Buderus SU54/5, SU80/5, SU100/5 Installation And Maintenance Instructions Manual

Storage water heater
6 720 805 397-00.1ITL
Acumulador de agua caliente Préparateur ECS
WARNING:
These installation instructions are intended solely for use by a licensed heating contractor or service techni­cian. Read all instructions before installing. Perform steps exactly in the order given. Failure to follow these instructions can result in severe injury, death or proper­ty damage.
PELIGRO:
Este manual de instalación únicamente lo pueden utili­zar instaladores de calefacción o técnicos especializa­dos. Antes de la instalación, lea todas las indicaciones. Realice todas las acciones exactamente en el orden indi­cado. En caso de incumplimiento, existe riesgo de lesio­nes graves e incluso de muerte o daños materiales considerables.
SU54/5, SU80/5, SU100/5
[en] Installation and maintenance instructions 2 [es] Instrucciones de instalación y de mantenimiento 20 [fr] Notice d'installation et d'entretien 35
AVERTISSEMENT :
Cette notice d’installation doit être utilisée uniquement par des installateurs chauffagistes ou des technici ens de maintenance qualifiés. Lisez attentivement toutes les consignes avant l’installation. Exécutez les actions préci­sément dans l’ordre indiqué. En cas de non-respect, vous risquez de subir de sérieuses blessures pouvant conduire à la mort ou d’entraîner de lourds dommages matériels.
6 720 808 532 (2013/08) (US/CA/MX)
Table of Contents
Table of Contents
1 Safety Considerations and Symbol Descriptions . . . . . . . . . . 2
1.1 Key to symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2 Safety considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Instructions for the owner and operator . . . . . . . . . . . . . 4
2 Product information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Product information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Data plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.5 Pressure drop curve of heating coil . . . . . . . . . . . . . . . . . 5
2.6 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.7 Physical and connection dimensions . . . . . . . . . . . . . . . 7
3 Standards, regulations and directives . . . . . . . . . . . . . . . . . . . 8
4 Moving the tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.1 Boiler installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.1.1 Requirements for installation location . . . . . . . . . . . . . . 8
5.1.2 Wall clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.1.3 Positioning the tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.2 Water connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.2.1 Connecting the tank on the water side . . . . . . . . . . . . . 10
5.2.2 Installing a T&P safety valve (on-site) . . . . . . . . . . . . . . 11
5.3 Install a tank water temperature sensor (accessory)
or aquastat (accessory). . . . . . . . . . . . . . . . . . . . . . . . . 11
9.3.3 Checking the magnesium anode at the side
(SU80/5, SU100/5) . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
9.4 Re-commissioning after performing maintenance . . . . 16
10 Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
1 Safety Considerations and Symbol
Descriptions
1.1 Key to symbols
Warnings
Warnings in this document are identified by a warning triangle printed against a grey background. Keywords at the start of a warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken.
The following keywords are defined and can be used in this document:
DANGER indicates a hazardous situation which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION indicates a hazardous situation which, if not avoided, could
result in minor to moderate injury.
NOTICE is used to address practices not related to personal injury.
Important information
This symbol indicates important information where there is no risk to people or property.
6 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.1 Commissioning the DHW tank . . . . . . . . . . . . . . . . . . . . 13
7 Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7.1 Shutting down the DHW tank . . . . . . . . . . . . . . . . . . . . . 13
7.2 Shutting down the heating system
when there is a risk of frost . . . . . . . . . . . . . . . . . . . . . . 13
8 Environmental Protection / Disposal . . . . . . . . . . . . . . . . . . . 13
9 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
9.1 Preparing the DHW tank for cleaning . . . . . . . . . . . . . . 13
9.2 Descaling/cleaning the DHW tank . . . . . . . . . . . . . . . . . 14
9.3 Checking the magnesium anode . . . . . . . . . . . . . . . . . . 15
9.3.1 Checking the upper magnesium anode
(SU80/5, SU100/5) . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
9.3.2 Checking the upper magnesium anode (SU54/5) . . . . 15
Additional symbols
Symbol Explanation
Step in an action sequence Cross-reference to another part of the document
List entry – List entry (second level)
Table 1
SU54/5, SU80/5, SU100/5 – 6 720 808 532 (2013/08)2
Safety Considerations and Symbol Descriptions
1
1.2 Safety considerations
Read all instructions before installing. Perform the steps in the indicated sequence. Have the DHW tank inspected by a trained service technician at least once every year. Failure to comply with these instructions can result in severe, possibly fatal, personal injury as well as damage to property and equipment.
Installation and maintenance
Risk of fire from soldering and brazing!
Take appropriate protective measures when soldering and brazing as the insulation is flammable, for example, cover the insulation.
▶ Ensure that only a licensed contractor installs or services the DHW
tank.
▶ Use installation material with adequate temperature stability.
Forbidden:
Connection of the potentiostat for an impressed current anode to the magnesium anode installed in a storage tank is absolutely forbidden! This would destroy the tank! The warranty would be voided.
Installation and commissioning
▶ In the Commonwealth of Massachusetts, the DHW tank must be
installed by a licensed plumber.
▶ The electrical power must be connected by a licensed electrician.
The wiring diagram must be followed.
▶ Do not install this device in rooms with a high moisture level
(e.g. bathrooms, saunas).
Function
▶ To ensure that the tank functions properly, heed these installation and
maintenance instructions.
▶ Never close the blow-off line of the T&P safety valve. For safety
reasons, water may escape during heating.
Danger from electric shock
▶ Ensure that only an authorized contractor performs electrical work. ▶ Before performing electrical work, disconnect the power and secure
the unit against unintentional reconnection.
▶ Ensure the system has been disconnected from the power supply.
Risk of scalding at the hot water draw-off point
▶ When the DHW tank is in operation, temperatures in excess of 122 °F
(50 °C) can occur. To limit the temperature at the tap, install a thermostatic DHW mixing valve.
▶ Water heated for washing the laundry, dishes and for other cleaning
purposes can cause scalding and permanent injuries.
▶ Children, elderly, and handicapped persons are more likely to be
permanently injured by hot water. Never leave such individuals in the tub or shower unattended under any circumstances. Children must not be allowed to operate hot water faucets themselves or to fill a bathtub.
▶ If the building has occupants in the above groups who operate hot
water faucets, or state laws / local ordinances stipulate specific water temperatures, take the following precautions: – Use the lowest possible temperature setting. – To prevent scalding, install a tempering device, such as an
automatic mixing valve, at hot water tap or water heater. Select and install the automatic mixing valve in accordance with the valve manufacturer's recommendations and instructions.
▶ Water exiting from drain valves can be extremely hot. To avoid
injuries: – Check that all connections are tight. – Direct exiting water away from people.
▶ Measures must be taken to protect against excessive temperature and
pressure! Installation of a T&P safety valve is required.
The chart below shows the relationship between water temperature and time until there is a risk of scalding. It can be used as the basis for determining the safest water temperature for your application.
Temperature Time to severe scalding
120 °F (48 °C) longer than 5 minutes 125 °F (51 °C) 1.5 to 2 minutes 130 °F (54 °C) approx. 30 seconds 135 °F (57 °C) approx. 10 seconds 140 °F (60 °C) less than 5 seconds 145 °F (62 °C) less than 3 seconds 150 °F (65 °C) approx. 1.5 seconds 155 °F (68 °C) approx. 1 second
Table 2 Approximate time-temperature relationship until there is a risk
of scalding
1) Source : Moritz, A.R. and Henriques, F.C., Jr. (1947). Stud ies of thermal injury. II. The relative importance of time and surface temperature in the causation of cutaneous burns, Am J of Pathol, 23, 695-720.
1)
To protect against corrosion and ensure compliance with the rules for electrical safety, observe the following points: ▶ Use metal fittings for drinking water heating systems with plastic
piping.
▶ Use only original accessories from the manufacturer. ▶ When installation of the tank is complete, inspect the ground
conductor (including metal fittings).
Maintenance Customers are advised to:
▶ Sign a maintenance and inspection contract with an authorized
contractor. Inspect and maintain the DHW tank as necessary on a yearly basis. Service as needed.
▶ Use only original spare parts.
Flooding
▶ After a flood, do not use the appliance if any part has been
submerged. Damage to appliances that have been submerged can be quite severe and pose numerous safety risks.
▶ An appliance that was subject to flooding must be replaced.
SU54/5, SU80/5, SU100/5 – 6 720 808 532 (2013/08) 3
2
6 720 805 397-01.1ITL
1
2
4
3
5
7
6
Product information
1.3 Instructions for the owner and operator
WARNING: Risk of scalding at the taps!
There is a risk of scalding at the taps if the tank temperature is set above 122 °F (50 °C) and during thermal disinfection.
▶ Advise users that they should draw off only mixed
water. Otherwise, install a thermostatic DHW mixing valve.
NOTICE: Risk of tank damage from excessively high pressure.
▶ Never plug the discharge line of the T&P safety valve.
▶ Explain the operation and handling of the heating system and DHW
tank, making a particular point of safety-relevant features. ▶ Explain the function and how to check the T&P safety valve. ▶ Hand all enclosed documents over to the owner/operator. ▶ Recommendation for the user: Sign a maintenance and inspection
contract with a licensed contractor. ▶ Highlight the following for the user:
– Water may be discharged from the T&P safety valve during heat-up.
– T he blow-off line on the T&P safety valve must always be kept open.
– Check that the T&P safety valve operates properly at least once
yearly.
– The tank must be inspected annually and maintained as required.
2 Product information
2.1 Scope of delivery
•Tanks
• Installation and Service Instructions
•B-KIT
Fig. 1 B-kit
[1] Tee 1" x 1" x ¾ " (2x) [2] Temperature and pressure relief valve [3] Blanking cap ¾ " [4] Drain valve [5] Bracket for aquastat, screws for aquastat bracket (4x) [6] Compensating spring for aquastat or tank temperature sensor [7] Quarter-circle spacer for aquastat or tank temperature sensor
(2x)
2.2 Intended use
The tank is designed for heating and storing drinking water. Please observe national, regional, and local codes, regulations, guidelines and standards for potable water.
Install this tank only in sealed unvented hydronic heating systems. Any other purpose is considered improper use. Any resulting damage is
excluded from the manufacturer's warranty.
Requirements for drinking water Unit
Water hardness, min. ppm
grain/US gallon
°dH pH value, min. – max. 6.5 – 9.5 Conductivity, min. – max. μS/cm 130 – 1500
Table 3 Requirements for drinking water
36
2.1 2
SU54/5, SU80/5, SU100/5 – 6 720 808 532 (2013/08)4
2.3 Product information
12
14
13
11
7
1
5
3
6
2
4
1
5
3
6
2
4
7
8
14
9
10 10
11
12
SU 54/5 SU80/5, SU100/5
6 720 805 397-02.1ITL
Product information
2
Fig. 2 Product information
Item Description 1 DHW outlet 2 Recirculation connection 3 Boiler flow 4 Sensor well for temperature sensor 5 Boiler return 6 Cold water inlet 7 Heat exchanger for heating by boiler, smooth enameled tubing 8 Inspection port for service and cleaning at the front 9 2nd anode in inspection port, with insulation 10 SU54/5: 2x built-in magnesium anodes with electrical
insulation SU80, SU100/5:built-in magnesium anode without electrical insulation
11 Tank, enameled steel 12 Jacket, painted sheet metal with rigid polyurethane foam
insulation, 2" (50 mm)
13 Inspection port for service and cleaning 14 PS top cover
Table 4 Product information
2.4 Data plate
The data plate is located at the top rear of the DHW tank.
2.5 Pressure drop curve of heating coil
8
6
3
2
4
1
A
2
Pressure drop [ft of head]
0
2
46810121416
ow rate [gpm]
Fig. 3 Pressure drop curve
[1] SU100/5 [2] SU80/5 [3] SU54/5
Example:
[A] 10 gpm, 2 ft of head
6 720 805 397-08.1ITL
SU54/5, SU80/5, SU100/5 – 6 720 808 532 (2013/08) 5
2
Product information
2.6 Technical Data
Unit SU54/5 SU80/5 SU100/5
Tank capacity
Tank capacity (total) gal
(l)
Maximum flow rate gpm
(l/min)
Maximum DHW temperature °F
(°C)
Maximum operating pressure DHW psi
(bar)
Tank performance at:
Domestic cold water inlet temperature °F
(°C)
Domestic hot water outlet temperature °F
(°C)
DHW temperature rise °F
(°C)
Coil supply water temperature (boiler water) °F
(°C)
Coil flow rate (boiler water) gpm
(l/h)
Coil pressure drop (boiler water) foh
(mbar)
Continuous rating gph
(l/h) gpm (l/min)
First hour rating gph
(l/h)
Maximum heat input to tank btu/hr
(kW)
Heat exchanger
Content gal
(l)
Surface area ft
Standby heat loss (at 149 °F (65 °C) DHW temperature, 68 °F (20 °C) room temperature)
Maximum coil supply water temperature °F
Maximum coil operating pressure psi
Table 5 Technical Data
2
(m2) °F/h
(K/h)
(°C)
(bar)
52.8 (200)
5.3 (20)
203 (95)
145 (10)
50 (10)
140 (60)
90 (50)
176 (80)
11.45 (2600)
2.68 (80)
114 (430)
1.9 (7)
151 (570)
85304 (25)
1.59 (6)
9.69 (0.9)
0.55 (0.31)
230 (110)
232 (16)
79.3 (300)
7.9 (30)
203 (95)
145 (10)
50 (10)
140 (60)
90 (50)
176 (80)
11.45 (2600)
3.35 (100)
134 (507)
2.2 (8)
190 (717)
100658 (29.5)
2.32 (8.8)
13.99 (1.3)
0.41 (0.23)
230 (110)
232 (16)
103 (390)
10.3 (39)
203 (95)
145 (10)
50 (10)
140 (60)
90 (50)
176 (80)
15.41 (3500)
6.93 (207)
209 (791)
3.5 (13)
281 (1064)
156959 (64)
3.2 (12.1)
19.38 (1.8)
0.34 (0.19)
230 (110)
232 (16)
SU54/5, SU80/5, SU100/5 – 6 720 808 532 (2013/08)6
2.7 Physical and connection dimensions
6 720 805 397-03.4TT
F
G
H
I
K
J
E
A
L
M
D
E
F
H
I
J
G
A
C
C
B
D
SU 54/5 SU80/5, SU100/5
1"
1"
1"
1"
¾"
¾"
1"
1"
1"
1"
¾"
¾"
Product information
2
Fig. 4 Physical and connection dimensions
Item Description Unit SU54/5 SU80/5 SU100/5
A Diameter inch
(mm)
B Minimum floor weight carrying capacity Ib
(kg)
C Clearance off floor inch
(mm)
D Overall height inch
(mm)
E Height, cold water inlet inch
(mm)
F Height, tank return inch
(mm)
G Height, sensor well for temperature sensor inch
H Boiler flow height inch
I Height, recirculation connection inch
(mm)
(mm)
(mm)
J Height, DHW outlet inch
(mm)
K Minimum room height for anode replacement inch
L Weight (empty) lb
M Weight (full) lb
Table 6 Physical and connection dimensions
(mm)
(kg)
(kg)
21-3/4 (550)
628 (284)
1/2 (12.5)
60-1/4 (1530)
3-1/4 (80)
10-1/2 (265)
17-1/8 (433)
21-7/8 (553)
27-3/4 (703)
56.4 (1399)
74-1/4 (1880)
160.9 (73)
601.9 (273)
26-3/8 (670)
893 (405)
3/8 - 3/4 (12.5)
58-7/8 (1495)
3-1/8 (80)
12-1/2 (318)
31-1/5 (617)
28-1/2 (722)
35-1/2 (903)
53-3/8 (1355)
72-7/8 (1850)
231.5 (105)
892.9 (405)
26-3/8 (670)
1122 (509)
3/8 - 3/4 (12.5)
72-1/4 (1835)
3-1/8 (80)
12-1/2 (318)
24-3/10 (793)
35-3/8 (898)
45 (1148)
66-3/4 (1695)
82-3/4 (2100)
282.2 (128)
1142 (518)
SU54/5, SU80/5, SU100/5 – 6 720 808 532 (2013/08) 7
3
6 720 800 035-03.1ITL
Standards, regulations and directives
3 Standards, regulations and directives
Observe all national, state, and local code, regulations and standards applicable to installation and operation of the tank!
All electrical components must be approved for the USA and Canada.
4 Moving the tank
WARNING: Risk of injury from carrying heavy loads and
inadequately securing loads for transport! ▶ Use suitable means of transportation, e.g. a dolly with
strap.
▶ Secure the load against falling.
Where possible, do not remove the DHW tank from its packaging until it has reached the installation location. This ensures protection during handling.
▶ Position the dolly at the back of the packed DHW tank. ▶ Secure the DHW tank to the means of transportation with a strap. ▶ Transport the DHW tank to the installation location. ▶ Only remove the DHW tank from the packaging at the installation
location.
5 Installation
The tank is delivered fully assembled. ▶ Check that the tank is complete and undamaged.
5.1 Boiler installation
5.1.1 Requirements for installation location
NOTICE: Risk of damage from inadequate load-bearing
capacity of the supporting substructure or unsuitable floor surface! ▶ Ensure that the installation area is level and offers
sufficient load-bearing capacity.
NOTICE: Risk of damage from stress cracking and corrosion!
▶ Position the DHW tank in a dry room free from the risk
of freezing.
▶ Install the tank only in closed-loop, unvented hydronic
heating systems.
▶ Open expansion vessels may NOT be used with this
tank.
NOTICE: If leaks can result in property damage or a drain pan is required by law:
▶ Install an adequate drain pan. ▶ Follow the installation instructions of the drain pan
manufacturer.
Fig. 5 Transporting with a dolly
Install an adequate drain pan if required by code, or if a leak could result in property damage. Follow drain pan manufacturer's instructions.
▶ Place the DHW tank on a raised platform if there is a risk that water
may collect at the installation site. ▶ The installation site must be a dry and frost-free room. ▶ Observe the minimum height (Tab. 6, page 7) and minimum wall
clearances inside the installation room (Fig. 6). ▶ Maintain a distance of 2" (51 mm) from heated pipes and combustible
surfaces.
SU54/5, SU80/5, SU100/5 – 6 720 808 532 (2013/08)8
Installation
6 720 801 769-03.1ITL
6 720 800 035-04.1ITL
6 720 801 769-15.1ITL
1.
2.
3.
6 720 801 769-13.1ITL
5
5.1.2 Wall clearances
Fig. 6 Recommended minimum wall clearances
5.1.3 Positioning the tank
▶ Unpack the tank by removing the wrap, wooden boards and foam pad
on the top.
▶ Lay the foam pad on the floor to serve as a mat.
▶ Unscrew the screw-in feet [3].
Fig. 8 Laying the DH tank on its side and exposing the adjustable feet
▶ Position the DHW tank on a level floor with adequate load-bearing
capacity.
Fig. 7 Unpacking the DHW tank
▶ Carefully place the DHW tank on the cover pad [1].
▶ Cut out the raised sections in the EPS bottom pad [2].
SU54/5, SU80/5, SU100/5 – 6 720 808 532 (2013/08) 9
Fig. 9 Positioning the tank
▶ Maintain minimum wall clearances. ▶ Using the adjustable feet, align the DHW tank vertically.
5
6 720 800 155-22.1ITL
A
B
6 720 800 138-05.1ITL
AW
5
Installation
▶ Remove the protective caps from the connections.
NOTICE: Risk of corrosion from damage to the enamel finish!
▶ Attach connections to the DHW tank only "hand-
tight".
5.2.1 Connecting the tank on the water side
System example with all recommended valves and shut-offs (Fig. 11).
▶ When sizing the heating system expansion vessel, take the volume
of the heating coil in the tank into consideration. ▶ Route the connection cables for the tank temperature sensors at the
back of the tank through the insulation to the heating appliance or
controller. ▶ Install piping runs so that natural circulation is prevented.
If necessary, install check valves. ▶ Install connection cables free of stress. ▶ Attach piping to the tank connections on-site. ▶ Check all connections for leaks.
Fig. 10 Removing the protective caps
▶ Use Teflon tape or Teflon cord to seal the connections. Do not use
hemp to seal the connections.
5.2 Water connections
CAUTION: Water damage
▶ Connect the drain to the bottom tank connection prior
to filling the tank.
▶ Seal off all unused tank connections.
DANGER: Risk of fire from soldering and brazing! ▶ Take appropriate safety measures when soldering
and brazing as the thermal insulation is flammable. For example, cover up the thermal insulation.
▶ Check tank jacket for damage after completing work.
DANGER: Risk of injury from contaminated water! Work carried out without due care for cleanliness
contaminates the drinking water. ▶ Install in accordance with national standards and
guidelines.
Fig. 11 Installation (illustrative)
[1] Storage tank [2] Shut-off valve [3] P&T safety valve (combined with hot water outlet) [4] Check valve [5] Tank primary pump [6] Recirculation pump (optional) [7] Air eliminator (in main supply) [8] Drain valve [9] Expansion vessel [AW] DHW outlet [EK] Cold water inlet [EL] Tank drain [EZ] Recirculation inlet [RS] DHW cylinder return [VS] DHW cylinder flow
SU54/5, SU80/5, SU100/5 – 6 720 808 532 (2013/08)10
5.2.2 Installing a T&P safety valve (on-site)
6 720 800 155-17.1ITL
5
4
123
▶ Install a listed T&P safety valve that is approved for potable water
(¾ ") in the DHW outlet. ▶ This DHW tank must be installed with a new T&P safety valve. ▶ The T&P valve must be sized no smaller than the rated tank capacity. ▶ Observe the safety valve installation instructions. ▶ T&P discharge pipe:
– The discharge pipe must be at least equal to the outlet cross-
section of the safety valve.
– Route the discharge line from the T&P valve directly to an adequate
drain (maximum length 6 ft (2m) with no more than two 90°­elbows).
– The discharge line must terminate at an adequate drain in order to
prevent property damage from spillage.
– Check that the T&P safety valve operates properly at least once
annually.
▶ Never plug the blow-off line. During heating, water may be discharged
for operational reasons at any time.
5.3 Install a tank water temperature sensor (accessory)
or aquastat (accessory).
Installation
5
DANGER: Risk of fatal injury from electric shock.
▶ Isolate the system electrically prior to commencing
work on the system.
Connect the electrical power and set the temperature on the DHW temperature sensor or the aquastat as shown in the respective aquastat or control manufacturer's instructions.
Install a tank temperature sensor or an aquastat on the DHW tank to measure and monitor the hot water temperature.
Installing the DHW temperature sensor
▶ Take the tank temperature sensor from the scope of delivery of the
control panel (accessories). ▶ Insert the sensor set until it bottoms out inside the sensor well [5].
This automatically pushes back the plastic spiral [3] that holds the
sensor set together. The compensating spring [4] ensures contact between the sensor well
and sensor surfaces, and a reliable temperature reading.
Always ensure that the full length of the sensor surface is in contact with the sensor well.
Fig. 12 Installing the DHW temperature sensor
[1] Quarter-circle spacer [2] Temperature sensor [3] Plastic spiral [4] Compensating spring [5] Sensor Well
▶ Push sensor retaining clip [1] from the side onto sensor well [2]. ▶ Route the sensor lead to the boiler or control panel and ensure the
cable is not strained. This cable must not be in contact with any hot boiler parts.
▶ In the case a sensor is being used without a compensating spring, the
empty space in the sensor well must be filled with a sufficient amount of heat-conducting paste.
SU54/5, SU80/5, SU100/5 – 6 720 808 532 (2013/08) 11
Fig. 13 Installing the sensor retainer
[1] Sensor retainer [2] Sensor Well
5
6 720 800 155-03.1ITL
6 720 800 155-04.1ITL
5
4
3
2 1
6
6 720 801 769-04.1ITL
1
2
3
4
Installation
Installing aquastat
▶ Remove cover from the aquastat. To do so, undo the screw on the top. ▶ If necessary, remove any unnecessary attachments. Attach bracket
[3] to aquastat [2] by means of two self-tapping screws [1].
Fig. 14 Attaching the aquastat to the bracket
[1] Self-tapping screws [2] Aquastat [3] Bracket
▶ Feed the temperature sensor [4] with the compensating spring [3]
into the sensor well [5].
▶ Attach bracket [6] to DHW tank by means of 4 self-tapping sheet
metal screws [1].
▶ Replace the cover of the aquastat [2].
Installing B-kit components
Fig. 16 Installing B-kit components
[1] Tee 1" x 1" x ¾ " (2x) with P&T safety valve [2] Cap ¾ " for recirculation connection [3] Bracket with aquastat [4] Tee with fill and drain valve
Fig. 15 Installing aquastat
[1] Self-tapping screws [2] Aquastat [3] Compensating spring [4] Temperature sensor [5] Sensor Well [6] Bracket
SU54/5, SU80/5, SU100/5 – 6 720 808 532 (2013/08)12
6 Commissioning
NOTICE: Risk of system damage from excessive
pressure! Excessive pressure can result in tension cracks in the enamel coating.
▶ Never plug the discharge line of the T&P safety valve.
6.1 Commissioning the DHW tank
Have the installer of the heating system or a qualified contractor commission the equipment.
▶ Commission the boiler and additional accessories in accordance with
manufacturer's instructions or the appropriate installation and
operating instructions.
Use only drinking water to check the DHW tank for leaks. On the DHW side, the test pressure must not exceed 145 psi (10 bar) gauge pressure.
▶ To bleed air from the DHW tank, open the highest tap/valve. ▶ To fill the tank, open the shut-off valve for the cold water inlet. ▶ Flush the tank and piping thoroughly prior to commissioning. ▶ Before heating up, verify that the boiler, tank and pipework are filled
with water. Open the air bleeder valve for this purpose. ▶ Check all connections, piping and the inspection port for leaks.
Commissioning
6
7.2 Shutting down the heating system when there is a risk of frost
▶ Shut down the heating system and the DHW tank as shown in
chapter 7.1.
Fully drain the tank – even the lowest section of the tank and the heating coil.
8 Environmental Protection / Disposal
Environmental protection is a fundamental principle of the Bosch Group. Quality of products, efficiency and environmental protection are equally important objectives for us. All legislation pertaining to the environment is strictly observed.
Packaging
For the packaging, we participate in the country-specific recycling systems, which guarantee optimal recycling. All packaging materials used are environmentally-friendly and recyclable.
Old appliances
Old appliances contain materials that should be recycled. The relevant assemblies are easy to separate, and all plastics are identified. This allows the various components to be sorted for appropriate recycling or disposal.
7 Shutdown
CAUTION: Risk of tank damage!.Residual moisture can
result in corrosion. ▶ Thoroughly dry out the inside (e. g. by means of hot
air) and leave the cleanout cover open.
7.1 Shutting down the DHW tank
▶ Switch off the temperature controller at the control panel, shut of the
heating system emergency shutoff switch, or disengage the heating system circuit breaker.
WARNING: Risk of scalding from hot water! ▶ Let the tank cool down sufficiently.
▶ Close the cold water inlet shutoff valve. ▶ Drain the DHW tank via the drain valve by opening the highest faucet. ▶ Close the shut-off valves to and from the boiler. ▶ Depressurize the heat exchanger. ▶ Drain and blow out the heat exchanger. ▶ To prevent corrosion, dry out the inner space and keep the inspection
port covers open.
9 Maintenance
▶ Allow the DHW tank to cool down sufficiently before performing any
maintenance. ▶ Remedy all faults immediately. ▶ Use original spare parts only! ▶ The tank must be inspected annually and maintained as required. ▶ Check the T&P safety valve annually.
9.1 Preparing the DHW tank for cleaning
The SU80/5 and SU100/5 tanks are cleaned by means of the cleanout on the side. The SU54/5 tank is cleaned by means of the cleanout at the top.
DANGER: RISK OF SCALDING Hot water can cause scalding. ▶ Prior to cleaning, allow the DHW tank to cool down
sufficiently.
▶ Disconnect electrical power from the heating system. ▶ Drain the DHW tank. To do so, close the shut-off valve for cold water
inlet and the open drain valve. To vent the system, open the air vent
valve or the highest faucet. ▶ Remove the PS top cover (SU54/5) (Fig. 17, page 14, [1]) or
cleanout cover shroud (SU80/5, SU100/5) ( Fig. 18, page 14,
[1]) from the tank. ▶ Loosen the hex bolts [2] in the cleanout cover [3].
SU54/5, SU80/5, SU100/5 – 6 720 808 532 (2013/08) 13
9
6 720 801 769-07.1ITL
1
2
3
4
5
6
6 720 805 397-09.1ITL
Maintenance
▶ Remove the cleanout cover [3], magnesium anode [5] and cleanout
cover gasket [4].
9.2 Descaling/cleaning the DHW tank
▶ Check the DHW tank interior for scale deposits (calcium).
CAUTION: Risk of tank damage due to damaged enamel. ▶ Never use hard objects or tools with sharp edges to
clean the interior of the tank
Should scale deposits be discovered inside the DHW tank, proceed as follows: ▶ Hose down the inside of the DHW tank with a “high-pressure” (approx.
58 – 72.5 psi (4 - 5 bar) gauge pressure) cold water jet. You can increase the cleaning effect by heating up the heat exchanger in the drained tank before cleaning. The thermal shock effect releases scale deposits more easily from the coil-type heat exchanger.
▶ Use a wet & dry vacuum cleaner with plastic suction hose to remove
the residues.
Extremely tough scale deposits inside the DHW tank can be removed by chemical means. We recommend that you have a qualified contractor carry out the chemical cleaning operation.
Fig. 17 Removing the cleanout cover SU54/5
[1] PS top cover [2] Hex bolts [3] Cleanout cover [4] Cleanout cover gasket [5] Magnesium anodes [6] Inspection port
Fig. 18 Removing the cleanout cover SU80/5, SU100/5
[1] Cleanout cover shroud [2] Hex bolts [3] Cleanout cover [4] Magnesium anode [5] Cleanout cover gasket [6] Inspection port
Fig. 19 Hose down the inside of the tank as shown in the example
SU80/5, SU100/5
SU54/5, SU80/5, SU100/5 – 6 720 808 532 (2013/08)14
Maintenance
6 720 800 155-23.1ITL
9
9.3 Checking the magnesium anode
If the magnesium anode is not serviced properly, the warranty is void. Annual service records must be kept in a safe location and submitted together with the original purchase receipt in the event of a warranty claim.
The purpose of the anode rod is to protect the DHW tank against corrosion. It is critical that the anode rod be inspection once a year to determine whether it requires replacing.
Upon inspection, the anode rod surface should appear sm ooth. If the rod surface appears pitted, bumpy, rusty, scale has built up on the surface, or if the rod is less than 5/8" (15 mm) in diameter, then it must be replaced.
Certain installations may require more frequent replacement of the anode rod:
• Recirculation applications,
• Poor water quality,
• Galvanic/electrolytic corrosion,
• High flow applications. In the event of poor water quality it is recommended that a water
treatment professional be consulted for water treatment options.
Never bring the magnesium anode surface in contact with oil or grease.
▶ Keep everything clean.
9.3.2 Checking the upper magnesium anode (SU54/5)
▶ Remove the cleanout cover (Fig. 17, page 14), if not yet removed. ▶ Check the magnesium anodes. ▶ Replace the magnesium anode if its diameter has been reduced to
approx. 5/8 " (15 mm). ▶ To release the ground cable eyelet [8], undo nut M8 [9]. ▶ Undo nut M8 [7]. ▶ Remove cleanout cover [3] from magnesium anode [1]. ▶ Install new magnesium anode with the aid of the hardware provided
(Fig. 21).
9.3.1 Checking the upper magnesium anode (SU80/5, SU100/5)
▶ Remove PS top cover if not already removed. ▶ Unscrew the magnesium anodes. ▶ Check the magnesium anodes for decomposition. ▶ Replace the magnesium anode if its diameter has been reduced to
approx. 5/8 " (15 mm).
▶ Screw the magnesium anodes back into the cover.
Fig. 20 Checking the upper magnesium anode SU80/5, SU100/5
[1] Hex bolt [2] Magnesium anode
Fig. 21 Replacing the magnesium anode
[1] Magnesium anode [2] Gasket [3] Cleanout cover [4] Insulating sleeve [5] U-washer [6] Serrated washer [7] M8Nut [8] Ground wire eyelet [9] M8Nut
9.3.3 Checking the magnesium anode at the side
(SU80/5, SU100/5)
▶ Empty the tank as described in chapter 9.1, page 13. ▶ Remove the cleanout cover (Fig. 17, page 14), if not yet removed. ▶ Check the magnesium anodes. ▶ Replace the magnesium anode if its diameter has been reduced to
approx. 1/2 " (15 mm). ▶ To release the ground cable eyelet [8], undo nut M8 [9]. ▶ Undo nut M8 [7]. ▶ Remove cleanout cover [3] from magnesium anode [1]. ▶ Install new magnesium anode with the aid of the hardware provided
(Fig. 21).
SU54/5, SU80/5, SU100/5 – 6 720 808 532 (2013/08) 15
9
6720 800 155-06.1ITL
Maintenance
9.4 Re-commissioning after performing maintenance
CAUTION: Risk of tank damage from a faulty gasket!
▶ To prevent the DHW tank from leaking, install a new
cleanout cover gasket upon completion of cleaning and maintenance.
▶ Put the cleanout cover [4] back in place (top or side) together with the
new gasket [2]. ▶ Thread hex bolts [5] into cleanout cover [4] "hand-tight". ▶ Then use a torque wrench to tighten the hex bolts to 18-22 lbf-ft
(25 - 30 Nm). ▶ Fill the DHW tank and restart the heating system. ▶ Check all connections and the inspection port for leaks. ▶ Replace the cleanout cover shroud. ▶ Reposition the PS top cover on the tank.
Fig. 22 Reassembling the inspection port
[1] Inspection port [2] Cleanout cover gasket [3] Magnesium anode [4] Cleanout cover [5] Hex bolts [6] Cleanout cover shroud
SU54/5, SU80/5, SU100/5 – 6 720 808 532 (2013/08)16
10 Spare Parts
6 720 805 397-18.1ITL
1
2
4
6
9
10
13
14
4
Spare Parts
10
Fig. 23 Spare parts for SU54/5
Item Article description Product No.
1 Cover D550 lid, black 8 718 542 319 0 2 Plug, EPS upper part D370 8 718 541 763 0 4 Self-tapping hex screw M10x25 (8x) 7 747 005 744 6 O-ring 120.02x6.99-N 8 718 572 538 0 9 Spacer, 1/4-circle (1x) 8 718 585 547 10 Compensator spring (5x) 8 718 585 143 13 Self-tapping screw St 4.2x13 (10x) 7 747 027 696 14 Retaining plate for the aquastat 7 747 028 761 0
Logo Buderus 8 718 541 573 0
Table 7
SU54/5, SU80/5, SU100/5 – 6 720 808 532 (2013/08) 17
Loading...
+ 39 hidden pages