Buderus Logano GC124 II/SP Installation And Service Instructions Manual

7 747 000 512 – 07/2006 US For installers
Please read carefully prior to installation and maintenance.
Installation and Service Instructions
Gas boiler Logano GC124 II/SP
CAUTION!
WARNING!
Installation, adjustment, modification, operation or maintenance of the heating system carried out by unqualified personnel may result in property damage, personal injury, and loss of life. The directions of this installation and maintenance manual must be followed precisely. Contact a qualified service company, service provider or the gas company if support or additional information is required.
CAUTION!
The operating manual is a component of the technical documentation handed over to the operator of the heating system. Discuss the instructions in this manual with the owner or operator of the heating system and ensure that they are familiar with all information required for operation of the heating system. In the Commonwealth of Massachusetts this boiler must be installed by a licensed plumber or gas fitter.
Keep this installation and maintenance manual available for future reference.
Summary
2
Installation and Service Instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
We reserve the right to make any changes due to technical modifications.
1 Safety considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Correct use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Observe the following symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Observe the following guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Tools, materials and accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.5 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Dimensions and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5 Moving the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.1 Moving the boiler with boiler cart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.2 Lifting and carrying the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6 Placing the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.1 Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.2 Leveling the boiler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7 Boiler installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7.1 Preparing for installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7.2 Connecting the heating system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.3 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7.4 Fuel gas supply connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7.5 Filling heating system and checking for leaks . . . . . . . . . . . . . . . . . . . . . . . . . 20
8 Check openings for combustion air supply and venting . . . . . . . . . . . . . 22
9 Requirements for connection to chimneys or venting systems . . . . . . . 23
10 Flue pipe installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
11 Placing the heating system in operation . . . . . . . . . . . . . . . . . . . . . . . . . 26
11.1 Starting up the GC124 II and GC124 SP boilers . . . . . . . . . . . . . . . . . . . . . . . 29
12 Final start-up procedures for GC124 II models . . . . . . . . . . . . . . . . . . . . 30
13 Final start-up procedure for GC124 SP models . . . . . . . . . . . . . . . . . . . . 35
14 Start-up protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
14.1 Informing the owner/operator and handing over technical documentation . . . . . . . 41
15 Taking the heating system out of operation . . . . . . . . . . . . . . . . . . . . . . 42
15.1 Normal system shut-down. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
15.2 Emergency shut-down procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Summary
3
We reserve the right to make any changes due to technical modifications.
Installation and Service Instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
16 Boiler inspection and maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
16.1 Why is regular maintenance important? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
16.2 Testing the flue system, including combustion air, air inlets and
Ventilation openings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
16.3 Inspection of the boiler and burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
16.4 Preparing boiler for cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
16.5 Cleaning the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
16.6 Cleaning the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
16.7 Maintenance protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
16.8 Troubleshooting the GC124 II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
16.9 Troubleshooting the GC124 SP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
17 Parts lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
18 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
19 Electrical circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Safety considerations1
4
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
We reserve the right to make any changes due to technical modifications.
1 Safety considerations
Observe these instructions for your safety.
The burner and control must be correctly installed and adjusted to ensure safe and economical operation of the gas boiler.
Read this installation and maintenance manual carefully and note the details on the boiler nameplate before placing the boiler in operation.
1.1 Correct use
The Logano GC124 II/SP atmospheric gas boiler is designed to heat water for a hot water heating system for heating single or multiple occupancy buildings.
1.2 Observe the following symbols
Two levels of danger are identified and signified by the following terms:
Additional symbols for identification of dangers and user instructions:
1.3 Observe the following guidelines
1.3.1 National regulations
The heating system must comply with the relevant regulations issued by national authorities, or the regulations issued by the National Fuel Gas Code, ANSI Z 223.1.
If specified by the local regulatory authorities the heating system must comply with the regulations of the "Standard for Controls and Safety Devices for Automatically Fired Boilers," ANSI/ASME CSD-1.
Carbon monoxide detectors must be installed as specified by the local regulations. The boiler must be serviced annually (Î Chapter 16, page 43).
Boiler Operating Conditions
The hot water piping system must comply with the current legislation and local regulations. If an existing boiler is replaced, the complete hot water piping system must be inspected to ensure that it is in perfect condition to ensure safe operation.
WARNING!
RISK TO LIFE
Identifies possible dangers originating from the product, which might lead to serious injury or death if proper care is not taken.
CAUTION!
RISK OF INJURY SYSTEM DAMAGE
Identifies potentially dangerous situations, which might lead to medium or minor injuries or to material losses if proper caution is not followed.
WARNING!
RISK TO LIFE
from electrical shock.
USER NOTE
Guidelines for the optimum use and setting of the control(s) plus other useful information.
Maximum boiler temperature: 220 °F Maximum operating pressure: 58 psi
WARNING!
RISK TO LIFE
due to neglecting your own safety in case of emergency, such as with a fire.
z Never put yourself at risk. Your own
safety must always take priority.
WARNING!
RISK TO LIFE
from explosion of flammable gases.
If you smell gas there is a danger of explosion.
z Never work on gas lines unless you are
licensed for this type of work.
z Make sure that a qualified company
installs the boiler, connects gas and ventplaces the boiler in operation, connects the electrical power, and maintains and repairs the boiler.
z No open flame! No smoking! Do not
use lighters
z Prevent spark formation. Do not
operate electrical switches, including telephones, plugs or door bells.
z Close main gas valve.
z Open doors and windows.
z Warn other occupants of the building,
but do not use door bells.
z Call gas company from outside the
building.
z If gas can be heard escaping, leave the
building immediately, prevent other people from entering, notify police and fire departments from outside the building.
Safety considerations 1
5
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
1.3.2 Installation notes
1.3.3 Information on the boiler room
CAUTION!
SYSTEM DAMAGE
due to incorrect installation.
z Observe all current standards and
guidelines applicable to the installation and operation of the boiler heating system as applicable in your state or local jurisdiction.
WARNING!
RISK TO LIFE
from electrical shock.
z Disconnect the power supply to the
boiler heating system before conducting any work on it, e.g. turn off the heating system emergency switch outside the boiler room.
z It is not sufficient just to turn off the
control.
CAUTION!
SYSTEM DAMAGE
due to unsatisfactory cleaning and boiler maintenance.
z Clean and service the boiler system
once a year. Check that the complete heating system operates correctly.
z Immediately correct all faults to prevent
system damage.
USER NOTE
Only use original Buderus spare parts. Losses caused by the use of parts not supplied by Buderus are excluded from the Buderus warranty.
WARNING!
RISK TO LIFE
from explosion of flammable gases.
z Never work on gas lines unless you are
licensed for this type of work.
WARNING!
RISK TO LIFE
from electrical shock.
z Do not carry out electrical work unless
you are qualified for this type of work.
z Before disconnect electrical power
completely and pad lock to prevent accidental reconnection.
z Observe the local installation
regulations.
WARNING!
RISK TO LIFE
by poisoning.
Insufficient ventilation or combustion air availability may cause dangerous flue gas leaks or formation.
z Make sure that inlets and outlets are not
reduced in size or closed.
z If faults are not corrected immediately,
the boiler must not be operated until all faults have been corrected.
z Inform the system operator and/or
owner of the fault and the danger in writing.
WARNING!
RISK TO LIFE
by poisoning.
When working on the flue gas venting equipment or vent damper leakage of flue gases may endanger the lives of people.
z Carefully observe proper operation of
the vent damper. Do not start up the boiler unless the vent damper is operating properly.
z Use only original parts when replacing
parts.
z When replacing the vent damper, install
the new one in the specified position.
WARNING!
RISK TO LIFE
by poisoning by spillage of flue gases.
If the blocked vent switch, attached to the open draft hood in the rear of the boiler trips frequently, there may be a problem with the chimney or the flue gas venting system.
z If the blocked vent switch trips
frequently the fault must be corrected and proper operation of the blocked vent switch test must be conducted.
WARNING!
RISK TO LIFE
by poisoning by leakage of flue gases.
z Make sure that the boiler is not
equipped with a thermally controlled flue gas vent damper after the open draft hood.
Safety considerations1
6
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
We reserve the right to make any changes due to technical modifications.
1.4 Tools, materials and accessories
You need standard tools for the installation and maintenance of the boiler as used in boiler heating system installation and oil, gas and water installations.
The following additional items will also be useful:
Boiler cart with strap.
Cleaning brushes and/or chemical cleaning agents
for wet cleaning of the cast iron heat exchanger.
1.5 Disposal
z Dispose of the packaging material in an
environmentally prudent fashion.
z Dispose of any components of the heating system
that require replacement in an environmentally prudent fashion.
WARNING!
FIRE DANGER
due to flammable materials or liquids.
z Make sure that there are no flammable
materials or liquids in the immediate vicinity of the boiler.
z Maintain a minimum distance of 15
inches from the boiler.
Product Description 2
7
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
2 Product Description
The boiler is a low temperature gas boiler.
The boiler consists of the following main components:
– Ignition module (GC124 II only) and adjustable
aquastat
Boiler jacket and front door
Boiler block with insulation
Burner
The ignition module and adjustable aquastat monitor and control all electrical and operational components of the boiler.
The boiler jacket prevents energy loss and acts as soundproofing.
The boiler block transfers the heat generated by the burner to the heating water. The insulation reduces energy loss.
Fig. 1 Logano GC124 II/SP gas boiler
1 Boiler front door 2 Aquastat (boiler temperature controller) 3 Ignition module (GC124 II only) 4 Boiler block with insulation 5 Burner 6 Boiler jacket
7 747 000 511-01.0K
6
1
5
3
4
2
GC124 II
GC124 SP
6
1
5
4
2
8
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
We reserve the right to make any changes due to technical modifications
Dimensions and Connections3
3 Dimensions and Connections
Tab. 1 Dimensions/specs for GC124 II and GC124 SP
Fig. 2 Back, side and front view, measurements in inches
* optional connection
RK 1¼"
VK 1¼"
GAS ½"
EL ¾"
(GAS ½")*
Connections (measurements see the following tables):
VK = Boiler supply RK = Boiler return EL = Boiler drain GAS = Gas connection
Boiler
size
Boiler
input
A B Vent connection
II/SP
Min. relief valve
capacity
Number of
Orifices
Water
volume
Dry
weight
Btu/hr Inches Inches Inches lb/hr Qty. US Gal. lbs
18/3 74000 13 1/8" 8" 5" 62 2 2.4 228
25/4 103000 16 3/4" 8 2/3" 5" 86 3 2.9 287
32/5 132500 20 3/8" 9 1/2" 6" 110 4 3.4 349.5
Fig. 3 Pressure drop/boiler
USER NOTE
For the size and dimensions of the main gas orifices, refer to Î Chapter 18, page 79.
Scope of delivery 4
9
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
4 Scope of delivery
z Check packaging upon receipt of delivery for dam-
age.
z Check delivery for completeness.
Component Qty Packaging
method
Boiler, complete 1 1 palette
B-kit components:
- 1-1/4" supply manifold
- 30 psi relief valve
- long shank boiler drain (¾")
- ¼" pressure/temperature gauge
- 90°-elbow (1¼" x 1" NPT)
- 90°-elbow (1¼" x 1¼" NPT)
- 90°-elbow (¾" NPT nipple)
- nipple1" NPT
- nipple 1¼" NPT
1 1 cardboard
box
1
Vent damper 1 1 cardboard
box
1
Circulator with whip 1 1 cardboard
box
1
Technical documents 1 plastic pack-
age
Tab. 2 Scope of delivery
1
On Palette
Accessory Qty
Cleaning Brush 1
Tab. 3 Scope of delivery
10
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
We reserve the right to make any changes due to technical modifications.
Moving the boiler5
5 Moving the boiler
This chapter describes how to move the boiler safely into place.
5.1 Moving the boiler with boiler cart
Move the boiler with packaging in tact and on its pallet as much as possible.
z Remove packaging straps and cardboard box from
pallet.
z Remove screws that secure the boiler base to the
wood pallet.
z Pick up boiler base from one side and slide to the
edge of the pallet. Place a steel pipe as roller under the boiler base. Place additional steel pipes under the boiler base and roll the boiler to its final destina­tion.
CAUTION!
SYSTEM DAMAGE
Due to uneven and rough surfaces.
z Observe the transport diagrams on the
packaging to protect the sensitive com­ponents from damage due to rough sur­faces. Handle the product with care.
USER NOTE
z Protect all boiler connections from dirt if
the boiler is not installed immediately following removal from packaging.
USER NOTE
Dispose of the packaging material in an environmentally prudent fashion.
Fig. 4 Moving the boiler with rollers
Moving the boiler 5
11
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
z Set the boiler cart or dolley on the front side of the
boiler and put a piece of cardboard between the two to prevent scratches.
z Secure boiler on the boiler cart.
z Move boiler to desired location.
z Place the boiler at its final postion.
5.2 Lifting and carrying the boiler
The boiler can be picked up at the both long sides of the boiler as shown.
Fig. 5 Moving the boiler with dolley or boiler cart.
1 Additional card board for protection.
1
CAUTION!
RISK OF INJURY
due to improper securing of the boiler dur­ing transport.
z Use a boiler coart or dolley and strap
for moving the boiler
z Secure boiler on the boiler cart.
z Remove the front door during lifting or
transport to prevent unintentional open­ing.
Fig. 6 Lifting and carrying the boiler
7 747 000 511-04.0K
CAUTION!
RISK OF INJURY
due to carrying heavy loads.
z Lift and carry the boiler with at least four
people at the designated side panel lo­cations.
12
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
We reserve the right to make any changes due to technical modifications.
Placing the boiler6
6 Placing the boiler
This chapter explains how to place the boiler and posi­tion it in the boiler room.
The boiler is very heavy when filled with water. Check that the floor can bear the weight before installation.
6.1 Clearances
The GC124 boiler is approved for closet installation. The following minimum distances must then be main­tained:
– front: 2", – sides: 2", – behind open draft hood: 6", – above boiler top panel: 30".
A space of at least 33 inches is recommended in front of the boiler with the door removed to allow sufficient ac­cess space for operation and maintenance. When the door is closed, a minimum clearance of 2 inches is re­quired at the front and sides, 2 inches clearance is also required for the flue pipe and 30 inches clearance to the ceiling. The installation location and the base must be smooth and horizontal.The boiler may be installed on a flammable base, but not on carpet.
6.2 Leveling the boiler
Level the boiler in both horizontal directions.
z Level the boiler using a level and place small wedges
(not supplied) for leveling purposes.
CAUTION!
SYSTEM DAMAGE
due to frost.
z Place the boiler in a frost-free room.
Fig. 7 Required clearances in the boiler room
1 Recommended service clearances 2 Required minimum clearances 3 Burner tray access door with combustion air opening as
required per ANSI Z.223.1
1
2
3
Boiler installation 7
13
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
7 Boiler installation
This chapter describes how to install the boiler. This in­cludes the following tasks:
Connecting the heating system
Electrical connection
Gas supply piping connection
7.1 Preparing for installation
z Unpack all boxes and containers and check all parts
against the packing lists to make sure that everything has been supplied.
USER NOTE
Every boiler is carefully inspected and tested before it leaves the factory. How­ever, if you discover any damage or miss­ing parts, please inform your supplier im­mediately. Before disposing of packing material, make sure that no parts are still in it.
USER NOTE
For better access remove the front door.
14
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
We reserve the right to make any changes due to technical modifications.
Boiler installation7
7.2 Connecting the heating system
Fig. 8 Low-water cut-off installation
1 Boiler 2 Radiator 3 Heating system with low-water cut-of 4 Heating system without low-water cut-off
1
2
2
1
2
2
2
2
3
4
CAUTION!
BOILER DAMAGE
Due to moisture.
z Protect the components of the gas igni-
tion system from moisture (dripping, spray, rain) during installation of the boiler, during operation and during maintenance work (such as replacing the pump, replacing the control, etc.).
CAUTION!
SYSTEM DAMAGE
Due to overheating as a result of a low wa­ter condition.
z Note that a boiler installed above the
level of the heating system must be equipped with a low-water cut-off. The low-water cut-off must be installed dur­ing installation of the boiler and placed above the water level in the boiler with­out any means of shutting the water off between the boiler and low water cut-off (Î Fig. 8).
CAUTION!
SYSTEM DAMAGE
Due to high temperature variations in the heating system.
z If the boiler is operated in connection
with a refrigeration system, make sure that the pipes for the refrigerated liquid are connected in parallel to the boiler system with suitable valves to prevent the refrigerated liquid from entering the boiler.
z The piping system of a boiler connect-
ed to the heating coils of hydro-air heat­ing systems that may be exposed to the circulation of cooled air must be equipped with a flow-control valve or some other automatic system for pre­venting the boiler water from circulating by gravity during the cooling cycle.
Boiler installation 7
15
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
Installation of B-kit
The relief valve and the pressure/temperature gauge are mounted on the boiler supply manifold which is attached to the VK (supply) connection of the boiler (included in B-kit).
Installing boiler supply VK:
z Remove factory installed plastic inserts from boiler
supply (VK), boiler return (RK) and boiler drain (EL) connections.
z Install the 1¼"NPT nipple into boiler supply, the 1"
NPT nipple into boiler return and ¾" male NPT drain valve into boiler drain connection.
z Install 90° 1¼" x 1¼"NPT on 1¼"
NPT supply nipple
and face upward and install 90° 1¼" x 1"NPT elbow on return nipple and face in desired direction.
z Install GC124 1¼" x 1¼"NPT supply manifold into
supply connection (VK) of the boiler. Do NOT place on return connection of the boiler!
z Install first 90° ¾" street elbow in upper ¾" NPT tap-
ping of GC124 1-1/4" supply manifold and install pressure relief valve into this ¾" tapping. Make sure to orient the discharge of the relief valve horizontally. Install the temperature/pressure gauge in the lower 3/4" tapping of the supply manifold.
Fig. 9 Installation of B-kit
1 Pressure relief valve ¾" 2 90° 3/4" street elbow 3 GC124 1-1/4" supply manifold 4 Pressure & temperature gauge 5 90° 1-1/4" NPT elbow 6 1-1/4" NPT nipple 7 Boiler drain ¾" NPT (backside of boiler) 8 90° 1-1/4" x 1" NPT elbow 9 1" NPT nipple
1
2
4
5
8
VK
RK
6
9
EL
7
3
USER NOTE
Install the relief valve after the leak test. (Î Chapter 7.5, page 20).
The relief valve must be installed in a ver­tical position.
The relief valve must also be installed in accordance with the requirements of the ANSI/ASME Boiler and Pressure Vessel Code, Section IV.
USER NOTE
We recommend installing a y-strainer (ac­cessory) in the boiler return connection to reduce build-up of debris on the water side inside the boiler.
USER NOTE
Ensure compliance with all state and local regulations pertaining to the installation of boiler systems.
16
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
We reserve the right to make any changes due to technical modifications.
Boiler installation7
7.3 Electrical connections
The electrical connections of the boiler must be made as specified by the local codes and the current regulations of the National Electrical Code, ANSI/NFPA–70.
The boiler must be grounded as specified by the regula­tions of the relevant local authorities; otherwise follow the regulations of the National Electrical Code, ANSI/NFPA–70.
The boiler is fully functional with the factory installed aquastat and the field installed vent damper and heating system circulation pump.
Power supply connection.
Install incoming power to the boiler per local and state codes.
z Install an ON/OFF switch near the boiler per local
code requirements.
CAUTION!
FIRE DANGER
due to exposure to hot water pipes.
z Maintain a minimum clearance of two
inches between non-insulated pipes carrying hot water and combustible walls and surfaces in the boiler room. A minimum of 1" high quality pipe insu­lation is required to permit direct con­tact with combustible surfaces.
USER NOTE
When making the electrical connections please observe the following guidelines:
z Perform only electrical work, if you pos-
sess the required certification for such work. When you do not have the re­quired certification, have the electrical work performed by a certified electri­cian.
z Observe all local and state installation
regulations.
Fig. 10 ON/OFF switch (emergency shutoff switch)
Boiler installation 7
17
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
Description of field installed wiring connections using factory supplied junction box.
z Remove two knock-outs from the left side of boiler
panel to route electrical feed and pump power into junction box.
z Route electrical power from the outside into junction
box.
z Install a metal strain relief for the incoming power line
on outside of left boiler jacket panel. (Î Fig. 12).
z Just use supplied wiring nuts and double proper wir-
ing before powering up the boiler.
z Check that the heating system functions correctly af-
ter any maintenance work.
Fig. 11 Electrical junction box
1 Electrical junction box (Inside of jacket cabinet) 2 Incoming line voltage wiring 3 Furnished wiring nuts.
2
1
3
USER NOTE
When making the electrical connections use only wires that are approved for elec­trical use.
USER NOTE
Refer to the wiring diagrams on pages Î page 80 bis Î page 82 for electrical details.
Fig. 12 Strain relief for shielded electrical wiring
WARNING!
RISK TO LIFE
from electrical shock.
z When conducting maintenance work
label all cables before disconnecting them.
z If cables are connected incorrectly the
system may not operate correctly with possibly dangerous consequences.
WARNING!
FIRE DANGER
Hot boiler components may damage elec­trical wiring.
z Make sure that all cables are routed in
the ducts or on the boiler insulation.
18
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
We reserve the right to make any changes due to technical modifications.
Boiler installation7
7.4 Fuel gas supply connection
7.4.1 Gas connections
For the gas pipe diameter required for the installation please see Î Tab. 4 and Î Tab. 5. Make sure that the pipe fitting has the correct thread size.
Make sure that a sediment trap is installed at the inlet for the gas supply pipe to the boiler. A manual stop valve must be installed outside the boiler jacket if required by the local code. We recommend installing a manual shut-off valve in the main gas pipe to the boiler. The gas pipe must be fastened outside the boiler.
The local codes must be observed during installation of the gas piping connections, otherwise the regulations of the National Fuel Gas Code, ANSI Z 223.1 must be fol­lowed.
z Install gas piping without any undue stress on the
piping.
z The Commonwealth of Massachusettes prohibits the
use of copper tubing for the gas line.
Gas carrying capacity (refer to technical manual Î Chapter 18, page 79)
Tab. 5 Gas pipe supply volume
1 Maximum gas supply volume in cubic feet per hour, based on
a specific gas weight of 0.60 and a gas pressure of 0.5 psi or less and a pressure gradient corresponding to a water column of
0.3 inches.
Fig. 13 Gas piping connection to gas valve – right or left side
1 Gas feed 2 Manual shut-off valve 3 Sediment trap
1
2
3
WARNING!
DANGER OF EXPLOSION
Leakage from the gas pipes and gas connections may cause an explosion.
z Use soap solution to find leaks.
Nominal
diameter of
iron pipe
(inches)
Equivalent lengths for pipe fittings in
feet
Pipe fitting type
90°-
angle
T-piece
Shut-off
valve
Gas
shut-off
Equivalent lengths in feet
1/2 1.4 2.7 0.3 0.80 3/4 2.1 4.1 0.5 1.25
1 2.6 5.2 0.6 1.6 1 1/4 3.5 6.9 0.8 2.15 1 1/2 4.0 8.0 0.9 2.50
Tab. 4 Equivalent lengths for pipe fittings
Length of pipe
in feet
Gas pipe supply volume in cubic feet of gas
per hour
1
1/2 3/4 1 1 1/4 1 1/2
10 132 278 520 1060 1600 20 92 190 350 730 1100 30 73 152 285 590 890 40 63 130 245 500 760 50 56 115 215 440 670
75 45 93 175 360 545 100 38 79 160 305 480 150 31 64 120 250 380
Boiler installation 7
19
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
Disconnect the boiler with the manual shut-off valve and physically separate the boiler from the gas piping if the gas piping system is pressure tested with a test pressure greater than 1/2 psi.
If the gas supply pipe system is pressure tested at a test pressure of 1/2 psi or less, it is sufficient to disconnect the boiler from the gas pipe system by closing the man­ual shut-off valve.
Use only sealant that is resistant to corrosion by LPG for pipe connection. Only a small amount of sealant must be applied to the external thread of the pipe connections.
If you wish to convert the boiler to propane, please con­tact Buderus for the required conversion components. Do not attempt to convert the boiler without the ap­proved Buderus propane conversion parts and the rele­vant technical documentation. The technical documen­tation is included with the propane conversion parts.
7.4.2 Installation at high altitudes
The boiler is designed for installation at altitudes below 8500 feet above sea level.
USER NOTE
If the installation location is over 8500 feet above sea level, please contact Buderus for another product option as the GC124 is not approved above 8500 feet opera­tion.
CAUTION!
SYSTEM DAMAGE
due to dirt.
If the boiler is assembled and not in use, note the following:
z Protect the boiler connections from dirt
by closing the connections.
20
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
We reserve the right to make any changes due to technical modifications.
Boiler installation7
7.5 Filling heating system and checking for leaks
The boiler is tested for leaks at the factory. Before plac­ing the heating system into use, check the entire system for soundness to avoid leaks occurring during operation.
Water treatment
Carry out the leak test at 1.5 times the normal operating pressure and as specified by the local codes as follows:
USER NOTE
Have the water analyzed before filling the heating system. The water may require treatment as a result of the analysis.
Please consult the local water supply company if the water is extremely hard or has a pH level below 7.0.
CAUTION!
SYSTEM DAMAGE
due to overpressure during the leak test. Pressure, control or safety components may be damaged by high pressure.
z Before conducting the leak test make
sure that no pressure, control or safety components that cannot be disconnect­ed from the water compartment of the boiler are installed.
Maximum operating pressure Maximum test
pressure
30 psi (based on supplied re-
lief valve)
45 psi
58 psi (with special relief
valve)
75 psi
Tab. 6 Pressure Test
Boiler installation 7
21
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
z Close connection for relief valve (Î Fig. 14) and all
other open connections with plugs.
z Disconnect the expansion tank from the system by
closing the expansion tank shut-off valve.
z Open mixing and shut-off valves on hot water side.
z Fill boiler slowly with water from the feed water con-
nection.
z Open automatic vents slightly to allow the air to es-
cape.
z Slowly fill heating system. Observe pressure display
on pressure gauge during this process.
z Check connections and pipes for leaks.
z Bleed heating system through the bleed valves on
the radiators or other air elimination components or high points in the system.
z If the pressure drops during air bleeding, water must
be added.
z Install pressure relief valve (Î Fig. 14).
z Open fill valve for additional filling.
z Set static system pressure to at least 15 psi at indi-
cated on pressure relief valve (Î Fig. 15).
z Close fill valve and remove fill hose for fill valve.
Fig. 14 B-kit installation
1 Pressure relief valve ¾"
1
VK
RK
EL
Fig. 15 Pressure temperature gauge
1 Pressure gauge 2 Set pressure mark
1 2
Check openings for combustion air supply and venting8
22
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
We reserve the right to make any changes due to technical modifications.
8 Check openings for combustion air supply and venting
To ensure an adequate combustion air supply and venting of the heating system suitable measures must be taken in accordance with the National Fuel Gas Code, Section 5.3, Air for Combustion and Ventilation, or the local codes.
Total air supply from inside the building
Make sure that the boiler room has two permanent openings that are connected with one or more other rooms. When calculating the cross-section areas of the openings, the total combustion output of all gas-fired appliances in the connected rooms must be taken into account. Each opening must have a minimum cross­section of one square inch per 1000 Btu/h of the total combustion output of all gas-fired appliances inside the connected rooms. Note that the minimum cross-section of every opening must not be less than 100 square inches. One opening must not be more than 12 inches from the ceiling and the other must not be more than 12 inches from the floor of the boiler room, calculated from the outer edge of the opening. The shortest dimension of all inlet and outlet openings must not be less than three inches.
Total air supply from outside the building
Make sure that the boiler room has two permanent openings, one of which must not be more than 12 inches from the ceiling and the other must not be more than 12 inches from the floor of the boiler room, calculated from the outer edge of the opening. The openings have a direct connection or a connection through ventilation ducts to the outside or to rooms that have an unobstructed connection to the outside (crawl space or attic). The shortest dimension of all inlet and outlet openings must not be less than three inches.
1. If there is a direct connection to the outside, each opening must have a minimum cross-section of one square inch per 4000 Btu/h of the total combustion output of all gas-fired appliances inside the closed room.
2. If there is a connection to the outside through vertical ventilation ducts, each opening must have a minimum cross-section of one square inch per 4000 Btu/h of the total combustion output of all gas-fired appliances inside the closed room.
3. If there is a connection to the outside through horizontal ventilation ducts, each opening must have a minimum cross-section of one square inch per 2000 Btu/h of the total combustion output of all gas­fired appliances inside the closed room.
4. If the openings are connected to ventilation ducts, the ducts must have the same cross-section area as the openings.
CAUTION!
BOILER DAMAGE AND OPERATING FAULTS
due to missing or inadequate openings for combustion air and venting of the boiler room.
Inadequate venting of the boiler room may result in excessive ambient temperatures. This can damage the boiler.
Inadequate combustion air supply may cause operating faults.
z Make sure that inlets and outlets are
not reduced or closed and that they are adequately dimensioned.
z If faults are not corrected immediately,
the boiler must not be operated
z Inform the system operator of the fault
and the danger.
CAUTION!
BOILER DAMAGE
due to contaminated combustion air.
z Never use cleaning agents that contain
chlorine and halogenated hydrocarbons (e.g. spray bottles, solvents and cleaning agents, paints, glues).
z Do not store or use these substances in
the boiler room.
z Prevent excessive dust levels.
WARNING!
FIRE DANGER
due to flammable materials or liquids.
z Do not store flammable materials or
liquids in the immediate vicinity of the heat generator.
Requirements for connection to chimneys or venting systems 9
23
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
9 Requirements for connection to chimneys or venting systems
The flue connection must comply with the regulations of the National Fuel Gas Code, Part 7, Venting of Equipment, and the local construction codes.
Flue connections of heating systems with natural venting must not be connected with any component of a mechanically operated venting system that operates with overpressure.
The cross-section of the flue connection must not be less than that specified in Tab. 1, page 8.
If the boiler is to be connected to a brick chimney, the chnimney must be thoroughly inspected before use. The chimney must be clean, in compliance with construction codes and of sufficient dimensions.
Chimneys with an internal liner are preferred and are only permitted if the liner complies with all national, state and local construction codes. Liners of fire-glazed brick with moisture-proof joints and liners of corrosion­resistant material are recommended. Contact the local gas supply company for advice and recommendations for flue connection and chimney liners. A flue pipe of single-walled sheet metal is required for flue connections for type II models.
An adequate chimney height in compliance with the tables of the National Fuel Gas Code, ANSI Z 223.1, is required.
Separation of a boiler from a common flue system
If an existing boiler is separated from a common venting system, the venting system will then be too large to guarantee correct venting for the heating systems that remain connected to the system.
Test the venting system by the following procedure:
Carry out these steps with every heating system that remains connected to the venting system when the boiler is separated from a common venting system. Every heating system must be started in operation and the other heating systems must remain turned off.
A All unused openings of the common system must be
sealed.
B Inspect the venting system to ensure that it has the correct
dimensions and longitudinal inclination. Make sure that the system is not blocked, leaking, corroded or has any other faults that cause it to operate improperly.
C If necessary, close all doors and windows in the building
and all doors between the space in which the heating systems that remain connected to the venting system are installed and the other rooms of the building. Turn off washing machines and dryers and all appliances that are not connected to the venting system. Run all venting fans
and bathroom exhaust fans at maximum speed. Fans in use in summer must remain in operation and oven exhaust system flaps must be closed.
D Now start the heating system that is to be tested. Follow the
instructions for starting. Set the thermostat for continuous operation.
E After the main gas burner has been operating for five
minutes, check the opening at the back flow check for drafts with a match flame or a candle, or with the smoke of a cigarette, cigar or pipe.
F Then all heating systems that remain connected to the
venting system have been checked as above to ensure that the venting operates properly, return all doors, windows, exhaust fans, oven exhaust flaps and all other gas-fired appliances to their original position.
G Any incorrect status of the common venting system must
be corrected to ensure that the heating system complies with the regulations of the National Fuel Gas Code, ANSI Z
223.1. If the size of any component of the common venting system is changed, the complete venting system must be resized to comply with the relevant tables in Part 11 of the National Fuel Gas Code, ANSI Z 223.1.
24
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
We reserve the right to make any changes due to technical modifications.
Flue pipe installation10
10 Flue pipe installation
This section describes the connection of the flue pipe and venting system.
Note that the open draft hood cannot be modified under any circumstances.
1. The flue collar is factory installed on the flue connection of the open draft hood and fastened with four (4) corrosion-resistant sheet metal screws.
The vent damper supplied with the boiler must be used for venting the boiler only.
The position of the vent damper position blade must be visible.
The open draft hood must be at least six inches from all combustible surfaces.
The vent damper must be freely accessible for maintenance.
The vent damper must be open when the main burner of the boiler is operating.
Installation of vent damper
2. Install pins in the hole of the vent damper blade for
the II models only. The openings in the vent damper blade must remain open for the SP model boilers.
3. Fasten vent damper to the flue collar of the open draft hood with three (3) corrosion-resistant sheet metal screws.
Connecting flue pipe
4. Connect flue pipe to the chimney with the shortest
possible length of flue pipe.
Use only flue pipes with the proper diameter for the boiler.
Every horizontal section of the flue pipe must have a minimum rise of 1/4 inch per foot towards the chimney. The flue pipe must be securely fastened to prevent it from hanging. A support must be installed at least every five feet. Fasten every connection with at least three (3) corrosion-resistance sheet metal screws.The end section of the flue pipe must connect to the inside of the chimney smoke duct.
Fig. 16 Installation of vent damper
1 Open draft hood 2 Vent connection 3 Vent damper 4 Damper blade position indicator 5 Vent damper motor 6 Flue gas collector 7 Boiler
5
6
7
4
3
1
2
USER NOTE
z The boiler can and may only be
operated with the electrical vent damper that is standard supplied with every GC124.
Flue pipe installation 10
25
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
A minimum clearance of six inches is required between the flue pipes and all flammable materials.
The vent pipe must not be reduced in size and the venting system must not be compromised by the installation of additional appliances.
Electrically connecting the vent damper
5. Disconnect your heating system from the main
electricity supply.
6. Route the connection wiring of the vent damper along the left side of the boiler into the opening on the left side of the boiler. Secure strain relief at the furnished knock-out.
7. Connect vent damper plug into the terminal bar as shown in the circuit diagram.
Fig. 17 Routing of vent damper wiring
1 Vent damper wiring 2 Vent damper wiring strain relief
1
2
Fig. 18 Connecting vent damper wiring
1 Vent damper connection plug 2 Aquastat 3 Power supply indicator light 4 Aquastat temperature control knob
1
3
2
4
All connection points on the complete venting system must be checked for correct installation and sealing immediately after carrying out one of the installation steps. The seams and connections must be checked for gas leaks. Regulations require the complete venting system to be checked at least once a year by a qualified technician after installation and initial operation.
26
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
We reserve the right to make any changes due to technical modifications.
Placing the heating system in operation11
11 Placing the heating system in operation
The burner and gas train integrated in the boiler have been tested at the factory as described in ANSI Z 21.13 to ensure safe operation of the heating system and verify specific performance indicators.
Preparing for operation
1. Set the room thermostat (optional) to the lowest
setting.
2. Check all combustion air and all flue gas ducts and openings. (Î Chapter 8 and 9, page 22 and page 23).
WARNING!
RISK TO LIFE
due to electric shock when the cover protecting the electric components has been removed.
Before removing the cover to the electric components:
z Cut power to the heating system by
turning the emergency shut-off switch to the OFF position, or by shutting off the heating system circuit breaker.
z Take precautions to prevent accidental
reactivation.
WARNING!
RISK TO LIFE
from gas poisoning.
Insufficient ventilation can lead to leaking of flue gases.
z Verify that all combustion air and all
flue gas openings are wide open and not obstructed.
z The boiler must not be placed in
operation unless all deficiencies have been removed.
z Inform the owner and operator of the
heating system of any deficiencies in writing.
Loading...
+ 58 hidden pages