Bryant ASPAX1BBA015 User Manual

Page 1
C
U
S
Installation and
Owner’s Manual
Air-cooled Automatic
Standby Generators
Model: ASPAX1BBA015
(13 kW NG, 15 kW LP)
LISTE
D
GENERAC
POWER SYSTEMS, INC.
*This manual should remain with the unit.*
or in life-support applications.
R
R
DANGER
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!
Page 2
INTRODUCTION
Thank you for purchasing this model of the Bryant product line. This model is a compact, high perfor­mance, air-cooled, engine-driven generator designed to automatically supply electrical power to operate critical loads during a utility power failure.
This unit is factory installed in an all-weather, metal enclosure that is intended exclusively for outdoor installation. This generator will operate using either vapor withdrawn liquid propane (LP) or natural gas (NG).
This unit meets the 1998 and later California emissions regulations. To ensure that the engine continues to meet these regulations, refer to the following information and instructions in this owner’s manual.
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, contact the nearest dealer for starting, operating and servicing procedures.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert person­nel to special instructions about a particular opera­tion that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their defini­tions are as follows:
DANGER
After this heading, read instructions that, if not
strictly complied with, will result in serious per­sonal injury, including death, in addition to severe property damage.
After this heading, read instructions that, if not
strictly complied with, may result in serious per­sonal injury or property damage.
After this heading, read instructions that, if not
strictly complied with, could result in damage to equipment and/or property.
NOTE:
After this heading, read explanatory statements
that require special emphasis.
These safety warnings cannot eliminate the haz­ards that they indicate. Common sense and strict compliance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates follows:
This symbol points out important safety infor-
mation that, if not followed, could endanger personal safety and/or property of others.
This symbol points out potential explosion haz-
ard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock
hazard.
The operator is responsible for proper and safe use of the equipment. The manufacturer strongly recom­mends that the operator read this Owner's Manual and thoroughly understand all instructions before using this equipment. The manufacturer also strong­ly recommends instructing other users to properly start and operate the unit. This prepares them if they need to operate the equipment in an emergency.
CONTENTS
This manual contains pertinent owner’s information, including warranty, electrical diagrams, exploded views and lists of repair parts, for model:
• Model ASPAX1BBA015 – 13 kW NG, 15 kW LP, V­twin GT-990 Engine
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by a dealer. Normal maintenance service and replacement of parts are the responsibility of the owner/operator and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage contribute to the need for mainte­nance service.
Proper maintenance and care of the generator ensures a minimum number of problems and keep operating expenses at a minimum. See a dealer for service aids and accessories.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs, simply contact a dealer for assistance. Service techni­cians are factory-trained and are capable of handling all service needs.
When contacting a dealer about parts and service, always supply the complete model number and serial number of the unit as given on its data decal, which is located on the generator.
The Bryant Dealer is:
Dealer Name
Address
City State Zip
Model No.______________ Serial No._______________
Page 3
Table of Contents
15 kW Generator
Introduction ........................Inside Front Cover
Read This Manual Thoroughly ........................ IFC
Contents .......................................................... IFC
Operation and Maintenance ............................ IFC
How to Obtain Service ..................................... IFC
Safety Rules ........................................................2
Standards Index ..................................................3
Section 1 – General Information ...................4
1.1 Unpacking/Inspection .................................... 4
1.2 Location ........................................................ 4
1.3 Protection Systems ........................................4
1.4 System Set LED ............................................4
1.5 The Generator ...............................................5
1.6 Specifications ................................................ 6
1.6.1 Generator ........................................... 6
1.6.2 Engine ................................................ 6
1.7 Fuel Requirements and Recommendations ...6
1.8 Fuel Consumption ......................................... 6
1.9 Reconfiguring the Fuel System ......................7
1.9.1 15 kW, 990cc Engines ........................7
1.10 Location ........................................................ 7
1.10.1 Generator ........................................... 7
1.10.2 Transfer Switch .................................. 8
1.11 Battery Installation ........................................ 8
1.12 The Battery ................................................... 8
Section 2 – Post Installation Start-up
and Adjustments .........................9
2.1 Before Initial Start-up ....................................9
2.2 Check Transfer Switch Operation .................9
2.3 Electrical Checks ..........................................9
2.4 Generator Tests Under Load ....................... 10
2.5 Checking Automatic Operation .................... 10
2.6 Adjusting the Regulator (Natural Gas Only) .. 11
2.7 Engine Governor Adjustment ...................... 12
2.7.1 15 kW Units ..................................... 12
2.8 Voltage Regulator Adjustment ...................... 12
Section 3 – Operation ....................................12
3.1 Break-in Procedure .....................................12
3.2 Using the Auto/Off/Manual Switch ............... 13
3.2.1 “Auto” Position ..................................13
3.2.2 “Off” Position....................................13
3.2.3 “Manual” Position ............................. 13
3.3 Automatic Transfer Operation ..................... 13
3.3.1 12 VDC Accessory Outlet .................13
3.3.2 120 VAC GFCI Outlet ....................... 14
3.4 Sequence of Automatic Operation ...............14
3.5 Manual Transfer Operation .........................14
3.5.1 Transfer to Generator
Power Source .....................................14
3.5.2 Transfer Back to Utility
Power Source .....................................15
3.6 Setting the Exercise Timer .......................... 15
3.7 Protection Systems ......................................15
3.7.1 Low Oil Pressure Switch .................. 15
3.7.2 High Temperature Switch .................15
3.7.3 Overcrank ........................................16
3.7.4 Overspeed ........................................ 16
Section 4 – Maintenance ...............................16
4.1 Fuses ...........................................................16
4.2 Checking the Engine Oil Level ..................... 16
4.3 Changing the Engine Oil .............................. 16
4.3.1 Engine Oil Recommendations .......... 16
4.3.2 Oil Change Procedure .......................17
4.4 Changing the Oil Filter ................................ 17
4.5 Changing the Engine Air Cleaner ................. 17
4.5.1 15 kW Generators ............................ 17
4.6 Spark Plug(s) .............................................. 17
4.7 Battery Maintenance ....................................18
4.8 Adjusting Valve Clearance ........................... 18
4.9 Cooling System ...........................................19
4.10 Attention After Submersion .........................19
4.11 Corrosion Protection ................................... 19
4.11.1 Additional Corrosion Protection .......19
4.12 Out of Service Procedure ............................. 20
4.12.1 Removal From Service......................20
4.12.2 Return to Service ............................. 20
4.13 Service Schedule ......................................... 21
Section 5 – Troubleshooting ........................ 22
5.1 Troubleshooting Guide ................................ 22
Section 6 – Mounting Dimensions ............. 23
Section 7 – Electrical Data ........................... 24
Section 8 – Exploded Views and
Parts Lists ................................... 28
Section 9 – Warranty ..................................... 40
1
Page 4
IMPORTANT SAFETY INSTRUCTIONS
15 kW Generator
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe
operation be copied and posted in potential hazard areas. Safety should be stressed to all
operators, potential operators, service and repair technicians for this equipment.
The engine exhaust from this product
contains chemicals known to the state
defects or other reproductive harm.
This product contains or emits chemicals known to the state of California to cause
cancer, birth defects or other reproductive harm.
Study these SAFETY RULES carefully before installing,operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely, efficiently and reliably only if it is properly installed, operated and maintained.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warn­ings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. Any personal injury or property damage resulting from the use of a procedure, work method or operating technique not specifically recommended by the manufacturer, shall be the sole responsibility of the operator. Operators who deviate from manufacturer recommended safety procedures and operating techniques, or fail to take the necessary precautions, do so at their own risk.
WARNING:
of California to cause cancer, birth
WARNING:
DANGER
Despite the safe design of this generator, oper-
ating this equipment imprudently, neglecting its maintenance or being careless can cause pos­sible injury or death. Permit only responsible and capable persons to operate or maintain this equipment.
Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot
during operation. Exercise care near running generators.
2
GENERAL HAZARDS
• For safety reasons, the manufacturer recommends that the installation, initial start-up and mainte­nance of this equipment is carried out by a deal­er.
• The engine exhaust fumes contain carbon monox­ide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. This exhaust system must be installed properly, in strict com­pliance with applicable codes and standards. Following installation, do nothing that might ren­der the system unsafe or in noncompliance with such codes and standards.
• Keep hands, feet, clothing, etc., away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and venti­lating air is critical to correct generator operation. Do not alter the installation or permit even partial blockage of ventilation provisions, as this can seri­ously affect safe operation of the generator. The generator MUST be installed outdoors.
• When working on this equipment, remain alert at all times. Never work on the equipment when physically or mentally fatigued.
• Inspect the generator regularly, and contact the nearest dealer for parts needing repair or replace­ment.
• Before performing any maintenance on the gen­erator, disconnect its battery cables to prevent accidental start up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating con­ditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
ELECTRICAL HAZARDS
• All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in opera­tion. Avoid contact with bare wires, terminals, connections, etc., while the unit is running. Ensure all appropriate covers, guards and barriers are in place before operating the generator. If work must
Page 5
be done around an operating unit, stand on an insulated, dry surface to reduce shock hazard.
• Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• The National Electrical Code (NEC) requires the frame and external electrically conductive parts of the generator to be connected to an approved earth ground. Local electrical codes also may require proper grounding of the generator electrical sys­tem.
• After installing this home standby electrical sys­tem, the generator may crank and start at any time without warning. When this occurs, load circuits are transferred to the STANDBY (GENERATOR) power source. To prevent possible injury if such a start and transfer occur, always set the generator’s AUTO/OFF/MANUAL switch to its OFF position before working on equipment and remove the 7.5A and 15A fuses from the generator control panel.
• In case of accident caused by electric shock, imme­diately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting imple­ment, such as a dry rope or board, to free the vic­tim from the live conductor. If the victim is uncon­scious, apply first aid and get immediate medical help.
• Never wear jewelry when working on this equip­ment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving com­ponents causing injury.
FIRE HAZARDS
• For fire safety, the generator must be installed and maintained properly. Installation always must comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is installed in accordance with the manufacturer’s instructions and recommendations. Following proper installa­tion, do nothing that might alter a safe installation and render the unit in noncompliance with the aforementioned codes, standards, laws and regula­tions.
• Keep a fire extinguisher near the generator at all times. Extinguishers rated “ABC” by the National Fire Protection Association are appropriate for use on the standby electric system. Keep the extin­guisher properly charged and be familiar with its use. Consult the local fire department with any questions pertaining to fire extinguishers.
IMPORTANT SAFETY INSTRUCTIONS
15 kW Generator
EXPLOSION HAZARDS
• Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no com­bustible materials are left in the generator com­partment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surround­ing the generator clean and free from debris.
• Gaseous fluids such as natural gas and liquid pro­pane (LP) gas are extremely EXPLOSIVE. Install the fuel supply system according to applicable fuel-gas codes. Before placing the home standby electric system into service, fuel system lines must be properly purged and leak tested according to applicable code. After installation, inspect the fuel system periodically for leaks. No leakage is permit­ted.
STANDARDS INDEX
In the absence of pertinent standards, codes, regu­lations and laws, the published information listed below may be used as installation guide for this equipment.
1. NFPA No. 37, STATIONARY COMBUSTION
ENGINES AND GAS TURBINES, available from the National Fire Protection Association, 470 Atlantic Avenue, Boston, MA 02210.
2. NFPA No. 76A, ESSENTIAL ELECTRICAL
SYSTEMS FOR HEALTH CARE FACILITIES, available same as Item 1.
3. NFPA No. 54, NATIONAL FUEL GAS CODE,
available same as Item 1.
4. NFPA No. 58, AMERICAN NATIONAL STANDARD
FOR STORAGE AND HANDLING OF LIQUEFIED PETROLEUM GAS, available same as Item 1.
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL
ELECTRIC CODE, available same as Item 1.
6. Article X, NATIONAL BUILDING CODE, available
from the American Insurance Association, 85 John Street, New York, N.Y. 10038.
7. AGRICULTURAL WIRING HANDBOOK, avail-
able from the Food and Energy Council, 909 University Avenue, Columbia, MO 65201.
8. ASAE EP-3634, INSTALLATION AND
MAINTENANCE OF FARM STANDBY ELECTRICAL SYSTEMS, available from the American Society of Agricultural Engineers, 2950 Niles Road, St. Joseph, MI 49085.
9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE
LIQUIDS CODE, available same as Item 1.
3
Page 6
Section 1 — General Information
15 kW Generator
DANGER
Only qualified electricians or contractors should
attempt such installations, which must comply strictly with applicable codes, standards and regulations.
1.1 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for damage.
• This standby generator set has been factory sup­plied with a weather protective enclosure that is intended for outdoor installation only.
If this generator is used to power electrical load
circuits normally powered by a utility power source, it is required by code to install a trans­fer switch. The transfer switch must effectively isolate the electrical system from the utility distribution system when the generator is oper­ating (NEC 700, 701 and 702). Failure to isolate an electrical system by such means will result in damage to the generator and also may result in injury or death to utility power workers due to backfeed of electrical energy.
If any loss or damage is noted at time of delivery, have the person(s) making the delivery note all damage on the freight bill or affix his or her signature under the consignor's memo of loss or damage.
If a loss or damage is noted after delivery, separate the damaged materials and contact the carrier for claim procedures.
“Concealed damage” is understood to mean damage to the contents of a package that is not in evidence at the time of delivery, but is discovered later.
1.2 LOCATION
To lift the generator, insert pipe having sufficient strength and diameter through the lifting holes which are located near the unit’s base (see Figure 1.1). The unit may also be lifted by using a hook and hoist method provided a spreader bar is used to ensure the lifting lines clear the roof panel.
DANGER
When lifting or hoisting equipment is used, be
careful not to contact overhead power lines.
The generator’s weight of more than 300
pounds requires proper tools, equipment and qualified personnel to be used in all phases of handling and unpacking.
1.3 PROTECTION SYSTEMS
Unlike an automobile engine, the generator may have to run for long periods of time with no operator pres­ent to monitor engine conditions. For that reason, the engine is equipped with the following systems that protect it against potentially damaging conditions:
1. Low Oil Pressure Sensor 3. Overcrank
2. High Temperature Sensor 4. Overspeed There are LED readouts on the control panel to indi-
cate that one of these faults has occurred. There is also a “System Set” LED that is described below.
1.4 SYSTEM SET LED
The “System Set” LED is lit when all of the following conditions are true:
1. The AUTO/OFF/MANUAL switch is set to the AUTO position.
2. The utility voltage being supplied to the unit is being sensed by the Control PCB. If the utility sense voltage is not connected to the unit or if it is below 168 volts AC, then the system set light will flash rapidly. This indicates that if the AUTO/ OFF/MANUAL switch is placed in the Auto posi­tion , the generator will start.
3. The “Not In Auto” dip switch is set to the OFF position on the control board.
4. No alarms are present, for example, low oil pres­sure, high temperature, etc.
4
Page 7
1.5 THE GENERATOR
Figure 1.1 – 15 kW, V-twin GT-990
Dipstick
Oil
Section 1 — General Information
15 kW Generator
Control
Panel
Data
Decal
Exhaust
Enclosure
Lifting Holes
Oil Filter
Battery
Compartment
GFCI Outlet
Fuel Regulator
Fuel Inlet
Composite Base
5
Page 8
Section 1 — General Information
15 kW Generator
1.6 SPECIFICATIONS
1.6.1 GENERATOR
Rated Max. Cont. Power Capacity (Watts*) ..... 13,000 NG/
15,000 LP†
Rated Voltage....................................................... 120/240
Rated Max. Continuous Load Current (Amps)
120 Volts + ......................................108.3 NG/125.0 LP
240 Volts .............................................. 54.2 NG/62.5 LP
Main Line Circuit Breaker ....................................65 Amp
Phase ............................................................................. 1
Number of Rotor Poles ................................................... 2
Rated AC Frequency ................................................60 Hz
Power Factor ..................................................................1
Recommended Air Filter ...........................Part # 0C8127
Battery Requirement at
-17.8° C (0° F) ....................... Group 26/26R 12 Volts and
525 Cold-cranking Amperes Minimum
Weight ........................................................... 487 Pounds
Output Sound Level @ 23 ft (7m)
at full load ................................................... 71.5 db (A)
Normal Operating Range ........................... -20°F (-28.8°C)
* Maximum wattage and current are subject to and limited by such factors
as fuel Btu content, ambient temperature, altitude, engine power and con­dition, etc. Maximum power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6° C (10° F) above 16° C (60° F).
+ Total current in two separate circuits. Current in each circuit must not
exceed the value stated for 240V.
1.6.2 ENGINE
Type of Engine ......................................................GT-990
Number of Cylinders ...................................................... 2
Rated Horsepower .................................. 30 @ 3,600 rpm
Displacement ..........................................................992cc
Cylinder Block .....................Aluminum w/Cast Iron Sleeve
Valve Arrangement ..................................Overhead Valves
Ignition System ..............................Solid-state w/Magneto
Recommended Spark Plug .................................. RC12YC
Spark Plug Gap ............................0.508 mm (0.020 inch)
Compression Ratio ................................................... 9.5:1
Starter .................................................................... 12Vdc
Oil Capacity Including Filter.................... Approx. 1.7 Qts
Recommended Oil Filter ........................... Part # 070185
Recommended Air Filter ...........................Part # 0C8127
Operating RPM ........................................................ 3,600
to 104°F (40°C)
1.7 FUEL REQUIREMENTS AND RECOMMENDATIONS
With LP gas, use only the vapor withdrawal sys­tem. This type of system uses the vapors formed
above the liquid fuel in the storage tank.
The engine has been fitted with a fuel carburetion system that meets the specifications of the 1997 California Air Resources Board for tamper-proof dual fuel systems. The unit will run on natural gas or LP gas, but it has been factory set to run on natural gas. Should the primary fuel need to be changed to LP gas, the fuel system needs to be reconfigured. See instructions in the “Reconfiguring the Fuel System” section.
Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas. Ask the fuel supplier for the Btu content of the fuel.
Required fuel pressure for natural gas is 5 inches
to 7 inches water column (0.18 to 0.25 psi); and for liquid propane, 11 inches to 14 inches of water column (0.4 to 0.5 psi).
NOTE:
Any piping used to connect the generator to the fuel supply should be of adequate size to ensure the fuel pressure NEVER drops below 4 inches water column for natural gas or 10 inches water column for liquid propane for all load ranges.
1.8 FUEL CONSUMPTION
Model # Nat. Gas (*) LP Vapor (**) 1/2 Load Full Load 1/2 Load Full Load
05207 156 220 1.58/58 2.40/88
* Natural gas is in cubic feet per hour. ** LP is in gallons per hour/cubic feet per hour. *** Values given are approximate.
DANGER
 Gaseous fuels such as natural gas and liquid
propane (LP) gas are highly explosive. Even the slightest spark can ignite such fuels and cause an explosion. No leakage of fuel is permitted. Natural gas, which is lighter than air, tends to collect in high areas. LP gas is heavier than air and tends to settle in low areas.
6
Page 9
G
T
T
U
T
G
OSE
S
L
T
OR
OUSING PORT
JUSTER
SC
S
OU
S
Section 1 — General Information
15 kW Generator
1.9 RECONFIGURING THE FUEL SYSTEM
1.9.1 15KW, 990CC ENGINES
To reconfigure the fuel system from NG to LP, follow these steps:
NOTE:
The primary regulator for the propane supply is NOT INCLUDED with the generator. A fuel pres­sure of 11 to 14 inches of water column (0.4 to
0.5 psi) to the fuel inlet of the generator MUST
BE SUPPLIED.
1. Turn off the gas supply. (if connected)
2. Open the roof and remove the door.
3. Remove the battery. (if installed)
4. Remove the engine air in baffle located on the left-
hand side of the battery compartment. Two M6 screws are located on top of the baffle and two M6 screws are located on the inside of the baffle towards the back.
5. Remove the small hose clamp and hose from the
fuel regulator. It may be necessary to pry the hose off of the brass fitting using a screwdriver to gen­tly lift up the hose edge.
6. Remove the small brass hose fitting from the
regulator casting.
7. Place the small fuel jet, thread side first, into the
threaded hole originally occupied by the brass hose fitting (Figure 1.2).
8. Using a short No. 2 Phillips screw driver, thread
the small fuel jet into the regulator casting. Do not over tighten.
9. Apply thread sealant to the threads of the hose
fitting and replace it into the regulator body.
10. Re-attach the small hose and hose clamp and
tighten as necessary.
11. Replace the engine air in baffle using the four M6
screws.
12. Identify both brass adjustment screws on the
regulator.
NOTE:
One adjustment screw can be accessed from the front of the unit and the second can be accessed from the back of the unit enclosure by removing the plastic hole plug. The screw can be turned with a long flat blade screwdriver.
13. To adjust the system to run on LP fuel, turn
BOTH adjuster screws 1/2 TURN CLOCKWISE. The system should now be set for maximum power and best performance. DO NOT, UNDER
ANY CIRCUMSTANCES, REMOVE THE SET PINS FROM THE REGULATOR HOUSING. THIS WILL VOID THE WARRANTY.
Figure 1.2 - Demand Regulator
TLET PORT
FUEL H
BRASS HOSE FITTIN
IDLE CIRCUI
POR
1/8 NP
BRASS HOSE
FITTIN
AD
REW
REGULAT H
MAL
FUEL JE
14. It may be necessary to make minor adjustments to the preset adjustment screw settings to achieve maximum power, particularly at higher altitudes. If experiencing problems with the unit producing maximum power, follow the procedure in Section
2.6 (Adjusting the Fuel Regulator).
1.10 LOCATION
1.10.1 GENERATOR
Install the generator set, in its protective enclosure, outdoors, where adequate cooling and ventilating air is always available. Consider these factors:
• Install the unit where air inlet and outlet open-
ings will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blowing or drifting, consider using a windbreak to protect the unit.
• Install the generator on high ground where water
levels will not rise and endanger it.
• Allow sufficient room on all sides of the generator
for maintenance and servicing. A good rule is to allow three feet of space on all sides.
• Where strong prevailing winds blow from one
direction, face the generator air inlet openings to the prevailing winds.
• Install the generator as close as possible to the fuel
supply, to reduce the length of piping.
• Install the generator as close as possible to
the transfer switch. HOWEVER, REMEMBER THAT LAWS OR CODES MAY REGULATE THE DISTANCE.
• The genset must be installed on a level surface.
The base frame must be level within two (2) inches all around.
7
Page 10
Section 1 — General Information
15 kW Generator
1.10.2 TRANSFER SWITCH
1.10.2.1 15 kW Units
Transfer switches for use with this generator are sold separately and can be purchased from dealers.
• Install any transfer switch in accordance with the instructions supplied with the transfer switch.
• Failure to utilize a the manufacturer’s transfer switch with this generator will void the warranty.
1.11 BATTERY INSTALLATION
Fill the battery with the proper electrolyte fluid if necessary and have the battery fully charged before installing it.
Before installing and connecting the battery, complete the following steps:
1. Set the generator's AUTO/OFF/MANUAL switch to
OFF.
2. Turn off utility power supply to the transfer
switch.
3. Remove the 7.5 amp and 15 amp fuses from the
generator control panel.
Battery cables were factory connected at the genera­tor (Figure 1.3). Connect cables to battery posts as follows:
4. Connect the red battery cable (from starter con-
tactor) to the battery post indicated by a positive, POS or (+).
5. Connect the black battery cable (from frame
ground) to the battery post indicated by a nega­tive, NEG or (—).
6. Replace the 7.5 amp and 15 amp fuses in the
generator control panel.
NOTE:
Damage will result if battery connections are made in reverse.
Figure 1.3 – Battery Cable Connections
NOTE:
The generator is equipped with a battery trickle charger that is active when the unit is set up for automatic operation. With the battery installed and utility power source voltage available to the transfer switch, the battery receives a trickle charge while the engine is not running, to prevent self-discharge. The trickle charger is designed to help extend the life of the battery by maintain­ing the battery when the unit is not running. The trickle charge feature cannot be used to recharge a discharged battery.
1.12 THE BATTERY
Servicing of the battery is to be performed or super­vised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized person­nel away from batteries.
When replacing the battery, use the following type of battery: Group 26/26R 12-volt battery with a rating of 525 cold-cranking amps minimum for 15 kW at
-17.8º C (0º F) minimum. When using a maintenance­free battery, it is not necessary to check the specific gravity or electrolyte level. Have these procedures performed at the intervals specified in the “Service Schedule.” A negative ground system is used. Battery connections are shown on the wiring diagrams. Make sure the battery is correctly connected and terminals are tight. Observe battery polarity when connecting the battery to the generator set.
DANGER
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following pre­cautions are to be observed when working on batteries:
• Remove the 7.5A and 15A fuses from the genera­tor control panel;
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the battery; and
• Disconnect charging source prior to connecting or disconnecting battery terminals.
8
Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically conductive and corrosive.
Page 11
Section 2 — Post Installation Start-up and Adjustments
15 kW Generator
The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off immediately with water;
• Where electrolyte contacts the eyes, immediately flush thoroughly with water and seek medical attention; and
• Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) or water. The bicar­bonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.
Lead-acid batteries present a risk of fire because
they generate hydrogen gas. The following procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touch­ing the battery by first touching a grounded metal surface.
Be sure the AUTO/OFF/MANUAL switch is set to
the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.
Be sure the utility power supply is turned off, or
sparking may occur at the battery posts as the cables are attached and cause an explosion.
2.1 BEFORE INITIAL START-UP
Before starting, complete the following:
1. Set the generator’s main circuit breaker to its
OFF (or open) position.
2. Set the generator's AUTO/OFF/MANUAL switch to
the OFF position.
3. Turn OFF the utility power supply to the transfer
switch using the means provided (such as the utility main line circuit breaker).
4. Check the engine crankcase oil level and, if neces-
sary, fill to the dipstick FULL mark with the rec­ommended oil. Do not fill above the FULL mark.
5. Check the fuel supply. Gaseous fuel lines must
have been properly purged and leak tested in accordance with applicable fuel-gas codes. All fuel shutoff valves in the fuel supply lines must be open.
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing this could damage the engine.
2.2 CHECK TRANSFER SWITCH OPERATION
Refer to Section 3.5, of the owner’s manual for man­ual operation procedures.
DANGER
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the transfer switch have been positively turned off. Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.
2.3 ELECTRICAL CHECKS
Complete electrical checks as follows:
1. Set the generator’s main circuit breaker to its
OFF (or open) position.
2. Set the generator's AUTO/OFF/MANUAL switch to
the OFF position.
3. Turn OFF the utility power supply to the transfer
switch using the means provided (such as the utility main line circuit breaker).
4. Turn on the utility power supply to the transfer
switch using the means provided (such as a utility main line circuit breaker).
DANGER
The transfer switch is now electrically “hot.”
Contact with “hot” parts will result in extremely hazardous and possibly fatal electrical shock. Proceed with caution.
5. Use an accurate AC voltmeter to check utility
power source voltage across terminals N1 and N2. Nominal line-to-line voltage should be 240 volts AC.
6. Check utility power source voltage across termi-
nals N1 and the transfer switch neutral lug; then across terminal N2 and neutral. Nominal line-to­neutral voltage should be 120 volts AC.
7. When certain that utility supply voltage is compat-
ible with transfer switch and load circuit ratings, turn OFF the utility power supply to the transfer switch.
8. Set the generator's main circuit breaker to its
OFF (or open) position. Initial tests will be con­ducted at no-load condition.
9. On the generator panel, set the AUTO/OFF/
MANUAL switch to MANUAL. The engine should crank and start.
10. Let the engine warm up for about five minutes to
allow internal temperatures to stabilize. Then, set the generator’s main circuit breaker to its ON (or closed) position.
9
Page 12
Section 2 — Post Installation Start-up and Adjustments
15 kW Generator
DANGER
Proceed with caution! Generator power voltage
is now supplied to the transfer switch. Contact with live transfer switch parts will result in dan­gerous and possibly fatal electrical shock.
11. Connect an accurate AC voltmeter and a fre­quency meter across transfer switch terminal lugs E1 and E2. Voltage should be 242-252 volts; frequency should read about 61-63 Hertz.
12. Connect the AC voltmeter test leads across ter­minal lug E1 and neutral; then across E2 and neutral. In both cases, voltage reading should be 121-126 volts AC.
13. Set the generator’s main circuit breaker to its OFF (or open) position. Let the engine run at no­load for a few minutes to stabilize internal engine generator temperatures.
14. Set the generator's AUTO/OFF/MANUAL switch to OFF. The engine should shut down.
NOTE:
It is important not to proceed until certain that generator AC voltage and frequency are correct and within the stated limits. Generally, if both AC frequency and voltage are high or low, the engine governor requires adjustment. If frequency is cor­rect, but voltage is high or low, the generator’s voltage regulator requires adjustment.
2.4 GENERATOR TESTS UNDER LOAD
To test the generator set with electrical loads applied, proceed as follows:
1. Set generator’s main circuit breaker to its OFF (or open) position.
2. Set the generator's AUTO/OFF/MANUAL switch to OFF.
3. Turn OFF the utility power supply to the transfer switch, using the means provided (such as a util­ity main line circuit breaker).
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the transfer switch have been positively turned off. Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.
4. Manually set the transfer switch to the STANDBY position, i.e., load terminals connected to the generator's E1/E2 terminals. The transfer switch operating lever should be down.
5. Set the generator's AUTO/OFF/MANUAL switch to MANUAL. The engine should crank and start immediately.
6. Let the engine stabilize and warm up for a few minutes.
7. Set the generator’s main circuit breaker to its ON (or closed) position. Loads are now powered by the standby generator.
8. Turn ON electrical loads. Apply an electrical load equal to the full rated wattage/amperage capacity of the installed generator.
9. Connect an accurate AC voltmeter and a frequen­cy meter across terminal lugs E1 and E2. Voltage should be greater than 230 volts; frequency should be greater than 58 Hertz.
10. Let the generator run at full rated load for 20-30 minutes. Listen for unusual noises, vibration or other indications of abnormal operation. Check for oil leaks, evidence of overheating, etc.
11. When testing under load is complete, turn OFF electrical loads.
12. Set the generator's main circuit breakers to their OFF (or open) positions.
13. Let the engine run at no-load for a few minutes.
14. Set the AUTO/OFF/MANUAL switch to OFF. The engine should shut down.
2.5 CHECKING AUTOMATIC
OPERATION
To check the system for proper automatic operation, proceed as follows:
1. Set the generator’s main circuit breaker to it’s OFF (or open) position.
2. Check that the AUTO/OFF/MANUAL switch is set to OFF.
3. Turn OFF the utility power supply to the transfer switch using the means provided (such as a utility main line circuit breaker).
4. Manually set the transfer switch to the UTILITY position, i.e., load terminals connected to the util­ity power source side.
5. Turn ON the utility power supply to the transfer switch, using the means provided (such as a util­ity main line circuit breaker).
6. Set the AUTO/OFF/MANUAL switch to AUTO. Then set the generator’s main circuit breaker to its ON (or closed) position. The system is now ready for automatic operation.
7. Turn OFF the utility power supply to the transfer switch.
With the AUTO/OFF/MANUAL switch at AUTO, the engine should crank and start when the utility source power is turned OFF. After starting, the transfer switch should connect load circuits to the standby side. Let the system go through its entire automatic sequence of operation.
10
Page 13
Section 2 — Post Installation Start-up and Adjustments
15 kW Generator
With the generator running and loads powered by generator AC output, turn ON the utility power supply to the transfer switch. The following should occur:
• After about six seconds, the switch should transfer loads back to the utility power source.
• About one minute after retransfer, the engine should shut down.
2.6 ADJUSTING THE REGULATOR
(NATURAL GAS ONLY)
Although the generator has been factory set to pro­vide maximum power, it may be necessary in some areas to adjust this setting. Because natural gas has different BTU or power content across the country the engine may not perform as designed.
If experiencing engine problems at high or full load conditions follow these steps. It will require a fre­quency meter to perform this procedure.
1. Turn off utility power to the main distribution
panel in the house. This can be done by switching the service main breaker to the off or open posi­tion.
2. Allow the generator to start before loading the
generator. Confirm the no-load frequency with the roof open and door off is set at 63-63.5 Hz. Transfer load to emergency circuits.
3. Turn on appliances, lights, pumps, etc., that are
on the emergency circuits in an attempt to fully load the generator. Be cautious not to overload the generator. Use the following chart as a guide:
Unit 120 Volts 240 Volts
15 kW 108.3 amps 54.2 amps
Figure 2.1 — Dual Fuel Regulators
V-twin
Adjustment Screw
(Both Sides)
Set Pin
(Both Sides)
Adjustment Screw
(One Side Only)
6. When the highest frequency is reached maximum power has been set. Then turn both adjustment screws 1/4 turn counterclockwise. Regulator is now set.
410
Set Pin
Figure 2.2 — Placement of Regulator
Adjustment Screw
4. When full load has been achieved. Connect a fre­quency meter to the output lugs of the generator’s main line circuit breaker.
5. The fuel regulator is fitted with two adjustment screws. While watching the frequency meter, slowly turn the adjustment screw clockwise or counterclockwise one at a time until highest fre­quency is read on the meter. Only limited adjust­ment is available between the set pins. Under no circumstances should any of the pins be removed (Figures 2.1 and 2.2).
7. Turn utility power to the main distribution panel back on. This can be done by switching the ser­vice main breaker to the on or closed position. Allow the generator to shut down.
Do not make any unnecessary adjustments.
Factory settings are correct for most applica­tions. However, when making adjustments, be careful to avoid overspeeding the engine.
If this procedure or equipment are not available, locate the nearest Dealer and they can perform the adjustments.
NOTE:
A service fee may be charged for this adjustment.
11
Page 14
Section 3 — Operation
15 kW Generator
2.7 ENGINE GOVERNOR ADJUSTMENT
If both AC frequency and voltage are correspondingly high or low, adjust the engine governor as follows:
2.7.1 15 KW UNITS
1. Loosen governor clamp bolt (See Figure 2.3).
Figure 2.3 — V-twin Engine Governor
Adjustment
Idle Spring
Governor Shaft
(Rotate
Clockwise)
Governor Clamp Bolt
2. Completely remove the idle spring.
3. With governor arm at wide open throttle position, rotate governor shaft fully clockwise. Tighten clamp bolt to 84 inch-pounds.
4. Start unit and apply full load. Use full load speed adjust screw (Figure 2.4) to adjust frequency to 58 Hz.
5. Remove load, stop engine, loosen the idle adjust screw and reconnect the idle spring.
6. Push the governor arm to the closed throttle posi­tion. Make sure the idle spring does not stretch at all.
7. Restart the unit.
8. Slowly turn the idle adjust screw to adjust the no­load idle frequency to 63-63.5 Hz.
9. The governor is now set.
Figure 2.4 — V-twin Full Load Speed Adjust
12
No Load Idle Adjustment Screw
Screw
Full Load Speed Adjust Screw
2.8 VOLTAGE REGULATOR ADJUSTMENT
With the frequency between 62-63.5 Hertz, slowly turn the slotted potentiometer (Figure 2.5) until line voltage reads 244-252 volts.
NOTE:
Remove the access panel on top of the control panel to adjust the voltage regulator.
Figure 2.5 – Voltage Adjustment Potentiometer
NOTE:
The voltage regulator is housed above the generator's control panel. The regulator maintains a voltage in direct proportion to frequency. For example, at 62 Hertz, line-to-neutral voltage will be 124 volts.
3.1 BREAK-IN PROCEDURE
Once the unit has been installed and all electrical checks have been made, it is strongly recommended that the following “Break-in Procedure” be completed to ensure correct generator operation in the future.
1. Set the generator’s AUTO/OFF/MANUAL switch to
AUTO.
2. Turn OFF the utility power supply to the transfer
switch using the means provided (such as a utility main line circuit breaker).
3. The unit will start, and the transfer switch will
transfer to standby.
4. Using the transfer switch’s built-in emergency
load center, turn on circuits to load the generator to approximately 25% rated load and run the unit for one hour.
5. Run the unit for one hour at 50% rated load.
6. Run the unit for one hour at 75% rated load.
7. Run the unit for one hour at 100% rated load.
8. Turn ON the utility power supply to the transfer
switch, which will allow the transfer switch to transfer back to utility power. The unit will con­tinue to run for one minute and then shut down.
Page 15
9. Allow the unit to cool.
10. Set the generator’s main circuit breaker to its OFF (or OPEN) position.
11. Set the generator's AUTO/OFF/MANUAL switch to OFF. Remove the 7.5A and 15A fuses from the generator control panel. Disconnect the battery cables as outlined in “General Hazards” (page
2).
12. Drain the oil and remove the oil filter. Replace the oil filter according to Section 3.4, “Changing the Oil Filter”. Replace the oil with synthetic oil as recommended in Section 3.3, “Changing the Engine Oil”.
13. Reconnect the battery cables as outlined in “General Hazards” (page 2) and insert the 7.5A and 15A fuses into the generator control panel. The generator is now ready for service.
3.2 USING THE AUTO/OFF/MANUAL
SWITCH (FIGURE 3.1)
3.2.1 “AUTO” POSITION
Selecting this switch position activates fully auto­matic system operation. It also permits starting and exercising the engine every seven days with the set­ting of the exercise timer (see “Setting the Exercise Timer” section). This position also is used for remote starting, when it is set up.
3.2.2 “OFF” POSITION
This switch position shuts down the engine. This position also prevents automatic operation.
Section 3 — Operation
15 kW Generator
With the switch set to AUTO, the engine may
crank and start at any time without warning. Such automatic starting normally occurs when utility power source voltage drops below a pre­set level or during the normal exercise cycle. To prevent possible injury that might be caused by such sudden starts, always set the switch to OFF and remove both fuses before working on or around the generator or transfer switch. Then, place a “Do Not Operate” tag on the generator panel and on the transfer switch.
3.3 AUTOMATIC TRANSFER OPERATION
To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are
set to their UTILITY position, i.e., loads con­nected to the utility power source (Figure 3.2).
2. Be sure that normal utility power source voltage
is available to transfer switch terminal lugs N1 and N2.
3. Set the generator’s AUTO/OFF/MANUAL switch to
AUTO.
4. Set the generator’s main circuit breaker to its ON
(or CLOSED) position.
With the preceding steps complete, the generator will start automatically when utility source voltage drops below a preset level. After the unit starts, loads are transferred to the standby power source. Refer to Section 3.4, “Sequence of Automatic Operation.”
3.2.3 “MANUAL” POSITION
Set the switch to MANUAL to crank and start the engine. Transfer to standby power will not occur unless there is a utility failure.
Figure 3.1 – Generator Control Panel
MAN.
12 VDC
ACCESSORY
OUTLET 7.5A MAX
EXTERNAL
GFCI
CIRCUIT
BREAKER
SYSTEM SET
LOW OIL
HIGH TEMP.
OVER SPEED
OVER CRANK
FLA S HING GREEN LED =
N O U T IL IT Y S EN S E
4FLAS HING RED LEDS =
EX ERCIS ER NO T S ET
OUTLET FUSE
7.5A
SYSTEM FUSE
15A
AUTO
EXERCISE
OFF
SET
TIME
3.3.1 12 VDC ACCESSORY OUTLET
The generator is equipped with a 12 VDC accessory outlet in the generator control panel (Figure 3.1). With the generator running or in standby mode, this outlet may be used to temporarily power low power accessories such as a work light, cell phone, radio or any other automotive style accessory. This outlet is capable of delivering a MAXIMUM of 7.5 amps. If the accessory to be used through this circuit demands too much power, the fuse that protects this circuit will melt open and the circuit will not be functional.
This 12 VDC outlet draws power from the gen-
erator’s starting battery and extended use of this outlet may drain the battery and the engine may not start. This outlet should NOT be used for battery charging.
13
Page 16
Section 3 — Operation
15 kW Generator
3.3.2 120 VAC GFCI OUTLET
The generator is equipped with an external 15 amp, 120 volt, GFCI convenience outlet that is located in the right rear of the generator enclosure. When the generator is running, in the absence of utility power, this outlet may be used to power items outside a home such as lights or power tools. This outlet may also be used when utility power is present by run­ning the generator in manual mode. This outlet does not provide power if the generator is not running. This outlet is protected by a 15 amp circuit breaker located in the generator control panel (Figure 3.1).
3.4 SEQUENCE OF AUTOMATIC OPERATION
The generator’s control panel houses a control logic circuit board. This board constantly monitors util­ity power source voltage. Should that voltage drop below a preset level, circuit board action will signal the engine to crank and start. After the engine starts, the circuit board signals the transfer switch to acti­vate and connect load circuits to the standby power supply (load terminal lugs T1/T2 connect to terminal lugs E1/E2).
Upon restoration of utility source voltage above a preset level, generator circuit board action signals the transfer switch to transfer loads back to that power supply. After retransfer, the engine is signalled to shut down.
The actual sequence of operation is controlled by sensors and timers on a control logic circuit board, as follows:
A. Utility Voltage Dropout Sensor
• This sensor monitors utility source voltage.
• If utility source voltage drops below about 70 percent of the nominal supply voltage, the sensor energizes a 15-second timer.
• Once the timer has expired, the engine will crank and start.
B. Engine Warm-up Time Delay
• This mechanism lets the engine warm up for about 10 seconds before the load is transferred to a standby source.
C. Standby Voltage Sensor
• This sensor monitors generator AC output volt­age. When the voltage has reached 50 percent of the nominal rated voltage, transfer to standby can occur.
D. Utility Voltage Pickup Sensor
• This sensor monitors utility power supply volt­age. When that voltage is restored to above 70 percent of the nominal source voltage, a retrans­fer time delay starts timing.
E. Retransfer Time Delay
• This timer runs for about 15 seconds.
• At end of a 15-second delay, circuit board action de-energizes the transfer relay in the transfer switch.
• Retransfer to utility power source then occurs.
F. Engine Cool-down Timer
• When the load is transferred back to utility power source, the engine cool-down timer starts tim­ing.
• The timer will run for about one minute, and the generator will then shut down.
3.5 MANUAL TRANSFER OPERATION
3.5.1 TRANSFER TO GENERATOR POWER
SOURCE
To start the generator and activate the transfer switch manually, proceed as follows:
1. Set the generator’s AUTO/OFF/MANUAL switch to OFF.
2. Set the generator’s main circuit breaker to its OFF (or OPEN) position.
3. Turn OFF the utility power supply to the transfer switch using the means provided (such as a utility main line circuit breaker).
DANGER
Do not attempt to activate the transfer switch
manually until all power voltage supplies to the switch have been positively turned off. Failure to turn off all power voltage supplies may result in extremely hazardous and possibly fatal elec­trical shock.
4. Use the manual transfer handle inside the trans­fer switch to move the main contacts to their “Standby”position, i.e., loads connected to the standby power source (Figure 3.2).
Figure 3.2 – Manual Transfer Switch Operation
14
Page 17
Section 3 — Operation
15 kW Generator
5. To crank and start the engine, set the AUTO/OFF/ MANUAL switch to MANUAL.
6. Let the engine stabilize and warm up for a few minutes.
7. Set the generator’s main circuit breaker to its ON (or CLOSED) position. The standby power source now powers the loads.
3.5.2 TRANSFER BACK TO UTILITY POWER
SOURCE
When utility power has been restored, transfer back to that source and shut down the generator. This can be accomplished as follows:
1. Set the generator’s main circuit breaker to its OFF (or OPEN) position.
2. Let the engine run for a minute or two at no-load to stabilize the internal temperatures.
3. Set the generator’s AUTO/OFF/MANUAL switch to its OFF (or OPEN) position. The engine should shut down.
4. Check that utility power supply to the transfer switch is turned OFF.
DANGER
Do not attempt to activate the transfer switch
manually until all power voltage supplies to the switch have been positively turned off. Failure to turn off all power voltage supplies may result in extremely hazardous and possibly fatal elec­trical shock.
5. Use the manual transfer handle inside the trans­fer switch to move the main contacts back to their UTILITY position, i.e., loads connected to the util­ity power source (Figure 3.2).
6. Turn ON the utility power supply to the transfer switch using the means provided.
7. Set the system to automatic operation as outlined in “Automatic Transfer Operation,” Section 2.3.
2. Hold down the set timer switch until the genera­tor starts (approximately 10 seconds) and then release.
3. The generator will start and run for approximate­ly 12 minutes and then shut down on its own. The exerciser will then be set to run at that time of day every week.
NOTE:
The exerciser will only work in the AUTO mode and will not work unless this procedure is per­formed. The exerciser will need to be reset every time the 12-volt battery is disconnected and then reconnected. The exerciser WILL NOT work if dip switch 2 (Remote Not Auto) on the controller printed circuit board is ON.
3.7 PROTECTION SYSTEMS
3.7.1 LOW OIL PRESSURE SWITCH
This switch (Figure 3.3) has normally closed contacts that are held open by engine oil pressure during cranking and operating. Should oil pressure drop below the 8 psi range, switch contacts close, and the engine shuts down. The unit should not be restarted until oil is added, and the AUTO/OFF/MANUAL switch must be turned to OFF and then back to AUTO.
3.7.2 HIGH TEMPERATURE SWITCH
This switch’s contacts (Figure 3.3) close if the tem­perature should exceed approximately 140º C (284º F), initiating an engine shutdown. The generator will automatically restart and the LED will reset once the temperature has returned to a safe operating level.
Figure 3.3 – Low Oil Pressure and
High Temperature Switches
Low Oil Switch
High Temp Switch
3.6 SETTING THE EXERCISE TIMER
The generator is equipped with an exercise timer. Once it is set, the generator will start and exercise once every seven days, on the day of the week and at the time of day the following sequence is completed. During this exercise period, the unit runs for approx­imately 12 minutes and then shuts down. Transfer of loads to the generator output does not occur during the exercise cycle.
A switch on the control panel (see Figure 3.1) permits selection of the day and time for system exercise. To select the desired day and time of day, the following sequence must be performed at that time.
1. Verify that the AUTO/OFF/MANUAL switch is set to AUTO.
Oil Drain Hose
L
o
o
s
e
n
Oil Filter
15
Page 18
Section 4 — Maintenance
15 kW Generator
3.7.3 OVERCRANK
This feature prevents the generator from damaging itself when it continually attempts to start and anoth­er problem, such as no fuel supply, prevents it from starting. The unit will crank and rest for a preset time limit. Then, it will stop cranking, and the LED will light indicating an overcrank failure. The AUTO/OFF/ MANUAL switch will need to be set to OFF and then back to AUTO to reset the generator control board.
NOTE:
If the fault is not repaired, the overcrank feature will continue to activate.
3.7.3.1 Approximate Crank Cycle Times
• 15 seconds ON
• 7 seconds OFF
• 7 seconds ON
• 7 seconds OFF
• Repeat for 45 seconds
Approximately 90 seconds total
3.7.4 OVERSPEED
This feature protects the generator from damage by shutting it down if it happens to run faster than the preset limit. This protection also prevents the genera­tor from supplying an output that could potentially damage appliances connected to the generator cir­cuit. Contact the nearest dealer if this failure occurs.
4.2 CHECKING THE ENGINE OIL LEVEL
For oil capacities, see the “Specifications,” Section. For engine oil recommendations, see Section 4.3.1. To check the engine oil level, proceed as follows (Figure 4.2):
1. Start the generator by moving the AUTO/OFF/
MANUAL switch to the MANUAL position. Allow it to run for a short while and then shut it down by moving the switch to the OFF position.
2. Remove the dipstick and wipe it dry with a clean
cloth.
3. Install the dipstick; then, remove it again. The oil
level should be at the dipstick “Full” mark. If nec­essary, add oil to the “Full” mark only. DO NOT FILL ABOVE THE “FULL” MARK.
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing this could damage the engine.
4. Install the dipstick.
5. Reset the AUTO/OFF/MANUAL switch to its origi-
nal position.
Figure 4.2 — Oil Dipstick and Fill, 15 kW
Oil Dipstick
4.1 FUSES
The generator panel’s 15 amp fuse (Figure 4.1) pro­tects the DC control circuit against overload. The fuse is wired in series with the battery output lead to the panel. If the fuse element has melted open, the engine cannot crank or start. Replace the fuse using only an identical 15-amp replacement.
The generator panel’s 7.5 amp fuse protects the 12 VDC accessory socket. If the fuse element has melted open, the 12 VDC socket will not provide power to any accessories. Replace the fuse using only an iden­tical 7.5 amp replacement. To remove fuse, push the fuse holder cap down and rotate counterclockwise.
Figure 4.1 – Generator Control Panel
MAN.
12 VDC
ACCESSORY
OUTLET 7.5A MAX
EXTERNAL
GFCI
CIRCUIT
BREAKER
SYSTEM SET
LOW OIL
HIGH TEMP.
OVER SPEED
OVER CRANK
FLA S HING GREEN LED =
N O U T IL IT Y S ENS E
4FLAS HIN G RED LEDS =
EX ERCIS ER NOT S ET
OUTLET FUSE
7.5A
SYSTEM FUSE
15A
AUTO
EXERCISE
TIME
OFF
SET
Oil Fill
4.3 CHANGING THE ENGINE OIL
4.3.1 ENGINE OIL RECOMMENDATIONS
Use oil of American Petroleum Institute (API) Service Class SG, SH or SJ. Use all season SAE 5W-30 Synthetic oil. Organic break-in oil is required before using synthetic oil.
NOTE:
The unit is supplied with “break-in” oil. See the “Break-in Procedure” Section for the first required oil change.
16
Page 19
Section 4 — Maintenance
15 kW Generator
4.5 CHANGING THE ENGINE
 Any attempt to crank or start the engine before
it has been properly serviced with the recom­mended oil may result in an engine failure.
4.3.2 OIL CHANGE PROCEDURE
To change the oil, proceed as follows:
1. Run the engine until it is thoroughly warmed up then shut OFF the engine.
2. Immediately after the engine shuts OFF, pull the oil drain hose (Figure 4.3) free of its retaining clip. Remove the cap from the hose and drain the oil into a suitable container.
3. After the oil has drained, replace the cap onto the end of the oil drain hose. Retain the hose in the clip.
4. Refill with the proper recommended oil (see “Engine Oil Recommendations”). See the “Specifications” Section for oil capacities.
Figure 4.3 – Oil Drain Hose and Filter
AIR CLEANER
4.5.1 15 KW GENERATORS
See Figure 4.4, for the location of the air cleaner. Use the following procedure:
1. Turn the two screws counterclockwise to loosen.
2. Remove the cover and air filter.
3. Wipe away dust or debris from inside of the air box and around edges.
4. Install the new air cleaner into the air box.
5. Install the cover. Turn the two cover screws clock­wise to tighten.
See the “Service Schedule,” Section for air cleaner maintenance. See the “Specifications” Section for air filter replacement part number.
Figure 4.4 — 15 kW Engine Air Cleaner
Screw
Cover
L
o
o
s
e
n
Oil Drain Hose
Oil Filter
4.4 CHANGING THE OIL FILTER
Change the engine oil filter as follows:
1. With the oil drained, remove the old oil filter by turning it counterclockwise.
2. Apply a light coating of clean engine oil to the gasket of the new filter. See the “Specifications” Section for recommended filter.
3. Screw the new filter on by hand until its gasket lightly contacts the oil filter adapter. Then, tighten the filter an additional 3/4 to one turn (Figure
4.4).
4. Refill with the proper recommended oil (see “Engine Oil Recommendations”). See the “Specifications” Section for oil capacities.
5. Start the engine and check for leaks.
Filter
4.6 SPARK PLUG(S)
Reset the spark plug(s) gap or replace the spark plug(s) as necessary. See the “Service Schedule” Section for maintenance requirements.
1. Clean the area around the base of the spark plug(s) to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and commercial solvent. Do not blast the spark plug(s) to clean.
2. Remove the spark plug(s) and check the con­dition. Replace the spark plug(s) if worn or if reuse is questionable. See the “Service Schedule” Section for recommended inspection.
3. Check the spark plug gap using a wire feeler gauge. Adjust the gap to 0.50 mm (0.020 inch) for 15 kW by carefully bending the ground electrode (Figure 4.5).
17
Page 20
Section 4 — Maintenance
15 kW Generator
Figure 4.5 – Setting the Spark Plug Gap
SET PLUG GAP AT
0.050 mm/0.020 inch
4.7 BATTERY MAINTENANCE
The battery should be inspected per the “Service Schedule”. The following procedure should be fol­lowed for inspection:
1. Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary.
2. Check the battery fluid level of unsealed batteries and, if necessary, fill with DISTILLED WATER ONLY. DO NOT USE TAP WATER IN BATTER­IES.
3. Have the state of charge and condition checked. This should be done with an automotive-type bat­tery hydrometer.
DANGER
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock and
high short circuit current. The following precau­tions are to be observed when working on bat­teries:
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the
battery; and
• Disconnect charging source prior to connecting or
disconnecting battery terminals;
• Remove the 7.5A and 15A fuses from the generator
control panel.
Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically conductive and corrosive. The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off immediately with water;
• Where electrolyte contacts the eyes, immediately flush thoroughly with water and seek medical attention; and
• Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) or water. The bicar­bonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.
Lead-acid batteries present a risk of fire because
they generate hydrogen gas. The following procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touch­ing the battery by first touching a grounded metal surface.
Be sure the AUTO/OFF/MANUAL switch is set to
the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.
Be sure the UTILITY power supply is turned
OFF, and the 7.5A and 15A fuses are removed from the generator control panel, or sparking may occur at the battery posts as the cables are attached, causing an explosion.
4.8 ADJUSTING VALVE CLEARANCE
After the first six (6) months of operation, adjust the valve clearance in the engine.
Important: If feeling uncomfortable about doing
this procedure or the proper tools are not available, please contact the dealer for service assistance. This is a very important step to insure longest life for the engine.
To adjust valve clearance:
• Make sure the engine is at room temperature.
• Make sure that the spark plug wire is removed
from the spark plug and out of the way.
• Remove the four screws attaching the valve cover
with a #2 or #3 phillips screwdriver.
18
Page 21
Section 4 — Maintenance
15 kW Generator
• Make sure the piston is at Top Dead Center (TDC) of its compression stroke (both valves closed). To get the piston at TDC, remove the intake screen at the front of the engine to gain access to the flywheel nut. Use a large socket and socket wrench to rotate the nut and hence the engine. While watching the piston through the spark plug hole. The piston should move up and down. The piston is at TDC when it is up as high as it can go.
• Loosen the rocker jam nut. Use an 10mm allen wrench to turn the pivot ball stud while checking clearance between the rocker arm and the valve stem with a feeler gauge. Correct clearance is
0.002-0.004 inch (0.05-0.1 mm). See Figure 4.6.
NOTE:
Hold the rocker arm jam nut in place as the pivot ball stud is turned.
When valve clearance is correct, hold the pivot ball stud in place with the allen wrench and tighten the rocker arm jam nut. Tighten the jam nut to 174 in/lbs. torque. After tightening the jam nut, recheck valve clearance to make sure it did not change.
Figure 4.6 - Valve Clearance Adjustment
4.9 COOLING SYSTEM
Air inlet and outlet openings in the generator com­partment must be open and unobstructed for con­tinued proper operation. This includes such obstruc­tions as high grass, weeds, brush, leaves and snow.
Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to quickly shut down. (See Figure 4.7 for vent loca­tions.)
The exhaust from this product gets extremely
hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.
Figure 4.7 – Cooling Vent Locations
Pivot Ball
Jam Nut
• Install new valve cover gasket.
• Re-attach the valve cover.
Start all four screws before tightening or it will not be possible to get them in place. Make sure the valve cover gasket is in place.
• Re-attach the spark plug wire to the spark plug.
• Repeat the process for the other cylinder.
Stud
NOTE:
Rocker
Arm
Valve Stem
The maximum ambient temperature for the
generator is 48.9° C (104° F).
4.10 ATTENTION AFTER SUBMERSION
If the generator has been submerged in water, it MUST NOT be started and operated. Following any submer-
sion in water, have a dealer thoroughly clean and dry the generator.
4.11 CORROSION PROTECTION
Periodically wash and wax the enclosure using auto­motive type products. Frequent washing is recom­mended in salt water/coastal areas. Spray engine linkages with a light oil such as WD-40.
4.11.1 ADDITIONAL CORROSION
PROTECTION
Periodically spray all engine linkage parts and brack­ets with corrosion inhibiting spray such as WD-40 or a comparable product.
19
Page 22
Section 4 — Maintenance
15 kW Generator
4.12 OUT OF SERVICE PROCEDURE
4.12.1 REMOVAL FROM SERVICE
If the generator cannot be exercised every seven days, and will be out of service longer than 90 days, pre­pare the generator for storage as follows:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line
and allow the unit to shut down.
3. Once the unit has shut down, it will signal a low
oil fault.
4. Set the generator’s main circuit breaker to its
OFF (or open) position.
5. Set the Auto/Off/Manual switch to OFF and
turn off the utility power to the transfer switch. Remove the 7.5A and 15A fuses from the genera­tor control panel. Disconnect the battery cables as outlined in “General Hazards” (page 2). Turn on the utility power supply to the transfer switch in order to power the emergency load centers cir­cuits while utility power is available.
6. While the engine is still warm from running,
drain the oil completely. Refill the crankcase with oil. See ”Engine Oil Recommendations,” Section.
7. Attach a tag to the engine indicating the viscosity
and classification of the oil in the crankcase.
8. Remove the spark plug(s) and spray fogging
agent into the spark plug(s) threaded openings. Reinstall and tighten the spark plug(s).
9. Remove the battery and store it in a cool, dry
room on a wooden board. Never store the battery on any concrete or earthen floor.
10. Clean and wipe the entire generator.
4.12.2 RETURN TO SERVICE
To return the unit to service after storage, proceed as follows:
1. Verify that utility power is turned off and that the Auto/Off/Manual switch is set to OFF.
2. Check the tag on the engine for oil viscosity and classification. Verify that the correct recom­mended oil is used in the engine (see “Engine Oil Recommendations”). If necessary, drain and refill with the proper oil.
3. Check the state of the battery. Fill all cells of unsealed batteries to the proper level with dis­tilled water. DO NOT USE TAP WATER IN THE BATTERY. Recharge the battery to 100 percent state of charge, or, if defective, replace the bat­tery. See the “Specifications” Section, for type and size.
4. Clean and wipe the entire generator.
5. Remove the 7.5A and 15A fuses from the genera­tor control panel. Reconnect the battery. Observe battery polarity. Damage may occur if the battery is connected incorrectly.
6. Open the fuel shutoff valve.
7. Insert the 7.5A and 15A fuses into the generator control panel. Start the unit by moving the Auto/ Off/Manual switch to MANUAL. Allow the unit to warm up thoroughly.
8. Stop the unit by setting the Auto/Off/Manual switch to OFF.
9. Turn on the utility power to the transfer switch.
10. Set the Auto/Off/Manual switch to AUTO.
11. The generator is now ready for service.
NOTE:
If the battery was dead or disconnected, the exer­cise timer must be reset.
20
Page 23
Section 4 — Maintenance
15 kW Generator
4.13 SERVICE SCHEDULE
ATTENTION: It is recommended that all service work
be performed by the nearest dealer.
SYSTEM/COMPONENT PROCEDURE FREQUENCY
X = Action Inspect Change Clean W = Weekly R = Replace as Necessary M = Monthly * = Notify Dealer Y = Yearly
if Repair is Needed.
FUEL
Fuel lines and connections* X M
LUBRICATION
Oil level X M
Oil X AFTER BREAK-IN,
AND Y
Oil filter X AFTER BREAK-IN,
AND Y
COOLING
Enclosure louvers X X W
BATTERY
Remove corrosion, X X M
ensure dryness
Clean and tighten
battery terminals
Check charge state
Electrolyte level X R EVERY 6 M (unsealed batteries only)*
ENGINE AND MOUNTING
Air cleaner X R Y
Spark plug(s) X R Y
GENERAL CONDITION
Vibration, Noise, Leakage, X M Temperature*
COMPLETE TUNE-UP* TO BE COMPLETED BY A DEALER
X X M
X R EVERY 6 M
21
Page 24
Section 5 — Troubleshooting
15 kW Generator
5.1 TROUBLESHOOTING GUIDE
Problem Cause Correction
The engine will not crank. 1. Fuse blown 1. Replace 15A fuse on generator con-
trol panel.
2. Loose, corroded or defective 2. Tighten, clean or replace battery cables as necessary.
3. Defective starter contactor (7 kW) 3. *
4. Defective starter motor 4. *
5. Dead Battery 5. Charge or replace battery.
The engine cranks but 1. Out of fuel 1. Replenish fuel. will not start. 2. Defective fuel solenoid (FS) 2. *
3. Open #14 wire from 3. * engine control board
4. Defective spark plug(s) 4. Clean, re-gap or replace plug(s).
5. Valve lash out of adjustment. 5. Reset valve lash.
The engine starts hard 1. Air cleaner 1. Check, replace air cleaner. and runs rough. plugged or damaged
2. Defective spark plug(s) 2. Clean, re-gap or replace plug(s).
3. Fuel regulator not set. 3. Set fuel regulator.
4. Fuel pressure incorrect. 4. Confirm fuel pressure is at (0.4-0.5 psi) for LP, and 5-7” water column (0.18-0.25 psi) for natural gas.
The AUTO/OFF/MANUAL switch 1. Defective switch 1. * is set to OFF, but the engine 2. AUTO/OFF/MANUAL switch 2. *
continues to run. wired incorrectly
3. Defective control board 3. *
There is no AC output from 1. Main line circuit breaker open 1. Reset circuit breaker the generator. to ON (or closed).
2. Generator internal failure 2. *
There is no transfer to 1. Defective transfer switch coil 1. * standby after utility 2. Defective transfer relay 2. * source failure. 3. Transfer relay circuit open 3. *
4. Defective control logic board 4. *
Unit consumes large 1. Break-in procedure 1. * amounts of oil. not followed
22
*Contact the nearest dealer for assistance.
Page 25
S
G
S
W
O
)
O
O
OO
G
O
S
CO
S
[
] OU
G
UG
U
S
SSU
O
Q
S
O
S
[
]
[
]
G U
U
[
36.0"
]
U
O OU
U
[
8 [
]
[
]
]
9
] ]
3 9
[
]
] [
]
[
]
[
]
[
CC
SS
O
S
)
PEN AREA
M
14mm
INIM
NIT
ND
LL AR
Section 6 — Mounting Dimensions
15 kW Generator
Drawing No. 0D3739-B
.
LE
46.2"
172.3
UIRED
F 11-14"
RE
EL INLET
PRE
ATER COLUMN RE
4" NPT F
A
H
E
ABLE A
L
NDIN
R
REMOVE PLUG FOR ACCESS
10.2"
INCHES
IN: N
I
ILLIMETERS
*ALL DIMEN
IDE VIE
14
5.9"
HT I
90.7
.19"
0.2mm
F"
47"
193
RNER
4-
T LIFT BY THE R
LE
H
N
IFTIN
D
4
27.7"
8.14"
07
48.5"
232
NT VIEW
R
M
3.00" M
RAVEL
IN
EA
6.2mm
12"
IF SUPPLIED
4
2
23.5"
04
24.5"
IDE VIEW
22
EFT
2
16
23
Page 26
)
CK
CUSTO
D
0
SP2
SP1
OP
0
O
86
85
D
Y
C
R
N
CH
Y
Y
SC
Y
1
2
SSU
CH
S
CH
S
CH
OCK
S
G
D
CH
OR
SC
OR
S
D
P
P
S
OR
E
SCR
o
1 - 20 Vac Sense Transformer
D
E
n
S
ON
56
SM
SC
C
C
C
6
3
85
86
C1
86
3
0
3
6
8
86
J1
SW
CO
OL
5
5
0
66A
5A
39
3
56
8
351
56
018
5
5
6
3
0
8
56
351
5
3
G
0
S
3
0
0
C
R
0
3
5B
0
3
0
5B
0
6
6
85
86
85
8
85
6
L
3
+
Section 7 — Electrical Data
15 kW Generator Wiring Diagram – Drawing No. 0E9016
ENGINE WIRIN
DIAGRAM KE
BA - BRUSH ASSEMBL
BCR - BATTERY CHARGE RELA
B1 - MAIN OUTPUT BREAKE
CB2 - CIRCUIT BREAKER, ALTERNATOR EXCITATIO
CB3 - CIRCUIT BREAKER, EXTERNAL OUTLET, PUSH/PUL D - DIOD DSW - PCB MOUNTED DIP SWIT
FS - FUEL SOLENOI
F1 - FUSE 15 AM
F2 - FUSE 7.5 AM
RD - CONTROL PANEL GROUN
HTO - HIGH OIL TEMPERATURE SWIT IC - INLINE CONNECT ICT - INTERCONNECTION TERMINAL
IM1 - IGNITION MODULE, CYLINDER #
IM2 - IGNITION MODULE, CYLINDER #
LOP - LOW OIL PRE
- STARTER CONTACT
R - STARTER CONTACTOR RELA
SP1, SP2 - SPARK PLUG
W1 - AUTO / OFF / MANUAL SWIT
W2 - SET EXERCISE SWIT
M - STARTER MOT
TB - INSULATED TERMINAL BL
TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.
RE SWIT
HARGE
1
F
1
22
1
22
I
1
1
I
I
1
1
1
1
1
1
1
1
24
HT
L
BLA
MER SUPPLIE
8
1
1
2
NTR
PRINTED CIRCUIT BOAR
2
1
1
22
1
1
L.E.D - ALARM INDICATOR
2 - Remote Not Aut
3 - 50 Hz Operatio
4 - SPAR
D
Page 27
GRD
94
5
5
225
5B
5
0
0
3
CLOSES
G
OUTPU
R
L
SSO
SOCKET
5B
0
5A
66A
39
5
0
5
5
5
3
13
5VO
GE
OR
5A
3
5
351
3
3
5
3
0
351
0
66A
6206
62
0
6
SW2
39
O
SW1
b
a
0
0
CO
ON
CUSTOMER
S
OR
OR
CB1
3
351
94
0
66A
55
55
0
C2
3
CO
OX
5B
3
66
5
5A
6
9
CR
3
0
66
5A
0
CB2
62
66
6
5
6
9
8
0
6
0
CO
C
ON
C
T
94
CO
L
S
R
3
66
66A
55
S
OR
94
3
0
5A
39
000
0
0
0
0
000
0
0
94
3
66A
0
33
33
CB3
OU
T
G
3
OT
OT G
D
GFCI
G
Section 7 — Electrical Data
15 kW Generator
Wiring Diagram – Drawing No. 0E9016
22
22
22
NTROL PANEL B
T TO BEARIN
B
1
22
22
1
1
22
14
1
LTA
REGULAT
1
1
1
1
TAT
1
1
2
1
2
2
1
2
1
1
22
1
1
1
1
1
1
1
2
1
1
1
1
2
1
1
AUT
MANUA
1
2
2
1
TLE
H
LOA
H
240VA
RELAY
12Vdc TRAN
I
FE
UTILITY INPU
240V GENERAT
T TO TRANSFE
WITCH CONTACT
NEUTRAL
NNE
TI
NNECTI
12VDC ACCE
RY
25
Page 28
C
R
)
0
Y
Y
SC
Y
SC
OR
CH
D
T
SSU
CH
2
1
S
CH
S
OR
S
CH
S
N
Y
P
E
P
62
GE
OR
C
6
0
(
)
C2-8
C2-7
C
1
C
0
CB2
0
6
0
3
0
C2-1
3
C1-3
6
C2-3
T
0
C1-6
C2-9
0
0
55
C2-4
0
G
UN
(
)
66
CO
OL
D
3
J2
3
0
9
5
J1
5
66A
66A
85
351
O
C1-4
C2-2
0
0
SW2
5
5
0
66A
94
3194
56
5A
66A239
8
86
3
86
0
OP225
39
5A
3
94
3
5B
G
3
6663
5A
9
CR
0
3
3
3
0
225A
5
0
5A
L
Section 7 — Electrical Data
15 kW Generator Electrical Schematic – Drawing No. 0E9017
22
ELECTRONI
VOLTA
REGULAT
HARGE
1
2-1
2-1
1
STATOR
DIAGRAM KE
BA - BRUSH ASSEMBL BCR - BATTERY CHARGE RELA CB1 - CIRCUIT BREAKER, MAIN OUTPU
CB2 - CIRCUIT BREAKER, ALT. EXCITATIO
CB3 - CIRCUIT BREAKER, EXTERNAL OUTLET, PUSH/PUL D - DIOD
FS - FUEL SOLENOI
F1 - FUSE 15 AM
F2 - FUSE 7.5 AM
HTO - HIGH OIL TEMPERATURE SWIT
IM1 - IGNITION MODULE, CYLINDER #
IM2 - IGNITION MODULE, CYLINDER #
LOP - LOW OIL PRE
- STARTER CONTACT
R - STARTER CONTACTOR RELA
SP1, SP2 - SPARK PLUG
W1 - AUTO / OFF / MANUAL SWIT
W2 - SET EXERCISE SWIT
M - STARTER MOT
TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.
RE SWIT
1
BATTERY CHARGE
WINDIN
22
1
ENGINE R
WINDIN STATOR
HT
NTR
PRINTED CIRCUI
BOAR
B
2
1
1
1
L
2
1
1
1
1
22
22
1
1
1
2
1
2
1
26
Page 29
SM
C1-1
5
0
8
C1-5
5618
5
5A
SCR
0
0
0
5
6
39
5
0
94
3
3
8
SP2
SP1
23
6
0
3
SC
0
SW1
5
5A
39
94
S
0
C2-1
G
(
)
R
CB1
33
56VA
3
5
5A
C2-5
C2-6
94
3
CUSTOMER
SU
D
CK
SC
0V
0V120V
CUSTOMER
CO
S
COIL
dc
U
Y
UT
C
R
SSO
SOCKET
+
0
5
3
94
GFCI
OU
T
GGG
CB3
0
5
515
3
5
5B
5B
0
39
Section 7 — Electrical Data
15 kW Generator
Electrical Schematic – Drawing No. 0E9017
24
240VA
TILIT
INP
12V
TRANSFE
NNECTION
12
22
22
12VDC ACCE
1
1
2
1
1
2
1
1
RY
1
1
1
1
1
POWE
WINDIN
1
1
1
2
1
2
2
STATOR
2
1
1
1
1
1
1
1
1
1
1
F
BLA
PPLIE
TLE
27
Page 30
35
68
49
52
Y
0
9
3
37
33
5
35
34
6
9
35
9
82
80
51
6
8
80
2
87
5
86
8
39
92
89491
6315
69
0
52
9
35
51
9
6
7
0
214
5
9
9
8
1
Section 8 — Exploded Views and Parts Lists
15 kW Generator Enclosure – Drawing No. 0F0080-C
PRE PACKAGED UNITS ONL
4
4
7
7
4
4
2
4
2
1
4
2
4
4
7
2
4
4
1
2
2
28
1
Page 31
Section 8 — Exploded Views and Parts Lists
15 kW Generator
Enclosure – Drawing No. 0F0080-C
ITEM PART NO. QTY. DESCRIPTION
1 0C6140 1 ASSEMBLY, ENCLOSURE BASE
0D1901 1 ASSEMBLY, ENCLOSURE BASE (7KW)
2 0C6735 2 SUPPORT, ROOF FOLDING
3 0F0063 1 ENCLOSURE, FRONT
4 0C7062 1 ENCLOSURE, EXHAUST SIDE
0C7062A 1 ENCLOSURE, EXHAUST SIDE (7KW)
5 0E8811 1 ENCLOSURE, SIDE & BACK
0E8811A 1 ENCLOSURE, SIDE & BACK (7KW)
6 0E9873 1 ENCLOSURE, ROOF
7 0C7065 1 PANEL, ALTERNATOR DIVIDER
0C7065A 1 PANEL, ALTERNATOR DIVIDER (7KW)
8 0C8101A 1 PANEL, MUFFLER BOX SIDE
0C8861 1 PANEL, MUFFLER BOX SIDE (7KW)
9 0C8101B 1 COVER, MUFFLER BOX
0C8862 1 COVER, MUFFLER BOX (7KW)
10 0C8283 1 GASKET, DOOR SEAL
11 0C8284A 1 FOAM, BACK ENCLOSURE
12 0C8
13 0C8284C 1 FOAM, FRONT ENCLOSURE
14 0C8285 1 BRACKET, BATTERY SUPPORT
15 0C8899A 1 PAD, 24"X48" WITH MOUNTING HOLES
16 0D1128 1 PANEL, ENGINE DIVIDER
0D1128A 1 PANEL, ENGINE DIVIDER (7KW)
17 0E4244 1 BAFFLE, INTAKE
0D1605A 1 BAFFLE, INTAKE (7KW)
18 0D1606 1 HOUSING, FAN
0D5264 1 BAFFLE, EXHAUST (7KW)
19 0D1839 2 BRACKET, TOP SUPPORT
20 0D1840 2 BRACKET, BOTTOM SUPPORT
21 0D2425 1 DUCT, BASE AIR
22 0D2588 1 GASKET, FRONT DIVIDER
0D2588A 1 GASKET, FRONT DIVIDER (7KW)
23 0D2676 1 COVER, FRONT EXHAUST ENCLOSURE
24 0D2677 1 COVER, BACK EXHAUST ENCLOSURE
25 0D2979B 2 CLOTH, HARDWARE 266.7mm x 146mm
0D2979B 3 CLOTH, HARDWARE 266.7mm x 146mm (7KW)
26 0D2979C 1 CLOTH, HARDWARE 543mm x 146mm
27 0D297
0D2979E 1 CLOTH, HARDWARE (7KW)
28 0E4245 1 FOAM, FRONT INTAKE BAFFLE
0D3058A 1 FOAM, FRONT INTAKE BAFFLE (7KW)
29 0E4245A 1 FOAM, TOP INTAKE BAFFLE
30 0E4245B 1 FOAM, BACK INTAKE BAFFLE
0D3058C 1 FOAM, BACK INTAKE BAFFLE (7KW)
31 0D3057D 1 FOAM, BACK ENCL. STRIP
32 0D3059A 1 FOAM, EXHAUST SIDE ENCLOSURE END
33 0D3059B 1 FOAM, EXHAUST SIDE ENCLOSURE FRONT
34 0D3059C 1 FOAM, EXHAUST FAN HOUSING
35 0D7176 24 WASHER, SELF LOCKING
22 WASHER, SELF LOCKING (7KW)
36 0D3059D 1 FOAM, FRONT EXHAUST ENCLSURE COVER
37 0D3059
38 0C7781A 2 DOOR, PAWL
39 0D3037 1 LATCH, QUARTER TURN LOCKING
40 0F0164 1 HINGE TYPE A WITH STUDS, PIN
41 0F0165 1 HINGE TYPE B WITH STUDS, PIN
42 0D3037A 1 LATCH, QUARTER TURN NON-LOCKING
43 0A2115 4 WASHER NYLON .250"
44 022097 1 WASHER LOCK M6-1/4"
46 0F0710 18 RIVET POP 0.125 X 0.337
284B 1 FOAM, ROOF ENCLOSURE
9D 1 CLOTH, HARDWARE 266.7mm x 387.4mm
E 1 FOAM, BACK EXHAUST ENCLOSURE COVER
ITEM PART NO. QTY. DESCRIPTION
47 047411 6 SCREW HHC M6-1.0 X 16 G8.8
047411 4 SCREW HHC M6-1.0 X 16 G8.8 (7KW)
48 043116 5 SCREW HHC M6-1.0 X 12 G8.8
043116 6 SCREW HHC M6-1.0 X 12 G8.8 (7KW)
49 0D3700 26 NUT, LOCKING FLANGE M6-1.0
0D3700 24 NUT, LOCKING FLANGE M6-1.0 (7KW)
50 0D4662 11 SCREW HHTT M8-1.2 X 20 BP
51 090388 36 SCREW TAPTITE M6-1.0 X 12 BP
24 SCREW TAPTITE M6-1.0 X 12 BP (7KW)
52 092120 2 NUT LOCK TRIC M6 X 1.0 Y/ZNC
54 0D3167 1 GASKET, BATTERY SUPPORT BRACKET
55 0A3328 1 PLUG, PLASTIC 0.593
56 055414 1 LUG SLDLSS #2-#8X17/64 CU
57 092079 1 SCREW TAPTITE M6-1.0X25 BP
58 0A1658 2 L/WASH SPECIAL ¼
59 0C2
60 086729 1 CONTACTOR, STARTER (7KW)
61 0388040AJ0 1 CABLE, #6 RED BATTERY 38.5"
62 022127 2 NUT HEX 1/4-20 STEEL (7KW)
63 022129 6 WASHER LOCK 5/16
022129 7 WASHER LOCK 5/16 (7KW)
64 074908 8 SCREW TAPTITE M5-0.8 X 10 BP
65 0D2346 1 HARNESS, ENGINE
0D2345 1 HARNESS, ENGINE (7KW)
66 023484F 1 BUSHING, SNAP SB-1000-12
67 022142 1 SCREW HHC 5/16-18 X 3/4 G5 (7KW)
68 0A7836 2 RIVET,1/8" X 0.126" - 0.375" LSH POP
69 0A8475 2 L/WASH SPECIAL #10
70 0912970069 1 ASSEMBLY, ROOF / DOOR GROUND WIRE
71 09129
72 055450 2 PLUG PLASTIC 1.375
73 0E5968 11 GASKET, EXTRUDED TRIM
74 0D3701 1 PLATE, "HOT"
75 0D3472 1 GROMMET 2.75 X 1/16
76 0C8742 1 EXTERNAL CONNECTION BOX
77 0C8911 1 POWER BLOCK
78 0D8442 1 HARNESS GENERATOR TO EXT CONN BOX
0D8652 1 HARNESS GENERATOR TO EXT
79 036937 2 SCREW PPHM #10-32 X 1
80 022152 5 WASHER LOCK #10
81 051713 2 WASHER FLAT M5
82 022158 5 NUT HEX #10-32 STEEL
83 0D3031 1 FUEL LINE, 3/4"OUTDOOR (NOT SHOWN)
84 026850 1 WASHER SHAKPROOF EXT 1/4 STEEL
85 04981
86 0F0164A 1 HINGE TYPE A WITH STUDS, SOCKET
87 0F0165A 1 HINGE TYPE B WITH STUDS, SOCKET
89 0E2874 1 SCREW HHTR 1/4-20 X 3/4
90 043107 4 SCREW HHC M8-1.25 X 25
91 022145 10 WASHER FLAT 5/16
92 045771 4 NUT HEX M8-1.25
93 0C3906 2 SELF-ALIGN SCREW M6 HH
94 0E4321 1 PANEL, EXHAUST ALIGNMENT
95 0E1330A 1 GROMMET, 38.1 CROSS SLIT WITH HOLE
96 0E9692 1 BRACKET, REGULATOR MOUNTING
97 042907 2 SCREW HHC M8-1.25 X 16mm
98 0F5241 1 PLATE, COVER
99 0F594
937 1 BRACKET, BATTERY HOLD DOWN (7KW)
70070 2 ASSEMBLY, ROOF / DOOR GROUND WIRE
CONNECTION BOX (7KW)
3 1 NUT HEX M6-1.0 G8 YELLOW CHROME
3 1 GASKET, COVER
29
Page 32
Section 8 — Exploded Views and Parts Lists
15 kW Generator Control Panel – Drawing No. 0E9162-J
30
Page 33
Section 8 — Exploded Views and Parts Lists
15 kW Generator
Control Panel – Drawing No. 0E9162-J
ITEM PART NO. QTY. DESCRIPTION
1 0E7886A 1 CIRCUIT BREAKER 30A X 2P 240V (7KW) 0E7886E 1 CIRCUIT BREAKER 50A X 2P 240V (12KW) 0E7886J 1 CIRCUIT BREAKER 65A X 2P 240V
(13/15KW) 2 0A1801 1 ASSEMBLY, BATTERY CHARGER ENGINE 3 083049 1 ASSEMBLY, POTTED REGULATOR 4 0C2174 1 RELAY, 12V 25A SPST 5 075210A 1 BLOCK 1 POSITION 6 0D3062 4 HEX STAND-OFF #6-32 x 3/8" 7 0D8615 1 ASSEMBLY, HOME STANDBY CONTROLLER 0D8615A 1 ASSEMBLY, HOME STANDBY CONTROLLER
(7KW) 8 032300 2 HOLDER, FUSE 9 022676 1 FUSE, 15AMP X AGC15 10 0E4494 1 SWITCH, ROCKER DPDT ON-OFF-ON 11 0E7890 1 CIRCUIT BREAKER MOUNTING BRACKET 12 023484E 1 SNAP BUSHING 13 075476 4 SCREW PPHM M4-0.7 x 16mm 15 0E6480 6 NUT HEX LOCK M4-0.7 NYLON IN 17 0C1085 6 SCREW PPHM M3-0.5 x 8mm 0C1085 4 SCREW PPHM M3-0.5 x 8mm (7KW) 19 054502 1 CIRCUIT BREAKER 3 X 1 ETA 46-500-P 053623 1 CIRCUIT BREAKER 2.5 X 1 ETA 46-500-P
(7KW) 20 0E7870 1 CONTROL, PANEL BOTTOM 0E7871 1 CONTROL, PANEL BOTTOM (7KW) 21 075235 4 SCREW HHC M5-0.8 x 30mm 22 0D5240 1 SWITCH, SPST (ON)-ON N/O 23 0D9784 6 NUT HEX LOCK M3-0.5 NYLON INSERT 0D9784 4 NUT HEX LOCK M3-0.5 NYLON INSERT
(7KW) 24 0D8502 1 NEUTRAL CONNECTOR 26 0E8956 1 HARNESS, CONTROL PANEL (NOT SHOWN) 0E8957 1 HARNESS, CONTROL PANEL WIRE (NOT
SHOWN) (7KW) 27 074908 4 SCREW TAPTITE, M5-0.8 x 10 BP 28 049226 6 WASHER LOCK M5
SERT
ITEM PART NO. QTY. DESCRIPTION
29 082025 6 NUT HEX LOCK M5-0.8 NYLON INSERT 30 0C3910 1 TRANSFORMER 31 022507 2 SCREW HHC 1/4"-20 x 1/2" 32 0A9611 1 FUSE 7.55A X AGC5 33 046689 1 BLOCK TERMINAL STRIP 20A 4 X 6 X 1100V 34 063617 1 RELAY PANEL 12VDC DPDT 10A 240VAC 35 075475 2 SCREW PPHM M4-0.7 x 10mm 36 043180 2 WASHER FLAT M4 37 0E8812 1 COVER, CONTROL PANEL COMPONENT 0E8895 1 COVER, CONTROL PANEL COMPONENT
(7KW) 38 092036 8 SCREW PPHMS/LW #6-32 x 1/4" 39 045770 2 SCREW HHC M5-0.8 x10mm 40 0E7866 1 COVER, CONTROL PANEL 0E7867 1 COVER, CONTROL PANEL (7KW) 41 0D3700 8 NUT FLANGE M6-1.0 NYLOK 42 0912970069 1 ASSEMBLY, ROOF/DOOR GROUND WIRE 43 0E2874 1 SCREW HHTR 1/4"-20 X 3/4" 44 0A1658 2 WASHER LOCK SPECIAL 1/4" 45 022473 3 WASHER FLAT 1/4"-M6 46 038750 1 SCREW HHC M6-1.0 x 30mm 47 022097 3 WASHER LOCK M6-1/4" 48 049813 1 NUT HEX M6-1.0 49 031879 6 WASHER FLAT #4 031879 4 WASHER FLAT #4 (7KW) 50 023897 2 WASHER FLAT #10 51 0E9056 1 SOCKET, 12VDC ACCESSORY 52 0E5840 1 CIRCUIT BREAKER 15A PUSH / PULL MAIN
RESET 53 036903 6 SCREW PPHM #6-32 X 5/ 54 0E7833 1 PLATE, WEATHERPROOF GFCI 55 0E4261 1 OUTLET, 15A GFCI DUPLEX 56 022985 4 WASHER FLAT #6 57 082625 4 NUT LOCK HEX #6-32 NYL INSERT 58 0E9171 1 GASKET, WEATHERPROOF GFCI 59 0F4793 2 SCREW PPHM M3-0.5 x 10mm
8"
31
Page 34
Section 8 — Exploded Views and Parts Lists
15 kW Generator GT-990 Engine – Drawing No. 0F4715-B Part 1
9
4
5
143
6
7
2
2, 5, 19, 20, 39, 40, 47, 64, 93, 140
66
34
8, 11, 12, 13
67
16A, 16B, 17, 18
4, 5, 6
68
69
36
37
35
7, 47, 48, 49, 50, 51, 52, 53, 54, 56, 57, 58, 59, 60, 63, 64
70
143
47, 48, 49, 50, 51, 52, 53, 54, 56, 57, 58, 59, 60, 62, 63, 64
71
140
39
27, 28, 29
72
22
34
3, 32, 33, 34, 35, 36, 40, 72
73
33
32
10
1
11
12
8
65
13
14
20
64
62
63
61
60
59
21
15
16A
19
17
18
16B
16A
57
58
25
30
56
54
23
144
24
53
52
55
27
26
47
49
48
3
3
31
51
50
28
29
43
44
46
45
32
38
40
41
42
Page 35
Section 8 — Exploded Views and Parts Lists
15 kW Generator
GT-990 Engine – Drawing No. 0F4715-B Part 1
ITEM PART NO. QTY. DESCRIPTION
1 0C5729 1 ASSEMBLY, CRANKCASE HOUSING WITH
SLEEVE
2 0E9843 1 SEAL, 38 I.D. CRANKSHAFT 3 090388 3 SCREW, TAPTITE M6-1.0 X 12 YC 4 0C5372 1 ASSEMBLY, BREATHER 5 0C3005 1 GASKET, BREATHER COVER 6 0E3372B 3 SEPARATOR, OIL BREATHER 7 0D8067A 1 ASSEMBLY, HEAD #1 G&S 8 071983 4 RETAINER, PISTON PIN 20 9 0C2981C 1 ROCKER, COVER NO OIL FILL 10 045761A 4 STUD M8-1.25/10MM X 30 G5 ZINC 11 0E2985 2 PISTON, HC 12 021533 2 SET, PISTON RING 90MM 13 0E1466 2 PIN PISTON 14 0D4041 1 ASSEMBLY, CAMSHAFT & GEAR 15 0C2 16A 0C2985A 2 ROLLER BEARING, GOVERNOR PLATE 16B 0C2985B 1 ROLLER BEARING, GOVERNOR 17 0D4042 1 ASSEMBLY,GOVERNOR GEAR 18 0A7811 1 SPOOL, GOVERNOR MACHINED 19 0C2977 1 GASKET, CRANK CASE 20 0C5943 1 SEAL, OIL PASSAGE 21 0E4357E 1 ASSEMBLY, CRANKSHAFT HORIZONTAL
22 0E3223 2 ASSEMBLY, CONNECTING ROD 23 0D2157 2 SCREW SHC M6-1.0 X 50 G8.8 24 0E6098 1 SCREEN, OIL PICKUP 25 0D4123A 1 ASSEMBLY, OIL PUMP 26 078699E 2 SLEEVE, SEAMED DOWEL 10 DIA. 27 0C3011 2 COVER, OIL RELIEF 28 0C3009 2 SPRING, OIL RELIEF 29 0C3010 2 BALL, 1/2D OIL RELIEF 30 093873 2 WASHER, LOCK RIB M6 31 0C5315 1 GEROTOR, OUTER 32 0C5998 1 CLAMP, OIL TUBE 33 0D1667 1 ARM, GOVERNOR 34 0C2991 2 E-RING, GOVERNOR ARM 35 0C2988 1 THRUST WASHER, GOVERNOR 36 0C2992 1 BUSHING, GOVERNOR LOWER
983 1 SHAFT, GOVERNOR
DIRECT DRIVE
ITEM PART NO. QTY. DESCRIPTION
37 0C3971C 1 ASSEMBLY, DIPSTICK WITH HANDLE 38 0C5305 1 TUBE, DIPSTICK 39 0C3027 1 O-RING, OIL CLR 3/8 X 1/2 40 0E9842 1 SEAL, 42 I.D. CRANKSHAFT 41 0C5731 1 ASSEMBLY, HOUSING COVER WITH
SLEEVE 42 0C3006 9 SCREW, HHFC M10-1.5 X 55 43 080318 8 SCREW HHFC M6-1.0 X 25 44 093064 1 ASSEMBLY, OIL FILL CAP 45 0C8808 2 HOOK, LIFTING 46 0D2723B 1 ROCKER, COVER WITH OIL FILL 47 0C2979 2 GASKET, VALVE COVER 48 086515 8 KEEPER, VALVE SPRING 49 0D2274 4 RETAINER, VALVE SPRING 50 0D3867 4 SPRING, VALVE 51 078672 2 SEAL, VALVE STEM D7 52 0C5371 4 WASHER, VALVE SPRING 53 072694 4 STUD, ROCKER ARM PIVOT 54 0D3998 4 NUT HEX M8-1.0 G8 YEL CHR 55 0C3027 2 O-RING, 3/8" X 1/2" 56 0D5313 4 ROCKER ARM 57 0D6024 2 PLATE, PUSH ROD GUIDE 58 0C2976 12 SCREW HHFC M8-1.25 X 65 59 086516 2 VALVE, EXHAUST 60 0C2229 2 VALVE, INTAKE 61 083897 4 TAPPET, SOLID 62 0D8067B 1 ASSEMBLY, HEAD #2 G&S 63 0D9853D 4 PUSHROD, 147 64 0C2978 2 GASKET, HEAD 65 043790 1 BARBED ELBOW 90 3/8NPT X 3/8 66 0D4010 1 KIT GASKET 67 0D4011 1 KIT PISTON & RINGS 68 0D4012 1 KIT BREATHER ASSEMBLY 69 0D4013 1 KIT GOVERNOR ASSEMBLY 70 0D8675A 1 KIT HEAD ASSEMBLY CYLINDER 1 71 0D8675B 1 KIT HEAD ASSEMBLY CYLINDER 2 72 0D4015 1 KIT OIL RELIEF 73 0D4016 1 KIT GEAR COVER
33
Page 36
Section 8 — Exploded Views and Parts Lists
15 kW Generator GT-990 Engine – Drawing No. 0F4715-B Part 2
82
83
81
79
80
74
117
143
76
77
96
75
95
78
130
114
122
119
118
97
121
98
124
99
100
124
125
123, 145
125
143
120
137
126
13
136
1
138
127
132
115
133
116
139
135
134
142
128
129
34
84
86
88
85
89
90
93
89
94
91
97
98
92
99
112
101
102
107
108
103
104
109
105
110
106
112
112
113
111
Page 37
Section 8 — Exploded Views and Parts Lists
15 kW Generator
GT-990 Engine – Drawing No. 0F4715-B Part 2
ITEM PART NO. QTY. DESCRIPTION
74 0C5136A 2 KNOB, AIR CLEANER 75 0C3024 1 COVER, AIRBOX NG/LP 76 0C3040 1 PRE-CLEANER, 77 0C8127 1 ELEMENT, AIR CLEANER 78 0D8564A 1 ASSEMBLY, MIXER/AIRBOX 990 0D8564B 1 ASSEMBLY, MIXER/AIRBOX 760 79 0D2595 4 SCREW SHOULDER (8MM) M6-1.0 X 18 80 0D4417 4 WASHER,RUBBER 1/4" X 1/8" THICK 81 0C3025 1 SWITCH, OIL PRESS 82 0D3083 1 ASSEMBLY, OIL DRAIN HOSE 83 0C7292 1 NIPPLE, 3/4"-16 UNF 84 070185D 1 OIL FILTER 85 075281 1 SWITCH, THERMAL 284F 86 0F2094 2 SCREW, M3-0.5 X 6 SEMS 87 0F1338A 1 ASSY, IGN COIL W/DIODE NO ADV 88 035461 2 BARBED STR 1/4NPT X 3/8 89 0F6301 4 CLAMP, HOSE OETIKER 16.5mm 90 0C9806 2 HOSE, 3/8" I.D. X 6" LONG 91 0C3026 1 COOLER, OIL 92 0C9764 4 PLASTITE,1/4-15 X 3/4 93 0C3043 2 GASKET, MANIFOLD / PORT 94 0C7694 1 MANIFOLD CYLINDER 2 95 0C7693 1 MANIFOLD CYLINDER 1 96 0C3041A 2 SLEEVE, RUBBER 97 070008 4 WASHER FLAT M8 SS 98 070006 4 WASHER LOCK M8 SSTL 99 040976 4 SCREW SHC M 100 0F1170A 1 PLATE, BACKING WITH OIL COOLER 101 0E4997 1 GROUND WIRE CONNECTOR 102 0C3725B 1 FLYWHEEL ASSEMBLY 103 0C3031 1 FAN, NYLON 104 0C3032 1 PLATE, FAN 105 0A5992 2 WASHER SHAKEPROOF INT M8 SS 106 051754 2 SCREW HHC M8-1.25 X 12 G8.8 107 0C3033 1 WASHER, 25mm I.D. 108 0C3034 1 NUT,HEX M24 109 0C8549A 1 SNORKEL, AIR INTAKE
8-1.25 X 20 G12.9
ITEM PART NO. QTY. DESCRIPTION
110 0F1169A 1 HOUSING, BLOWER NG COOLER 111 0D1131 1 GUARD, FAN 112 045756 25 SCREW TAPTITE M6-1X10 YELLOW
CHROME 113 0C9763 4 NUT, GROMMET 1/4 PLUG 114 0C3036A 1 HOSE, BREATHER 115 022145 1 WASHER FLAT 5/16-M8 ZINC 116 022129 1 WASHER LOCK M8-5/16 117 0C3018 1 WRAPPER, UPPER CYLINDER 1 118 0C3019 1 WRAPPER, LOWER CYLINDER 1 119 0D1142A 1 WRAPPER, LOWER CYLINDER 2 120 0D1143 1 WRAPPER, UPPER CYLINDER 2 121 0E6043 2 SCREW TAPTITE M5-0.8 X 8 ZP 122 0F1177 1 ASSEMBLY, GROUND WIRE 123 0F1338B 1 ASSY, IGN COIL W/DIODE NO ADV 124 022097 4 WASHER LOCK M6-1/4 125 092079 4 SCREW TAPTITE M6-1.0 X 25 BP 126 0E4271 1 STARTER 127 0D4529 2 SPARKPLUG 128 022129 2 WAS 129 061906 2 SCREW HHC M8-1.25 X 85 G8.8 1 30 082774 1 KEY, WOODRFF 4 X 19D 1 31 0E5343 1 NUT HEX LOCK M10-1.50 1 32 0C8468 1 SPRING, ANTI-LASH 1 33 0C3048 1 ROD, GOVERNOR CONTROL 1 34 0D3754 1 ASSEMBLY, GOVERNOR LEVER 1 35 0D3742 1 SPRING, GOVERNOR 1 36 0C8482 1 ASSEMBLY, GOVERNOR ADJUSTER 1 37 0E0486 1 SCREW SHC M10-1.5 X 75 G10.9 1 38 0D3743 1 SPRING, GOVERNOR IDLE 1 39 0D3705 1 ASSEMBLY, GOVERNOR ADJUSTER
140 0C2993 1 SEAL, GOVERNOR SHAFT 142 045771 1 NUT HEX M8-1.25 G8 143 0D6147 7 SCREW HHFC M6-1.0 X 10mm 144 0E8152 1 O-RING 0.49" I.D. X 0.07" THICK
HER LOCK M8-5/16
BRACKET
35
Page 38
41
42
Section 8 — Exploded Views and Parts Lists
15 kW Generator 15 kW Generator – Drawing No. 0D3417-L
36
35
36
29
41
10
32
31
28
36
17
27
28
16
32
10
19
35
36
28
29
18
26
24
32
25
19
10
30
1
15
2
3
40
37
22
14
20
38
31
28
32
17
31
36
6
498
13
39
12
33
34
7
21
43
24
5
23
11
Page 39
Section 8 — Exploded Views and Parts Lists
15 kW Generator – Drawing No. 0D3417-L
ITEM PART NO. QTY. DESCRIPTION
1 0C6934 1 ADAPTOR, ENGINE
2 0C7930 1 STATOR 12KW
0D2359 STAT O R 1 3KW / 15KW
3 0C7944 1 ROTOR 12KW
0D2356 ROTOR 13KW / 15KW
4 0C6043 1 CARRIER, REAR BEARING
5 0D2336 1 FAN, 12" CURVED BLADE
6 0D6634 1 MUFFLER
7 0D3220 1 TAIL PIPE, MUFFLER
8 0C8101 1 PANEL, MUFFLER BASE
9 056482 1 BEARING 1.1811-2.8346
10 0C3168 3 5/16 SPECIAL LOCK WASHER
11 0D1838 1 BOLT, HHCS 3/8"-24 x 15.50"
12 0D1846 4 BOLT, HHCS M8-1.25 x 345mm
13 0C7038 1 BRACKET, ALTERNATOR MOUNTING
14 0D1609 1 DUCT, ALTERNATOR AIR
15 0D2559 1 GASKET, ALTERNATOR AIR DUCT
16 0C7038A 1 BRACKET, ENGINE MOUNTING
17 0C775
18 0388050AD0 1 CABLE, #6 48" BLACK BATTERY
19 0C2417A 1 EARTH STRAP 3/8X 3/8
20 082121C 1 CLIP-J, VYNL COAT 0.625" ID
21 066386 1 ASSEMBLY BRUSH HOLDER
22 029451 2.6 FT TAPE ELEC UL FOAM 1/8 X 1/2
23 049451 1 WASHER FLAT .406ID X 1.62OD
24 022237 5 WASHER LOCK 3/8
25 022511 4 SCREW HHC 3/8-16 X 1-1/4 G5
26 022131 4 WASHER FLAT 3/8 ZINC
27 051731 4 SCREW HHC M8-1.25 X 50 G8.8
28 022145 12 WASHER FLAT 5/16 ZINC
29 049820 4 NUT LOCK HEX M8-1.25 NYL INSERT
30 045756 2 SCREW TAPTITE M6-1.0X10 BP
31 022129 10 WA
32 022259 8 NUT HEX 5/16-18 STEEL
33 059637 2 SCREW TAPTITE 3/8-16 X 3/4 BP
34 0D4662 4 SCREW 5/16-18X3/4" HH THD ROLL
35 0F7065 3 FT HOSE RES 1/2 LP GAS
36 048031M 4 HOSE CLAMP 3/4" I.D.
37 0F0462 4 NUT HEX W/TOOTH WSHR M8-1.25
38 0C2824 1 SCREW TAP-R #10-32 x 9/16
39 025145 1 U-BOLT 5/16"-18 X 1.25" WITH SADDLE
40 0C4138 2 GASKET, EXHAUST PORT
41 040173 2 CLAMP HOSE #5.5 0.62"-0.62"
42 074995 1.44 FT HOS
43 066849 2 SCREW HHTT M5-0.8 X 16
8 4 RUBBER MOUNT
SHER LOCK M8-5/16
E 1\4 ID LPG 350PSI UL21
15 kW Generator
37
Page 40
Section 8 — Exploded Views and Parts Lists
15 kW Generator Gas Regulator – Drawing No. 0D8720-G
7
4
1
2
2
38
Page 41
Section 8 — Exploded Views and Parts Lists
15 kW Generator
Gas Regulator – Drawing No. 0D8720-G
ITEM PART NO. QTY. DESCRIPTION
1 0D5694 1 CASTING, TWIN REGULATOR HOUSING 2 0F5022 1 SOLENOID COIL, 12VDC 3 0C4647 1 GASKET , SOLENOID 4 0D4166 1 PLUNGER, LP REGULATOR ASSEMBLY 5 0C6070 1 SPRING-SOLENOID, PLUNGER 8 0F4795 4 SCREW PPHM SEMS M4-0.7 X 10 9 0C5760J 1 JET, GN 410 ENGINE LP (7KW) 10 0C6606 2* BARBED STRAIGHT 1/2NPT x 1/2 11 097934 2* O-RING, CHECK VALVE 12 0C4645 2* ADJUSTER SCREW, TWIN REGULATOR 13 0C5761 2 LEVER, REGULATOR 14 0C5968 2 SUPPORT, INLET SEAL 15 0C6066 2 SEAL, INLET 16 0C5759 2 PIN, PIVOT ARM 17 0C5764 2 SPRING, REGULATOR 0C5764A 2 SPRING, REGULATOR (7KW) 18 070728 4 SCREW, PFHMS M3-0.5 x 5 19 0C6069 2 GASKET, DIAPHRAGM 20 0C5762 2 COVER, TWIN REGULATOR 21 045764 16 SCREW, TAPTITE M4X8 BP 22 0C673 23 0C6067 2 SUPPORT, DIAPHRAGM 24 0C4706 2 DIAPHRAGM, TWIN REGULATOR 25 0C6068 2 CAP, DIAPHRAGM SUPPORT 26 0C4643A 2 INLET, TWIN REGULATOR 11.11 DIA. 27 026073 1 PLUG, STANDARD PIPE 1/8" STEEL SQUARE HEAD 026073 2 PLUG, STANDARD PIPE 1/8" STEEL SQUARE HEAD (7KW) 28 0A4032 2* PIN, LIMITED ADJUSTMENT 29 0D3308 4 WASHER, FLAT M3 X 10mm O.D. 30 024310 1 PLUG, STANDARD PIPE 1/2" STEEL SQUARE HEAD (7KW) 31 028414A 1 BARBED STRAIGHT 1/8"NPT X 1/4" 32 0D5698A 1 JET IDLE PRIMER PHILLIPS HD (V-TWIN ONLY) 37 0D3973 1 PLUG, EXPANSION 16mm
1 2 RIVET, POP .118 X .125
* A QUANTITY OF 1 IS TO BE USED ON 7KW HOME STANDBY
39
Page 42
Section 9 – Warranty
15 kW Generator
NOTE: This Emission Control Warranty Statement pertains to this product only IF the generator size is 15 kW or below.
CALIFORNIA AND FEDERAL EMISSION CONTROL WARRANTY STATEMENT
YOUR WARRANTY RIGHTS AND OBLIGATIONS
The California Air Resources Board (CARB) and the United States Environmental Protection Agency (EPA), together with Generac Power Systems, Inc. (Generac), are pleased to explain the Emission Control System Warranty on your new engine.* New (small off road) engines must be designed, built and equipped to meet stringent anti-smog standards for the state of California and the federal government. Generac will warrant the emission control system on your engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modification or improper maintenance of your engine.
Your emission control system may include parts such as the carburetor, ignition and exhaust systems. Generac will repair your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.
MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:
Emissions control systems on engines are warranted for two years as hereinafter noted. If, during such warranty period, any emission-related component or system on your engine is found to be defective in materials or workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Facility.
PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES:
As the engine purchaser/owner, you are responsible for the completion of all required maintenance as listed in your factory supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance on your engine. However, Generac cannot deny warranty solely because of the lack of receipts or for your failure to ensure the completion of all scheduled maintenance.
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect, improper maintenance or unap­proved modifications, or the use of counterfeit and/or “grey market” parts not made, supplied or approved by Generac.
You are responsible for presenting your engine to a Generac Authorized Warranty Service Facility as soon as a problem occurs. The warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility. To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:
1-800-333-1322
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System Warranty (ECS Warranty), which is provided to you by Generac pursuant to California and federal law. See also the “Generac Limited Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe important rights and obli­gations with respect to your new engine.
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty ser­vice, evidence must be presented showing the date of the sale to the original purchaser/owner. The purchaser/owner shall be responsible for any expenses or other charges incurred for service calls and/or transportation of the product to/from the inspection or repair facilities. The purchaser/owner also shall be responsible for any and/or all damages or losses incurred while the engine is being transported/shipped for inspection or warranty repairs.
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at the following address:
ATTENTION WARRANTY DEPARTMENT
GENERAC POWER SYSTEMS, INC.
P.O. BOX 297
WHITEWATER, WI 53190
Part 1
40
Page 43
Section 9 – Warranty
15 kW Generator
EMISSION CONTROL SYSTEM WARRANTY
Emission Control System Warranty (ECS Warranty) for 1997 and later model year engines:
(a) Applicability: This warranty shall apply to 1997 and later model year engines. The ECS Warranty Period shall begin on the
date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue for 24 consecutive months thereafter.
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or
equipment, and to each subsequent purchaser/owner, that each of its engines is ...
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the EPA and CARB pursuant to
their respective authority, and
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a war-
ranted emissions-related part to fail to be identical in all material respects to the part as described in the engine manufac­turer’s application for certification.
(c) The ECS Warranty only pertains to emissions-related parts on your engine, as follows:
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual
shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or replace as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s Manual
shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection (4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no charge
to the owner at a Generac Authorized Warranty Service Facility.
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsible
for diagnostic costs if the repair is deemed warrantable.
(6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused
by a failure under warranty of any emission-related part covered by the ECS Warranty.
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient to
meet the expected demand for such emission-related parts.
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS
Warranty maintenance or repairs and will be provided without charge to the purchaser/owner. Such use shall not reduce Generac’s ECS Warranty obligations.
(9) Unapproved, add-on, modified, counterfeit and/or “grey market” parts may not be used to modify or repair a Generac
engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim. Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of such an unapproved, add-on, modified, counterfeit and/or “grey market” part.
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:
1) Fuel Metering System:
1.1) Gasoline carburetor assembly and its internal components (if so equipped).
a) Fuel filter (if so equipped) b) Carburetor gaskets c) Fuel pump (if so equipped)
1.2) LPG carburetion assembly and its internal components (if so equipped).
a) Fuel controller (if so equipped) b) Mixer and its gaskets (if so equipped) c) Carburetor and its gaskets (if so equipped) d) Primary gas regulator (if so equipped) e) LP liquid vaporizer (if so equipped)
2) Air Induction System including: a) Intake pipe/manifold b) Air cleaner
3) Ignition System including: a) Spark plug b) Ignition module
4) Catalytic Muffler Assembly (if so equipped) including: a) Muffler gasket b) Exhaust manifold
5) Crankcase Breather Assembly including: a) Breather connection tube
*Generac engine types covered by this warranty statement include the following:
1) Utility
2) Lawn and Garden Equipment
3) Recreational Vehicle (RV) Generator
4) Industrial Mobile (IM) Generator
Part 2
41
Page 44
Section 9 – Warranty
15 kW Generator
BRYANT "TWO YEAR" LIMITED WARRANTY FOR
"PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS"
For a period of two years from the date of original sale, warrants that its generator will be free from defects in material and workman­ship for the items and period set forth below. Bryant will, at its option, repair or replace any part which, upon examination, inspection and testing by a Bryant Dealer, is found to be defective. All transportation costs under the warranty, including return to the factory, are to be borne and prepaid by the purchaser/owner. This warranty applies only to Bryant prepackaged emergency automatic standby generators sold and rated for use in "Standby" applications.
WARRANTY SCHEDULE
YEARS ONE AND TWO - 100% (one hundred percent) transferable coverage on Labor and Part(s) listed. ENGINE - All Components ALT ERNATOR - All Components TRANSFER SYSTEM - All Components
Steel enclosures are warranted against rusting for the first year of ownership only. Damage caused after receipt of generator is the responsibility of the owner and is not covered by this warranty. Nicks, scrapes, dents or scratches to the painted enclosure should be repaired promptly by the owner.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
• Bryant generators that utilize non-Bryant replacement parts.
• Bryant generators utilizing non-Bryant automatic transfer switches.
Any Bryant generators used as rental or trailer mounted applications.
Air-cooled units used for prime power in place of existing utility power where utility power is present or in place of utility power where utility power service does not normally exist.
• Costs of normal maintenance, adjustments, installation and start-up.
Steel enclosures that are rusting due to the improper installation, location in a harsh or saltwater environment or scratched where integrity of paint applied is compromised.
• Failures caused by any contaminated fuels, oils, coolants or lack of proper fluid amounts.
• Failures due, but not limited to, accident, misuse, abuse, negligence or improper installation. As with all mechanical devices, the Bryant engines need periodic part(s) service and replacement to perform well.
• Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire, freezing, lightning, earthquake, windstorm, hail, volcanic eruption, water or flood, tornado or hurricane.
• Damage related to rodent and/or insect infestation.
• Products that are modified or altered in a manner not authorized by Bryant in writing.
Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the defective part(s).
• Failure due to misapplication.
• Telephone, cellular phone, facsimile, internet access or other communication expenses.
• Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific unit warranty period.
• Expenses related to "customer instruction" or troubleshooting where no manufacturing defect is found.
Rental equipment used while warranty repairs are being performed.
• Costs incurred for equipment used for removal and/or reinstallation of generator, (i.e.; cranes, hoists, lifts, etc.)
• Overnight freight costs for replacement part(s).
• Overtime labor.
Starting batteries, fuses, light bulbs and engine fluids.
THIS WARRANTY IS IN
BRYANT MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
BRYANT 'S ONLY L I ABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL BRYANT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF BRYANT 'S NEGLIGENCE. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation may not apply to you. This warranty gives you specific legal rights. You also have other rights from state to state.
Part No. 0F7614 Rev. 0 (08/24/05) Printed in U.S.A.Catalog No. OM18-7
PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY,
Revision (10/01/04)
Loading...