Bryant 564A User Manual

installation, start-up
564A
and service instructions
3-PHASE PACKAGED AIR CONDITIONERS
NOTE: Read the entire instruction manual before starting the installation.
Index Page
SAFETY CONSIDERATIONS .....................................................1
RULES FOR SAFE INSTALLATION
AND OPERATION........................................................................1
GENERAL ................................................................................1
RECEIVING AND INSTALLATION.......................................5-8
IDENTIFY UNIT......................................................................5
INSPECT SHIPMENT .............................................................5
Provide Unit Support .....................................................................5
SLAB MOUNT.........................................................................5
Provide Clearances.........................................................................5
Select and Install Ductwork .......................................................5-6
INSTALL FLANGES FOR DUCTWORK
CONNECTIONS (060 Only) ...................................................5
CONVERTING HORIZONTAL DISCHARGE UNITS
TO DOWNFLOW (Vertical) DISCHARGE ...........................6
Provide for Condensate Disposal ..................................................6
Install Electrical Connections.....................................................6-8
HIGH-VOLTAGE CONNECTIONS .......................................7
ROUTING POWER LEADS INTO UNIT..............................8
CONNECTING GROUND LEAD TO UNIT GROUND ......8
ROUTING CONTROL POWER WIRES................................8
ACCESSORY ELECTRIC HEAT WIRING...........................8
SPECIAL PROCEDURES FOR 208-V OPERATION...........8
PRE-START-UP .........................................................................8-9
MAINTENANCE....................................................................14-16
TROUBLESHOOTING ...............................................................17
START-UP CHECKLIST............................................................18
NOTE TO INSTALLER — Before the installation, READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY. Also, make sure the User’s Manual and Replacement Guide are left with the unit after installation.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified workers should install, repair, or service air-conditioning equipment.
Untrained workers can perform basic maintenance functions of cleaning coils and filters. All other operations should be performed by trained service people. When working on air-conditioning equipment, pay attention to precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
036-060
Cancels: New II 564A-36-1
1-06
C00001
Fig. 1—Unit 564A (Size 036 Shown)
WARNING: Before performing service or maintenance
operations on system, turn off main power to unit. Turn off accessory heater power switch if applicable. Electrical shock can cause serious injury or death.
RULES FOR SAFE INSTALLATION AND OPERATION
Recognize safety information. This is the safety-alert symbol When you see this symbol in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residen­tial construction practices. We require these instructions as a minimum for a safe installation.
A. General
564A cooling units are fully self-contained and designed for outdoor installation. See Fig. 1. As shown in Fig. 2-4, units are shipped in a horizontal-discharge configuration for installation on a ground-level slab. All units can be field-converted to downflow discharge configurations for rooftop applications with a field­supplied plenum.
.
—1—
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
TOP OF UNIT.........................................................................................0
DUCT SIDE OF UNIT.............................................................................0
SIDE OPPOSITE DUCTS ......................................................................0
BOTTOM OF UNIT.................................................................................0
NEC. REQUIRED CLEARANCES.
BETWEEN UNITS, POWER ENTRY SIDE....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0] UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
CONDENSER . COIL ACCESS SIDE..............................................30.00 [762.0]
POWER ENTRY SIDE....................................................................30.00 [762.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP.......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................30.00 [762.0]
LEGEND
NEC – National Electrical Code
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor­fan discharge, with the exception of the condenser coil (36.00 in [914.0 mm]. A removable fence or barricade requires no clearance.
2. Dimensions are in inches. Dimensions in [ ] are in millimeters.
INCHES [mm]
INCHES [mm]
INCHES [mm]
Fig. 2—Base Unit Dimensions 564A036
UNIT ELECTRICAL CHARACTERISTICS
UNIT WEIGHT
lb kg X Y Z
036 208/230-3-60 250 114 355.6 (14.00) 508.0 (20.00) 241.3 (9.50)
CENTER OF GRAVITY
IN. [MM]
—2—
C00002
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
TOP OF UNIT.........................................................................................0
DUCT SIDE OF UNIT.............................................................................0
SIDE OPPOSITE DUCTS ......................................................................0
BOTTOM OF UNIT.................................................................................0
NEC. REQUIRED CLEARANCES.
BETWEEN UNITS, POWER ENTRY SIDE....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0] UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
CONDENSER . COIL ACCESS SIDE.............................................. 30.00 [762.0]
POWER ENTRY SIDE....................................................................30.00 [762.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP.......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................30.00 [762.0]
LEGEND
NEC – National Electrical Code
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor­fan discharge, with the exception of the condenser coil (36.00 in [914.0 mm]. A removable fence or barricade requires no clearance.
2. Dimensions are in inches. Dimensions in [ ] are in millimeters.
INCHES [mm]
INCHES [mm]
INCHES [mm]
Fig. 3—Base Unit Dimensions, 564A042,048
UNIT ELECTRICAL CHARACTERISTICS
UNIT WEIGHT
lb kg X Y Z 042 208/230-3-60 297 135 355.6 (14.00) 508.0 (20.00) 304.8 (12.00) 048 208/230-3-60 310 141 355.6 (14.00) 508.0 (20.00) 304.8 (12.00)
CENTER OF GRAVITY
IN. [MM]
—3—
C00003
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
TOP OF UNIT.........................................................................................0
DUCT SIDE OF UNIT.............................................................................0
SIDE OPPOSITE DUCTS ......................................................................0
BOTTOM OF UNIT.................................................................................0
NEC. REQUIRED CLEARANCES.
BETWEEN UNITS, POWER ENTRY SIDE....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0] UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
CONDENSER . COIL ACCESS SIDE..............................................30.00 [762.0]
POWER ENTRY SIDE....................................................................30.00 [762.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP.......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................30.00 [762.0]
LEGEND
NEC – National Electrical Code
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor­fan discharge, with the exception of the condenser coil (36.00 in [914.0 mm]. A removable fence or barricade requires no clearance.
2. Dimensions are in inches. Dimensions in [ ] are in millimeters.
INCHES [mm]
INCHES [mm]
INCHES [mm]
Fig. 4—Base Unit Dimensions, 564A060
UNIT ELECTRICAL CHARACTERISTICS
060 208/230-3-60, 460-3-60 350 159 355.6 (14.00) 508.0 (20.00) 355.6 (14.00)
UNIT WEIGHT
lb kg X Y Z
CENTER OF GRAVITY
IN. [MM]
—4—
C00004
RECEIVING AND INSTALLATION
I. CHECK EQUIPMENT
A. Identify Unit
The unit model number and serial number are stamped on the unit identification plate. Check this information against shipping pa­pers.
B. Inspect Shipment
Inspect for shipping damage while unit is still on shipping pallet. If unit appears to be damaged or is torn loose from its securing points, have it examined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the nearest Carrier Air Conditioning office if any item is missing.
To prevent loss or damage, leave all parts in original packages until installation.
II. PROVIDE UNIT SUPPORT
A. Slab Mount
Place the unit on a rigid, level surface, suitable to support the unit weight. The flat surface should extend approximately 2-in. beyond the unit casing on the 2 sides. The duct connection side and condensate drain connection sides should be flush with the edge of the flat surface. A concrete pad or a suitable fiberglass mounting pad is recommended.
A 6-in. wide gravel apron should be used around the flat surface to prevent airflow blockage by grass or shrubs. Do not secure the unit to the flat surface except where required by local codes.
The unit should be level to within 1/4 inch. This is necessary for the unit drain to function properly.
III. PROVIDE CLEARANCES
The required minimum service clearances and clearances to combustibles are shown in Fig. 2-4. Adequate ventilation and condenser air must be provided.
The condenser fan pulls air through the condenser coil and discharges it through the fan on the top cover. Be sure that the fan discharge does not recirculate to the condenser coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48 in. above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 inches.
CAUTION: Do not restrict condenser airflow. An air restriction at either the outdoor-air inlet or the fan discharge can be harmful to compressor life.
Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. The unit may be installed on wood flooring or on Class A, B, or C roof covering materials.
IV. PLACE UNIT
Unit can be moved with the handholds provided in the unit basepan. Refer to Table 1 for operating weights. Use extreme
caution to prevent damage when moving the unit. Unit must remain in an upright position during all moving operations. The
unit must be level for proper condensate drainage; the ground-level pad must be level before setting the unit in place. When a field-fabricated support is used, be sure that the support is level and that it properly supports the unit.
V. SELECT AND INSTALL DUCTWORK
The design and installation of the duct system must be in accordance with:
• the standards of the NFPA (National Fire Protection Associa­tion) for installation of nonresidence-type air conditioning and ventilating systems;
• NFPA90Aor residence-type, NFPA90B; and/or local codes and residence-type, NFPA 90B;
• and/or local codes and ordinances.
Select and size ductwork, supply-air registers and return-air grilles according to ASHRAE (American Society of Heating, Refrigera­tion, and Air Conditioning Engineers) recommendations.
Use the duct flanges provided on the supply- and return-air openings on the side of the unit. See Fig. 2-4 for connection sizes and locations. The 14-in. round duct collars (size 024-048 units) are shipped inside the unit attached to the indoor blower. They are field-installed and must be removed from the indoor cavity prior to start-up, even if they are not used for installation.
A. INSTALL FLANGES FOR DUCTWORK CONNEC­TIONS (060 Only)
The 564A060 units are shipped with flanges which must be field-installed on the unit.
To install unit flanges:
1. Five pieces of flange are shipped on the return-air opening of the unit. Remove the flanges from the shipping position. See Fig. 5. Screws are field-supplied.
2. One piece of flange is used as it is shipped (straight). Bend the other 4 pieces at right angles.
3. Install the straight flange on the right side of the return-air opening in holes provided. See Fig. 6. Flanges should stick out from unit to allow for connection of ductwork.
4. Install 2 hand-formed flanges onto return air opening in holes provided to form a rectangle around the return air opening.
5. Install remaining 2 hand-formed flanges around discharge air opening in holes provided.
6. Ductwork can now be attached to flanges.
When designing and installing ductwork, consider the following:
CAUTION: When connecting ductwork to units, do not drill deeper than 3/4 inch in shaded area shown in Fig. 7 or coil may be damaged.
• All units should have field-supplied filters installed in the return-air side of the unit. Recommended sizes for filters are shown in Table 1.
• Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air performance. Use flexible connectors between ductwork and unit to prevent transmission of vibration. Use suitable gaskets to ensure weathertight and airtight seal.
• Size ductwork for cooling air quantity (cfm). The minimum air quantity for proper electric heater operation is listed in Table 2. Heater limit switches may trip at air quantities below those recommended.
• Insulate and weatherproof all external ductwork. Insulate and cover with a vapor barrier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and Air Condi­tioning Contractors National Association (SMACNA) and Air Conditioning Contractors Association (ACCA) minimum in­stallation standards for residential heating and air conditioning systems.
• Secure all ducts to building structure. Flash, weatherproof, and vibration-isolate duct openings in wall or roof according to good construction practices.
Fig. 8 shows a typical duct system with 564A unit installed.
—5—
FIVE PIECES OF DUCT
19.17 3.92
FLANGE ATTACHED HERE FOR SHIPMENT
Fig. 5—Shipping Location of Duct Flanges
(Size 060 Only)
HAND FORM
C00005
B. CONVERTING HORIZONTAL DISCHARGE UNITS TO DOWNFLOW (Vertical) DISCHARGE
WARNING: Before performing service or maintenance
operations on system, turn off main power to unit. Turn off accessory heater power switch if applicable. Electrical shock can cause serious injury or death.
Units are dedicated side supply products. They are not convertible to vertical air supply. A field-supplied plenum must be used to convert to vertical air discharge.
VI. PROVIDE FOR CONDENSATE DISPOSAL
NOTE: Be sure that condensate-water disposal methods comply
with local codes, restrictions, and practices.
Unit removes condensate through a 1-3/64-in. ID hole which is located at the end of the unit. See Fig. 2-4 for location of condensate connection.
Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground­level installations. Install a field-supplied condensate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. lower than the drain-pan condensate connection to prevent the pan from overflowing. See Fig. 9A and 9B. Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit.
If the installation requires draining the condensate water away from the unit, install a 2-in. trap using a 3/4-in. OD tube or pipe. See Fig. 9A and 9B. Make sure that the outlet of the trap is at least 1 in. lower than the unit drain-pan condensate connection to prevent the pan from overflowing. Prime the trap with water. Connect a drain tube using a minimum of 3/4-in. PVC, 3/4-in. CPVC, or 3/4-in. copper pipe (all field supplied). Do not undersize the tube. Pitch the drain tube downward at a slope of at least 1 in. for every 10 ft of horizontal run. Be sure to check the drain tube for leaks. Prime trap at the beginning of the cooling season start-up. Allowable glues for condensate trap connection are: Standard ABS, CPVC, or PVC cement.
HAND FORM
STRAIGHT PIECE
Fig. 6—Flanges Installed on 564A060 Units
Fig. 7—Area Not to Be Drilled More Than 3/4-in.
C00006
C00007
VII. INSTALL ELECTRICAL CONNECTIONS
WARNING: The unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the pos­sibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI (American National Standards Institute)/NFPA (latest edition) (in Canada, Canadian Electrical Code CSA C22.1) and local electrical codes. Failure to adhere to this warning could result in serious injury or death.
—6—
TABLE 1—PHYSICAL DATA
UNIT 564A 036 042 048 060
OPERATING WEIGHT (lbs) 250 297 310 350
COMPRESSOR TYPE Reciprocating
REFRIGERANT Charge (lb)
REFRIGERANT METERING DEVICE Acutrol™ Device
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
CONDENSER-FAN MOTOR CFM
FIELD-SUPPLIED RETURN-AIR FILTER†
* 460-v motors are 2-speed or 3-speed. †Required filter sizes shown are based on the ARI (Air Cinditioning and Refrigeration Institute) rated airflow at a velocity of 300 ft/min for throwaway type or 450 ft/min for high capacity type. Recommended filters are 1-in. thick.
Nominal Rpm
Motor Hp
Diameter (in.)
EVAPORATOR COIL Copper Tubes, Aluminum Plate Fins
Rows...Fins/in.
Face Area (sq ft)
EVAPORATOR FAN MOTOR
Blower Motor Size (in.)
Nominal Cfm
Rpm Range
Number of Speeds
Factory Speed Setting
CONNECTING DUCT SIZES
Motor Hp
Supply Air (in.) Return Air (in.)
Throwaway (in.)
4.7 4.4 6.1 7.5
2...17
6.2
2000 1100
1/4
20
3...15
3.1
10x8
1200
800-1050
3
Low
1/2
Copper Tubes, Aluminum Plate Fins
1...17
11.1
2600 1100
1/4
20
3...15
3.9
10x9
1400
800-1050
3
Med
1/2
Round
14 14
24 x 24 24 x 24 24 x 30 24x30
R-22
Direct Drive
2...17
8.6
2600 1100
1/4
20
3...15
4.3
10x9
1600
1000-1100
2
Low
3/4
2...17
10.7
2800 1100
1/4
20
4...15
4.9
10x10
1850
950-1100
3*, 2*
Low
1
Square
13.9 x 13.9
13.9 x 27.8
INDOOR THERMOSTAT
RETURN AIR
TOP COVER
Power Wiring
Control Wiring
Condenser Airflow
Evaporator Airflow
POWER AND LOW-VOLTAGE ENTRY
COMPOSITE RUST-PROOF BASEPAN
CONDENSATE DRAIN CONNECTION
*Separate disconnect per NEC (National Electrical Code) required for electric heater when single­point conection is not used.
FROM POWER SOURCE
DISCONNECT PER NEC* (UNIT AND ELECTRIC HEATER)
C00008
C00008
Fig. 8—Typical Installation
TABLE 2—MINIMUM AIRFLOW FOR SAFE ELECTRIC
HEATER OPERATION (CFM)
SIZE
036 042 048 060
1200 1225 1400 1750
1” (25mm) MIN.
TRAP OUTLET
2” (50mm) MIN.
C99013
Fig. 9A—Condensate Trap (Using Tubing)
TRAP OUTLET
1" min.
2" min.
C00009
Fig. 9B—Condensate Trap (Using PVC Piping)
CAUTION: Failure to follow these precautions could
result in damage to the unit being installed:
1. Make all electrical connections in accordance with NEC ANSI/NFPA (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between field-supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within operating voltage range indicated on unit rating plate.
4. Insulate low-voltage wires for highest voltage con­tained within conduit when low-voltage control wires are run in same conduit as high-voltage wires.
5. Do not damage internal components when drilling through any panel to mount electrical hardware, con­duit, etc. On 3-phase units, ensure phases are balanced within 2%. Consult local power company for correc­tion of improper voltage and/or phase imbalance.
—7—
A. HIGH-VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a field­supplied, waterproof disconnect switch mounted at, or within sight from, the unit. Refer to the unit rating plate for maximum
fuse/circuit breaker size and minimum circuit amps (ampacity) for
HIGH-VOLTAGE POWER WIRING ENTRY HOLE
LOW-VOLTAGE WIRING ENTRY HOLE
wire sizing. See Table 3 for electrical data.
The field-supplied disconnect may be mounted on the unit over the high-voltage inlet hole. (See Fig. 2-4.)
CAUTION: Operation of unit on improper line voltage constitutes abuse and may cause unit damage that could affect warranty.
B. ROUTING POWER LEADS INTO UNIT
Use only copper wire between disconnect and unit. The high­voltage leads should be in a conduit until they enter the unit; conduit termination at the unit must be watertight. Run the high-voltage leads through the hole on the control box side of the unit (see Fig. 10 for location). When the leads are inside the unit, run leads to the control box (Fig. 11). On 3-phase units, connect the leads to the black, yellow, and blue wires (see Fig. 12).
C. CONNECTING GROUND LEAD TO UNIT GROUND
Refer to Fig. 11 and 12. Connect the ground lead to the chassis using the unit ground lug in the control box.
D. ROUTING CONTROL POWER WIRES
Form a drip-loop with the thermostat leads before routing them into the unit. Route the thermostat leads through grommeted hole provided in unit (see Fig. 10) into unit control box. Connect thermostat leads to unit control power leads as shown in Fig. 13.
Route thermostat wires through grommet providing a drip-loop at the panel. Connect low-voltage leads to the thermostat as shown in Fig. 13.
The unit transformer supplies 24-v power for complete system including accessory electrical heater. Transformer is factory wired for 230-v operation. If supply voltage is 208 v, rewire transformer primary as described in the Special Procedures for 208-v Opera­tion section below.
E. ACCESSORY ELECTRIC HEAT WIRING
Refer to accessory electric heat installation instructions for infor­mation on installing accessory electric heat. Accessory electric heat wiring is shown in Fig. 14.
F. SPECIAL PROCEDURES FOR 208-V OPERATION
WARNING: Make sure that the power supply to the unit
is switched OFF before making any wiring changes. Electrical shock can cause serious injury or death.
1. Remove wirenut from connection of ORG wire to BLK wire. Disconnect the ORG transformer-primary lead from the BLK wire. Save wirenut. See unit wiring label. (See Fig.
15.)
2. Remove the wirenut from the terminal on the end of the RED transformer-primary lead.
3. Save the wirenut.
4. Connect the RED lead to the BLK wire from which the ORG lead was disconnected. Insulate with wirenut from Step 1.
5. Using the wirenut removed from the RED lead, insulate the loose terminal on the ORG lead.
6. Wrap the wirenuts with electrical tape so that the metal terminals cannot be seen.
Indoor blower-motor speeds may need to be changed for 208-v operation. Refer to Indoor Airflow and Airflow Adjustments section in this publication.
C00010
Fig. 10—Unit Electrical Connection Entry Holes
PRE-START-UP
WARNING: Failure to observe the following warnings
could result in serious injury or death:
1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured.
3. Do not remove compressor terminal cover until all electrical sources are disconnected.
4. Relieve all pressure from both high and low pressure sides of the system before touching or disturbing anything inside terminal box if refrigerant leak is suspected around compressor terminals. Use accepted methods to recover refrigerant.
5. Never attempt to repair soldered connection while refrigerant system is under pressure.
6. Do not use torch to remove any component. System contains oil and refrigerant under pressure. To remove a component, wear protective goggles and proceed as follows: a. Shut off electrical power to unit. b. Relieve all refrigerant from system using both high-
and low-pressure ports. Use accepted methods to recover refrigerant.
c. Cut component connecting tubing with tubing cutter
and remove component from unit.
d. Carefully unsweat remaining tubing stubs when
necessary. Oil can ignite when exposed to torch flame.
Use the Start-Up Checklist supplied at the end of this book and proceed as follows to inspect and prepare the unit for initial start-up:
1. Remove all access panels.
2. Read and follow instructions on all DANGER, WARNING, CAUTION, and INFORMATION labels attached to, or shipped with, unit.
Make the following inspections:
a. Inspect for shipping and handling damages such as
broken lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections and
on unit base. Detecting oil generally indicates a refrig-
—8—
C00011
ELECTRIC HEATER FUSES
GROUND LUG
INDOOR FAN RELAY
OUTDOOR FAN MOTOR AND COMPRESSOR START CAPACITOR
HIGH VOLTAGE LEADS
Fig. 11—Control Box Wiring
erant leak. Leak-test all refrigerant tubing connections using electronic leak detector, or liquid-soap solution. If a refrigerant leak is detected, see following Check for Refrigerant Leaks section.
c. Inspect all field- and factory-wiring connections. Be sure
that connections are completed and tight.
d. Inspect coil fins. If damaged during shipping and han-
dling, carefully straighten fins with a fin comb.
3. Verify the following conditions:
a. Make sure that outdoor-fan blade is correctly positioned
in fan orifice. Top edge of blade should be 3.125 in. down from condenser outlet grille. See Condenser Fan section in this publication.
b. Make sure that air filter is in place.
c. Make sure that condensate drain pan and trap are filled
with water to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose parts
have been removed.
START-UP
Use the Start-Up Checklist supplied at the end of this book, and proceed as follows:
I. CHECK FOR REFRIGERANT LEAKS
A. Locate and repair refrigerant leaks and charge the unit as follows:
1. Using both high- and low-pressure ports, locate leaks and reclaim remaining refrigerant to relieve system pressure.
2. Repair leak following accepted practices.
NOTE: Install a filter drier whenever the system has been opened for repair.
3. Check system for leaks using an approved method.
4. Evacuate refrigerant system and reclaim refrigerant if no additional leaks are found.
5. Charge unit with R-22 refrigerant, using a volumetric­charging cylinder or accurate scale. Refer to unit rating plate for required charge. Be sure to add extra refrigerant to compensate for internal volume of field-installed filter drier.
II. START-UP COOLING SECTION AND MAKE ADJUST­MENTS
CAUTION: Complete the required procedures given in
the Pre-Start- Up section this page before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the compressor when the outdoor tem­perature is below 40 F. Do not rapid-cycle the compressor. Allow 5 minutes between ‘‘on’’ cycles to prevent compressor damage.
A. CHECKING COOLING CONTROL OPERATION
Start and check the unit for proper cooling control operation as follows:
1. Place room thermostat SYSTEM switch in OFF position. Observe that blower motor starts when FAN switch is placed in ON position and shuts down when FAN switch is placed in AUTO position.
2. Place SYSTEM switch in COOL position and FAN switch in AUTO position. Set cooling control below room tem­perature. Observe that compressor, condenser fan, and evaporator blower motors start. Observe that cooling cycle shuts down when control setting is satisfied.
3. When using an automatic changeover room thermostat, place both SYSTEM and FAN switches in AUTO. posi­tions. Observe that unit operates in Cooling mode when temperature control is set to ‘‘call for cooling’’ (below room temperature).
III. REFRIGERANT CHARGE
Amount of refrigerant charge is listed on unit nameplate (also refer to Table 1). Refer to Carrier Refrigerant Service Techniques Manual, Refrigerants section.
Unit panels must be in place when unit is operating during charging procedure.
A. NO CHARGE
Use standard evacuating techniques. After evacuating system, weigh in the specified amount of refrigerant (refer to Table 1).
B. LOW CHARGE COOLING
Use Cooling Charging Charts, Fig. 17-20. Vary refrigerant until the conditions of the appropriate chart are met. Note that charging charts are different from the type normally used. Charts are based on charging the units to the correct superheat for the various operating conditions. Accurate pressure gauge and temperature sensing device are required.
To measure suction pressure, perform the following:
1. Connect the pressure gauge to the service port on the suction line.
2. Mount the temperature sensing device on the suction line and insulate it so that outdoor ambient temperature does not affect the reading. Indoor air cfm must be within the normal operating range of the unit.
C. TO USE COOLING CHARGING CHARTS
1. Take the outdoor ambient temperature and read the suction pressure gauge.
—9—
R
UNIT GROUND
GROUND
LEAD
3-PHASE CONNECTIONS TO DISCONNECT PER NEC
SINGLE-PHASE CONNECTIONS TO DISCONNECT PER NEC
L
L
L
BLK
YEL
BLU
C00012
Fig. 12—Line Power Connections
2. Refer to appropriate chart to determine what the suction temperature should be.
3. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover some of the charge.
4. Recheck the suction pressure as charge is adjusted. EXAMPLE: (Fig. 17)
Outdoor Temperature .....................85° F
Suction Pressure .......................80 psig
Suction Temperature should be .............70° F
(Suction Temperature may vary ±5˚ F.)
If Chargemaster® charging device is used, temperature and pressure readings must be accomplished using the charging chart.
IV. INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS
CAUTION: For cooling operation, the recommended
airflow is 350 to 450 cfm per each 12,000 Btuh of rated cooling capacity.
Table 4 shows dry coil air delivery for horizontal discharge units. Tables 5-7 show pressure drops.
NOTE: Be sure that all supply- and return-air grilles are open, free from obstructions, and adjusted properly.
G
Y
W1
W2
UNIT CONTROL BOX
RED
GRN
YEL
THERMOSTAT
AND SUBBASE
C00013
Fig. 13—Control Connections
WARNING: Disconnect electrical power to the unit
before changing blower speed. Electrical shock can cause serious injury or death.
Airflow can be changed by changing the lead connections of the blower motor.
Units 564A036,048, and 060 blower motors are factory wired for low speed operation. Unit 564A042 is factory wired for medium speed operation.
A. For 208/230-v
The motor leads are color-coded as follows:
3-SPEED 2-SPEED
black = high speed black = high speed
blue = medium speed -
red = low speed red = low speed
To change the speed of the blower motor (BM), remove the fan motor speed leg lead from the indoor (evaporator) fan relay (IFR) and replace with lead for desired blower motor speed. Insulate the
removed lead to avoid contact with chassis parts.
TO
UNIT POWER
WIRING
FUSE BLOCK
L2
L1
C
W1
W1
F3
F4
F1
F2
BRN (COMMON)
VIO (STEP 2)
WHT ( STEP 1)
BLK
YEL
YEL
YEL
BLK
BLK
CONTACTOR 2
BRN
YEL
CONTACTOR 1
YEL
YEL
YEL
BRN
YEL
YEL
Fig. 14—Accessory Electric Heater Wiring
—10—
EL 1
EL 2
EL 3
AUTO-LIMIT
BLK
BLK
BLK
C00014
Fig. 15—208/230-3-60 Wiring Diagram
—11—
A06023
Fig. 16—460-3-60 Wiring Diagram
—12—
A06024
OUTDOOR TEMP ° F ° C
115 46 105 41
95 35
85 29
75 24
65 18 55 13
45 7
OUTDOOR TEMP ° F ° C
115 46 105 41
95 35
85 29 75 24
65 18
55 13
45 7
°
Fig. 17—Cooling Charging Chart—564A036 Units
OUTDOOR TEMP ° F ° C
115 46
105 41
95 35
85 29
75 24
65 18
55 13
45 7
°
C00017
°
Fig. 18—Cooling Charging Chart—564A042 Units
OUTDOOR TEMP ° F ° C
125 52 115 46 105 41
95 35
85 29
75 24
65 18
55 13
45 7
°
C00018
C00019
Fig. 19—Cooling Charging Chart—564A048 Units
B. For 460-v Motors
The motor leads are color coded as follows:
3-SPEED (060 ONLY) 2-SPEED
black = high speed black = to purple
- yellow = line
orange = medium speed purple = to black
blue = low speed red = line
To change the speed of the blower motor (BM) from low speed to high speed, removethe red lead from the indoor-fan relay (IFR). Insulate the red lead to avoid contact with any chassis parts. Separate the black lead from the purple lead. Connect the black lead to the IFR. Insulate the purple lead to avoid contact with any chassis parts.
C00020
Fig. 20—Cooling Charging Chart—564A060 Units
V. UNIT CONTROLS
All compressors have the following internal-protection controls.
A. HIGH-PRESSURE RELIEF VALVE
This valve opens when the pressure differential between the low and high side becomes excessive.
B. COMPRESSOR OVERLOAD
This overload interrupts power to the compressor when either the current or internal temperature become excessive, and automati­cally resets when the internal temperature drops to a safe level. This overload may require up to 60 minutes (or longer) to reset; therefore, if the internal overload is suspected of being open, disconnect the electrical power to the unit and check the circuit
—13—
TABLE 3—ELECTRICAL DATA
UNIT 564A
SIZE
036 208/230-3-60 187 254 8.9 64.5 1.5 2.8
042 208/230-3-60 187 254 10.9 73.0 1.5 2.8
048 208/230-3-60 187 254 12.3 73.0 1.5 4.2
060
(See legend following Electrical Data charts)
V-PH-HZ
208/230-3-60 187 254 16.3 114 1.4 5.8
460-3-60 414 508 7.4 64.0 0.7 2.6
VOLTAGE
RANGE
Min Max RLA LRA FLA FLA Nominal kW* FLA MCA MOCP FLA LRA
COMPRESSOR OFM IFM ELECTRIC HEAT POWER SUPPLY DISCONNECT SIZE
-/-
3.8/5.0
7.5/10.0
11.3/15
15.0/20.0
-/-
3.8/5.0
7.5/10
11.3/15
15.0/20.0
-/-
3.8/5.0
7.5/10
11.3/15
15.0/20.0
-/-
3.8/5.0
7.5/10
11.3/15
15.0/20.0
-
5 10 15 20
-/-
10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
-/-
10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
-/-
10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
-/-
10.4/12
23.8/24.1
31.3/36.1
47.7/48.1
-
6 12 18 24
15.4/15.4
16.5/18.5
29.6/33.6
42.6/48.6
55.6/63.6
17.9/17.9
17.9/18.5
29.6/33.6
42.6/48.6
55.6/63.6
21.1/21.1
21.1/21.1
31.3/35.3
44.3/50.4
57.4/65.4
27.5/27.5
27.5/27.5
33.3/37.3
46.3/52.3
59.3/67.3
12.6
12.6
18.3
25.8
33.3
20/20 20/20 30/35 45/50
60/70†
25/25 25/25 30/35 45/50
60/70†
25/25 25/25 35/60 45/60
60/70†
35/35 35/35 35/40 50/60
60/70†
20 20 20 30 35
15/15 15/17 27/31 39/45 51/59 17/17 17/17 27/31 39/45 51/59 21/21 21/21 29/32 41/46 53/60 27/27 27/27 31/34 43/48 55/62
15 15 18 24 31
74
83
87
131
70 71 71 71 71
LEGEND
FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor-Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection
(fuses or HACR-type circuit breaker) NEC — National Electrical Code OFM — Outdoor-Fan Motor RLA — Rated Load Amps UL — Underwriters Laboratories * Single-Point Wiring Connections. † Dual-Point Wiring Connections.
NOTES:
1.2.In compliance with NEC requirements for multimotor and
combination load equipment (refer to NEC Articles 430 and
440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The UL, Canada, units may be fuse or circuit breaker. Unbalanced 3-Phase supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.
% Voltage imbalance
= 100 x
max voltage deviation from average voltage
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
452 + 464 + 455
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 ­(BC) 464 ­(AC) 457 -
452=5v 457=7v
455=2v Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
®
—14—
TABLE 4—DRY COIL AIR DELIVERY* HORIZONTAL DISCHARGE
(DEDUCT 10% FOR 208 VOLT OPERATION)
230 AND 460 VOLT
Unit Motor Speed Air Delivery
Low
036
042
048
060†
2 Speed
060
3 Speed
* Air delivery values are based on operating voltage of 230 v or 460 v, dry coil, without filter or electric heater. Deduct wet coil, filter and electric heater pressure drops to
obtain external static pressure available for ducting. See Tables 5-7. †460-v motors have 2 or 3 speeds (size 060 only). NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below
this point.
2. Dashes indicate portions of the table that are beyond the blower motor capacity or are not recommended.
Med
High
Low
Med
High
Low
High
Low
Med
High
Low
Med
High
Watts 450 435 420 400 380 335 326 311 -
Cfm 1231 1218 1204 1120 1008 950 863 751 -
Watts 470 450 445 410 388 359 338 321 -
Cfm 1302 1264 1205 1163 1081 940 873 783 -
Watts 660 635 610 575 540 505 485 460 -
Cfm 1700 1660 1581 1450 1297 1190 1095 999 -
Watts 478 458 440 411 378 350 327 317 -
Cfm 1303 1270 1224 1179 1126 1022 911 816 -
Watts 481 468 450 438 404 370 338 320 735
Cfm 1310 1280 1241 1181 1110 1022 943 811 -
Watts - 798 678 647 618 578 540 500 -
Cfm - 1736 1688 1618 1510 1421 1309 1187 1060
Watts - - 801 760 730 688 650 600 570
Cfm - - 1898 1841 1757 1682 1564 1429 1365
Watts - - 870 842 818 782 696 632 628
Cfm - - 2000 1903 1799 1718 1625 1446 1333
Watts 890 850 810 790 735 680 580 480 422
Cfm 1834 1820 1791 1762 1703 1640 1415 1159 950
Watts 1040 1018 1000 950 890 835 790 650 580
Cfm 2230 2102 2025 1960 1901 1855 1752 1468 1121
Watts 1073 1038 1001 958 896 840 800 691 575
Cfm 2230 2202 2160 2122 2052 1926 1791 1588 1202
Watts 1058 1008 942 891 860 828 750 700 630
Cfm 2384 2200 2197 2071 1989 1889 1820 1729 1640
Watts 1266 1086 1021 1002 977 924 860 819 700
Cfm 2724 2476 2392 2344 2262 2132 2001 1910 1820
Watts 1301 1216 1197 1127 1058 1011 979 869 870
Cfm 2760 2618 2543 2423 2292 2169 2056 1943 1832
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
External Static Pressure (in. wg)
through the overload with an ohmmeter or continuity tester.
VI. SEQUENCE OF OPERATION
A. FAN OPERATION
The FAN switch on the thermostat controls indoor fan operation. When the FAN switch is placed in the ON position, the IFR (indoor-fan relay) is energized through the G terminal on the thermostat. The normally-open contacts close, which then provide power to the indoor (evaporator) fan motor (IFM). The IFM will run continuously when the FAN switch is set to ON.
When the FAN switch is set to AUTO, the thermostat deenergizes the IFR (provided there is not a call for cooling). The contacts open and the IFM is deenergized. The IFM will be energized only when there is a call for cooling, or if the unit is equipped with accessory electric heat, the indoor-fan motor will also run while he accessory electric heat is energized.
NOTE: 564A060 unit is equipped with a time-delay relay. On this unit, the indoor fan remains on for 30 seconds after G or Y is deenergized.
B. COOLING
On a call for cooling, the compressor contactor (C) and the IFR are energized through the Y and G terminals of the thermostat. On units with a compressor time-delay relay, there is a 5-minute (± 45 sec) delay between compressor starts. Energizing the compressor contactor supplies power to the compressor and the outdoor (condenser) fan motor (OFM). Energizing the IFR provides power to the IFM.
When the need for cooling has been satisfied, the OFM, compres­sor, and IFM (FAN on AUTO) are deenergized. If the unit is equipped with a 30-second delay, the indoor fan will remain energized for 30 seconds after the compressor is deenergized 060 unit only).
C. HEATING
If accessory electric heaters are installed, on a call for heat the thermostat energized the W relay which energizes the electric heaters. The IFR is energized which starts the indoor-fan motor. If the heaters are staged, W2 is energized when the second stage of heating is required. When the need for heating is satisfied, the heater and IFM are deenergized.
MAINTENANCE
To ensure continuing high performance, and to reduce the possi­bility of premature equipment failure, periodic maintenance must be performed on this equipment. This cooling unit should be inspected at least once each year by a qualified service person. To troubleshoot cooling of units, refer to Troubleshooting chart in back of book.
NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a maintenance contract.
WARNING: The ability to properly perform mainte­nance on this equipment requires certain expertise, me­chanical skills, tools and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment, other than those procedures recommended in the User’s Manual. FAILURE TO HEED THIS WARN­ING COULD RESULT IN SERIOUS INJURY, DEATH OR DAMAGE TO THIS EQUIPMENT.
The minimum maintenance requirements for this equipment are as follows:
1. Inspect air filter(s) each month. Clean or replace when necessary.
—15—
TABLE 5—WET COIL PRESSURE DROP
UNIT SIZE
564A
036
042
048
060
AIRFLOW
(CFM)
1000 0.07 1200 0.09 1400 0.11 1600 0.12 1000 0.04 1200 0.06 1400 0.08 1600 0.09 1400 0.07 1600 0.08 1800 0.09 1700 0.07 1800 0.08 2100 0.09 2300 0.10
PRESSURE DROP
(IN. WG)
I. AIR FILTER
NEVER OPERATE THE UNIT WITHOUT A SUITABLE AIR FILTER IN THE RETURN-AIR DUCT SYSTEM. ALWAYS REPLACE THE FILTER WITH THE SAME DIMENSIONAL SIZE AND TYPE AS ORIGINALLY INSTALLED. SEE TABLE 1 FOR RECOMMENDED FILTER SIZES.
Inspect air filter(s) at least once each month and replace (throwaway-type) or clean (cleanable-type) at least twice during each cooling season or whenever the filters become clogged with dust and lint.
Replace filters with the same dimensional size and type as originally provided, when necessary.
II. UNIT TOP REMOVAL (CONDENSER-COIL SIDE)
NOTE: When performing maintenance or service procedures that
require removal of the unit top, be sure to perform all of the routine maintenance procedures that require top removal, including coil inspection and cleaning, and condensate drain pan inspection and cleaning.
TABLE 6—FILTER PRESSURE DROP (IN. WG)
FILTER
UNIT
SIZE
SIZE
036, 042 24 x 24 0.06 0.07 0.08 0.08 0.09 0.09 0.09 0.10 0.11 0.12
048,060 24x30----- - - -0.080.09
UNIT
SIZE
036, 042 24x240.140.15-------
048,060 24 x 30 0.10 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18
500 600 700 800 900 1000 1100 1200 1300 1400
(IN.)
FILTER
SIZE
1500 1600 1700 1800 1900 2000 2100 2200 2300
(IN.)
CFM
CFM
TABLE 7—ACCESSORY ELECTRIC HEAT PRESSURE
DROP (IN. WG)
HEATER KW
5-20
600 800 1000 1200 1400 1600 1800 2000 2200
0.06 0.08 0.10 0.13 0.15 0.18 0.20 0.23 0.25
CFM
2. Inspect indoor coil, outdoor coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness each cooling season. Clean when necessary. For first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.
4. Check electrical connections for tightness and controls for proper operation each cooling season. Service when neces­sary.
5. Check the drain channel in the top cover periodically for blockage (leaves, insects). Clean as needed.
WARNING: Failure to follow these warnings could result in serious injury or death:
1. Turn off electrical power to the unit before performing any maintenance or service on the unit.
2. Use extreme caution when removing panels and parts. As with any mechanical equipment, personal injury can result from sharp edges, etc.
3. Never place anything combustible either on, or in contact with, the unit.
WARNING: Disconnect and tag electrical power to the unit before removing top. Failure to adhere to this warning could cause serious injury or death.
Only qualified service personnel should perform maintenance and service procedures that require unit top removal. Refer to the following top removal procedures:
1. Remove 7 screws on unit top cover surface. (Save all screws.)
2. Remove 2 screws on unit top cover flange. (Save all screws.)
3. Lift top from unit carefully. Set top on edge and make sure that top is supported by unit side that is opposite duct (or plenum) side.
4. Carefully replace and secure unit top to unit, using screws removed in Steps 1 and 2, when maintenance and/or service procedures are completed.
III. EVAPORATOR BLOWER AND MOTOR
For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually.
WARNING: Disconnect and tag electrical power to the unit before cleaning the blower wheel. Failure to adhere to this warning could cause serious injury or death.
To clean the blower wheel:
1. Access the blower assembly as follows:
a. Remove top access panel.
b. Remove 3 screws that hold blower orifice ring to blower
housing. Save screws.
c. Loosen setscrew(s) which secure wheel to motor shaft.
2. Remove and clean blower wheel as follows:
a. Lift wheel from housing. When handling and/or cleaning
blower wheel, be sure not to disturb balance weights (clips) on blower wheel vanes.
b. Remove caked-on dirt from wheel and housing with a
brush. Remove lint and/or dirt accumulations from wheel and housing with vacuum cleaner, using a soft brush attachment. Remove grease and oil with a mild solvent.
—16—
c. Reassemble blower into housing. Place upper orifice ring
on blower to judge location of the blower wheel. Blower wheel should be approximately 0.2-in. below bottom of orifice ring when centered correctly. Be sure setscrews are tightened on motor and are not on round part of shaft.
d. Set upper orifice ring in place with 3 screws removed in
Step 1.
e. Replace top access panel.
IV. CONDENSER COIL, EVAPORATOR COIL, AND CONDENSATE DRAIN PAN
Inspect the condenser coil, evaporator coil, and condensate drain pan at least once each year. Proper inspection and cleaning requires the removal of the unit top. See Unit Top Removal section above.
The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Remove all obstructions (including weeds and shrubs) that interfere with the airflow through the condenser coil. Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using a soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent-and-water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray condenser-coil fins from inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to flush all dirt and debris from the unit base.
Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain tube with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain tube is restricted, clear it with a ‘‘plumbers snake’’ or similar probe device. Ensure that the auxiliary drain port above the drain tube is also clear.
V. CONDENSER FAN
CAUTION: Keep the condenser fan free from all ob-
structions to ensure proper cooling operation. Never place articles on top of the unit. Damage to unit may result.
3.125 in.
C00021
Fig. 21—Condenser-Fan Adjustment
NOTE: Refer to the Sequence of Operation section in this
publication, as an aid in determining proper control operation.
VII. REFRIGERANT CIRCUIT
Inspect all refrigerant tubing connections and the unit base for oil accumulations annually. Detecting oil generally indicates a refrig­erant leak.
If oil is detected or if low cooling performance is suspected, leak-test all refrigerant tubing using an electronic leak-detector, or liquid-soap solution. If a refrigerant leak is detected, refer to Check for Refrigerant Leaks section in this publication.
If no refrigerant leaks are found and low cooling performance is suspected, refer to Refrigerant Charge section in this publication.
VIII. EVAPORATOR AIRFLOW
The cooling airflow does not require checking unless improper performance is suspected. If a problem exists, be sure that all
supply- and return-air grilles are open and free from obstructions, and that the air filter is clean. When necessary, refer to Indoor
Airflow and Airflow Adjustments section in this publication to check the system airflow.
IX. METERING DEVICES
Refrigerant metering devices are fixed orifices and are located in the inlet header to the evaporator coil.
X. LIQUID LINE STRAINER
The liquid line strainer (to protect metering device) is made of wire mesh and is located in the liquid line on the inlet side of the metering device.
1. Shut off unit power supply.
2. Remove condenser-fan assembly (grille, motor, motor cover, and fan) by removing screws and flipping assembly onto unit top cover.
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 21.
5. Tighten setscrews.
6. Replace condenser-fan assembly.
VI. ELECTRICAL CONTROLS AND WIRING
Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit.
Remove the top panel to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections. If any smoky or burned connections are noticed, disassemble the connection, clean all the parts, restrip the wire end and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, replace all the panels. Start the unit, and observe at least one complete cooling cycle to ensure proper operation. If discrepancies are observed in operating cycle, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumenta­tion. Refer to the unit wiring label when making these checkouts.
—17—
SYMPTOM CAUSE REMEDY
Compressor and condenser fan will not start.
Compressor will not start but condenser fan runs.
Compressor cycles (other than normally sat­isfying thermostat).
Compressor operates continuously.
Excessive head pressure.
Head pressure too low.
Excessive suction pressure.
Suction pressure too low.
TABLE 8 — TROUBLESHOOTING — COOLING
Power failure Call power company. Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker. Defective thermostat, contactor, transformer, or control relay Insufficient line voltage Determine cause and correct. Incorrect or faulty wiring Check wiring diagram and rewire correctly.
Thermostat setting too high
Faulty wiring or loose connections in compressor circuit Compressor motor burned out, seized, or internal overload open Defective run/start capacitor, overload, start relay Determine cause and replace.
One leg of 3-phase power dead
Refrigerant overcharge or undercharge
Defective compressor Replace and determine cause. Insufficient line voltage Determine cause and correct. Blocked condenser Determine cause and correct. Defective run/start capacitor, overload or start relay Defective thermostat Replace thermostat. Faulty condenser-fan motor or capacitor Replace. Restriction in refrigerant system Locate restriction and remove. Dirty air filter Replace filter. Unit undersized for load Decrease load or increase unit size. Thermostat set too low Reset thermostat. Low refrigerant charge Locate leak, repair, and recharge. Leaking valves in compressor Replace compressor.
Air in system
Condenser coil dirty or restricted Clean coil or remove restriction. Dirty air filter Replace filter. Dirty condenser coil Clean coil. Refrigerant overcharged Recover excess refrigerant.
Air in system
Condenser air restricted or air short-cycling Determine cause and correct. Low refrigerant charge Check for leaks, repair and recharge. Compressor valves leaking Replace compressor. Restriction in liquid tube Remove restriction. High heat load Check for source and eliminate. Compressor valves leaking Replace compressor. Refrigerant overcharged Recover excess refrigerant. Dirty air filter Replace filter. Low refrigerant charge Check for leaks, repair and recharge. Metering device or low side restricted Remove source of restriction.
Insufficient evaporator airflow
Temperature too low in conditioned area Reset thermostat. Outdoor ambient below 40° F Install low-ambient kit. Field-installed filter-drier restricted Replace.
Replace component.
Lower thermostat setting below room tempera­ture.
Check wiring and repair or replace.
Determine cause. Replace compressor.
Replace fuse or reset circuit breaker. Determine cause. Recover refrigerant, evacuate system, and re­charge to capacities shown on nameplate.
Determine cause and replace.
Recover refrigerant, evacuate system, and re­charge.
Recover refrigerant, evacuate system, and re­charge.
Increase air quantity. Check filter — replace if necessary.
—18—
START-UP CHECKLIST (REMOVE AND STORE IN JOB FILE)
I. PRELIMINARY INFORMATION
Model No. ...................................................................................................................................................................................................................
Serial No. ....................................................................................................................................................................................................................
Date .............................................................................................................................................................................................................................
Technician ...................................................................................................................................................................................................................
II. PRE-START-UP
___ Verify that all packing materials have been removed from unit
___ Verify that condensate connection is installed per installation instructions
___ Check all electrical connections and terminals for tightness
___ Check that indoor (evaporator) air filter is clean and in place
___ Verify that unit installation is level
___ Check fan wheel and propeller for location in housing and setscrew tightness
III. START-UP
Supply Voltage L1-L2 __________ L2-L3 _________ L3-L1 __________
Compressor Amps L1 __________ L2 _________ L3 __________
Indoor (Evaporator) Fan Amps __________
TEMPERATURE
Outdoor (Condenser) Air Temperature __________ DB
Return-Air Temperature __________ DB __________ WB
Cooling Supply Air __________ DB __________ WB
PRESSURES
Refrigerant Suction __________ psig
Suction Line Temp* __________
Refrigerant Discharge __________ psig
Discharge Temp† __________
___ Verify refrigerant charge using charging tables
* Measured at suction inlet to compressor † Measured at liquid line leaving condenser
—19—
© 2006 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231
—20—
Printed in U.S.A. Catalog No. II 564A-36-1
Loading...