Buderus MCM10 Installation Instructions Manual

For heating contractors Pour le professionel
Please read carefully before installing and servicing A lire attentivement avant le montage et l’entretien
MCM10
en-us Installation Instructions 2
fr Notice d´installation 20
6 720 616 690 (08/2009)
Table of contents
MCM10
2
Table of contents
1 Explanation of symbols and safety instructions 3
1.1 Symbols, explanation of 3
1.2 Safety instructions 3
2 Details about the MCM10 module 4
2.1 Declaration of conformity 4
2.2 Information regarding the documentation 4
2.3 Proper use 4
2.4 Scope of delivery 4
2.5 Accessories 4
2.6 Technical specifications 5
2.6.1 General 5
2.6.2 Dimensions 5
2.6.3 Power connection parameters 5
2.6.4 Measurement values supply temperature sensor 5
2.6.5 Measurement values outdoor temperature sensor 5
2.7 System integration of the MCM10 6
2.7.1 Principles of cascade control 6
2.7.2 Heating controls for MCM10 cascade systems 6
2.7.3 Water heating with MCM10 cascade systems 6
2.7.4 Internal frost protection function 6
2.7.5 Control of one heating pump 7
2.7.6 External switching contact 7
2.7.7 System versions overview 7
2.7.8 Connection of additional modules in case of heating system controls with 2-wire BUS control 9
3 Installation 10
3.1 Installation 10
3.1.1 Wall mounting 10
3.2 Making the electrical connections 11
3.2.1 Connection of the low voltage part with BUS connections 11
3.2.2 120 V AC connection 11
3.2.3 Connection of a remote fault indication with optical and acoustic signal 12
3.2.4 Electrical connection of the outdoor temperature sensor 12
3.2.5 Electrical connection of the supply temperature sensor 12
3.2.6 Electrical connection of the external switching contact 12
3.2.7 Disposal 12
3.3 Installing other accessories 12
4 Start-up and shut-down 13
4.1 Configuration 13
4.2 Commissioning 13
4.3 Configuration reset 13
4.4 Shutting down 13
5 Operating and fault indications 14
5.1 Operating and fault indications via the heating appliance displays 14
5.2 Fault message via the remote fault indication 14
5.3 Operating and fault indications via LED 14
5.4 Operating and fault indications via the RC35 16
5.5 Replacing the fuse for the heating zone pump connection 17
6 Environmental protection 18
7Appendix 19
1
Explanation of symbols and safety information
MCM10
3
1 Explanation of symbols and safety information
1.1 Explanation of symbols
Warning symbols
Signal words indicate the seriousness of the hazard in terms of the consequences of not following the safety instructions.
NOTICE indicates possible damage to property or
equipment, but where there is no risk of injury.
CAUTION indicates possible injury.
WARNING indicates possible severe injury.
DANGER indicates possible risk to life.
Important information
Additional symbols
1.2 Safety precautions
B To ensure proper function, follow these instructions. B Install and start up the heating appliance and all
accessories according to the associated instructions.
B Use this accessory exclusively in conjunction with the
controllers and heating appliances listed. Follow the connection diagram!
B This accessory has inputs and outputs with different
voltages. Never connect the low voltage side to the 120 V power supply or vice-versa.
B In case of wall installation: never install this accessory
in wet areas.
B Work on electrical components only if you have the
required training and qualification.
B Before you start working on the system, disconnect the
heating system from electrical power by shutting off the emergency shut-off switch or the heating system circuit breaker.
B Secure against unintentional reconnection. B It is not sufficient to simply shut off the controls. B Observe all applicable electrical codes and
regulations.
Safety instructions in this document are framed and identified by a warning triangle which is printed on a grey background.
Electrical hazards are identified by a lightning symbol surrounded by a warning triangle.
Notes contain important information in cases where there is no risk of personal injury or material losses and are identified by the symbol shown on the left. They are bordered by horizontal lines above and below the text.
Symbol Meaning
B a step in an action sequence
Æ a reference to a related part in the docu-
ment or to other related documents
•a list entry – a list entry (second level)
2
Details about the MCM10 module
MCM10
4
2 Details about the MCM10 module
2.1 Declaration of conformity
2.2 Information regarding the documentation
We reserve the right to make technical modifications!
2.3 Proper use
The MCM10 modules are designed to control cascade systems. A cascade system is a heating system where several smaller heating appliances are connected in parallel to achieve a higher output (Æ Fig. 12, page 19).
The MCM10 modules are only suitable for controlling heating appliances with Logamatic EMS BUS.
For floor-standing heaters, the MCM10 module is only suitable for the activation of gas heaters with modulating burners without operating conditions.
2.4 Scope of delivery
Fig. 1 Scope of delivery
1 MCM10 2 Duct connection box 3 Sensor well 4 Supply temperature sensor FV 5 Package with:
- 3 screws and 3 wall-plugs
- 4 strain relief clips and 8 screws
6 Installation and operating instructions
B Check that the delivery is complete.
2.5 Accessories
Here is a list with typical accessories. In order to get a complete overview of all available accessories, please contact the manufacturer.
• Outdoor temperature sensor FA for connection to terminal F (only for system variant 1).
RC35: Outdoor reset heating system controls with plaintext display for controlling a heating system with mixed or unmixed heating zones.
WM10: Low loss header module for EMS.
MM10: Mixer module for EMS.
AM10: Outdoor reset controller with thermostat connection.
The design and operation of this product conform to the U.S. and Canadian Directives. Its conformity is demonstrated by the CSA designation.
The Declaration of conformity can be claimed. See the address at the back of this manual.
Hand all enclosed documents over to the user.
6 720 616 690-02.1TD
1
2
4
3
6
5
2
Details about the MCM10 module
MCM10
5
2.6 Technical specifications
2.6.1 General
2.6.2 Dimensions
Fig. 2 Dimensions
2.6.3 Power connection parameters
2.6.4 Measurement values supply temperature
sensor
2.6.5 Measurement values outdoor temperature
sensor
Designation Unit
Dimensions (Æ Fig. 2) Weight (without packaging) lb (kg) 1.76 (0.8) Rated voltage MCM10 AC … V 120 Frequency Hz 60 Max. on-site fuse protection of the input voltage
Amp 10
Power draw MCM10 W 5 Rated voltage BUS DC … V 15 Internal appliance fuse, heating pump output
Amp 5 AF, ceramic, filled
with sand Measuring range, supply temperature sensor
° F ( °C) 32 … 212
(0 … 100) Measuring range, outside temperature sensor
° F ( °C) – 40 … 122
( – 40 … 50) Permissible ambient temperature MCM10
° F ( °C) 32 … 122
(0 … 50) Permissible ambient temperature, supply temperature sensor
° F ( °C) 32 … 212
(0 … 100) Permissible ambient temperature outdoor temperature sensor
° F ( °C) – 58 … 212
( – 50 … 100) Maximum cable length, 2-wire BUS connections
ft (m) (ÆTab. 6, page 11)
Maximum lead lengths, sensor leads
ft (m) (ÆTab. 7, page 11)
EMC suppression level to IEC 60730 Enclosure rating II in accordance
with IEC 60730
NEMA definition Type 2
Tab. 1 General
2-1/2" (62mm)
6 720 616 690-03.1TD
2-1/2" (62mm)
9-1/4" (235mm)
2-1/4" (58mm)
1-1/2" (37mm)
5-9/16" (142mm)
6-1/2" (165mm)
Pos.
1)
1) (Æ Fig. 12, page 19)
Interface
A Input Power supply from the power
line or from the previous mod­ule MCM10
120 V AC, max. 10 Amp.
B Output Power supply for additional
MCM10
120 V AC, max. 10 Amp.
C Output Pump 120 V AC,
max. 250 W
D Output Remote fault indication zero volt,
max. 120 V, 2Amp.
E Input Supply temperature sensor NTC (ÆTab. 3) F Input Outdoor temperature sensor NTC (ÆTab. 4) G Input External switching contact Zero volt H Input Heating controls
(ON/OFF contact)
24 V DC
I Input Heating controls (propor-
tional interface)
0-10 V DC
J 2-wire BUS to the heating controller
(RC35, WM10, MM10)
K 2-wire BUS from the previous MCM10
module
L 2-wire BUS to the next MCM10 module
M 2-wire BUS to the heating appliance
Tab. 2 Power connection parameters
°F ( °C) Ω °F ( °C) Ω
68 (20) 12490 140 (60) 2488 77 (25) 10000 149 (65) 2083 86 (30) 8057 158 (70) 1752
95 (35) 6531 167 (75) 1481 104 (40) 5327 176 (80) 1258 113 (45) 4369 185 (85) 1072 122 (50) 3603 194 (90) 917 131 (55) 2986 203 (95) 788
Tab. 3 Measurement values supply temperature sensor
°F ( °C) Ω °F ( °C) Ω
– 4 ( – 20) 97070 50 (10) 19900
5 ( – 15) 72929 59 (15) 15708
14 ( – 10) 55330 68 (20) 12490
23 ( – 5) 42315 77 (25) 10000
32 (0) 32650 86 (30) 8057 41 (5) 25388 95 (35) 6531
Tab. 4 Measurement values outdoor temperature
sensor
2
Details about the MCM10 module
MCM10
6
2.7 System integration of the MCM10
2.7.1 Principles of cascade control
When the heating appliance generates a heat demand (Æ Tab. 5, system versions 1, 2, 3, and 4), initially one heating appliance is started and, if required, its heat output is raised to its maximum nominal power. Only then will another heating appliance be started.
If excessive heat is being generated, heating appliances are controlled one after another in sequence without delay down to their respective minimum nominal power, and then shut down until heat demand and generation match. With system version 4 all appliances are shut down simultaneously.
The MCM10 module automatically determines the sequence in which the heating appliances are controlled. The MCM10 module safeguards an even distribution of the burner hours of operation for all heating appliances. This takes into account heating and DHW. This increases the heating appliance service life. If the power supply to the MCM10 module is interrupted, the hours run meters in the MCM10 module are reset to zero.
As soon as a heating appliance is not able to start (DHW heating for a directly-connected hot water tank, heating appliance fault, communication fault with MCM10 module), another heating appliance will be started automatically to cover the heat demand.
2.7.2 Heating controls for MCM10 cascade systems
The MCM10 modules stage the heating appliances based on the heat demand calculated. For control according to the heat demand, the MCM10 modules always require heating system controls (Æ Fig. 12, terminals H, I or J, page 19). Depending on the heating system controls, there are four possible system versions (ÆTab. 5).
One MCM10 module can control up to four heating appliances. By connecting up to four MCM10 modules, up to 16 heating appliances can be linked to form a single cascade (Æ Fig. 12, page 19). In this case, one MCM10 module controls the cascade (MCM10 master).
Depending on the heating system controls used, a cascade system with up to 4 or up to 16 heating appliances can be created. The maximum number of heating appliances that can be connected and the number of MCM10 modules required for the different systems are shown in Tab. 5, page 8.
The MCM10 module controls the entire boiler loop (primary loop including the low loss header). All other heating system components (secondary side of the low loss header, such as the heating zones, hot water tank) can be regulated by a weather-dependent heating controller with a 2-wire BUS interface and additional modules (WM10, MM10...). Contact the manufacturer for further details. You will find the relevant address on the back cover.
Heating appliances of any output can be part of a cascade.
2.7.3 Water heating with MCM10 cascade systems
Hot water tanks can be connected hydraulically and electrically directly to a heating appliance (storage tank model).
• Water heating is controlled by the heating appliance.
During a DHW demand, this heating appliance will not be called by the MCM10 module. In case of demand, another heating appliance may be started.
• If water heating is timed using a heating system control
with 2-wire BUS connection, the heating appliance with the storage tank must be connected to the MCM10 module (master) via terminals 17 and 18.
2.7.4 Internal frost protection function
The MCM10 module is equipped with an internal frost protection function: if the supply temperature falls below 45 °F ( 7 °C ), a heating appliance starts and runs until a supply temperature of 60 °F (15 °C) has been achieved. Any heating pump that is connected to the MCM10 module will also run (Æ paragrahp 2.7.5).
B Connect the supply temperature sensor to the MCM10
master module if the internal frost protection function is required.
Note that, for the correct function, only one heating system control/building management system may be connected.
The different system versions require the connection of certain accessories (supply temperature sensors, outdoor temperature sensors, heating pumps, and heating system controls) (Æ Tab. 5, page 8).
If the user wants to prepare hot water using the 3-way valve of the heating appliance and he wants to continue supplying the heating zone, he must switch off the warm water priority on the RC35 for all heating zones since with the factory settings, hot water priority is active by default.
The frost protection function of heating system controls with 2-BUS interface provides comprehensive system frost protection. This requires the connection of an outdoor temperature sensor.
2
Details about the MCM10 module
MCM10
7
2.7.5 Control of one heating pump
In heating systems with only one heating zone, the heating pump can be connected directly to the MCM10 module (master).
The heating pump runs:
• as long as at least one heating appliance pump is running (if required, set the pump run-on time on the heating appliance accordingly Æ heating appliance installation instructions); or
• briefly after remaining idle for 24 hours (anti-seizing protection).
2.7.6 External switching contact
The MCM10 module is equipped with an external switching contact (Æ Fig. 12, pos. G). For the characteristics of this switch, see Æ Tab. 2, page 5.
This external switching contact can be used optionally, e.g. to connect a temperature switch for protecting the radiant floor heating against a too-high water temperature.
If the switching contact is opened, all heating appliances are switched off via the MCM10 module. As soon as the switching contact is closed again, the heating appliances are ready for operation again.
2.7.7 System versions overview
As a manufacturer of advanced heating technology, we give high priority to the development and manufacture of economical and clean-burning heating appliances. To guarantee this, our heating appliances are equipped with modulating burners. To make optimum use of the burner characteristics, heating system controls with 2-wire BUS control should be used.
The anti-seizing pump protection lets the heating pump run at least once every day even without a heat demand (e.g. during summer).
B Leave your heating system switched on all
year to prevent the pump (in summer) from seizing up.
2
Details about the MCM10 module
MCM10
8
System version 1: Modulating weather­compensated heating controller (RC35)
An advantage of this system is the ability of the modules to communicate, enabling all heating zones to be controlled (function module WM10 or MM10) with the MCM10 module via a common BUS, parallel to terminal J on the MCM10 module (Æ Fig. 12, page 19). This ensures matching generated heat amount to the actual heat demand of all heating zones in the system. With this version, the heating system achieves optimum comfort with maximum energy savings.
System version 2: Modulating weather­compensated heating controller (AM10)
The supply target temperature of the AM10 module depends on the outdoor temperature. In contrast to system version 1, it is not possible to use the WM10 and MM10 modules.
System version 3: Modulating 0 - 10 V controller, regulated acc. to output
In conjunction with a building management system with 0 - 10 V interface, the total output of the cascade can be selected as control variable. Setting is achieved via a jumper (Æ Fig. 3).
System version
Symbol forcontroller
connection
Heating controller to MCM10 master module
Type
Max. number MCM10
Max. number of heating
applianceswith BUS-enabled
Logamatic EMS
Required accessories with connection to MCM10 (Æ Fig. 12, page 19)
1 Modulating weather-compensated
controller 2-wire BUS control
RC35 4 16 • Outdoor temperature sensor.
• One WM10 module. The WM10 module is delivered with a supply temperature sensor (see explanation on the following page).
• Heating pump (secondary zone) is connected to the WM10 module.
2 Modulating weather-compensated
controller 2-wire BUS control
AM10 weather­compen­sated con­troller
4 16 • Connect outdoor temperature sensor to AM10.
• Common supply temperature sensor on terminal E (only for internal frost protection).
• Heating pump (secondary zone) (Æ Fig. 12, [19]) on termi­nal C, only in case of one or several heating zones without heating pump or in case of heating zones that do not com­municate via BUS modules with the MCM10module.
3 Modulating
0 - 10 V controller,e.g. building man­agement system; control of the heat output
Any 4 16 • Common supply temperature sensor on terminal E (only for
internal frost protection).
• Heating pump (secondary zone) (Æ Fig. 12, [19]) on terminal C, only with one or several heating zones without heating pump or with heating zones that are not regulated via the building management system.
4 Modulating
0 - 10 V controller, e.g. building man­agement system; supply temperature control
Any 4 16 • Common supply temperature sensor on terminal E
• Heating pump (secondary zone) (Æ Fig. 12, [19]) on terminal C, only with one or several heating zones without heating pump or with heating zones that are not regulated via the building management system.
5 ON/OFF controller (zero volt) Any 4 16 • Common supply temperature sensor on terminal E (only for
internal frost protection).
• Heating pump (secondary zone) (Æ Fig. 12, [19]) on terminal C.
Tab. 5 System versions overview
0 ... 10V
0 ... 10V
2
Details about the MCM10 module
MCM10
9
Fig. 3 Setting via jumper
Fig. 4 Correlation between the input voltage and heat
output
U Input voltage P Output in % of the rated cascade output
System version 4: Modulating 0 - 10 V controller, regulated to supply temperature
In conjunction with a building management system with 0 - 10 V interface, the supply temperature can be selected as control variable. Setting is achieved via a jumper (Æ Fig. 3).
Fig. 5 Correlation between the input voltage and the
supply temperature
U Input voltage VT Supply temperature
System version 5: Heating control with ON/OFF contact
In conjunction with a control unit with ON/OFF contact, module MCM10 regulates the cascade output in accordance with the contact closure respectively up to maximum output, by starting one appliance after another. When the contact is opened, all heating appliances are shut down simultaneously.
The ON/OFF contact of the heating system controls must be a dry contact.
2.7.8 Connection of additional modules in case of heating system controls with 2-wire BUS control
Any additional modules, such as the WM10 and MM10 modules (Æ Fig. 12, [21], page 19), must be connected to the BUS of the heating controller (parallel to terminal J on the MCM10 module).
6 720 617 648-001.1TD
VT [˚F]
P [%]
0246810
6 720 617 648-09.1TD
0
30
50
70
90
U [V DC]
P [%]
194 (90)
167 (75)
140 (60)
113 (45)
86 (30)
59 (15)
0
0246810
6 720 617 648-10.1TD
U [V DC]
[˚F (˚C)] VT
3
Installation
MCM10
10
3 Installation
3.1 Installation
3.1.1 Wall mounting
B Determine the location on the wall in accordance with
the dimensions of the MCM10 module.
B Determine whether the main power cord is laid in stiff
or flexible ducts that require duct connection box and appropriate free space under the MCM10.
B Undo two screws at the bottom of the MCM10 module,
pull the cover at the bottom forward and lift off upwards (Æ Fig. 6).
Fig. 6 Removing the cover
B For the upper attachment screw, drill a Ø 1/4" (6 mm)
hole, insert an appropriate wall anchor, and insert the screw until only 1/16" (1.5 mm) protrudes (Æ Fig. 7).
Fig. 7 Upper attachment screw
B In the back panel of the MCM10 module, create two
holes for the lower attachment screws using the breakouts prepared.
B Attach the MCM10 module at the top attachment
screw.
B Mark the holes to be drilled on the wall through the
breakouts created.
B Remove the MCM10 module. B Drill Ø 1/4" (6 mm) holes and insert wall anchors
(Æ Fig. 8).
Fig. 8 Insert wall anchor
DANGER: Risk of electric shock!
B Before connecting the power supply,
interrupt the power supply to the heating appliances and to all other BUS subscribers.
7 746 800 090-03.1O
1/4"
3,5 mm
0.05" (1,5mm)
6 720 617 648-02.1O
3.
4.
4.
2.
1.
1/4"
1/4"
3,5 mm
6 720 617 648-03.1O
1/4"
1/4"
3
Installation
MCM10
11
B Hook in the MCM10 module at the top attachment
screw and secure with the two lower screws.
B With the use of stiff or flexible ducts:
Remove all plastic grommets from the slits on the
lower side of the MCM10; – push the duct connection to the intended place; – break out the required number of cable entries by
knocking cautiously with a screwdriver handle; – mount the duct according to the manufacturer's
instructions.
Note: When using ducts, no plastic grommets are required.
3.2 Making the electrical connections
B Observe electrical code for the connection and use at
least cable AWG14 for the main power cord.
B Always route cables through the preassembled
grommets and apply the strain relief supplied to protect the system against the ingress of dripping water.
B Wiring preferably with single core cable. When using
multi-strand (flexible) cables, fit them with wire ferrules.
B Cables can be pulled off the contact strip for their
connection to the screw terminals. The connectors are color-coded and keyed to prevent mismatch of cable terminals.
3.2.1 Connection of the low voltage part with BUS connections
The minimum permissible cable cross-section of the 2­wire BUS connection arises from the cable length:
B Route all low-voltage cables separately from cables
carrying 120V to avoid inductive interference (minimum separation 4 inches)(100 mm).
B In case of inductive external influences, use shielded
cables. This way, the cables are screened against external influences (e.g. high-voltage cables, contact wires, transformer stations, radio and TV devices, amateur radio stations, microwave devices, etc.).
B When sensor leads are extended, apply the following
lead cross-sections:
B To safeguard the splash-proof rating (IP):
Route cables so that the cable sheath protrudes at least 0.8" (20 mm) into the cable grommet (Æ Fig. 9) or the duct connection box.
Fig. 9 Splash-proof
3.2.2 120 V AC connection
B Only use electric cable of similar quality. B Never connect additional controllers that regulate other
system components to outputs C (pump) and D (fault signal).
CAUTION: Malfunction! B Always wire in accordance with the wiring
diagram (Æ Fig. 12, page 19).
B Never connect one BUS to another.
Cable length Min. cross-section
< 325 ft (100 m) AWG 20
325 - 650 ft (100 - 200 m) AWG 18
Tab. 6 Minimum permissible cross-section of the
2-wire BUS connections
Cable length Min. cross-section
< 65 ft (20 m) AWG 20
65 - 100 ft (20 - 30 m) AWG 18
Tab. 7 Sensor lead extension
CAUTION: Risk of pole reversal. Malfunction through interchanged
connection on the 0 - 10 V interface.
B Ensure connection to the correct poles
(9 = negative, 10 = positive).
CAUTION: The MCM10 module input is not fuse-protected.
Overloading the outputs can damage the MCM10 modules.
B Protect the MCM10 module power supply
(master) with a fuse with maximum rating 10 Amp.
CAUTION: Output C (pump) of the MCM10 module has a maximum load capacity of 250 W.
B Connect pumps drawing more current via
relays.
6 720 617 648 - 04.1O
1" (25 mm)
3
Installation
MCM10
12
B Recommendation when using several MCM10
modules (cascade with more than four heating appliances): Provide the additional modules with power via the first MCM10 module (master). This ensures simultaneous start-up.
3.2.3 Connection of a remote fault indication with optical and acoustic signal
For example, a fault indicator can be connected to the zero volt fault contact (Æ Fig. 12, terminal D, page 19). The state of the fault contact is also indicated via an LED on the MCM10 (Æ Tab. 9, page 14).
This is a dry contact that carries a maximum current of 2 A at 120 V AC.
3.2.4 Electrical connection of the outdoor temperature sensor
In conjunction with heating system controls with 2-wire BUS control, always connect outdoor temperature sensor to the MCM10 module (master) (Æ Fig. 12, page 19) and not to the heating appliance.
3.2.5 Electrical connection of the supply temperature sensor
For system version 1, the common supply temperature sensor must be connected to the WM10 (Æ installation instructions for WM10) and for the system versions 2, 3, 4, and 5, to the MCM10, terminal E (Æ Fig. 12, [18], page 19).
3.2.6 Electrical connection of the external switching contact
If an external switching contact must be connected, the bridge on the plug must be removed first.
3.2.7 Disposal
B Dispose of packaging in an environmentally-
responsible manner.
B When replacing components, dispose of the old parts
in an environmentally-responsible manner.
3.3 Installing other accessories
B Install accessories according to the legal requirements
and the installation instructions supplied with them.
B The BUS subscribers RC35, WM10, and MM10 must
be connected to terminal J (Æ Fig. 12, page 19).
The maximum current drawn by the system components (pump, etc.) must not exceed specifications (Æ Tab. 2, page 5).
Situation Operating status contact
Current on, no fault
Current on, fault
No current
Tab. 8 Operating status contact
The remote fault indication is enabled when the power supply to the MCM10 module is interrupted (master) (function check).
Loading...
+ 28 hidden pages