the vent system is developed the blocked vent switch will open interrupting power to the gas valve. The main burners will be extinguished immediately and the vent damper will remain open until the thermostat is turned off. The source of blockage must be corrected by trained and skilled
personnel from a qualied service agency before
resetting switch.
3. Flame Rollout Switch: In the event excessive
blockage in the boiler section ue passageways is developed the ame rollout switch will open
interrupting power to the gas valve. The main burners will be extinguished immediately and the vent damper will remain open until the thermostat is
turned off. If the ame rollout switch is activated do
not attempt to place the boiler in operation. The source of the blockage must be corrected and the
ame rollout switch replaced by trained and skilled personnel from a qualied service agency.
4. Pilot: The thermocouple proves pilot ame and in
the absence of such within 45-90 seconds causes the combination gas valve, which is equipped with a
100% shut-off provision, to be de-energized, thus, preventing main gas or pilot gas ow.
15
Figure 14: Wiring Diagram, Electronic Ignition (EI), Continuous or Gravity Circulation
SEQUENCE OF OPERATION NORMAL OPERATION
1. When the thermostat calls for heat the vent damper opens (see Paragraphs 17A through 17D). When the damper blade reaches the fully open position, the
ignition module is energized opening the pilot valve and energizing the igniter to ignite the pilot burner.
2. Sensor proves presence of pilot ame. Main valve
opens to ignite main burners.
3. The burners will operate until the thermostat is
satised.
4. When thermostat is satised, ignition module is de­energized, extinguishing pilot and main ame. If
boiler is equipped with circulator, circulator will continue to run. Vent damper closes (see Para-graph 17E).
SAFETY SHUTDOWN
1. Limit: Automatically interrupts main burner operation when water temperature exceeds set point. Maximum allowable temperature is 250°F. Normal operation resumes when water temperature falls below set point.
2. Blocked Vent Switch: Automatically interrupts
main burner operation when excessive vent system blockage occurs. Control is a multiple use device. If blocked vent switch is activated do not attempt to place boiler in operation. Correct source of blockage and reset blocked vent switch.
3. Flame Roll-out Switch: Automatically interrupts
boiler operation when ames or excessive heat are
present in vestibule. Control is single use device. If
ame roll-out switch is activated do not attempt to
place boiler in operation. Correct source of blockage
and replace ame roll-out switch.
4. Igniter/Sensor: senses pilot ame and causes
ignition module to turn off main burner and pilot
burner gas ow should pilot burner ame
extinguish. Five to six minutes after shutdown, ignition module restarts ignition sequence.
5. For Electronic Ignition Trouble Shooting Guide, see Page 25 of this manual.
16
Loading...
+ 36 hidden pages