Bryant BW4B, BW9, BW5B, BS1, BW2 User Manual

...
Gas and Oil-Fired Water and Gas Fired Steam Boilers
MODEL BW1, BW2
Series B
BS BW
MODEL BW3
Series B
MODEL BW4B, BW5B
Series B
MODEL BS1, BS2
Series B
MODEL BW9
Series A
Form No. PDS BS1A.75.3
B — Boiler
Type of System
W — Water S i— Steam
MODEL NUMBER NOMENCLATURE
BW9AAN000075AAAA
B W 9 A A N 000 075 A A AA
Variations
AA — Standard
Series
A i— Original
Combustion/Ignition
1 — Natural Draft/Standing Pilot 2 — Natural Draft/Electronic 3 — Induced Draft/Electronic 4 — Oil Burner/Without Tankless Coil 5 — Oil Burner/With Tankless Coil 9 — 90% Direct Vent/Sealed
Combustion
Model Code
Electrical
A 110 to 125 60 Hz
Fuel
H — Heating Oil N — Natural Gas P — Propane
Heating Size
Btu Input (x 1000)
Cooling
Labeling
A — Common Unit G — Canada Only (oil)
BOILER ACCESSORIES
BW1/BW2
DESCRIPTION PART NO.
Filtrol Package (Up to 75,000 Btuh Input) KBAFP0101DNK
Filtrol Package (Up to 150,000 Btuh Input) KBAFP0201DNK
Filtrol Package (Over 150,000 Btuh Input) KBAFP0301DNK
High Limit Control KBAHL0101DNK
Combustible Floor Base (2 thru 6 section models) KBASB0301DNK
Combustible Floor Base (7 thru 9 section models) KBASB0401DNK
Zoning Valve 3/4 in. KBAZV0101DNK
Zoning Valve 1 in. KBAZV0201DNK
Gas Conversion Kit Natural to Propane (After 1799V) KBANP0201DNK
Gas Conversion Kit Propane to Natural KBAPN0201DNK
NOTE: There was never a Natural to Propane conversion kit for BW/BS boiler prior to 1799V.
BW3
DESCRIPTION PART NO.
Filtrol Package (Up to 75,000 Btuh Input) KBAFP0101DNK
Filtrol Package (Up to 150,000 Btuh Input) KBAFP0201DNK
Filtrol Package (Over 150,000 Btuh Input) KBAFP0301DNK
High Limit Control KBAHL0101DNK
Combustible Floor Base (2 thru 6 section models) KBASB0301DNK
Combustible Floor Base (6 thru 7 section models) KBASB0401DNK
Zoning Valve 3/4 in. KBAZV0101DNK
Zoning Valve 1 in. KBAZV0201DNK
Gas Conversion Kit Natural to Propane (After 1799V) KBANP0201DNK
Gas Conversion Kit Propane to Natural KBAPN0201DNK
NOTE: There was never a Natural to Propane conversion kit for BW/BS boiler prior to 1799V.
BS1/BS2
DESCRIPTION PART NO.
Combustible Floor Base (2 thru 6 section models) KBASB0301DNK
See notes on page 3.
—2—
BOILER ACCESSORIES (CONT.)
Combustible Floor Base (6 thru 7 section models) KBASB0401DNK
Gas Conversion Kit Natural to Propane (3 section, BS1/2-075) KBANP0301DNK
Gas Conversion Kit Natural to Propane (4 section, BS1/2-112) KBANP0401DNK
Gas Conversion Kit Natural to Propane (5 section, BS1/2-150) KBANP0501DNK
Gas Conversion Kit Natural to Propane (6 section, BS1/2-187) KBANP0601DNK
Gas Conversion Kit Natural to Propane (7 section, BS1/2-225) KBANP0701DNK
Gas Conversion Kit Natural to Propane (8 section, BS1/2-262) KBANP0801DNK
Gas Conversion Kit Natural to Propane (9 section, BS1/2-299) KBANP0901DNK
NOTE: There was never a Natural to Propane conversion kit for BW/BS boilers prior to 1799V.
BW4/BW5
DESCRIPTION PART NO.
Filtrol Package (Includes Air Purge Extrol Tank and Fill Valve) KBAFP0201DNK
KBAFP0301DNK
Zone Valve - 3/4 in. KBAZV0101DNK
Zone Valve - 1 in. KBAZV0201DNK
High-Limit Control - Manual Reset* KBAHL0101DNK
Tankless Water Heater Kit KBATH0101IDNK
Combustible Floor Base KBASB0301DNK
Low Fire Rate Kit - 3 Section BW4/BW5 KBALF0101DNK
Low Fire Rate Kit - 4 Section BW4/BW5 KBALF0201DNK
BW9
DESCRIPTION PART NO.
Concentric Vent Termination Kit (Single Pipe) - 2 in. KGAVT0501CVT
Concentric Vent Termination Kit (Single Pipe) - 3 in. KGAVT0601CVT
Filtrol Package (Up to 75,000 Btuh Input) KBAFP0101DNK
Filtrol Package (Up to 150,000 Btuh Input) KBAFP0201DNK
Zoning Valve 3/4 in. KBAZV0101DNK
Zoning Valve 1 in. KBAZV0201DNK
Gas Conversion Kit Natural to Propane (BW9-050) KBANP1101DNK
Gas Conversion Kit Natural to Propane (BW9-075) KBANP1201DNK
Gas Conversion Kit Natural to Propane (BW9-100) KBANP1301DNK
Gas Conversion Kit Propane to Natural (BW9-050) KBAPN1101DNK
Gas Conversion Kit Propane to Natural (BW9-075) KBAPN1201DNK
Gas Conversion Kit Propane to Natural (BW9-100) KBAPN1301DNK
* 2–6 Section Models on BS1, BS2, BW1, and BW2; 2–5 Section Models on BW3.
† 7–9 Section Models on BS1, BS2, BW1, and BW2; 6–7 Section Models on BW3.
Note: Accessory High Limit Control is a strap-on aquastat used as an auxiliary limit or reverse acting circulator control.
—3—
CIRCULATOR CURVE
WATER FLOW M3/H
12
10
1
8
23 45
3
6
4
TOTAL HEAD FEET
2
40
8 12162024
WATER FLOW GPM
2
1
TOTAL HEAD METERS
WATER BOILER CIRCULATOR CURVE
ELECTRICAL DATA
ALL MODELS
Voltage—Hertz—Phase 115 — 60 — 1
Minimum Branch Circuit Wire Size (AWG) 14
Maximum Fuse Size (Amps) 15
Control Circuit Power Available 40va–@ 24v
STANDARD BOILER WARRANTIES (Yrs)
MODEL BW1 BW2 BW3 BW4 BW5 BW9 BS1 BS2
Circulator Pump 3 3 3 3 3 3
Vent Damper 5 5 5 5
Heat Exchanger Section Assembly (Non-prorated) 20 20 20 20 20 15 12 12
Oil Burner 3 3
®
ama
ASME
—4—
CERTIFIED
®
MODELS BW9
The BW9 is a gas fired direct vent condensing hot water boiler with cast aluminum heat exchanger sections. A revolutionary cast aluminum heat exchanger means better heat transfer and thermal storage than similarly sized cast iron boiler, which results in higher efficiency. The heating system water absorbs large amounts of heat from the cast aluminum heat exchanger, cooling the flue gases and causing condensation. Sealed combustion, premix gas burner, and low flame temperature means drastically reduced CO and NOx emissions, which contribute to a cleaner and healthier environment.
The BW9, unlike normal residential atmospheric and induced draft boilers, takes its combustion air directly from the outdoors (sealed combustion) and does not compete with building occupants for fresh air. Sealed combustion (also known as direct vent) is the safest and best way to obtain plenty of clean combustion air. The induced draft fan draws in the outside combustion air, then takes the cooler flue gases from the heat exchanger and provides a positive removal of the flue gases from the building through inexpensive and readily available PVC and CPVC pipes.
FEATURES
RANGE OF CAPACITIES —Three sizes ranging from 50,000
through 100,000 Btuh input. COMPLETELY PACKAGED —Each boiler is completely
assembled, including all controls (except room thermostat). All necessary wiring is factory installed. The boiler is ready for gas piping, room thermostat, and electrical power connections as shipped. Circulator is shipped pre-wired with 6 ft bx conduit for easy installation for supply side pumping.
VENTING —This boiler is direct vented with PVC and CPVC pipe. See the Installation Instructions for common venting requirements.
ALUMINUM SECTIONS —These sections speed heat transfer to the boiler water. With faster thermal response, greater comfort and economy are achieved.
PRE-MIX BURNER —Provides quiet operation and improved combustion efficiency.
CONTROLS —Integrated Boiler Control provides safe, dependable operation of burners. Factory-installed safety components provide maximum safety against overheating, pressure buildup, and low-water operation.
SECTIONS TESTED —Each section is hydrostatically tested to 50 psig. Individual sections are tested to 125 psig at factory. Assembled sections are tested to 75 psig at the factory. The maximum allowable pressure is 50 psig for hot water boilers.
PROPANE CONVERTIBLE —With factory approved conversion kit accessory.
WARRANTY —The aluminum sections are covered by a limited 15-year warranty on the entire assembly. Circulator pump is covered by a limited 3-year warranty. All other parts are covered by a 1-year limited warranty.
SPECIFICATIONS
UNIT SIZE 050 075 100
Sections 1
GAS CONTROLS
Gas Valve Honeywell
Inlet Size In. 1/2
Ignition Hot Surface Ignition
BurnerStainless/Titanium Alloy 1
Burner Orifice No. 0.0615
CONTROLS
Limit Control Range °F 100-200
Pressure Relief Valve Setting Psig 30
Integrated Boiler Control UTEC factory installed
CIRCULATOR
Taco Model 007
Full Load Amps 2.0 AMPS/330 WATTS
Flange Size FPT In. 1-1/4
#48 #44
5