Bryant CAPVP series, CAPVP1917ALA, CAPVP2517ALA, CAPVP3717ALA, CAPVP3721ALA Installation Instructions Manual

...
CAPVP
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation.
TABLE OF CONTENTS
PAGE
INTRODUCTION 1...................................
INSTALLATION 2....................................
Inspect Equipment 2...............................
Select Installation 2................................
Installation of Evaporator Coils 2......................
Connect Refrigerant Piping 3.........................
Connect Lines 3...................................
Refrigerant Metering Device 4........................
Condensate Drain Line Connection 4...................
Waste Line Connection 4............................
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing and work gloves. Use quenching cloths for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and the current editions of the National Electrical Codes (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety--alert symbol When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING and
CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Evaporator Coil
Upflow --- Downflow Cased
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power if applicable. Lock out and tag disconnect switch with a suitable warning label.
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.
!
CAUTION
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
This coil contains Nitrogen precharge of up to 15 PSI. Release of this pressure through the center of the rubber plugs is required before removing the plugs.
!
.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
IMPORTANT: Nitrogen can leak out through the hole that the needle pierced in the plugs. This does not indicate a leaking coil nor warrant return of the coil.
CAUTION
Table 1 – CAPVP Cased Coil Information
MODEL SIZE (TON)
CAPVP1917ALA 1.5 17---1/2” / 445 mm 3/8 3/4 CAPVP2517ALA 2.0 17---1/2” / 445 mm 3/8 3/4 CAPVP3717ALA 3.0 17---1/2” / 445 mm 3/8 3/4 CAPVP3721ALA 3.0 21” / 533 mm 3/8 7/8 CAPVP4321ALA 3.5 21” / 533 mm 3/8 7/8 CAPVP6124ALA 5.0 24---1/2” / 622 mm 3/8 7/8
FLUSH FIT TO
FURNACE WIDTH
COIL CONNECTION TUBE SIZE (IN.)
Liquid Suction
INTRODUCTION
Use this instruction manual to install CAPVP indoor coil on multipoise furnaces. (See Fig. 1.) The CAPVP coil is enclosed in a casing.
Supply
CAPVP
Evaporator
Coil
Upflow
Furnace
Installation
Return
Fig. 1 -- Typical Installation Upflow/Downflow Cased Coils
Return
Supply
Downflow
Furnace
Installation
A13060
3. When installing wider coil on narrow furnace, create field fabricated adapter. (See Fig. 2.)
4. When installing narrow coil on wide furnace, create field fabricated adapter. (See Fig. 2.)
NOTE: On upflow installations where the indoor coil is placed in an unconditioned space, a 6” (152 mm) wide piece of insulation should be applied and wrapped around the outside of coil casing and supply duct contact point.
See Table 1 for dimensions. Note instructions for placement of coil casing on furnace.
Downflow CAPVP Coil Installation.
IMPORTANT: Installing “A” coils rotated 90_ from the front of
the furnace in downflow applications can cause water blow off or coil freeze up. This is due to the concentration of air on one coil slab or lack of air on the opposite coil slab. If the airflow is high due to ductwork or other causes, and there is a chance for water blow off, it is recommended that a 3” (76 mm) field--supplied adapter be placed between the coil and the furnace to allow the air to distribute evenly to both coil slabs. (See Fig. 3.)
Wide Coil
Narrow Furnace
Field Fabricated
Adapter(s)
* CAUTION: DO NOT MOUNT COIL LOWER THAN
3˝ (76mm) MINIMUM OR FURNACE FAILURE MAY RESULT
Narrow Coil
3˝ (76mm)
Wide Furnace
A13061
Fig. 2 -- Adapter(s) Installation When Coil Overhangs or Un-
derhangs Furnace
INSTALLATION
Inspect Equipment
File claim with shipper if equipment is damaged or incomplete.
Select Installation
Upflow CAPVP Coil Installation.
The cased coil is designed to fit furnaces of the same width.
1. Set coil in place on upflow furnace discharge air opening.
2. Ensure coil is level for proper condensate drainage. Do not tip coil toward condensate drain. Coil casing need not be fastened or screwed to furnace.
3” (76mm)
A13062
Fig. 3 -- Downflow Installation With Coil Rotated 90_
1. Set cased coil on supply duct opening.
2. Place field fabricated 3” (76 mm) adapter on coil casing. Adapter should be tapered to fit coil/furnace combination when one of them is larger than the other.
3. Set furnace on adapter.
NOTE: In downflow installation with a 4--way multipoise furnace, break off perforated duct flanges on furnace. See furnace installation instructions.
CONNECT REFRIGERANT PIPING
Use accessory tubing package or field--supplied tubing of refrigerant grade, see Product Data information for ordering. Suction tube must be insulated. Do not use damaged, dirty, or contaminated tubing because it may plug refrigerant flow--control device. AL WAYS evacuate the coil and field--supplied tubing before opening outdoor unit service valves.
2