Bryant 569C User Manual

installation, start-up and service instructions
COMMERCIAL AIR-COOLED CONDENSING UNITS
IMPORTANT —READ BEFORE INSTALLING
1. Read and become familiar with these installation instructions before installing this unit (Fig. 1).
2. Be sure the installation conforms to all applicable local and national codes.
3. These instructions containimportantinformation for the proper maintenance and repair of this equipment. Re­tain these instructions for future use.
Page
SAFETY CONSIDERATIONS ....................... 1
INSTALLATION .................................1-9
I. Locate the Unit ............................ 2
II. Rig and Place Unit ......................... 2
III. Compressor Mounting ...................... 2
IV. Unit Refrigerant Piping Connections .......... 2
V. Electrical Connections ...................... 6
VI. Accessory Installation ...................... 9
PRE-START-UP ..................................9
START-UP ..................................... 10
I. Start-Up and Adjustments .................. 10
CARE AND MAINTENANCE ...................... 10
SERVICE .....................................11-13
I. Cleaning ................................ 11
II. Lubrication .............................. 11
III. Condenser-Fan Adjustment ................ 11
IV. Capacity Control .......................... 12
V. Compressor Removal ..................... 12
VI. Crankcase Heater ......................... 12
VII. Refrigerant Charge ........................ 12
VIII. Refrigerant Service Ports ...................12
TROUBLESHOOTING GUIDE ....................14,15
SAFETY CONSIDERATIONS
WARNING:
ation, service, maintenance, or use can cause explo­sion, fire, electric shock, or other occurrences which may injure you or damage your property. Consult a quali­fied installer or service agency for information or assis­tance. The qualified installer or agency must use only factory-authorized kits or accessories when repairing this product.
Recognize safety information. This is the safety-alert sym­bol. ( ) When you see this symbol on the unit and in instructions or manuals, be alert to the potential for per­sonal injury.
Improper installation, adjustment, alter-
569C 576B
Cancels: II 569C-72-3 II 569C-72-4
5/1/99
Fig.1—Typical Unit (569C072 Shown)
Understand the signal words — DANGER, WARNING, and CAUTION. These words are used with the safety-alert sym­bol. Danger identifies the most serious hazards which will result in severe personal injury or death. Warning indicates a condition that could result in personal injury. Caution is used to identify unsafe practices which would result in minor personal injury or product and property damage.
WARNING:
nance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
1. The power supply (volts, hertz, and phase) must corre­spond to that specified on unit rating plate.
2. The electrical supply provided by the utility must be suf­ficient to handle load imposed by this unit.
3. Refer to the Locate the Unit section on page 2 and Fig. 2 and 3 for locations of electrical inlets, required clearances, and weight distribution based on recom­mended support points before setting unit in place.
4. This installation must conform with local building codes. Refer to local plumbing or wastewater codes and other applicable local codes.
NOTE: When installing any accessory item, see the manu­facturer’s installation instructions packaged with the acces­sory. A qualified agency must use factory-authorized kits or accessories when modifying this unit.
The 569C072,090, and 120 units use hermetic compressors. The 576B090,102, and 120 units use semi-hermetic compres­sors. Refer to Tables 1A and 1B.
Before performing service or mainte-
INSTALLATION
NOTE: If vibration isolators are required for a particular in-
stallation, use corner weight information in Fig. 2 to make proper selection.
NOTES:
1. Dimensions in [ ] are in millimeters.
2. See Fig. 3 for additional information.
WEIGHT CHART*
UNIT
569C072 340 154 86 39 53 24 77 35 124 56 569C090 370 168 86 39 78 35 99 45 107 49 569C120 395 179 89 40 92 42 109 49 105 48 576B090 510 231 115 52 89 40 133 60 173 87 576B102 564 256 133 50 97 44 141 64 193 88 576B120 564 256 133 60 97 44 141 64 193 88
*Weights are for aluminum coils.
Std Unit Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg
CornerWCornerXCornerYCorner
Z
Fig.2—Weight Distribution
I. LOCATE THE UNIT A. Clearance
Maintain clearance around and above unit to provide mini­mum distance from combustible materials, proper airflow,and service access. Refer to Fig. 2 and 3.
Minimum clearance (local codes or jurisdiction may prevail): a. Bottom to combustible surfaces 0 inches. b. Condenser coil, for proper airflow, 36 in. (914 mm) one side,
12 in. (305 mm) the other. The left or rear side receiving the greater clearance is optional.
c. Overhead, 60 in. (1524 mm) to ensure proper condenser
fan operation.
d. Between units, control box side, 42 in. (1067 mm) per NEC
(National Electrical Code, U.S.A. Standard).
e. Between unit and ungrounded surfaces, control box side,
36 in. (914 mm) per NEC.
f. Between unit and block or concrete walls and other grounded
surfaces, control box side, 42 in. (1067 mm) per NEC.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Slab-mounted units should be at least 4 in. (102 mm) above the highest expected water level (flood and runoff). Do not use the unit if it has been under water.
II. RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by us­ing unit frame as a reference. See Tables 1A and 1B and Fig. 4 for additional information. Operating weight is shown in Tables 1A and 1B.
These units are designed for overhead rigging only. Rig with packaging assembly and wood bumper strips in place to pre­vent unit damage by rigging cable. As further protection for coil faces, plywood sheets may be placed against sides of unit, behind cables. Run cables to a central suspension point so that angle from the horizontal is not less than 45 degrees. Raise and set unit down carefully.
If it is necessary to roll unit into position,mount unit on lon­gitudinal rails, using a minimum of 3 rollers. Apply force to rails, not unit. If unit is to be skidded into position, place it on a large pad and drag it by the pad. Do not apply any force
to unit.
Raise from above to lift unit from rails or pad when unit is in final position.
Lifting holes are provided in base rails as shown in Fig. 4. Refer to rigging instructions on unit.
IMPORTANT: If unit has forklift protection skids, be sure to remove forklift protection skids from under unit before set­ting unit in place.
After unit is in position, remove shipping materials and rig­ging skids.
III. COMPRESSOR MOUNTING
Compressors are shipped from the factory held down by 4 bolts. After unit is installed, loosen each bolt until the snubber washer can be moved with finger pressure (376B units only). See Fig. 5.
IV. UNIT REFRIGERANT PIPING CONNECTIONS
Suction connection is sweat with plastic cap; liquid connec­tion is sweat with plastic cap. Refer to Table 2 for refrigerant piping sizes. Follow standard piping practices.
A. Size Refrigerant Lines
Consider length of piping required between condensing unit and evaporator, amount of liquid lift, and compressor oil return. See Table 3 for design details and line sizing. Refer to evaporator installation instructions for additional information.
—2—
Table 1A — Specifications (English)
UNIT 569C072 569C090 569C120 576B090 576B102 576B120 NOMINAL CAPACITY (Tons) 67 OPERATING WEIGHT (lb)
Aluminum Coils (Standard) 340 370 395 510 564 564 Copper Coils (Optional) 386 438 472 578 632 632
RIGGING WEIGHT (lb)
Aluminum Coils (Standard) 390 420 445 560 614 614 Copper Coils (Optional) 436 488 522 628 682 682
1
2
10 71⁄
2
81⁄
2
10
REFRIGERANT* R-22 COMPRESSOR Bristol, Reciprocating Copeland, Scroll Copeland, Scroll Reciprocating, Semi-Hermetic
Quantity...Type 1...H26A72Q 1...ZR94KC 1...ZR125KC 1...06DA818 1...06DA824 Quantity Cylinders 2—4 6
Speed (Rpm) 3500 3500 3500 1750 1750 Oil Charge (oz) (ea) 65 85 110 88 128
CONDENSER FAN Propeller; Direct Drive
Quantity...Rpm 1...850 1...1100 Diameter (in.) 26 26 Motor Hp (NEMA) Nominal Airflow (cfm) 3800 6500 7000 6500 6500 6500
CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fins
Face Area (sq ft) 12.24 15.75 20.5 18.0 18.0 18.0 Storage Capacity (lb)† 11.26 14.88 18.87 16.56 16.56 16.56
CONNECTIONS (sweat)
Suction (in.) 1 Liquid (in.)
CONTROLS
Pressurestat Settings (psig)
High Cutout 426 6 7
Cut-in 320 6 20
Low Cutout 7 6 3
Cut-in 22 6 5
LEGEND
NEMA — National Electrical ManufacturingAssociation
*Unit is factory supplied with holding charge only.
†Storage capacity of condenser coil with coil 80% full of liquid R-22 at
124 F.
1
3
1
8
1
2
11⁄
8
1
2
NOTE: Unit 576B120 has one step of unloading. Full load is 100% ca­pacity, and one step of unloading is 67% capacity. Unit 576B120 has the following unloader settings: load is 70 6 1 psig and unload is 60 6 2 psig.
11⁄
8
5
8
3
4
11⁄
8
1
2
11⁄
8
5
8
1...06DH824 (See Note)
11⁄
8
5
8
—3—
Table 1B — Specifications (SI)
UNIT 569C072 569C090 569C120 576B090 576B102 576B120 NOMINAL CAPACITY (kW) 21 26 35 26 29.9 35 OPERATING WEIGHT (kg)
Aluminum Coils (Standard) 154 168 179 231 256 256 Copper Coils (Optional) 175 199 214 262 287 287
RIGGING WEIGHT (kg)
Aluminum Coils (Standard) 176 191 202 254 279 279
Copper Coils (Optional) 198 221 237 285 309 309 REFRIGERANT* R-22 COMPRESSOR Bristol, Reciprocating Copeland, Scroll Copeland, Scroll Reciprocating, Semi-Hermetic
Quantity...Type 1...H26A72Q 1...ZR94KC 1...ZR125KC 1...06DA818 1...06DA824
Quantity Cylinders 2—4 6
Speed (R/s) 58.4 58.4 58.4 29.2 29.2
Oil Charge (L) (ea) 1.92 2.51 3.25 2.60 3.78 CONDENSER FAN Propeller; Direct Drive
Quantity...R/s 1...14.2 1...18.3
Diameter (mm) 660 660
Motor Hp (NEMA)
Nominal Airflow (L/s) 1800 3050 3300 3050 3050 3050 CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fins
Face Area (sq m) 1.14 1.46 1.90 1.67 1.67 1.67
Storage Capacity (kg)† 5.1 6.75 8.6 7.5 7.5 7.5 CONNECTIONS (sweat)
Suction (in.) 1
Liquid (in.) CONTROLS
Pressurestat Settings (kPa)
High Cutout 2937 6 48
Cut-in 2206 6 138
Low Cutout 48 6 20
Cut-in 152 6 34
LEGEND
NEMA — National Electrical ManufacturingAssociation
*Unit is factory supplied with holding charge only.
†Storage capacity of condenser coil with coil 80% full of liquid R-22 at
51 C.
1
3
1
8
1
2
11⁄
8
1
2
NOTES:
1. Unit576B120 has one step of unloading. Full load is 100% capacity,
2. Equivalent mm values for connectors are as follows:
11⁄
8
5
8
and one step of unloading is 67% capacity. Unit 576B120 has the following unloader settings: load is 483 6 6.9 kPa and unload is 414 6 13.8 kPa.
3
4
11⁄
8
1
2
11⁄
8
5
8
in. mm
1
⁄212.7
5
⁄815.9
11⁄828.6
1...06DH824 (See Note 1)
11⁄
8
5
8
—4—
UNIT DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F
569C072
569C090
569C120
576B090
576B102
576B120
NOTES:
1. Dimensions in [ ] are in millimeters.
1
⁄29 18-23⁄49 —18-21⁄49 18-45⁄169 28-95⁄
18-6 [470.0] [375.0] [362] [415] [846.5]
18-89 18-6
[508.0] [470.0] [381] [613] [1052.5]
18-99 18-89 28-09 18-39 28-
[533.4] [508.0] [609.6] [381] [613] [1052.5]
18-69 18-4
[457.2] [425.5] [858.8] [381] [613] [1052.5]
18-79 18-59 28-9
[482.6] [431.8] [858.8] [381] [613] [1052.5]
18-79 18-59 28-9
[482.6] [431.8] [858.8] [381] [613] [1052.5]
1
⁄29 —18-39 28-5⁄169 38-57⁄
5
⁄169 38-57⁄
3
⁄49 28-913⁄169 18-39 28-5⁄169 38-57⁄
13
⁄169 18-39 28-5⁄169 38-57⁄
13
⁄169 18-39 28-5⁄169 38-57⁄
16
9
16
9
16
9
16
9
16
9
16
9
2. Center of Gravity. See chart for dimensions.
3. Direction of Airflow.
4. Minimum clearance (local codes or jurisdiction may prevail): a. Condenser coil, for proper airflow, 36 in. [914] one side, 12 in. [305]
the other.The left or rear side getting the greater clearance is optional.
b. Overhead, 60 in. [1524] to assure proper condenser fan operation.
UNIT
Std Unit Corner W Corner X Corner Y Corner Z
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg
569C072 340 154 86 39 53 24 77 35 124 56 569C090 370 168 86 39 78 35 99 45 107 49 569C120 395 179 89 40 92 42 109 49 105 48 576B090 510 231 115 52 89 40 133 60 173 87 576B102 564 256 133 60 97 44 141 64 193 88 576B120 564 256 133 60 97 44 141 64 193 88
*Weights are for aluminum coils.
c. Between units, control box side, 42 in. [1067]
per NEC (National Electrical Code) (U.S.A. Standard).
d. Between unit and ungrounded surfaces, con-
trol box side, 36 in. [914] per NEC.
e. Betweenunit and block or concrete walls and
other grounded surfaces, control box side, 42 in. [1067] per NEC.
5. With the exception of the clearance for the con­denser coil as stated in note 4b, a removable fence or barricade requires no clearance.
6. Unitsmay be installed on combustible floors made from wood or Class A, B, or C roof covering material.
WEIGHT CHART*
ELECTRICAL CONNECTIONS
CONNECTION SIZES
3
AA 1
⁄89 DIA [35] FIELD POWER SUPPLY HOLE
BB 29 DIA [51] POWER SUPPLY KNOCK-OUT
1
⁄29 DIA [64] POWER SUPPLY KNOCK-OUT
CC 2
7
⁄89 DIA [22] FIELD CONTROL WIRING HOLE
DD
SERVICE VALVE CONNECTIONS — 60 Hz
UNIT SUCTION LIQUID
569C072 1 569C090 1 569C120 1 576B090 1 576B102 1 576B120 1
1
⁄89 [28.6]
1
⁄89 [28.6]
1
⁄89 [28.6]
1
⁄89 [28.6]
1
⁄89 [28.6]
1
⁄89 [28.6]
1
⁄29 [12.7]
1
⁄29 [12.7]
5
⁄89 [15.9]
1
⁄29 [12.7]
5
⁄89 [15.9]
5
⁄89 [15.9]
Fig. 3 — Base Unit Dimensions
UNIT
569C072 390 176 45.0 1143 38.5 978 35.5 904 569C090 420 191 45.0 1143 38.5 978 43.5 1105 569C120 445 202 45.0 1143 38.5 978 43.5 1105 576B090 560 254 45.0 1143 38.5 978 43.5 1105 576B102 614 279 45.0 1143 38.5 978 43.5 1105 576B120 614 279 45.0 1143 38.5 978 43.5 1105
*Weights are for aluminum coils.
RIGGING WEIGHT* A B C
lb kg in. mm in. mm in. mm
Fig. 4 — Rigging Label
—5—
Table 3 — Liquid Line Data
Fig.5—Typical Compressor Mounting (576B Units)
B. Filter Drier and Moisture Indicator
The filter drier is factory installed. Moisture indicator is a field-installed accessory and should be installed just after liq­uid line shutoff valve. Do not use a receiver. A receiver is not supplied with the unit and should not be used.
NOTE: Unit is shipped with R-22 holding charge. System pres­sure must be relieved before removing caps. Recover refrig­erant prior to brazing.
Pass nitrogen or other inert gas through piping while braz­ing to prevent formation of copper oxide.
Install field-supplied thermostatic expansion valve(s) in evapo­rator section. It is recommended that a field supplied liq­uid line solenoid be positioned in the main liquid line (near the evaporator coil). It should be wired to close when com­pressor stops to minimize refrigerant migration during the ‘‘OFF’’ cycle.
Table 2 — Refrigerant Piping Sizes
LINEAR LENGTH OF PIPING — FT (M)
0-25
UNIT
(0-7.6)
LSLSLSLS
569C072
1
⁄211⁄
569C0901⁄211⁄ 569C1205⁄811⁄ 576B0901⁄211⁄ 576B1025⁄811⁄ 576B1205⁄811⁄
LEGEND
L—Liquid Line S—Suction Line NOTES:
1. Pipe sizes are based on a 2° F (1° C) loss for liquid and suction lines.
2. Pipe sizes are based on the maximum linear length shown for each column, plus a 50% allowance for fittings.
3. Chargeunits with R-22 in accordance with unit installation instructions.
4. Line size conversion to mm is:
in. mm
1
2
5
8 1
1
8
13⁄
8
8 8 8 8 8 8
12.7
15.9
28.6
34.9
25-50
(7.6-15.2)
Line Size (in. OD)
1
⁄211⁄ ⁄211⁄ ⁄813⁄ ⁄211⁄ ⁄811⁄ ⁄811⁄
8 8 8 8 8 8
1 5 1 5 5
50-75
(15.2-22.9)
1
2
11⁄
5
8
11⁄
5
8
13⁄
5
8
11⁄
5
8
13⁄
5
8
13⁄
8 8 8 8 8 8
75-100
(22.9-30.5)
1
2
11⁄
5
8
13⁄
5
8
13⁄
5
8
13⁄
5
8
13⁄
5
8
13⁄
8 8 8 8 8 8
LIQUID LINE
Max Allowable
Temp Loss
UNIT
MAX
ALLOWABLE
LIQUID LIFT
Max Allowable Pressure Drop
Ft M psi kPa F C
569C072 86 26.2 7 48.3 2 1 569C090 60 18.3 7 48.3 2 1 569C120 70 21.3 7 48.3 2 1 576B090 60 18.3 7 48.3 2 1 576B102 65 19.8 7 48.3 2 1 576B120 65 19.8 7 48.3 2 1
NOTE: Values shown are for units operating at 45 F (7.2 C) saturated
suction and 95 F (35 C) entering air.
V. ELECTRICAL CONNECTIONS
WARNING:
The unit cabinet must have an uninter­rupted, unbroken electrical ground to minimize the pos­sibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire con­nected to the unit ground lug in the control compart­ment or conduit approved for electrical ground when installed in accordance with the NEC and local electri­cal codes. Failure to adhere to this warning could re­sult in personal injury.
CAUTION:
Failure to follow these precautions could result in damage to the unit being installed:
A. Field Power Supply (Fig. 6-8)
1. Make all electrical connections in accordance with NEC ANSI/NFPA (American National Standards Institute/ National Fire ProtectionAssociation) 70, latest edition, and local electrical codes governing such wiring. Refer to unit wiring diagram.
2. Use only copper or copper-clad conductor fan connec­tions between field-supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE. Maximum wire size is no. 2 AWG (American Wire Gage).
3. Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (also see Table 4). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown inTable 4, Note 2, to determine the percent voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable warranty.
4. Insulate low-voltage wires for highest voltage con­tained within conduit when low-voltage control wires are run in same conduit as high-voltage wires.
5. Donot damage internal components when drilling through any panel to mount electrical hardware, conduit, etc.
—6—
Loading...
+ 14 hidden pages