Buderus SB615, Logano plus SB615 Gas Installation And Maintenance Instructions Manual

For contractors
Read carefully prior to installation and maintenance.
Note:
This boiler must only be operated with natural gas or liquid propane (LP)!
Gas fired condensing boiler
Logano plus SB615 Gas
6 720 640 266 - 08/2009 GB/IE
Contents
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
2
Contents
1 Explanation of symbols and safety instructions . . 3
1.1 Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Safety information . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Information about the appliance . . . . . . . . . . . . . . . 5
2.1 EU Declaration of Conformity . . . . . . . . . . . . . . . . 5
2.2 Correct use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Data plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Standard delivery . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.5 Tools, materials and auxiliary equipment . . . . . . . 5
2.6 Specifications, dimensions, connections . . . . . . . 6
3 Regulations, standards and guidelines . . . . . . . . . . 9
3.1 Low water indicator installation . . . . . . . . . . . . . . . 9
3.2 Standards and guidelines/directives . . . . . . . . . . . 9
3.3 Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.4 Safety limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.5 Boiler positioning . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.5.1 Foundation and recommended wall clearances 11
3.5.2 Levelling the boiler . . . . . . . . . . . . . . . . . . . . . . . . 12
3.6 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4 Transporting the boiler . . . . . . . . . . . . . . . . . . . . . . . 13
4.1 Means of transport . . . . . . . . . . . . . . . . . . . . . . . . 13
4.1.1 Transporting the boiler using a forklift truck . . . . 13
4.1.2 Transporting the boiler using two pallet trucks . 13
5 Installation of the boiler . . . . . . . . . . . . . . . . . . . . . . 14
5.1 Checking delivery for completeness . . . . . . . . . . 14
5.2 Disposing of packaging . . . . . . . . . . . . . . . . . . . . 14
5.3 Minimum clearances / product dimensions . . . . 14
5.4 Changing the hinging of the burner door . . . . . . 14
5.5 Installing the minimum pressure switch and
minimum pressure limiter . . . . . . . . . . . . . . . . . . 15
5.6 Low water indicator (accesory), fitting
(400 – 600kW) . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.7 Connecting the boiler to the pipework . . . . . . . . 16
5.7.1 Connecting the return to the boiler . . . . . . . . . . . 16
5.7.2 Connecting the flow to the boiler . . . . . . . . . . . . 16
5.7.3 Connecting the safety line flow . . . . . . . . . . . . . . 16
5.8 Filling the heating system and checking
connections for leaks . . . . . . . . . . . . . . . . . . . . . 17
5.9 Fitting the lagging . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.10 Fitting the connection plates . . . . . . . . . . . . . . . . 19
5.11 Fitting the side panels . . . . . . . . . . . . . . . . . . . . . 20
5.12 Routing the burner cable . . . . . . . . . . . . . . . . . . . 21
5.13 Fitting the back plate . . . . . . . . . . . . . . . . . . . . . . 22
5.14 Fitting the front boiler cover . . . . . . . . . . . . . . . . . 23
5.15 Fit and connect the control unit (accessory) . . . 23
5.16 Installing the temperature sensor set . . . . . . . . . 25
5.17 Fitting the boiler cover sections . . . . . . . . . . . . . 26
5.18 Fitting the front panel . . . . . . . . . . . . . . . . . . . . . . 27
5.19 Securing the shield, device label
and data plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.20 Connecting and filling the neutraliser
(accesory) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.21 Installing condensate pipework . . . . . . . . . . . . . 29
5.22 Connecting the flue side of the heating system 30
5.22.1 General information on flue systems . . . . . . . . . 30
5.22.2 Fitting the flue pipe sealing collar (accessory) . 30
5.22.3 Fitting the flue temperature sensor (accessory) 30
5.23 Fitting burner (accessory) and connecting gas
supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
5.23.1 Fitting the burner plate . . . . . . . . . . . . . . . . . . . . 31
5.23.2 Fitting the burner to the burner plate . . . . . . . . . 32
5.23.3 Connecting the gas supply . . . . . . . . . . . . . . . . . 33
6 Initial operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.1 Flushing the heating system . . . . . . . . . . . . . . . . 34
6.2 Filling the heating system . . . . . . . . . . . . . . . . . . 35
6.3 Preparing the heating system for operation . . . 36
6.4 Commissioning the control unit and the burner 36
6.5 Commissioning report . . . . . . . . . . . . . . . . . . . . . 37
7 Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.1 Shutting down the heating system . . . . . . . . . . 38
7.2 Shutting down the heating system in an
emergency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
8 Inspection/maintenance . . . . . . . . . . . . . . . . . . . . . . 39
8.1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
8.2 Preparing the boiler for inspection and
maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
8.3 Cleaning the boiler . . . . . . . . . . . . . . . . . . . . . . . 40
8.4 Cleaning the flue gas collector . . . . . . . . . . . . . 42
8.5 Checking the heating system water pressure . . 43
8.6 Inspection and maintenance reports . . . . . . . . . 44
1
Explanation of symbols and safety instructions
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
3
1 Explanation of symbols and safety instructions
1.1 Symbols
Signal words indicate the hazard risk level resulting from not following the instructions.
Caution indicates that minor damage to property could result.
Warning indicates that minor personal injury or serious material losses could result.
Danger indicates that serious personal injury could result. In particularly serious cases, lives could be at risk.
Notes contain important information in cases where there is no risk of personal injury or material losses.
1.2 Safety information
These installation and maintenance instructions contain important information for the safe and appropriate installation, commissioning and servicing of the Logano plus SB615 Gas condensing boiler.
These installation and maintenance instructions are designed for specialists, who, – through their vocational training and experience, – are knowledgeable in handling heating systems and gas installations.
Observe all standards and guidelines applicable to the installation and operation of this system in your country.
Only use original Buderus spare parts. Losses caused by the use of parts not supplied by Buderus are excluded from the Buderus warranty.
Risk to life from gas explosion
There is a risk of explosion if you can smell gas!
B No open flames. Do not smoke. Do not use lighters. B Prevent sparks. Do not operate electrical switches,
including telephones, plugs, door-bells, mobiles or other electrical devices.
B Close the main gas shut-off valve. B Open windows and doors. B Warn all occupants of the building, but do not ring
doorbells.
B Do call your gas supplier from outside the building. B If you hear gas escaping, immediately leave the
building, prevent others from entering and notify the police and fire brigade from outside the building.
Customer information:
B Only qualified personnel may carry out the installation,
the main fuel and flue gas connections, the initial start-up, electrical connections and any maintenance or repair work.
B Work on gas-carrying equipment is to be carried out by
a licensed company.
Risk to life from poisoning
An insufficient supply of air can result in the escape of dangerour flue gases!
B Prevent air inlet and outlet vents from becoming
blocked or restricted.
B Do not operate the boiler until any ventilation defects
have been rectified.
B Inform the system user in writing of the fault and its
associated dangers.
Safety information in the text is framed and marked with a warning triangle on a grey background.
Notes are identified by the symbol shown on the left. They are bordered by horizontal lines above and below the text.
1
Explanation of symbols and safety instructions
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
4
Risk of injury from electric shock
B Isolate the heating system from the mains electricity
supply before starting work. Use either an emergency isolation switch or the relevant circuit breaker. A contact separation of at least 3mm must be achieved across EACH pole.
B Prevent unintentional reconnection of the electricty
supply.
Risk of fire from flammable materials or liquids
B Never store flammable materials or liquids in the
immediate vicinity of the boiler.
Laws and regulations
B The appliance must be installed in accordance with
and comply to, the current: Statutory Instrument Laws, Gas Safety Regulations, IEE Regulations, Building Regulations, Local Water By-Laws, Health & Safety document 635 (The Electricity at Work Regulations) and any other local requirements. Observe all European and local installation standards, building regulations and the latest edition of the wiring regulations. Chemically aggressive substances, can corrode the appliance and invalidate any warranty.
Preventative maintenance
B Carry out annual maintenance and cleaning
procedures. In the course of this work, check the entire heating system (including neutralisation device) for correct function.
B Have faults corrected as quickly as possible in order to
prevent system damage and to help protect your heating system.
Frost protection
The heating system may freeze in cold weather if the control unit is not turned on.
B Protect your heating system against frost when
temperatures below zero are expected. If for some reason the control unit is to be switched off, drain the system water from the boiler, DHW cylinder and all heating system pipework.
System damage and personal injury due to operator errors
Operator errors can result in injury and damage to property.
B Ensure that children never operate this appliance
unsupervised or play with it.
B Ensure that only personnel who can operate this
appliance correctly have access to it.
Instructing the customer
B Hand these installation and maintenance instructions
to your customer when handing over the system. Request that these instructions are kept in a safe location next to the boiler.
B Explain to the customer how the appliance works and
how to operate it.
2
Information about the appliance
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
5
2 Information about the appliance
2.1 EU Declaration of Conformity
The design and operation of this product conform to European Directives and the supplementary national requirements. Its conformity is demonstrated by the CE designation.
You can view the Declaration of Conformity on the internet at www.buderus.de/konfo or request a copy from your local Buderus sales office.
2.2 Correct use
The Logano plus SB615 Gas condensing boiler has been designed for wet heating systems in e.g. multiple dwelling units or in industrial applications. Any gas burner type-tested to EN 676 can be used if its operating range matches the boiler specifications.
2.3 Data plate
2.4 Standard delivery
B Upon delivery, check all packaging for damage. B Check the delivered package(s) for completeness.
• Boiler mounted on pallet
• Connection pipe for low water indicator, connected to the boiler body (for boiler size 400 kW)
• Technical documents, attached to boiler block
• Siphon in the combustion chamber
• Boiler casing with thermal insulation and accessory bag, packed in the wooden crate
• Control unit with wiring diagram and operating instructions for electronic boiler and heating circuit control, packed in carton (accessories ordered separately).
• Neutralisation device, packed in individual carton (accessory ordered separately)
It is possible that some of the standard accessories will not be necessary for certain boiler types.
2.5 Tools, materials and auxiliary
equipment
For the installation and maintenance of the boiler, you require standard tools, as used in space heating as well as gas and water installations.
The information on the type plate is binding and must be observed!
2
Information about the appliance
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
6
2.6 Specifications, dimensions, connections
The specification provides information on the output profile of the Logano plus SB615 gas condensing boiler.
Fig. 1 Specifications, dimensions, connections
ØAAFlue pipe internal diamater A Clearance AKO Condensate outlet B Boiler width incl. casing B
GR
Base frame
DAAGas outlet EL Cold water inlet/drain H Boiler height including control unit, e.g. Logamatic
4311/12 control unit, = H + 235 mm
H
AA
Flue outlet height
HELDrain HKBoiler height excl. control unit L Boiler length incl. casing L
BR
Burner length
LKBoiler block length RK1 Boiler return 1 RK2 Boiler return 2 VK Boiler flow VSL Flow safety line 1 Side-mounted control unit holder (left/right) 2 Spigot for low water indicator for boiler sizes 400 kW and
above
3 Minimum pressure monitor for boiler size 145 – 240 kW
or minimum pressure limiter for boiler size 310 kW as accessory
2
Information about the appliance
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
7
Specifications for Logano plus SB615 Gas
Boiler size Unit 145 185 2301)/240 310 400 510 640
Length
L mm 1816 1816 1845 1845 1845 1980 1980 L
K
mm 1746 1746 1774 1774 1774 1912 1912
Burner length
L
BR
- Logatop VM mm 376 376 376 376
L
BR
- WG mm 500 500 500 500 577 868 868
L
BR
- BS/M mm 280 301
L
BR
- RS/M mm 580 580 580 580 840
L
BR
- RS/M BLU mm 840
Width
B mm 900 900 970 970 970 1100 1100
Height
H mm 1606 1606 1638 1638 1842 2000 2000 H
K
mm 1376 1376 1408 1408 1612 1770 1770 Width/height/ for transport mm 720/1340 720/1340 790/1370 790/1370 790/1570 920/1730 920/1730 Length mm 1735 1735 1760 1760 1760 1895 1895 Base frame B
GR
mm 720 720 790 790 790 920 920 Clearance A mm 285 285 285 285 285 367 367
Flue outlet
ØD
AA
inside DN 183 183 203 203 253 303 303
H
AA
mm 300 300 305 305 333 370 370
Combustion chamber
Length mm 1460 1460 1460 1460 1460 1594 1594 Ø mm 453 453 453 453 550 650 650
Burner door
Depth mm 185 185 185 185 185 185 185 H
B
mm 985 985 1017 1017 1135 1275 1275
Boiler flow
2)
ØVK DN656580 80100100100 H
VK
mm 1239 1239 1260 1260 1442 1613 1613
Boiler return 1
2)
Ø RK1 DN 65 65 80 80 100 100 100 H
RK1
mm 142 142 142 142 150 150 150
A
1
mm 275 275 300 300 290 284 284
Boiler return 2
2)
ØRK2 DN R 1½ R 1½ R 1½ 65 65 80 80 H
RK2
mm 495 495 512 512 597 685 685
A
2
mm 295 295 310 310 315 360 360
Flow, safety line
3)
Ø VSL DN R 1¼ R 1¼ 32 32 50 50 50 H
VSL
mm 1180 1180 1213 1213 1327 1549 1549
A
3
mm 160 160 170 170 210 195 195
Condensate outlet
H
AKO
mm 164 164 164 164 164 160 160
A
4
mm 100 100 120 120 140 155 155 Drain H
EL
mm 85 85 82 82 90 138 138 Logatop gas connection VM DN 2
Combustion heat output
of kW 54.3 69.3 89.8 116.0 149.5 191.6 239.9
up to kW 135.8 173.2 224.4 289.9 373.8 478.9 599.8
Logatop VM
Partial load
35% kW
47.5 60.6 75.3 101.5 – – –
Full load
kW
135.8 173.2 215 289.9
CO2 content % 10
Weight
net kg 613 620 685 705 953 1058 1079 With burner kg 648/643
1)
655/6501)720/7151)753/7351)1001 1156 1177 Water capacity l 560 555 675 645 680 865 845 Gas capacity l 327 333 347 376 541 735 750 Free draught Pa 501)/boiler-dependent4). Hot gas resistance mbar 1.20 1.55 2.20 2.40 3.00 3.55 4.40 Permissible flow temperature
5)
°C 120 Permissible operating pressure bar 4 4 5 5 5.5 5.5 5.5 CE mark, boiler CE-0085 AT 0075
Tab. 1 Specification
2
Information about the appliance
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
8
System temperatures 50/30 °C
Rated output
Full load kW 145 185 240 310 400 510 640 Partial load kW 59.2 75.6 97.8 126.3 162.4 208.8 261.5 Logatop VM Full load kW 145 185 230 310 – Partial load kW 51.8 66.1 82.1 110.6
Flue gas temperature
6)
Full load °C 40 40 46 46 42 44 44 Partial load °C 33 33 35 34 37 35 32
Flue gas mass flow rate
Full load kg/s 0.0552 0.0704 0.0928 0.1200 0.1528 0.1969 0.2466 Partial load kg/s 0.0217 0.0277 0.0360 0.0465 0.0603 0.0770 0.0958 Logatop VM Full load kg/s 0.0633 0.0808 0.1010 0.1350 – Partial load kg/s 0.0220 0.0283 0.0352 0.0474
System temperatures 80/60 °C
Rated output
Full load kW 132.7 169.2 218.9 282.8 365.2 467.9 585.4 Logatop VM Full load kW 132.7 169.2 210.7 282.8 – Partial load kW 50.6 64.5 80.2 108.1
Flue gas temp.
6)
Full load °C 66 66 71 71 68 69 71 Partial load °C 45 45 45 44 45 44 44
Flue gas mass flow rate
Full load kg/s 0.0579 0.0738 0.0956 0.1235 0.1592 0.2040 0.2555 Partial load kg/s 0.0231 0.0295 0.0383 0.0494 0.0637 0.0816 0.1022 Logatop VM Full load kg/s 0.0633 0.0808 0.1010 0.1350 – Partial load kg/s 0.0220 0.283 0.0352 0.0474
1) In conjunction with Logatop VM.
2) According to EN 1092-1 PN6
3) According to EN 1092-1 PN16
4) With Logano plus SB615 with third party burner
5) Safety limit (High limit safety cut-out). Max. possible flow temperature = safety limit (STB) – 18K. Example: Safety limit (STB): 100 °C, max. possible flow temperature = 100 - 18 = 82 °C
6) To DIN EN 303. Minimum flue gas temperatures for chimney design calculations in accordance with EN 13394-1 Æ Technical Guide "Boiler characteristic values for the dimensioning of flue gas systems".
Specifications for Logano plus SB615 Gas
Boiler size Unit 145 185 2301)/240 310 400 510 640
Tab. 1 Specification
3
Regulations, standards and guidelines
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
9
3 Regulations, standards and guidelines
During installation and operation of the system, standard engineering practices, the buildings regulations and any legislative requirements must be observed.
3.1 Low water indicator installation
B For boilers > 300 kW, install a low water indicator,
following the manufacturer's technical documents for installation and operation.
B If the LWI connection provided is not used for the
installation of an SYR 932.1 low water indicator (Buderus accessory), seal the connection off with a plug (Æ Chapter 5.6, page 15).
The Logamatic control system is used for this boiler.
3.2 Standards and guidelines/directives
This device meets all basic requirements of relevant European standards and guidelines:
• 90/396/EC Gas Appliance Directive
• EN 677, EN 303-1, EN 303-3, DIN 4702-6, EN 267,
EN 303-2
• 92/42/EC Efficiency Directive
• 2006/95/EC Low voltage Directive
• 2004/108/EC Electro Magnetic Compatibility
Directive
• 97/23/EC Pressure equipment Directive
Standard: TRD 702
Observe the following during installation and operation:
• Local Building Regulations concerning boiler room
installations
• Local Building Regulations regarding air supply and
extraction equipment as well as connection to a flue
• Latest edition of the IEE Wiring regulations governing electrical connection to the mains power supply
• The technical rules of the gas supply utility regarding the connection of the gas burner to the local mains gas supply
• Regulations and standards regarding the safety equipment in water-filled heating systems
• Installation instructions for heating engineers
• In Belgium, the standards NBN D 30-003, NBN D 51-004 and addenda must be observed.
• In the Netherlands, technical rules, building regulations and other legal requirements (e.g. NEN 1078 (GAVO), NEN 3028 and NEN 1010) must be observed when installing and operating the system.
• In Austria, observe local building regulations as well as ÖVGW Directive G1 or G2 (ÖVGW-TR gas or LPG) during installation. The requirements of the national directive Article 15a B-VG, regarding emissions and efficiency, are fulfilled.
•For Switzerland: By carrying out measurements at the installation location, it must be checked whether the LRV maximum permitted limits concerning CO and NOx are being observed. The boilers have been tested according to VKF fire safety regulations. During installation, observe the guidelines for installing and operating gas-fired boilers G3 d/f, the gas guidelines G1 SVGW, and local fire safety regulations in force within the canton. The output figures shown in the tab. "Specifications" are nominal output figures. In practice, these values will sometimes not be reached within the specified output range in order to adhere to LRV regulations.
Permissible fuels
Logano SB615 Gas and Logano plus SB615 VM gas condensing boilers can be operated using the following fuels:
• Natural gas and liquid propane (LP) according to DVGW (German certification body) worksheet G 260
• Natural gas and liquid propane (LP) supplied by public gas utility (Austria, Switzerland)
B Only use burners that are compatible with these gas
types.
B Observe the specifications of the burner supplier.
Observe all standards and guidelines applicable to the installation and operation of this system in your country! The details on the boiler rating plate are definitive and must be observed.
For UK & Ireland: B For boilers > 300 kW, install a low water
indicator as required by BS-EN 12828.
B For installation and operation, refer to the
technical documents provided by the manufacturer.
For Poland: B For boilers > 100 kW, equip the boiler
with a low water indicator as required by PN-91/B-2414 (p2.5).
3
Regulations, standards and guidelines
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
10
3.3 Leaks
B Carrying out the leak test.
The testing pressure is based on the normal operating pressure of the heating system and should be 1.3 times that pressure, and in any case no less than 1 bar.
3.4 Safety limits
Safety limits
Maximum flow temperature 120 °C
1)
1) For Germany. Always follow the national standards and regulations of the country where the appliance is installed.
Permissible operating pres­sure
145 – 185 kW 4bar
210 – 310 kW 5 bar
400 – 640 kW 5.5 bar
Maximum time constant on:
High limit safety cut-out 40 s
Control thermostat 40 s
Tab. 2 Safety limits
3
Regulations, standards and guidelines
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
11
3.5 Boiler positioning
This chapter explains how to properly position the boiler.
3.5.1 Foundation and recommended wall
clearances
B When providing foundations or a support area, observe
the specified minimum wall clearances (values in brackets) (Æ Fig. 2 and Tab. 4) so that the installation and maintenance instructions can be followed without difficulty. The front edge of the boiler should be flush with the edge of the plinth.
It is useful if there is a drain outlet near the installation location.
Fig. 2 Boiler room (for dimensions see Tab. 4),
dimensions in mm
1)
In addition to the burner length
3)
take dimension A2 into
consideration when installing a third party burner.
2)
When using a side-mounted control unit holder.
3)
Take account of burner dimensions.
CAUTION: System damage due to frost! B Install the heating system in a room
protected from the risk of frost.
The support area must be flat and able to support the applied weight, with a slight incline to the rear to ensure ventilation of the boiler.
Make sure there is additional space for noise silencing.
Recommended (and minimum) wall clearances mm
Boiler
size kW
Clear-
ance
Clear-
ance
Length Width
Width/
Height
A
1
A
2
1)
1) For boiler installations with third party burners, dimension A2
also depends on the burner length
3)
.
L B Transport
145 760
(460)
1700 (1200)
1816 900 720/1340
185 760
(460)
1700 (1200)
1816 900 720/1340
240 800
(500)
1700 (1200)
1845 970 790/1370
310 800
(500)
1700 (1200)
1845 970 790/1370
400 900
(1600)
1750 (1250)
1845 970 790/1570
510 1000
(700)
2000 (1500)
1980 1100 920/1730
640 1000
(700)
2000 (1500)
1980 1100 920/1730
Tab. 3 Wall clearances
3
Regulations, standards and guidelines
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
12
Allow extra space if a flue silencer is to be installed.
If you wish to fix the control unit to the side of the boiler using the holder (accessory), you have to ensure additional clearance (Æ Fig. 2, page 11).
3.5.2 Levelling the boiler
B Level the boiler towards the back using a spirit level to
prevent air pockets forming inside the boiler.
Fig. 3 Level the boiler backwards
(for legend, see Fig. 1, page 6)
3.6 Disposal
Use metal shims to level the boiler.
Please note the following: B Dispose of packaging in an
environmentally responsible manner.
B Dispose of all heating system components
that have to be replaced at an authorised disposal site.
4
Transporting the boiler
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
13
4 Transporting the boiler
This chapter describes how to handle the boiler safely without risk of damage.
B When raising and transporting the boiler, make sure
that the weight is distributed evenly across the forks of the forklift truck/pallet truck.
4.1 Means of transport
4.1.1 Transporting the boiler using a forklift truck
B Insert the forks of the forklift truck under the front and
the back of the boiler.
4.1.2 Transporting the boiler using two pallet
trucks
B Slide a pallet truck under the front and the back of the
boiler.
B Raise the boiler evenly using the two pallet trucks.
DANGER: Risk to life from incorrectly secured boiler!
B Use suitable equipment when
transporting the boiler, e.g. two pallet trucks or a forklift truck.
B When transporting, secure the boiler to
the method of transport to prevent it slipping.
CAUTION: System damage due to damaged boiler body!
B The boiler may only be transported with a
forklift truck if the forks are long enough to extend from the front of the boiler to the back.
B Prior to lifting the boiler body, check
whether the boiler front and back panels are positioned on the fork of the forklift truck.
5
Installation of the boiler
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
14
5 Installation of the boiler
This chapter explains how to correctly install the boiler.
5.1 Checking delivery for completeness
B Upon delivery, check all packaging for damage. B Check the delivered package(s) for completeness
(Æ Chapter 2.4).
5.2 Disposing of packaging
B Dispose of packaging in an environmentally
responsible manner.
5.3 Minimum clearances / product
dimensions
5.4 Changing the hinging of the burner
door
The burner door can be moved from the right-hand side (factory-set) to the left-hand side.
B Push the hinge bolts out of the hinges from underneath
[1].
B Refit the washer [2] and the two hinge pins to the
adjacent hinges. Make sure that the washer is re-installed.
Fig. 4 Reversing the door hinges
1 Hinge pin 2 Washer
CAUTION: System damage due to open
combustion chamber! The combustion chamber must remain
sealed by the burner door so that the stainless steel combustion chamber is not damaged by any welding or grinding work.
B Ensure when fitting the front thermal
insulation pad that the combustion chamber remains sealed by the burner door.
Observe the recommended minimum wall clearances when positioning (Æ Tab. 3, page 11).
DANGER: Risk of injury from unsupported door!
B Change the door hinging only when the
door is closed and bolted.
5
Installation of the boiler
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
15
5.5 Installing the minimum pressure
switch and minimum pressure limiter
B Connect the minimum pressure monitor or minimum
pressure limiter (with R½ to R¼ connection piece adapter) to the MDW/MDB connection on the boiler (Æ Fig 5).
Fig. 5 Logano plus SB615 Gas boiler connections
5.6 Low water indicator (accesory),
fitting (400 – 600 kW)
B Seal the flow pipe for the low water indicator into the
2" LWI connection on the boiler (Æ Fig. 5).
B Fit the low water indicator onto the low water indicator
tube.
B If the LWI connection is not being used for the
installation of a low water indicator, remove the plastic plug and close off the LWI connection with a blanking plug.
Note that a minimum pressure monitor must be connected for 145 kW to 240 kW! For 310 kW (145 kW and higher in Poland) a minimum pressure limiter (MDB) must be installed. This requires an R½ to connection piece adapter R¼ .
For Germany B For boilers > 300 kW, install a low water
indicator or minimum pressure limiter as required by DIN-EN 12 828.
B For installation and operation, refer to the
technical documents provided by the manufacturer.
For Poland B For boilers > 100 kW, equip the boiler
with a low water indicator as required by PN-91/B-2414 (p2.5).
Loading...
+ 33 hidden pages