Buderus Logano GB125 BE Installation And Maintenance Instructions Manual

Installation and Maintenance Instructions
Oil condensing boiler
CAUTION!
Observe the safety instructions of this installation and maintenance manual before placing the boiler in operation.
DANGER!
CAUTION!
The operating manual is a component of the techni­cal documentation and must be handed over to the operator of the heating system. Discuss the instruction in this manual with the ow­ner or operator of the heating system to ensure that they are familiar with all information required for operation of the heating system.
Logano GB125 BE US/CA
6 720 649 307 - 2011/07 US/CA
For contractors
Please read carefully prior to installation and servicing.
Contents
Contents
1 Safety instructions and explanation of
symbols 3
1.1 Safety instructions 3
1.2 Explanation of symbols 4
2 Product description 5
2.1 Intended use 5
2.2 Standards, regulations and code compliance 5
2.3 Notes on installation and operation 5
2.4 Product description 6
2.5 Boiler water quality 7
2.6 Tools, Materials and Accessories 7
2.7 Scope of delivery 7
2.8 Dimensions and specifications 8
2.9 Conditions for operation 9
2.9.1 General operating conditions 9
2.9.2 Conditions for the boiler room and the environment 10
2.9.3 Fuel conditions 10
2.9.4 Power supply conditions 10
2.9.5 Conditions for hydraulic system and water quality 10
2.10 Disposal 11
3 Moving the boiler 12
3.1 Reducing the boiler weight for handling purposes 12
3.2 Lifting and carrying the boiler 13
3.3 Moving the boiler with hand truck 13
4 Placing the boiler 14
4.1 Wall clearances 14
4.2 Reversing the burner door 15
4.3 Mounting the adjustable feet (included with B-kit) 16
4.4 Positioning and leveling the boiler 16
5 Installing the boiler 17
5.1 Flue pipe installation 17
5.2 Test ports 18
5.3 Installation options 20
5.4 Making the water connections 22
5.4.1 Installing B-kit 22
5.4.2 Mounting the drain valve (included with B-kit) 23
5.4.3 Installation of system components 23
5.5 Filling the heating system and checking for leaks 24
5.6 Connecting the fuel supply 25
5.7 Bleed off condensate 25
5.8 Electrical supply connections 27
5.8.1 Installing the control panel 27
5.8.2 Installing the temperature sensor assembly 28
5.8.3 Power connection and connections of additional components 29
5.8.4 Installing cable strain relief 30
5.9 Installing the back boiler cover 30
6 Starting up the heating system 31
6.1 Bringing the system up to operating pressure 31
6.2 Testing safety valve 32
6.3 Checking position of heat exchanger baffles 32
6.4 Preparing the heating system for operation 32
6.5 Starting up the control panel and the burner 33
6.6 Taking measurements 33
6.7 Checking the manual reset high limit (STB) 34
6.8 Installing the burner hood 34
6.9 Commissioning log 35
7 Shutting down the heating system 36
7.1 Normal shut-down 36
7.2 Shutting down the heating system in an emergency 36
7.2.1 Action in an emergency 36
8 Heating system inspection 37
8.1 Why is regular maintenance important? 37
8.2 Preparing the boiler for inspection 37
8.3 Cleaning the boiler 38
8.3.1 Cleaning the boiler with cleaning brushes 38
8.3.2 Wet cleaning (chemical cleaning) 39
8.4 Cleaning the heat exchanger system 40
8.5 Cleaning the neutralizing system and trap 42
8.6 Checking the air supply hose 44
8.7 Check heating system operating pressure 44
8.8 Test safety valve 45
8.9 Concentric supply air and flue gas routing 45
8.10 Air supply system 45
8.11 Inspection and maintenance reports 46
9 Troubleshooting 49
10 Examples of installations 50
11 Spare parts 53
12 Wiring diagrams 61
Index 62
2
Logano GB125 BE US/CA - Subject to technical modifications.
Safety instructions and explanation of symbols
1 Safety instructions and explanation of symbols
1
1.1 Safety instructions
If you smell flue gas
B Switch off the boiler (Æ page 36). B Open windows and doors. B Inform an authorized heating contractor.
Risk of poisoning. An insufficient supply of air can result in dangerous escape of flue gas.
B Never close off or reduce the size of air intake and
outlet openings.
B The boiler must not be operated until the obstruction
has been removed.
B Ensure that no mechanical air-extraction equipment
draws air from the boiler room, e.g. kitchen vent hood, clothes dryer, central vacuum system, etc.
B Inform the system user in writing of an existing problem
and associated dangers.
Danger from escaping flue gases
B Make sure that the vent pipes and gaskets are not
damaged.
B Use silicone as sealing compound. B Never operate this boiler with a barometric or a
thermally-controlled vent damper.
B Connect only one boiler to each venting system or
chimney flue.
B The venting system piping must not feed into another
air extraction duct.
B Do not route the venting system piping through or
inside another duct used for exhaust air or other flue gases.
B To prevent the combustion gases from reaching the
boiler room, the siphon must always be filled with water.
Danger from electrical shock
B Before opening the boiler:
Disconnect the heating system from the electrical power supply by means of the emergency shutoff switch or the heating system circuit breaker on the main fuse panel.
B It is not sufficient just to switch off the control panel. B Take measures to ensure that the heating system
cannot be switched on again unintentionally.
Installation
B Correct and proper installation and adjustment of the
burner and the control panel are the fundamental requirements for safe and economical operation of the boiler.
B The boiler may only be installed or maintained by an
approved heating contractor.
B Do not modify any parts that carry flue gases. B Only qualified electricians are permitted to carry out
electrical work. Follow applicable code.
B The hot water tank may only be used for heating
domestic hot water.
B Never shut off safety valves!
Water may escape from the safety valve when it is being heated.
Danger due to failing to consider your own safety in an emergency such as a fire
B Never put yourself at risk of fatal injury. Your own safety
must always take the highest priority.
Dangers posed by explosive and combustible materials
B Do not use or store easily-combustible materials
(paper, lace curtains, clothing, thinners, paints, etc.) near the boiler.
B Maintain a clearance of 16 inches (40.6 cm) from the
boiler.
Combustion air
B Keep the supply of combustion air free of corrosive
substances (e.g. halogenated hydrocarbons that contain chlorine or fluorine compounds). This will help prevent corrosion.
Logano GB125 BE US/CA - Subject to technical modifications.
3
1
Safety instructions and explanation of symbols
Inspection/maintenance
Heating systems must be maintained regularly.
This way, they maintain a high level of efficiency and low fuel consumption.
You will achieve a high level of operational safety.
And you will obtain the cleanest possible combustion.
B Recommendation for customers: take out a
maintenance and inspection contract with an approved heating contractor covering annual inspection and condition-based maintenance.
B Maintenance and repairs may only be carried out by an
approved heating contractor.
B Have any faults corrected immediately in order to
prevent damage to the system.
B Use only genuine spare parts. Damage caused by the
use of parts not supplied by Buderus is not covered by the Buderus warranty.
Instructing the customer
B Explain to the customer how the boiler works and how
to operate it.
B Inform the customer that he/she must not carry out any
alterations or repairs.
1.2 Explanation of symbols
Warnings are indicated by a warning
triangle and a gray background.
Signal words are used to indicate the seriousness of the ensuing risk if measures for minimizing damage are not taken.
Caution indicates that minor damage to property may
occur.
Warning means that minor injury or severe property
damage may occur.
Danger means that severe injury may occur. Very
serious cases may result in death.
Notesare identified in the text by this symbol. They are separated by horizontal lines above and below the text.
Notes contain important additional information.
Notes do not contain any warnings or information about hazards or risks.
Cross-references to particular places in the document or to other documents are marked with an arrow Æ.
4
Logano GB125 BE US/CA - Subject to technical modifications.
2 Product description
Product description
2
This installation and maintenance manual contains important information for the safe and correct installation, initial start-up and maintenance of this boiler.
The Logano GB125 BE oil-fired condensing boiler is generally referred to below simply as the boiler.
These installation and maintenance instructions are designed for specialists, who – through their vocational training and experience –are knowledgeable in handling heating systems and DHW installations.
This boiler must only be installed with one of the Buderus supplied concentric supply air and flue gas routing systems.
• Concentric air supply and flue pipe exiting through external wall
• Concentric supply air and flue gas routing via roof
• Concentric supply air/flue gas routing through a flue inside a duct
This boiler produces significant amounts of acidic flue gas condensate while in operation. Condensate may cause damage to sewer pipes and septic systems, and disposal may be subject to local regulations. In the absence of such regulations Buderus recommends a condensate neutralization kit.
The boiler must draw all combustion air from the outside.
2.3 Notes on installation and operation
When installing and operating the heating system observe the following:
• The local building codes regarding the installation
• The local building codes regarding combustion air supply and venting systems, and the chimney connection
• Regulations governing power connection to the power supply
• The regulations and standards relating to the safety systems for the water heating system
Other important information
• Only operate the boiler with the combined combustion air/flue venting system specifically designed and approved for it.
• Follow the local code when connecting the condensate outlet to the public sewer system.
2.1 Intended use
The boiler is designed for the central heating and indirect heating of domestic hot water (e.g. in a hot water tank), for instance in single family homes or multi-family buildings.
2.2 Standards, regulations and code compliance
It is the installer's responsibility to ensure the installation and operation of this heating system meets all applicable federal, state, and local codes.
The boiler must be installed by a qualified installer and in accordance with all requirements of NFPA-31, "Installation of Oil­Burning Equipment". Installation must comply with all local and national legal requirements and the regulations of all institutions having legislative authority with regard to the installation of oil-fired boilers. For Canada, the guidelines of the CSA/CGA B139 Installation Code apply.
Logano GB125 BE US/CA - Subject to technical modifications.
5
2
Product description
2.4 Product description
This boiler is an oil-fired condensing boiler with modulating control of boiler water temperature.
The boiler consists of:
• Control panel
• Boiler casing
• Boiler block with thermal insulation
• Burner
• Heat exchanger system
The control panel monitors and controls all electrical boiler components.
The boiler casing prevents heat loss and reduces noise.
The boiler block transfers the heat generated by the burner to the boiler water. The insulation prevents energy loss.
Fig. 1 Boiler with burner
1 Control panel 2 Boiler casing 3 Boiler block with thermal insulation 4 Burner hood 5 Burner
6
Fig. 2 Rear view with heat exchanger (thermal
insulation not shown)
1 Heat exchanger system
Logano GB125 BE US/CA - Subject to technical modifications.
Product description
2
2.5 Boiler water quality
Poor water quality can damage heating systems due to scale formation and corrosion. (Tab. 8, page 10).
CAUTION: Risk of system damage due to unsuitable boiler water!
B When using oxygen-permeable pipes, e.
g. for radiant floor heating systems, you must separate the system using heat exchangers. Unsuitable heating system water promotes sludge formation and corrosion. This can result in heat exchanger malfunction and damage.
2.6 Tools, Materials and Accessories
For the installation and maintenance of the boiler, you need standard tools used for central heating and DHW systems, plus metric wrenches and metric Allen wrenches.
The following may also prove useful:
• Hand truck with securing strap or Buderus boiler cart
• Wood battens
• Cleaning brushes and/or chemical cleaning agent for
wet cleaning
2.7 Scope of delivery
B After delivery, check all packaging for perfect
condition.
B Check the delivery for completeness.
Component Qty Packaging
Boiler block 1 1 pallet
Boiler casing, factory­installed on the boiler block
Burner hood, factory­installed on the boiler block
Heat exchanger system, factory-installed on the boiler block
Oil burner with factory­installed burner door
Air supply hose, factory­installed
Siphon 1 1 bag
B-kit components:
1 1 foil
• Conversion nipple (1¼ " NPT)
• 30 psi safety valve
• Drain valve (¾ ")
• Pressure/temperature gauge
• Double nipple (1¼ " NPT × R1¼ )
• 90°-elbow (1¼ ” NPT)
• 90°-elbow (¾ " NPT)
• Screw set (for burner mounting)
• Adjustable feet
1)
package
1)
Logano GB125 BE US/CA - Subject to technical modifications.
Control panel 1 1 box
Tigerloop oil filter and
11 box
de-aerator
Technical documentation 1 bag
Tab. 1 Scope of delivery
1) Under the burner hood
7
2
Product description
2.8 Dimensions and specifications
Fig. 3 Connections and dimensions (measurements in inches)
VK = Boiler supply RK = Boiler return EL = Boiler drain (connection for drain valve)
6 720 649 309-01.1ITL
Dimensions and connections:
Boiler type Unit GB125/22 BE GB125/30 BE GB125/35 BE
Boiler sections 344 Rated heat output (gross output) 131/86 °F Rated heat output (net IBR rating) 131/86 °F Rated heat output/heating capacity (gross output)176/140 °F Rated heat output (net IBR rating)176/140 °F Rated thermal input/burner input MBtu/hr 81 108 131 AFUE % 91.2 91.1 91.0 Flue gas temperature 176/140 °F °F (°C) 176 (80) 176 (80) 192 (89) Boiler water content gal (l) 8.7 (35.6) 11.8 (44.9) 11.8 (44.9) Gas volume of combustion chamber and heat exchanger Oil consumption/oil firing rate gph (l/h) 0.60 (2.3) 0.75 (2.9) 0.95 (3.6) Flue gas resistance in. W.C.
Heat exchanger water pressure drop (DeltaT = 18 °F)
Maximum supply temperature Maximum operating pressure psi (bar) 44 (3) Maximum time constant of thermostat and manual reset high limit (STB)
1)
MBtu/hr 76 102 124
MBtu/hr 67 90 109
MBtu/hr 75 100 121
MBtu/hr 65 87 105
cu. ft.
(l)
(Pa)
ft. of head
(mbar)
°F (°C) 212 (100)
s 40
1.5 (42.9) 2.0 (57.9) 2.0 (57.9)
0.08" - 0.14" W.C. (20 - 35)
1.8' (54) 2.0' (60) 2.7' (81)
Tab. 2 Technical specifications
1) Safety limit (manual reset high limit, STB) Maximum permitted supply temperature = manual reset high limit (STB) – 32 °F Example: manual reset high limit (STB) = 212 °F, maximum possible supply temperature = 212 - 32 = 180 °F The safety limit must comply with the requirements applicable in your country.
8
Logano GB125 BE US/CA - Subject to technical modifications.
Product description
Boiler type Unit GB125/22 BE GB125/30 BE GB125/35 BE
Boiler overall length (L) Inches 37 1/2" 42 3/8" 42 3/8" Boiler block length (LK) Inches 25 3/4" 30 1/2" 30 1/2" Combustion chamber length Inches 16" 20 1/2" 20 1/2" Combustion chamber length Inches 10 5/8" Burner door thickness Inches 2 1/3" Distance between boiler feet (FL) Inches 16 1/8" 20 7/8" 20 7/8" Net weight
1)
lbs 423 503 503
Tab. 3 Dimensions, weight and other data for boilers with burners
1) Weight incl. packaging material approx. 6-8 % more.
2.9 Conditions for operation
Maintaining the specified operating conditions will enable the boiler to provide a high level of reliability and long service life. Some details relate only to operation with Logamatic control panels from Buderus.
CAUTION: Risk of system damage if operating conditions are not maintained.
Extreme divergence from the stated conditions may cause irreversible damage to individual components of the boiler.
B The information on the rating plate is
definitive.
2
2.9.1 General operating conditions
Operating conditions
Min. boiler water tempera-
ture
In combination with Logamatic control panel for variable low-temperature operating modes, such as Logamatic 2107.
No requirements. Operating
temperatures are safeguarded
by the Logamatic control
panel.
2)
Operating interruption
(complete boiler shutdown)
Automatically by Logamatic control
panel
Heating zone with
heating zone mixing valve
Not required but recommended with low-temperature heating system design 130/113 °F.
Required with:
• Radiant floor heating system
• Systems with large water capacity: > 115 gal/MBH (1 MBH = 100,000 Btu/hr)
1)
Min. return temperature
No requirements
Tab. 4 General operating conditions
1) A heating zone with a mixing valve improves controllability and is specifically recommended for systems with several heating zones.
2) If the control panel does not influence the heating zones or a heating zone actuating component (e.g. Pumplogic), the burner ON mode must reach an operating temperature of 122 °F within 10 min by restricting volume flow.
Logano GB125 BE US/CA - Subject to technical modifications.
9
2
Product description
2.9.2 Conditions for the boiler room and the environment
Operating conditions Notes – Requirement in greater detail
Temperature in the boiler room 40 to 104 °F
(5 to 40 °C) Relative humidity max. 90 % No condensation or precipitation inside the boiler room Dust/airborne particles Excessive dust inside the boiler room must be avoided when the boiler is operat-
ing, e.g.:
• Dust from building work
Combustion air supplied from outside must not be excessively loaded with dust or airborne seed; if necessary, air filters should be installed to prevent this:
• Air supply contaminated with dust from dirt roads and paths.
• Air supply contaminated with dust from production and processing facilities, e.g. quar­ries, mines, etc.
• Airborne particles from thistles and similar
Halogenated-hydrocarbon com­pounds
Small animals Prevent small animals from entering the boiler room, particularly through the air inlet vents –
Fire safety Maintain clearances between the boiler and flammable materials in accordance with local
Flooding In case of an acute risk of flooding, disconnect the boiler in time from its fuel and power
The combustion air must be free from halogen-hydrocarbon compounds.
• Identify the source of halogen-hydrocarbon compounds and seal it off. Where this is impossible, route combustion air from areas that are not contaminated by halogen­hydrocarbon compounds.
by installing screens.
regulations. A minimum clearance of 16” is required. Never store flammable materials or liq­uids in the vicinity of the boiler.
supply before water enters the room. Any general and burner components or control equip­ment that comes into contact with water must be replaced before starting up again.
Tab. 5 Boiler room and ambient conditions
2.9.3 Fuel conditions
Country All countries
Fuels #2 Fuel oil ASTM D396-05 Type 2
Approved for B5 Fuel Oil (5% biodiesel (B100) according ASTM D6751)
Remarks The burner may only be operated with the specified fuel. Clean and service once a year. Check that the entire
system functions properly at the same time. Immediately remedy faults.
Tab. 6 Country-specific fuels and remarks
2.9.4 Power supply conditions
Operating conditions Notes – Requirement in greater detail
Line voltage 110 – 120 V The outer casing/boiler must be grounded to protect people and in order to function correctly. Circuit breaker 10 A Frequency 60 Hz Protection class IP 40 (protected against contact by entry of foreign objects > 0.04 inches Ø (> 1 mm Ø ), no
waterproofing)
Tab. 7 Power supply
2.9.5 Conditions for hydraulic system and water quality
Operating conditions Notes – Requirement in greater detail
Operating pressure (above atmo­spheric) Permissible test pressure 45 – 58 psi
Safety temperature limitation by TR temperature controller Safety temperature limitation by man­ual reset high limit (STB) Water quality The heating system may only be filled and topped up with water of domestic water qual-
15 – 44 psi (1 to 3 bar)
(3 to 4 bar) 122 – 194 °F (50 to 90 °C)
212 °F
(100 °C)
Maximum 30 psi with the supplied safety valve.
ity. We recommend a pH level of 8.2 – 9.5.
Tab. 8 Hydraulics and water quality
10
Logano GB125 BE US/CA - Subject to technical modifications.
2.10 Disposal
B Dispose of boiler packaging in an environmentally-
responsible manner.
B All heating system components that have to be
replaced should be disposed of in environmentally­responsible manner at an authorized disposal site.
Product description
2
Logano GB125 BE US/CA - Subject to technical modifications.
11
3
Moving the boiler
3 Moving the boiler
This section details how to move the boiler safely.
CAUTION: Risk of system damage from impact shocks!
Fragile components could be damaged.
B Follow the transport instructions on the
packaging.
Protect connectors against contamination if the boiler is not immediately put into operation.
Dispose of packaging in an environmentally­responsible manner.
3.1 Reducing the boiler weight for handling purposes
If required, you can reduce the weight of the boiler by removing the burner hood and door.
B Unscrew the burner hood screws. B Lift burner hood slightly and pull forwards to remove. B Before removing the burner door: unplug the burner
plug from the burner controller.
Prevent the burner door from falling over and damaging the burner and burner tube.
B Unscrew two hex bolts at the sides. B Open the boiler door. B Lift the burner door off its hinges.
12
Fig. 4 Removing burner hood
7 747 019 141-04.1RS
Fig. 5 Removing the burner door
Logano GB125 BE US/CA - Subject to technical modifications.
3.2 Lifting and carrying the boiler
The boiler is secured to the pallet by 2 screws for transportation purposes.
The boiler can be held and carried at the grip positions shown (Fig. 6).
B Unscrew the transit screws.
WARNING: Risk of injury from carrying heavy loads!
B Always lift and move the equipment with
the assistance of another person using the grip positions shown.
3.3 Moving the boiler with hand truck
WARNING: Risk of injury if load is
inadequately secured during transportation! B Use suitable means of transportation, e.g.
the Buderus boiler hand truck with strap.
B Secure the load against falling.
Moving the boiler
Fig. 6 Lifting and carrying the boiler
3
7 747 019 141-05.1RS
You can order the boiler hand truck from your Buderus distributor.
Moving the boiler with hand truck (Fig. 7) B Place the hand truck (e.g. boiler trolley or sack truck) at
the back of the boiler.
B Boiler, securing on the hand truck. B Move the boiler to the installation location.
The boiler trolley can also be used to facilitate work on the underneath of the boiler, e.g. fitting the adjustable feet (Æ Chapter 4.3, page 16).
Fig. 7 Moving the boiler with a boiler hand truck
Logano GB125 BE US/CA - Subject to technical modifications.
13
4
Placing the boiler
4 Placing the boiler
This section describes how to install and place the boiler in the boiler room.
CAUTION: Risk of system damage due to freezing!
B Install the heating system in a frost-free
room.
4.1 Wall clearances
Wherever possible, position the boiler with the recommended wall clearances. Reducing the minimum clearances makes the boiler more difficult to access.
The boiler base or foundation must be perfectly flat and level.
The burner door is factory-installed with the hinges on the right. The burner door can be converted to left-hand closing.
Dimen­sion
A Recommended 40"
Minimum 27"
B Recommended 27"
Minimum 16"
C Recommended 28"
Minimum 20"
D Recommended 16"
Minimum 6"
L Æ Chapter 2.8, page 8
Tab. 9 Recommended and minimum wall clearances
(dimensions in inches).
The boilers are designed for a side clearance of 6". Where applicable, allow extra wall clearances for additional components such as DHW tank pipe connections, flue silencer, other flue components, etc.
WARNING: Risk of fire from flammable materials or liquids!
B Clearances less than 6" must comply with
local and statutory codes.
B Make sure that there is a sufficient
clearance between combustible materials and the chimney connection as specified by NFPA 31 (distance of 18 ").
B The floor must comply with the
requirements of NFPA 31.
Wall clearance
Fig. 8 Wall clearances in the boiler room (boiler
positioned on the right-hand side)
14
Logano GB125 BE US/CA - Subject to technical modifications.
4.2 Reversing the burner door
The burner door is factory-installed with the hinges on the right – the burner door opens to the right. You can change the burner door hinges over to the left-hand side if required to suit the installation site.
Requirement: the burner hood must have been removed first (Æ Chapter 3.1, page 12).
B Removing the burner door (Æ Chapter 3.1, page 12). B Unscrew the hex bolts [1] and remove the hinge pins
[2].
B Fix the hinge pins [2] on the left-hand side of the boiler
using the hex bolts.
B Unscrew the hex bolts [1] and remove the hinge barrels
[2].
B Fix the hinge barrels [2] on the left-hand side of the
burner door [3] using the hex bolts.
B Hang the burner door [3] by locating the hinge barrels
[2] on the hinge pins [4].
B Check that the heat exchanger baffles are placed
horizontally (Æ Chapter 6.3, page 32).
B Close the burner door [3] and secure with the two hex
bolts. Tighten the hex bolts evenly (approx. 90 lbs in) so that the burner door seals properly.
If the burner door hinges have been changed over to the left-hand side, the burner cable must be disconnected from the burner before opening the burner door.
Placing the boiler
12 21
7 747 019 141-08.1RS
Fig. 9 Reversing the burner door (boiler block
attachments)
1 Hex bolts 2 Hinges
3
2
1
4
7 747 019 141-09.1RS
4
5
Logano GB125 BE US/CA - Subject to technical modifications.
Fig. 10 Reversing the burner door (door attachments)
1 Hex bolts 2 Hinge barrels 3 Burner door 4 Hinges 5 Heat exchanger baffle plates
15
4
Placing the boiler
4.3 Mounting the adjustable feet (included with B-kit)
Level the boiler by turning the adjustable feet to prevent air pockets becoming trapped inside the boiler.
Requirement: the burner hood or burner door panel must have been removed first (Æ Chapter 3.1, page 12).
If the boiler is mounted on top of a horizontal hot water tank the adjustable feet are not used.
B Tilt the boiler with the aid of a hand truck or trolley (Æ
Chapter 3.3, page 13) or place a wooden batten underneath to jack it up.
B Screw in adjustable feet [2] ¼ " – 1/8". B Gently set the boiler down.
1
Fig. 11 Fitting the adjustable feet
(burner not shown)
1 Angle bracket 2 Adjustable feet
2
7 747 019 141-10.1RS
4.4 Positioning and leveling the boiler
B Position the boiler in its final location. B Level the boiler by rotating the adjustable feet as
required and using a level.
Protect boiler connections from damage and dirt if the boiler is not to be installed immediately.
7 747 019 141-11.1RS
Fig. 12 Leveling the boiler
16
Logano GB125 BE US/CA - Subject to technical modifications.
5 Installing the boiler
Installing the boiler
5
This section details how to install your boiler correctly. This involves the following steps:
• Flue pipe installation
• Providing air supply for combustion
• Making the water connections
• Making the electrical connections
• Connecting the fuel supply
DANGER: Risk of fatal injury from toxic flue gases!
B Never connect more than one boiler to a
flue system – regardless of whether the flue is vertical or horizontal.
B Common venting systems can cause
damage to property and personal injury.
B Do not route the flue system through
another flue system that is in use, e.g. a masonry chimney connected to a wood stove.
B Follow the instructions of the flue pipe
manufacturer.
The boiler must be installed by a trained and certified installer in accordance with all requirements of NFPA-31, "Installation of Oil­Burning Equipment". Installation must comply with all local and national codes applicable to the installation of oil-fired boilers.
5.1 Flue pipe installation
The overall burner air supply/boiler flue pipe system conforms to the types of oil combustion equipment listed in the table below.
Observe the national standards and regulations for operating oil-fired appliances.
Installa­tion type
HT-K
DO
GA-K
Tab. 10 Types of installation
Combustion air supply and flue system
I
or
II
or
III
or
Concentric supply air and flue pipe exiting
through external wall. Combustion air supply
and flue systems are part of the combustion
equipment.
Concentric supply air and flue gas routing
via roof. Combustion air supply and flue sys-
tems are part of the combustion equipment.
Concentric air/flue gas routing through a flue
inside a duct. The space around the vent
pipe is used for combustion air.
In Canada, the requirements of CSA/CGA­B139 Installation Code apply.
The GB125 boiler is approved for zero (0") clearance between its concentric vent pipe and combustibles.
Because of the tight construction of modern houses, this boiler must draw all air supply for combustion from outside (RLU).
Logano GB125 BE US/CA - Subject to technical modifications.
17
5
Installing the boiler
5.2 Test ports
Flue gas readings and combustion air temperature readings are taken exclusively at the dedicated testing ports.
Follow the directions in the instructions for the Logatop BE oil burner.
1
2
6 720 649 309-03.1ITL
Fig. 13 Installing the flue/air connector (included with
the venting system)
1 Air intake test port 2 Flue gas test port
18
Logano GB125 BE US/CA - Subject to technical modifications.
Choice of installation site for side-wall flue termination
Choosing the right location for the terminal is critical to proper functioning of the appliance. As well as the minimum clearances (Æ Fig. 14), the following rules must be observed:
Concentric wall terminations on the house wall
Installing the boiler
.
5
at least 1 ft above grade and snow line
Concentric wall terminations on the house wall
must be at least 3 ft above forced air inlets within 10 ft.
Fig. 14 Minimum clearances for side wall terminations
1. The termination should not face the prevailing wind direction.
2. The termination must be installed in such a way that the flue gases can disperse freely without re-entering the building.
3. The termination must be at least 2 ft from adjacent buildings and it must not be possible for the flue gas to enter adjacent buildings.
4. Where the building adjoins public walkways, the termination must be located at least 7 ft above ground. Make sure that freezing condensate does not constitute a hazard.
5. The termination must never be located below building overhangs, roof eaves, porches, enclosed spaces or lower parts of the building that could prevent unrestricted outflow of the flue gases.
6. The termination must never be located within 3 ft of inside corners of buildings and never less than 2 ft from outside corners of buildings.
7. If there is a fan-assisted air intake vent within 10 ft, the termination must be at least 3 ft above it.
.
Forced Air Inlet
Concentric wall terminations on the house wall
Gravity Air Inlet
8. The termination must be at least 4 ft below, 1 ft above or 4 ft horizontally from doors, windows or air inlet vents.
9. The termination must be at least 1 ft above ground and snow line, and protected from falling and accumulating snow, ice, leaves or debris.
10. The termination should be at least 3 ft from any type of building opening, oil tank filling or venting apparatus, and 6 ft from gas meters and similar equipment.
11. The position of the termination should be chosen so that the last horizontal section of pipe slopes downwards to the inside by ¼ " per ft. The flue terminal itself must also be inclined at ¼ " per ft to the inside so that any condensate drains inwards.
6 720 641 158-20.1TL
Logano GB125 BE US/CA - Subject to technical modifications.
19
5
Installing the boiler
5.3 Installation options
The GB125 boiler is approved with the following flue gas systems available from Buderus:
Types of installation Description
I
Concentric air supply and
or
flue pipe exiting through
HT-K
DO
external wall.
II
Concentric supply air and
or
flue gas routing via roof.
Horizontal direct vent concentric combustion air and venting pipe system.
Vertical concentric supply air and flue gas routing.
III
Concentric air/flue gas
or
routing through a flue
GA-K
inside a duct.
Tab. 11 Installation options
To prevent reverse flow of flue gas into the air intake even with wind influence, the included wall terminations must be used.
Table 12, page 21 shows the maximum permissible vent length for the different types of systems.
Flue pipe inside an existing masonry chimney similar to a liner. Chimney chase used as a raceway to bring in combustion air. Concentric supply air and flue gas routing from the chimney to the boiler.
Installation type III or GA-K may not be suitable for homes with a double flue chimney where the second flue is used with a second combustion appliance.
20
Logano GB125 BE US/CA - Subject to technical modifications.
Loading...
+ 44 hidden pages