Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations must
be performed by trained service personnel. When working on
heating equipment, observe precautions in the literature, on tags,
and on labels attached to or shipped with the unit and other safety
precautions that may apply.
Follow all safety codes, including NFPA 54/ANSI Z223.1-1996,
National Fuel Gas Code and ANSI/NFPA 90B, Installation Standards, Warm Air Heating and Air Conditioning Systems. In
Canada, refer to the current edition of the National Standard of
Canada CAN/CGA-B-149. Wear safety glasses and work gloves.
Have a fire extinguisher available during start-up and adjustment
procedures and service calls.
CANADIAN GAS ASSOCIATION
APPROVED
R
As an ENERGY STAR
Partner, Bryant Heating &
Cooling Systems has determined that this product meets
the ENERGY STAR guidelines for energy efficiency.
SM
Recognize safety information. This is the safety-alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
WARNING: The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools, and equipment. If you do not
possess these, do not attempt to perform any maintenance
on this equipment other than those procedures recommended in the User’s Manual. FAILURE TO FOLLOW
THIS WARNING COULD RESULT IN POSSIBLE
DAMAGE TO THIS EQUIPMENT, SERIOUS PERSONAL INJURY, OR DEATH.
.
Page 2
WARNING: Never store anything on, near, or in contact
with the furnace, such as:
1. Spray or aerosol cans, rags, brooms, dust mops,
vacuum cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning
compounds, plastic or plastic containers, gasoline,
kerosene, cigarette lighter fluid, dry cleaning fluids, or
other volatile fluids.
3. Paint thinners and other painting compounds, paper
bags, or other paper products. Failure to follow this
warning can cause corrosion of the heat exchanger,
fire, personal injury, or death.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
CAUTION: Electrostatic discharge can affect electronic
components. Take precautions during furnace installation
and servicing to protect the furnace electronic control.
Precautions will prevent electrostatic discharges from
personnel and hand tools which are held during the
procedure. These precautions will help to avoid exposing
the control to electrostatic discharge by putting the
furnace, the control, and the person at the same electrostatic potential.
AIRFLOW
UPFLOW
AIRFLOW
HORIZONTAL
LEFT
DOWNFLOW
AIRFLOW
HORIZONTAL
Fig. 2—Multipoise Orientations
WARNING: Turn off the gas and electrical supplies to
the unit before performing any maintenance or service.
Follow the operating instructions on the label attached to
the furnace. Failure to follow this warning could result in
personal injury or death.
RIGHT
AIRFLOW
A93041
1. Disconnect all power to the furnace. DO NOT TOUCH
THE CONTROL OR ANY WIRE CONNECTED TO THE
CONTROL PRIOR TO DISCHARGING YOUR BODY’S
ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the
furnace chassis which is close to the control. Tools held in
a person’s hand during grounding will be satisfactorily
discharged.
3. After touching the chassis you may proceed to service the
control or connecting wires as long as you do nothing that
recharges your body with static electricity (for example; DO
NOT move or shuffle your feet, DO NOT touch ungrounded objects, etc.).
4. If you touch ungrounded objects (recharge your body with
static electricity), firmly touch furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded) furnaces.
6. Before removing a new control from its container, discharge your body’s electrostatic charge to ground to protect
the control from damage. If the control is to be installed in
a furnace, follow items 1 through 5 before bringing the
control or yourself into contact with the furnace. Put all
used AND new controls into containers before touching
ungrounded objects.
7. An ESD service kit (available from commercial sources)
may also be used to prevent ESD damage.
GENERAL
These instructions are written as if the furnace is installed in an
upflow application. An upflow furnace application is where the
blower is located below the combustion and controls section of the
furnace, and conditioned air is discharged upward. Since this
furnace can be installed in any of the 4 positions shown in Fig. 2,
you must revise your orientation to component location accordingly.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible equipment failure, it is essential that maintenance be performed annually
on this equipment. Consult your local dealer for maintenance and
maintenance contract availability.
The minimum maintenance that should be performed on this
equipment is as follows:
1. Check and clean or replace air filter each month as required.
2. Check blower motor and wheel for cleanliness annually.
3. Check electrical connections for tightness and controls for
proper operation each heating season. Service as necessary.
4. Check for proper condensate drainage. Clean as necessary.
5. Check for blockages in combustion-air and vent pipes
annually.
6. Check burners for cleanliness annually.
CAUTION: Personal injury could result from sharp
metal edges, etc. Use care when removing parts.
I. CLEANING AND/OR REPLACING AIR FILTER
The air filter arrangement may vary depending on the application
or orientation.
CAUTION: Never operate unit without a filter or with
the blower access panel removed. Failure to follow this
warning could result in a fire or personal injury.
To clean or replace the filters, proceed as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access panel.
3. Release filter retainer wire. (See Fig. 3 and 4.)
4. Slide filter out of furnace.
5. Furnaces are equipped with permanent, washable filter(s).
Clean filter by spraying cold tap water through filter in
opposite direction of airflow.
6. Rinse filter and let dry. Oiling or coating of filter is not
recommended.
7. Slide filter into furnace.
—2—
Page 3
WASHABLE
FILTER
WASHABLE
FILTER
FILTER
RETAINER
FILTER
SUPPORT
FILTER
RETAINER
A93046
Fig. 3—Bottom Filter Arrangement
8. Recapture filter retainer wire.
9. Replace blower access panel and main furnace door.
10. Turn on electrical supply to furnace.
NOTE: If the filter has cross-mesh binding, the binding must face
the blower. If the filter has an air direction arrow, the arrow must
point toward the blower.
II. BLOWER MOTOR AND WHEEL MAINTENANCE
To ensure long life, economy, and high efficiency, clean accumulated dirt and grease from blower wheel and motor annually.
The inducer and blower motors are pre-lubricated and require no
additional lubrication. These motors can be identified by the
absence of oil ports on each end of the motor.
The following items should be performed by a qualified service
technician.
Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access panel.
3. Disconnect wires.
a. Disconnect motor wiring harness plug on blower hous-
ing.
b. Disconnect auxiliary limit switch leads at switch.
c. Disconnect field thermostat connections depending on
their length and routing.
4. Position control box, transformer, and door switch assembly
to right side of furnace casing.
5. If condensate trap is located in left- or right-hand side of
furnace casing, proceed to item 6, otherwise remove trap
and tubing as described below.
a. Disconnect field drain connection from condensate trap.
b. Disconnect drain and relief port tubes from condensate
trap.
c. Remove condensate trap from blower shelf.
6. Remove screws securing blower assembly to blower shelf
and slide blower assembly out of furnace.
7. Clean blower wheel and motor by using a vacuum with soft
brush attachment. Be careful not to disturb balance weights
(clips) on blower wheel vanes. Do not bend wheel or blades
as balance will be affected.
8. If greasy residue is present on blower wheel, remove wheel
from the blower housing and wash it with an appropriate
degreaser. To remove wheel:
A93045
Fig. 4—Filter Installed for Side Inlet
a. Mark blower wheel location on shaft before disassembly
to ensure proper reassembly.
b. Loosen setscrew holding blower wheel on motor shaft.
NOTE: Mark blower mounting arms and blower housing so each
arm is positioned at the same hole location during reassembly.
c. Mark blower wheel orientation and cutoff plate location
to ensure proper reassembly.
d. Remove screws securing cutoff plate and remove cutoff
plate from housing.
e. Remove bolts holding motor mounts to blower housing
and slide motor and mounts out of housing.
f. Remove blower wheel from housing.
g. Clean wheel per instructions on degreaser cleaner.
9. Reassemble motor and blower wheel by reversing items 8b
through 8f. Ensure wheel is positioned for proper rotation.
10. Reinstall blower assembly in furnace.
11. Reinstall condensate trap and tubing if previously removed.
a. Reinstall condensate trap in hole in blower shelf.
b. Connect condensate trap drain tubes. See Fig. 8 or tubing
diagram on main furnace door for proper tube location.
(1.) Connect 1 tube (blue or blue and white striped)
from collector box.
(2.) Connect 1 tube (violet or unmarked) from inducer
housing.
(3.) Connect 1 tube (relief port, green or pink) from
collector box.
c. Connect field drain to condensate trap.
NOTE: Ensure tubes are not kinked or pinched, as this will affect
operation.
12. Reinstall control box, transformer, and door switch assembly on blower shelf.
13. Reconnect wires.
a. Refer to furnace wiring diagram, and connect motor and
auxiliary limit switch leads. (See Fig. 16.)
b. Connect thermostat leads if previously disconnected.
14. Turn on electrical supply. Manually close blower access
panel door switch. Use a piece of tape to hold switch closed.
Check for proper rotation and speed changes between
heating and cooling by jumpering R to G and R to Y on
control center thermostat terminals. (See Fig. 11.)
—3—
Page 4
WARNING: Blower access panel door switch opens
115-v power to control center. No component operation
can occur. Caution must be taken when manually closing
this switch for service purposes. Failure to follow this
warning could result in personal injury or death.
15. If furnace is operating properly, release blower access panel
door switch, replace blower access panel, and replace main
furnace door.
III. CLEANING BURNERS
The following items should be performed by a qualified service
technician. If the burners develop an accumulation of light dirt or
dust, they may be cleaned by using the following procedure:
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Remove burner box cover.
4. Using backup wrench, disconnect gas supply pipe from gas
valve.
CAUTION: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper and
dangerous operation.
5. Remove wires from gas valve. Note location for reassembly.
6. Remove burner box pressure tube from gas valve regulator
fitting.
7. Remove screws that secure manifold to burner box. (See
Fig. 5.)
13. Reconnect wires to gas valve. Refer to furnace wiring
diagram for proper wire location.
14. Reinstall burner box pressure tube to gas valve regulator
fitting.
15. Reinstall gas supply pipe to gas valve using backup wrench
on gas valve to prevent rotation and improper orientation.
NOTE: Use propane gas resistant pipe dope to prevent gas leaks.
DO NOT use Teflon tape.
WARNING: Gas valve knob or switch MUST be facing
forward or tilted upward. Failure to follow this warning
could result in property damage, personal injury, or death.
16. Replace burner box cover.
17. Turn on gas and electrical supplies to furnace.
18. Check for gas leaks.
WARNING: Never use matches, candles, flame, or
other sources of ignition to check for gas leakage. Use a
soap-and-water solution. Failure to follow this warning
could result in a fire, personal injury, or death.
19. Replace main furnace door.
IV. CLEANING HEAT EXCHANGERS
The following items should be performed by a qualified service
technician.
A. Primary Heat Exchangers
If the heat exchangers get an accumulation of light dirt or dust on
the inside, they may be cleaned by the following procedure:
NOTE: If the heat exchangers get a heavy accumulation of soot
and carbon, both the primary and secondary heat exchangers
should be replaced rather than trying to clean them thoroughly due
to their intricate design. A build-up of soot and carbon indicates
that a problem exists which needs to be corrected, such as
improper adjustment of manifold pressure, insufficient or poor
quality combustion air, improper vent termination, incorrect size
or damaged manifold orifice(s), improper gas, or a restricted heat
exchanger (primary or secondary). Action must be taken to correct
the problem.
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
A96304
Fig. 5—Burner Box Assembly
8. Remove manifold, orifices, and gas valve as 1 assembly.
9. Remove screws attaching burner assembly in burner box.
10. Remove burner assembly from burner box.
NOTE: All burners are attached to burner bracket and can be
removed as 1 assembly.
11. Clean burners with soft brush and vacuum.
12. Reinstall manifold, orifice, and gas valve assembly in
burner box. Ensure manifold seal grommet is installed
properly and burners fit over orifices.
CAUTION: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper and
hazardous operation.
3. Disconnect wires or connectors to rollout switch, gas valve,
ignitor, and flame sensor.
4. Disconnect combustion-air intake pipe from intake housing.
5. Remove the pressure switch tube from intake housing.
6. Remove screws attaching intake housing to burner box, and
rotate intake housing away from burner box for removal.
7. Using backup wrench, disconnect gas supply pipe from gas
valve.
8. Disconnect pressure tubing from gas valve.
9. Remove 2 screws attaching top filler panel and rotate
upwards to gain access to screws attaching burner box to
cell panel.
Page 5
10. Remove screws attaching burner box to cell panel. (See Fig.
5.)
NOTE: Burner box, cover, manifold, gas valve, and burner
assembly should be removed as 1 assembly.
11. Clean heat exchanger openings with a vacuum and a soft
brush. (See Fig. 6.)
NOTE: After cleaning, inspect the heat exchangers to ensure they
are free of all foreign objects that may restrict flow of combustion
products.
12. Reverse items 4 through 10 for reassembly.
WARNING: The ground wire from the gas valve MUST
be attached to the burner box attachment screw. Failure to
attach this ground wire to an adequate casing ground will
cause the furnace control to lock out.
NOTE: Be sure burner box gasket is installed between burner box
and cell panel. If gasket is damaged, replace it.
NOTE: Inspect combustion-air intake housing. If foamed gasket
was removed, check for any damage. If gasket is damaged in any
way, it must be repaired. To repair, remove damaged gasket
section, apply sealant releasing agent such as PAM cooking spray
or equivalent (must not contain corn or canola oil, aromatic or
halogenated hydrocarbons or inadequate seal may occur) to burner
Page 6
INSTALLATION
LEVEL (0")
This appliance requires a special venting system. Refer to the
installation instructions for parts list and method of installation.
TO
1/2" MAX
Furnace must be installed level, or pitched forward within 1/2 inch
of level for proper drainage. Failure will result in equipment or
property damage. See Installation Manual for IMPORTANT unit
support details on horizontal applications.
UPFLOW OR
DOWNFLOW
FRONT
Furnace is shipped from factory in upflow configuration. Pressure tube and drain tube routing MUST match the diagrams below.
Condensate Trap; Factory
Installed in Blower Shelf
(Blower access panel removed)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
INDUCER HOUSING (MOLDED)
DRAIN TUBE (BEHIND
COLLECTOR BOX DRAIN TUBE)
COLLECTOR BOX
DRAIN TUBE (BLUE)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE COUPLING
(LEFT DRAIN OPTION)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
Condensate Trap on
LEFT Side
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRI PED)
COLLECTOR BOX
EXTENSION TUBE
CONDENSATE TRAP
INDUCER HOUSING
DRAIN TUBE (VIOLET)
Tube location when used on
HORIZONTAL - LEFT application
AUXILIARY "J" BOX
RELOCATED HERE
PLUG
CAP
CAP
Tube location when used in UPFLOW application
CAP
PLUG
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
CONDENSATE TRAP
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE COUPLING
(RIGHT DRAIN OPTION)
FIELD-INSTALLED
FACTORY-SUPPLIED
1/2-IN. CPVC STREET
ELBOWS (2) FOR
LEFT DRAIN OPTION
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
DRAIN TUBE (BLUE)
CONDENSATE
TRAP
INDUCER
HOUSING
DRAIN TUBE
(VIOLET)
Tube location when used in DOWNFLOW application
COLLECTOR BOX
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX
EXTENSION TUBE
PLUG
COLLECTOR BOX
TUBE (PINK)
TUBE (GREEN)
COLLECTOR
BOX DRAIN
TUBE (BLUE
& WHITE
STRIPED)
INDUCER
HOUSING DRAIN
TUBE (VIOLET)
DRAIN TUBE
COUPLING
DRAIN TUBES
ROUTED IN FRONT
OF GAS VALVE
Tube location when used on
HORIZONTAL - RIGHT application
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRI PED)
COLLECTOR
BOX TUBE
(GREEN)
PLUG
CAP
LEVEL (0")
TO
1/2" MAX
FRONT
HORIZONTAL
Condensate Trap on LEFT
Side Optional
CAP
PLUG
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
Condensate Trap on
RIGHT Side
CAP
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX
TUBE (PINK)
PLUG
COLLECTOR BOX
EXTENSION TUBE
CONDENSATE TRAP
COLLECTOR BOX
EXTENSION DRAIN
GAS VALVE
COLLECTOR BOX DRAIN TUBE (BLUE)
COLLECTOR BOX TUBE (PINK)
TUBE
COLLECTOR BOX
EXTENSION TUBE
CONDENSATE TRAP
EXTENSION DRAIN TUBE
NOTE:
BETWEEN BLOWER SHEL F AND INDUCER HOUSING FOR
COLLECTOR BOX
COLLECTOR BOX TUBE (PINK) RELOCATE TUBE
040,060, AND 080 HEATING INPUT FURNACES
DRAIN TUBE
COUPLING
INDUCER
HOUSING
DRAIN TUBE
(VIOLET)
COLLECTOR BOX
DRAIN TUBE
(BLUE)
COLLECTOR BOX TUBE (GREEN)
COLLECTOR BOX DRAIN TUBE
(BLUE AND WHITE STRIPED)
INDUCER HOUSING
DRAIN TUBE (VIOLET)
1. All tubing must be connected securely and routed to avoid kinks and traps.
2. Pressure tubing must always slope away from pressure switch to collector box connection as shown.
3. HORIZONTAL-LEFT installations require the collector box pressure tube to be relocated between the inducer housing and the blower
shelf to prevent a trap. Refer to the Installation Instructions for further details.
322094-101 REV. B
Fig. 8—Furnace Pressure and Drain Tubing Diagram
—6—
COLLECTOR
BOX
EXTENSION
TUBE
CONDENSATE
TRAP
A94212
Page 7
VI. SERVICING HOT SURFACE IGNITOR
The ignitor does NOT require annual inspection. Check ignitor
resistance before removal.
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Disconnect ignitor wire connection.
4. Check ignitor resistance.
a. Using an ohm meter, check resistance across both ignitor
leads in connector.
b. Cold reading should be between 45 ohms and 90 ohms.
c. If ohm reading is higher than 110 ohms, ignitor is
cracked and must be replaced.
5. Remove ignitor assembly.
A89020
Fig. 9—Burner Flame
12. Reconnect pressure tubes to pressure switches. See diagram
on main furnace door for proper location of tubes. Be sure
tubes are not kinked. (See Fig. 8.)
13. Turn on gas and electrical supplies to furnace.
14. Check furnace operation through 2 complete heat operating
cycles. Check area below inducer housing, vent pipe, and
condensate trap to ensure no condensate leaks occur. If
leaks are found, correct the problem.
15. Check for gas leaks.
WARNING: Never use matches, candles, flame, or
other sources of ignition to check for gas leakage. Use a
soap-and-water solution. Failure to follow this warning
could result in a fire, personal injury, or death.
16. Replace main furnace door.
CAUTION: Allow ignitor to cool before removal. Normal operation temperatures exceed 2000°F.
a. Do not remove ignitor from bracket while assembly is in
furnace. Using a 1/4 in. nutdriver, remove screw securing bracket and ignitor assembly to bottom of burner
box. The screw in the bracket is always located toward
outside of burner box. The screw may be hidden by inlet
box or inlet pipe, but can be removed without removing
either. After removing screw, slide ignitor and bracket
toward outside of burner box and pull straight out.
CAUTION: The ignitor is fragile. DO NOT allow it to
hit the side of the burner box opening while removing or
replacing it.
b. Inspect ignitor for a white area indicating a crack may be
present. If found, replace ignitor.
NOTE: A small crack cannot be seen on a new ignitor. After a
period of operation, a white area will be visible around the crack.
c. If replacement is required, replace ignitor on ignitor
bracket external to furnace to avoid damage as the
silicon portion is very brittle and will easily crack or
shatter.
d. To remove ignitor from ignitor bracket, remove screw
holding ignitor ceramic block to bracket and pull ceramic block out of bracket.
6. To replace ignitor/ignitor assembly, reverse items 5a
through 5d.
7. Reconnect ignitor wire connection.
8. Turn on gas and electrical supplies to furnace.
9. Verify ignitor operation by initiating control board self-test
feature or by cycling thermostat.
10. Replace main furnace door.
VII. ELECTRICAL CONTROLS AND WIRING
CAUTION: There may be more than 1 electrical supply
to the unit. Check accessories and cooling unit for
additional electrical supplies.
The electrical ground and polarity for 115-v wiring must be
maintained properly. Refer to Fig. 11 for field wiring information
and to Fig. 16 for unit wiring information.
NOTE: If the polarity is not correct, the STATUS LED on the
control center will flash rapidly and prevent the furnace from
operating. The control system also requires an earth ground for
proper operation of the control center and flame sensing.
Page 8
→ Fig. 11—Field Wiring
The 24-v circuit contains an automotive-type, 3-amp fuse located
on the control center. (See Fig. 12.) Any direct shorts of the 24-v
wiring during installation, service, or maintenance will cause this
fuse to blow. If fuse replacement is required, use ONLY a fuse of
identical size.
With power to the unit disconnected, check all electrical connections for tightness. Tighten all screws on electrical connections. If
any smoky or burned connections are found, disassemble the
connection, clean all parts, strip wire, and reassemble properly and
securely.
Reconnect electrical supply to unit and observe unit through 1
complete operating cycle. Electrical controls are difficult to check
without proper instrumentation; if there are any discrepancies in
the operating cycle, contact your dealer and request service.
VIII. TROUBLESHOOTING
For an explanation of fault codes, refer to service label located on
back of main furnace door or Fig. 15.
The control center stores all fault codes for a period of 5 "good or
proper" operating cycles, regardless of 115- or 24-v power
interruption.
NOTE: Removing blower access panel opens blower access
panel door switch and terminates 115-v power to control center.
Look into blower access panel sight glass for current LED status.
1. To retrieve fault code proceed with the following:
NOTE: NO thermostat signal may be present at control center
and all blower time delay off periods must be completed.
a. Leave 115-v power to furnace turned on.
b. Remove main furnace door.
c. Look into blower access panel sight glass for current
LED status.
d. Remove blower access panel.
e. Turn setup switch SW-1 to ON position. (See Fig. 12 or
16 for location.)
f. Manually close blower access panel door switch. Use a
piece of tape to hold switch closed.
A98325
WARNING: Blower access panel door switch opens
115-v power to control center. No component operation
can occur. Caution must be taken when manually closing
this switch for service purposes. Failure to follow this
warning could result in personal injury or death.
g. LEDs display last fault code to occur first, followed by
any other fault that has occurred in the last 5 "good or
proper" cycles. The remaining faults displayed will be in
numerical order starting from the lowest number first.
Only 1 of each fault code will be displayed, regardless of
how many times the fault has occurred.
h. Fault code display will continue and repeat as described
above or until setup switch SW-1 is turned off.
i. Release blower access panel door switch and replace
blower access panel.
j. Operate furnace through 1 heat cycle to test for proper
operation and check LED status.
k. If furnace is operating properly and LEDs indicate
proper operation, replace main furnace door.
2. Fault code display can be removed from control’s display
mode by performing the following. This is also called the
"Clean Up Procedure."
a. Leave 115-v power to furnace turned on.
b. Remove main furnace door.
c. Look into blower access panel sight glass for current
LED status.
d. Remove blower access panel.
e. Turn setup switch SW-1 to ON position. (See Fig. 12 or
16 for location.)
f. Jumper thermostat terminals R, W, and Y on control
center.
Page 9
EAC-ELECTRONIC AIR
CLEANER TERMINALS
(115-VAC 1 AMP MAX)
MAIN BLOWER
CONTROL WIRE
CONNECTOR
CONTINUOUS
FAN (CF) SETUP
SWITCHES
HOT SURFACE
IGNITOR CONNECTOR
HUM
RG
W/W1 Y/Y2
24V
COM
TRANSFORMER
24-V CONNECTORS
COMMUNICATION
CONNECTOR
W2
→ Fig. 12—Variable-Capacity Control Center
115-V
CONNECTORS
PRESSURE SWITCH
CONNECTOR
HUM-HUMIDIFIER
TERMINAL
(24-VAC 0.5 AMP MAX)
24-V THERMOSTAT
TERMINALS
DEHUMIDIFY ENABLE (DE)
(WHEN PROVIDED)
DEHUMIDIFIER (DEHUM)
CONNECTOR
3-AMP FUSE
STATUS AND DIAGNOSTIC
LED LIGHTS
AIR CONDITIONING
(A/C) SETUP SWITCH
SETUP SWITCHES
(SW) AND BLOWER
OFF DELAY SETUP
SWITCHES
MODEL PLUG
A98296
g. Manually close blower access panel door switch. Use a
piece of tape to hold switch closed.
WARNING: Blower access panel door switch opens
115-v power to control center. No component operation
can occur. Caution must be taken when manually closing
this switch for service purposes. Failure to follow this
warning could result in personal injury or death.
h. After fault code 11 flashes for at least 2 times, remove R,
W, and Y jumpers.
i. Turn setup switch SW-1 to OFF position.
j. Release blower access panel door switch and replace
blower access panel.
k. Operate furnace through 1 heat cycle to check for proper
operation and check LED status.
l. If furnace is operating properly and LEDs indicate proper
operation, replace main furnace door.
3. The control can also assist in troubleshooting by performing
a Component Test. The Component Test will functionally
operate all furnace components, except the gas valve.
a. To initiate Component Test proceed with the following:
(1.) Leave 115-v power to furnace turned on.
(2.) Remove main furnace door.
(3.) Remove blower access panel.
(4.) Turn setup switch SW-6 to ON position.
(5.) Manually close blower access panel door switch.
Use a piece of tape to hold switch closed.
WARNING: Blower access panel door switch opens
115-v power to control center. No component operation
can occur. Caution must be taken when manually closing
this switch for service purposes. Failure to follow this
warning could result in personal injury or death.
b. When items (1) through (5) above have been completed,
the following will occur:
(1.) The control center goes through a brief self test.
This self test takes approximately 2 sec to complete.
After door switch is closed, red (microprocessor)
LED briefly comes on. Then green LED comes on
for 1 sec, followed by 1 sec where both the green
and yellow LEDs are on. During this time, the
control is checking itself.
(2.) Inducer motor operates for 20 sec at low speed,
operates for 20 sec at high speed, then turns off.
(3.) Hot surface ignitor is energized for 15 sec, then
de-energized.
(4.) Main blower motor operates for 20 sec at low
speed, operates at high speed for 20 sec, then turns
off.
(5.) After component operation test is completed, 1 or
more fault codes (11, 22, 41, or 42) will flash. See
service label on back of main furnace door or Fig.
15 for explanation of codes.
NOTE: To repeat component test, turn setup switch SW-6 to OFF
and then back to ON.
c. After component test, perform the following:
—9—
Page 10
(1.) Release blower access panel door switch and turn
setup switch SW-6 to OFF position.
(2.) Replace blower access panel.
(3.) Operate furnace through 1 heat cycle to check for
proper operation and check LED status.
(4.) If furnace is operating properly and LEDs indicate
proper operation, replace main furnace door.
IX. CHECKING HEAT TAPE OPERATION
(IF APPLICABLE)
In applications where the ambient temperature around the furnace
is 32°F or lower, freeze protection measures are required. If this
application is where heat tape has been applied, check to ensure it
will operate when low temperatures are present.
NOTE: Heat tape, when used, should be wrapped around the
condensate drain trap and drain line. There is no need to use heat
tape within the furnace casing. Most heat tapes are temperature
activated, and it is not practical to verify the actual heating of the
tape. Check the following:
1. Check for signs of physical damage to heat tape such as
nicks, cuts, abrasions, gnawing by animals, etc.
2. Check for discolored heat tape insulation. If any damage or
discolored insulation is evident, replace heat tape.
3. Check that heat tape power supply circuit is on.
X. WINTERIZING
32°F MINIMUM INSTALLED
AMBIENT OR FREEZE
PROTECTION REQUIRED
A93058
CAUTION: If this furnace is installed in an unconditioned space where the ambient temperatures may be
32°F or lower, freeze protection measures must be taken.
CAUTION: Freezing condensate left in the furnace will
damage the equipment.
If the furnace will be off for an extended period of time in a
structure where the temperature will drop to 32°F or below,
winterize as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door.
3. Disconnect drain tube from inducer housing. (See Fig. 13.)
4. Insert funnel in drain tube and pour antifreeze, propylene
glycol (RV, swimming pool antifreeze, or equivalent) into
furnace until it is visible at point where condensate enters
open drain. (See Fig. 14.)
5. Reconnect drain tube to inducer housing.
6. Replace main furnace door.
CAUTION: Do not use ethylene glycol (Prestone II
antifreeze/coolant or equivalent automotive type). Failure
of plastic components will occur.
—10—
Page 11
Fig. 13—Inducer Housing Drain Tube
A94208
Page 12
STATUS
SERVICE
position and jumper thermostat terminals "R", "W/W1", and "Y/Y2" simultaneously with
the door switch pushed in and power to the unit "ON". Disconnect jumper and place
RED LED1 ONFurnace is operating in emergency heat.
RED LED2 ONThe microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON"
LED CODE
setup switch in the "OFF" position. If LED2 reappears replace main control board.
YELLOW LED3 ONFurnace is operating in high heat.
GREEN LED4 ONFurnace is operating in low heat.
RED LED2 FLASHINGLine voltage polarity is reversed.
read recent fault history put setup switch "SW-1" in the "ON" position. To clear recent fault history,
put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1", and "Y/Y2"
simultaneously until an "11" is flashed.
greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT
DETERMINED BY NUMBER OF FLASHES OF THE YELLOW LED AND THE SECOND DIGIT DETERMINED
BY NUMBER OF FLASHES OF THE GREEN LED.
11 NO FAULT IN RECENT HISTORY DISPLAY - Indicates no faults have occurred within last five cycles. To
to fault #44 section.
12 BLOWER CALIBRATION LOCKOUT - Indicates RPM calculated for low heat was less than 250 RPM or
13 LIMIT SWITCH LOCKOUT - Indicates the occurrence of 10 successive limit trips during high heat or three
successive limit trips during low heat. Auto reset after three hours.
- Improper high or low heat gas input adjustment.
- Stuck high heat solenoid in gas valve.
Check for: - Improper or misaligned limit and/or limit shield.
14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.
correct connector jumper location.
combinations will cause the fault.
21 INVALID MODEL SELECTION - Indicates model plug is missing or incorrect. See wiring diagram for
22 SETUP ERROR - Indicates setup switch "SW-1" or SW-6" is positioned improperly. The following
- Thermostat call with "SW-1" "ON".
- Thermostat call with "SW-6" "ON".
-"SW-1" and "SW-6" both "ON" together.
14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and
20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing
unit will default to closest allowable airflow.
23 INVALID BLOWER AIRFLOW SELECTION - Indicates improper "A/C" or "CF" switch se tting. The 042 and
24 SECONDARY VOLTAGE FUSE IS OPEN - Indicates the fuse is open and there is a short circuit in the low
- Water in vent piping, possibly sagging pipe.
- Improper pressure switch wiring or pressure switch tubing connections.
voltage wiring.
or fails to close after call, or opens in high heat.
Check for: - Plugged condensate drain.
31 HIGH PRESSURE SWITCH FAULT - Indicates high pressure switch is closed at call, or in low heat,
- Failed or "Out-of-Calibration" pressure switches.
32 LOW PRESSURE SWITCH FAULT - Indicates low pressure switch is closed at call, or fails to close
- Water in vent piping, possibly sagging pipe.
- Improper pressure switch wiring or pressure switch tubing connections.
- Failed or "Out-of-Calibration" pressure switches.
- Improper low heat gas input adjustment.
- Stuck high heat solenoid in gas valve.
after call, or opens during operation.
Check for: - Plugged condensate drain.
is operating in high heat only mode due to two successive low heat limit trips.
Check for: - Improper or misaligned limit and/or limit shield.
33 LIMIT SWITCH FAULT - Indicates the limit, rollout switch or auxiliary limit switch is open or the unit
—12—
Page 13
- Oxide buildup on flame sensor (clean with fine sandpaper.)
- Main shutoff valve turned "OFF".
320624-101 REV. E
A93305
HUMGRY/Y2W/W1CW2
42 FAULT
SPEED RANGE
=
INDUCER OUTSIDE VALID
(2)
FLASHES
NO. OF
COUNT THE
(4)
FLASHES
NO. OF
COUNT THE
MALFUNCTION
MICROPROCESSOR
RED LED2
RED LED1
- Green wire MUST be connected to furnace sheet metal.
- Proper flame sense microamps (.5 microamps D.C. minimum)
- Inadequate flame carryover or rough ignition.
- Low inlet gas pressure
- Water in vent piping, possibly sagging pipe.
- Improper pressure switch wiring or pressure switch tubing connections.
- Failed or "Out of Calibration" pressure switches.
1
21
OFF
2345678
1
EMER HT.
OFF
SETUP SW,(SW1-8)
FUSE
2
3
1
OFF
COMPONENT TEST
4
3
32
YELLOW
LED3
HIGH HT.
GREEN
LOW HT.
LED4
and control center.
Fig. 15—Service Label
Check for: - Gas valve turned "OFF".
34 IGNITION PROVING FAULT - Control will try three more times before a lockout #14 occurs.
STATUS CODE EXAMPLE
If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the
trouble-shooting guide.
or has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to
the trouble-shooting guide.
during high heat purge are not within the calibration range.
Check for: - Plugged condensate drain.
41 BLOWER OUTSIDE VALID SPEED RANGE - Indicates the blower is not operating at the calculated RPM.
42 INDUCER OUTSIDE VALID SPEED RANGE - Indicates the inducer is not operating at the calculated RPM,
43 PRESSURE SWITCH CALIBRATION FAULT - Indicates the low and high pressure switch "make" points
44 BLOWER CALIBRATION FAULT - Indicates the calculated blower speed is below 250 or above 1300
RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunction with
fault #41 check wiring to motor otherwise refer to the trouble-shooting guide. If this fault occurs by
itself check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.
To initiate the component test sequence, shut "OFF" the room thermostat or disconnect the "R" thermostat
lead. Put setup switch "SW-6" in the "ON" position to start the component test sequence. Once initiated the
main board will turn "ON" the inducer motor-low speed, indu cer motor-high speed, hot surface ignitor, blower
motor-low speed, and blower motor-high speed for 15-20 seconds each. When component test is completed
22 SETUP ERROR - Same as code 22 above.
one or more of the following codes will flash.
CODEDESCRIPTION
11 Indicates inducer and blower motor tested OK. Visual check of hot surface ignitor required.
—13—
wiring and control center.
41 BLOWER OUTSIDE VALID SPEED RANGE - Indicates blower motor failed test. Check blower, wiring,
42 INDUCER OUTSIDE VALID SPEED RANGE - Indicates inducer motor failed test. Check inducer,
To repeat component test turn setup switch "SW-6" "OFF" and then back "ON". After component test is
completed put setup switch "SW-6" in the "OFF" position and reconnect the "R" thermostat lead.
Page 14
A98305
→ Fig. 16—Wiring Diagram
B2
HSI
12
PL9
3
FSE
P
GV
2
EAC2
EAC1
1.5 AMP
M
C
PL7
BLK
WHT
GRN
YEL
BRN
ORN
12104 612
FRSLSALS
RED
BRN
10 11
9
RED
8
PL4
1
GRN
7
BRN
6
ORN
5
YEL
4
3
BLU
2
1
PL1
3
HI
NOTE #3
PL3
5BLU
4YEL
3VIO
2ORN
1RED
5
RED
RED
ORN
VIO
YEL
BLU
WHT
BLK
5
ORN
VIO
YEL
BLU
1
987654321
PL11
PL10
PL12
GRN
#7
1
NOTE
IND.
YEL
12543
PL11
RED
3168
PL13
VIO
YEL
BLU
ORN
6
14
MTR2
Page 15
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your
knowledge of the equipment discussed in this manual, including:
• Unit Familiarization• Maintenance
• Installation Overview• Operating Sequence
A large selection of product, theory, and skills programs is available, using popular
video-based formats and materials. All include video and/or slides, plus companion
book.
Classroom Service Training plus "hands-on" the products in our labs can mean
increased confidence that really pays dividends in faster troubleshooting, fewer
callbacks. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-962-9212
[ ] Packaged Service Training[ ] Classroom Service Training