Bryant 559B User Manual

Bryant
Airconditioning Company
installation instructions
SELF-CONTAINED ELECTRIC COOLING UNITS
559B
Sizes 024, 030,
Series E
The Model 559B unit is a complete cooling system, with provisions for addition of accessory electric heaters. Units are air cooled, designed for outdoor installation, and may be connected into existing duct system. Required con nections include air ducts, condensate drain, and high- and low-voltage wiring. A field-supplied filter box must be in stalled in return air duct.
When optional electric heaters are being installed, see instructions beginning on page 8 of this publication for procedures.

TRANSPORTATION DAMAGE

File claim with shipping company if shipment is damaged or incomplete. Move unit to installation site in upright position.
Important—Read Before Installing
1. Check all local codes and ordinances that could affect installation of equipment.
2. Be sure power supply available (voltage, hertz, and phase) corresponds to that specified on unit rating plate.
3. Check electrical service provided by utility for building to be sure service capacity is sufficient to handle load imposed by unit.
4. Refer to dimensional drawing for locations of elec trical, condensate drain, and duct connections before setting unit in place.
Installation consists of the following steps;

I. Locating and Mounting Unit

II. Connecting Ductwork
III. Connecting Condensate Drain
IV. Electrical Connections
V. Startup and Adjustment
VI. Maintenance
VII. Instructions to Owner
I. LOCATING AND MOUNTING UNIT
Place unit on a solid, level, concrete pad. Pad should be minimum of 3 inches high, extend about 6 inches from both sides and front of unit, and must not extend more than 1 inch from back (duct side) of unit. Insert sheet of tar-base construction felt paper between unit and pad. Unit does not need to be secured to pad because there are no refrigerant lines extending outside of unit that could be damaged.
Be sure grass and shrubs do not interfere with condenser airstream. If necessary, extend gravel apron around pad.
Place duct side against building structure so ductwork can not be seen from outside.
When installing unit, allow sufficient space for condenser airflow clearance, wiring, and servicing unit. See Figure 2. Position unit so water from roof will not pour directly on top of unit. Do not locate unit under eaves.
Recornmended minimum service clearance; 18 inches all sides except duct side
0 inches bottom 36 inches top
Cancels: 39559D47
Figure 1—Model 559B
II. CONNECTING DUCTWORK
39559DP61
6/1/74
Flanges are provided on unit for duct connections. See Figure 2 for unit connection sizes and locations. Use
weathertight connectors between ductwork and unit to prevent transmission of vibration.
Ductwork should be selected and sized according to Part 2 of Bryant Air Distribution Manual. All ductwork in un conditioned space should be insulated and weatherproof if used outdoors.
t'.\l”JT()\; D'l nol opi-rau* unit longer than .“) minutes
Filters must be located in return airstream. Recommended sizes are shown in Table II. When electric heaters are installed, use an asbestos (or similar heat-resistant ma terial) connector between ductwork and unit supply duct connection.
When flexible duct is used, friction loss in straight runs is approximately double amount found in Bryant Air Distribution Manual, Part 2, for air duct design.
It is recommended that rigid elbows should be used for bends. If rigid elbows are not used, ratio of centerline bend, radius to duct diameter (R/D) should be at least 1.5 for minimum friction loss. If rectangular ducts are used over unit round connections, unit entering pressure loss must be considered when designing system.
\\ \KMN(i l><> iiol •lull hull-- III ,11-1.1 sliiiMM in
It is also recommended that abrupt duct expansions and contractions be avoided.
NOTE: Mobile home duct kits (which include a return air filter box, filter, floor grille, flexible duct sections, and in
stallation hardware) are available for mobile home in stallation. See your Bryant Distributor.
Mobile Home Duct Design
Design duct system to have friction loss of between 0.25 in. wc and 0.70 in. wc for proper unit operation. Insulated flexible ductwork (1-ft inside diameter) of weatherproof type is recommended. Do not reduce duct inside diameter below 1 ft. Combined length of supply and return ducts should not exceed 20 ft, with minimum supply duct length
^CONDENSER AIR DISCHARGE
20" DIAMETER
, 1
DIMENSIONS IN INCHES
SIZE
024
C
17-5/8 030 17-5/8 12 036 19-5/8 14 14 042 27-5/8 14 048 27-5/8
D
12
14
E F G H
12 10-1/4 14-1/2 12 10-1/4 14-1/2
11-1/4 16-1/2 14 12-1/4 14
12-1/4 24-1/2
24-1/2 9-5/8
8-5/8 25-5/16 8-5/8 8-5/8 25-5/16
9-5/8
J
25-5/16
24-5/16 24-5/16
LOW-VOLT CONN (2) )î:NOCKOUTS
’(RUBBER TUBE)
Figure 2 — Dimensional Drawing
Q RETURN AIR FLOOR GRILLE
(T) 20x25 xl DISPOSABLE FILTER
Q) RETURN AIR FILTER BOX
(4) QUICK-CONNECT COLLAR
(5) flexible DUCT (i) TAP-IN COLLAR
DETAIL A
(RETURN ASSEMBLY)
DETAIL B
(SUPPLY ASSEMBLY)
Figure 3 — Typical Installation
-2-
--------
CONTROL WIRING
--------
POWER WIRING
CONDENSER AIRFLOW EVAPORATOR AIRFLOW
MODEL
Rated Cooling Capacity* Btuh Nameplate Voltage-Freq-Phase Operating Voltage Range
Compressor Motor FLA
Locked Rotor Amps
Condenser Fan Motor** HP
Full Load Amps
Evaporator Blower Motor** HP
Full Load Amps
Rated Total Power Consumption KWH
Electrical Connections
Unit Full Load Amps
Unit Ampacity for Electrical Conductor Sizing Min Branch Circuit Wire Size 60°C Temp Rating Copper
Conductor*** AWG No. Max Line Length**** Ft Largest Wire Size Line-Voltage Con nections Will Accommodate AWG No. Max Branch Circuit Fuse Size Amps
Refrigerant type/lbs-ozs
Evaporator Airflow CFM
Approximate Shipping Weight lbs

TABLE I—RATINGS AND PERFORMANCE

559B-024-E
24,000
230-60-1
207-254 207-254
15.7 19.5 72 88 1/5 1/5
1.3
1/4 1/3
2.0
3.5
19.0 23.9
22.9 28.8
10 10
119 95
4 4
25
R-22/2-6
900 1125 265
230-60-1 208-60-3
R-22/3-0
285
1.3 1.4
3.1
4.6
30
559B-030-E
30,000
187-229
12.3 11.1 70
1/5
1/3
2.9
4.6
16.6
19.7
12 12 8 10 92 110
4
25 20 40 30 25
R-22/3-0
1125 1125 1350
285 285 305 305
230-60-3 230-60-1
207-254 207-254
60 100 80
1/5
1.3 1.8 2.1 1/3 1/3 1/3
3.1 3.6 3.8
4.6
15.5
18.3 35.4 24.9
4
R-22/3-0
24.0
1/4
5.7
29.4
122 115
4 4
R-22/3-10
5S9B-036-E
35,000
208-60-3
187-229
15.2
1/4
5.7
21.1
R-22/3-10
1350 1350
R-22/3-10
230-60-3
207-254
14.0 70
1/4
1.8 1/3
3.6
5.7
19.4
22.9
10
142
4
305
MODEL
Nameplate Voltage-Freq-Phase Operating Voltage Range
Locked Rotor Amps
Full Load Amps
Full Load Amps
Electrical Connections
Unit Full Load Amps Unit Ampacity for Electrical Conductor Sizing 37.4 Min Branch Circuit Wire
Size 60°C Temp Rating Copper
Max Line Length**** Ft Largest Wire Size Line-Voltage Con nections Will Accommodate AWG No. Max Branch Circuit Fuse Size Amps
Rated Cooling Capacity* Bfuh
Compressor Motor FLA
Condenser Fan Motor** HP
Evaporator Blower Motor** HP
Rated Total Power Consumption KWH
Conductor*** AWG No.
Refrigerant type/lbs-ozs Evaporator Airflow CFM
Approximate Shipping Weight lbs 345
230-60-1
R-22/4-13 R-22/4-13
42,000 . 41,000 42,000 48,000
207-254
25.0 111
1/4 1/4 1/4
1.8 1/2
4.2
6.3 6.3
31.0
8 10
116
4
40 30
1570 1570 1570 1800
559B-042-E
208-60-3 230-60-3
187-229
16.9 15.3 92
2.1 1/2 1/2 1/2 1/2 1/2 1/2
4.4
23.4
27.6
103
4 4 4
345 345
207-254
92 118 90 78.5 39.3
1.8
4.2 4.9 5.1 4.9 4.9
6.3 7.2 7.2 7.2
21.3
25.1 40.0 33.3
10 8
130
30
R-22/4-13
230-60-1 208-60-3
207-254 187-229
26.5
1/4
1.9
33.3
108
45
R-22/4-11
367
559B-048-E
20.9 18.0 9.1
1/4 1/4
2.1 1.8 1.8
28.1 24.7
8 10 12
137
4
35 30 20
R-22/4-11 R-22/4-11 R-22/4-11
1800 1800 1800
367 367 367
*Rated in Accordance with ARI Standard 210-66.
**Condenser fan and evaporator motors are single phase.
***If other than 60 °C copper conductor is used, determine size from unit ampacity and the National Electrical Code. Voltage drop of
wire must be less than 2% of unit rated voltage.
****Wire length shown is measured one way along the wire path between unit and service panel for minimum voltage drop.
230-60-3
207-254 414-508
29.2 18.1
112 225
4
460-60-3
1/4
7.2
15.8
4
Unit Size Disposable Permanent

TABLE II—FILTER DIMENSIONS

Minimum Filter Size or Equivalent, Inches
024 030 16x20x1 20x20x1 12x20x1 16x20x1 20x20x1 20x20x1 20x25x1
036
20x25x1
042
25x25x1
048
25x25x1
X = Size 024, 030, & 036................................................................................1-3/4 in.
Size 042 & 048 ............................................................................................2 in.
Figure 4—Required Condenser
Fan Position
-3-
DO NOT DRILL HOLES IN SHADED AREA WHEN INSTALUNG RECTANGULAR DUCTS
Figure 5
of 6 ft and minimum return duct length of 3 ft. Do not operate unit longer than 5 minutes without ductwork. Refer to Bryant Air Distribution Manual, Part 2, for air duct design.
Flanges are provided on unit for duct connections. See Figure 2 for connection sizes and Figure 3 for typical duct installation.
Supply Air Connection in Mobile Home
Connect flexible duct to unit supply air connection at ap proximate center of trailer. Install turning vanes in main supply duct directly above elbow connection, using stan dard sheet metal practices.

Return Air Connection in Mobile Home

Purchase or field-fabricate a filter box. Suggested minimum filter box dimensions are shown in Figure 6. At ap proximate center of trailer, cut a return air opening in floor. Locate opening where it will not be obstructed by furniture. Size opening to accept filter box. Cut a hole in carpet or floor covering to sarne size as filter box floor opening. En sure electrical wiring or main structural supports are not accidentally cut. Insert filter box thru floor opening. Weather-seal floor connection in accordance with good con struction practice. Insert filter in filter box, and cover with return air grille.
Connect flexible duct to filter box. Extend duct from filter box to unit return air connection. When existing furnace is kept in system: During heating season, insert sheet metal panel beneath return air grille and over filter to prevent air movement thru cooling unit.
When furnace is removed from system, blank-off original furnace floor connection.

III. CONNECTING CONDENSATE DRAIN

The unit is designed to dispose of accumulated water through condensate drain hose on unit. It is recommended that a drain line that includes a trap should be installed to avoid possibility of abnormal negative fan pressure preven ting complete drainage of condensate. If drain connection is not practical or feasible, a factory-supplied condensate trap (taped at supply duct connection) must be installed for
proper drainage. See Figure 7.

IV. ELECTRICAL CONNECTIONS

Field wiring must comply with National Electrical Code and local codes. Install a branch circuit fused disconnect of adequate size to handle unit current load. Provide separate fused disconnect for electric heaters.
Voltage to unit during operation must be within ±10% of voltage indicated on rating plate.
W.-VRNI.N'Ci: Failure berause of operation of unit on im
proper line voltage constitutes abuse and is not coveretl by
Brvant warr.mtv.
Figure 6 — Minimum Dimensions-Return
Air Filter Box
Connect line-power leads from fused disconnect(s) to line power leads located in junction box. Screw connectors, which are suitable for aluminum or copper wires, are provided. See Figures 8 and 9. Tape screw connectors after connections are completed. Table I is provided to assist in staller in selecting proper wire and fuse sizes.
Thermostat connections are made to color-coded wires located in junction box. See Figures 8 and 9. Be sure color­coded wires not used are adequately and individually taped at end.

Rgure 7 —Condensate Drain Connection

NOTE: When using Model 883 (P/N 34427D03O) ther mostat with optional electric heat package, W and J ter minals on thermostat must be jumpered to ensure fan operation when thermostat is in HEAT position.

V. STARTUP AND ADJUSTMENT

Before starting system, make an initial overall inspection.
1. Check to be sure all wiring connections, including fac tory connections, have been completed and are tight.
2. Inspect all supply ducts and grilles to ensure proper adjustment.
3. Check to ensure air filters are in place.
4. Inspect refrigerant piping for damage or leaks that might have occurred during shipment.
5. Check for correct position of condenser fan blade in fan orifice plate. See Figure 4 for setting.
6. Check to ensure all tools and loose parts have been removed.
7. Check to ensure all panels and covers are in place.
Following initial inspection, unit may be started and ad-
-4-
justed for proper airflow. Recommended evaporator airflow is 350 to 450 CFM per
12,000 Btuh.
1. Set thermostat to call for cooling, thus energizing unit.
2. Measure static pressure in duct system at unit.
3. To determine airflow across evaporator coil, see Tables III through VII.
Model 559B utilizes a direct-drive blower, factory-wired on high-speed tap. If airflow is incorrect, blower speed can be adjusted as follows:
1. Disconnect electric power to unit.
2. Disconnect cooling relay lead from high-speed tap (black wire). Tape end of wire removed.
3. Refer to appropriate Air Delivery Performance Table and connect relay lead to correct speed tap.
Blue wire med speed
Orange wire med-low speed
Red Wire low speed
4. Recheck system static pressure.
The air conditioner has been tested and factory sealed. There is no need to check refrigerant charge. If it is necessary to open refrigerant circuit, contact your Bryant Distributor for proper procedure. The type and amount of refrigerant are listed on rating plate.
Typical Sequence of Operation
Do not leave installation until unit has been observed throughout one or two complete cycles. Installer, should make certain during this time that all components are operating in correct sequence. Refer to line-to-line wiring diagrams. Figure 10 or 11. The following sequence of operation pertains to the units shown; however, the sequence of operation of all units is very similar.
NOTE: Although the unit wiring may vary slightly from that shown in Figure 10 or 11, the sequence of operation will not be affected.
Sizes 024, 030, and 036, 230V-60-1
Line voltage is supplied through terminals LI and L2 to compressor contactor (2D) and to primary of control trans former (lAl). An external low-voltage thermostat is con
nected across low-voltage wires R, Y, and G. Set system switch to COOL and fan switch to AUTO on thermostat. On call for cooling, power is supplied from con trol transformer (lAl) through wire R, external thermostat,
wire Y, low-pressure switch (7C), and contactor holding coil
(2D) to other side of control transformer (lAl), closing con tactor contacts (2D).
When contactor contacts (2D) close, condenser fan motor (3C) is energized through run capacitor (4A2), starting con denser fan. In addition, power flows through compressor
motor run capacitor (4A3), compressor start capacitor
(4Cl), start relay (2K), and compressor motor (3J), starting
compressor motor. When cooling fan relay contacts (2A) close, power flows
through run capacitor (4A1) and blower motor (3D1) starting blower motor.
When thermostat ceases to require cooling, it breaks circuit
between wires R and Y and wires R and G, shutting down
unit.

Size 048, 208V- or 230V-60-3

Line voltage is supplied through terminals Ll, L2, and L3
to compressor contactors (2D) and to control transformer
(lAl). An external low-voltage thermostat is connected across low-voltage wires R, Y, and G. Set system to COOL and fan switch to AUTO on thermostat.
On a demand for cooling by the external thermostat, power
is supplied from control transformer (lAl) through ter minal R. Terminal R makes to terminals Y and G through the thermostat.
As R makes to G, the coil of the cooling fan relay (2A1) is
energized, closing the fan relay contacts (2A1). Power is now allowed to flow through blower motor run capacitor
(4A1), and the blower motor (3D1) starts.
As terminal R makes to terminal Y through the thermostat, the coil of cooling relay (2A2) is energized, closing the
cooling relay contacts (2A2). Power is now allowed to flow through the low-pressure switch (7C), the compressor in ternal thermostat (7H), compressor overload contacts (8A),
and the Bryant COMPROTEC'" circuit which includès
timer motor (3M), and the coil of the holding relay (2C).
The energized coil of the holding relay (2C) closes its nor mally open contacts and opens its normally closed contacts.
Timer motor (3M) runs through a 15-second (approx.) cy
cle. The timer motor contacts are then switched. Power is now allowed to flow through the coil of compressor con tactor (2D), which closes the normally open contacts of compressor contactor (2D).
When compressor contactor contacts (2D) are closed, power is allowed to flow through compressor overloads (8A) and compressor motor (3L) starts. At this same time, power is allowed to flow through low-ambient condenser fan switch
(7K), condenser fan run capacitor (4A2), and the two-speed
condenser fan motor (3D2) starts. When outdoor tem perature drops to 85°F, low-ambient condenser fan switch
(7K) will switch contacts, energizing a lower speed of con
denser fan motor (3D2).
When the demand for cooling is satisfied, the external ther mostat breaks the circuit between terminal R and terminals Y and G. Breaking this circuit deenergizes compressor holding coil (2D), cooling relay coil (2A2), and cooling fan
relay coil (2A1). The condenser fan motor (3D2), com pressor motor (3L), and blower motor (3D1) are now deenergized.
At the same time, the holding relay coil (2C) is deenergized,
opening its normally open contacts and closing its normally closed contacts. Power now flows through normally closed
contacts of holding relay (2C) and timer motor (3M). In ap proximately 4 minutes 45 seconds, the timer motor contacts switch, breaking circuit to timer motor. The unit is now in a
“standby” position, ready for the next demand for cooling by the external thermostat.
-5-

VI. MAINTENANCE

Refrigerant Charging
Unit is factory charged. When recharging is necessary, blow any refrigerant remaining in system, then weigh in total charge indicated on unit rating plate. Standard 1/4-inch Schrader service connections are provided on high and
low sides of refrigerant system for evacuation and charging.

Cleaning

Before cleaning, disconnect electrical power. Condenser Coil: Lift or remove unit top cover for access to
condenser coil. Inspect coil periodically. Clean with brush,
vacuum cleaner, low-pressure water, steam, or air.
Evaporator Coil: Lift or remove unit top cover for access to evaporator coil. Inspect coil periodically. Clean with brush, vacuum cleaner, or low-pressure air.
NOTE: When cleaning condenser coil or evaporator coil, be sure to thoroughly clean out the spaces between fins.
Return Air Filter: Clean filter a minimum of twice yearly. Flush permanent type with hot water, steam; or soak in mild solution of soap, or detergent, and water. Allow filters to dry, and replace. Refer to filter manufacturer’s in structions, as required, for other types of filters.
VII. INSTRUCTIONS TO OWNER
This Bryant self-contained cooling unit is designed and in
stalled to provide maximum comfort. Adherence to following guidelines will help promote greater efficiency and longer operating life.
1. Do not rapid-cycle unit. Allow at least 3 minutes before returning unit to operation after shutdown. On size 048 units, do not manually override COMPROTEC^.
2. If there is a general power failure, it is recommended that electrical power supply be turned off at unit disconnect switch until electrical power supply to building is restored. This prevents excessive current draw that would result from momentary low-voltage conditions at time power is restored.
3. Air filters should be cleaned or replaced regularly to
protect against restricted airflow across cooling coil.
4. Size 048 units incorporate Bryant’s COMPROTEC™ system for compressor protection. If compressor overloads or hi-pressure switch have cause to function, COMPROTEC ™ system will hold unit off for approxL
mately 5 minutes. At that time, unit will try to restart. Should original condition still exist, unit will again
cycle on COMPROTEC™ system.

TABLE III — SIZE 024 AIR DELIVERY PERFORMANCE

Air
Delivery
CFM
600 0,84 700 800 0,67 900 0,57
1000 0.45 0.17
External S tatic Pressure Available
High Med Med L ow Low High Med Med Lo w
0.76 0.69 0.56 0.25 0.79
Wet Coil No Filters Dry Co il No Filters
0.80
0,56
0.40
0.71
0.38
0.14
0.60 0.86
_

TABLE IV — SIZE 030 AIR DELIVERY PERFORMANCE

Air
Delivery
CFM
800 1,12
900 1,01 1000 0,89 0.61 1100 1200 0,56
External S tatic Pressure Available External S tatic Pressure Available .
High Med
0,74 0.37
Wet Coil No Filters Dry Coil No Filters
0.96
0.80
Med Low
0.80 0.21 1.14 0.98 0.82
0.48
— —
Low
— —

TABLE V — SIZE 036 AIR DELIVERY PERFORMANCE

Air
Delivery
CFM
1000 1100 1.06 1200 0.95 1300 1400 0.67 0.42
External S tatic Pressure Available External S tatic Pressure Available
High Med
1.17 1.10
0.82
0.97
0.82 0.55
0.64
Wet Coil No Filters
Med Low
0,95 0.70 0,77 0.35
— _
Low

TABLE VI — SIZE 042 AIR DELIVERY PERFORMANCE

Air
Delivery
CFM
1100 1200 1300 1400 1500 1.00 0.55 1600 0.85 0.93
External S tatic Pressure Available
High Med
1.15
Wet Coil No Filters
— — — — 1.10
0.87
Med Low
1.10
0.83
0.35
— —
External S tatic Pressure Available
0.82 0.73 0.62
0.72 0.59 0.28
0.71
0.62
0.50 0.22
High M ed Med Low Low
1.04 0.83 0.51
0.93 0,79 0,63
High Med Med Low Low
1.21
1.11 1.02 0.82 0.40
1.01 0.88 0.61 0,89
0.76
High Med M ed Lo w
1.20 0.91
1.06
0.60 0.42
0.45
0.65
0.42
Dry Co il No Filters
1.14
0.71
0.51
External S tatic Pressure Available
Dry Co il No Filters
1.14 — —
0.19
0.99 0.74
1.15 0.40
0.61
Low
0.23
0.87
— —
— —

TABLE VII — SIZE 048 AIR DELIVERY PERFORMANCE

Air
Delivery
CFM
1400 1500 1600 0.92 1700 0.80 0.40 1800 0.68 0.15 1900 0.53
External S tatic Pressure Available External S tatic Pre ssure Available
High
1.12
1.02
Wet Coil No Filters Dry Coil N o Filters
Med
0.95 0.60 1.17 1.00 0.65
0.79
0.61
Low
0.25
— — 0.87 0.47 — — —
-6-
High Med Low
1.07
0.97 0.66
0.76 0.23
0.64
0.84
0.30
-FACTORY WIRING
- FIELD LOW-VOLTAGE WIRING
•FIELD HIGH-VOLTAGE WIRING
MODEL 883C
THERMOSTAT P/N34427DP78
® Ç) ©
---------
^—h
THERMOSTAT CONNECTIONS
THERMOSTAT & SUBBASE
P/N 34427D03O
® © (^ Ç>
t—r
I
o
©
©
® ©
©
©
COLOR-CODED LEADS (FROM UNIT)
located inside
JUNCTION BOX

Figure 9 — Low-Voltage Field Wiring (Cooling Only)

Figure 10—559B-024, -020, -030, & -036 Wiring Diagram, 230-60-1
® ©
© © ©
A72409
LEGEND
1A1-Control Transformer 1A2-460- to 230-V Transformer
2A-Cooling Fan Relay 2A1-Cooling Fan Relay 2A2-Cooling Relay
2C-Holding Relay
2D-Compressor Contactor (2 pole)
2K-Start Relay
2M-Compressor Contactor (3 pole)
3C-Condenser Fan Motor 3D1-Blower Motor 3D2-Two-speed Condenser Fan
Motor
3J-Compressor Motor with
Internal Protection
3L-Compressor Motor with
Internal Protection
3M-Timer Motor 4A1-Blower Motor Run Capacitor 4A2-Condenser Motor Run Capacitor 4A3-Compressor Motor Run
Capacitor
4C1-Compressor Motor Start
Capacitor 7C-Low-Pressure Switch 7H-lnternal Compressor Thermostat 7K-Low-Ambient Condenser Fan
Switch
8A-Com pressor Motor Overload
12-Receptacle
Figure 11 — 559B-048 Wiring Diagram, 208- or 230-60-3
-7-

Accessory Electric Heater Installation

(For Use With 559B Self-contained Cooling Units)

T

INTRODUCTION

Single-phase electric heaters in 5-. through 15-KW sizes, and three-phase electric heaters in 5.6- through 14.5-KW sizes, are installed internally on 559B units. The 20- and
25-KW size single-phase heaters, and the 14.9- thru 25-KW size three-phase heaters, are mounted externally on the 559B supply air connection. Do not use more than one heater per unit. See Table I for heater model and 559B usage.

I. ELECTRIC HEATER INSTALLATION

A. Internal Heaters
1. Remove fan section access panel.
2. Remove sheet metal plate covering heater installation
area (between evaporator fan discharge and supply air connection). See Figure 5. Discard sheet metal plate.
3. Insert heater into opening provided.
NOTE: Ensure the heater support bar (Figures 1 and 5) en ters the hole in the side of the fan discharge duct.
4. Fasten heater in place at top and bottom with two sheet metal screws.
5. Attach heater wiring label provided to inside of fan section access panel.
6. Installation is now ready for electrical connections. See “Wiring”, Section III.
SCREW
CLEARANCE HOLES (7)
UNIT
HIGH-VOLTAGE LEADS
(CONNECTORS SUPPLIED)
Figure 1—Internal Heater
EXTERNAL HEmi nn (BOTTOM)
Figure 3—Power Knockouts on
SCREW CLEARANCE HOLES (2)
(TOP AND BOTTOM)
External Heater
•SERVICE PANEL
I5-LINE
'POWER
KNOCKOUT
INLINE
power
KNOCKOUT
A73166
Figure 2—Entering Air Side of
DUCT CONNEC FLANGE
EXTERNAL HEATER (DUCT SIDE)
Figure 4—Duct Connection Side of
External Heater
External Heater
IIRViCE . „NEL
151
-8-
FAN
Section
HEATER
HEATER
TOP ELECTRICAL KNOCKOUT CONTROL WIRING HOLE
INTERNAL ELECTRIC HEATER
LINE POWER LEADS
Figure 5—Internal Electric Heater Installation

B. External Heaters

CONTROL
-WIRING PLUG
SUPPLY AIR CONN
The external heaters are self-locating on the 559B evaporator fan supply air connection. See Figure 6. Flanges are provided on the heater for connection to the 559B with
sheet metal screws. See Figure 2. Before installing the heater, ensure the factory-supplied gasket is in place around the heater entering air connection as shown in Figures 2 and 3. Complete installation as follows;
NOTE: When installing external heaters, remove the in ternal air baffle from the 559B. The external heaters have their own air baffle.
1. Remove top electrical knockout on 559B. See Figure 6.
2. Place heater over 559B supply air connection. See Figure 6.
3. Align control wiring hole in entering air side of heater (Figure 2) with top electrical knockout in 559B. See Figure 6.
4. Drill holes in 559B to align with screw clearance holes in heater flanges. See Figure 2 for location of clearance holes in flanges.
NOTE: Mark the drilling locations while holding the
heater in place against the 559B.
( Al TION: I).. nol pem-lraif drill more iliaii 1 inch iusitlc
5. Fasten heater in place with sheet metal screws.
6. Installation is now ready for electrical connections. See “Wiring”, Section III.

II. DUCTWORK REQUIREMENTS

Refer to Connecting Ductwork section on page 1 of these instructions for complete duct installation details. The following ductwork recommendations pertain to electric
heater applications:
1. Flexible connectors are required between duct con
nection flanges and ductwork to prevent transmission of vibration. When electric heater is installed, it is recommended that asbestos (or similar heat-resistant material) connector be used between ductwork and
heater duct connection flange. If non-heat-resistant
flexible duct is used, it is recommended that a sheet
metal sleeve be inserted inside of duct. Heat-resistant
Figure 6—External Heater Installation
duct connector (or sheet metal sleeve) should extend 24
inches from electric heater element.
2. Single-phase external heaters are provided with means for attachment of circular ductwork only.
Three-phase external heaters are provided with
means for attachment of circular or square ductwork.
3. When electric heater is used, the ductwork must be capable of handling minimum air quantities shown in Table III.

III. WIRING

Field wiring must be made in accordance with the National
Electrical Code and local electrical codes governing such wiring. Provide a separate fused disconnect for each electric heater circuit. See Table II. Refer to heat package wiring label.

A. Line-Power Connections

On internal heater installations, bring the line-power leads from the fused disconnect(s) through the power holes in the 559B unit panel. Knockouts are provided on the ex ternal heater cabinet for passage of the line-power leads. See Figure 3.
Connect the line-power leads to the heater line-power
pigtails or to the heater high-voltage terminal block. See
Figure 10 and Table II for branch circuit data and line-
power connections. Use screw connectors provided for pigtail connections, and tape each connection. The screw connectors and terminal block are suitable for copper or aluminum wire.
If aluminum conductors are used, the wire gauge selected
must have current capacity not less than the copper wire
specifled and must not create a voltage drop between the service panel and the unit in excess of 2% of the unit rated
voltage.
NOTE: If aluminum conductors are used, the connections
must be made in accordance with the National Electrical
Code. In preparing the wire, just before installing the con
nector, all aluminum wire must be “brush-scratched” and the wire coated with a corrosion inhibitor, such as Pentrox
A. When it is suspected that the connection will be exposed
to moisture, it is very important to cover the entire con nection completely to prevent an electro-chemical action
that will cause the connection to fail very quickly. Reducing the effective size of the wire, such as cutting off strands so that the wire will fit a connector, is very poor practice.
Proper size connectors should be used.
-9-
TABLE I—HEATER DATA & USAGE
Heater
Model No.
88EA0050CA00
88EA0075CAOO 7O181D02
88EA0100CA00
88EA0150CA00t
88EA12O0CAOOt
88EA1250CA00t 88EA1250LA00t
88EA0075EA00
88EA0100EAOO 7O181D011
88EA0145EA00
88EA1198EAOOt
88EA1250EA00t 88EA0160FA00 88EA1200FA00t
Bryant
P/N
7O181D01
7O181D03 10 240-60-1 7O181D04 7O181D05 20 240-60-1 62,690
70181D06 7O181D08 7O181D01O 5.6/7.5
7O181D012 10.9/14.5 7O181D013 14.9/19.8 7O181D014 7O181D016 10 7O181D018
KW* Phase
5 240-60-1
7.5
15 240-60-1
25 240-60-1 78,363 25 208-60-3
7.5/10
18.75/25
20
Voltage-
Hertz-
240-60-1
208/240-60-3 19,227 208/240-60-3 208/240-60-3 37,171 208/240-60-3 208/240-60-3
480-60-3 480-60-3
208V 230V 240V 480V
23,509
_
85,325
25,635
50,758 64,089
Btuh Output
15,673
31,345 47,018 51,195
23,509 31,345 45,450 62,063 67,577 78,363
34,130
-
17,065 25,598 34,130
68,260 85,325
25,598 34,130
49,489
85,325
68,260
*At rated voltage. tThese heaters are wired for two-stage heating. Remaining heaters are wired for single-stage heating.
NOTE: The 18.75/25- and 25-KW heaters must be field-connected for two-stage operation. All other heaters wired for two-stage heating
may be field-connected for single- or two-stage operation.

TABLE II—HEATER ELECTRICAL DATA

KW
5t
7.5t 240-60-1 1 31.2 lot
15t
20 240-60-1
25
25
5.6/7.5t
7.5/1 Ot
10.9/14.5t
14.9/19.8 208/240-60-3 1
18.75/25 208/240-60-3
lot 20
Voltage-
Hertz-
Phase-
240-60-1 1
240-60-1 240-60-1 2 41.7
240-60-1 3 41.7
208-60-3
208/240-60-3 1 208/240-60-3 208/240-60-3 1
480-60-3 1 12.0 480-60-3 1 24.0
No. of
Circuits
1 41.7
2 41.7
2
1 ■
2 26.0/30.1
FLA
(each)
20.8 10 45 30
20.8
41.7
41.7
20.8
34.7
34.7
15.6/18.0 12/10 49/49
20.8/24.0 10/10 59/59
30.2/34.9
41.3/47.6 6/4 46/73
26.0/30.1 8/8 47/47
Branch Circuit
Wire
Size*
(AWG No.)
8 45 40 6 55 50 6 55 50
10 45 30
6 55 50 6 55 50 6 55 50 6 55
10 45 30
6 55 45 6 55
8/6 63/63 40/45
8/8 47/47 35/40
14 59 15 10
Max Wire
Length
(ft)**
74
Fuse
Amps
20/25 30/30
60/60
35/40
tThese heaters are internally installed. All others are externally installed. *Based on 60°C copper wire. If other than 60°C copper conductor is used, determine size from unit ampacity and the
National Electrical Code. Voltage drop of wire must be less than 2% of unit rated voltage.
**Length shown is for one way along the wire path from unit to service panel for minimum voltage drop.
Size Unit
Used With
024, 030, & 036
024 thru 048
024 thru 048
030 thru 048
042 & 048
,042 & 048
042 & 048 030 thru 048 030 thru 048 030 thru 048
042 & 048
042 & 048
048 048
50
45
30

B. Control Wiring (24V)

Between Heater and 559B
A low-voltage control-wiring plug is provided on the heater for connection to the receptacle in the 559B control-wiring
terminal box. On internal heater installations, extend the control-wiring
plug through the hole provided in the 559B control-wiring terminal box and connect to the receptacle. On external heaters, feed the plug through the control-wiring hole provided in the heater cabinet (Figures 2 and 6) and into the 559B. Extend the plug into the 559B control-wiring ter
minal box and connect the plug to the receptacle.
NOTE: When heater installation is completed, be sure to seal holes around all electrical openings to prevent air leakage.

C. Thermostat leads

The thermostat leads are brought through the grommeted
hole, provided in the 559B, into the control-wiring terminal box. Connect the thermostat leads to the low-voltage pigtails. See Figure 8 or 9 for thermostat connection diagrams. Tape unused pigtails separately. When aluminum field wire is used, lubricate splices with a suitable splice compound, and use approved copper-to­aluminum splice connectors. Set the thermostat heat an
ticipator as described in “Determining Heat Anticipator
Setting”, Section V.
IV. SERVICE A. Limit Switch
The limit switch provides overtemperature protection. A switch malfunction prevents the heating elements from being energized. Replace the limit switch if a malfunction occurs.
B. Time-Delay Relay
The 14.9- through 25-KW heaters are sequenced. The time-
-10-
TABLE III
SIZE UNIT
024 600 030 036 900 042 048
' *Minimum unit cfm for safe
heater operation.
CFM*
750
1050 1200
delay relay provides a time delay between the heater elements coming on or shutting off. A relay malfunction will prevent the heaters from being energized or prevent the heaters from being deenergized. Replace the time-delay relay if a malfunction occurs.
C. Safety Fan Relay (14.9- through 25-KW heaters)
The safety fan relay ensures the operation of the evaporator fan while the sequenced heater elements are energized. A malfunction will cause excess heat problems; the fan motor will not start or will not shut off. Replace the safety fan
relay if a malfunction occurs.
V. DETERMINING HEAT ANTICIPATOR SETTING
Because of the numerous combinations of components that
a heating control circuit may contain, it is necessary to
measure the load in amperes, so that the thermostat heat
anticipator (s) can be set properly after the installation is completed. A hook-around ammeter is used to measure the heating control circuit load in this procedure.
Figure 7 shows the proper use of a hook-around ammeter to determine the load. This illustration shows the circuit with five turns around the jaws of the ammeter. Five turns should be used to obtain an accurate reading.
To obtain correct heat anticipator setting, divide the am meter reading by the number of turns around the jaws of the ammeter.
Example:
3.5 amperes
0.7 amperes setting
5 turns around jaws
Procedure for two-stage heating units:
1. Disconnect lead from thermostat terminal W1 and make five turns around ammeter jaws. See Figure 7.
2. Disconnect lead from thermostat terminal Rh and connect to W1 as shown in Figure 7.
3. Obtain ammeter reading for calculating first-stage heat anticipator setting.
4. Reconnect W1 lead and disconnect W2 lead from thermostat.
5. Follow same procedure used above to obtain ammeter reading for calculating second-stage heat anticipator setting.
6. Reconnect W2 and Rh leads to thermostat terminals.
NOTE: The procedure for single-stage heating units is the same, except the leads from thermostat terminals W and 4­R are connected together.
NOTE: For accurate load calculations, the ammeter
readings should be taken at the thermostat as shown in
Figure 7. The thermostat hookup leads must be in the cir cuit when taking these readings.
THERMOSTAT a SUBBASE
JUMPER
*N0TE; W2 CONNECTION
FOR l5-a20-KW HEATERS ONLY
Figure 8—Cooling and Single-Stage Heating
P/N34427D03O
COLOR-CODED LEADS (FROM UNIT) LOCATED INSIDE JUNCTION BOX
Thermostat Connections
THERMOSTAT CONNECTIONS
-11-
BRYANT
THERMOSTAT
P/N 34427D54 8 SUBBASE P/N 34427D66
@ @
I
_l UJ 5 CD >- $
Figure 9—Cooling and Two-Stage Heating
i
_______
1
r—
» • (
o I <
SI®
cc 3
(D CD
Thermostat Connections
1
r-J
ÜJ cr
SINGLE-PHASE HEATERS
TO FUSED DISCONNECT
TO FUSED DISCONNECT
TO FUSED . DISCONNECT
KW Voltage-
5 240-1
7.5 10 15 240-1
20
25
Phase
240-1 240-1
240-1 2
240-1 3 .
*Based on 60°C copper wire. See Table II.
Circuits
Used
1 A 1 A 8 1 A 6 2 A 6
B . 10 A 6 B 6 A 6 B 6 C 10
Wire
Size*
10
THREE-PHASE HEATERS
(PIGTAIL CONNECTIONS)
THREE-PHASE HEATERS
(TERMINAL BOARD CONNECTIONS)
LEGEND
CIRCUITA TO FUSED
DISCONNECT
CIRCUIT B TO FUSED
KW Voltage-
25
14.9/19.8 208/240-3 1 A 6/4
18.75/25
20
Phase
208-3 2 A '6
208/240-3 2 A 8/8
480-3
DISCONNECT *Based on 60°C copper wire. See Table II.
FACTORY LINE-VOLTAGE WIRING FIELD LINE-VOLTAGE WIRING FIELD SPLICE
Circuits
Used
1 A
Wire
Size*
B 6
B 8/8
10
Figure 10—Line-Power Connections
-12-
Loading...