Bryant Series A Service And Maintenance Procedures Manual

Page 1
service and
352MAV
maintenance procedures
DELUXE 4-WAY MULTIPOISE 2-SPEED, 2-STAGE DIRECT-VENT CONDENSING GAS FURNACE
NOTE: Read the entire instruction manual before starting the installation.
A93040
Series A
Cancels: New SP05-48
3-01
EFFICIENCY RATING CERTIFIED
r
o
p
C
o
r
r
e
i
r
r
a
C
R
E
G
I
S
I
T
S
O
9
0
REGISTERED QUALITY SYSTEM
a
t
i
o
n
CERTIFIED
®
E
R
0
1
M
R
I
F
D
E
3
8
8
2
A
#
TABLE OF CONTENTS
SAFETY CONSIDERATIONS.....................................................1
INTRODUCTION..........................................................................2
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS........2
CARE AND MAINTENANCE.....................................................2
Cleaning and/or Replacing Air Filter.......................................3
Cleaning Burners ......................................................................4
Cleaning Heat Exchangers........................................................5
Flushing Collector Box and Drainage System ........................7
Electrical Controls and Wiring.................................................8
Checking Heat Tape Operation (If Applicable) ......................8
Winterizing................................................................................9
WIRING DIAGRAM.....................................................................9
TROUBLESHOOTING .................................................................9
Status Codes..............................................................................9
Component Test........................................................................9
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment. Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations
must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety codes including the National Fuel Gas Code (NFGC) NFPA 54-1999/ANSI Z223.1-1999 and the Installation Standards, Warm Air Heating and Air Conditioning Systems (NFPA 90B) ANSI/NFPA 90B. In Canada, refer to the CAN/CGA-B/49.1- and
Highly Efficient Gas Furnace
A01060
Fig. 1—Multipoise Furnace in Upflow Orientation
.2-M00 National Standard of Canada, Natural Gas and Propane Installation Codes (NSCNGPIC). Wear safety glasses and work gloves. Have a fire extinguisher available during start-up and adjustment procedures and service calls.
—1—
Page 2
This is the safety-alert symbol . When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAU­TION. These words are used with the safety-alert symbol. DAN­GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING: The ability to properly perform mainte-
nance on this equipment requires certain knowledge,
mechanical skills, tools, and equipment. If you do not
possess these, do not attempt to perform any maintenance
on this equipment other than those procedures recom-
mended in the Users Manual. FAILURE TO FOLLOW
THIS WARNING COULD RESULT IN POSSIBLE
DAMAGE TO THIS EQUIPMENT, SERIOUS PER-
SONAL INJURY, OR DEATH.
WARNING: Never store anything on, near, or in contact
with the furnace, such as:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds, plastic or plastic containers, gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids.
3. Paint thinners and other painting compounds, paper bags, or other paper products. A failure to follow this warning can cause corrosion of the heat exchanger, fire, personal injury, or death.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
INTRODUCTION
These instructions are written as if the furnace is installed in an upflow application. An upflow furnace application is where the blower is located below the combustion and controls section of the furnace, and conditioned air is discharged upward. Since this furnace can be installed in any of the 4 positions shown in Fig. 2, you must revise your orientation to component location accord­ingly.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
AIRFLOW
UPFLOW
HORIZONTAL
RIGHT
AIRFLOW
A93041
AIRFLOW
HORIZONTAL
LEFT
DOWNFLOW
AIRFLOW
Fig. 2Multipoise Orientation
2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a persons hand during grounding will be satisfactorily discharged.
3. After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch un­grounded objects, etc.).
4. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touch­ing control or wires.
5. Use this procedure for installed and uninstalled (un­grounded) furnaces.
6. Before removing a new control from its container, dis­charge your bodys electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible equip­ment failure, it is essential that maintenance be performed on this equipment. Consult your local dealer about proper maintenance frequency and the availability of a maintenance contract.
CAUTION: Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electro­static potential.
1. Disconnect all power to the furnace. DO NOT TOUCH
THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODYS ELECTROSTATIC CHARGE TO GROUND.
WARNING: Turn off the gas and electrical supplies to the unit before performing any maintenance or service. Follow the operating instructions on the label attached to the furnace. Failure to follow this warning could result in personal injury or death.
The minimum maintenance that should be performed on this equipment is as follows:
1. Check and clean or replace air filter each month as required.
2. Check blower motor and wheel for cleanliness each heating or cooling season.
3. Check electrical connections for tightness and controls for proper operation each heating season. Service as necessary.
2
Page 3
WASHABLE FILTER
FILTER SUPPORT
FILTER RETAINER
WASHABLE FILTER OR DISPOSABLE MEDIA FILTER IN FILTER CABINET
Fig. 3Bottom Filter Arrangement
A00232
4. Check for proper condensate drainage. Clean as necessary.
5. Check for blockages in combustion-air and vent pipes annually.
6. Check burners for cleanliness annually.
CAUTION: Personal injury could result from sharp metal edges, etc. Use care when removing parts.
I. CLEANING AND/OR REPLACING AIR FILTER
The air filter arrangement may vary depending on the application or orientation.
WARNING: Never operate unit without a filter or with the blower access door removed. Failure to follow this warning could result in a fire, personal injury, or death.
NOTE: If the filter has an airflow direction arrow, the arrow must point toward the blower.
To clean or replace filters, proceed as follows: If filter is installed in filter cabinet adjacent to furnace:
1. Turn off electrical supply to furnace.
2. Remove filter cabinet door.
3. Slide filter out of cabinet.
4. If equipped with permanent, washable filter, clean filter by spraying cold tap water through filter in opposite direction of airflow. Rinse filter and let dry. Oiling or coating of filter is not recommended.
5. If equipped with factory specified disposable media filter, replace only with media filter having the same part number and size.
6. Slide filter into cabinet.
7. Replace filter cabinet door.
8. Turn on electrical supply to furnace.
If filter is installed in furnace blower compartment:
1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access door.
3. Release filter retainer wire. (See Fig. 3 and 4.)
4. Slide filter out of furnace.
WASHABLE
FILTER
IN FURNACE
FILTER RETAINER
WASHABLE FILTER OR DISPOSABLE MEDIA FILTER IN FILTER CABINET
Fig. 4Filter Installed for Side Inlet
A00233
5. Furnaces are equipped with permanent, washable filter(s). Clean filter by spraying cold tap water through filter in opposite direction of airflow.
6. Rinse filter and let dry. Oiling or coating of filter is not recommended.
7. Slide filter into furnace.
8. Recapture filter retainer wire.
9. Replace blower access door and main furnace door.
10. Turn on electrical supply to furnace.
II. BLOWER MOTOR AND WHEEL MAINTENANCE
To ensure long life, economy, and high efficiency, clean accumu­lated dirt and grease from blower wheel and motor annually.
The inducer and blower motors are pre-lubricated and require no additional lubrication. These motors can be identified by the absence of oil ports on each end of the motor.
The following items should be performed by a qualified service technician.
Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access door.
3. Disconnect wires.
All factory wires can be left connected, but field thermostat connections may need to be disconnected depending on their length and routing.
4. Remove control box mounting screws and position control box, transformer, and door switch assembly to right side of furnace casing.
5. If condensate trap is located in left- or right-hand side of furnace casing, proceed to item 6, otherwise remove trap and tubing as described below:
a. Disconnect field drain connection from condensate trap. b. Disconnect drain and relief port tubes from condensate
trap.
c. Remove condensate trap from blower shelf.
6. Remove screws securing blower assembly to blower shelf and slide blower assembly out of furnace.
7. Clean blower wheel and motor by using a vacuum with soft brush attachment. Be careful not to disturb balance weights (clips) on blower wheel vanes. Do not bend wheel or blades as balance will be affected.
3
Page 4
8. If greasy residue is present on blower wheel, remove wheel from the blower housing and wash it with an appropriate degreaser. To remove wheel:
a. Mark blower wheel location on shaft before disassembly
to ensure proper reassembly.
b. Loosen setscrew holding blower wheel on motor shaft.
NOTE: Mark blower mounting arms and blower housing so each arm is positioned at the same hole location during reassembly.
c. Mark blower wheel orientation and cutoff plate location
to ensure proper reassembly.
d. Remove screws securing cutoff plate and remove cutoff
plate from housing.
e. Remove bolts holding motor mounts to blower housing
and slide motor and mounts out of housing. Disconnect capacitor and ground wire attached to blower housing before removing motor.
f. Remove blower wheel from housing.
CAUTION: The blower wheel should not be dropped or bent as balance will be affected.
g. Clean wheel per instructions on degreaser cleaner.
9. Reassemble motor and blower wheel by reversing items 8b through 8f. Ensure wheel is positioned for proper rotation.
10. Reinstall blower assembly in furnace.
11. Reinstall control box, transformer, and door switch assem­bly on blower shelf.
12. Reinstall condensate trap and tubing if previously removed. a. Reinstall condensate trap in hole in blower shelf. b. Connect condensate trap drain tubes. See Fig. 8 or tubing
diagram on main furnace door for proper tube location. (1.) Connect 1 tube (blue or blue and white striped)
from collector box.
(2.) Connect 1 tube (violet or unmarked) from inducer
housing.
(3.) Connect 1 tube (relief port, green or pink) from
collector box.
NOTE: Refer to Table 1 for motor speed lead relocation if leads were not identified before disconnection.
13. Reconnect wires.
Refer to furnace wiring diagram and connect thermostat leads if previously disconnected. (See Fig. 15.)
14. Turn on electrical supply. Manually close blower access door switch. Use a piece of tape to hold switch closed. Check for proper rotation and speed changes between heating and cooling by jumpering R-to-W/W1, R-to­W/W1-and-W2 and then R-to-Y/Y2 on control thermostat terminals. (See Fig. 11.)
WARNING: Blower access door switch opens 115-v power to control. No component operation can occur. Caution must be taken when manually closing this switch for service purposes. Failure to follow this warning could result in personal injury or death.
15. If furnace is operating properly, release blower access door switch, replace blower access door, and replace main furnace door.
III. CLEANING BURNERS
The following items should be performed by a qualified service technician. If the burners develop an accumulation of light dirt or dust, they may be cleaned by using the following procedure:
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Remove burner box cover.
CELL
PANEL
MANIFOLD MOUNTING SCREW
MANIFOLD
TABLE 1SPEED SELECTION
COLOR SPEED AS SHIPPED
White Common C Black High Cool
Yellow Med-High SPARE
Orange Med High-Gas Heat
Blue Med-Low Spare/High-Gas Heat
Red Low* Low-Gas Heat
* Continuous blower speed. Available on 5-speed blowers only.
CAUTION: Heating air speed selection MUST be ad­justed to provide proper temperature rise as specified on the rating plate. Failure to adjust the heating speed may shorten heat exchanger life.
c. Connect field drain to condensate trap.
NOTE: Ensure tubes are not kinked or pinched, as this will affect operation.
OM
GAS VALVE REGULATOR FITTING
GAS VALVE
A96304
Fig. 5Burner Box Assembly
4. Using backup wrench, disconnect gas supply pipe from gas valve.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
5. Remove wires from gas valve. Note location for reassem­bly.
6. Remove burner box pressure tube from gas valve regulator fitting.
7. Remove screws that secure manifold to burner box. (See Fig. 5.)
4
Page 5
8. Remove manifold, orifices, and gas valve as 1 assembly.
9. Remove screws attaching burner assembly in burner box.
10. Remove burner assembly from burner box.
NOTE: All burners are attached to burner bracket and can be removed as 1 assembly.
11. Clean burners with soft brush and vacuum.
12. Reinstall manifold, orifice, and gas valve assembly in burner box. Ensure manifold seal grommet is installed properly and burners fit over orifices.
13. Reconnect wires to gas valve. Refer to furnace wiring diagram for proper wire location.
14. Reinstall burner box pressure tube to gas valve regulator fitting.
15. Reinstall gas supply pipe to gas valve using backup wrench on gas valve to prevent rotation and improper orientation.
NOTE: Use propane gas resistant pipe dope to prevent gas leaks. DO NOT use Teflon tape.
WARNING: Gas valve switch or knob MUST be facing forward or tilted upward. Failure to follow this warning could result in property damage, personal injury, or death.
16. Replace burner box cover.
17. Turn on gas and electrical supplies to furnace.
18. Check for gas leaks.
PRIMARY HX INLET OPENINGS
A96305
Fig. 6Cleaning Inlet Openings of Primary Heat
Exchangers
RTV
WARNING: Never use matches, candles, flame, or other sources of ignition to check for gas leakage. Use a soap-and-water solution. Failure to follow this warning could result in a fire, personal injury, or death.
19. Replace main furnace door.
IV. CLEANING HEAT EXCHANGERS
The following items should be performed by a qualified service technician.
A. Primary Heat Exchangers
If the heat exchangers get an accumulation of light dirt or dust on the inside, they may be cleaned by the following procedure:
NOTE: If the heat exchangers get a heavy accumulation of soot and carbon, both the primary and secondary heat exchangers should be replaced rather than trying to clean them thoroughly due to their intricate design. A build-up of soot and carbon indicates that a problem exists which needs to be corrected, such as improper adjustment of manifold pressure, insufficient or poor quality combustion air, improper vent termination, incorrect size or damaged manifold orifice(s), improper gas, or a restricted heat exchanger (primary or secondary). Action must be taken to correct the problem.
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and hazardous operation.
3. Disconnect wires or connectors to rollout switch, gas valve, ignitor, and flame sensor.
4. Disconnect combustion-air intake pipe from intake housing.
PAM
A93087
Fig. 7Combustion-Air Intake Housing Gasket Repair
5. Remove the pressure switch tube from intake housing.
6. Remove screws attaching intake housing to burner box, and rotate intake housing away from burner box for removal.
7. Using backup wrench, disconnect gas supply pipe from gas valve.
8. Disconnect pressure tubing from gas valve.
9. Remove 2 screws attaching top filler panel and rotate upwards to gain access to screws attaching burner box to cell panel.
10. Remove screws attaching burner box to cell panel. (See Fig.
5.)
NOTE: Burner box cover, manifold, gas valve, and burner assembly should be removed as 1 assembly.
11. Clean heat exchanger openings with a vacuum and a soft brush. (See Fig. 6.)
NOTE: After cleaning, inspect the heat exchangers to ensure they are free of all foreign objects that may restrict flow of combustion products.
12. Reverse items 4 through 10 for reassembly.
WARNING: The ground wire from the gas valve MUST be attached to the burner box attachment screw. Failure to attach this ground wire to an adequate casing ground will cause the furnace control to lock out.
NOTE: Be sure burner box gasket is installed between burner box and cell panel. If gasket is damaged, replace it.
5
Page 6
TUBE ROUTING
Furnace is shipped from factory in upflow configuration. Pressure tube and drain tube routing MUST match the diagrams below.
Condensate Trap; Factory Inst alled
in Blower Shelf
(Blower access panel remo ved)
COLLECTOR BOX TUBE
(PINK)
COLLECTOR BOX TUBE
(GREEN)
INDUCER HOUSING (MOLDED) DRAIN TUBE
(BEHIND COLLECTOR BOX DRAIN TUBE)
COLLECTOR BOX DRAIN TUBE
(BLUE )
FIELD-INSTALLED
FACT OR Y-SUPPLIED DRAIN TUBE
COUPLING (LEFT DRAIN OPTION)
FIELD-INSTALLED FACTORY-SUPPLIED
DRAIN TUBE
Condensate Trap on
LEFT Side
CAP
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRIPED)
COLLECTOR BOX EXTENSION TUBE
CONDENSA TE TRAP
BURNER ENCLOSURE PRESSURE
REFERENCE TUBE ASSEMBLY
INDUCER HOUSING DRAIN TUBE (VIOLET)
Tube location when used on
HORIZONTAL - LEFT ap plic ation
AUXILIARY "J" BOX
PLUG
CAP
BURNER ENCLOSURE
PRESSURE REFERENCE
TUBE ASSEMBL Y
COLLECTOR BOX
EXTENSION TUBE
CONDENSA TE TRAP
COLLECTOR BOX EXTENSION DRAIN TUBE
NOTE:
1. All tubing must be connected securely and routed to avoid kinks and traps.
2. Pressure tubing must alwa ys s lope away from pressure switc h to collector box connection as sho wn.
3. HORIZONTAL-LEFT installations require the collector box pres sure tube to be relocated between the inducer housing and the blowershelf to prevent a trap. Refer to the Installation Instructions for further details.
Tube location when used in UPFLOW application
BURNER ENCLOSURE
PRESSURE REFERENCE
TUBE ASSEMBLY
CAP
PLUG
COLLECTOR BOX DRAIN
TUBE
(BLUE & WHITE STRIPED)
CONDENSATE TRAP
FIELD-INSTALLED
FACT ORY- SUPPLIED
DRAIN TUBE COUPLING
(RIGHT DRAIN OPTION)
FIELD-INSTALLED FACT OR Y-SUPPLIED 1/2-IN. CPVC STREET ELBOWS (2)
FOR LEFT DRAIN OPTION
COLLECTOR BOX TUBE
(PINK)
COLLECTOR BOX TUBE (GREEN)
COLLECTOR BOX DRAIN TUBE
(BLUE )
CONDENSATE TRAP
Tube loca tio n when us ed in DOWNFLOW application
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX DRAIN TUBE
DRAIN TUBE
COUPLING
PLUGGED END
PLUG
COLLECTOR BOX EXTENSION TUBE
COLLECTOR BOX
TUBE (PINK)
(BLUE & W HITE STRIPED)
COLLECTOR BOX
TUBE (GREEN)
INDUCER HOUSING
DRAIN TUBE
(VIOLE T )
COLLECTOR BOX
COLLECTOR BOX TUBE (PINK)
RELOCATE TUBE BETWEEN BLOWER
SHELF AND INDUCER HOUSING FOR
DRAIN TUBE (BLUE)
060 AND 080 HEA TING INPUT
FURNACES
COLLECTOR BOX DRAIN
TUBE
(BLU E & WH ITE STRIP ED )
INDUCER HOUSING DRAIN
TUBE (VIOLET)
DRAIN TUBE COUPLING
DRAIN TUBES ROUTED IN
FRONT OF GAS VALVE
COLLECTOR BOX DRAIN TUBE
(BLUE)
PLUG
CAP
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX DRAIN TUBE
(BLUE AND W HITE STRIPED)
Tube location when used on
HORIZONTAL - RIGHT application
COLLECTOR BOX EXTENSION TUBE
COLLECT OR BOX TUBE (PINK)
INDUCER HOUSING DRAIN TUBE (VIOLET)
Condensate Trap on LEFT
CAP
PLUG
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRIPED)
INDUCER HOUSING DRAIN TUBE
PLUG
CAP
COLLECTOR BOX DRAIN TUBE
COLLECTOR BOX TUBE
COLLECTOR BOX TUBE
COLLECTOR BOX EXTENSION TUBE
BURNER ENCLOSURE PRESSU
CONDENSATE TRAP
COLLECTOR BOX
GAS VALVE
EXTENSION DRAIN TUBE
AUXILIARY "J" BOX RELOCATED HERE
COLLECTOR BOX EXTENSION TUBE
CONDENSA TE TRAP
326476-201 REV. B (lit-bottom)
Side Optional
BURNER ENCLOSURE
PRESSURE REFERENCE
TUBE ASSEMBLY
(VIOLET)
Condensate Trap on
RIGHT Side
T
(BLUE)
(PINK)
(GRE EN)
REFERENCE TUBE ASSEMBL
BURNER ENCLOSURE
PRESSURE REFERENCE
TUBE ASSEMBL Y
Fig. 8Furnace Pressure and Draining Tube Diagram
NOTE: Inspect combustion-air intake housing. If foamed gasket
was removed, check for any damage. If gasket is damaged in any way, it must be repaired. To repair, remove damaged gasket section, apply sealant releasing agent such as PAM cooking spray or equivalent (must not contain corn or canola oil, aromatic or halogenated hydrocarbons or inadequate seal may occur) to burner box and apply a small bead of G.E. RTV 162, G.E. RTV 6702, or Dow-Corning RTV 738 sealant to edge of combustion-air intake housing. (See Fig. 7.)
13. Refer to furnace wiring diagram and reconnect wires to rollout switch, gas valve, ignitor, and flame sensor.
14. Reconnect pressure switch tubes to gas valve and intake housing. Refer to tube routing label on main furnace door or Fig. 8 for proper tube location. Be sure tubes are not kinked.
15. Turn on gas and electrical supplies to furnace.
A01052
16. Check furnace operation through 2 complete heat operating cycles. Look through sight glass in burner enclosure to check burners. Burner flames should be clear blue, almost transparent. (See Fig. 9.)
17. Check for gas leaks.
WARNING: Never use matches, candles, flame, or other sources of ignition to check for gas leakage. Use a soap-and-water solution. Failure to follow this warning could result in a fire, personal injury, or death.
18. Replace main furnace door.
6
Page 7
B. Secondary Heat Exchangers NOTE: The condensing side (inside) of the secondary heat
exchangers CANNOT be serviced or inspected. A small number of bottom outlet openings can be inspected by removing the inducer assembly. See Flushing Collector Box and Drainage System section for details on removing inducer assembly.
BURNER FLAME
BURNER
MANIFOLD
A89020
Fig. 9Burner Flame
V. FLUSHING COLLECTOR BOX AND DRAINAGE SYS­TEM
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Disconnect inducer motor and pressure switch wires or connectors.
4. Disconnect pressure switch tubes.
5. Disconnect vent pipe from inducer housing outlet by loosening coupling clamp on inducer outlet.
6. Disconnect drain tube from inducer housing. (See Fig. 8.)
7. Remove inducer housing assembly by removing 4 bolts attaching assembly to cell panel.
8. Flush inside of collector box with water until discharge from condensate trap is clean and runs freely.
NOTE: Ensure the drain tube disconnected from the inducer housing is higher than the collector box opening or water will flow out tube.
9. Inspect inside area of collector box for any pieces of foreign materials and remove if present.
CAUTION: DO NOT use wire brush or other sharp object to inspect or dislodge materials in secondary heat exchangers as failure of the secondary heat exchanger will occur. Flush with water only.
10. Reassemble inducer assembly by reversing items 5-7. Tighten vent coupling clamp screw(s) to 15 in.-lb of torque.
NOTE: If seal between the inducer housing and the collector box is damaged in any way, it must be repaired. To repair, apply sealant releasing agent such as PAM cooking spray or equivalent (must not contain corn or canola oil, aromatic or halogenated hydrocarbons or inadequate seal may occur) to inducer housing. (See Fig. 10.) Apply a small bead of G.E. RTV 162, G.E. RTV 6702, or Dow-Corning RTV 738 sealant to groove in collector box.
11. Refer to furnace wiring diagram and reconnect wires to inducer motor and pressure switches or connectors.
PAM
RTV
A93081
Fig. 10Gasket on Collector Box
12. Reconnect pressure tubes to pressure switches. See diagram on main furnace door for proper location of tubes. Be sure tubes are not kinked. (See Fig. 8.)
13. Turn on gas and electrical supplies to furnace.
14. Check furnace operation through 2 complete heat operating cycles. Check area below inducer housing, vent pipe, and condensate trap to ensure no condensate leaks occur. If leaks are found, correct the problem.
15. Check for gas leaks.
WARNING: Never use matches, candles, flame, or other sources of ignition to check for gas leakage. Use a soap-and-water solution. Failure to follow this warning could result in a fire, personal injury, or death.
16. Replace main furnace door.
VI. SERVICING HOT SURFACE IGNITOR
The ignitor does NOT require annual inspection. Check ignitor resistance before removal.
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Disconnect ignitor wire connection.
4. Check ignitor resistance. a. Using an ohm meter, check resistance across both ignitor
leads in connector. b. Cold reading should be between 45 ohms and 90 ohms. c. If ohm reading is higher than 110 ohms, ignitor is
cracked and must be replaced.
5. Remove ignitor assembly.
CAUTION: Allow ignitor to cool before removal. Nor­mal operation temperatures exceed 2000°.
a. Do not remove ignitor from bracket while assembly is in
furnace. Using a 1/4 in. nutdriver, remove screw secur-
ing bracket and ignitor assembly to bottom of burner
7
Page 8
115-V
SINGLE
PHASE
115-V
FIELD-SUPPLIED
DISCONNECT
SWITCH
FURNACE CONTROL
CENTER
FIVE
WIRE
THREE-WIRE
HEATING
ONLY
AUXILIARY J-BOX
NOTE 5
TERMINAL
BLOCK
WCR GY
W/W1
NOTE
W2
3
R
G
C
Y/Y2
24-V
NOTE 1
NOTES:
1.
2.
3.
4.
5.
Fig. 11Field Wiring
FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-, 208/230-, 460-V WIRING
THERMOSTAT TERMINALS
GND
GND
CONDENSING
UNIT
TWO WIRE
Connect Y or Y/Y2 terminal as shown for proper cooling operation. Proper polarity must be maintained for 115-v wiring. Use W2 with 2-stage thermostat when zoning. If any of the original wire, as supplied, must be replaced, use same type or equivalent wire. Some thermostats require a "C" terminal connection as shown.
FIELD-SUPPLIED
DISCONNECT
208/230- OR
460-V
THREE PHASE
GND
208/230-V
SINGLE
PHASE
GND
A98325
box. The screw in the bracket is always located toward outside of burner box. The screw may be hidden by inlet box or inlet pipe, but can be removed without removing either. After removing screw, slide ignitor and bracket toward outside of burner box and pull straight out.
CAUTION: The ignitor is fragile. DO NOT allow it to hit the side of the burner box opening while removing or replacing it.
b. Inspect ignitor for a white area indicating a crack may be
present. If found, replace ignitor.
NOTE: A small crack cannot be seen on a new ignitor. After a period of operation, a white area will be visible around the crack.
c. If replacement is required, replace ignitor on ignitor
bracket external to furnace to avoid damage as the silicon portion is very brittle and will easily crack or shatter.
d. To remove ignitor from ignitor bracket, remove screw
holding ignitor ceramic block to bracket and pull ce­ramic block out of bracket.
6. To replace ignitor/ignitor assembly, reverse items 5a through 5d.
7. Reconnect ignitor wire connection.
8. Turn on gas and electrical supplies to furnace.
9. Verify ignitor operation by initiating control board self-test feature or by cycling thermostat.
10. Replace main furnace door.
VII. ELECTRICAL CONTROLS AND WIRING
CAUTION: There may be more than 1 electrical supply
to the unit. Check accessories and cooling unit for additional electrical supplies.
The electrical ground and polarity for 115-v wiring must be maintained properly. Refer to Fig. 11 for field wiring information and to Fig. 15 for unit wiring information. NOTE: If the polarity is not correct, the STATUS LED on the control will flash rapidly and prevent the furnace from operating. The control system also requires an earth ground for proper operation of the control and flame sensing. The 24-v circuit contains an automotive-type, 3-amp fuse located on the control center. (See Fig. 11.) Any direct shorts of the 24-v wiring during installation, service, or maintenance will cause this fuse to blow. If fuse replacement is required, use ONLYa3amp fuse. The control LED will display status code 24 when fuse needs to be replaced. With power to the unit disconnected, check all electrical connec­tions for tightness. Tighten all screws on electrical connections. If any smoky or burned connections are found, disassemble the connection, clean all parts, strip wire, and reassemble properly and securely. Reconnect electrical supply to unit and observe unit through 1 complete operating cycle. Electrical controls are difficult to check without proper instrumentation; if there are any discrepancies in the operating cycle, contact your dealer and request service.
VIII. CHECKING HEAT TAPE OPERATION (IF APPLI­CABLE)
In applications where the ambient temperature around the furnace is 32° or lower, freeze protection measures are required. If this application is where heat tape has been applied, check to ensure it will operate when low temperatures are present.
8
Page 9
NOTE: Heat tape, when used, should be wrapped around the condensate drain trap and drain line. There is no need to use heat tape within the furnace casing. Most heat tapes are temperature activated, and it is not practical to verify the actual heating of the tape. Check the following:
1. Check for signs of physical damage to heat tape such as nicks, cuts, abrasions, gnawing by animals, etc.
CAUTION: If this furnace is installed in an uncondi­tioned space where the ambient temperatures may be 32°F or lower, freeze protection measures must be taken.
2. Check for discolored heat tape insulation. If any damage or discolored insulation is evident, replace heat tape.
3. Check that heat tape power supply circuit is on.
IX. WINTERIZING
CAUTION: Do not use ethylene glycol (Prestone II
antifreeze/coolant or equivalent automotive type). Failure of plastic components will occur.
WIRING DIAGRAM
EAC - ELECTRONIC
AIR CLEANER
(115-VAC 1 AMP MAX)
SEC-2
LED
HUM GRY/Y2W/W1
24-VOLT THERMOSTAT TERMINALS
24 V
COM
W2
3-AMP FUSE
LED ­DIAGNOSTIC LIGHT
TWIN / TEST TERMINAL
HUM ­HUMIDIFIER (24-VAC 0.5 AMP MAX)
78 9
456
123
L2
PR2
L1
PR1
PARK
COM
EAC-2
EAC-1
3
FU1
-HEAT
-HEAT
HI-GAS
LO-GAS
HI-COOL
SEC-1
10 11 12
789
456
123
MASTER SLAVE
1
TWIN
TEST
1
1234
OFF
ON
FURNACE AND BLOWER OFF DELAY SETUP SWITCHES
32°F MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED
A93058
CAUTION: Freezing condensate left in the furnace will damage the equipment.
If the furnace will be off for an extended period of time in a structure where the temperature will drop to 32° or below, winterize as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door.
3. Disconnect cap from unused drain tap on inducer housing. (See Fig. 13.)
4. Insert funnel in drain tube and pour antifreeze, propylene glycol (RV, swimming pool antifreeze, or equivalent) into furnace until it is visible at point where condensate enters open drain. (See Fig. 14.)
5. Reconnect drain tube to inducer housing.
6. Replace main furnace door.
A93348
Fig. 12Two-Stage Control
See Fig. 15 for Wiring Diagram
TROUBLESHOOTING
Use the Troubleshooting Guide, the status code LED on the control and the Component Test to isolate furnace operation problems.
I. STATUS CODES
For an explanation of status codes, refer to service label located on back of main furnace door or Fig. 16. The control will store up to 5 previous codes but will not store a non-current code longer than 48 hours. NOTE: Removing the blower access door will open the blower access door switch and terminate 115-v power to the control is interrupted. To read current status code, remove main furnace door. The status code LED can be viewed through the sight glass on the blower access door. NOTE: NO thermostat signals may be present at control and all blower off delays must be expired to view previous codes. To retrieve previous codes, remove 1 of the red main limit wires 1 to 4 sec until the LED light goes out, then reconnect it. (Do not leave red wire disconnected for longer periods of time as the control will assume an overtemperature condition exits and will respond with blower operation.) This places the control in the status recall mode and displays the first code stored in memory Record the code and repeat the disconnect and reconnect of the red wire, recording each code until code 11 is displayed indicating no additional faults. After the last code is displayed or after 2 minutes in the code, recall mode the control will return to normal standby mode.
II. COMPONENT TEST
Use the Component Test to check furnace components for proper operation. To initiate the component self-test sequence, shut off the room thermostat or disconnect the Rthermostat lead. Briefly (approx. 2 sec) short the TWIN/TEST terminal to the C
OM 24V
terminal. The status LED will turn off. The test sequence will be as follows:
9
Page 10
Fig. 13Inducer Housing Drain Tube
A99118
1. The inducer will start and run on high speed.
2. After 7 sec the inducer motor will continue to run while the hot surface ignitor HSI is energized for 15 sec, then de-energized.
3. The inducer motor changes to low speed and continues to run the remainder of the component self-test.
4. The blower motor operates on LO GAS-HEAT speed for 7 sec.
Fig. 14Funnel in Drain and Antifreeze
A99119
Running Through Trap
5. The blower motor operates on HI GAS-HEAT speed for 7 sec.
6. The blower motor operates on HI COOL speed for 7 sec.
7. The gas valve and humidifier terminal HUM are not energized for safety reasons.
10
Page 11
Fig. 15Wiring Diagram A01018
LEGEND
BHI / LOR BLOWER MOTORSPEED CHANGE RELAY, SPDT BHT / CLR BLOWER MOTOR SPEED CHANGE RELAY, SPDT BLWM BLOWER MOTOR, 4 or 5 -SPEED,PERMAN ENT-SPLIT-CAPA CITOR BLWR BLOWER MOTOR RELAY, SPST (N.O.) CAP CAPACITOR -1 = BLWM -2 = IDM CPU MICROPROCESSOR AND CIRCUITRY EAC-1 ELECTRONIC AIR CLEANERCONNECTION (115 VAC, 1AMP MAX .) EAC-2 ELECTRONIC AIR CLEA NERCONNECTION (COMMON) FRS FLAME ROLLOUT SWITCH OVERTEMP. MANUAL RESET, SPST (N.C.) FSE FLAME-PROVING SENSOR ELECTRODE FU1 FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED FU2 FUSE, FIELD INSTALLED GV GAS V ALVE, REDUNDANTLOW-HEAT OPERATORS, 2-STAGE HPS HIGH-HEAT PRESSURE SWITCH, SPST(N.O.) HPSR HIGH-HEAT PRESSURE SWITCHRELAY , SPST (N.C.) HSI HOT-SURFACEIGNITE R (115 VAC) HSIR HOT-SURFACE IGNITOR RELAY, SPST (N.O.) HUM 24VAC HUMIDIFIER CONNECTION (0.5 AMP. MAX.) IDM INDUCED DRAFT MOTOR,2-SPEED,SHAD ED-POLE IDR INDUCER MOTOR RELAY, SPST(N.O.) IHI / LOR INDUCER MOTORSPEED CHANGE RELAY, SPDT ILK BLOWER DOOR INTERLOCK SWITCH, SPST (N.O.) JB JUNCTION BOX LED LIGHT-EMITTING DIODEFORSTATUS CODES LGPS LOW GAS-PRESSURE SWITCH, SPST (N.O.) LPS LOW-HEAT PRESSURE SWITCH, SPST (N.O.) LS LIMIT SWITCH, OVERTEMPERATURE-AUTO RESET, SPST (N.C.)
MGVR MAIN GAS VALVE RELAY , DPST (N.O.)
-
1 = VALVE-2 = HUM ID IFIER PL1 12-CIRCUIT CONNECTOR PL2 9-CIRCUIT CONNECTOR PL3 4-CIRCUIT IDM CONNECTOR PL6 2-CIRCUIT HSI CONNECTOR SW1 HIGH-HEAT-ONLY SWITCH, SPST (MANUAL)
*
SW2 LOW-HEAT-ONLY SWITCH, SPST (MANUAL)
*
SW3 & 4 BLOWER-OFF DELAY SETTING SWITCHES,
SPST (MANUAL)
*
TJ TWINNING JUMPER,SPDT FOR MASTER OR
SLAVE STATUS (MANUAL CHANGE OVER) TRAN TRANSFORMER-115V AC/24VAC TWIN/TEST 1-CIRCUITTWINNING BUSS CONNECTOR,
ALSO COMPONENT TEST
JUNCTION TERMINAL CONTROL TERMINAL FACTORY POWER WIRING (115VAC) FACTORYCO NTROL WIRING (24VAC) FIELD POW ER WIRING (115VAC) FIELD CONTROL WIRING (24VAC) CONDUCTORO N CO N TROL FIELD WIRING SCREW TERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE
NOTES:
1. Use only copperwire between thedisconnect switch and the unit.
2. If any of the original wire, as supplied, must be replaced, use the sameor equivalenttypew ire.
3. Inducer (IDM) and blower (BLWM) motors contain internal auto-reset thermal overload switches.
4. Blower motor speed selections arefor averagecondition s. See Installation Instructio ns for details on optimum sp e e d s election.
5. Replace only with a 3-AMP fuse.
6. This wire must be connectedto furnace s hee t m e tal for control to prove flame.
7. Factoryconnected when LGPS not used.
RED
LS
FRS
RED
RED
ORN
LGPS
LPS
(WHEN USED)
SWITCH 12
HEAT SET-UP SWITCH
NORM HI HT LO HT
*
ON
OFF
OFF
ON
BLOWER­OFF DELAY (SEC.)
SWITCH
3
4
90 SEC
135 SEC
*
180 SEC 225 SEC
ON
OFF
OFF
ON
2-STAGE FURNACE CONTROL
FACTORY
SETTINGS
1
2
34
ON
OFF
3
2
1
BLOWER-OFF DELAY BLOWER-OFF DELAY LOW-HEAT ONLY HIGH-HEAT ONL Y
*
W2 Com
24V
W/W1 Y/Y2 R G HUM
LED
S
M
TJ
TWIN TEST
12
11 10
PL1
321
9
87
FSE
HPS
HI
M
IDM
HSI
ILK
JB
L1
PL6
12
123
PL2
PR1 PR2
L1 L2
COMMON
HI-COOL
HI-GAS HEAT
EAC-2
EAC-1
LO-GAS HEAT
SPARE
SEC1
FU1
SEC2
NOTE #4
BLWM
BRN
BRN
CAP-1
TRAN
GV
C
GRN/YEL
FUSED DISCONNECT
SWITCH (WHEN REQ'D)
NOTE #1
BLK WHT GRN
L2
GND
FU2
CONNECTION DIAGRAM
L1
BLWR
TO 115VAC FIELD DISCONNECT SWITCH
NOTE #1
EQUIPMENT GROUND
LO-GAS-HEAT
HI-GAS-HEAT
SPARE
NOTE #4
COMMON
HSIR
EAC-1
SCHEMATIC DIAGRAM (NATURAL GAS & PROPANE)
EAC-2
31
HSI
2
9
PL2
PR2
115VAC
PR1
TRAN
24VAC
IDR
L2
ILK
BLWM
BHI / LO R
BHT / CLR
CAP-1
BRN
BRN
PL6
IHI / LO R
SEC1
FU1
NOTE #5
1 2 3
HPSR
1 5 6
2
N/A N/A
HI-COOL
PL3
4 7
SEC2
8
LS
FRS
N/A
12
2 3
MGVR-2
9 6
NOTE #7
(WHEN USED)
TWIN TEST
SLAVE
MASTER
W/W1
R
HUM
TWINNING JUMPER
TJ
W2
Y/Y2
G
MGVR-1
HPS
5
4
1
10
7
8
FSE
11
HI
M
C
NOTE#6
PL1
COMPONENT TEST
CPU
LGPS
C
OM
RED
LO
RED
MED LO
BLU
COM W HT
BLK
HI
YELMED HI
MED
COM
HI
MED
MED LO
LO
NOTE #14
ORN
SPARE
MED HI
SPARE
BLU
NOTE #14
RED
RED
ORN
BLU
GRN/YEL
GRY
BRN
WHT
WHT
BLK
YEL
YEL
WHT
GRY
WHT
ORN
WHT
BLK
WHT
BLK
BLK
BLK
GRN / YEL
BLU
WHT
BRN
BRN
GRY
4
GRN/YEL
NOTE #6
PL3
LO
4
COM
HI
LPS
GV
8. Symbols are an electrical representationonly.
9. BLOWER-ON DELAY: Gas heating 60 seconds, Cooling/Heat Pump 2 seconds.
10. BLOWER-OFFDE LA Y : Gas heating 90, 135, 180, or 225 seconds,cooling orheatpump 90 seconds.
11. IGNITION-LOCKOUT w ill occur afte r f o u r consec utiveuns uccessfu l tr ia ls-for-ignitio n . Controlwill automatic a llyreset after three hours.
12. Control must be grounded at pin 10 of12-pin conne ctor.
13. NA - Not Applicable (Not used)
14. Orange lead not available on all models.
CAP-2
BRN
BRN
GRN
CAP-2
RED
To initiate the componenttest sequence with no thermostat inputs andwith all inducer Post-Purge andBlower-Off D elay periods completed,short the"TWIN/TEST" terminal to the"COM" terminal for about two seconds.The control will turn ON the inducer motor High-Speed, HSI, inducer motor Low-Speed, blower motor Low-Gas-Heat Speed, blower motor High-Gas-Heat Speed, and blower motor High-Cool Speed for 7-15 seconds each (the inducermotor will be ON theentirelength of the test). Neither the gas valve northe hu midifier will be turned ON.
RED
WHT
OL
YEL
IDM
OL
NOTE #7
326050-101 REV. B
ORN
11
Page 12
If status code recall is needed, do not remove power or blower door. Briefly remove
SERVICE
and then reconnect one main limit wire to display stored status code.
LED CODE
CONTINUOUS OFF CONTINUOUS ON RAPID FLASHING
Each of the following status codes is a two-digit number with the first digit determined by the number of short flashes and the second digit by the number of long flashes.
11 NO PREVIO US CODE - Stored status codes are erased when power (115VAC or
24VAC) t o control is interrupted o r 48 hou rs a fte r each fault is clea re d.
12 BLOWER ON AFTER POWER UP (115VAC or 24VAC) - Blower runs for 90 seconds,
if unit is powered up during a call for heat (R-W closed).
13 LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT - Control will auto reset after three
hours. Reset switch or replace fuse link. Refer to #33.
14 IGNITION LOCKOUT - Control will auto-reset afte r three hours. Refer to #34. 21 GAS HEATING LOCKOUT - C ont r ol w ill NO T aut o-res et.
Check for: - Mis-wired gas va lv e - Defec tive con tr ol (v alv e relay)
22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is de-
energized. Inducer will run until fault is cleared. Check for:
- Leaky gas valve - Stuck-o pe n gas v alve
23 PRESSURE SWITCH DID NOT OPEN Check for:
- Obstructed pressure t ubing - Pressure switch stu ck closed.
24 SECONDARY V OLTAGE FUSE IS OPEN Check for: - Short-circu it in second a ry
voltage (24V AC) wiring
31 HIGH-HEAT PRESSURE SWITCH OR RELAY DID NOT CLOSE OR REOPENED
Check for: -Control relay may be defective - Refer to #32
32 LOW-HEAT PRESSURE, DRAFT SAFEGUARD (when used),AUX-LIMIT(when used*)
SWITCH DID NOT CLOSE OR REOPENED (DOWNFLOW ONLY*) If open longer than
five minutes, inducer shuts off for 15 min utes before retry. If it opens after trial for ignition period, blower will come on for 90 se cond recycle delay. Check for:
*- Defective blower motor or capacitor - Restricted vent
- Proper vent sizing - Low inducer voltage (115VA C)
- Disconnected or obstructed pressure tubing - Excessive wind
- Defective inducer motor - Defective p ressure switch
- Inadequate combustion air supply
33 LIMIT OR FLAME ROLL-OUT SWITC H IS OPEN - If open longer than three minutes,
code changes to #13. Flame roll-out switch requires manual reset. Check for:
- Dirty filter or restricted duct system. - Loose blower wheel.
- Defective blower motor or capacitor. - Defective switch or connections.
- Inadequate combustion air supply (Flame roll-out switch or fuse link open).
- Open flame roll-out switch, or fuse link. Manual reset or replace.
34 IGNITION PROVING FAILURE - Control will try three more times before lockout #14
occurs. If flamesignal is lost after trial for ignit ion period, blower will come on for 90 second recycle delay. Check for:
- Gas valv e de f e ct iv e o r gas v alve turned off.
- Oxide buildup o n flame se nso r (clea n w ith fine steel wool) .
- Proper flame sense current (.5 microamps D.C. min., 4.0 - 6.0 nom. in HIGH HEAT).
- Green wireMUST be connected to furnace sheet metal.
- Flame senso r must be un gr o u n d e d . - Manual valve s h u t-o ff.
- Defective hot surface ignitor - Control ground continuity.
- Inadequate flame carryover or rough ignition. - Low inlet gas pressure.
43 LOW-HEAT PRESSURE, DRAFT SAFEGUARD (when used), OR AUX-LIMIT (when used*)
SWITCH OPEN WHILE HIGH-HEAT PRESSURE SWITCH IS CLOSED Check for:
- Pressure switch stuck op en
- Disconnected or obstructed pressure tubing - Refer to #32 and #33
45 REPLACE CONTROL
- Check for 115VAC at L1 and L2, and 24VAC at SEC1 and SEC2 .
- Control has 24VAC power.
- Line voltage (115VAC) polarity reversed. If twinned, refer t o twinning kit instructions.
COMPONENT TEST
OM
W2
C
24 V
W/W1
Y/Y2
To initiate the component self-test sequence, shut off the room thermostat or disconn e ct the "R" ther mostat lead. Brief ly short the TWIN/TEST term in al to the Com24V terminal. Status LED will turn off. NON-C O NDENSING F URNACE: The control will turn O N the inducer mo t o r low speed, then high speed and remain on high speed for the entire test. Th e other comp onents will be ON for 7 to 15 seconds: Hot surface ignitor, Low heat blower speed, High heat blower speed, High cooling blower speed. CONDENSING FURNACE: The inducer m otor will start in high speed and remain on high spee d until the end of the test, then shift to low speed for 7 to 15 seconds . All other components will be tested in the same sequence as the NON-CONDENSING.
GR
HUM
ST ATUS
TWIN
TEST
LED
12 - CIRCUIT CONNECTOR
320893-101 REV. E
A01053
Fig. 16Service Label
12
Page 13
NOTES:
1.
Refer to information label on blower compartment door for procedure for use of LED status codes and problem solving suggestions.
2.
LED indicator is viewed through window on blower compartment door.
3.
If 115-vac power is energized or interrupted during a call for heat, the indoor blower will run for 90 sec before a gas heating cycle begins – Code 12.
4.
After replacing any component, verify correct operating sequence.
START
Turn thermostat OFF.
On furnace control, note current settings for setup switches 1 (SW-1) and 2 (SW-2) then set SW-1 to OFF
and SW-2 to ON.
Cycle 115-v power
off for 3 sec, then on.
Continuous LED?
Yes
Set thermostat to call for heat.
Set FAN switch to AUTO.
Draft inducer motor starts.
Yes
Is Code 22 displayed?
Yes
Flame present when not normal.
Replace gas valve.
15-sec inducer pre-purge.
Yes
Ignitor warms up and glows
orange/yellow; 17-sec warm-up.
Yes
Main burners ignite.
Yes
No
No
No
No
No
TROUBLESHOOTING
GUIDE
If LED is flashing rapidly, check line voltage polarity. If Code 24 is displayed, check for blown fuse. If LED is OFF, check line voltage and 24-v transformer. If Code 45 is displayed, replace control.
Is indoor blower on ?
No
24v should be present across C and W. If not, check for:
1. Open thermostat.
2. Open 24-v fuse (FU1) – Code 24.
3. Failed transformer. If Code 23 is displayed, the pressure switch(es) is stuck closed.
Replace switch and/or check pressure tube for blockage. System malfunction – Code 21.
115v should be present at the inducer motor. If so, replace inducer motor. If not, check 115-v wiring.
If Code 32 is displayed check for:
1. Open gas inlet pressure switch (when used).
2. Open pressure switch (LPS) and/or tube – Code 32.
3. Open Propane low gas pressure switch (LGPS) – Code 32.
4. Check all low-voltage wiring connections. 115v should be present at the ignitor. If so, replace the ignitor; if not,
check 115-vac wiring to ignitor. LPS or LGPS open while HPS is closed (high-gas-heat only) –
Code 43.
Control will attempt to light burners 4 times (approximately 1 minute between attempts – Code 34). Voltage is present at the gas valve for 7 sec during each ignition trial. System will lockout after 4 attempts.
Is the gas valve control knob in the OPEN or ON position? 24v should be present across the gas valve terminals C and M (and C and HI for high-fire test) during the 7 sec ignition trial. If not, check all low-voltage wiring connections to valve.
If 24v are present, and main gas does not flow:
1. Supply pressure > 13.6-in. wc.
2. Replace gas valve. Check ignitor position. Check burner carryover gap. Check gas supply pressure (4.5-in. wc minimum). Check manifold pressure (1.3- to 1.7-in. wc for low-fire; 3.2- to
3.8-in. wc for high fire). Check for proper orifice size.
WARNING
!
ELECTRICAL SHOCK HAZARD
ONLY QUALIFIED AND TRAINED SERVICE PERSONNEL SHOULD
PERFORM THIS PROCEDURE
24v should be present across R
Yes
No
No
No
and C. If not, check for:
Open flame rollout switch
1. (FRS) – Code 33. Open limit switch (LS) –
2.
Code 33.
Check all low-voltage wiring
3. connections.
Replace control only if all checks
Replace control only if Code 45 is displayed, or if all checks are OK.
Replace control only if Code 45 is displayed, or if all checks are OK.
No
are OK.
Main burners stay on.
Yes
Indoor blower motor starts on
heating speed after 60-sec
warm-up period.
Yes
Furnace runs until call for
heat ends.
Yes
Turn thermostat to OFF; gas valve
shuts off burners; 15-sec inducer
post purge.
Yes
Indoor blower motor stops after
90, 135, 180, or 225 sec.
Yes
Heating sequence of operation
complete. Remove blower door,
move setup switch 1 (SW-1) to ON
position and repeat process to check
high-fire operation. (When finished
return SW-1
and SW-2 to original
desired settings.)
Is Code 31 (high-gas-heat only), 32, 33, or 34 displayed? Check code information label to diagnose.
No
No
No
No
No
Check polarity of 115-v power at J-box and control. Twinned furnace polarities must match – rapid flashing LED.
Check ground continutity from J-box to control. Check flame sensor microamps (4.0 nominal; 0.5 minimum for
control to recognize flame).
115v should be present at the blower motor. If so, check capacitor. If capacitor is OK, replace blower motor. If 115v are not present at the blower motor, check all 115-v wiring to motor.
If not, check for:
1. Satisfied thermostat.
2. Open inlet gas pressure switch (when used).
3. Open propane low gas pressure switch (LGPS) – Code 32.
4. Open auxilliary limit (ALS)(downflow/horizontal only) – Code 32.
5. Open 24-v fuse (FU1) – Code 24.
6. Open limit switch (LS) – Code 13 or 33.
7. Open flame rollout switch (FRS) – Code 13 or 33.
8. Check 115-v line voltage – LED off. Check for sources of electrical noise interference (electronic air
cleaners, nearby TV, or radio antennas).
If inducer and burners continue to operate, check for 24v at the gas valve. If 24v are present, verify that the thermostat is open across R and W. If no voltage is present, turn the gas valve control knob to the OFF position. Replace gas valve.
24v should be present across R and C. If not, check for:
1. Open limit switch (LS) – Code 13 or 33.
2. Open flame rollout switch (FRS) – Code 13 or 33. 24v should not be present across R and G. If so, turn thermostat
FAN switch to AUTO.
No
No
No
No
No
Replace control if Code 45 is dis-
played, or if all checks are OK.
Clean flame sensor if microamps
are below nominal.
Replace control only if Code 45 is displayed, or if all checks are OK.
Replace control only if Code 45 is displayed, or if all checks are OK.
Replace control only if Code 45 is displayed, or if all checks are OK.
Replace control only if Code 45 is displayed, or if all checks are OK.
A01056
13
Page 14
14
Page 15
15
Page 16
© 2001 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231
16
Printed in U.S.A. sp0548 Catalog No. 5335-201
Loading...