Buderus Logano GC 124 II, Logano GC124 II-18, Logano GC124 II-25, Logano GC124 II-32 User Manual

Conversion instructions from natural gas to propane
Gas boiler
WARNING!
This conversion kit must only be installed by a qua­lified heating contractor as specified by the manuf­acturer’s instructions and the applicable rules and regulations of the local authorities. If these instruc­tions are not followed exactly, a fire, explosion or release of carbon monoxide may occur with serious property damage or loss of life and serious injury. The heating contractor is liable for correct conversion of the heating system with this conver­sion kit.
CAUTION!
Before converting the heating system to a different type of gas the gas line must first be shut off and then the power to the heating system must be dis­connected.
Note:
Please keep these instructions for future refer­ence.
Logano GC 124 II
In the Commonwealth of Massachusetts this boiler must be installed by a licensed plumber or gas fit­ter.
6 720 804 435 (2012/09) EN-US
C
Contents
Contents
1 Safety considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.1 Key to symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Product information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.1 Correct use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 Conversion to propane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4 Start-up instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.1 Starting up boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.1.1 Prepare pressure measurement . . . . . . . . . . . . . . . . . . . 6
4.1.2 Turning on heating system . . . . . . . . . . . . . . . . . . . . . . . . 6
5 Final start-up procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1 Safety considerations
1.1 Key to symbols
Warnings
Warnings in this document are identified by a warning triangle printed against a grey background. Keywords at the start of a warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken.
The following keywords are defined and can be used in this document:
NOTE indicates a situation that could result in damage to property or equipment.
CAUTION indicates a situation that could result in minor to medium personal injury.
WARNING indicates a situation that could result in severe personal injury or death.
DANGER indicates a situation that will result in severe injury or death.
Important information
This symbol indicates important information where there is no risk of personal injury or property damage.
Additional symbols
Symbol Explanation
B Step in an action sequence
Æ Cross-reference to another part of the document
List entry – List entry (second level)
Table 1
1.2 Safety instructions
Risk to life through the explosion of volatile gases
B Work on gas components must be carried out by qualified and
authorized personnel only.
Risk to life from electric shock.
B Disconnect the power supply to the heating system before conducting
any work on it, e.g. switch off the heating emergency switch outside the boiler room.
B It is not sufficient just to switch off the control.
Logano GC 124 II – 6 720 804 435 (2012/09)2
2 Product information
T
2.1 Correct use
This conversion kit and the accompanying instructions are for conversion of GC124 II special gas-fired boilers from natural gas to propane.
Requirements
GC124 II–18 74 MBtu/hr
GC124 II-25 103 MBtu/hr
GC124 II-32
132.5 MBtu/hr
Table 2 Requirements
2.2 Scope of delivery
Honeywell gas solenoid valve conversion kit # 393 691, comprising:
black safety screwpressure adjustment screwred springyellow label for gas valve
GC124 II: BBR 12 pilot gas orifice
Main gas orifices and seals
"Conversion to propane" label (to be filled out and attached to the
unit)
Technical documents
3 Conversion to propane
For your own safety read the instructions before conversion.
WARNING: Risk to life through not observing the conversion instructions.
B If you wish to convert the boiler for operation with
propane, the conversion from natural gas to propane must be carried out first as specified by the attached conversion instructions.
Fig. 1 Opening boiler front door
WARNING: Danger to life through fire or explosion.
B Never use excessive force on the ON/OFF knob
(Æ figure 2).
B Turn ON/OFF knob only by hand. B Never use tools to turn knob. B If you are unable to turn the knob by hand, do not try
to repair it.
B Call Buderus technical service for assistance.
Product information
6 720 804 435-01.1
2
The following instructions must be followed for conversion of the boiler to propane:
B If the boiler was in operation, close the gas shut-off. Otherwise open
boiler front door.
B Set room thermostat (optional) to the lowest value. B Disconnect the heating system from the power supply. B Open boiler front door.
1
6 720 804 435-02.1T
Fig. 2 Gas valve
[1] ON/OFF knob (shown in ON position)
B Turn gas valve ON/OFF knob clockwise to OFF position. Do not use
force.
Logano GC 124 II – 6 720 804 435 (2012/09) 3
3
Conversion to propane
WARNING: Risk to life through the explosion of volatile
gases. B Wait five (5) minutes until all gas residues have
dissipated. Check whether there is any smell of gas, including at floor level. If you can smell gas, close the gas shut-off and disconnect the heating system from the power supply and contact the customer service technician or the gas company.
B If there is no sign of a gas odor, continue with the next step.
Removing burner
B Secure gas manifold with wire or cord. B Remove igniter cable from ignition module (Æ figure 3, [6]). B Disconnect cable connector from bottom of gas valve
(Æ figure 3, [3]).
B Label cables to the flame roll-out switch, then remove cable
(Æ figure 3, [2]).
5
6
7
8
2
1
6 720 804 435-04.1T
Fig. 4 Removing burner
[1] Screw nuts (two) [2] Screws on gas manifold on top of gas valve (four)
B Remove four (4) screws from gas manifold on top of gas valve. B Remove two (2) screw nuts on burner tray and take out the tray.
9
Replacing main gas orifices
B Install the new main gas orifices and copper gasket. Check with
table 3 that the correct orifices for operation of the boiler are installed.
4
3
Fig. 3 Front view
[1] Flame roll-out switch [2] Flame roll-out switch cable [3] Gas valve [4] Gas supply pipe [5] Aquastat [6] Ignition module [7] Igniter cable [8] Gas valve cable connector [9] Pilot line [10] Igniter cable
1
2
6 720 804 435-03.1T
10
These orifice sizes are exclusively for installations 0­8500 feet above sea level.
Orifice sizes for propane Model GC124-18 GC124-25 GC124-32 Orifice size 180 175 170 Qty 234
Table 3 Orifice sizes for propane
These values are applicable for the U.S.A. only. for altitudes of 0 - 8500 ft.
Logano GC 124 II – 6 720 804 435 (2012/09)4