Bryant 597C User Manual

installation and start-up instructions
12 SEER SPLIT-SYSTEM AIR CONDITIONER
NOTE: Read the entire instruction manual before starting the installation.
This symbol indicates a change since the last issue.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thor­oughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU­TION. These words are used with the safety-alert symbol. DAN­GER identifies the most serious hazards which willresultinsevere personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING: Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label. Electrical shock can cause personal injury or death.
INTRODUCTION AND RECOMMENDATIONS
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where unit operation sounds may disturb customer.
2. Ensure that vapor- and liquid-tube diametersareappropriate to capacity of unit.
3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb vibration.
5. When passing refrigerant tubes through the wall, seal opening with RTV or other pliable silicon-based caulk. (See Fig. 2.)
597C
Cancels: II 597C-18-4 II 597C-18-5
11-00
.
A98515
Fig. 1—Model 597C
6. Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap that comes in direct contact with tubing. (See Fig. 2.)
8. Ensure that tubing insulation is pliable and completely surrounds vapor tube.
9. When necessary, use hanger straps which are 1 in. wide and conform to shape of tubing insulation. (See Fig. 2.)
10. Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation.
When outdoor unit is connected to factory-approved indoor unit, outdoor unit contains system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft of field-supplied or factory-accessory tubing. For proper unit opera­tion, check refrigerant charge using charging information located on control-box cover.
IMPORTANT: Maximum liquid-line size is 3/8-in. O.D. for all residential applications including long line.
IMPORTANT: Always install a liquid-line filter drier on any system using an existing field service lineset and/or indoor evaporator coil or fan coil. Also, always use liquid line filter driers on burnout compressor replacements. Refer to Product Data Sheets for appropriate part number. Obtain filter driers from your local distributor or branch.
INSTALLATION
I. CHECK EQUIPMENT AND JOB SITE A. Unpack Unit
Move to final location. Remove carton, taking care not to damage unit.
—1—
Avoid contact between tubing and structureNOTE:
OUTDOOR WALL INDOOR WALL
CAULK
INSULATION
THROUGH THE WALL
HANGER STRAP
(AROUND VAPOR
TUBE ONLY)
1 MIN.
SUSPENSION
LIQUID TUBE
VAPOR TUBE
JOIST
INSULATION
VAPOR TUBE
LIQUID TUBE
A94028
Fig. 2Connecting Tubing Installation
B. Inspect Equipment
File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit-rating plate on unit-corner panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications.
II. INSTALL ON A SOLID, LEVEL MOUNTING PAD
If conditions or local codes require the unit be attached to pad, tie-down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit-mounting pattern in Fig. 3 to determine base-pan size and knockout-hole location.
On rooftop applications, mount on level platform or frame. Place unit above a load-bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.
Roof-mounted units exposed to winds above 5 mph may require wind baffles to achieve adequate defrost. Consult Low-Ambient Guideline for wind-baffle construction.
NOTE: Unit must be level to within ± 2° (± 3/8 in./ft) per compressor manufacturer specifications.
III. CLEARANCE REQUIREMENTS
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 30-in. clearance to service end of unit and 48 in. above unit. For proper airflow, a 6-in. clearance on 1 side of unit and 12 in. on all remaining sides must be maintained. Maintain a distance of 24 in. between units. Position so water, snow, or ice from roof or eaves cannot fall directly on unit.
On rooftop applications, locate unit at least 6 in. above roof surface.
IV. OPERATING AMBIENTS
The minimum outdoor-operating ambient in cooling mode is 55°F, and the maximum outdoor-operating ambient in cooling mode is 125°F.
A
C
L
B
3
8 IN. DIA TIEDOWN
KNOCKOUTS
(2) PLACES
IN BASEPAN
DIMENSIONS (IN.)
UNIT SIZE
018 20 x 27 4–1/8 7–1/8
024–060 26 x 32 5–1/16 9-11/16
MINIMUM
MOUNTING-PAD
DIMENSIONS
TIEDOWN KNOCKOUT LOCATIONS
Fig. 3Mounting Unit to Pad
V. CHECK INDOOR CHECK-FLO-RATERPISTON
Check indoor-coil piston to see if it matches the required piston shown on outdoor unit-rating plate. If it does not match, replace indoor-coil piston with piston shipped with outdoor unit. The piston shipped with outdoor unit is correct for any approved indoor-coil combination.
CAUTION: Remove indoor-coil piston if unit is to be installed on system with a TXV-metering device.
VI. MAKE PIPING CONNECTIONS
WARNING: Relieve pressure and recover all refrigerant
before system repair or final unit disposal to avoid personal injury or death. Use all service ports and open all flow-control devices, including solenoid valves.
CAUTION: If ANY refrigerant tubing is buried, pro­vide a 6-in. vertical rise at service valve. Refrigerant­tubing lengths up to 36 in. may be buried without further consideration. For lengths above 36 in., consult your local distributor.
CAUTION: To prevent damage to unit or service valves observe the following:
Use a brazing shield.
Wrap service valves with wet cloth or use a heat sink
material.
Outdoor units may be connected to indoor unit using accessory­tubing package or field-supplied refrigerant-grade tubing of cor­rect size and condition. For tubing requirements beyond 50 ft, substantial capacity and performance losses can occur. Following the recommendations in the Residential Split-System Long-Line Application Guideline will reduce these losses. Refer to Table 1 for field-tubing equivalent-line length. Refer to Table 2 for accessory requirements.
8 3⁄16
A97375
AB
2
TABLE 1REFRIGERANT CONNECTIONS AND RECOMMENDED LIQUID- AND VAPOR-TUBE DIAMETERS (IN.)
UNIT SIZE
018, 024 3/8 3/8 5/8 5/8 5/8 3/4 030, 036 3/8 3/8 3/4 3/4 3/4 7/8 042, 048 3/8 3/8 7/8 7/8 7/8 1–1/8
060 3/8 3/8 7/8 1–1/8 7/8 1–1/8
NOTES:
1. Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult Residential Long-Line Application Guideline.
2. Do not apply capillary-tube indoor coils to these units.
Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter
LIQUID VAPOR VAPOR (LONG LINE)
For buried-line applications greater than 36 in., consult your local distributor.
If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.
A. Outdoor Unit Connected to Factory-Approved In­door Unit
Outdoor unit contains correct system-refrigerant charge for opera­tion with indoor unit of same size when connected by 15 ft of field-supplied or factory-accessory tubing. Check refrigerant charge for maximum efficiency.
B. Refrigerant Tubing
Connect tubing to fittings on outdoor unit vapor- and liquid­service valves. (See Table 1.) Use refrigerant-grade tubing.
C. Sweat Connection
CAUTION: To avoid valve damage while brazing, ser-
vice valves must be wrapped in a heat-sinking material, such as a wet cloth.
Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, tubing set can be brazed to service valve using either silver-bearing or non-silver-bearing brazing material. Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.
VII. MAKE ELECTRICAL CONNECTIONS
WARNING: To avoid personal injury or death, do not
supply power to unit with compressor terminal-box cover removed.
Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit-rating plate. Contact local power company for correction of improper voltage. See unit-rating plate for recommended circuit­protection device.
NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit-rating plate. Do not install unit in system where voltage may fluctuate above or below permissible limits.
NOTE: Use copper wire only between disconnect switch and unit.
NOTE: Install branch-circuit disconnect of adequate size per NEC to handle unit-starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440-14 of NEC.
A. Route Ground and Power Wires
Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit-control box.
WARNING: The unit cabinet must have an uninter­rupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes. Failure to follow this warning can result in an electric shock, fire, or death.
B. Connect Ground and Power Wires
Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 4.
DISCONNECT PER N. E. C. AND/OR LOCAL CODES
CONTACTOR
FIELD POWER
WIRING
FIELD GROUND
WIRING
GROUND LUG
Fig. 4Line Power Connections
C. Connect Control Wiring
Route 24v control wires through control-wiring grommet and connect leads to control wiring. (See Fig. 5.)
Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If thermostat is located more than 100 ft from unit, as measured along the control-voltage wires, use No. 16 AWG color-coded wire to avoid excessive voltage drop.
All wiring must be NEC Class 1 and must be separated from incoming power leads.
Use furnace transformer, fan-coil transformer, or accessory trans­former for control power, 24v/40va minimum.
NOTE: Use of available 24v accessories may exceed the mini­mum 40va power requirement. Determine total transformer load­ing and increase the transformer capacity or split the load with an accessory transformer as required.
IMPORTANT: Check factory wiring and wire connections to ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing, sheet metal, etc.
VIII. COMPRESSOR CRANKCASE HEATER
When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit. To furnish power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than 50 ft. Refer to Residential Split-System Long-Line Application Guideline.
A91056
3
Loading...
+ 5 hidden pages