Bryant A07044, A07045 User Manual

T6--PRH, T6--NRH PREFERREDt SERIES THERMIDISTAT
Installation Instructions
A07045 A07044
Programmable Control Non--- Programmable Control
NOTE: Read the entire instruction manual before starting the installation.
PAGE
SAFETY CONSIDERATIONS 2....................................
INTRODUCTION 3..............................................
INSTALLATION CONSIDERATIONS 4..............................
INSTALLATION 8...............................................
SYSTEM START--UP AND CHECKOUT 40..........................
OPERATIONAL INFORMATION 51................................
TROUBLESHOOTING 54.........................................
WIRING DIAGRAMS 58..........................................
THERMIDISTAT CONFIGURATION RECORD 78.....................
SAFETY CONSIDERATIONS
Read and follow manufacturer instructions carefully. Follow all local electrical codes during installation. All wiring must conform to local and national electrical codes. Improper wiring or installation may damage Thermidistatt Control.
Recognize safety information. This is the safety--alert symbol this symbol on the equipment and in the instruction manual, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING,andCAUTION.These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
. When you see
2
INTRODUCTION
Bryant’s 7--day, 5/2--day, 1--day programmable and non--programmable Preferred Series Thermidistat Control is a wall--mounted, low--voltage control which combines temperature and humidity control in either a single unit or a two--piece unit. In two--piece configuration, the relays are located near the equipment and a two--wire connection is used between the Display Module and the Equipment Control Module. Single--piece installation requires more wiring and results in a higher profile. The Preferred Series Thermidistat has no need for batteries to store user--configured settings in memory. During power loss its internal memory saves settings for unlimited time, and the clock continues to run for at least 24 hours. An extension of Bryant’s proven line of thermostats; it provides separate setpoints for heating and cooling in addition to humidification and dehumidification.
In the Preferred Series Thermidistat Control’s programmable configuration, different heating and cooling setpoints and times are programmable for 4 periods per day or 2 periods per day. Programming can be done for 7 days per week, 5/2 days per week, or 1 day. The programmable Thermidistat Control can also be user configured as a non--programmable Thermidistat Control. When operating as non--programmable, the Thermidistat Control will still have both temperature and humidity control.
The non--programmable Thermidistat Control features Touch ’N’ Got settings for quick and easy temperature change without complicated programming schedules. The non--programmable Thermidistat Control will still have both temperature and humidity control. And, its Touch ’N’ Go technology enables the user to switch between three different user--configurable settings through intuitive buttons located just below the display.
3
INSTALLATION CONSIDERATIONS
Power
This control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and C terminals) of the low--voltage transformer to be connected to it for proper operation. It will not operate without these 2 connections. Rh and Rc are connected via PCB breakout jumper. See Fig. 1. For applications using two 24VAC transformers, one in the indoor unit and one in the outdoor unit, connect the common from each to the C terminal. Connect R from the indoor unit to the Rh terminal. Connect R from the outdoor unit to the Rc terminal. Then, break jumper on the circuit board. The W and HUM signals are taken from the Rh power and the G signal is taken from the Rc power. If Thermidistat Control has been installed in a two--transformer application that is later changed to a single--transformer installation, installer must install a field supplied jumper between Rc and Rh. Depending on the installation, up to 14 wires may be required. Installation as two--piece unit is recommended. Only 2 wires are required for connection between Display Module and Equipment Control Module. These two wires (V+ and Vg) do not provide ordinary 24VAC. They carry a combination of power and communications data that is unique to these products.
4
A07052
Fig. 1 -- PCB Breakout Jumper
Models
There are programmable and non--programmable models for all applications. They can be configured for AC or HP, 1--or 2--speed compressor, and for Hybrid Heatt installations, allowing it to be used in place of all Bryant thermostats. Programmable Thermidistat Controls may be configured as non--programmable if user desires.
Humidify Equipment and Connections
The humidify output connects directly to 24VAC operated humidifiers. No other connection or interlock is required. Any of several installer--selectable operating modes are available.
5
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
DO NOT connect furnace HUM terminal directly to Thermidistat Control HUM terminal. This will bypass furnace safety controls. See Low Voltage Wiring Diagrams and notes for proper connection.
WARNING
Dehumidify Equipment and Connections
The dry contact output connects to the dehumidify input on variable--speed furnaces and fan coils. Additional dehumidification is done by controlling the compressor. A variety of operating modes are available. The dry contact must be configured for dehumidification in setup Option 19. See Wiring Diagrams for more information.
Outdoor Temperature Sensor
Outdoor air temperature sensor is included in the box with the Thermidistat Control. Optimum performance is obtained when an outdoor temperature sensor is used with the Thermidistat Control. Plan installation so that 2 wires can be run from Equipment Control Module to an outdoor location, preferably on the north side of the house or refer to Installation Instructions included with the outdoor temperature sensor for simplified connection. Sensor can be mounted to outdoor unit and existing control wires may be used for its connection. Details are provided in sensor instructions.
6
Remote Indoor Temperature Sensor
A remote temperature sensor may be used with the programmable model, where it is desirable to install the Thermidistat Control in a limited access location while measuring the temperature in the living space. The remote room sensor may be used as a stand alone or average with local sensor.
Two--Piece Thermidistat Configuration
The Preferred Series Thermidistat Control can be installed in one of two configurations. The control may be installed as a single--piece Thermidistat or it may be split into two pieces and mounted in separate locations. As a single--piece unit, all required wiring must be brought to the Equipment Control Module for connection to the terminal strip. In two--piece configuration, the Display Module can be mounted in the living space while the Equipment Control Module may be mounted near the indoor furnace or fan coil. Connection from the display to the Equipment Control Module requires only two wires. All other control wires are connected to the Equipment Control Module from the HVAC equipment. This configuration results in a slimmer display and locates the Equipment Control Module containing the switching relays away from the main living space where relay clicking will not be heard.
7
INSTALLATION
Carton contains the following components. See Fig. 2 for T6--PRH or Fig. 3 for T6-- NRH.
A07752
Fig. 2 -- T6--PRH Carton Contents
1. Display Module
2. Stand--off for Equipment Control Module
3. Outside Air Temperature Sensor, screws and pigtail.
4. Equipment Control Module
8
Fig. 3 -- T6--NRH Carton Contents
1. Display Module
2. Stand--off for Equipment Control Module
3. Outside Air Temperature Sensor, screws and pigtail.
4. Equipment Control Module
Thermidistat Control Location
Thermidistat Control should be mounted:
S Approximately 5 ft (1.5m) from floor. S Close to or in a frequently used room, preferably on an inside parti-
tioning wall.
S On a section of wall without pipes or duct work.
Thermidistat Control should NOT be mounted:
S Close to a window, on an outside wall, or next to a door leading to the
outside.
9
A07753
S Exposed to direct light or heat from a lamp, sun, fireplace, or other
temperature--radiating objects which could cause a false reading.
S Close to or in direct airflow from supply registers and return--air regis-
ters.
S In areas with poor air circulation, such as behind a door or in an al-
cove.
Installer should determine whether control will be installed as single--piece or two--piece. In single-- piece configuration, as many as 14 wires may need to run to wall mounting location for connection to the control. In two--piece configuration, the Display Module and Equipment Control Module are connected by two wires.
Install Ther midistat Control
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing Thermidistat Control, turn off all power to equipment. There may be more than 1 power disconnect.
10
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Improper wiring or installation may damage Thermidistat Control. Check to make sure wiring is correct before proceeding with installation or turning on power.
1. Turn off all power to equipment.
2. If an existing Thermidistat Control is being replaced a. Remove existing control from wall.
b. Disconnect wires from existing control, 1 at a time.
c. As each wire is disconnected, record wire color and terminal marking.
d. New or additional wire may be needed to accommodate added hu-
midity outputs.
e. Discard or recycle old control.
11
!
CAUTION
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental damage.
Mercury is a hazardous waste. Federal regulations require that Mercury be disposed of properly.
Two--Piece Installation
The following steps should be followed for the installation of the two--piece configuration.
NOTE: The 2--wire pigtail is not intended to support the weight of the User Interface. Do not hang the User Interface from the Equipment Control Module screw terminals.
1. Remove mounting plate from back of Display Module by pressing the two tabs on the bottom edge and pulling away. See Fig. 4 and 5.
12
Fig. 4 -- Press Tabs to Remove Backplate
Fig. 5 -- Take Apart
13
A07225
A07226
2. Route wires through large hole in mounting base. Level mounting base against wall (for aesthetic value only—Display Module need not be lev­eled for proper operation) and mark wall through 2 mounting holes. See Fig. 6.
A07165
Fig. 6 -- Backplate Mounting
3. Drill two 3/16--in. mounting holes in wall where marked. Thermidistat may be mounted to a standard junction box, if desired. Hole pattern on Thermidistat Control mounting base matches junction box mounting holes.
4. Secure rear plastic mounting base to wall with 2 screws and anchors pro­vided. Additional mounting holes are available for more secure mounting if needed. Make sure all wires extend through hole in mounting base.
5. Adjust length and routing of each wire to reach proper connector block and terminal on mounting base with 1/4-- in. extra wire.
14
6. Match and connect equipment wires to proper terminals of each connector block, being careful not to over tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the Thermidistat Control mounting base. If wires are con­nected incorrectly, the Display Module will not operate. See Fig. 7, 8 and
9.
OAT /
OAT / RRS
RRS return
return
dry
dry contact
contact
connect
connect to user
to user interface
interface
{
{
SRTN
SRTN
Control Module Wiring Guide
Control Module Wiring Guide
OAT
OAT
RRS
RRS
HUM
HUM
D1
D1 D2
D2
V+
V+ Vg
Vg
Rc
Rc
Rh
Rh
W / W1
W / W1 G
G Y/Y2
Y/Y2
C
C
O/W2/B
O/W2/B Y1
Y1
Y1 used for
Y1 used for multi-speed
multi-speed cooling
cooling Y1 = stage 1
Y1 = stage 1 Y2 = stage 2
Y2 = stage 2
Relays
Relays
Y used for
Y used for single stage
single stage cooling
cooling
Fig. 7 -- Control Module Wiring Guide
S Red is V+
S Black is Vg
A07687
15
Fig. 8 -- Secure Wires to Terminal Strip
Fig. 9 -- Connect Pigtail Wires to Display Module
16
A07166
A07167
NOTE: The 2--wire pigtail is not intended to support the weight of the User Interface. Do not hang the User Interface from the Equipment Control Module screw terminals.
S Red of the pigtail is V+
S Black of the pigtail is Vg
7. Push any excess wire into wall and against mounting base. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incorrect temperature and/or humidity measurement.
8. Make sure 2--wire pigtail is attached to Display Module mounting base. This should come attached from the factory. Attach two--wire pigtail to the back of the Display Module via 2 pin, keyed connector.
9. Reattach Display Module body to mounting base by first setting on at top of mounting base and then push bottom corners of Display Module to snap into place. See Fig. 10.
A07169
Fig. 10 -- Attach Display to Backplate
17
10. Find suitable indoor mounting location for Equipment Control Module, either near or on equipment. See Fig. 11.
IMPORTANT NOTE: Equipment Control Module should not be mounted to duct work or below any other controls or equipment (i.e. humidistat, humidifier, etc.).
A07217
Fig. 11 -- Equipment Control Module on Equipment
11. Route wires through rear of Equipment Control Module using either a clearance hole or supplied standoff. See Fig. 12.
18
A07227
Fig. 12 -- Standoff
12. Match and connect equipment wires to proper terminals of each connector block being careful not to over tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the Thermidistat Control mounting base. If wires are con­nected incorrectly, the Display Module will not operate. See Fig. 7, 8 and
9.
13. Snap cover over top of Equipment Control Module. See Fig. 13.
19
A07218
Fig. 13 -- Cover on Equipment Control Module
14. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2--digit code appears on large display which identifies Thermidistat Control configuration. Refer to Option 33.
a. AC — 1--stage air conditioner
b. HP — 1--stage heat pump
c. A2 — 2-- stage air conditioner
d. H2 — 2--stage heat pump
e. hh — Hybrid Heat system with 1--stage heat pump
f. h2 — Hybrid Heat system with 2--stage heat pump g. H — heating only system
h. C — cooling only system
20
Single--Piece Installation
The following steps should be followed for the installation of the single--piece configuration.
1. Remove cover from Equipment Control Module by pressing the two tabs on the bottom edge and pulling away. Route wires through large hole in Equipment Control Module. Level Equipment Control Module against wall (for aesthetic value only -- Equipment Control Module need not be leveled for proper operation) and mark wall through 2 mounting holes.
2. Drill two 3/16--in. mounting holes in wall where marked. Thermidistat Control may be mounted to a standard junction box if desired. Hole pat­tern on Equipment Control Module matches junction box mounting holes.
3. Secure rear plastic Equipment Control Module to wall with 2 screws and anchors provided. Additional mounting holes are available for more se­cure mounting if needed. Make sure all wires extend through hole in Equipment Control Module.
4. Adjust length and routing of each wire to reach proper connector block and terminal on Equipment Control Module with 1/4--in. extra length. See Fig. 14.
21
A07219
Fig. 14 -- Equipment Control Module
5. Match and connect equipment wires to proper terminals of each connector block.
6. Push any excess wire into wall and against Equipment Control Module. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incorrect temperature and/or humidity measurement.
7. Remove 2-- wire pigtail from Thermidistat Control mounting base and at­tach to Equipment Control Module terminal block (terminals V+ and Vg). Attach two-- wire pigtail to the back of the Display Module via 2 pin, keyed connector.
8. Reattach Display Module body to Equipment Control Module by first setting on at top and then push bottom corners to snap into place. See Fig.
15.
22
A07221
Fig. 15 -- Reattach Display Module
9. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2--digit code appears on large display which identifies Thermidistat Control configuration. Refer to Option 33.
a. AC — 1--stage air conditioner
b. HP — 1--stage heat pump
c. A2 — 2-- stage air conditioner
d. H2 — 2--stage heat pump
e. hh — Hybrid Heat system with 1--stage heat pump
f. h2 — Hybrid Heat system with 2--stage heat pump g. H — heating only system
h. C — cooling only system
23
Set Thermidistat Control Configuration
Configuration options enable the installer to configure the Thermidistat Control for a particular installation. Most are not presented to the homeowner and therefore must be properly set by the installer. (Only those marked with an asterisk * below are available to the homeowner.) The homeowner configurations are described in the owner’s manual. A special procedure allows entry into the configuration mode. While in configuration mode, up to 33 selections can be made. Description of each selection and how to use the configuration mode follows.
CONFIGURATION OPTIONS -- SUMMARY
Option 01 — Equipment Type Option 02 — Clean Filter Timer Adjustment
Option 03* — Fahrenheit/Centigrade Selection Option 04 — Fan (G) on with W/W1 Selection Option 05 — Room Air Temperature Sensing (programmable
models only)
Option 06 — Cooling Lockout Below 55_F Selection (only
available if outdoor air sensor is present) Option 07 — Zoning
Option 08 — Auxiliary Heat Lockout Temperature Setting (only
available when heat pump is used and when
outdoor air temperature sensor is present)
Option 09 — Heat Pump Lockout Temperature Option 10 — Reversing Valve
24
Loading...
+ 56 hidden pages