NOTE TO INSTALLER — Before the installation, READ THESE
INSTRUCTIONS CAREFULLY AND COMPLETELY. Also,
make sure the User’s Manual and Replacement Guide are left with
the unit after installation.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified workers should install, repair, or service
air-conditioning equipment.
Untrained workers can perform basic maintenance functions of
cleaning coils and filters. All other operations should be performed
by trained service people. When working on air-conditioning
equipment, pay attention to precautions in the literature, tags and
labels attached to the unit, and other safety precautions that may
apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguisher
available for all brazing operations.
036-060
Cancels: NewII 564A-36-1
1-06
C00001
Fig. 1—Unit 564A (Size 036 Shown)
WARNING: Before performing service or maintenance
operations on system, turn off main power to unit. Turn
off accessory heater power switch if applicable. Electrical
shock can cause serious injury or death.
RULES FOR SAFE INSTALLATION AND OPERATION
Recognize safety information. This is the safety-alert symbol
When you see this symbol in instructions or manuals, be alert to
the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances,
especially those that may not have kept up with changing residential construction practices. We require these instructions as a
minimum for a safe installation.
A. General
564A cooling units are fully self-contained and designed for
outdoor installation. See Fig. 1. As shown in Fig. 2-4, units are
shipped in a horizontal-discharge configuration for installation on
a ground-level slab. All units can be field-converted to downflow
discharge configurations for rooftop applications with a fieldsupplied plenum.
.
—1—
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
TOP OF UNIT.........................................................................................0
DUCT SIDE OF UNIT.............................................................................0
SIDE OPPOSITE DUCTS ......................................................................0
BOTTOM OF UNIT.................................................................................0
NEC. REQUIRED CLEARANCES.
BETWEEN UNITS, POWER ENTRY SIDE....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
POWER ENTRY SIDE....................................................................30.00 [762.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP.......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................30.00 [762.0]
LEGEND
NEC – National Electrical Code
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoorfan discharge, with the exception of the condenser coil (36.00 in [914.0 mm]. A
removable fence or barricade requires no clearance.
2. Dimensions are in inches. Dimensions in [ ] are in millimeters.
POWER ENTRY SIDE....................................................................30.00 [762.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP.......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................30.00 [762.0]
LEGEND
NEC – National Electrical Code
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoorfan discharge, with the exception of the condenser coil (36.00 in [914.0 mm]. A
removable fence or barricade requires no clearance.
2. Dimensions are in inches. Dimensions in [ ] are in millimeters.
POWER ENTRY SIDE....................................................................30.00 [762.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP.......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................30.00 [762.0]
LEGEND
NEC – National Electrical Code
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoorfan discharge, with the exception of the condenser coil (36.00 in [914.0 mm]. A
removable fence or barricade requires no clearance.
2. Dimensions are in inches. Dimensions in [ ] are in millimeters.
The unit model number and serial number are stamped on the unit
identification plate. Check this information against shipping papers.
B. Inspect Shipment
Inspect for shipping damage while unit is still on shipping pallet.
If unit appears to be damaged or is torn loose from its securing
points, have it examined by transportation inspectors before
removal. Forward claim papers directly to transportation company.
Manufacturer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the
nearest Carrier Air Conditioning office if any item is missing.
To prevent loss or damage, leave all parts in original packages
until installation.
II. PROVIDE UNIT SUPPORT
A. Slab Mount
Place the unit on a rigid, level surface, suitable to support the unit
weight. The flat surface should extend approximately 2-in. beyond
the unit casing on the 2 sides. The duct connection side and
condensate drain connection sides should be flush with the edge of
the flat surface. A concrete pad or a suitable fiberglass mounting
pad is recommended.
A 6-in. wide gravel apron should be used around the flat surface to
prevent airflow blockage by grass or shrubs. Do not secure the unit
to the flat surface except where required by local codes.
The unit should be level to within 1/4 inch. This is necessary for
the unit drain to function properly.
III. PROVIDE CLEARANCES
The required minimum service clearances and clearances to
combustibles are shown in Fig. 2-4. Adequate ventilation and
condenser air must be provided.
The condenser fan pulls air through the condenser coil and
discharges it through the fan on the top cover. Be sure that the fan
discharge does not recirculate to the condenser coil. Do not locate
the unit in either a corner or under an overhead obstruction. The
minimum clearance under a partial overhang (such as a normal
house overhang) is 48 in. above the unit top. The maximum
horizontal extension of a partial overhang must not exceed 48
inches.
CAUTION: Do not restrict condenser airflow. An air
restriction at either the outdoor-air inlet or the fan
discharge can be harmful to compressor life.
Do not place the unit where water, ice, or snow from an overhang
or roof will damage or flood the unit. The unit may be installed on
wood flooring or on Class A, B, or C roof covering materials.
IV. PLACE UNIT
Unit can be moved with the handholds provided in the unit
basepan. Refer to Table 1 for operating weights. Use extreme
caution to prevent damage when moving the unit. Unit must
remain in an upright position during all moving operations. The
unit must be level for proper condensate drainage; the ground-level
pad must be level before setting the unit in place. When a
field-fabricated support is used, be sure that the support is level
and that it properly supports the unit.
V. SELECT AND INSTALL DUCTWORK
The design and installation of the duct system must be in
accordance with:
• the standards of the NFPA (National Fire Protection Association) for installation of nonresidence-type air conditioning and
ventilating systems;
• NFPA90Aor residence-type, NFPA90B; and/or local codes and
residence-type, NFPA 90B;
• and/or local codes and ordinances.
Select and size ductwork, supply-air registers and return-air grilles
according to ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) recommendations.
Use the duct flanges provided on the supply- and return-air
openings on the side of the unit. See Fig. 2-4 for connection sizes
and locations. The 14-in. round duct collars (size 024-048 units)
are shipped inside the unit attached to the indoor blower. They are
field-installed and must be removed from the indoor cavity prior to
start-up, even if they are not used for installation.
A. INSTALL FLANGES FOR DUCTWORK CONNECTIONS (060 Only)
The 564A060 units are shipped with flanges which must be
field-installed on the unit.
To install unit flanges:
1. Five pieces of flange are shipped on the return-air opening
of the unit. Remove the flanges from the shipping position.
See Fig. 5. Screws are field-supplied.
2. One piece of flange is used as it is shipped (straight). Bend
the other 4 pieces at right angles.
3. Install the straight flange on the right side of the return-air
opening in holes provided. See Fig. 6. Flanges should stick
out from unit to allow for connection of ductwork.
4. Install 2 hand-formed flanges onto return air opening in
holes provided to form a rectangle around the return air
opening.
5. Install remaining 2 hand-formed flanges around discharge
air opening in holes provided.
6. Ductwork can now be attached to flanges.
When designing and installing ductwork, consider the following:
CAUTION: When connecting ductwork to units, do not
drill deeper than 3/4 inch in shaded area shown in Fig. 7
or coil may be damaged.
• All units should have field-supplied filters installed in the
return-air side of the unit. Recommended sizes for filters are
shown in Table 1.
• Avoid abrupt duct size increases and reductions. Abrupt change
in duct size adversely affects air performance.
Use flexible connectors between ductwork and unit to prevent
transmission of vibration. Use suitable gaskets to ensure
weathertight and airtight seal.
• Size ductwork for cooling air quantity (cfm). The minimum air
quantity for proper electric heater operation is listed in Table 2.
Heater limit switches may trip at air quantities below those
recommended.
• Insulate and weatherproof all external ductwork. Insulate and
cover with a vapor barrier all ductwork passing through
conditioned spaces. Follow latest Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air
Conditioning Contractors Association (ACCA) minimum installation standards for residential heating and air conditioning
systems.
• Secure all ducts to building structure. Flash, weatherproof, and
vibration-isolate duct openings in wall or roof according to
good construction practices.
Fig. 8 shows a typical duct system with 564A unit installed.
—5—
FIVE PIECES OF DUCT
19.17″3.92″
FLANGE ATTACHED
HERE FOR SHIPMENT
Fig. 5—Shipping Location of Duct Flanges
(Size 060 Only)
HAND
FORM
C00005
B. CONVERTING HORIZONTAL DISCHARGE UNITS TO
DOWNFLOW (Vertical) DISCHARGE
WARNING: Before performing service or maintenance
operations on system, turn off main power to unit. Turn
off accessory heater power switch if applicable. Electrical
shock can cause serious injury or death.
Units are dedicated side supply products. They are not convertible
to vertical air supply. A field-supplied plenum must be used to
convert to vertical air discharge.
VI. PROVIDE FOR CONDENSATE DISPOSAL
NOTE: Be sure that condensate-water disposal methods comply
with local codes, restrictions, and practices.
Unit removes condensate through a 1-3/64-in. ID hole which is
located at the end of the unit. See Fig. 2-4 for location of
condensate connection.
Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in groundlevel installations. Install a field-supplied condensate trap at end of
condensate connection to ensure proper drainage. Make sure that
the outlet of the trap is at least 1 in. lower than the drain-pan
condensate connection to prevent the pan from overflowing. See
Fig. 9A and 9B. Prime the trap with water. When using a gravel
apron, make sure it slopes away from the unit.
If the installation requires draining the condensate water away
from the unit, install a 2-in. trap using a 3/4-in. OD tube or pipe.
See Fig. 9A and 9B. Make sure that the outlet of the trap is at least
1 in. lower than the unit drain-pan condensate connection to
prevent the pan from overflowing. Prime the trap with water.
Connect a drain tube using a minimum of 3/4-in. PVC, 3/4-in.
CPVC, or 3/4-in. copper pipe (all field supplied). Do not undersize
the tube. Pitch the drain tube downward at a slope of at least 1 in.
for every 10 ft of horizontal run. Be sure to check the drain tube
for leaks. Prime trap at the beginning of the cooling season
start-up. Allowable glues for condensate trap connection are:
Standard ABS, CPVC, or PVC cement.
HAND FORM
STRAIGHT PIECE
Fig. 6—Flanges Installed on 564A060 Units
Fig. 7—Area Not to Be Drilled More Than 3/4-in.
C00006
C00007
VII. INSTALL ELECTRICAL CONNECTIONS
WARNING: The unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should
occur. This ground may consist of an electrical wire
connected to the unit ground in the control compartment,
or conduit approved for electrical ground when installed
in accordance with NEC (National Electrical Code),
ANSI (American National Standards Institute)/NFPA
(latest edition) (in Canada, Canadian Electrical Code
CSA C22.1) and local electrical codes. Failure to adhere
to this warning could result in serious injury or death.
—6—
TABLE 1—PHYSICAL DATA
UNIT 564A036042048060
OPERATING WEIGHT (lbs)250297310350
COMPRESSOR TYPEReciprocating
REFRIGERANT Charge (lb)
REFRIGERANT METERING DEVICEAcutrol™ Device
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
CONDENSER-FAN MOTOR CFM
FIELD-SUPPLIED RETURN-AIR FILTER†
* 460-v motors are 2-speed or 3-speed.
†Required filter sizes shown are based on the ARI (Air Cinditioning and Refrigeration Institute) rated airflow at a velocity of 300 ft/min for throwaway type or 450 ft/min for
high capacity type. Recommended filters are 1-in. thick.
Nominal Rpm
Motor Hp
Diameter (in.)
EVAPORATOR COILCopper Tubes, Aluminum Plate Fins
Rows...Fins/in.
Face Area (sq ft)
EVAPORATOR FAN MOTOR
Blower Motor Size (in.)
Nominal Cfm
Rpm Range
Number of Speeds
Factory Speed Setting
CONNECTING DUCT SIZES
Motor Hp
Supply Air (in.)
Return Air (in.)
Throwaway (in.)
4.74.46.17.5
2...17
6.2
2000
1100
1/4
20
3...15
3.1
10x8
1200
800-1050
3
Low
1/2
Copper Tubes, Aluminum Plate Fins
1...17
11.1
2600
1100
1/4
20
3...15
3.9
10x9
1400
800-1050
3
Med
1/2
Round
14
14
24 x 2424 x 2424 x 3024x30
R-22
Direct Drive
2...17
8.6
2600
1100
1/4
20
3...15
4.3
10x9
1600
1000-1100
2
Low
3/4
2...17
10.7
2800
1100
1/4
20
4...15
4.9
10x10
1850
950-1100
3*, 2*
Low
1
Square
13.9 x 13.9
13.9 x 27.8
INDOOR
THERMOSTAT
RETURN
AIR
TOP COVER
Power Wiring
Control Wiring
Condenser Airflow
Evaporator Airflow
POWER AND
LOW-VOLTAGE
ENTRY
COMPOSITE
RUST-PROOF
BASEPAN
CONDENSATE
DRAIN
CONNECTION
*Separate disconnect per NEC
(National Electrical Code) required
for electric heater when singlepoint conection is not used.
FROM
POWER
SOURCE
DISCONNECT
PER NEC*
(UNIT AND
ELECTRIC
HEATER)
C00008
C00008
Fig. 8—Typical Installation
TABLE 2—MINIMUM AIRFLOW FOR SAFE ELECTRIC
HEATER OPERATION (CFM)
SIZE
036042048060
1200122514001750
1” (25mm) MIN.
TRAP
OUTLET
2” (50mm) MIN.
C99013
Fig. 9A—Condensate Trap (Using Tubing)
TRAP
OUTLET
1" min.
2" min.
C00009
Fig. 9B—Condensate Trap (Using PVC Piping)
CAUTION: Failure to follow these precautions could
result in damage to the unit being installed:
1. Make all electrical connections in accordance with
NEC ANSI/NFPA (latest edition) and local electrical
codes governing such wiring. In Canada, all electrical
connections must be in accordance with CSA standard
C22.1 Canadian Electrical Code Part 1 and applicable
local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between
field-supplied electrical disconnect switch and unit.
DO NOT USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within
operating voltage range indicated on unit rating plate.
4. Insulate low-voltage wires for highest voltage contained within conduit when low-voltage control wires
are run in same conduit as high-voltage wires.
5. Do not damage internal components when drilling
through any panel to mount electrical hardware, conduit, etc. On 3-phase units, ensure phases are balanced
within 2%. Consult local power company for correction of improper voltage and/or phase imbalance.
—7—
A. HIGH-VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a fieldsupplied, waterproof disconnect switch mounted at, or within sight
from, the unit. Refer to the unit rating plate for maximum
fuse/circuit breaker size and minimum circuit amps (ampacity) for
HIGH-VOLTAGE
POWER WIRING
ENTRY HOLE
LOW-VOLTAGE
WIRING ENTRY
HOLE
wire sizing. See Table 3 for electrical data.
The field-supplied disconnect may be mounted on the unit over the
high-voltage inlet hole. (See Fig. 2-4.)
CAUTION: Operation of unit on improper line voltage
constitutes abuse and may cause unit damage that could
affect warranty.
B. ROUTING POWER LEADS INTO UNIT
Use only copper wire between disconnect and unit. The highvoltage leads should be in a conduit until they enter the unit;
conduit termination at the unit must be watertight. Run the
high-voltage leads through the hole on the control box side of the
unit (see Fig. 10 for location). When the leads are inside the unit,
run leads to the control box (Fig. 11). On 3-phase units, connect
the leads to the black, yellow, and blue wires (see Fig. 12).
C. CONNECTING GROUND LEAD TO UNIT GROUND
Refer to Fig. 11 and 12. Connect the ground lead to the chassis
using the unit ground lug in the control box.
D. ROUTING CONTROL POWER WIRES
Form a drip-loop with the thermostat leads before routing them
into the unit. Route the thermostat leads through grommeted hole
provided in unit (see Fig. 10) into unit control box. Connect
thermostat leads to unit control power leads as shown in Fig. 13.
Route thermostat wires through grommet providing a drip-loop at
the panel. Connect low-voltage leads to the thermostat as shown in
Fig. 13.
The unit transformer supplies 24-v power for complete system
including accessory electrical heater. Transformer is factory wired
for 230-v operation. If supply voltage is 208 v, rewire transformer
primary as described in the Special Procedures for 208-v Operation section below.
E. ACCESSORY ELECTRIC HEAT WIRING
Refer to accessory electric heat installation instructions for information on installing accessory electric heat. Accessory electric
heat wiring is shown in Fig. 14.
F. SPECIAL PROCEDURES FOR 208-V OPERATION
WARNING: Make sure that the power supply to the unit
is switched OFF before making any wiring changes.
Electrical shock can cause serious injury or death.
1. Remove wirenut from connection of ORG wire to BLK
wire. Disconnect the ORG transformer-primary lead from
the BLK wire. Save wirenut. See unit wiring label. (See Fig.
15.)
2. Remove the wirenut from the terminal on the end of the
RED transformer-primary lead.
3. Save the wirenut.
4. Connect the RED lead to the BLK wire from which the
ORG lead was disconnected. Insulate with wirenut from
Step 1.
5. Using the wirenut removed from the RED lead, insulate the
loose terminal on the ORG lead.
6. Wrap the wirenuts with electrical tape so that the metal
terminals cannot be seen.
Indoor blower-motor speeds may need to be changed for 208-v
operation. Refer to Indoor Airflow and Airflow Adjustments
section in this publication.
C00010
Fig. 10—Unit Electrical Connection Entry Holes
PRE-START-UP
WARNING: Failure to observe the following warnings
could result in serious injury or death:
1. Follow recognized safety practices and wear protective
goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provide any electric
power to unit unless compressor terminal cover is in
place and secured.
3. Do not remove compressor terminal cover until all
electrical sources are disconnected.
4. Relieve all pressure from both high and low pressure
sides of the system before touching or disturbing
anything inside terminal box if refrigerant leak is
suspected around compressor terminals. Use accepted
methods to recover refrigerant.
5. Never attempt to repair soldered connection while
refrigerant system is under pressure.
6. Do not use torch to remove any component. System
contains oil and refrigerant under pressure. To remove
a component, wear protective goggles and proceed as
follows:
a. Shut off electrical power to unit.
b. Relieve all refrigerant from system using both high-
and low-pressure ports. Use accepted methods to
recover refrigerant.
c. Cut component connecting tubing with tubing cutter
and remove component from unit.
d. Carefully unsweat remaining tubing stubs when
necessary. Oil can ignite when exposed to torch
flame.
Use the Start-Up Checklist supplied at the end of this book
and proceed as follows to inspect and prepare the unit for
initial start-up:
1. Remove all access panels.
2. Read and follow instructions on all DANGER, WARNING,
CAUTION, and INFORMATION labels attached to, or
shipped with, unit.
Make the following inspections:
a. Inspect for shipping and handling damages such as
broken lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections and
on unit base. Detecting oil generally indicates a refrig-
—8—
C00011
ELECTRIC
HEATER
FUSES
GROUND
LUG
INDOOR
FAN
RELAY
OUTDOOR FAN MOTOR
AND COMPRESSOR
START CAPACITOR
HIGH
VOLTAGE
LEADS
Fig. 11—Control Box Wiring
erant leak. Leak-test all refrigerant tubing connections
using electronic leak detector, or liquid-soap solution. If
a refrigerant leak is detected, see following Check for
Refrigerant Leaks section.
c. Inspect all field- and factory-wiring connections. Be sure
that connections are completed and tight.
d. Inspect coil fins. If damaged during shipping and han-
dling, carefully straighten fins with a fin comb.
3. Verify the following conditions:
a. Make sure that outdoor-fan blade is correctly positioned
in fan orifice. Top edge of blade should be 3.125 in.
down from condenser outlet grille. See Condenser Fan
section in this publication.
b. Make sure that air filter is in place.
c. Make sure that condensate drain pan and trap are filled
with water to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose parts
have been removed.
START-UP
Use the Start-Up Checklist supplied at the end of this book, and
proceed as follows:
I. CHECK FOR REFRIGERANT LEAKS
A. Locate and repair refrigerant leaks and charge the
unit as follows:
1. Using both high- and low-pressure ports, locate leaks and
reclaim remaining refrigerant to relieve system pressure.
2. Repair leak following accepted practices.
NOTE: Install a filter drier whenever the system has been opened
for repair.
3. Check system for leaks using an approved method.
4. Evacuate refrigerant system and reclaim refrigerant if no
additional leaks are found.
5. Charge unit with R-22 refrigerant, using a volumetriccharging cylinder or accurate scale. Refer to unit ratingplate for required charge. Be sure to add extra refrigerant to
compensate for internal volume of field-installed filter
drier.
II. START-UP COOLING SECTION AND MAKE ADJUSTMENTS
CAUTION: Complete the required procedures given in
the Pre-Start- Up section this page before starting the
unit.
Do not jumper any safety devices when operating the
unit.
Do not operate the compressor when the outdoor temperature is below 40 F.
Do not rapid-cycle the compressor. Allow 5 minutes
between ‘‘on’’ cycles to prevent compressor damage.
A. CHECKING COOLING CONTROL OPERATION
Start and check the unit for proper cooling control operation as
follows:
1. Place room thermostat SYSTEM switch in OFF position.
Observe that blower motor starts when FAN switch is
placed in ON position and shuts down when FAN switch is
placed in AUTO position.
2. Place SYSTEM switch in COOL position and FAN switch
in AUTO position. Set cooling control below room temperature. Observe that compressor, condenser fan, and
evaporator blower motors start. Observe that cooling cycle
shuts down when control setting is satisfied.
3. When using an automatic changeover room thermostat,
place both SYSTEM and FAN switches in AUTO. positions. Observe that unit operates in Cooling mode when
temperature control is set to ‘‘call for cooling’’ (below
room temperature).
III. REFRIGERANT CHARGE
Amount of refrigerant charge is listed on unit nameplate (also refer
to Table 1). Refer to Carrier Refrigerant Service Techniques
Manual, Refrigerants section.
Unit panels must be in place when unit is operating during
charging procedure.
A. NO CHARGE
Use standard evacuating techniques. After evacuating system,
weigh in the specified amount of refrigerant (refer to Table 1).
B. LOW CHARGE COOLING
Use Cooling Charging Charts, Fig. 17-20. Vary refrigerant until
the conditions of the appropriate chart are met. Note that charging
charts are different from the type normally used. Charts are based
on charging the units to the correct superheat for the various
operating conditions. Accurate pressure gauge and temperature
sensing device are required.
To measure suction pressure, perform the following:
1. Connect the pressure gauge to the service port on the
suction line.
2. Mount the temperature sensing device on the suction line
and insulate it so that outdoor ambient temperature does not
affect the reading. Indoor air cfm must be within the normal
operating range of the unit.
C. TO USE COOLING CHARGING CHARTS
1. Take the outdoor ambient temperature and read the suction
pressure gauge.
—9—
R
UNIT GROUND
GROUND
LEAD
3-PHASE
CONNECTIONS
TO DISCONNECT
PER NEC
SINGLE-PHASE
CONNECTIONS
TO DISCONNECT
PER NEC
L
L
L
BLK
YEL
BLU
C00012
Fig. 12—Line Power Connections
2. Refer to appropriate chart to determine what the suction
temperature should be.
3. If suction temperature is high, add refrigerant. If suction
temperature is low, carefully recover some of the charge.
4. Recheck the suction pressure as charge is adjusted.
EXAMPLE: (Fig. 17)
Outdoor Temperature .....................85° F
Suction Pressure .......................80 psig
Suction Temperature should be .............70° F
(Suction Temperature may vary ±5˚ F.)
If Chargemaster® charging device is used, temperature and
pressure readings must be accomplished using the charging
chart.
IV. INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS
CAUTION: For cooling operation, the recommended
airflow is 350 to 450 cfm per each 12,000 Btuh of rated
cooling capacity.
Table 4 shows dry coil air delivery for horizontal discharge units.
Tables 5-7 show pressure drops.
NOTE: Be sure that all supply- and return-air grilles are open,
free from obstructions, and adjusted properly.
G
Y
W1
W2
UNIT CONTROL BOX
RED
GRN
YEL
THERMOSTAT
AND SUBBASE
C00013
Fig. 13—Control Connections
WARNING: Disconnect electrical power to the unit
before changing blower speed. Electrical shock can cause
serious injury or death.
Airflow can be changed by changing the lead connections of the
blower motor.
Units 564A036,048, and 060 blower motors are factory wired for
low speed operation. Unit 564A042 is factory wired for medium
speed operation.
A. For 208/230-v
The motor leads are color-coded as follows:
3-SPEED2-SPEED
black = high speedblack = high speed
blue = medium speed-
red = low speedred = low speed
To change the speed of the blower motor (BM), remove the fan
motor speed leg lead from the indoor (evaporator) fan relay (IFR)
and replace with lead for desired blower motor speed. Insulate the
removed lead to avoid contact with chassis parts.
TO
UNIT POWER
WIRING
FUSE BLOCK
L2
L1
C
W1
W1
F3
F4
F1
F2
BRN (COMMON)
VIO (STEP 2)
WHT ( STEP 1)
BLK
YEL
YEL
YEL
BLK
BLK
CONTACTOR 2
BRN
YEL
CONTACTOR 1
YEL
YEL
YEL
BRN
YEL
YEL
Fig. 14—Accessory Electric Heater Wiring
—10—
EL 1
EL 2
EL 3
AUTO-LIMIT
BLK
BLK
BLK
C00014
Fig. 15—208/230-3-60 Wiring Diagram
—11—
A06023
Fig. 16—460-3-60 Wiring Diagram
—12—
A06024
OUTDOOR TEMP
° F° C
115 46
105 41
95 35
85 29
75 24
65 18
55 13
457
OUTDOOR TEMP
° F° C
115 46
105 41
95 35
85 29
75 24
65 18
55 13
457
°
Fig. 17—Cooling Charging Chart—564A036 Units
OUTDOOR TEMP
° F° C
115 46
105 41
95 35
85 29
75 24
65 18
55 13
457
°
C00017
°
Fig. 18—Cooling Charging Chart—564A042 Units
OUTDOOR TEMP
° F° C
125 52
115 46
105 41
95 35
85 29
75 24
65 18
55 13
457
°
C00018
C00019
Fig. 19—Cooling Charging Chart—564A048 Units
B. For 460-v Motors
The motor leads are color coded as follows:
3-SPEED (060 ONLY)2-SPEED
black = high speedblack = to purple
-yellow = line
orange = medium speedpurple = to black
blue = low speedred = line
To change the speed of the blower motor (BM) from low speed to
high speed, removethe red lead from the indoor-fan relay (IFR).
Insulate the red lead to avoid contact with any chassis parts.
Separate the black lead from the purple lead. Connect the black
lead to the IFR. Insulate the purple lead to avoid contact with any
chassis parts.
C00020
Fig. 20—Cooling Charging Chart—564A060 Units
V. UNIT CONTROLS
All compressors have the following internal-protection controls.
A. HIGH-PRESSURE RELIEF VALVE
This valve opens when the pressure differential between the low
and high side becomes excessive.
B. COMPRESSOR OVERLOAD
This overload interrupts power to the compressor when either the
current or internal temperature become excessive, and automatically resets when the internal temperature drops to a safe level.
This overload may require up to 60 minutes (or longer) to reset;
therefore, if the internal overload is suspected of being open,
disconnect the electrical power to the unit and check the circuit
FLA— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM— Indoor-Fan Motor
LRA— Locked Rotor Amps
MCA— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
(fuses or HACR-type circuit breaker)
NEC— National Electrical Code
OFM— Outdoor-Fan Motor
RLA— Rated Load Amps
UL— Underwriters Laboratories
* Single-Point Wiring Connections.
† Dual-Point Wiring Connections.
NOTES:
1.2.In compliance with NEC requirements for multimotor and
combination load equipment (refer to NEC Articles 430 and
440), the overcurrent protective device for the unit shall be
fuse or HACR breaker. The UL, Canada, units may be fuse
or circuit breaker.
Unbalanced 3-Phase supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to
determine the percent of voltage imbalance.
% Voltage imbalance
= 100 x
max voltage deviation from average voltage
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
452 + 464 + 455
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 (BC) 464 (AC) 457 -
452=5v
457=7v
455=2v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
®
—14—
TABLE 4—DRY COIL AIR DELIVERY* HORIZONTAL DISCHARGE
(DEDUCT 10% FOR 208 VOLT OPERATION)
230 AND 460 VOLT
UnitMotor SpeedAir Delivery
Low
036
042
048
060†
2 Speed
060
3 Speed
* Air delivery values are based on operating voltage of 230 v or 460 v, dry coil, without filter or electric heater. Deduct wet coil, filter and electric heater pressure drops to
obtain external static pressure available for ducting.
See Tables 5-7.
†460-v motors have 2 or 3 speeds (size 060 only).
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below
this point.
2. Dashes indicate portions of the table that are beyond the blower motor capacity or are not recommended.
Med
High
Low
Med
High
Low
High
Low
Med
High
Low
Med
High
Watts450435420400380335326311-
Cfm12311218120411201008950863751-
Watts470450445410388359338321-
Cfm13021264120511631081940873783-
Watts660635610575540505485460-
Cfm1700166015811450129711901095999-
Watts478458440411378350327317-
Cfm130312701224117911261022911816-
Watts481468450438404370338320735
Cfm131012801241118111101022943811-
Watts-798678647618578540500-
Cfm-17361688161815101421130911871060
Watts--801760730688650600570
Cfm--1898184117571682156414291365
Watts--870842818782696632628
Cfm--2000190317991718162514461333
Watts890850810790735680580480422
Cfm18341820179117621703164014151159950
Watts104010181000950890835790650580
Cfm223021022025196019011855175214681121
Watts107310381001958896840800691575
Cfm223022022160212220521926179115881202
Watts10581008942891860828750700630
Cfm238422002197207119891889182017291640
Watts1266108610211002977924860819700
Cfm272424762392234422622132200119101820
Watts130112161197112710581011979869870
Cfm276026182543242322922169205619431832
0.10.20.30.40.50.60.70.80.9
External Static Pressure (in. wg)
through the overload with an ohmmeter or continuity tester.
VI. SEQUENCE OF OPERATION
A. FAN OPERATION
The FAN switch on the thermostat controls indoor fan operation.
When the FAN switch is placed in the ON position, the IFR
(indoor-fan relay) is energized through the G terminal on the
thermostat. The normally-open contacts close, which then provide
power to the indoor (evaporator) fan motor (IFM). The IFM will
run continuously when the FAN switch is set to ON.
When the FAN switch is set to AUTO, the thermostat deenergizes
the IFR (provided there is not a call for cooling). The contacts open
and the IFM is deenergized. The IFM will be energized only when
there is a call for cooling, or if the unit is equipped with accessory
electric heat, the indoor-fan motor will also run while he accessory
electric heat is energized.
NOTE: 564A060 unit is equipped with a time-delay relay. On this
unit, the indoor fan remains on for 30 seconds after G or Y is
deenergized.
B. COOLING
On a call for cooling, the compressor contactor (C) and the IFR are
energized through the Y and G terminals of the thermostat. On
units with a compressor time-delay relay, there is a 5-minute (± 45
sec) delay between compressor starts. Energizing the compressor
contactor supplies power to the compressor and the outdoor
(condenser) fan motor (OFM). Energizing the IFR provides power
to the IFM.
When the need for cooling has been satisfied, the OFM, compressor, and IFM (FAN on AUTO) are deenergized. If the unit is
equipped with a 30-second delay, the indoor fan will remain
energized for 30 seconds after the compressor is deenergized 060
unit only).
C. HEATING
If accessory electric heaters are installed, on a call for heat the
thermostat energized the W relay which energizes the electric
heaters. The IFR is energized which starts the indoor-fan motor. If
the heaters are staged, W2 is energized when the second stage of
heating is required. When the need for heating is satisfied, the
heater and IFM are deenergized.
MAINTENANCE
To ensure continuing high performance, and to reduce the possibility of premature equipment failure, periodic maintenance must
be performed on this equipment. This cooling unit should be
inspected at least once each year by a qualified service person. To
troubleshoot cooling of units, refer to Troubleshooting chart in
back of book.
NOTE TO EQUIPMENT OWNER: Consult your local dealer
about the availability of a maintenance contract.
WARNING: The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools and equipment. If you do not possess
these, do not attempt to perform any maintenance on this
equipment, other than those procedures recommended in
the User’s Manual. FAILURE TO HEED THIS WARNING COULD RESULT IN SERIOUS INJURY, DEATH
OR DAMAGE TO THIS EQUIPMENT.
The minimum maintenance requirements for this equipment are as
follows:
1. Inspect air filter(s) each month. Clean or replace when
necessary.
NEVER OPERATE THE UNIT WITHOUT A SUITABLE AIR
FILTER IN THE RETURN-AIR DUCT SYSTEM. ALWAYS
REPLACE THE FILTER WITH THE SAME DIMENSIONAL
SIZE AND TYPE AS ORIGINALLY INSTALLED. SEE
TABLE 1 FOR RECOMMENDED FILTER SIZES.
Inspect air filter(s) at least once each month and replace
(throwaway-type) or clean (cleanable-type) at least twice during
each cooling season or whenever the filters become clogged with
dust and lint.
Replace filters with the same dimensional size and type as
originally provided, when necessary.
II. UNIT TOP REMOVAL (CONDENSER-COIL SIDE)
NOTE: When performing maintenance or service procedures that
require removal of the unit top, be sure to perform all of the routine
maintenance procedures that require top removal, including coil
inspection and cleaning, and condensate drain pan inspection and
cleaning.
2. Inspect indoor coil, outdoor coil, drain pan, and condensate
drain each cooling season for cleanliness. Clean when
necessary.
3. Inspect blower motor and wheel for cleanliness each
cooling season. Clean when necessary. For first heating
season, inspect blower wheel bimonthly to determine
proper cleaning frequency.
4. Check electrical connections for tightness and controls for
proper operation each cooling season. Service when necessary.
5. Check the drain channel in the top cover periodically for
blockage (leaves, insects). Clean as needed.
WARNING: Failure to follow these warnings could
result in serious injury or death:
1. Turn off electrical power to the unit before performing
any maintenance or service on the unit.
2. Use extreme caution when removing panels and parts.
As with any mechanical equipment, personal injury
can result from sharp edges, etc.
3. Never place anything combustible either on, or in
contact with, the unit.
WARNING: Disconnect and tag electrical power to the
unit before removing top. Failure to adhere to this
warning could cause serious injury or death.
Only qualified service personnel should perform maintenance and
service procedures that require unit top removal.
Refer to the following top removal procedures:
1. Remove 7 screws on unit top cover surface. (Save all
screws.)
2. Remove 2 screws on unit top cover flange. (Save all
screws.)
3. Lift top from unit carefully. Set top on edge and make sure
that top is supported by unit side that is opposite duct (or
plenum) side.
4. Carefully replace and secure unit top to unit, using screws
removed in Steps 1 and 2, when maintenance and/or service
procedures are completed.
III. EVAPORATOR BLOWER AND MOTOR
For longer life, operating economy, and continuing efficiency,
clean accumulated dirt and grease from the blower wheel and
motor annually.
WARNING: Disconnect and tag electrical power to the
unit before cleaning the blower wheel. Failure to adhere
to this warning could cause serious injury or death.
To clean the blower wheel:
1. Access the blower assembly as follows:
a. Remove top access panel.
b. Remove 3 screws that hold blower orifice ring to blower
housing. Save screws.
c. Loosen setscrew(s) which secure wheel to motor shaft.
2. Remove and clean blower wheel as follows:
a. Lift wheel from housing. When handling and/or cleaning
blower wheel, be sure not to disturb balance weights
(clips) on blower wheel vanes.
b. Remove caked-on dirt from wheel and housing with a
brush. Remove lint and/or dirt accumulations from
wheel and housing with vacuum cleaner, using a soft
brush attachment. Remove grease and oil with a mild
solvent.
—16—
c. Reassemble blower into housing. Place upper orifice ring
on blower to judge location of the blower wheel. Blower
wheel should be approximately 0.2-in. below bottom of
orifice ring when centered correctly. Be sure setscrews
are tightened on motor and are not on round part of shaft.
d. Set upper orifice ring in place with 3 screws removed in
Step 1.
e. Replace top access panel.
IV. CONDENSER COIL, EVAPORATOR COIL, AND
CONDENSATE DRAIN PAN
Inspect the condenser coil, evaporator coil, and condensate drain
pan at least once each year. Proper inspection and cleaning
requires the removal of the unit top. See Unit Top Removal section
above.
The coils are easily cleaned when dry; therefore, inspect and clean
the coils either before or after each cooling season. Remove all
obstructions (including weeds and shrubs) that interfere with the
airflow through the condenser coil. Straighten bent fins with a fin
comb. If coated with dirt or lint, clean the coils with a vacuum
cleaner, using a soft brush attachment. Be careful not to bend the
fins. If coated with oil or grease, clean the coils with a mild
detergent-and-water solution. Rinse coils with clear water, using a
garden hose. Be careful not to splash water on motors, insulation,
wiring, or air filter(s). For best results, spray condenser-coil fins
from inside to outside the unit. On units with an outer and inner
condenser coil, be sure to clean between the coils. Be sure to flush
all dirt and debris from the unit base.
Inspect the drain pan and condensate drain line when inspecting
the coils. Clean the drain pan and condensate drain by removing all
foreign matter from the pan. Flush the pan and drain tube with
clear water. Do not splash water on the insulation, motor, wiring,
or air filter(s). If the drain tube is restricted, clear it with a
‘‘plumbers snake’’ or similar probe device. Ensure that the
auxiliary drain port above the drain tube is also clear.
V. CONDENSER FAN
CAUTION: Keep the condenser fan free from all ob-
structions to ensure proper cooling operation. Never place
articles on top of the unit. Damage to unit may result.
3.125 in.
C00021
Fig. 21—Condenser-Fan Adjustment
NOTE: Refer to the Sequence of Operation section in this
publication, as an aid in determining proper control operation.
VII. REFRIGERANT CIRCUIT
Inspect all refrigerant tubing connections and the unit base for oil
accumulations annually. Detecting oil generally indicates a refrigerant leak.
If oil is detected or if low cooling performance is suspected,
leak-test all refrigerant tubing using an electronic leak-detector, or
liquid-soap solution. If a refrigerant leak is detected, refer to Check
for Refrigerant Leaks section in this publication.
If no refrigerant leaks are found and low cooling performance is
suspected, refer to Refrigerant Charge section in this publication.
VIII. EVAPORATOR AIRFLOW
The cooling airflow does not require checking unless improper
performance is suspected. If a problem exists, be sure that all
supply- and return-air grilles are open and free from obstructions,
and that the air filter is clean. When necessary, refer to Indoor
Airflow and Airflow Adjustments section in this publication to
check the system airflow.
IX. METERING DEVICES
Refrigerant metering devices are fixed orifices and are located in
the inlet header to the evaporator coil.
X. LIQUID LINE STRAINER
The liquid line strainer (to protect metering device) is made of wire
mesh and is located in the liquid line on the inlet side of the
metering device.
1. Shut off unit power supply.
2. Remove condenser-fan assembly (grille, motor, motor
cover, and fan) by removing screws and flipping assembly
onto unit top cover.
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 21.
5. Tighten setscrews.
6. Replace condenser-fan assembly.
VI. ELECTRICAL CONTROLS AND WIRING
Inspect and check the electrical controls and wiring annually. Be
sure to turn off the electrical power to the unit.
Remove the top panel to locate all the electrical controls and
wiring. Check all electrical connections for tightness. Tighten all
screw connections. If any smoky or burned connections are
noticed, disassemble the connection, clean all the parts, restrip the
wire end and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, replace all the
panels. Start the unit, and observe at least one complete cooling
cycle to ensure proper operation. If discrepancies are observed in
operating cycle, or if a suspected malfunction has occurred, check
each electrical component with the proper electrical instrumentation. Refer to the unit wiring label when making these checkouts.
—17—
SYMPTOMCAUSEREMEDY
Compressor and condenser fan will not start.
Compressor will not start but condenser fan
runs.
Compressor cycles (other than normally satisfying thermostat).
Compressor operates continuously.
Excessive head pressure.
Head pressure too low.
Excessive suction pressure.
Suction pressure too low.
TABLE 8 — TROUBLESHOOTING — COOLING
Power failureCall power company.
Fuse blown or circuit breaker trippedReplace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer, or
control relay
Insufficient line voltageDetermine cause and correct.
Incorrect or faulty wiringCheck wiring diagram and rewire correctly.
Thermostat setting too high
Faulty wiring or loose connections in compressor
circuit
Compressor motor burned out, seized, or internal
overload open
Defective run/start capacitor, overload, start relayDetermine cause and replace.
One leg of 3-phase power dead
Refrigerant overcharge or undercharge
Defective compressorReplace and determine cause.
Insufficient line voltageDetermine cause and correct.
Blocked condenserDetermine cause and correct.
Defective run/start capacitor, overload or start
relay
Defective thermostatReplace thermostat.
Faulty condenser-fan motor or capacitorReplace.
Restriction in refrigerant systemLocate restriction and remove.
Dirty air filterReplace filter.
Unit undersized for loadDecrease load or increase unit size.
Thermostat set too lowReset thermostat.
Low refrigerant chargeLocate leak, repair, and recharge.
Leaking valves in compressorReplace compressor.
Air in system
Condenser coil dirty or restrictedClean coil or remove restriction.
Dirty air filterReplace filter.
Dirty condenser coilClean coil.
Refrigerant overchargedRecover excess refrigerant.
Air in system
Condenser air restricted or air short-cyclingDetermine cause and correct.
Low refrigerant chargeCheck for leaks, repair and recharge.
Compressor valves leakingReplace compressor.
Restriction in liquid tubeRemove restriction.
High heat loadCheck for source and eliminate.
Compressor valves leakingReplace compressor.
Refrigerant overchargedRecover excess refrigerant.
Dirty air filterReplace filter.
Low refrigerant chargeCheck for leaks, repair and recharge.
Metering device or low side restrictedRemove source of restriction.
Insufficient evaporator airflow
Temperature too low in conditioned areaReset thermostat.
Outdoor ambient below 40° FInstall low-ambient kit.
Field-installed filter-drier restrictedReplace.
Replace component.
Lower thermostat setting below room temperature.
Check wiring and repair or replace.
Determine cause. Replace compressor.
Replace fuse or reset circuit breaker. Determine
cause.
Recover refrigerant, evacuate system, and recharge to capacities shown on nameplate.
Determine cause and replace.
Recover refrigerant, evacuate system, and recharge.
Recover refrigerant, evacuate system, and recharge.
Increase air quantity. Check filter — replace if
necessary.
—18—
START-UP CHECKLIST (REMOVE AND STORE IN JOB FILE)
I. PRELIMINARY INFORMATION
Model No. ...................................................................................................................................................................................................................
Serial No. ....................................................................................................................................................................................................................
Date .............................................................................................................................................................................................................................