Bryant R-22 561G User Manual

installation and start-up instructions
10 SEER 3 PHASE R-22 SPLIT SYSTEM AIR CONDITIONER
NOTE: Read the entire instruction manual before starting the installation.
This symbol indicates a change since the last issue.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thor­oughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU­TION. These words are used with the safety-alert symbol. DAN­GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death. Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
INSTALLATION RECOMMENDATIONS
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, and decks where unit-operation sound may disturb customer.
2. Ensure that vapor- and liquid-tube diameters are appropriate to capacity of unit. (See Table 1.)
3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb vibration.
5. When passing refrigerant tubes through the wall, seal opening with RTV or other pliable silicon-based caulk. (See Fig. 2.)
561G
Cancels: II 561C-18-6 II 561G-30-1
3-06
.
6. Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap that comes in direct contact with tubing. (See Fig. 2.)
8. Ensure that tubing insulation is pliable and completely surrounds vapor tube.
9. When necessary, use hanger straps which are 1 in. wide and conform to shape of tubing insulation. (See Fig. 2.)
10. Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation.
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation. If ANY refrigerant tubing is buried, providea6in. vertical rise at service valve. Refrigerant tubing lengths up to 36 in. may be buried without further special consideration. Do not bury more than 36 inches of refrigerant tubing in the ground.
I. CHECK EQUIPMENT AND JOB SITE
A. UNPACK UNIT
Move to final location. Remove carton, taking care not to damage unit.
B. INSPECT EQUIPMENT
File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit-rating plate on unit-corner panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications.
Fig. 1—Model 561G
INSTALLATION
A98524
—1—
Avoid contact between tubing and structureNOTE:
OUTDOOR WALL INDOOR WALL
CAULK
LIQUID TUBE
unit and 48 in. above unit. For proper airflow, a 6-in. clearance on 1 side of unit and 12 in. on all remaining sides must be maintained. Maintain a distance of 24 in. between units. Position so water, snow, or ice from roof or eaves cannot fall directly on unit.
On rooftop applications, locate unit at least 6 in. above roof surface. Place unit above a load-bearing wall and isolate unit and tubing set from structure.
INSULATION
THROUGH THE WALL
JOIST
HANGER STRAP
(AROUND VAPOR
TUBE ONLY)
1 MIN.
SUSPENSION
INSULATION
LIQUID TUBE
Fig. 2—Connecting Tubing Installation
VAPOR TUBE
VAPOR TUBE
C
A94028
IV. OPERATING AMBIENT
The minimum outdoor operating ambient in cooling mode is 55°F, and the maximum outdoor operating ambient in cooling mode is 125°F.
V. CHECK INDOOR CHECK-FLO-RATER® PISTON (IF REQUIRED) OR ADD TXV
Check indoor coil piston to see if it matches the required piston shown on outdoor unit rating plate. If it does not match, replace indoor coil piston with piston shipped with outdoor unit. The piston shipped with outdoor unit is correct for any approved indoor coil combination.
NOTE: If a TXV is to be installed on indoor unit, remove indoor coil piston and follow Section VI.
VI. INSTALL TXV
IMPORTANT: If not factory installed, the TXV should be
mounted as close to the indoor coil as possible and in a vertical upright position. Avoid mounting the inlet tube vertically down. Valve is more susceptible to malfunction due to debris if inlet tube is facing down. A factory-approved filter drier must be installed in the liquid line.
A. Installing TXV in Place of Piston
1. Pump system down to 2 psig and recover refrigerant.
3
⁄8″D. (9.53) TIEDOWN
A
B
DIMENSIONS (IN.)
UNIT BASE
DIMENSIONS
22-1/2 x 22-1/2 3-11/16 18-1/8 14-3/8
30x30 6-1/2 23-1/2 20
TIEDOWN KNOCKOUT LOCATIONS
KNOCKOUTS (2) PLACES
A94199
ABC
Fig. 3—Mounting Unit to Pad
II. INSTALL ON A SOLID, LEVEL MOUNTING PAD
If conditions or local codes require the unit be attached to pad, tie-down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit-mounting pattern in Fig. 3 to determine base-pan size and knockout-hole location.
Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.
III. CLEARANCE REQUIREMENTS
When installing, allow sufficient space for airflow, wiring, refrig­erant piping, and service. Allow 30-in. clearance to service end of
2. Remove hex nut from piston body. Use backup wrench on fan coils.
3. Remove and discard factory-installed piston. Be sure Teflon seal is in place.
4. Reinstall hex nut. Finger tighten nut plus 1/2 turn.
NOTE: If the piston is not removed from the body, TXV will not function properly.
CAUTION: EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation. To prevent damage to the unit, use a brazing shield and wrap TXV with wet cloth or use heat sink material.
5. Install TXV on indoor coil liquid line. Sweat swivel adapter to inlet of indoor coil and attach to TXV outlet. Use backup wrench to avoid damage to tubing or valve. Sweat inlet of TXV, marked INto liquid line. Avoid excessive heat which could damage valve.
6. Install vapor elbow with equalizer adapter to suction tube of line set and suction connection to indoor coil. Adapter has a 1/4-in. male connector for attaching equalizer tube.
7. Connect equalizer tube of TXV to 1/4-in. equalizer fitting on vapor line adapter.
8. Attach TXV bulb to horizontal section of suction line using clamps provided. Insulate bulb with field-supplied insula­tion tape. See Fig. 4 for correct positioning of sensing bulb.
—2—
TABLE 1—REFRIGERANT CONNECTIONS AND RECOMMENDED LIQUID- AND VAPOR-TUBE DIAMETERS (IN.)
1
UNIT SIZE
030, 036 3/8 3/8 3/4 3/4
042-048 3/8 3/8 7/8 7/8
060 3/8 3/8 7/8 1-1/8
NOTES:
1. Tube diameters are for lengths up to 80 ft horizontal or 20 ft vertical differential. For tubing lengths greater than 80 ft, consult Residenital Split System Long-Line Application Guidelines—Air Conditioners and Heat Pumps Using R-22 Refrigerant. Maximum liquid lines 3/8 in., including long-line applications.
2. Do not apply capillary-tube indoor coils to these units.
Connection Diameter Tube Diameter Connection Diameter Tube Diameter
LIQUID RATED VAPOR (UP TO 80 FT
)
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit compo­nent damage. To avoid equipment damage and/or loss of performance remove indoor-coil piston if unit is to be installed on system with a TXV-metering device.
Check outdoor unit piston. Remove retainer on liquid service valve and check piston size with matching number listed on outdoor unit rating plate.
VII. MAKE REFRIGERANT PIPING CONNECTIONS
Outdoor units may be connected to indoor section using accessory tubing package or field-supplied refrigerant-grade tubing of cor­rect size and condition. For tubing requirements beyond 80 ft, consult Residential Split System Long-Line Application Guideline—Air Conditioners and Heat Pumps Using R-22 Refrig­erant. Connect tubing to fittings on outdoor unit vapor and liquid service lines. (See Table 1.)
If refrigerant tubes or the indoor coil are exposed to atmospheric conditions for longer than 5 minutes they must be evacuated to 500 microns to eliminate contamination and moisture in system.
A. OUTDOOR UNIT CONNECTED TO FACTORY­APPROVED INDOOR UNIT
Outdoor unit contains correct system-refrigerant charge for opera­tion with indoor unit of same size when connected by 15 ft of field-supplied or factory accessory tubing. Check refrigerant charge for maximum efficiency.
B. SWEAT CONNECTION
Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit-rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device.
NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit-rating plate. Do not install unit in system where voltage or phase imbalance (3 phase) may fluctuate above or below permissible limits.
NOTE: Use copper wire only between disconnect switch and unit.
NOTE: Install branch-circuit disconnect of adequate size per NEC to handle unit-starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440-14 of NEC.
A. ROUTE GROUND AND POWER WIRES
Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit-control box.
WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury and or death. The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes.
B. CONNECT GROUND AND POWER WIRES
Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 4.
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit compo­nent damage. To avoid valve damage while brazing, service valves must be wrapped in a heat sink material, such as a wet cloth.
Use refrigerant grade tubing. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, tubing set can be brazed to service valve using industry accepted methods and materials. Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.
VIII. MAKE ELECTRICAL CONNECTIONS
WARNING: ELECTRICAL SHOCK AND EXPLO-
SION HAZARD
Failure to follow this warning could result in personal injury, death and or property damage. Do not supply power to unit with compressor terminal-box cover re­moved.
—3—
DISCONNECT PER N.E.C. AND/OR LOCAL CODES
CONTACTOR
FIELD POWER
WIRING
3 PHASE ONLY
FIELD GROUND
WIRING
BLUE
GROUND LUG
A94025
Fig. 4—Line Power Connections
C. CONNECT CONTROL WIRING
Route 24v control wires through control wiring grommet and connect leads to control wiring. (See Fig. 6.)
Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If thermostat is located more than 100 ft from unit, as measured along the control voltage wires, use No. 16 AWG color-coded wire to avoid excessive voltage drop.
Use furnace transformer, fan-coil transformer, or accessory trans­former for control power, 24v/40va minimum.
NOTE: Use of available 24v accessories may exceed the mini­mum 40va power requirement. Determine total transformer load­ing and increase the transformer capacity or split the load with an accessory transformer as required.
IX. COMPRESSOR CRANKCASE HEATER
1. When equipped with a crankcase heater, energize heater a minimum of 24 hr before starting unit. To energize heater only, set thermostat to OFF mode and close electrical disconnect to outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than 80 ft.
X. INSTALL ELECTRICAL ACCESSORIES
Refer to individual instructions packaged with kits or accessories when installing.
XI. START-UP
CAUTION: PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury. Service valve gage ports are equipped with Schrader valves. Wear safety glasses and gloves when handling refrigerant.
for compressor operation. (See Fig. 5 and Table 2.) If the phasing is correct, circuit R-Y energizes contactor, starting outdoor fan motor and compressor circuit. R-G energizes indoor unit blower relay, starting indoor blower motor on high speed.
NOTE: If the phasing is incorrect, the contactor will not be energized. To correct the phasing, interchange any two of the three power connections on the field side.
A00010
Fig. 5—3-Phase Monitor Control
1. Fully open liquid and vapor service valves.
2. Unit is shipped with valve stem(s) front seated (closed) and caps installed. Replace stem caps after system is opened to refrigerant flow. Replace caps finger-tight and tighten an additional 1/12 turn with wrench.
3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature. Be sure set point is below indoor ambient temperature.
5. Set room thermostat to COOL and fan control to ON or AUTO mode. Operate unit for 15 minutes. Check system­refrigerant charge. (See Check Charge.)
WARNING: PERSONAL INJURY AND ENVIRNO­MENTAL HAZARD
Failure to follow this warning could result in personal injury or death. Relieve pressure and recover all refrig­erant before system repair or final unit disposal. Use all service ports and open all flow control devices, including solenoid valves.
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit compo­nent damage.
• 3-phase scroll compressors are rotation sensitive.
• A flashing LED on phase monitor indicates reverse rotation. (See Fig. 5 and Table 2.)
• This will not allow contactor to be energized.
• Disconnect power to unit and interchange 2 field wiring leads on unit contactor.
A. SEQUENCE OF OPERATION
Turn on power to indoor and outdoor units. Transformer is energized.
On a call for cooling, thermostat makes circuits R-Y and R-G. Three phase models with scroll compressors, are equipped with a phase monitor to detect if the incoming power is correctly phased
TABLE 2—PHASE MONITOR LED INDICATORS
LED STATUS OFF No call for compressor operation
FLASHING Reversed phase
ON Normal
When thermostat is satisfied, its contacts open, de-energizing contactor and blower relay. Compressor and motors stop.
If indoor unit is equipped with an off delay circuit, the indoor blower can run an additional 120 sec to increase system efficiency.
XII. CHECK CHARGE
UNIT CHARGE
Factory charge is shown on unit rating plate. Charge procedure is shown on wiring/charging label locate on unit.
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit compo­nent damage. Compressor damage may occur if system is overcharged.
CAUTION: ENVIRNOMENTAL HAZARD
Failure to follow this caution may result in environmental damage and fines. Federal regulations require that you do not vent refrigerant to the atmosphere. Recover during system repair or final unit disposal.
A. Cooling Only Procedure—Indoor unit equipped with piston, superheat method
Factory charge is shown on unit rating plate. To check charge in cooling mode, refer to Cooling Only Procedure on unit wiring and charging label.
NOTE: If superheat or subcooling charging conditions are not favorable, charge must be weighed in accordance with unit rating plate ± 0.6 oz/ft of 3/8-in. liquid line above or below 15 ft respectively.
—4—
B. Cooling Only Procedure—Indoor unit equipped with TXV—Subcooling Method
Factory charge and subcooling are shown on unit information plate. To check charge, follow the procedure below. NOTE: If subcooling charging conditions are not favorable, charge must be weighed in accordance with unit rating plate, ±0.6 oz/ft. of 3/8-in. liquid line above or below 15 ft, respectively. Favorable conditions fall within the ranges given on the charging chart on the outdoor unit plate. EXAMPLE: To calculate additional charge required for a 25-ft. line set; 25 ft ­15 ft = 10 ft X 0.6 oz/ft=6ozofadditional charge. This system requires charging by the subcooling method.
1. Operate unit a minimum of 10 minutes before checking charge.
2. Measure liquid service valve pressure by attaching an accurate gauge to service port.
3. Measure liquid line temperature by attaching an accurate thermistor type of electronic thermometer to liquid line near outdoor coil.
4. Refer to unit rating plate for required subcooling tempera­ture.
5. Refer to Table 3. Find the point where required subcooling temperature intersects measured liquid service valve pres­sure.
6. To obtain required subcooling temperature at the specific liquid line pressure, add refrigerant if liquid line tempera­ture is higher than indicated or reclaim refrigerant if temperature is lower. Allow a tolerance of ±3°F.
NOTE: In long-line applications, See the Residential Split Sys­tem Long-Line Application Guideline for special charging require­ments.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible equip­ment failure, it is essential that periodic maintenance be performed on this equipment.Consult your servicing contractor or Owner’s Manual for proper frequency of maintenance. Frequency of maintenance may vary depending upon geographic areas, such as coastal applications.
A/C
THERMOSTAT
Typical
FURNACE
AIR
CONDITIONER
Leave Owner’s Manual with homeowner. Explain system opera­tion and maintenance procedures outlined in manual.
TABLE 3—REQUIRED SUBCOOLING TERMPERATURE
(°F)
LIQUID
PRESSURE AT
SERVICE VALVE
(PSIG) 5 10 15 20
134 71 66 61 56 141 74 69 64 59 148 77 72 67 62 156 80 75 70 65 163 83 78 73 68 171 86 81 76 71 179 89 84 79 74 187 92 87 82 77 196 95 90 85 80 205 98 93 88 83 214 101969186 223 104999489 233 107 102 97 92 243 110 105 100 95 253 113 108 103 98 264 116 111 106 101 274 119 114 109 104 285 122 117 112 107 297 125 120 115 110 309 128 123 118 113 321 131 126 121 116 331 134 129 124 119 346 137 132 127 122 359 140 135 130 125
REQUIRED SUBCOOLING TERMPERATURE (°F)
A/C
THERMOSTAT
Typical
FAN COIL
AIR
CONDITIONER
24 VAC HOT
24 VAC COM
HEAT STAGE 1
COOL STAGE 1
INDOOR FAN
R
C
W/W1
Y/Y2
G
R
C
W
Y
G
C
24 VAC HOT
24 VAC COM
HEAT STAGE 1
COOL STAGE 1
INDOOR FAN
R
C
W/W1
Y/Y2
G
R
C
W2
G
Fig. 6—Generic Wiring Diagram
(See Thermostat Installation Instructions for wiring specific unit combinations)
—5—
C
A02326
© 2006 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231
—6—
Printed in U.S.A. Catalog No. II 561G-30-1
Loading...