Bryant 302B, 602B060, 602B048, 602B042, 602B036 Installation, Start-up And Service Instructions Manual

...
Installation, Start-Up, and Service Instructions
SINGLE-PACKAGE HEAT PUMP UNITS WITH PURON (R-410A) REFRIGERANT
NOTE: Read the entire instruction manual before starting the installation.
This symbol indicates a change since the last issue.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS.....................................................1
Introduction ....................................................................................2
Receiving and Installation..............................................................2
Check Equipment......................................................................2
Provide Clearances....................................................................2
Rig and Place Unit....................................................................2
Select and Install Ductwork .....................................................5
Provide for Condensate Disposal.............................................6
Install Electrical Connections...................................................7
PRE-START-UP ..........................................................................10
START-UP...................................................................................12
Check for Refrigerant Leaks..................................................12
Start-Up Adjustments..............................................................12
Defrost Control .......................................................................19
MAINTENANCE.........................................................................20
Air Filter..................................................................................22
Indoor Blower and Motor.......................................................22
Outdoor Coil, Indoor Coil, and Condensate Drain Pan........22
Outdoor Fan............................................................................22
Electrical Controls and Wiring...............................................22
Refrigerant Circuit..................................................................22
Indoor Airflow........................................................................23
Metering Devices–Accurater Piston.......................................23
Pressure Switches....................................................................23
Loss of Charge Switch ...........................................................23
High-Pressure Switch..............................................................23
Copeland Scroll Compressor (Puron Refrigerant).................23
Refrigerant System..................................................................23
System Information.................................................................24
TROUBLESHOOTING ...............................................................24
Start-Up Checklist........................................................................24
NOTE TO INSTALLER — READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY before installing this unit. Also, make sure the Owner’s Manual and Service Instructions are left with the unit after installation.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags, and labels attached to the unit, and other safety precautions that may apply.
602B
Cancels: II 602B-24-1 II 602B-24-2
12-00
C99063
Fig. 1—Unit 602B
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
WARNING: Improper installation, adjustment, alter­ation, service, maintenance, or use can cause explosion, fire, electric shock, or other occurrences, which could cause serious injury or death or damage your property. Consult a qualified installer or service agency for infor­mation or assistance. The qualified installer or agency must use only factory-authorized kits or accessories when modifying this product.
Recognize safety information. This is the safety-alert symbol . When you see this symbol on the product or in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words — DANGER, WARNING, CAU­TION, and NOTE. Danger identifies the most serious hazards, which will result in severe personal injury or death. Warning indicates a condition that could cause serious personal injury or death. Caution is used to identify unsafe practices, which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
1. The power supply (volts, phase, and hertz) must correspond to that specified on unit rating plate.
2. The electrical supply provided by the utility must be sufficient to handle load imposed by this unit.
—1—
3. This installation must conform with local building codes and with NEC (National Electrical Code). Refer to provin­cial and local plumbing or waste water codes and other applicable local codes.
WARNING: Before performing service or maintenance operations on system, turn off main power to unit. Turn off accessory heater power switch if applicable. Electrical shock could cause severe injury or death.
CAUTION: Puron (R-410A) systems operate at higher pressures than standard R-22 systems. DO not use R-22 service equipment or components on Puron (R-410A) equipment. Ensure service equipment is rated for Puron (R-410A)
INTRODUCTION
The 602B heat pump is fully self-contained and designed for outdoor installation. (See Fig. 1) Standard units are shipped in a horizontal-discharge configuration for installation on a ground­level slab. Standard units can be converted to downflow (vertical) discharge configurations for rooftop applications.
RECEIVING AND INSTALLATION
I. CHECK EQUIPMENT A. IDENTIFY UNIT
The unit model number and serial number are stamped on the unit identification plate. Check this information against shipping pa­pers.
B. INSPECT SHIPMENT
Inspect for shipping damage while unit is still on shipping pallet. If unit appears to be damaged or is torn loose from its anchorage, have it examined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manu­facturer is not responsible for any damage incurred in transit. Check all items against shipping list. Immediately notify the nearest Bryant Air Conditioning office if any item is missing. To prevent loss or damage, leave all parts in original packages until installation.
II. PROVIDE UNIT SUPPORT A. ROOF CURB
Install accessory roof curb in accordance with instructions shipped with curb. (See Fig. 5) Install insulation, cant strips, roofing, and flashing. Ductwork must be attached to curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasketing material supplied with the roof curb. Improperly applied gasketing also can result in air leaks and poor unit performance.
Curb should be level to within 1/4 in. (See Fig. 6) This is necessary for unit drain to function properly. Refer to accessory roof curb installation instructions for additional information as required.
B. SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of 4 in. thick with 2 in. above grade. (See Fig. 7) The slab should extend approximately 2 in. beyond the casing on all 4 sides of the unit. Do not secure the unit to the slab except when required by local codes.
C. GROUND MOUNT
The unit may be installed either on a slab or placed directly on the ground if local codes permit. Place the unit on level ground prepared with gravel for condensate discharge.
III. PROVIDE CLEARANCES
The required minimum service clearances are shown in Figs. 2 and
3. Adequate ventilation and outdoor air must be provided. The outdoor fan draws air through the outdoor coil and discharges it through the top fan grill. Be sure that the fan discharge does not recirculate to the outdoor coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48 in. above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 in.
IMPORTANT: Do not restrict outdoor airflow. An air restriction at either the outdoor-air inlet or the fan discharge may be detrimental to compressor life.
Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install the unit on carpeting or other combustible materials. Slab-mounted units should be at least 4 in. above the highest expected water and runoff levels. Do not use unit if it has been under water.
IV. RIG AND PLACE UNIT
Rigging and handling of this equipment can be hazardous for many reasons due to the installation location (roofs, elevated structures, etc.)
Only trained, qualified crane operators and ground support staff should handle and install this equipment.
When working with this equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equipment, and any other safety precautions that might apply.
Follow all applicable safety codes. Wear safety shoes and work gloves.
A. INSPECTION
Prior to initial use, and at monthly intervals, all rigging brackets and straps should be visually inspected for any damage, evidence of wear, structural deformation, or cracks. Particular attention should be paid to excessive wear at hoist hooking points and load support areas. Brackets or straps showing any kind of wear in these areas must not be used and should be discarded.
B. INSTALLATION
1. Remove unit from shipping carton. Leave top shipping skid on the unit as a spreader bar to prevent the rigging straps from damaging the unit. If the wood skid is not available, use a spreader bar of sufficient length to protect unit from damage.
2. Position the lifting bracket assembly around the base of the unit. Be sure the strap does not twist.
3. Place each of the 4 metal lifting brackets into the handholds in the composite pan.
4. Thread lifting bracket strapping around bottom perimeter of unit as follows:
a. Open lever of tension buckle (ratchet type). b. Feed strapping through tension buckle as shown in Fig.
8. c. Pull strapping through tension buckle unit taut. d. Snap lever down to lock strap in tension buckle. To
release strapping, squeeze safety latch, lift lever, and pull webbing outward.
5. Tighten the tension buckle until it is taut. Lifting brackets must be secure in the handholds.
6. Attach field-supplied clevis or hook of sufficient strength to hole in the lifting bracket. (See Fig. 9)
7. Attach the 2 safety straps directly to the clevis or hook at the 4 rigging brackets. DO NOT attach the safety straps to the lifting brackets. (See Fig. 9)
2
UNIT ELECTRICAL CHARACTERISTICS
602B024 208/230-1-60 299 135.6 35.02 (889.5) 19.0 (482.6) 18.3 (463.6) 16.0 (406.4) 602B030 208/230-1-60,208/230-3-60 320 145.2 37.02 (940.3) 20.0 (508.0) 19.3 (489.0) 17.6 (447.0) 602B036 208/230-1-60,208/230-3-60, 460-3-60 328 148.8 37.02 (940.3) 20.0 (508.0) 19.0 (482.6) 16.5 (419.1)
UNIT WEIGHT
lb kg X Y Z
UNIT HEIGHT
IN. (MM)
A
Fig. 2602B024-036 Unit Dimensions
3
C00160
CENTER OF GRAVITY
IN. (MM)
UNIT ELECTRICAL CHARACTERISTICS
602B042 208/230-1-60, 208/230-3-60, 460-3-60 350 158.8 40.98 (1040.9) 21.0 (533.4) 20.5 (520.7) 16.6 (421.6) 602B048 208/230-1-60, 208/230-3-60, 460-3-60 355 161.0 40.98 (1040.9) 20.0 (508.0) 21.3 (539.8) 18.0 (457.2) 602B060 208/230-1-60, 208/230-3-60, 460-3-60 428 194.1 42.98 (1091.7) 21.0 (533.4) 20.0 (508.0) 17.6 (447.0)
UNIT WEIGHT
lb kg X Y Z
UNIT HEIGHT
IN. (MM)
A
Fig. 3602B 042-060 Unit Dimensions
4
C00161
CENTER OF GRAVITY
IN. (MM)
12
y
43
CORNER WEIGHTS (SMALL CABINET) CORNER WEIGHTS (LARGE CABINET)
Unit 24 30 36
Total Weight 299 320 328 Total Weight 350 355 428 Corner Weight 1 63 63 64 Corner Weight 1 75 76 92 Corner Weight 2 62 74 76 Corner Weight 2 49 50 60
Model 602B
8. Position lifting point directly over the units center of
9. Lift unit. When unit is directly over the roof curb, remove
10. After the unit is placed on the roofcurb or mounting pad,
V. SELECT AND INSTALL DUCTWORK
The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of non-residence type air conditioning and ventilating systems, NFPA 90A or residence-type, NFPA 90B and/or local codes and ordi­nances. Select and size ductwork, supply-air registers, and return air grilles according to ASHRAE (American Society of Heating, Refrigera­tion, and Air Conditioning Engineers) recommendations. The unit has duct flanges on the supply- and return-air openings on the side of the unit. When designing and installing ductwork, consider the following:
Corner Weight 3 56 56 58 Corner Weight 3 95 96 116 Corner Weight 4 118 127 130 Corner Weight 4 131 133 160
gravity.
the 2 safety straps. Lower the equipment onto the roof curb.
remove the top crating. On 602B060 units only, 2 wire ties fastened to the outdoor coils and reversing valve/accumulator assembly must be cut. Remove the left and front louver panels and corner post to access wire ties. The wire tie to be cut on the left is located approximately 4 in. down the tube sheet. The wire tie to be cut on the right is located approximately 6 in. down the tube sheet.
WARNING: For vertical supply and return units, tools or parts could drop into ductwork and cause serious injury or death. Install a 90 degree turn in the return ductwork between the unit and the conditioned space. If a 90 degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space. Units with electric heaters require 90 degree elbow in supply duct.
x
Model 602B
Fig. 4Corner Weights
2. Avoid abrupt duct size increases and reductions. Abrupt
IMPORTANT: Use flexible connectors between ductwork and unit to prevent transmission of vibration. Use suitable gaskets to ensure weather tight and airtight seal. When electric heat is installed, use fireproof canvas (or similar heat resistant material) connector between ductwork and unit discharge connection. If flexible duct is used, insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve) must extend 24-in. from electric heater element.
3. Size ductwork for cooling air quantity (cfm). The minimum
4. Seal, insulate, and weatherproof all external ductwork. Seal,
5. Secure all ducts to building structure. Flash, weatherproof,
A. CONVERTING HORIZONTAL DISCHARGE UNITS TO DOWNFLOW (VERTICAL) DISCHARGE UNITS
C00071
Unit 42 48 60
change in duct size adversely affects air performance.
air quantity for proper electric heater operation is listed in Table 2. Heater limit switches may trip at air quantities below those recommended.
insulate and cover with a vapor barrier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors Association (ACCA) minimum installation standards for residential heating and air conditioning systems.
and vibration-isolate duct openings in wall or roof accord­ing to good construction practices.
WARNING: Before performing service or maintenance operations on system, turn off main power to unit. Turn off accessory heater power switch if applicable. Electrical shock could cause serious injury or death.
1. All units should have field-supplied filters or accessory filter rack installed in the return-air side of the unit. Recommended sizes for filters are shown in Table 1.
1. Open all electrical disconnects before starting any service work.
2. Remove horizontal duct covers to access bottom return and supply knock out panels.
5
HVAC unit
Screw
(NOTE A)
*Gasketing
outer flange
Flashing field
supplied
Roofing material
field supplied
Cant strip
field supplied
base
Gasketing
inner flange*
Wood nailer*
Roofcurb*
Insulation (field
supplied)
Duct work
field supplied
HVAC unit
Screw
(NOTE A)
*Gasketing
outer flange
Flashing field
supplied
Roofing material
field supplied
Cant strip
field supplied
base
Gasketing
inner flange*
Duct work
field supplied
Wood nailer*
Roofcurb*
Insulation (field
supplied)
Roof
*Provided with roofcurb
Roof Curb for Small Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used.
Supply opening (B x C)
5
44
/16"
B Typ .
C Typ .
*Provided with roofcurb
Roof Curb for Large Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used.
D
R/A
A
Gasket around
Roof
S/A
duct
Short
Insulated deck pan
Return opening
(B X C)
UNIT SIZE ODS CATALOG NUMBER
602B024-036
602B042-060
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Dimensions in ( ) are in millimeters.
4. Roof curb is made of 16-gage steel.
5. Table lists only the dimensions, per part number, that have changed.
6. Attach ductwork to curb (flanges of duct rest on curb).
7. Insulated panels: 1-in. thick fiberglass 1 lb. density.
8. Dimensions are in inches.
9. When unit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane or seismic conditions. This bracket is available through Micrometl.
CPRFCURB006A00 8 (203) 11(279) 161/2 (419) 28-3/4 (730) CPRFCURB007A00 14 (356) 11(279) 161/2 (419) 28-3/4 (730) CPRFCURB008A00 8 (203) 16 3/16 (411) 17 3/8 (441) 40-1/4 (1022) CPRFCURB009A00 14 (356) 16 3/16 (411) 17 3/8 (441) 40-1/4 (1022)
Support
Long
Support
A
IN. (MM)
Fig. 5Roof Curb Dimensions
3. Use a screwdriver and hammer to remove the panels in the bottom of the base pan.
NOTE: These panels are held in place with tabs similar to an electrical knockout.
4. Reinstall the horizontal duct covers (Fig. 11) to block off the horizontal air openings.
NOTE: Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air performance.
Insulated deck pan
B
IN. (MM)
Gasket around
outer edge
IN. (MM)
C
D
IN. (MM)
VI. PROVIDE FOR CONDENSATE DISPOSAL NOTE: Ensure that condensate-water disposal methods comply
with local codes, restrictions, and practices. The 602B units dispose of condensate through a 3/4 in. NPT
female fitting that exits on the compressor end of the unit. Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground level installations. Install a field-supplied condensate trap at end of
C00076
6
OPTIONAL
RETURN
A
B
Fig. 6Unit Leveling Tolerances
C
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
1/4 1/4 1/4
C99065
2"
AIR
OPENING
OPTIONAL
SUPPLY
AIR
OPENING
condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. lower than the drain-pan condensate connection to prevent the pan from overflowing. Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit.
If the installation requires draining the condensate water away from the unit, install a field-supplied 2 -in. trap at the condensate connection to ensure proper drainage. Condensate trap is available as an accessory or is field-supplied. Make sure that the outlet of the trap is at least 1 in. lower than the unit drain-pan condensate connection to prevent the pan from overflowing. Connect a drain trough using a minimum of field-supplied 3/4-in. PVC or field­supplied 3/4-in. copper pipe at outlet end of the 2-in. trap. (See Fig.
12) Do not undersize the tube. Pitch the drain trough downward at a slope of at least 1 in. every 10 ft. of horizontal run. Be sure to check the drain trough for leaks. Prime the trap at the beginning of the cooling season start-up.
VII. INSTALL ELECTRICAL CONNECTIONS
WARNING: The unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the pos­sibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground lug in the control compart­ment, or conduit approved for electrical ground when installed in accordance with NEC, ANSI/NFPA Ameri­can National Standards Institute/National Fire Protection Association (latest edition) (in Canada, Canadian Electri­cal Code CSA C22.1) and local electrical codes. Failure to adhere to this warning could result in serious injury or death.
EVAP. COIL COND. COIL
Fig. 7Slab Mounting Detail
HANDHOLD
HOOK
FEED
Fig. 8Threading Belt
“A”
“B”
914-137" (36"-54")
SCALE 0.250
TIGHTEN STRAPPING SECURELY WITH TENSION BUCKLE
C99096
C99067
DETAIL A
7
INSTALL SAFETY STRAPS TO RIGGING CLEVIS AT 4 RIGGING BRACKETS
PLACE RIGGING BRACKET ASSEMBLY IN 4 HAND HOLES AND INSTALL TIE DOWN STRAP AROUND PERIMETER OF UNIT AND THROUGH
SEE DETAIL A
SPACE IN BRACKET ASSEMBLY
C99075
UNIT MAXIMUM WEIGHT A B
Size lb kg in. mm. in. mm. 602B024 321 145.6 19.0 482.6 18.25 463.6 602B030 342 155.2 20.0 508 19.25 489 602B036 350 158.8 20.0 508 19.0 482.6 602B042 372 168.8 21.0 533.4 20.5 520.7 602B048 377 171.0 20.0 508 21.25 539.8 602B060 450 204.2 21.0 533.4 20.0 508.0
Fig. 9Suggested Rigging
TABLE 1PHYSICAL DATAUNIT 602B
UNIT SIZE 602B024 602B030 602B036 602B042 602B048 602B060
NOMINAL CAPACITY (ton) 2 2-1/2 3 3-1/2 4 5
OPERATING WEIGHT (lb.) 299 320 328 350 355 428
COMPRESSOR QUANTITY 1
TYPE SCROLL COMPRESSOR
REFRIGERANT R-410A
REFRIGERANT METERING DEVICE Accurater
Refrigerant (R-410A) Quantity (lb.) 7.0 8.9 9.3 9.5 10.6 12.4
ORIFICE ID (in.) 0.061 0.061 0.067 0.073 0.076 0.088
ORIFICE OD (in.) 0.032 (2) 0.040 (2) 0.040 (2) 0.038 (2) 0.046 (2) 0.052 (2)
OUTDOOR COIL
Rows... Fins/in.
face area (sq. ft.)
OUTDOOR FAN
Nominal Airflow (CFM)
Diameter
Motor HP (RPM)
INDOOR COIL
Rows... Fins/in.
face area (sq. ft.)
INDOOR BLOWER
Nominal Airflow (CFM)
Size (in.)
Motor (HP)
HIGH-PRESSURE SWITCH (psig)
LOSS-OF-CHARGE/LOW-PRESSURE SWITCH
RETURN-AIR FILTERS (in.)*
* Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throwaway type or 450 ft/minute for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg.
Cutout
Reset (Auto)
(Liquid Line) (psig)
Cutout
Reset (Auto)
throwaway
2...17
8.5
2350
22
1/8 (825)
3...15
3.7
800
10x10
1/4
20x20x1 20x20x1 20x24x1 24x30x1 24x30x1 24x30x1
2...17
10.3
2350
22
1/8 (825)
3...15
3.7
1000
10x10
1/4
2...17
10.3
2800
22
1/4 (1100)
4...15
3.7
1200
10x10
1/2
1/8 (825)
610±15 420±25
20±5
45±10
2...17
13.5
2500
22
3...15
4.7
1400
11x10
1/2
2...17
13.5
3300
22
1/4 (1100)
4...15
4.7
1600
11x10
1/2
2...17
15.4
3300
22
1/4 (1100)
4...15
5.7
1750
11x10
1
TABLE 2MINIMUM AIRFLOW FOR RELIABLE ELECTRIC HEATER OPERATION (CFM)
SIZE 602B024 602B030 602B036 602B042 602B048 602B060
AIRFLOW (CFM) 800 1000* 1200 1400 1600 2000
* The 030 size models must be run on medium or high speed when used in conjunction with 15 kw electric heat accessory
A. HIGH-VOLTAGE CONNECTIONS
CAUTION: Failure to follow these precautions could
result in damage to the unit being installed:
1. Make all electrical connections in accordance with NEC ANSI/NFPA (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between field-supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within operating voltage range indicated on unit rating plate. On 3-phase units, ensure phases are balanced within 2 percent. Consult local power company for correction of improper voltage and/or phase imbalance.
4. Insulate low-voltage wires for highest voltage con­tained within conduit when low-voltage control wires are in same conduit as high-voltage wires.
5. Do not damage internal components when drilling through any panel to mount electrical hardware, con­duit, etc.
The unit must have a separate electrical service with a field­supplied, waterproof disconnect switch mounted at, or within sight from the unit. Refer to the unit rating plate, NEC and local codes for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing (See Table 3 for electrical data).
The field-supplied disconnect may be mounted on the unit over the high-voltage inlet hole (See Figs. 2 and 3).
If the unit has an electric heater, a second disconnect may be required. Consult the Installation, Start-Up, and Service Instruc­tions provided with the accessory for electrical service connec­tions.
Operation of unit on improper line voltage constitutes abuse and may cause unit damage that could affect warranty.
B. ROUTING POWER LEADS INTO UNIT
Use only copper wire between disconnect and unit. The high­voltage leads should be in a conduit until they enter the duct panel; conduit termination at the duct panel must be watertight. Run the high-voltage leads through the power entry knockout on the power entry side panel. (See Fig. 2 and 3 for location and size) When the leads are inside the unit, run leads up the high-voltage raceway to the line wiring splice box. (See Fig. 13 through 15) For single-
8
RETURN AIR
INDOOR THERMOSTAT
TOP COVER
FROM POWER SOURCE
DISCONNECT PER NEC*
*NEC - NATIONAL ELECTRICAL CODE
C00063
Fig. 10Typical Installation
1 MIN.
TRAP OUTLET
2 MIN.
Duct Covers
C00092
phase units, connect leads to the black and yellow wires; for
Fig. 11602B with Duct Covers On
3-phase units, connect the leads to the black, yellow, and blue wires. (See Fig. 18)
C. CONNECTING GROUND LEAD TO GROUND LUG
Refer to Fig. 18. Connect the ground lead to the chassis using the ground lug in the wiring splice box.
D. ROUTING CONTROL POWER WIRES (24-V)
Form a drip-loop with the thermostat leads before routing them into the unit. Route the thermostat leads through grommeted, low-voltage hole provided in unit into unit control power splice box. (See Fig. 2 and 3) Connect thermostat leads to unit control power leads as shown in Fig. 17.
C99013
Fig. 12Condensate Trap
The unit transformer supplies 24-v power for complete system including accessory electrical heater. An automatic-reset circuit breaker (See Fig. 19) is provided in the 24-v circuit; see the caution label on the transformer or Fig. 20. Transformer is factory wired for 230-v operation. If supply voltage is 208-v, rewire transformer primary as described in Special Procedures for 208-v Operation section.
E. SPECIAL PROCEDURES FOR 208-V OPERATION
1. Be sure unit disconnect switch is open.
2. Disconnect the yellow primary lead (w 110) from the transformer. See unit wiring label. (See Fig. 13 and 14)
3. Connect the yellow primary lead (w110) to the transformer terminal labeled 200-v.
Indoor blower-motor speeds may need to be changed for 208-v operation. Refer to indoor airflow and airflow adjustments section.
9
Loading...
+ 19 hidden pages