Buderus Installation And Service Instructions Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
Solar and High-Performance
DHW Storage Tanks
WARNING:
These installation instructions are intended solely for use by a licensed
heating contractor or service technician. Read all instructions before installing. Perform steps exactly in the order given. Failure to follow these
instructions can result in severe injury, death or property damage.
NOTICE:
The heat transfer medium must be nontoxic water with Toxicity Class 1
as listed in "Clinical Toxicology of Commercial Products," 5th edition.
The heat transfer medium must be limited to a maximum pressure of
30 PSIG by an approved safety or pressure relief valve.
DANGER :
Cette notice d’installation doit être utilisée uniquement par des installateurs chauffagistes ou des techniciens de maintenance qualifiés. Lisez
attentivement toutes les consignes avant l’installation. Exécutez les actions précisément dans l’ordre indiqué. En cas de non-respect, vous risquez de subir de sérieuses blessures pouvant conduire à la mort ou
d’entraîner de lourds dommages matériels.
REMARQUE :
Le milieu caloporteur doit être de l’eau non toxique de classe 1 telle que
précisé dans la 5e édition de « Clinical Toxicology of Commercial
Products ». Le liquide caloporteur doit être limité à une pression maximale
de 30 PSIG par une soupape de sécurité ou de surpression homologuée.
PELIGRO :
Este manual de instalación únicamente lo pueden utilizar instaladores de
calefacción o técnicos especializados. Antes de la instalación, lea todas
las indicaciones. Realice todas las acciones exactamente en el orden indicado. En caso de incumplimiento, existe riesgo de lesiones graves e incluso de muerte o daños materiales considerables.
6 720 647 567-00.1ITL
AVISO :
El portador de calor se debe limitar a una presión máxima de 2 bar mediante una válvula de seguridad o de sobrepresión.
▶ The electrical connection must be connected by a electrician.
The wiring diagram must be followed.
▶ Do not install this device in rooms with a high moisture level
(e.g. bathrooms, saunas).
1
Warnings
Warnings in this document are identified by a warning
triangle printed against a grey background.
Keywords at the start of a warning indicate the type and
seriousness of the ensuing risk if measures to prevent
the risk are not taken.
The following keywords are defined and can be used in this document:
• DANGER indicates a hazardous situation which, if not avoided, will
result in death or serious injury.
• WARNING indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
• CAUTION indicates a hazardous situation which, if not avoided,
could result in minor to moderate injury.
• NOTICE is used to address practices not related to personal injury.
Important Information
This symbol indicates important information where
there is no risk to people or property. It is separated by
horizontal lines above and below the text.
Additional symbols
Symbol Function
▶Sequence of steps
Cross-reference to another part of the document
Read all instructions before installing. Perform the steps in the indicated
sequence. Have the DHW tank inspected by a trained service technician
at least once every year. Failure to comply with these instructions can
result in severe, possibly fatal, personal injury as well as damage to
property and equipment.
Installation and servicing
▶ Risk of fire from soldering and brazing!
Take appropriate protective measures when soldering and brazing as
the insulation is flammable, for example, cover the insulation.
▶ Ensure that only a licensed contractor installs or services the DHW
tank.
▶ Use installation material with adequate temperature stability.
Function
▶ To ensure that the tank functions properly, heed these installation
and maintenance instructions.
▶ Never close the blow-off line of the T&P safety valve. For safety
reasons, water may escape during heating.
Danger from electric shock
▶ Make sure that only certified electricians perform the electrical work.
▶ Before performing electrical work, disconnect the power and secure
the unit against unintentional reconnection.
▶ Ensure the system has been disconnected from the power supply.
Risk of scalding at the hot water draw-off point
▶ When the DHW tank is in operation, temperatures in excess of 122 °F
(50 °C) can occur. To limit the temperature at the tap, install a
thermostatic DHW mixing valve.
▶ Water heated for washing the laundry, dishes and for other cleaning
purposes can cause scalding and permanent injuries.
▶ Children, elderly, and handicapped persons are more likely to be
permanently injured by hot water. Never leave such individuals in the
tub or shower unattended under any circumstances. Children must
not be allowed to operate hot water faucets themselves or to fill a
bathtub.
▶ If the building has occupants in the above groups who operate hot
water faucets, or state laws / local ordinances stipulate specific
water temperatures, take the following precautions:
– Use the lowest possible temperature setting.
– To prevent scalding, install a tempering device, such as an
automatic mixing valve, at hot water tap or water heater. Select
and install the automatic mixing valve in accordance with the
valve manufacturer's recommendations and instructions.
▶ Water exiting from drain valves can be extremely hot. To avoid
injuries:
– Check that all connections are tight.
– Direct exiting water away from people.
▶ Measures must be taken to protect against excessive temperature
and pressure! Installation of a T&P safety valve is required.
The chart below shows the relationship between water temperature and
time until there is a risk of scalding. It can be used as the basis for
determining the safest water temperature for your application.
Forbidden:
Connection of the potentiostat for an impressed current anode to the
magnesium anode installed in a storage tank is absolutely forbidden!
This would destroy the tank! The warranty would be voided.
Table 2 Approximate time-temperature relationship until there is a risk
of scalding
1. Source: Moritz, A.R. and Henriques, F.C., Jr. (1947). Studies of thermal injury.
II. The relative importance of time and surface temperature in the causation of
cutaneous burns, Am J of Pathol, 23, 695-720.
To protect against corrosion and ensure compliance with the rules for
electrical safety, observe the following points:
▶ Use metal fittings for drinking water heating systems with plastic
piping.
▶ Use only original accessories from the manufacturer.
▶ When installation of the tank is complete, inspect the ground
conductor (including metal fittings).
Maintenance
Customers are advised to:
▶ Sign a maintenance and inspection contract with an authorized
contractor. Inspect and maintain the DHW tank as necessary on a
yearly basis. Service as needed.
▶ Use only original spare parts.
Flooding
▶ After a flood, do not use the appliance if any part has been
submerged. Damage to appliances that have been submerged can be
quite severe and pose numerous safety risks.
▶ An appliance that was subject to flooding must be replaced.
1
1.3Instructions for the owner and operator
WARNING: Risk of scalding at the taps!
There is a risk of scalding at the taps if the tank
temperature is set above 122 °F (50 °C) and during
thermal disinfection.
▶ Advise users that they should draw off only mixed
water. Otherwise, install a thermostatic DHW mixing
valve.
▶ Highlight the following for the user:
– Water may be discharged from the T&P safety valve during heat-
up.
– The blow-off line on the T&P safety valve must always be kept
open.
– Check that the T&P safety valve operates properly at least once
yearly.
– The tank must be inspected annually and maintained as required.
2Product Information
2.1Scope of delivery
• DHW tanks
•Tank components
• Installation and Maintenance Instructions
3
1
2
4
5
6
7
6 720 805 397-01.1ITL
Fig. 1Tank components
[1]Tee 1" x 1" x 3/4" (2x)
[2]Temperature and pressure relief valve
[3]Recirculation connection cap 3/4"
[4]Drain valve
[5]Bracket for aquastat, screws for aquastat bracket (4x)
[6]Com pensating spring for aquastat or cylinder temperature sens or
[7]Quarter-circle spacers for aquastat or tank temperature sensor
(2x)
NOTICE: Risk of tank damage from excessively high
pressure.
▶ Never close the temperature and pressure safety
valve blow-off line.
▶ Explain the operation and handling of the heating system and DHW
tank, making a particular point of safety-relevant features.
▶ Explain the function and how to check the T&P safety valve.
▶ Hand all enclosed documents over to the owner/operator.
▶ Recommendation for the user: Sign a maintenance and inspection
contract with a licensed contractor.
SM80/5, SM100/5 – 6 720 800 156 (2017/07)4
2.2Designated use
The DHW tank can be operated in a solar thermal system with a boiler as
a back-up, or for high output only with a boiler. (Operation of the two
heat exchangers in series or parallel.) The tank is designed for heating
and storing drinking water. Please observe national, regional, and local
codes, regulations, guidelines and standards for drinking water. When
operated as part of a solar system, the solar thermal system must be
filled with solar antifreeze to prevent frost damage.
The tank can be used only in closed loop systems and is not suitable for
drain-back solar thermal systems. Any other purpose is considered
improper use. Any resulting damage is excluded from the
manufacturer's warranty.
Requirements
for potable waterUnit
Water hardness, min.ppm
grain/US gallon
°dH
36
2.1
2
pH value, min. – max.6.5 – 9.5
Conductivity, min. – max.μS/cm130 – 1500
Table 3 Requirements for potable water
2.3Product Information
14
13
12
11
10
Product Information
16
15
17
2
1
2
3
4
5
6
7
8
ItemDescription
1DHW outlet
2Boiler supply
3Sensor well for temperature sensor, heat source or
aquastat
4Recirculation connection
5Boiler return
6Solar supply
7Sensor well for temperature sensor, solar
8Solar return
9Cold water inlet
10Bottom heat exchanger for heating by a solar system,
smooth enameled tubing
11Inspection port for service and cleaning at the front
12Fitted magnesium anode without electrical insulation
13Upper heat exchanger for reheating by heating appliance,
smooth enameled tubing
14Tank, enameled steel
15Fitted magnesium anode without electrical insulation
16PS top cover
17Jacket, painted sheet metal with rigid polyurethane foam
insulation, 2" (50 mm)
Table 4 Product Information
9
6 720 800 155-01.1ITL
Fig. 2SM80/5, SM100/5
2.4Data plate
The data plate is located at the top rear of the DHW tank.
SM80/5, SM100/5 – 6 720 800 156 (2017/07)5
2
feed of head
feed of head
Product Information
2.5Pressure drop curve of heating coil
Pressure drop curve of bottom heat exchanger
20.00
15.00
10.00
feed ofhead
5.00
A
0.00
4.00 6.00 8.00 10.00 12.00 14.00 16. 00
2
18.00
20.00 22.00 24.00
gpm
Fig. 3Pressure drop curve of bottom heat exchanger
[1]SM80/5
[2]SM100/5
Example:
[A]8 gpm, 2.2feed of head
1
26.00 28.00
6 720 800 155-18.2T
Pressure drop curve of top heat exchanger
20.00
15.00
10.00
feed ofhead
5.00
2
B
0.00
4.00 6.00 8.00 10.00 12.00 14.00 16.00
Fig. 4Pressure drop curve of top heat exchanger
[1]SM80/5
[2]SM100/5
Example:
[B]8 gpm, 1.4 feed of head
If the two heat exchangers are piped in series, the
pressure drops are cumulative.
If they are operated in parallel, a separate pump is
recommended for each heat exchanger. Otherwise, fl ow
setters are needed to regulate the flow through the two
heat exchangers.
Ensure that in any case the pumps meet the load.
ADiameterinch (mm)26-3/8 (670)26-3/8 (670)
BMinimum floor weight carrying capacitylb (kg)899 (408)1135 (515)
CClearance off floor inch (mm)3/8 - 3/4 (10 - 20)3/8 - 3/4 (10 - 20)
DOverall heightinch (mm)58-7/8 (1495)72-1/4 (1835)
EHeight, cold water inletinch (mm)3-1/8 (80)3-1/8 (80)
FHeight, solar returninch (mm)12-1/2 (318)12-1/2 (318)
GHeight, sensor well for temperature sensor (solar)inch (mm)24-21/64 (618)31-7/32 (793)
HHeight, solar supplyinch (mm)28-1/2 (722)35-3/8 (898)
iHeight, tank returninch (mm)32 (813)40-5/8 (1033)
JHeight, recirculation connectioninch (mm)35-1/2 (903)45 (1143)
KHeight, sensor well for temperature sensor
(heat source or aquastat)
VBoiler flow connection heightinch (mm)44 (1118)54-1/2 (1383)
MHeight, hot water outletinch (mm)53-3/8 (1355)66-3/4 (1695)
NMinimum room height for anode replacementinch (mm)72-7/8 (1850)82-3/4 (2100)
OEmpty weightlb (kg)260 (118)298 (135)
PTotal weight when filledlb (kg)899 (408)1135 (515)
Table 6
inch (mm)39-7/8 (1013)50-5/16 (1278)
SM80/5, SM100/5 – 6 720 800 156 (2017/07)8
Standards, regulations and directives
6 720 647 567-02.1ITL
3
3Standards, regulations and directives
Observe all local regulations and standards applicable to
installation and operation of the system in your country!
All electrical components must be approved for the USA
and Canada.
4Moving the tank
WARNING: Risk of injury from carrying heavy loads and
inadequately securing loads for transport.
▶ Use suitable means of transportation, e.g. a dolly
with strap.
▶ Secure the load against falling.
Where possible, do not remove the DHW tank from its
packaging until it has reached the installation location.
This ensures protection during handling.
▶ Position the dolly at the back of the packed DHW tank.
▶ Secure the DHW tank to the means of transportation with a strap.
▶ Transport the DHW tank to the installation location.
▶ Only remove the DHW tank from the packaging at the installation
location.
5Installation
The DHW tank is delivered fully assembled.
▶ Check DHW tank for completeness and damage.
5.1Tank installation
5.1.1Requirements for installation location
NOTICE: Risk of damage from inadequate load-bearing
capacity of the supporting substructure or unsuitable
floor surface!
▶ Ensure that the installation area is level and offers
sufficient load-bearing capacity.
NOTICE: Risk of damage from stress cracking and
corrosion!
▶ Position the DHW tank in a dry room free from the
risk of freezing.
▶ Install this DHW tank only in closed-loop, unvented
systems.
▶ Open expansion vessels can NOT be used for this
DHW tank.
NOTICE: If l ea ks can re sul t i n pr op er ty d am age or a d rai n
pan is required by law:
▶ Install an adequate drain pan.
▶ Follow the installation instructions of the drain pan
manufacturer.
Follow drain pan manufacturer's instructions.
Fig. 6Transporting with a dolly
5.1.2Wall clearances
▶ Place the DHW tank on a plinth if there is a risk that water may collect
at the installation site.
▶ The installation site must be a dry and frost-free room.
▶ Observe minimum room height ( Tab. 6, page 8) and minimum
wall clearance in installation room ( Fig. 7, page 10).
▶ Maintain a distance of 2" (51 mm) from heated pipes and
combustible surfaces.
SM80/5, SM100/5 – 6 720 800 156 (2017/07)9
5
6 720 647 567-05.1ITL
Installation
19-¾ inch
▶ Unscrewing the adjustable foot[3].
(500 mm)
1.
15-¾ inch
(400 mm)
4 inch
(102 mm)
6 720 800 155-10.1ITL
Fig. 7Recommended minimum wall clearances
5.1.3Positioning the tank
▶ Unpack the tank by removing the wrap, wooden boards and foam pad
on the top.
▶ Lay the foam pad on the floor to serve as a mat.
2.
3.
6 720 647 567-35.1ITL
Fig. 9Lay the DHW cylinder on its side and expose the adjustable foot
Fig. 8Unpacking the DHW tank
▶ Carefully lay the tank on the foam pad [1].
▶ Cut out the protections in the foam bottom [2].
SM80/5, SM100/5 – 6 720 800 156 (2017/07)10
Installation
6 720 800 155-22.1ITL
A
B
5
▶ Position the DHW tank on a level floor with adequate load-bearing
capacity.
▶ Remove the caps from the connections.
6 720 647 567-07.1ITL
Fig. 10 Positioning the tank
▶ Maintain minimum wall clearances.
▶ Using the adjustable foot, align the DHW cylinder vertically.
Fig. 11 Remove caps
▶ Use Teflon tape or Teflon cord to seal the connections. Do not use
hemp to seal the connections.
5.2Water connections
WARNING: Risk of fire from soldering and brazing!
▶ Take appropriate protective measures when
soldering and welding as the insulation is flammable,
for example, cover the insulation.
▶ Check tank jacket for damage after completing work.
DANGER: Risk of injury from contaminated water!
Work carried out without due care for cleanliness
contaminates the drinking water.
▶ Install in accordance with national standards and
guidelines.
NOTICE: Water damage
▶ Connect the drain to the bottom tank connection
prior to filling the tank.
▶ Seal off all unused tank connections.
SM80/5, SM100/5 – 6 720 800 156 (2017/07)11
NOTICE: Risk of corrosion from damage to the enamel
coating!
▶ Attach connections to the DHW tank only "hand-
tight".
5
6 720 800 155-11.1ITL
1
1
6 720 800 155-05.1ITL
Installation
5.2.1Connecting the tank on the water side
Example of system with all recommended valves ( Fig. 12, page 12).
▶ When selecting the expansion vessel for the hot water side, take the
content of the heat exchanger and DHW tank into consideration.
▶ Route the connection cables for the tank temperature sensors at the
back of the tank through the insulation to the heating appliance or
controller.
▶ Install piping runs so that natural circulation is prevented. If
necessary, install check valves.
▶ Install connection cables free of stress.
▶ Attach piping to the tank connections on-site.
▶ Check all connections for leaks.
5.2.2Installing a T&P safety valve (on-site)
▶ Install a listed T&P safety valve that is approved for drinking water
( ¾ ")in the DHW outlet.
▶ This DHW tank must be installed with a new T&P safety valve.
▶ The T&P valve must be sized no smaller than the rated tank capacity.
▶ Observe the safety valve installation instructions.
▶ T&P discharge pipe:
– T he bl ow-o ff l ine m ust be at lea st equal to the outlet cross-section
of the safety valve.
– Route the blow-off line from the T&P valve directly to an adequate
drain (maximum length 6 ft (2 m) with no more than two 90°elbows).
– The discharge line must terminate at an adequate drain in order to
prevent property damage from spillage.
– Check that the T&P safety valve operates properly at least once
annually.
▶ Never plug the blow-off line. During heating, water may be
discharged for operational reasons at any time.
Fitting the B-kit
Fig. 12 Installation (illustrative)
[1]Storage tank
[2]Shutoff valve
[3]P&T safety valve (combined with hot water outlet)
[4]Check valve
[5]Tank primary pump
[6]Recirculation pump (optional)
[7]Air eliminator (in main supply)
[8]Drain valve
[9]Expansion vessel
[10] Thermostatic DHW mixing valve
[11] Tank primary pump
[12] Solar pump station
[AW] DHW outlet
[EZ] Recirculation inlet
[VS1] Tank supply (solar)
[RS1] Tank return (solar)
[VS2] Tank supply (boiler)
[RS2] Tank return (boiler)
[EK] Cold water inlet
[EL] Tank drain
Fig. 13 Connecting the DHW tank components
[1]Tee 1" x 1" x 3/4" (2x) with T&P safety valve
[2]3/4" cap for recirculation connection
[3]Bracket with Aquastat
[4]Tee with fill and drain valve
5.3Installing the DHW water temperature sensor
(accessory) or Aquastat (accessory)
DANGER: Risk of fatal injury from electric shock.
▶ Isolate the system electrically prior to commencing
work on the system.
SM80/5, SM100/5 – 6 720 800 156 (2017/07)12
Installation
6 720 800 155-03.1ITL
5
Connect the electrical power and set the temperature on
the DHW temperature sensor or the aquastat as shown in
the respective aquastat or control manufacturer's
instructions.
Install a tank temperature sensor or an aquastat on the DHW tank to
measure and monitor the hot water temperature.
Installing the DHW temperature sensor
▶ Take the tank temperature sensor from the scope of delivery of the
control panel (accessories).
▶ Insert the sensor set until it bottoms out inside the sensor well [5].
This automatically pushes back the plastic spiral [3] that holds the
sensor set together.
The compensating spring [4] ensures contact between the sensor well
and sensor surfaces, and a reliable temperature reading.
Always ensure that the full length of the sensor surface is
in contact with the sensor well.
123
▶ In the case a sensor is being used without a compensating spring, the
empty space in the sensor well must be filled with a sufficient amount
of heat-conducting paste.
Fig. 15 Installing the sensor retainer
[1]Sensor retainer
[2]Sensor Well
Installing the aquastat
▶ Remove cover from the aquastat. To do so, undo the screw on the
top.
▶ If necessary, remove any unnecessary attachments. Attach bracket
[3] to aquastat [2] by means of two self-tapping screws [1].
4
5
6 720 800 155-17.1ITL
Fig. 14 Installing the DHW temperature sensor
[1]Quarter-circle spacer
[2]Temperature sensor
[3]Plastic spiral
[4]Compensating spring
[5]Sensor Well
▶ Push sensor retaining clip [1] from the side onto sensor well [2].
▶ Route the sensor lead to the boiler or control panel and ensure the
cable is not strained. This piping must not be in contact with any hot
boiler parts.
Fig. 16 Screw the bracket onto the aquastat
[1]Self-tapping screws
[2]Aquastat
[3]Holder
SM80/5, SM100/5 – 6 720 800 156 (2017/07)13
5
6 720 800 155-04.1ITL
5
4
3
21
6
Installation
▶ Feed the temperature sensor [4] with the compensating spring [3]
into the sensor well [5].
▶ Attach bracket [6] to DHW cylinder by means of 4 self-tapping sheet
metal screws [1].
▶ Replace the cover of the aquastat [2].
Fig. 17 Installing the aquastat
[1]Self-tapping screws
[2]Aquastat
[3]Compensating spring
[4]Temperature sensor
[5]Sensor Well
[6]Holder
5.4Connecting the KS solar pump station
Fig. 18 Connecting the KS solar pump station (schematic illustration)
Allow only an authorized contractor to make all the
piping connections.
WARNING: Risk of equipment damage from very high
operating temperatures and pressures!
▶ Use pressure- and temperature-resistant piping
materials.
▶ Do not use any galvanized piping, pipe connections
or graphite seals.
▶ Do not use any plastic piping or connections of any
kind.
▶ When using soldered connections in the entire solar
circuit, use high-temperature solder (melting point
455 °F (235 °C)).
To ensure proper operation of the solar thermal system,
air must be bled adequately from the entire system.
For information on bleeding the solar thermal system,
refer to the installation instructions for the KS solar
pump station.
▶ Attach the KS solar pump station [4] to the lower heat exchanger in
the DHW tank at the VS1 (solar supply) and RS1 (solar return)
connections.
▶ Attach the reheating device to the upper heat exchanger in the DHW
tank at the VS2 (storage tank supply) and RS2 (storage tank return)
connections.
▶ Use piping and pipe connections made of copper, brass and non-
galvanized steel for the connection between the KS solar pump
station [4] and DHW tank [5].
▶ Attach one grounding clamp each to the supply and return pipes (at
any position).
▶ Connect the grounding clamps to the building's grounding rod by
means of standard bonding cables AWG9.
Laying pipes with an automatic air vent valve on the roof (available
as accessory)
▶ Pipes to the air vent valve should follow a rising gradient. For every
downwards change of direction, an additional air separator with air
vent valve is required (heat-resistant to 302 °F (150 °C)).
5.5Connection as high-performance DHW tank
The DHW tank can also be used as a high-performance DHW tank.
In this case, 2 connection configurations are possible.
5.5.1Series connection of the lower and upper heat exchanger
▶ Attach the upper connection on the lower heat exchanger to the
lower connection on the upper heat exchanger in the DHW tank.
▶ Attach the tank charging pump to the upper connection on the upper
heat exchanger.
When the heat exchangers are connected in series, the
pressure loss across the two coils is cumulative.
Pressure drop of connecting pipe must be added. Ensure
that the pump used can handle the resulting pressure
drop.
▶ Attach the lower connection on the lower heat exchanger to the
return piping on the boiler.
SM80/5, SM100/5 – 6 720 800 156 (2017/07)14
Start-up procedure
6
▶ Install the Aquastat or DHW temperature sensor in the sensor well
provided for this purpose ( Fig. 2, page 5, [3]).
5.5.2Parallel connection of the lower and upper heat exchanger
We recommend that the two heat exchangers in the tank each be
connected to its own primary pump.
6Start-up procedure
NOTICE: Risk of equipment damage from excess
pressure! Excess pressure can cause stress cracking in
the enamel.
▶ Never close the temperature and pressure safety
valve blow-off line.
6.1Commissioning the DHW tank
Have the installer of the heating system or a qualified contractor
commission the equipment.
▶ Commission the boiler and other accessories in accordance with the
manufacturer's instructions in the corresponding installation and
operating manuals.
Use only drinking water to check the DHW tank for leaks.
On the DHW side, the test pressure must not exceed
150 psi (10.3 bar) gauge pressure.
▶ To bleed air from the DHW tank, open the highest tap/valve.
▶ To fill the DHW tank, open the shut-off valve for the cold water inlet.
▶ Flush the tank and piping thoroughly prior to commissioning.
▶ Before heating up, verify that the boiler, tank and pipework are filled
with water. Open the air bleeder valve for this purpose.
▶ Check all connections, piping and the inspection port for leaks.
▶ To prevent corrosion, dry out the inner space and keep the
inspection port covers open.
7.2Shutting down the heating system when there is a
risk of frost
▶ Shut down the heating system and the DHW tank as shown in
Chapter 7.1.
Drain the DHW tank completely, even the lower chamber
of the tank and the heat exchanger.
8Environmental protection/disposal
Environmental protection is one of the fundamental company policies of
the Bosch Group. We regard quality of performance, economy and
environmental protection as equal objectives.
Environmental protection laws and regulations are strictly adhered to.
To protect the environment, we use the best possible technology and
materials taking into account economic points of view.
Packaging
For the packaging, we participate in the country-specific recycling
systems, which guarantee optimal recycling. All packaging materials
used are environmentally-friendly and recyclable.
Old electrical and electronic appliances
Electrical or electronic devices that are no longer
serviceable must be collected separately and sent for
environmentally compatible recycling (in accordance
with the European Waste Electrical and Electronic
Equipment Directive).
To dispose of old electrical or electronic devices, you
should use the return and collection systems put in place
in the country concerned.
7Shutdown
NOTICE: Risk of tank damage!
Residual moisture can result in corrosion.
▶ Thoroughly dry out the inside (e. g. by means of hot
air) and leave the cleanout cover open.
7.1Shutting down the tank
WARNING: Risk of scalding from hot water!
▶ Let the tank cool down sufficiently.
▶ Switch off the temperature controller at the control panel, shut of the
heating system emergency shutoff switch, or disengage the heating
system circuit breaker.
▶ Close the cold water inlet shutoff valve.
▶ Drain the DHW tank via the drain valve by opening the highest faucet.
▶ Close the shut-off valves to and from the boiler.
▶ Depressurize the heat exchanger.
▶ Drain and blow out the heat exchanger.
9 Maintenance
▶ Allow the DHW tank to cool down sufficiently before performing any
maintenance.
▶ Remedy all faults immediately.
▶ Use original spare parts only!
▶ The tank must be inspected annually and maintained as required.
▶ Check the T&P safety valve annually.
9.1Preparing the DHW tank for cleaning
WARNING: Risk of scalding!
Hot water can cause scalding.
▶ Prior to cleaning, allow the DHW tank to cool down
sufficiently.
▶ Disconnect electrical power from the heating system.
▶ Drain the DHW tank. To do so, close the shut-off valve for cold water
inlet and the open drain valve. To vent the system, open the air vent
valve or the highest faucet.
▶ Remove the cleanout cover [6] shroud over the inspection port [1] in
the DHW tank.
SM80/5, SM100/5 – 6 720 800 156 (2017/07)15
9
6720 800 155-02.1ITL
Maintenance
▶ Loosen the hex bolts [5] in the cleanout cover [4].
▶ Remove the cleanout cover [4], magnesium anode [3] and cleanout
▶ Check the DHW tank interior for scale deposits (calcium).
NOTICE: Risk of tank damage due to damaged enamel.
▶ Never use hard objects or tools with sharp edges to
clean the interior of the tank.
Should limescale be discovered inside the DHW tank, proceed as
follows:
▶ Hose down the inside of the DHW tank with a "high pressure"
(approx. 58 – 72.5 psi (4 – 5 bar) gauge pressure) stream of cold
water ( Fig. 20, page 16).
You can increase the cleaning effect by heating up the heat exchangers
in the drained DHW tank before cleaning. The thermal shock effect
releases scale deposits more easily from the coil-type heat exchanger.
▶ Use a wet & dry vacuum cleaner with plastic suction hose to remove
the residues.
Extremely tough limescale inside the DHW tank can be removed by
chemical means. We recommend that you have a qualified contractor
carry out the chemical cleaning operation.
9.3Check the magnesium anodes
The warranty is void if the magnesium anode is not
correctly maintained. Annual service records must be
kept in a safe location and submitted together with the
original purchase receipt in the event of a warranty
claim.
The purpose of the magnesium anode is to protect the storage tank
against corrosion.
Every year, check whether the magnesium anode must be replaced. The
surface of the magnesium anode must be free of deposits.
If the rod surface appears pitted, bumpy, rusty, deposits have built up on
the surface, or if the rod is less than 5/8" (15 mm) in diameter, then it
must be replaced.
Certain installations may require more frequent replacement of the
magnesium anode rod:
• Recirculation connection
• Poor water quality
• Galvanic/electrolytic corrosion
• High flow rate
In the event of poor water quality it is recommended that a water
treatment professional be consulted for water treatment options. The
DHW cylinder warranty is void if the magnesium anode is not correctly
maintained.
Never bring the magnesium anode surface into contact
with oil or grease.
▶ Keep everything clean.
Checking the top magnesium anode
▶ Remove PS top cover if not already removed.
▶ Unscrew the magnesium anodes.
▶ Check the magnesium anodes for degradation.
▶ Replace the magnesium anode if the diameter has decreased to
approx. 5/8" (15 mm).
SM80/5, SM100/5 – 6 720 800 156 (2017/07)16
Maintenance
6 720 800 155-23.1ITL
6720 800 155-02.1ITL
9
▶ Insert the magnesium anodes into the sleeve again.
Fig. 21 Checking the top magnesium anode
[1]Hex bolt
[2]Magnesium anode
Checking the side magnesium anode
▶ Empty the DHW cylinder as described in Chapter 9.1.
▶ Remove cleanout cover ( Fig. 19, page 16), if it is not already
removed.
▶ Check the magnesium anodes.
▶ Replace the magnesium anode if the diameter has decreased to
approx. 5/8" (15 mm).
▶ Unscrew the nut M8 [9] to release the eyelet of the grounding cable
connecting lead[8].
▶ Unscrew the M8 nut [7].
▶ Remove the handhole cover [1] from the magnesium anode [3].
▶ Fit the new magnesium anode together with all small parts supplied
with it.
Key to Fig. 22:
[1]Magnesium anode
[2]Gasket
[3]Handhole cover
[4]Insulating sleeve
[5]Dished washer
[6]Serrated washer
[7]M8 Nut
[8]Eyelet of the grounding cable connecting lead
[9]M8 Nut
9.4Startup after maintenance
NOTICE: Risk of tank damage from a faulty gasket!
▶ To prevent the DHW tank from leaking, install a new
cleanout cover gasket upon completion of cleaning
and maintenance.
▶ Put the cleanout cover [4] back in place together with the new gasket
[2].
▶ Thread hex bolts [5] into cleanout cover [4] "hand-tight".
▶ Then use a torque wrench to tighten the hex bolts to 18-22 lbf-ft
(25 – 30 Nm).
▶ Fill the DHW tank and restart the heating system.
▶ Check all connections and the inspection port for leaks.
▶ Replace the cleanout cover shroud.
▶ Reinstall the PS jacket cover ( Fig. 2, page 5) on the DHW tank.