Heater
High-Voltage
Ignitor
Induced-Draft Motor
Indoor (Evaporator) Fan Contactor
Indoor (Evaporator) Fan
Circuit Breaker
Indoor (Evaporator) Fan Motor
Indoor (Evaporator) Fan Relay
Integrated Gas Controller
Light
Light-Emitting Diode
Liquid Line Solenoid
Lockout Relay
Low-Pressure Switch
Limit Switch
Mixed-Air Thermostat
Main Gas Valve
National Electrical Code
Neutral
Outdoor-Air Thermostat
Outdoor (Condenser) Fan Contactor
Outdoor (Condenser) Fan Motor
Overcurrent Protection
Plug Assembly
Primary
Quadruple Terminal
Rollout Switch
Sensor
Solenoid Relay
Accessory or Optional Wirin
To indicate common poten-
tial only, not to represent
wiring.
—2—
OPERATING SEQUENCE
Cooling, Units Without Economizer
When thermos tat calls for cool ing, terminals G and Y1 are
energized. The indoor (evaporator) fan contactor (IFC) and
compressor contactor no. 1 (C1) are energized, and
evaporator-fan motor (IFM), compressor no. 1 and condenser
fan(s) start. The condenser-fan motor(s) runs continuously
while unit is c ooli ng. When t he th e rmo s tat call s fo r a sec on d
stage of cooling by energizi ng Y2, comp ressor con tacto r no. 2
(C2) is energized and compressor no. 2 starts.
Heating, Units Without Economizer (579F180-300)
NOTE: The 579F180-300 units have 2 stages of heat.
When the thermostat calls for heating, power is sent to W on
the IGC (integrated gas unit controller) board. An LED
(light-emitting diode) on the IGC board will be on during
normal operation. A check is ma de to ensure that the rol lout
switch and limit switch are closed. The induced-draft motor
is then energized, and when speed is proven with the hall
effect sensor on the motor, the ignition activation period
begins. The burners will ignite within 5 seconds.
If the burners do not light, there is a 22-second delay before
another 5-second attempt. If the burners still do not light,
this sequence is repeated for 1 5 minutes. After the 15 minutes have elapsed, if the burners still have not lighted, heating is locked out. To reset the control, br eak 24-v power to
the thermostat.
When ignition occ urs the IGC board will continue to mo nitor the condition of the rollout and limit switches, the hall
effect sensor, as well as the flame sensor. If the unit is controlled through a room thermostat set for fan auto., 45 seconds after ignition occurs, the indoor-fan motor will be
energized. If for some reason the overtemperature limit
opens prior to the start of the indoor fan blower, on the next
attempt, the 45-second delay will b e shortened to 5 seconds
less than the time from initiation of heat to when the limit
tripped. Gas will not be interrupted to the burners and heating will continue. Once modified, the fan on delay will
not change back to 45 seconds unless power is reset to the
control.
When additional heat is required, W2 closes and initiates
power to the second stage of the main gas valve. When the
thermostat is satisfied, W1 and W2 open and the gas valve
closes, interrupting the flow of gas to the main burners. If
the call for W1 lasted less than 1 m inute, the heating cycle
will not terminate until 1 minute after W1 became active. If
the unit is controlled through a ro om thermostat set for fan
auto., the indoor-fan motor will continue to operate for an
additional 45 seconds then stop. If the overtemperature limit
opens after the indoor motor is stopped within 10 minutes of
W1 becoming inactive, on the next cycle the time will be
extended by 15 seconds. The maximum delay is 3 minutes.
Once modified, the fan off delay will not change back to
45 seconds unless power is reset to the control.
An LED indicator is provided on the IG C to monitor operation. The IGC is located by removing the side panel and
viewing the IGC through the view port located in the control
box access panel. During normal operation, the LED is continuously on.
Heating, Units Without Economizer (559F180-300, If Accessory or Optional Heater is Installed)
Upon a call for heating through terminal W1, IFC and
heater contactor no. 1 (HC1) are energized. On units
equipped for 2 stages of heat, when additional heat is
needed, HC2 is energized through W2.
Cooling, Units With Economizer
Upon a call for cooling, when outdoor ambient is above the
temperature control setting, the economizer damper moves
to VENT position. The co mpres sors an d evapo rator a nd condenser fans energize.
Upon a first call for cooli ng, when outdoor ambient is be low
the temperature control setting, the evaporator fan starts
and the economizer opens to maintain 53 F leaving-air temperature. The compressors remain off.
Upon a second-stage call for cooling, compressor no. 1 is
energized and mechanical cooling is integrated with economizer cooling. If the outdoor-air temperature drops below
50 F, a cooling lockout switch prevents the compressors from
running.
When supply-air temperature drops below a fixed set point,
the economizer damp er modulate s to maintain the tempera ture at the fixed set point.
Freeze protection thermostats (FPT) are located on the evaporator coil. They detect frost build-up and turn the c ompressors off locking them out an d re qu ir ing a man ual res et. Onc e
frost has melted, the compressors can be reenergized.
Heating, Units With Economizer
Outdoor-air damper stays at VENT position while evaporator fan is operating. Refer to Heating, Units Without
Economizer (579F180-300) and Heating, Units Without
Economizer (559F1 80-300 , If Ac cessor y or O ptio nal He ater i s
Installed) sections on this page for remainder of operating
sequence.
—3—
NOTES FOR FIG. 1, 3, 5, 7
1. Compressor and/or fan motors are thermally protected.
Three-phase motors are protected against primary single phasing
conditions.
2. If any of the original wire furnished must be replaced, it must be
replaced with type 90 C or its equivalent.
3. On 208/230-v unit, TRAN1 is factory wired to ORN lead for 230-v
power supply. If unit is to be run on 208-v power supply, TRAN1 must
be rewired. Disconnect the BLK wire on TRAN1 and connect wire to
208-v RED wire. Insulate 230-v ORN wire.
5. Indoor fan circuit breaker must trip amps value is equal to or less
than 140% FLA.
NOTES FOR FIG. 2, 4, 6, 8
1. Compressor and/or fan motors are thermally protected.
Three-phase motors are protected against primary single phasing
conditions.
2. If any of the original wire furnished must be replaced, it must be
replaced with type 90 C or its equivalent.
3. Jumpers are omitted when unit is equipped with an economizer.
5. Indoor fan circuit breaker must trip amps value is equal to or less
than 140% FLA.
NOTES FOR FIG. 9, 11, 13, 15
1. Compressor and/or fan motors are thermally protected.
Three-phase motors are protected against primary single phasing
conditions.
2. If any of the original wire furnished must be replaced, it must be
replaced with type 90 C or its equivalent.
3. Jumpers are omitted when unit is equipped with an economizer.
4. Indoor fan circuit breaker must trip amps value is equal to or less
than 140% FLA.
5. On 208/230-v unit, TRAN1 is factory wired to ORN lead for 230-v
power supply. If unit is to be run on 208-v power supply, TRAN1 must
6. The CLO locks out the compressor to prevent short cycling on compressor overload and safety devices. Before replacing CLO, check
these devices.
7. Jumpers are omitted when unit is equipped with an economizer.
8. Number(s) indicate the line location of used contacts. A bracket over
2 numbers signifies a single-pole, double-throw contact. An underlined number signifies a normally closed contact. A plain (no line)
number signifies a normally open contact.
6. The CLO locks out the compressor to prevent short cycling on compressor overload and safety devices. Before replacing CLO, check
these devices.
7. Number(s) indicate the line location of used contacts. A bracket over
2 numbers signifies a single-pole, double-throw contact. An underlined number signifies a normally closed contact. A plain (no line)
number signifies a normally open contact.
be rewired. Disconnect the BLK wire on TRAN1 and connect wire to
208-v RED wire. Insulate 230-v ORN wire.
6. The CLO locks out the compressor to prevent short cycling on compressor overload and safety devices. Before replacing CLO, check
these devices.
7. Number(s) indicate the line location of used contacts. A bracket over
2 numbers signifies a single-pole, double-throw contact. An underlined number signifies a normally closed contact. A plain (no line)
number signifies a normally open contact.
NOTES FOR FIG. 10, 12, 14, 16
1. Compressor and/or fan motors are thermally protected.
Three-phase motors are protected against primary single phasing
conditions.
2. If any of the original wire furnished must be replaced, it must be
replaced with type 90 C or its equivalent.
3. Jumpers are omitted when unit is equipped with an economizer.
4. Indoor fan circuit breaker must trip amps value is equal to or less
than 140% FLA.
5. If unit is to be run on 460-v power supply, TRAN1 must be wired to
BLK wire.
6. The CLO locks out the compressor to prevent short cycling on compressor overload and safety devices. Before replacing CLO, check
these devices.
7. Number(s) indicate the line location of used contacts. A bracket over
2 numbers signifies a single-pole, double-throw contact. An underlined number signifies a normally closed contact. A plain (no line)
number signifies a normally open contact.
—4—
Fig. 1 — Label Diagram — 559F180, 208/230-3-60 Units
—5—
Fig. 1 — Label Diagram — 559F180, 208/230-3-60 Units (cont)
—6—
Fig. 2 — Label Diagram — 559F180, 460-3-60 Units
—7—
Fig. 2 — Label Diagram — 559F180, 460-3-60 Units (cont)
—8—
Fig. 3 — Label Diagram — 559F216, 208/230-3-60 Units
—9—
Fig. 3 — Label Diagram — 559F216, 208/230-3-60 Units (cont)
—10—
Fig. 4 — Label Diagram — 559F216, 460-3-60 Units
—11—
Fig. 4 — Label Diagram — 559F216, 460-3-60 Units (cont)
—12—
Fig. 5 — Label Diagram — 559F240, 208/230-3-60 Units
—13—
Fig. 5 — Label Diagram — 559F240, 208/230-3-60 Units (cont)
—14—
Fig. 6 — Label Diagram — 559F240, 460-3-60 Units
—15—
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.