Bryant 558F.36.1 User Manual

wiring diagrams
A A C C C C C
G
SINGLE PACKAGE ROOFTOP ELECTRIC COOLING UNITS
Cancels: New WD 558F.36.1
DIAGRAM INDEX
UNIT LABEL DIAGRAM
Unit 558F Voltage-Phase-Hertz Type Label Diagram Figure No.
208/230-1-60 Schematic/Component Arrangement 50DK508524 1
036,048
060
072
090-150
208/230-3-60 Schematic/Component Arrangement 50DK508526 2
208/230-3-60, 460-3-60 Schematic/Component Arrangement 50DK508528 9
575-3-60 Schematic/Component Arrangement 50DK508533 10
208/230-3-60, 460-3-60 Schematic/Component Arrangement 50DK508793 11
575-3-60 Schematic/Component Arrangement 50DK508794 12
3 to 121/2 Tons
558F
036-150
11/15/00
ACCESSORY WIRING
Description Unit Size Fig. No.
Motormaster® I Control 036-150 13
Motormaster II Control
Time Guard® II Device 036-150 16 Solid-State Enthalpy Control 036-150 17 Differential Enthalpy Control 036-150 18
EconoMi$er 036-072 19
EconoMi$er Sensor Wiring 036-150 20
Power Exhaust 036-072 21
036-072 14 090-150 15
LEGEND
HA Adjustable Heat Anticipator WG American Wire Gage
Contactor, Compressor AP. Capacitor B—Circuit Breaker C—Cooling Compensator OMP — Compressor Motor
D—Diode EC Enthalpy Control ECON — Economizer EPS Emergency Power Supply
EQUIP — Equipment ER Economizer Relay FPT Freeze-Up Protection Thermostat FU Fuse
ND Ground
HC Heater Contactor (Strip Heat) HPS High-Pressure Switch IFC Indoor-Fan Contactor IFM Indoor-Fan Motor IFMOVL— Indoor-Fan Motor Overload
(Nine-Volt Battery)
IFR Indoor-Fan Relay LPS Low-Pressure Switch LSM Limit Switch (Manual Reset) MTR Motor OAT Outdoor-Air Thermostat OFC Outdoor-Fan Contactor OFM Outdoor-Fan Motor OLR Overload Relay P—Plug PL Plug Assembly QT Quadruple Terminal R—Relay SAT Supply-Air Thermostat SEN Sensor ST Start Thermistor SW1 Switch Fully Open SW2 Switch Fully Closed SW3 Switch Minimum Vent Position SW4 Switch Maximum Vent Position TB Terminal Block TC Thermostat, Cooling
TDR — Time-Delay Relay TH Thermostat, Heating TRAN — Transformer
Field Splice
Marked Wire Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked) Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To indicate common potential only.
Not to represent wiring.
NOTES FOR FIG. 1, 2, 5, 6, 9
1. If any of the original wire furnished must be replaced, it must be replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing conditions.
3. Thermostat: HH07AT170, 172, 174, and P272-2783 Subbase: HH93AZ176, 178, and P272-1882, 1883
NOTES FOR FIG. 3, 4, 7, 8, 10
1. If any of the original wire furnished must be replaced, it must be replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing conditions.
3. Thermostat: HH07AT170, 172, 174, and P272-2783 Subbase: HH93AZ176, 178, and P272-1882, 1883
NOTES FOR FIG. 11
1. If any of the original wire furnished must be replaced, it must be replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing conditions.
3. Thermostat: HH07AT170, 172, 174, and P272-2783 Subbase: HH93AZ176, 178, and P272-1882, 1883
4. Set heat anticipator at 1 amp.
5. Use copper conductors only.
6. Use copper, copper-clad aluminum or aluminum conductors.
4. Set heat anticipator at 1 amp.
5. Use copper conductors only.
6. Use copper, copper-clad aluminum or aluminum conductors.
7. For 208/230-3-60 v units: TRAN is wired for 230-v unit. If unit is to be run with 208-v power supply, disconnect BLK wire from 230-v tap (RED) and connect to 208-v tap (BLU). Insulate end of 230-v tap.
4. Set heat anticipator at 1 amp.
5. Use copper conductors only.
6. Use copper, copper-clad aluminum or aluminum conductors.
7. For 208/230-3-60 v units: TRAN is wired for 230-v unit. If unit is to be run with 208-v power supply, disconnect BLK wire from 230-v tap (RED) and connect to 208-v tap (BLU). Insulate end of 230-v tap.
8.
CIRCUIT
BREAKER
CB 24 V
CB1 150 460-3-60
VOLTS MFG. PT. NO.
Potter & Brumfield
Heinemann Airpax
MUST
TRIP
AMPS
3.2W2BX-1024-3.2
8.5CF3-Z228-4 219-3-2600-486
NOTES FOR FIG. 12
1. If any of the original wire furnished must be replaced, it must be replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing conditions.
3. Thermostat: HH07AT170, 172, 174, and P272-2783 Subbase: HH93AZ176, 178, and P272-1882, 1883
4. Set heat anticipator at 1 amp.
5. Use copper conductors only.
6. Use copper, copper-clad aluminum or aluminum conductors.
7.
CIRCUIT
BREAKER
CB 24 V
CB1 150 460-3-60
VOLTS MFG. PT. NO.
Potter & Brumfield
Heinemann Airpax
MUST
TRIP
AMPS
3.2W2BX-1024-3.2
8.5CF3-Z228-4 219-3-2600-486
—2—
—3—
Fig. 1 — Schematic/Component Arrangement; 558F036,048; 208/230-1-60
—4—
Fig. 2 — Schematic/Component Arrangement; 558F036,048; 208/230-3-60
—5—
Fig. 3 — Schematic/Component Arrangement; 558F036,048; 460-3-60
—6—
Fig. 4 — Schematic/Component Arrangement; 558F036,048; 575-3-60
Loading...
+ 14 hidden pages