Buderus GB142-60, GB142-45, GB142-30 Instruction

Propane Conversion Kit Instruction
Condensing gas boiler
GB142-24/30/45/60
7215 0100 (10/2007) US/CA
For the contractor
Please read these instructions carefully!
Required Input Rates
This kit and instructions are for converting the GB142 model boilers from Natural Gas to Liquid Propane.
Notice! Save these instructions for later use.
GB142-24 84,800 btu/hr
GB142-30 106,000 btu/hr
GB142-45 160,900 btu/hr
GB142-60 214,800 btu/hr
WARNING!
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer's instructions and all applicable codes and requirements of the authority having jurisdiction. The information in these instructions must be followed to minimize the risk of fire or explosion or to prevent property dam­age, personal injury or death. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted boiler is checked as specified in the manufac­turer’s instructions supplied with the kit.
CAUTION!
The gas supply shall be shut off prior to disconnecting the elec­trical power, before proceeding with the conversion.
Contents
GB142-15/24/30/45/60 - We reserve the right to make any changes due to technical modifications!2
Contents 3
1 Safety considerations 3
1.1 Application purpose 3
1.2 Hazard definitions 3
1.3 Observe the following symbols 3
2 Parts list for converting the boiler
to propane 4
3 LP conversion 5
3.1 Testing for gas leaks 6
3.2 Inlet gas pressure 7
3.3 Checking and adjusting the gas/air ratio 8
3.4 Carrying out a tightness test in operating conditions 9
3.5 Measuring the carbon monoxide content (CO) 10
3.6 Lighting Instructions 10
4 Operating Instructions 11
1 Safety considerations
GB142-24/30/45/60 - We reserve the right to make any changes due to technical modifications! 3
Contents
1 Safety considerations
For use in Canada the conversion kit shall be carried out in accordance with the requirements of the provin
­cial authorities having jurisdiction and in accordance with the requirements of the CAN-B149.1 and CAN1-B149.2 Installation Code. See also E.I.V.
Please observe the following safety instructions.
1.1 Application purpose
This kit and instructions are for converting the GB142­24/30/45/60 from Natural gas to Liquid Propane.
1.2 Hazard definitions
The following defined terms are used throughout the documentation to bring attention to the presence of hazards of various risk levels. Notices give important information concerning the operation of the product.
1.3 Observe the following symbols
DANGER
Indicates the presence of hazards that will cause severe personal injury, death or substantial property damage.
WARNING
Indicates the presence of hazards that can cause severe personal injury, death or substantial property damage.
CAUTION
Indicates presence of hazards that will or cause minor personal injury or property damage.
CAUTION
Risk of electric shock.
Indicates presence of hazards due to elec­tric shock.
NOTICE
Indicates special instructions on installa­tion, operation or maintenance that are important but not related to personal injury or property damage.
DANGER
due to explosion of gas.
z Work only on gas components when
you have a license to do so.
z Note that the assembly of gas and vent
connections, the initial start-up, the electrical connections, the maintenance and service can only be performed by a licensed service contractor or techni
-
can.
DANGER
due to electricity.
z Prior to doing any work on the heating
system, disconnect all electrical power to the appliance at the emergency switch.
z It is NOT sufficient to shut off only the
appliance control!
2 Parts list for converting the boiler to propane
GB142-24/30/45/60 - We reserve the right to make any changes due to technical modifications!4
2 Parts list for converting the boiler to propane
Conversion kit propane for the 24/30 kW # 76687 includes:
orifice # 7099016 (dia. 3.35 mm / 0.131 inch)
2 o-rings
bag
these instructions
label to be filled out and affixed to the boiler.
Conversion kit propane for the 45 kW # 76688 includes:
orifice # 7099935 (dia. 4.05 mm / 0.158 inch)
2 o-rings
bag
these instructions
label to be filled out and affixed to the boiler.
Conversion kit propane for the 60 kW # 7746900156 includes:
orifice # 76690 (dia. 5.40 mm / 0.213 inch)
2 o-rings
bag
these instructions
label to be filled out and affixed to the boiler.