Bryant 559B User Manual

Bryant
Airconditioning Company
installation instructions
SELF-CONTAINED ELECTRIC COOLING UNITS
559B
Sizes 024, 030,
Series E
The Model 559B unit is a complete cooling system, with provisions for addition of accessory electric heaters. Units are air cooled, designed for outdoor installation, and may be connected into existing duct system. Required con nections include air ducts, condensate drain, and high- and low-voltage wiring. A field-supplied filter box must be in stalled in return air duct.
When optional electric heaters are being installed, see instructions beginning on page 8 of this publication for procedures.

TRANSPORTATION DAMAGE

File claim with shipping company if shipment is damaged or incomplete. Move unit to installation site in upright position.
Important—Read Before Installing
1. Check all local codes and ordinances that could affect installation of equipment.
2. Be sure power supply available (voltage, hertz, and phase) corresponds to that specified on unit rating plate.
3. Check electrical service provided by utility for building to be sure service capacity is sufficient to handle load imposed by unit.
4. Refer to dimensional drawing for locations of elec trical, condensate drain, and duct connections before setting unit in place.
Installation consists of the following steps;

I. Locating and Mounting Unit

II. Connecting Ductwork
III. Connecting Condensate Drain
IV. Electrical Connections
V. Startup and Adjustment
VI. Maintenance
VII. Instructions to Owner
I. LOCATING AND MOUNTING UNIT
Place unit on a solid, level, concrete pad. Pad should be minimum of 3 inches high, extend about 6 inches from both sides and front of unit, and must not extend more than 1 inch from back (duct side) of unit. Insert sheet of tar-base construction felt paper between unit and pad. Unit does not need to be secured to pad because there are no refrigerant lines extending outside of unit that could be damaged.
Be sure grass and shrubs do not interfere with condenser airstream. If necessary, extend gravel apron around pad.
Place duct side against building structure so ductwork can not be seen from outside.
When installing unit, allow sufficient space for condenser airflow clearance, wiring, and servicing unit. See Figure 2. Position unit so water from roof will not pour directly on top of unit. Do not locate unit under eaves.
Recornmended minimum service clearance; 18 inches all sides except duct side
0 inches bottom 36 inches top
Cancels: 39559D47
Figure 1—Model 559B
II. CONNECTING DUCTWORK
39559DP61
6/1/74
Flanges are provided on unit for duct connections. See Figure 2 for unit connection sizes and locations. Use
weathertight connectors between ductwork and unit to prevent transmission of vibration.
Ductwork should be selected and sized according to Part 2 of Bryant Air Distribution Manual. All ductwork in un conditioned space should be insulated and weatherproof if used outdoors.
t'.\l”JT()\; D'l nol opi-rau* unit longer than .“) minutes
Filters must be located in return airstream. Recommended sizes are shown in Table II. When electric heaters are installed, use an asbestos (or similar heat-resistant ma terial) connector between ductwork and unit supply duct connection.
When flexible duct is used, friction loss in straight runs is approximately double amount found in Bryant Air Distribution Manual, Part 2, for air duct design.
It is recommended that rigid elbows should be used for bends. If rigid elbows are not used, ratio of centerline bend, radius to duct diameter (R/D) should be at least 1.5 for minimum friction loss. If rectangular ducts are used over unit round connections, unit entering pressure loss must be considered when designing system.
\\ \KMN(i l><> iiol •lull hull-- III ,11-1.1 sliiiMM in
It is also recommended that abrupt duct expansions and contractions be avoided.
NOTE: Mobile home duct kits (which include a return air filter box, filter, floor grille, flexible duct sections, and in
stallation hardware) are available for mobile home in stallation. See your Bryant Distributor.
Mobile Home Duct Design
Design duct system to have friction loss of between 0.25 in. wc and 0.70 in. wc for proper unit operation. Insulated flexible ductwork (1-ft inside diameter) of weatherproof type is recommended. Do not reduce duct inside diameter below 1 ft. Combined length of supply and return ducts should not exceed 20 ft, with minimum supply duct length
^CONDENSER AIR DISCHARGE
20" DIAMETER
, 1
DIMENSIONS IN INCHES
SIZE
024
C
17-5/8 030 17-5/8 12 036 19-5/8 14 14 042 27-5/8 14 048 27-5/8
D
12
14
E F G H
12 10-1/4 14-1/2 12 10-1/4 14-1/2
11-1/4 16-1/2 14 12-1/4 14
12-1/4 24-1/2
24-1/2 9-5/8
8-5/8 25-5/16 8-5/8 8-5/8 25-5/16
9-5/8
J
25-5/16
24-5/16 24-5/16
LOW-VOLT CONN (2) )î:NOCKOUTS
’(RUBBER TUBE)
Figure 2 — Dimensional Drawing
Q RETURN AIR FLOOR GRILLE
(T) 20x25 xl DISPOSABLE FILTER
Q) RETURN AIR FILTER BOX
(4) QUICK-CONNECT COLLAR
(5) flexible DUCT (i) TAP-IN COLLAR
DETAIL A
(RETURN ASSEMBLY)
DETAIL B
(SUPPLY ASSEMBLY)
Figure 3 — Typical Installation
-2-
--------
CONTROL WIRING
--------
POWER WIRING
CONDENSER AIRFLOW EVAPORATOR AIRFLOW
MODEL
Rated Cooling Capacity* Btuh Nameplate Voltage-Freq-Phase Operating Voltage Range
Compressor Motor FLA
Locked Rotor Amps
Condenser Fan Motor** HP
Full Load Amps
Evaporator Blower Motor** HP
Full Load Amps
Rated Total Power Consumption KWH
Electrical Connections
Unit Full Load Amps
Unit Ampacity for Electrical Conductor Sizing Min Branch Circuit Wire Size 60°C Temp Rating Copper
Conductor*** AWG No. Max Line Length**** Ft Largest Wire Size Line-Voltage Con nections Will Accommodate AWG No. Max Branch Circuit Fuse Size Amps
Refrigerant type/lbs-ozs
Evaporator Airflow CFM
Approximate Shipping Weight lbs

TABLE I—RATINGS AND PERFORMANCE

559B-024-E
24,000
230-60-1
207-254 207-254
15.7 19.5 72 88 1/5 1/5
1.3
1/4 1/3
2.0
3.5
19.0 23.9
22.9 28.8
10 10
119 95
4 4
25
R-22/2-6
900 1125 265
230-60-1 208-60-3
R-22/3-0
285
1.3 1.4
3.1
4.6
30
559B-030-E
30,000
187-229
12.3 11.1 70
1/5
1/3
2.9
4.6
16.6
19.7
12 12 8 10 92 110
4
25 20 40 30 25
R-22/3-0
1125 1125 1350
285 285 305 305
230-60-3 230-60-1
207-254 207-254
60 100 80
1/5
1.3 1.8 2.1 1/3 1/3 1/3
3.1 3.6 3.8
4.6
15.5
18.3 35.4 24.9
4
R-22/3-0
24.0
1/4
5.7
29.4
122 115
4 4
R-22/3-10
5S9B-036-E
35,000
208-60-3
187-229
15.2
1/4
5.7
21.1
R-22/3-10
1350 1350
R-22/3-10
230-60-3
207-254
14.0 70
1/4
1.8 1/3
3.6
5.7
19.4
22.9
10
142
4
305
MODEL
Nameplate Voltage-Freq-Phase Operating Voltage Range
Locked Rotor Amps
Full Load Amps
Full Load Amps
Electrical Connections
Unit Full Load Amps Unit Ampacity for Electrical Conductor Sizing 37.4 Min Branch Circuit Wire
Size 60°C Temp Rating Copper
Max Line Length**** Ft Largest Wire Size Line-Voltage Con nections Will Accommodate AWG No. Max Branch Circuit Fuse Size Amps
Rated Cooling Capacity* Bfuh
Compressor Motor FLA
Condenser Fan Motor** HP
Evaporator Blower Motor** HP
Rated Total Power Consumption KWH
Conductor*** AWG No.
Refrigerant type/lbs-ozs Evaporator Airflow CFM
Approximate Shipping Weight lbs 345
230-60-1
R-22/4-13 R-22/4-13
42,000 . 41,000 42,000 48,000
207-254
25.0 111
1/4 1/4 1/4
1.8 1/2
4.2
6.3 6.3
31.0
8 10
116
4
40 30
1570 1570 1570 1800
559B-042-E
208-60-3 230-60-3
187-229
16.9 15.3 92
2.1 1/2 1/2 1/2 1/2 1/2 1/2
4.4
23.4
27.6
103
4 4 4
345 345
207-254
92 118 90 78.5 39.3
1.8
4.2 4.9 5.1 4.9 4.9
6.3 7.2 7.2 7.2
21.3
25.1 40.0 33.3
10 8
130
30
R-22/4-13
230-60-1 208-60-3
207-254 187-229
26.5
1/4
1.9
33.3
108
45
R-22/4-11
367
559B-048-E
20.9 18.0 9.1
1/4 1/4
2.1 1.8 1.8
28.1 24.7
8 10 12
137
4
35 30 20
R-22/4-11 R-22/4-11 R-22/4-11
1800 1800 1800
367 367 367
*Rated in Accordance with ARI Standard 210-66.
**Condenser fan and evaporator motors are single phase.
***If other than 60 °C copper conductor is used, determine size from unit ampacity and the National Electrical Code. Voltage drop of
wire must be less than 2% of unit rated voltage.
****Wire length shown is measured one way along the wire path between unit and service panel for minimum voltage drop.
230-60-3
207-254 414-508
29.2 18.1
112 225
4
460-60-3
1/4
7.2
15.8
4
Unit Size Disposable Permanent

TABLE II—FILTER DIMENSIONS

Minimum Filter Size or Equivalent, Inches
024 030 16x20x1 20x20x1 12x20x1 16x20x1 20x20x1 20x20x1 20x25x1
036
20x25x1
042
25x25x1
048
25x25x1
X = Size 024, 030, & 036................................................................................1-3/4 in.
Size 042 & 048 ............................................................................................2 in.
Figure 4—Required Condenser
Fan Position
-3-
DO NOT DRILL HOLES IN SHADED AREA WHEN INSTALUNG RECTANGULAR DUCTS
Figure 5
of 6 ft and minimum return duct length of 3 ft. Do not operate unit longer than 5 minutes without ductwork. Refer to Bryant Air Distribution Manual, Part 2, for air duct design.
Flanges are provided on unit for duct connections. See Figure 2 for connection sizes and Figure 3 for typical duct installation.
Supply Air Connection in Mobile Home
Connect flexible duct to unit supply air connection at ap proximate center of trailer. Install turning vanes in main supply duct directly above elbow connection, using stan dard sheet metal practices.

Return Air Connection in Mobile Home

Purchase or field-fabricate a filter box. Suggested minimum filter box dimensions are shown in Figure 6. At ap proximate center of trailer, cut a return air opening in floor. Locate opening where it will not be obstructed by furniture. Size opening to accept filter box. Cut a hole in carpet or floor covering to sarne size as filter box floor opening. En sure electrical wiring or main structural supports are not accidentally cut. Insert filter box thru floor opening. Weather-seal floor connection in accordance with good con struction practice. Insert filter in filter box, and cover with return air grille.
Connect flexible duct to filter box. Extend duct from filter box to unit return air connection. When existing furnace is kept in system: During heating season, insert sheet metal panel beneath return air grille and over filter to prevent air movement thru cooling unit.
When furnace is removed from system, blank-off original furnace floor connection.

III. CONNECTING CONDENSATE DRAIN

The unit is designed to dispose of accumulated water through condensate drain hose on unit. It is recommended that a drain line that includes a trap should be installed to avoid possibility of abnormal negative fan pressure preven ting complete drainage of condensate. If drain connection is not practical or feasible, a factory-supplied condensate trap (taped at supply duct connection) must be installed for
proper drainage. See Figure 7.

IV. ELECTRICAL CONNECTIONS

Field wiring must comply with National Electrical Code and local codes. Install a branch circuit fused disconnect of adequate size to handle unit current load. Provide separate fused disconnect for electric heaters.
Voltage to unit during operation must be within ±10% of voltage indicated on rating plate.
W.-VRNI.N'Ci: Failure berause of operation of unit on im
proper line voltage constitutes abuse and is not coveretl by
Brvant warr.mtv.
Figure 6 — Minimum Dimensions-Return
Air Filter Box
Connect line-power leads from fused disconnect(s) to line power leads located in junction box. Screw connectors, which are suitable for aluminum or copper wires, are provided. See Figures 8 and 9. Tape screw connectors after connections are completed. Table I is provided to assist in staller in selecting proper wire and fuse sizes.
Thermostat connections are made to color-coded wires located in junction box. See Figures 8 and 9. Be sure color­coded wires not used are adequately and individually taped at end.

Rgure 7 —Condensate Drain Connection

NOTE: When using Model 883 (P/N 34427D03O) ther mostat with optional electric heat package, W and J ter minals on thermostat must be jumpered to ensure fan operation when thermostat is in HEAT position.

V. STARTUP AND ADJUSTMENT

Before starting system, make an initial overall inspection.
1. Check to be sure all wiring connections, including fac tory connections, have been completed and are tight.
2. Inspect all supply ducts and grilles to ensure proper adjustment.
3. Check to ensure air filters are in place.
4. Inspect refrigerant piping for damage or leaks that might have occurred during shipment.
5. Check for correct position of condenser fan blade in fan orifice plate. See Figure 4 for setting.
6. Check to ensure all tools and loose parts have been removed.
7. Check to ensure all panels and covers are in place.
Following initial inspection, unit may be started and ad-
-4-
Loading...
+ 8 hidden pages