COMMERCIAL
SINGLE-PACKAGE ROOFTOP
ELECTRIC COOLING UNITS
Model 558D/559F
Sizes 036-300
3to25Tons
Model 558D036-072
Model 558D090-150
DESCRIPTION
The 558D/559F electric cooling rooftop units are designed to
deliver optimum performance and reliability in a commercial
rooftop unit. The 3 to 25 ton units are one-piece electric cooling
units that are prewired and precharged with R-22 at the factory,
making jobsite installation easy. Every unit is factory run-tested
prior to shipment to ensure reliable installation.
The 558D/559F units are designed to be field-convertible from
vertical supply/return to horizontal supply/return (180-300 units
require an accessoryhorizontal supply curb or adapter), making
them easily adaptable to a wide variety of new construction and
replacement applications. For vertical supply/return jobs, ductwork can be connected directly to the roof curb, allowing ductwork to be completed before unit is available for installation. All
units include easily replaceable internal filters.
The 558D/559F units are available with a range of accessory,
field-installed electric heating sizes and voltage options to meet
most job requirements. Low-voltage terminal blocks make wiring connections quick and simple.
All units are listed with either UL (Underwriters’ Laboratories)
or ETL(ETLTestingLaboratory) and withCSA(CanadianStandards Association), UL Canada, or ETL Canada.All units areARI
(Air-Conditioning & Refrigeration Institute) approved (except the
size 300, which is beyond the scope of the ARI Certification program) and comply with ASHRAE Standard 62 (American Society of Heating, Refrigeration, and Air Conditioning Engineers).
Model 559F180,216
Model 559F240,300
STANDARD FEATURES
EFFICIENT DESIGN means cooling energy savings. Standard
units have EERs (energy efficiency ratios) of up to 9.2, and
SEERs (Seasonal Energy Efficiency Ratios) of up to 10.0 (036060 units only).
THE FACTORY-ASSEMBLED PACKAGE (036-150 Units) is a
compact, fully self-contained electric cooling unit that is prewired, prepiped, and precharged for minimum installation
expense.
UNITS MAY BE CONVERTED TO HORIZONTAL DISCHARGE in the field. The units can be modified at the jobsite to
fit a variety of applications (180-300 units require an accessory
horizontal supply/return roof curb or a horizontal supply/return
adapter).
NEW TOOL-LESS FILTER ACCESS PANEL (036-150 Units)
provides easy access to filters. The new panel provides additional access space, permitting easy filter replacement in the
unit, even with an outdoor-air device mounted in a horizontal
position.
INTERNAL RETURN-AIR FILTERS are provided. Two-in.
throwaway filters are provided standard on all units, and can be
easily accessed through the tool-less access filter door.There is
no need to field-fabricate filter racks or install external filter
accessories.
COMPRESSOR PROTECTION is assured. The 036-150 units
have an internal pressure relief valve and line break (current
overload) protections, and the 180-300 units have high- and
low-pressure and freeze protection external to the compressor.
These protections prohibit operation under abnormal unit
conditions.
Form No. PDS 558D.36.5B
DUAL COMPRESSORS AND DUAL REFRIGERATION CIRCUITS (090-150 and 216-300 Units) are provided. Two com-
pressors, each on its own independent circuit, provide standby
reliability and high operating efficiency.
ADVANCED DESIGN of evaporator and condenser coils provides optimum heat transfer and cooling efficiency. Coils are
computer-designed with advanced heat transfer surfaces, and
are fabricated of copper tubing with aluminum fins.
COMMERCIAL STRENGTH BASE RAILS (full-perimeter on
036-150 units) with built-in rigging capability allow easy rigging
of unit.
WEATHER-RESISTANT CABINET is built for durability in any
climate. The cabinet is made of pre-painted, galvanized steel for
long life and high-quality appearance.
LOW-AMBIENT OPERATION is provided standard on most
units. The 036-150 units and the 240 units operate in cooling
down to 25 F as shipped from the factory. The 180 units operate
down to 40 F, the 216 units operate down to 35 F, and the
300 units operate down to 48 F. Low-ambient kits are not required for most applications.
HERMETICALLY-SEALED COMPRESSORS on the 036-150
units prevent contamination to help promote longer life and dependable operation. The 180-300 units have semi-hermetic
compressors.
COMPRESSOR VIBRATION ISOLATION MOUNTING on all
units eliminates noise-causing vibration transmission into the
conditioned space.
CRANKCASE HEATERS on the 180-300 units keep the oil free
of refrigerant during the off cycle for added compressor life and
reliability.Crankcase heaters are not necessary on the 036-150
units due to high-side crankcase design (072,150 units) and low
refrigerant charge levels (036-150 units).
POWER AND CONTROL CONNECTIONS are made on the
same side of the unit to simplify installation.
STANDARDWARRANTIESinclude 1 year on parts, with an additional 4 years on compressors (036-180 units). Additional extended warranties are also available.
3 TO 6 TON UNITS WEIGH LESS THAN 500 LB as standard
from the factory. This can eliminate the need for structural engineering approval on replacement jobs.
BELT-DRIVEN EVAPORATOR-FAN MOTORS are standard on
all 6 to 25 ton units, allowing adjustment of the available static
pressure to meet the job requirements of even the most demanding applications. Belt-driven evaporator-fan motors are
available as a factory-installed option on the 3 to 5 ton units.
• To reduce energy usage. Use whenever the number of hours
of operation at below 55 F is significant.
• The damper may be used on either vertical or horizontal
applications.
Parablade Economizer (036-150 Units) — The unique design
of the Parablade economizer saves energy while providing economical and reliable cooling. The new design uses a parallelopposed blade damper to permit outdoor ventilation air to enter
the unit any time the evaporator fan is running. The economizer
will permit cooling using 100% outdoor air whenever outdoor air
alone will provide adequate cooling. If the economizer alone
cannot provide enough cooling, then simultaneous economizer
and compressor operations will provide the most economical
operation. The economizer also has built-in spring return for reliable close-on-power loss. The Parablade design incorporates
standard enthalpy controls.
SUGGESTED USE:
• To allow a fixed percentage of outdoor air on vertical applications any time the evaporator fan is on, or to operate in economizer mode if outdoor air can provide cooling, but closes
when the evaporator fan is off to prevent cold backdrafts and
wasted energy.
• To reduce energy usage. Use whenever the number of hours
of operation at below 55 F is significant.
NOTE: Indoor-air quality (IAQ) restrictions require enthalpy controls to help regulate humidity in the occupied space.
25% and 50% Manual Outdoor-Air Damper — Package consists of a damper which can be set at 25% or 50% (036-150)
outdoor air. The package includes a rainhood and birdscreen.
SUGGESTED USE:
• Toallow a fixed percentage of outdoor air for ventilation under
all conditions.
• The damper may be used on either vertical or horizontal
applications.
NOTE: The 25% manual outdoor-air damper will be factory
installed whenever the factory-installed economizer is not
chosen on the 180-300 units.
and/or drives allow operation of the evaporator fan at conditions
outside the range of the standard factory motor and drive
combination.
SUGGESTED USE:
• When higher static/airflow is required to meet job conditions.
FACTORY-INSTALLED OPTIONS
DESCRIPTION AND USAGE
Durablade (036-150) and Standard Integrated (180-300)
Economizers — The economizer will allow a fixed percentage
(between 0 and 100%) outdoor ventilation air into the unit any
time the evaporator fan is running. A dry-bulb thermostat placed
outdoors will bring in up to 100% outdoor air whenever the temperature of the outdoor air alone will adequately provide cooling.
If the economizer alone cannot provide enough cooling, then simultaneous economizer and compressor operation will provide
the most economical operation.
SUGGESTED USE:
• Toallow a fixed percentage of outdoor air any time the evaporator fan is on, or operates in economizer mode if outdoor air
can provide cooling, but closes when the evaporator fan is off
to prevent cold backdrafts and wasted energy.
Controls Upgrade Kit (036-150 Units) — The controls kit includes high-pressure, loss-of-charge/low-pressure, and freeze
protection cutout switches. The high-pressure and loss-ofcharge/low-pressure switches can be easily added by screwing
the switches onto Schrader-type fittings provided on the refrigerant lines.
SUGGESTED USE:
• Kit provides additional protection against system high pressure, loss-of-charge/low pressure, and evaporator coil frost
build-up for 036-150 units.
NOTE: These switches are standard on the 180-300 units.
Condenser Coil Grille (036-150 units) — The grille protects
the condenser coil from damage and requires no additional
clearance.
SUGGESTED USE:
• When unit is located in high traffic areas or could be subject to
damage.
• As an alternate location for the field-supplied disconnect
switch.
FIELD-INSTALLED ACCESSORY
DESCRIPTION AND USAGE
Roof Curbs (Vertical and Horizontal) — Full-perimeter galva-
nized steel support frame in 14- and 24-in. high designs provides wood nailer to attach roof counter flashing. Insulated
basepans in curb are provided to prevent condensation. Ductwork attaches to rails provided in the roof curb. A gasket is provided to form an air- and watertight seal between unit and curb.
The gasket meets the standards of the NRCA (National Roofing
Contractors’ Association).
SUGGESTED USE:
• Rooftop application for vertical discharge.
• Slab-mounted applications when elevation of the unit is
necessary.
Horizontal Adapter (180-300 Units) — The curb is prefabricated, easily field-assembled, and permits full perimeter mounting. The curb also improves unit static performance by up to
0.6 in. wg.
SUGGESTED USE:
• Rooftop application for horizontal discharge on 180-300 units.
• Rooftop applications for horizontal discharge on 180-300
units where high air delivery cfms are required.
Condenser Coil Hail Guard (036-150 Units) — Package consists of a hood and coil grille which attach to the condenser coil.
SUGGESTED USE:
• To protect the condenser coil from hail and other debris on
036-150 units.
• As an alternate location for field-installed disconnect switch.
Condenser Coil Grille (036-150 Units) — The grille protects
the condenser coil from damage and requires no additional
clearance.
SUGGESTED USE:
• When unit is located in high traffic areas or could be subject to
damage.
• As an alternate location for the field-supplied disconnect
switch.
25% and 50% Manual Outdoor-Air Dampers (036-150 Units)
— Package consists of a damper which can be set at either
25% or 50% outdoor air (as appropriate). The package includes
a rainhood, birdscreen, and a panel with a hole in it for easy
installation.
SUGGESTED USE:
• Toallow a fixed percentage of outdoor air for ventilation under
all conditions.
• The damper may be used on either vertical or horizontal
applications.
Two-Position Dampers — Package consists of a low-leak
damper assembly and a panel with a hole in it for easy installation (036-150 units). The damper will allow either 0 or 25% or
100% (depending on accessory package) outdoor air into the
unit any time the evaporator fan is running, and features closeon-power-loss. When the evaporator fan is off, the damper will
be closed.
SUGGESTED USE:
• Allows a fixed percentage of outdoor air any time the evaporator fan is on, but closes when the evaporator fan is off to
prevent cold backdrafts and wasted energy.
• The damper may be used on either vertical or horizontal airflow applications.
Economizers — See descriptions listed under FactoryInstalled Options Description and Usage section on page 2.
NOTE: When the accessory Durablade economizer is ordered
for the 036-150 units, the package also contains an outdoor-air
panel for easy installation.
Solid-State Enthalpy Control (036-150 Units) — Package
consists of a solid-state control and sensor which is capable of
sensing outdoor-air heat content (temperature and humidity)
and controlling economizer cut-in point to have minimum heat
content air passing over the evaporator coil. The solid-state enthalpy control replaces the standard dry-bulb thermostat in the
economizer.
SUGGESTED USE:
• To enhance economizer operation for additional energy
savings.
Enthalpy Control Sensor — Package consists of a solid-state
sensor to be used in conjunction with the solid-state enthalpy
control (036-150 units) or paired with a second enthalpy sensor
(180-300 units) for differential enthalpy control. This sensor is
mounted on the economizer assembly so that it can sense
building temperature. The 2 sensors will determine which combination of outdoor and return air will provide the greatest energy savings.
SUGGESTED USE:
• To enhance economizer operation for maximum energy
savings.
NOTE: On 180-300 units, a single sensor may be used for
single-sensor, outdoor-air enthalpy control if desired.
Time GuardT II Device — Package consists of a control to be
field wired into the unit controls, and provides a 5-minute delay
in compressor operation between cooling cycles.
SUGGESTED USE:
• Prevents compressor short cycling when rapid compressor
cycles may be a problem.
Controls Upgrade Kit (036-150 Units) — See description
listed under Factory-Installed Options Description and Usage
section on page 2.
Fan/Filter Status (036-150 Units) — Provides status of indoor
(evaporator) fan (ON/OFF) or filter (CLEAN/DIRTY). Status
shall be displayed with a field-supplied indicator light at the
thermostat.
SUGGESTED USE:
• To assist in servicing the unit.
3
Head Pressure Control — Kit consists of an outdoor-air thermostat that permits adequate head pressure control during
cooling operation at low outdoor-ambient temperatures.
Refer to Trade Prices for more details or contact your local
representative.
SUGGESTED USE:
• When cooling at low-ambient outdoor temperatures is
desired.
NOTE: The head pressure control is not necessary for 036-150
units to allow cooling operation down to 25 F.
Low-Ambient Kit — Kit consists of a solid-state control and
condenser coil temperature sensor to cycle the condenser-fan
motors in order to maintain condenser-coil head pressure for
proper cooling operation. Refer to Trade Prices for more
details or contact your local representative.
SUGGESTED USE:
• Whenever cooling is required at low outdoor ambient temperatures (as low as −20 F).
• Low-ambient kit is not usually required when economizer is
used.
Electric Heat Packages — Each package consists of one or
more heater modules. Each module slides into keyed mounting
slots in the fan discharge section.
SUGGESTED USE:
• To provide heat in the unit when required.
Single Point Packages (036-150 Units) — Each package consists of a control box, which provides a watertight and UL and
UL Canada approved connection point for electric heat kits.
SUGGESTED USE:
• Required with all electric heat packages for UL and UL
Canada approved single point electrical connection on 036150 units.
Thermostats and Subbases — Provide staged cooling and
heating, automatic (or manual) changeover, fan control, and indicator light.
SUGGESTED USE:
• To control unit operations.
Barometric Relief Package (180-300 Units) — This package
is useful when it is necessary to remove excess pressure from
the conditioned space.
NOTE: Optional economizer is required with this accessory.
SUGGESTED USE:
• When the job requires the ability to relieve internal building
pressure using 180-300 units.
Power Exhaust (180-300 Units) — This package is useful
when it is necessary to remove excess pressure from the conditioned space.
NOTE: Optional economizer is required with this accessory.
SUGGESTED USE:
• When the job requires the ability to relieve internal building
pressure and pressure losses through the return-air ductwork
are greater than 0.20 in. wg using 180-300 units.
• When the job requires the ability to move large quantities
of air to relieve pressure in the conditioned space using
180-300 units.
Winter Start Time Delay Relay (216-300 Units) — Used in
conjunction with accessory low-ambient kit or head pressure
control device, permits operation in cooling at lower outdoor ambient temperatures. See Trade Prices for more details or contact
your local representative.
SUGGESTED USE:
• When job requires the ability to operate in cooling at low
outdoor-ambient temperatures.
Thru-The-Bottom Power Connection (036-150 Units) —
Used to make power connections through the bottom of the unit.
SUGGESTED USE:
• When utility connections need to be made through the bottom
of the unit.
MODEL DESCRIPTION
(ODS Model Number)
LEGEND
ODS — Order Distribution System
*Refer to Trade Price Sheets or contact your local representative for specific information regarding which options are available on which units.
Bels— Sound Levels (1 bel = 10 decibels)
EER— Energy Efficiency Ratio
IPLV — Integrated Part-Load Values
SEER — Seasonal Energy Efficiency Ratio
SOUND
RATING
(Bels)
(Bels)
*Air Conditioning and Refrigeration Institute.
†Applies only to units with capacity of 65,000 Btuh or less.
**The IPLV applies only to 2-stage cooling units.
NOTES:
1. Rated in accordance with ARI Standards 210/240-89 (unit sizes 036-120) or 360-86 (unit sizes 150-240) and 270-84.
2. Ratings are net values, reflecting the effects of circulating fan heat. The 300 size is beyond the scope of the ARI certification
program.
3. Ratings are based on:
Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F db air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature.
*Weights are for unit only (aluminum plate fins) and do not include options or crating.
CONNECTION SIZES
1
⁄89 Dia. [28.6] Field Power Supply Hole
A1
3
⁄49-14 NPT Condensate Drain
B
3
⁄89 Dia. [35] Power Supply Knockout
C1
D29 Dia. [50.8] Power Supply Knockout
NOTES:
1. Dimensions in [ ] are in millimeters.
2.Center of gravity.
3.Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Bottom to combustible surfaces (when not using curb) 0 inches. On horizontal discharge units with
electric heat 1 in. clearance to ductwork for 1 ft.
b. Condensercoil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater clear-
ance is optional.
c. Overhead, 60 in. to assure proper condenser fan operation.
d. Between units, control box side, 42 in. per NEC (National Electrical Code).
e. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
f. Between unit and block or concrete walls and other grounded surfaces, control box side,
42 in. per NEC.
g. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil or combustible surfaces as stated in
Notes 5a and b, a removable fence or barricade requires no clearance.
7. Unitsmay be installed on combustible floors made from wood or class A, B, or C roof covering material.
8. The vertical center of gravity is 18-6
gravity is shown.
BOTTOM POWER CHART, THESE HOLES REQ’D FOR USE
THREADED CONDUIT
†Select either
1
⁄29 [470] up from the bottom of the base rail. Horizontal center of
*Weights are for unit only (aluminum plate fins) and do not include options or crating.
CONNECTION SIZES
3
⁄89 Diameter [35] Field Power Supply Hole
A1
1
⁄29 Diameter [64] Power Supply Knockout
B2
3
⁄49 Diameter [44] Charging Port Hole
C1
7
D
⁄89 Diameter [22] Field Control Wiring Hole
3
⁄49-14 NPT Condensate Drain
E
F29 Diameter [51] Power Supply Knockout
NOTES:
1. Dimensions in [ ] are in millimeters.
2.Center of gravity.
3.Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Bottom to combustible surfaces (when not using curb) 0 inches. On horizontal discharge units with
electric heat 1 in. clearance to ductwork for 1 ft.
b. Condensercoil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater clear-
ance is optional.
c. Overhead, 60 in. to assure proper condenser fan operation.
d. Between units, control box side, 42 in. per NEC (National Electrical Code).
e. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
f. Between unit and block or concrete walls and other grounded surfaces, control box side,
42 in. per NEC.
g. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil and combustible surfaces as stated in
Notes 5a and b, a removable fence or barricade requires no clearance.
7. Unitsmay be installed on combustible floors made from wood or class A, B, or C roof covering material.
8. The vertical center of gravity is 18-7
bottom of the base rail. Horizontal center of gravity is shown.
BOTTOM POWER CHART, THESE HOLES REQ’D FOR USE
THREADED CONDUIT
†Select either
1
⁄29 [495] for 090 and 102, 28-09 [610] for 120 and 150 up from the
WITH ACCESSORY PACKAGES — CRBTMPWR001A00
1
(
⁄2(,3⁄4() OR CRBTMPWR002A00 (1⁄2(,11⁄4()
SIZE
1
⁄2(24 v
3
⁄4(POWER†11⁄89 [28.4]
1
⁄4(POWER†13⁄49 [44.4]
1
3
⁄49 or 11⁄49 for power, depending on wire size.
WIRE SIZE
REQ’D HOLE
SIZES (MAX.)
7
⁄89 [22.2]
7
DIMENSIONAL DRAWING — 559F180,216
LEGEND
KO — Knockout
NOTES:
1. Dimensions in ( ) are in millimeters.
2.Center of gravity.
3.Direction of airflow.
4. Ductwork to be attached to accessory roof curb or adapter only.
5. For units with electric heat, a field-supplied 90° elbow must be
installed in the supply ductwork below the unit discharge
connection.
6. Minimum clearance:
a. Rear: 78-09 (2134) for coil removal. This dimension can be re-
duced to 48-09 (1219) if conditions permit coil removal from the
top.
b. Left side: 48-09 (1219) for proper condenser coil airflow.
c. Front: 48-09 (1219) for control box access.
d. Right side: 48-09 (1219) for proper operation of damper and
power exhaust if so equipped.
e. Top: 68-09 (1829) to assure proper condenser fan operation.
f. Local codes or jurisdiction may prevail.
7. With the exception of clearance for the condenser coil and the
damper/power exhaust as stated in note no. 6, removable fence or
barricade requires no clearance.
8. Dimensions are from outside of corner post. Allow 08each side for top panel drip edge.
4. Ductwork to be attached to accessory roof curb or adapter
only.
5. For units with electric heat, a field-supplied 90° elbow must
be installed in the supply ductwork below the unit discharge
connection.
6. Minimum clearance:
a. Rear: 78-09 (2134) for coil removal. This dimension can
be reduced to 48-09 (1219) if conditions permit coil re-
moval from the top.
b. Left side: 48-09 (1219) for proper condenser coil airflow.
c. Front: 48-09 (1219) for control box access.
d. Right side: 48-09 (1219) for proper operation of damper
and power exhaust if so equipped.
e. Top: 68-09 (1829) to assure proper condenser fan
operation.
f. Local codes or jurisdiction may prevail.
7. With the exception of clearance for the condenser coil and
the damper/power exhaust as stated in note no. 6, removable fence or barricade requires no clearance.
8. Dimensionsare from outside of corner post. Allow 08on each side for top panel drip edge.
CONDENSER COILEnhanced Copper Tubes, Aluminum Lanced Fins
Rows...Fins/in.1...171...171...172...17
Total Face Area (sq ft)7.3611.3913.1910.42
CONDENSER FANPropeller Type
Nominal Cfm4100410041004100
Quantity...Diameter (in.)1...22.01...22.01...22.01...22.0
Motor Hp...Rpm
Watts Input (Total)325325325325
EVAPORATOR COILEnhanced Copper Tubes, Aluminum Double-Wavy Fins
Expansion DeviceAcutrol™ Feed Device
Rows...Fins/in.2...152...153...154...15
Total Face Area (sq ft)4.175.55.55.5
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)Std1...10 x 101...10 x 101...11 x 101...10 x 10
Type DriveStdDirectDirectDirectBelt
Nominal Cfm1200160020002400
Motor HpStd————
Maximum Continuous BhpStd.34.751.202.40
Motor Frame SizeStd48484856
Nominal Rpm High/LowStd860/8001075/9701075/970—
Fan Rpm RangeStd———1070-1460
Motor Bearing TypeBallBallBallBall
Maximum Allowable Rpm2100210021002100
Motor Pulley Pitch Diameter A/B (in.)Std———2.8/3.8
Nominal Motor Shaft Diameter (in.)Std
Fan Pulley Pitch Diameter (in.)Std———4.5
Belt, Quantity...Type...Length (in.)Std———1...A...40
Pulley Center Line Distance (in.)Std———14.7-15.5
Speed Change per Full Turn ofStd———80
Movable Pulley Flange (rpm)Alt487080—
Movable Pulley Maximum Full TurnsStd———5
From Closed PositionAlt555—
Factory SettingStd——— 3
Factory Speed Setting (rpm)Std———1225
Fan Shaft Diameter at Pulley (in.)
Alt1...10 x 101...10 x 101...10 x 10—
AltBeltBeltBelt—
††Circuit 1 consists of lower portion of both the condenser and evaporator coils, and
Circuit 2 consists of the upper portion of both coils.
\The 559F300 units require 2-in. industrial-grade filters capable of handling face ve-
locities up to 625 ft/min (such as American Air Filter no. 5700 or equivalent).
NOTE: The 036-150 units have a loss-of-charge/low-pressure switch (accessory or option) located in the liquid line. The 180-300 units have a low-pressure switch (standard)
located on the suction side.
1
2
1
⁄4...1100
1
1
1
1
2
1
⁄4...1100
⁄
2
⁄
2
⁄
2
5
⁄
8
—
1
⁄
2
14
SPECIFICATIONS — 558D090-150
UNIT SIZE090102120150
NOMINAL CAPACITY (tons)7
OPERATING WEIGHT (lb)
Unit
Al/Al*755760915930
Economizer
Durablade44444444
Parablade62626262
Roof Curb†143143143143
COMPRESSORHermetic
Quantity
No. Cylinders (per circuit)
Oil (oz)50 ea50 ea50 ea54 ea
REFRIGERANT TYPER-22
Operating Charge (lb-oz)
Circuit 14-136-145-139-6
Circuit 24-146-35-149-0
CONDENSER COILEnhanced Copper Tubes, Aluminum Lanced Fins
Rows...Fins/in.1...172...172...172...17
Total Face Area (sq ft)20.5018.0017.4225.00
CONDENSER FANPropeller Type
Nominal Cfm6500650070007000
Quantity...Diameter (in.)2...222...222...222...22
Motor Hp...Rpm
Watts Input (Total)600600600600
EVAPORATOR COILEnhanced Copper Tubes, Aluminum Double-Wavy Fins
Expansion DeviceAcutrol™ Feed Device
Rows...Fins/in.3...153...153...154...15
Total Face Area (sq ft)8.08.010.011.1
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)Std1...15 x 151...15 x 151...15 x 151...15 x 15
Type DriveStdBeltBeltBeltBelt
Nominal Cfm3000340040005000
Motor HpStd————
Maximum Continuous BhpStd2.402.402.404.20
Motor Frame SizeStd56565656
Nominal Rpm High/LowStd————
Fan Rpm RangeStd590-840685-935685-935860-1080
Motor Bearing TypeBallBallBallBall
Maximum Allowable Rpm2100210021002100
Motor Pulley Pitch Diameter A/B (in.)Std2.4/3.42.8/3.82.8/3.84.0/5.0
Nominal Motor Shaft Diameter (in.)Std
Fan Pulley Pitch Diameter (in.)Std7.07.07.08.0
Belt, Quantity...Type...Length (in.)Std1...A...491...A...491...A...491...A...52
Pulley Center Line Distance (in.)Std16.75-19.2516.75-19.2515.85-17.5015.85-17.50
Speed Change per Full Turn ofStd50505044
Movable Pulley Flange (rpm)Alt50—5050
Movable Pulley Maximum Full TurnsStd5555
From Closed PositionAlt5—5 6
Factory SettingStd5555
Factory Speed Setting (rpm)Std590685685860
Fan Shaft Diameter at Pulley (in.)1111
Alt1...15 x 15—1...15 x 151...15 x 15
AltBelt—BeltBelt
*Evaporator coil fins/condenser coil fins.
†Weight of 14-in. roof curb.
**Requires the accessory controls upgrade kit.
1
2
2
1
⁄4...1100
5
⁄
⁄
2
8
81⁄
2
2
1
⁄4...1100
5
⁄
8
2
10121⁄
2
2
1
⁄4...1100
5
⁄
8
7
⁄
8
1...16 x 25 x 1
††Circuit 1 consists of lower portion of both the condenser and evaporator coils, and
Circuit 2 consists of the upper portion of both coils.
\The 559F300 units require 2-in. industrial-grade filters capable of handling face ve-
locities up to 625 ft/min (such as American Air Filter no. 5700 or equivalent).
NOTE: The 036-150 units have a loss-of-charge/low-pressure switch (accessory or option) located in the liquid line. The 180-300 units have a low-pressure switch (standard)
located on the suction side.
Quantity
No. Cylinders (per circuit)
Oil (oz)115115,88115 ea128 ea
REFRIGERANT TYPER-22
Operating Charge (lb-oz)
Circuit 1††19-413-412-1316-12
Circuit 2—11-012-1315-12
CONDENSER COILEnhanced Copper Tubes, Aluminum Lanced Fins
Rows...Fins/in.2...173...153...154...15
Total Face Area (sq ft)22.222.222.222.2
CONDENSER FANPropeller Type
Nominal Cfm10,50014,20014,200
Quantity...Diameter (in.)3...222...302...30
Motor Hp...Rpm
Watts Input (Total)110034003400
EVAPORATOR COILCopper Tubes, Aluminum or Copper Plate Fins
Expansion DeviceTXVAcutrol™ Feed Device
Rows...Fins/in.2...173...173...154...15
Total Face Area (sq ft)17.917.917.917.9
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)2...10 x 102...10 x 102...12 x 122...12 x 122...12 x 12
Type DriveBeltBeltBeltBeltBelt
Nominal Cfm600060007200800010,000
Motor Hp3.7357
Maximum Continuous Bhp4.253.455.908.7 [208/230,575 v]
Motor Frame Size56H56H184T213T215T
Fan Rpm Range1227-15591201-14621047-12511238-14941323-1579
Motor Bearing TypeBallBallBallBallBall
Maximum Allowable Rpm15591550155015501550
Motor Pulley Pitch Diameter Min/Max (in.)3.7/4.74.3/5.34.9/5.95.4/6.45.8/7.0
Nominal Motor Shaft Diameter (in.)
Fan Pulley Pitch Diameter (in.)5.26.48.47.97.9
Belt, Quantity...Type...Length (in.)1...BX...421...BX...451...BX..501...BX..501...BX...51
Pulley Center Line Distance (in.)——13.3-14.814.6-15.414.6-15.4
Speed Change per Full Turn of6652344343
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full Turns556 66
From Closed Position
Factory Setting43.5333
Factory Speed Setting (rpm)12931279114913661451
Fan Shaft Diameter at Pulley (in.)1
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief—
Cutout426
Reset (Auto.)320
††Circuit 1 consists of lower portion of both the condenser and evaporator coils, and
Circuit 2 consists of the upper portion of both coils.
\The 559F300 units require 2-in. industrial-grade filters capable of handling face ve-
locities up to 625 ft/min (such as American Air Filter no. 5700 or equivalent).
NOTE: The 036-150 units have a loss-of-charge/low-pressure switch (accessory or option) located in the liquid line. The 180-300 units have a low-pressure switch (standard)
located on the suction side.
16
SELECTION PROCEDURE (With 559F180 Example)
I Determine cooling and heating requirements at design
II Select unit based on required cooling capacity.
Enter Gross Cooling Capacities table on page 22 for
559F180 at condenser entering dry bulb temperature
95 F, air entering evaporator at 6000 cfm, 80 F edb and
67 F ewb. The 559F180 unit will provide a total cooling capacity of 188,000 Btuh, a sensible heating capacity of
136,000 Btuh and a total unit kW of 17.8 kW. For
evaporator-air temperatures other than 80 F edb, calculate
sensible heat capacity correction, as required, using the
formula in the notes following the Cooling Capacities
tables.
NOTE: Unit ratings are gross capacities and do not include
the effect of evaporator-fan motor heat. To calculate net
capacities, see Step V.
III Select electric heat.
Heating load required is 76,000 Btuh.
76,000 Btuh
3,412 Btu/kW
Enter the Electric Resistance Heater Data table for the
559F180 on page 64 at 230-3-60. The 34 kW electric
heater most closely satisfies the heat required.
= kW of heat required
= 22.3 kW
IV Determine fan speed and motor horsepower require-
ments at design conditions.
Enter Accessory/FIOP Static Pressure Drop table on
page 47 at selected unit size and heater kW.
Find that at given air quantity (6000 cfm), pressure loss is
.09 in. wg.
Before entering the Air Delivery tables, calculate the total
static pressure required based on unit components. From
the given and the Accessory/FIOP Pressure table
(page 47) find:
External static pressure0.66 in. wg
34 kW Heater static pressure0.09 in. wg
Total static pressure0.75 in. wg
Enter Air Delivery table for unit 559F180 on page 42. Interpolate to see that at 6000 cfm and 0.75 in. wg external
static pressure, the fan speed is 1184 rpm, the watts are
2631, and the bhp is 2.96. The standard motor with a fieldsupplied drive is suitable.
V Determine net cooling capacity.
Cooling capacities are gross capacities and do not include
indoor (evaporator) fan motor (IFM) heat.
Use the watts input power to the motor from the Air Delivery table (calculated in Section IV above).
IFM watts = 2631
Determine net cooling capacity using the following
fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
3. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details.
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)
2.indicates field-supplied motor and drive are required.
3.
4. Maximum usable watts input is 1000 and maximum continuous bhp
indicates maximum usable bhp/watts.
is 1.00. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using
0.70.80.91.01.11.2
LEGEND
External Static Pressure (in. wg)
your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
5. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
6. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details.
7. Motor drive range: 760 to 1000 rpm. All other rpms require fieldsupplied drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
26
AIR DELIVERY — 558D036-150 VERTICAL DISCHARGE UNITS (cont)
your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
3. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details.
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)
2.indicates field-supplied motor and drive are required.
3.
4. Maximum usable watts input is 1000 and maximum continuous bhp
is 1.00. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
5. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
6. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details.
7. Motor drive range: 835 to 1185 rpm. All other rpms require fieldsupplied drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
27
AIR DELIVERY — 558D036-150 VERTICAL DISCHARGE UNITS (cont)
your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
3. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details.
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)
2.indicates field-supplied motor and drive are required.
3.
4. Maximum usable watts input is 1921 and maximum continuous bhp
indicates maximum usable bhp/watts.
is 1.80. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using
1.01.21.41.61.8
LEGEND
External Static Pressure (in. wg)
your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
5. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
6. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details.
7. Motor drive range: 900 to 1300 rpm. All other rpms require fieldsupplied drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
28
AIR DELIVERY — 558D036-150 VERTICAL DISCHARGE UNITS (cont)
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)
2.indicates field-supplied motor and drive are required.
3.
4. Maximum usable watts input is 2120 and maximum continuous bhp
indicates maximum usable bhp/watts.
is 2.40. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using
0.10.20.40.60.8
Standard Belt-Drive Motor
External Static Pressure (in. wg)
1.01.21.41.6
LEGEND
External Static Pressure (in. wg)
your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
5. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
6. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details.
7. Motor drive range: 1070 to 1460 rpm. All other rpms require fieldsupplied drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
29
AIR DELIVERY — 558D036-150 VERTICAL DISCHARGE UNITS (cont)
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 9.)
2.indicates alternate drive is required.
3.indicates field-supplied motor and drive are required.
4.
5.
6. Maximum usable watts input is 2120 and maximum continuous bhp
is 2.40. Extensive motor and electrical testing on these units
0.20.40.60.81.01.2
Standard Belt-Drive Motor
External Static Pressure (in. wg)
1.41.61.82.0
LEGEND
indicates maximum usable bhp/watts of standard drive.
indicates maximum usable bhp/watts of alternate drive.
External Static Pressure (in. wg)
ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For additional information on motor performance refer to Evaporator-Fan Motor Performance table on
page 62.
7. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
8. Use of a field-supplied motor may affect wire sizing. Contact your
local representative for details.
9. Standard drive range: 590 to 840 rpm. Alternate drive range: 685 to
935 rpm. All other rpms require field-supplied drive.
10. Interpolation is permissible. Do not extrapolate.
11. Minimum allowable cfm is 300 cfm/ton.
30
AIR DELIVERY — 558D036-150 VERTICAL DISCHARGE UNITS (cont)
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)
2.indicates field-supplied motor and drive are required.
3.
4. Maximum usable watts input is 2120 and maximum continuous bhp
indicates maximum usable bhp/watts.
is 2.40. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using
0.20.40.60.81.01.2
Standard Belt-Drive Motor
External Static Pressure (in. wg)
1.41.61.82.0
LEGEND
External Static Pressure (in. wg)
your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance refer to
Evaporator-Fan Motor Performance table on page 62.
5. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
6. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details.
7. Motor drive range: 685 to 935 rpm. All other rpms require fieldsupplied drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
31
AIR DELIVERY — 558D036-150 VERTICAL DISCHARGE UNITS (cont)
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied or alternate (as appropriate)
drive is required. (See Note 9.)
2.indicates alternate motor and drive are required.
3.indicates field-supplied motor and drive are required.
4.
5.indicates maximum usable bhp/watts of alternate motor.
6. Maximum usable watts input is 2120 with standard motor and 2615
with alternate motor. Maximum continuous bhp is 2.40 with
1.41.61.82.0
LEGEND
indicates maximum usable bhp/watts of standard motor.
External Static Pressure (in. wg)
standard motor and 2.90 with alternate motor.Extensive motor and
electrical testing on these units ensures that the full range of the
motor can be utilized with confidence. Using your fan motors up to
the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For additional information on motor performance, refer to Evaporator-Fan
Motor Performance table on page 62.
7. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
8. Use of a field-supplied motor may affect wire sizing. Contact your
local representative for details.
9. Standard motor drive range: 685 to 935 rpm. Alternate motor drive
range: 835 to 1085 rpm. All other rpms require field-supplied drive.
10. Interpolation is permissible. Do not extrapolate.
11. Minimum allowable cfm is 300 cfm/ton.
32
AIR DELIVERY — 558D036-150 VERTICAL DISCHARGE UNITS (cont)
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied or alternate (as appropriate) drive is re-
2.indicates alternate motor and drive are required.
3.indicates field-supplied motor and drive are required.
4.
5.indicates maximum usable bhp/watts of alternate motor.
6. Maximum usable watts input is 3775 with standard motor and 4400 with al-
RpmBhpWattsRpmBhpWattsRpmBhpWattsRpmBhpWatts
quired. (See Note 9.)
indicates maximum usable bhp/watts of standard motor.
ternate motor. Maximum continuous bhp is 4.20 with standard motor and 5.25
1.41.61.82.0
LEGEND
Standard and Alternate Belt-Drive Motors
External Static Pressure (in. wg)
with alternate motor. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected. For additional information on motor performance, refer to Evaporator-Fan Motor
Performance table on page 62.
7. Values include losses for filters, unit casing, and wet coils. See page 47 for
accessory/FIOP static pressure information.
8. Use of a field-supplied motor may affect wire sizing. Contact your local rep-
resentative for details.
9. Standard motor drive range: 860 to 1080 rpm. Alternate motor drive range:
900 to 1260 rpm. All other rpms require field-supplied drive.
10. Interpolation is permissible. Do not extrapolate.
11. Minimum allowable cfm is 300 cfm/ton.
33
AIR DELIVERY — 558D036-150 HORIZONTAL DISCHARGE UNITS
your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
3. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details.
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 4.)
2. Maximum usable watts input is 1000 and maximum continuous bhp
is 1.00. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or prematuremotor failure. Unit warrantywill not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
3. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
4. Motor drive range: 760 to 1000 rpm. All other rpms require fieldsupplied drive.
5. Interpolation is permissible. Do not extrapolate.
6. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details.
7. Minimum allowable cfm is 300 cfm/ton.
34
AIR DELIVERY — 558D036-150 HORIZONTAL DISCHARGE UNITS (cont)
your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
3. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details.
that the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or prematuremotor failure. Unit warrantywill not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
5. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
6. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details.
7. Motor drive range: 835 to 1185 rpm. All other rpms require fieldsupplied drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
35
AIR DELIVERY — 558D036-150 HORIZONTAL DISCHARGE UNITS (cont)
your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
3. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details.
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)
2.indicates field-supplied motor and drive are required.
3.
4. Maximum usable watts input is 1921 and maximum continuous bhp
is 1.80. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using
indicates maximum usable bhp/watts.
1.01.21.41.61.8
LEGEND
External Static Pressure (in. wg)
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or prematuremotor failure. Unit warrantywill not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
5. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
6. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details.
7. Motor drive range: 900 to 1300 rpm. All other rpms require fieldsupplied drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
36
AIR DELIVERY — 558D036-150 HORIZONTAL DISCHARGE UNITS (cont)
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)
2.indicates field-supplied motor and drive are required.
3.
4. Maximum usable watts input is 2120 and maximum continuous bhp
is 2.40. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using
indicates maximum usable bhp/watts.
0.10.20.40.60.8
Standard Belt-Drive Motor
External Static Pressure (in. wg)
1.01.21.41.6
External Static Pressure (in. wg)
your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
5. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
6. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details.
7. Standard motor drive range: 1070 to 1460 rpm. All other rpms require field-supplied drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
37
AIR DELIVERY — 558D036-150 HORIZONTAL DISCHARGE UNITS (cont)
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 9.)
2.indicates alternate drive is required.
3.indicates field-supplied motor and drive are required.
4.
5.
6. Maximum usable watts input is 2120 and maximum continuous bhp
indicates maximum usable bhp/watts of standard drive.
indicates maximum usable bhp/watts of alternate drive.
is 2.40. Extensive motor and electrical testing on these units
0.20.40.60.81.0
1.21.41.61.82.0
LEGEND
External Static Pressure (in. wg)
Standard Belt-Drive Motor
External Static Pressure (in. wg)
ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For additional information on motor performance, refer to Evaporator-Fan Motor Performance table on
page 62.
7. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
8. Use of a field-supplied motor may affect wire sizing. Contact your
local representative for details.
9. Standard drive range: 590 to 840 rpm. Alternate drive range: 685 to
935 rpm. All other rpms require field-supplied drive.
10. Interpolation is permissible. Do not extrapolate.
11. Minimum allowable cfm is 300 cfm/ton.
38
AIR DELIVERY — 558D036-150 HORIZONTAL DISCHARGE UNITS (cont)
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)
2.indicates field-supplied motor and drive are required.
3.
4. Maximum usable watts input is 2120 and maximum continuous bhp
indicates maximum usable bhp/watts.
is 2.40. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using
0.20.40.60.81.0
1.21.41.61.82.0
LEGEND
External Static Pressure (in. wg)
Standard Belt-Drive Motor
External Static Pressure (in. wg)
your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
5. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
6. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details.
7. Motor drive range: 685 to 935 rpm. All other rpms require fieldsupplied drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
39
AIR DELIVERY — 558D036-150 HORIZONTAL DISCHARGE UNITS (cont)
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied or alternate (as appropriate)
drive is required. (See Note 9.)
2.indicates an alternate motor and drive are required.
3.indicates field-supplied motor and drive are required.
4.
5.indicates maximum usable bhp/watts of alternate motor.
6. Maximum usable watts input is 2120 with standard motor and 2615
indicates maximum usable bhp/watts of standard motor.
with alternate motor. Maximum continuous bhp is 2.40 with
1.21.41.61.82.0
LEGEND
External Static Pressure (in. wg)
standard motor and 2.90 with alternate motor.Extensive motor and
electrical testing on these units ensures that the full range of the
motor can be utilized with confidence. Using your fan motors up to
the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
7. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
8. Use of a field-supplied motor may affect wire sizing. Contact your
local representative for details. For additional information on motor
performance, refer to Evaporator-Fan Motor Performance table on
page 62.
9. Standard motor drive range: 685 to 935 rpm. Alternate motor drive
range: 835 to 1085 rpm. All other rpms require field-supplied drive.
10. Interpolation is permissible. Do not extrapolate.
11. Minimum allowable cfm is 300 cfm/ton.
40
AIR DELIVERY — 558D036-150 HORIZONTAL DISCHARGE UNITS (cont)
indicates maximum usable bhp/watts of standard motor.
1.21.41.61.82.0
LEGEND
Standard and Alternate Belt-Drive Motors
External Static Pressure (in. wg)
6. Maximum usable watts input is 3775 with standard motor and 4400 with
alternate motor. Maximum continuous bhp is 4.20 with standard motor and
5.25 with alternate motor. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized with confidence.
Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
7. Values include losses for filters, unit casing, and wet coils. See page 47 for
accessory/FIOP static pressure information.
8. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details. For additional information on motor performance, refer
to Evaporator-Fan Motor Performance table on page 62.
9. Standard motor drive range: 860 to 1080 rpm. Alternate motor drive range:
900 to 1260 rpm. All other rpms require field-supplied drive.
10. Interpolation is permissible. Do not extrapolate.
11. Minimum allowable cfm is 300 cfm/ton.
41
AIR DELIVERY — 559F180-300 UNITS
559F180 (15 TON)
Standard Belt-Drive Motor; 208/230-V and 460-V Units
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required. (See Note 2.)
2. Factory-shipped motor drive range is 1227 to 1559 rpm. Other rpms
require a field-supplied drive.
3. Maximum continuous bhp is 4.25 and maximum continuous watts
are 3775. Do not adjust motor rpm such that motor maximum bhp
and/or watts is exceeded at the maximum operating cfm.
4. Static pressure losses (i.e., economizer) must be added to external
static pressure before entering Air Delivery table. See page 47 for
accessory/FIOP static pressure information.
0.20.40.60.81.01.1
Standard Belt-Drive Motor; 208/230-V and 460-V Units
External Static Pressure (in. wg)
1.21.41.61.82.0
LEGEND
External Static Pressure (in. wg)
5. Interpolation is permissible. Do not extrapolate.
6. Fan performance is based on wet coils, clean filters, and casing
losses.
7. Extensive motor and drive testing on these units ensures that the full
horsepower and watts range of the motor can be utilized with confidence. Using your fan motors up to the watts or bhp rating shown will
not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
8. Minimum allowable cfm is 300 cfm/ton.
9. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details. For additional information on motor
performance, refer to Evaporator-Fan Motor Performance table on
page 62.
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required. (See Note 2.)
2. Factory-shipped motor drive range is 1201 to 1462 rpm. Other rpms
require a field-supplied drive.
3. Maximum continuous bhp is 3.45 and maximum continuous watts
are 3065. Do not adjust motor rpm such that motor maximum bhp
and/or watts is exceeded at the maximum operating cfm.
4. Static pressure losses (i.e., economizer) must be added to external
static pressure before entering Air Delivery table. See page 47 for
accessory/FIOP static pressure information.
0.20.40.60.81.01.1
Standard Belt-Drive Motor; 575-V Units
External Static Pressure (in. wg)
1.21.41.61.82.0
LEGEND
External Static Pressure (in. wg)
5. Interpolation is permissible. Do not extrapolate.
6. Fan performance is based on wet coils, clean filters, and casing
losses.
7. Extensive motor and drive testing on these units ensures that the full
horsepower and watts range of the motor can be utilized with confidence. Using your fan motors up to the watts or bhp rating shown will
not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
8. Minimum allowable cfm is 300 cfm/ton.
9. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details. For additional information on motor
performance, refer to Evaporator-Fan Motor Performance table on
page 62.
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required. (See Note 2.)
2. Factory-shipped motor drive range is 1047 to 1251 rpm. Other rpms
require a field-supplied drive.
3. Maximum continuous bhp is 5.90 and maximum continuous watts
are 5180. Do not adjust motor rpm such that motor maximum bhp
and/or watts is exceeded at the maximum operating cfm.
4. Static pressure losses (i.e., economizer) must be added to external
static pressure before entering Air Delivery table. See page 47 for
accessory/FIOP static pressure information.
0.20.40.60.81.0
Standard Belt-Drive Motor
External Static Pressure (in. wg)
1.21.41.61.8
LEGEND
External Static Pressure (in. wg)
5. Interpolation is permissible. Do not extrapolate.
6. Fan performance is based on wet coils, clean filters, and casing
losses.
7. Extensive motor and drive testing on these units ensures that the full
horsepower range of the motor can be utilized with confidence. Using your fan motors up to the watts or bhp rating shown will not result
in nuisance tripping or premature motor failure. Unit warranty will not
be affected.
8. Minimum allowable cfm is 300 cfm/ton.
9. Use of a field-supplied motor may affect wire sizing. Contact your local representative for details. For additional information on motor
performance, refer to Evaporator-Fan Motor Performance table on
page 62.
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required. (See Note 3.)
2.indicates additional capability of 460 v motor.
3. Factory-shipped motor drive range is 1238 to 1494 rpm. Other rpms
require a field-supplied drive.
4. Maximum continuous bhp is 8.7 (208/230, 575 v) or 9.5 (460 v)
and maximum continuous watts are 7915 (208/230, 575 v) or
8640 (460 v). Do not adjust motor rpm such that motor maximum bhp
and/or watts is exceeded at the maximum operating cfm.
5. Static pressure losses (i.e., economizer) must be added to external
static pressure before entering Air Delivery table.
0.20.40.60.81.0
1.21.41.61.82.0
LEGEND
External Static Pressure (in. wg)
Standard Belt-Drive Motor
External Static Pressure (in. wg)
6. Interpolation is permissible. Do not extrapolate.
7. Fan performance is based on wet coils, clean filters, and
casing losses. See page 47 for accessory/FIOP static pressure
information.
8. Extensive motor and drive testing on these units ensures that the
full horsepower range of the motor can be utilized with confidence.
Using your fan motors up to the watts or bhp rating shown will not
result in nuisance tripping or premature motor failure. Unit warranty
will not be affected.
9. Minimum allowable cfm is 300 cfm/ton.
10. Use of a field-supplied motor may affect wire sizing. Contact your
local representative for details. For additional information on motor
performance, refer to Evaporator-Fan Motor Performance table on
page 62.
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Watts Input to Motor
NOTES:
1. Boldface indicates field-supplied drive is required. (See Note 3.)
2.indicates additional capability of 460-v motor.
3. Factory-shipped motor drive range is 1323 to 1579 rpm. Other rpms
require a field-supplied drive.
4. Maximum continuous bhp is 10.26 (208/230, 575 v) or 11.80 (460 v)
and maximum continuous watts are 9510 (208/230, 575 v) or
11,000 (460 v). Do not adjust motor rpm such that motor maximum
bhp and/or watts is exceeded at the maximum operating cfm.
5. Static pressure losses (i.e., economizer) must be added to external
static pressure before entering Air Delivery table.
6. Interpolation is permissible. Do not extrapolate.
7. Fan performance is based on wet coils, clean filters, and
casing losses. See page 47 for accessory/FIOP static pressure
information.
8. Extensive motor and drive testing on these units ensures that the
full horsepower and watts range of the motor can be utilized with
confidence. Using your fan motors up to the watts or bhp rating
shown will not result in nuisance tripping or premature motor failure.
Unit warranty will not be affected.
9. Minimum allowable cfm is 280 cfm/ton in cooling.
10. Use of a field-supplied motor may affect wire sizing. Contact your
local representative for details. For additional information on motor
performance, refer to Evaporator-Fan Motor Performance table on
page 62.
NOTE: The 389210-201 high static regain adapter accessory may
be used to provide horizontal supply/return.
559F180-300 Horizontal Supply/Return Fan Performance
With 389210-201 High Static Regain Adapter Curb
NOTE: The 389210-201 horizontal supply/return adapter accessory
improves 559F180-300 fan performance by increasing external
static pressure by amount shown above.
Min Max RLA LRA Quantity Hp FLA FLA Nom kW**FLAMCAMOCP††FLALRA
Std
208/230-1-60
187 254 28.31411
Alt8.5
Std
060
(5 Ton)
208/230-3-60
187 254 17.71101
Alt8.5
Std
460-3-60
414 5088.6551
Alt4.5
Std
518 6326.4441
Alt2.6——11.4151262
Std187 25420.91421
072
(6 Ton)
575-3-60
208/230-
3-60
460-3-60Std4145089.9721
575-3-60Std5186327.9581
LEGEND
FLA— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC— National Electrical Code
OFM— Outdoor (Condenser) Fan Motor
RLA— Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and
575 v.Heaters are rated at 240 v, 480 v, and 575 v.If power distribution voltage to unit
varies from rated heater voltage, heater kW will vary accordingly. To determine heater
capacity at actual unit voltage, multiply 240 v, 480 v, or 575 v capacity by multipliers
found in Electric Heat Multiplication Factors table on page 48.
†Used to determine minimum disconnect size per NEC.
**Heaters are field installed only.
††Fuse or HACR circuit breaker.
\Fusing in single point box provides the required branch circuit protection.
NOTES:
1. Incompliance with NEC requirements for multimotor and combination load equipment
(refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall
be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than
2%.
Use the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance =100 x
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
max voltage deviation from average voltage
452 + 464 + 455
1371
=
3
= 457
COMPR
(each)
OFMIFM
1
1
1
1
1
1
1
LEGEND AND NOTES FOR ELECTRICAL DATA TABLES ON PAGES 49-54
Min Max RLA LRA Qty Hp FLA FLA Nom kW**FLAMCAMOCP††FLALRA
COMPR
(ea)
OFMIFM
Std
208/230-3-60
187 254 22.3 142.02
1
⁄41.4
Alt15.0
Std
414 508 10.472.02
1
⁄40.8
(12
150
1
⁄2Tons)
460-3-60
Alt7.4
Std
1
575-3-60
518 6329.658.52
⁄40.8
Alt7.4
LEGEND AND NOTES FOR ELECTRICAL DATA TABLES ON PAGES 49-54
FLA— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC— National Electrical Code
OFM— Outdoor (Condenser) Fan Motor
RLA— Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and
575 v. Heaters are rated at 240 v, 480 v, and 575 v. If power distribution voltage
to unit varies from rated heater voltage, heater kW will vary accordingly.To determine heater capacity at actual unit voltage, multiply 240 v, 480 v, or 575 v
capacity by multipliers found in Electric Heat Multiplication Factors table on
page 48.
†Used to determine minimum disconnect size per NEC.
**Heaters are field installed only.
††Fuse or HACR circuit breaker.
\Fusing in single point box provides the required branch circuit protection.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The Canadian units may be
fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2%.
imbalance.
% Voltage Imbalance = 100 x
EXAMPLE: Supply voltage is 460-3-60.
LEGEND
Use the following formula to determine the percent of voltage
max voltage deviation from average voltage
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
FLA— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC— National Electrical Code
OFM— Outdoor (Condenser) Fan Motor
RLA— Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and
†Used to determine minimum disconnect size per NEC.
**Heaters are field installed only.
††Fuse or HACR circuit breaker.
\Fusing in single point box provides the required branch circuit protection.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
2. Unbalanced 3-Phase Supply Voltage
NOMINAL
V-PH-Hz
208/230-3-60 18725435.619835.6198215.50 25.0/25.0
240
460-3-6041450817.89917.899212.8013.0
575-3-6051863214.37914.379213.4010.0
208/230-3-60 18725443.622843.6228215.50 28.0/28.0
300
460-3-6041450822.1114 22.1114212.8014.6
575-3-6051863217.99117.991213.4013.0
575 v. Heaters are rated at 240 v, 480 v, or 575 v. If power distribution voltage
to unit varies from rated heater voltage, heater kW will vary accordingly.To determine heater capacity at actual unit voltage, multiply 240 v, 480 v, or 575 v
capacity by multipliers found in Electric Heat Multiplication Factors table on
page 48.
equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The Canadian units may be
fuse or circuit breaker.
Never operate a motor where a phase imbalance in supply voltage is greater
than 2%.
imbalance.
EXAMPLE: Supply voltage is 460-3-60.
Use the following formula to determine the percent of voltage
% Voltage Imbalance = 100 x
RANGE
Min Max RLA LRA RLA LRA Quantity Hp
LEGEND
max voltage deviation from average voltage
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
COMPRESSOR
No. 1No. 2
LEGEND AND NOTES FOR ELECTRICAL DATA TABLES ON PAGES 49-54
average voltage
452 + 464 + 455
3
1371
=
3
= 457
OFMIFM
FLA
FLAFLA LRAFLANom kW**MCAMOCP††
(ea)
Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.
3. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps)
+ (1.00 x heater FLA).
stat calls for cooling, terminals G and Y1 are energized. The indoor (evaporator) fan contactor (IFC) and compressor contactor
no. 1 (C1) are energized and evaporator-fan motor, compressor
no. 1 (036-150 and 216-300) or unloaded compressor (180),
and condenser fan(s) start. The condenser-fan motor runs continuously while unit is cooling. On 090-300 units, if the thermostat calls for a second stage of cooling by energizing Y2,
compressor contactor no. 2 (C2) is energized and compressor
no. 2 starts (090-150 and 216-300), or compressor no. 1 runs
fully loaded (180).
HEATING, UNITS WITHOUT ECONOMIZER (IF ACCESSORY
OR OPTIONAL HEATER IS INSTALLED) — Upon a call for
heating through terminal W1, IFC and heater contactor no. 1
(HC1) are energized. On units equipped for 2 stages of heat,
when additional heat is needed, HC2 is energized through W2.
COOLING, UNITS WITH DURABLADE ECONOMIZER (036-
150) — When the outdoor-air temperature is above the outdoor-
air thermostat (OAT) setting and the room thermostat calls for
cooling, compressor contactor no. 1 is energized to start compressor no. 1 and the condenser-fan motor. The evaporator-fan
motor is energized and the economizer damper moves to the
minimum position. Upon a further call for cooling, compressor
contactor no. 2 will be energized, starting compressor no. 2. After the thermostat is satisfied, the damper moves to the fullyclosed position.
When the outdoor-air temperature is below the OAT setting and
the thermostat calls for cooling, the economizer dampers move
to the minimum position. If the supply-air temperature is above
57 F, the damper continues to open until it reaches the fullyopenpositionoruntil thesupply-airtemperaturedropsbelow 57F.
When the supply-air temperature falls to between 57 F and 52 F,
the damper will remain at an intermediate open position. If the
supply-air temperature falls below 52 F, the damper will modulate closed until it reaches the minimum position or until the
supply-air temperature is above 52 F. When the thermostat is
satisfied, the damper will move to the fully-closed position.
If the outdoor air alone cannot satisfy the cooling requirements
of the conditioned space, economizer cooling is integrated with
mechanical cooling, providing second-stage cooling. Compressor no. 1 and the condenser fan will be energized and the
position of the economizer damper will be determined by the
supply-air temperature. Compressor no. 2 is locked out.
When the second stage of cooling is satisfied, the compressor
and condenser-fan motor will be deenergized. The damper position will be determined by the supply-air temperature.
When the first stage of cooling is satisfied, the damper will move
to fully-closed position.
COOLING, UNITS WITH PARABLADE ECONOMIZER
(036-072) — When the outdoor air is above the enthalpy control
(EC) setting, and the room thermostat calls for cooling, the compressor contactor is energized to start the compressor and the
condenser-fan motor. The evaporator-fan motor is energized
and the economizer damper moves to the minimum position. After the room thermostat is satisfied, the damper will spring return to the fully-closed position.
When the outdoor-air is below the EC setting and the thermostat
calls for cooling, the economizer outdoor-air damper is opened
proportionally to maintain between 50 and 56 F at the mixed-air
sensor. If outdoor air alone cannot satisfy the cooling requirements, economizer cooling is integrated with mechanical cooling. When the room thermostat is satisfied, the damper will
spring return to the fully-closed position.
COOLING, UNITS WITH PARABLADE ECONOMIZER
(090-150) — When the outdoor-air is above the enthalpy control
(EC) setting, and the room thermostat calls for cooling, compressor contactor no. 1 is energized to start compressor
no. 1 and the condenser-fan motor.The evaporator-fan motor is
energized and the economizer damper moves to the minimum
position. Upon a further call for cooling, compressor contactor
no. 2 is energized, starting compressor no. 2. After the room
thermostat is satisfied, the damper will spring return to the fullyclosed position.
When the outdoor-air temperature is below the EC setting and
the thermostat calls for cooling, the economizer outdoor-air
damper is opened proportionally to maintain between 50 and
56 F at the mixed-air sensor. If outdoor-air alone cannot satisfy
the cooling requirements, economizer cooling is integrated with
mechanical cooling, and the second compressor is locked out.
When the room thermostat is satisfied, the damper will spring
return to the fully-closed position.
COOLING, UNITS WITH ECONOMIZER (180-300) — Upon a
call for cooling, when outdoor ambient temperature is above the
temperature control setting, the evaporator and condenser fans
and compressor energize. The economizer damper moves to
VENT position.
Upon a first-stage call for cooling, when outdoor ambient temperature is below the temperature control setting, the evaporator fan starts and economizer damper modulates to maintain
mixed-air temperature. The compressor(s) remains off.
Upon a second-stage call for cooling, compressor no. 1 (180-
300) or unloaded compressor (180) is energized and mechanical cooling is integrated with economizer cooling. Compressor
no. 2 is locked out. If the air temperature is above 50 F, a cooling
lockout switch prevents the compressor(s) from running.
When supply-air temperature drops below a fixed set point, the
economizer damper modulates to maintain the temperature at
the fixed set point.
A freeze protection thermostat (FPT) is located on the evaporator coil. It detects frost build-up and turns off the compressor, allowing the coil to clear. Once frost has melted, the compressor
can be reenergized.
HEATING, UNITS WITH ECONOMIZER (036-150) (IFACCESSORY OR OPTIONAL HEATER IS INSTALLED) — When the
room thermostat calls for heat through terminal W1, the
evaporator-fan contactor and heater contactor no. 1 are energized. On units equipped for 2 stages of heat, when additional
heat is needed, heater contactor no. 2 is energized through W2.
The economizer damper moves to the minimum position during
heating. When the thermostat is satisfied, the damper moves to
the fully closed position.
HEATING, UNITS WITH ECONOMIZER (180-300) (IFACCESSORY OR OPTIONAL HEATER IS INSTALLED) — The
outdoor-air damper stays at VENT position while the evaporator
fan is operating. Refer to Heating, Units Without Economizer
section, above, for remainder of operating sequence.
55
TYPICAL WIRING SCHEMATIC — 558D036-150
56
(See Legend, page 59.)
TYPICAL WIRING SCHEMATIC — 559F180-300
57
(See Legend, page 59.)
TYPICAL INSTALLATION — 558D090-150
Vertical Discharge Ducting
NEC — National Electrical Code
Horizontal Discharge Ducting
58
TYPICAL INSTALLATION — 559F180-300
NEC — National Electrical Code
NOTES:
1. Illustration shown is a general guide only and is not intended to
include all details for any specific installation.
2. Installation must comply with all applicable codes.
LEGEND FOR TYPICAL WIRING SCHEMATICS
AHA— Adjustable Heat Anticipator
BRK W/AT — Breaks With Amp Turns
C—Contactor, Compressor
CB— Circuit Breaker
CC— Cooling Compensator
CH— Crankcase Heater
CLO— Compressor Lockout
CLS— Compressor Lockout Switch
COMP— Compressor Motor
CT— Current Transformer
DM— Damper Motor
DU— Dummy Terminal
EC— Enthalpy Control
EQUIP— Equipment
FL— Fuse Link
FPT— Freeze Protection Thermostat
FU— Fuse
GND— Ground
HC— Heater Contactor
HPS— High-Pressure Switch
HTR— Heater
IFC— Indoor (Evaporator) Fan Contactor
IFCB— Indoor (Evaporator) Fan Circuit Breaker
IFM— Indoor (Evaporator) Fan Motor
IFR— Indoor (Evaporator) Fan Relay
IP— Internal Protector
L—Light
LOR — Lockout Relay
LPS— Low-Pressure Switch
LS— Limit Switch
MAT — Mixed-Air Thermostat
NC— Normally Closed
NEUT — Neutral
NO— Normally Open
OAT — Outdoor-Air Thermostat
OFC — Outdoor (Condenser) Fan Contactor
OFM — Outdoor (Condenser) Fan Motor
OP— Overcurrent Protector
PL— Plug Assembly
PRI— Primary
QT— Quadruple Terminal
SW— Switch
SW1 — Switch, Fully Open
SW2 — Switch, Fully Closed
SW3 — Switch, Minimum Vent Position
SW4 — Switch, Maximum Vent Position
Field Control Wiring
Field Power Wiring
Accessory Wiring or Optional Wiring
Accessory
To indicate common potential only,
not to represent wiring
59
APPLICATION DATA
1. Units approved for outdoor installation only.
2. Ductwork (036-150) — Secure vertical discharge ductwork
to roof curb. For horizontal discharge applications, either attach ductwork to unit, or use field-supplied flanges attached
to the horizontal discharge openings and attach all ductwork to flanges.
3. Ductwork (180-300) — Ductwork should be attached to the
curb on all units. Interior installation may proceed before
unit is set in place on roof. If ductwork is to be attached to
unit, do not drill in condensate drain pan area — leaks may
result. Field-fabricated concentric ductwork may be connected as shown on page 61.
4. On 180-300 size units with electric heat, a field-supplied
90° elbow must be installed in the supply ductwork below
the unit discharge connection.
5. To convert from vertical discharge to horizontal discharge
(036-150):
a. Remove Durablade economizer or two-position damper
to gain access to return duct opening.
b. Move the horizontal-discharge duct opening covers to
the vertical discharge openings.
c. Rotate economizer or two-position damper 90 degrees.
d. Rotate the barometric relief damper 90 degrees.
e. Install block-off plate over the opening on the access
panel.
NOTE: Parablade economizer is only used for vertical discharge units.
6. Roof curb connections allow field power wires and control
wires to enter through the roof curb opening.
7. Use of 2-stage heating and cooling thermostat is recommended for all units. A 2-stage cooling thermostat is required on units with accessory economizer to provide
integrated cooling.
8. All units are automatic changeover from heating to cooling
when automatic changeover thermostat and subbase are
used.
9. Units are draw-thru on cooling and blow-thru on heating.
10. To minimize the possibility of condensate blow-off from
evaporator, airflow through units should not exceed
500 cfm/ton on 036-240 units and 11,250 cfm on 300 units.
11. For cooling minimum airflow is 300 cfm/ton for 036-240
units and 280 cfm/ton on 300 units. For units with electric
heating, required minimum cfm is 900 for 036; 1200 for 048;
1500 for 060; 1800 for 072; 2250 for 090; 2550 for 102; and
3000 for 120 and 150, with the following exceptions:
NOTE: The 180-300 units with electric heating have a required
minimum heating of 300 cfm/ton.
12. Minimumambientcoolingoperatingtemperature
(036-150) — The minimum temperature for size 036-150
standard units is 25 F. With accessory low-ambient kit, units
can operate at outdoor temperatures down to –20 F.
13. Minimumambientcoolingoperationtemperature
(180-300) — Units are designed to operate at outdoor temperatures down to 40 F for 180, 35 F for 216, 25 F for 240,
and 48 F for 300. Tooperate at lower outdoor temperatures,
see Trade Prices or contact your local representative for
appropriate accessories.
14. Due to the internal unit design (draw-thru over the motor),
air path, and specially designed motors, the full horsepower
(maximum continuous bhp) listed in the Specifications table
and the notes following each Air Delivery table can be utilized with confidence.
Using motors with the values listed in the Specifications
table
will not
result in nuisance tripping or premature motor
failure. The unit warranty will not be affected.
60
APPLICATION DATA (cont)
NOTE: Do not drill in this area, damage to basepan may result in water
leak.
Concentric Duct Air Distribution
(180-300 Only)
OPTION AND ACCESSORY LIST
Durablade Economizer (036-150; Includes Hood)XX
Parablade Economizer (036-150)X
Integrated Economizer (180-300)XX
Manual Outdoor-Air Dampers**XX††
Controls Upgrade Kit (036-150)|XX
Condenser Coil Grille (036-150)XX
Alternate Drive (090)X
Alternate Motor and Drive (036-060, 120, 150)X
Electric Heat and Single Point KitsX¶
25% Open Two-Position DamperX
100% Open Two-Position Damper (036-150)X
Barometric Relief Damper (180-300)X
Roof Curbs (Horizontal and Vertical)X
Horizontal Adapter (180-300)X
Thermostats and SubbasesX
Power Exhaust (180-300)X
Head Pressure Control DeviceX
Low-Ambient KitsX
Time GuardT II Control CircuitX
Thru-the-Bottom Power Connections Packages (036-150)X
Solid-State Enthalpy Control (036-150)X
Enthalpy Control SensorX
Condenser Coil Hail Guard Assembly (036-150)X
Winter Start Time-Delay Relay (216-300)X
Fan/Filter Status (036-150)X
*Factory installed.
†Field installed.
**Factory installed on 180-300 units whenever factory-installed economizer is not selected.
††Only available as an accessory on 036-150 units.
\Includes high-pressure, low-pressure/loss of charge, and freeze protection switches.
¶Electric heat for 575-v units is only offered on 558D090-180 units. Electric heat is field-installed on all units.
ITEMOPTION*ACCESSORY†
Shaded area indicates block-off panels.
NOTE: Dimension A, A8 and B, B8 are obtained from field-supplied ceiling
diffuser.
Concentric Duct Details (180-300 Only)
61
APPLICATION DATA (cont)
EVAPORATOR-FAN MOTOR PERFORMANCE
UNIT
558D036
558D048
558D060
558D072Standard
558D090Standard
558D102Standard
558D120
558D150
559F180Standard
559F216Standard
559F240Standard
559F300Standard
LEGEND
BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower range of the motors can be
utilized with confidence. Using your fan motors up to the horsepower ratings shown in this table will not result in
nuisance tripping or premature motor failure. Unit warranty will not be affected.
*Two heater packages required to provide kW indicated.
NOTES:
1. The kW ratings shown above are at 240, 480, and 575 v. Use the
Electric Heat Multiplication Factors table on page 48 to determine
heater capacity for your particular voltage.
2. Heaters are not available for size 036-072, 575-v units.
VOLTAGE
(60 Hz)
208/230
(3 phase)
460
(3 phase)
575
(3 phase)
208/230
(3 phase)
460
(3 phase)
575
(3 phase)
ACCESSORY
kW
10.4
16.0
24.8
32.0
42.4*
13.9
16.5
27.8
33.0
41.7*
18.0
36.0
10.4
16.0
32.0
42.4*
50.0*
16.5
27.8
33.0
41.7*
50.0*
18.0
36.0
54.0*
ELECTRIC RESISTANCE HEATER DATA — 559F180-300
UNIT
559F
180
216-300
*Maximum number of stages using accessory low-ambient kit or head pressure control device and low-
ambient kit.
NOTE: Heaters are rated at 240 v, 480 v, and 575 v.
ENGINEERS’ SPECIFICATION GUIDE — MODELS 558D036-150 (3 TO 121⁄2TONS)
GENERAL: Furnish and install single-package, outdoor rooftopmounted, electrically controlled cooling unit utilizing a reciprocating compressor. Unit shall discharge supply air vertically or
horizontally as shown on the contract drawings.
Nominal unit electrical characteristics shall be
tory operation within voltage limits of
COOLING CAPACITY: Total cooling capacity of the unit shall
be
rator air entering unit at
bulb and condenser entering air of
design conditions shall be a minimum of
CABINET: The cabinet shall be constructed of galvanized steel,
bonderized, and coated with a prepainted baked enamel finish.
COMPRESSOR: Compressor shall be of the fully-hermetic type
with suitable vibration isolators.
CONDENSER SECTION: The condenser coils shall have aluminum plate fins mechanically bonded to seamless copper
tubes with all joints brazed. Condenser fan shall be of the directdrive propeller type and shall discharge air vertically. Fan shall
have permanently lubricated bearings.
EVAPORATOR SECTION: Evaporator coils shall have aluminum plate fins mechanically bonded to seamless copper tubes
with all joints brazed. Evaporator fan shall be direct drive with 2
or 3 speeds or belt drive as shown on the equipment drawings.
Belt drive shall include an adjustable pitch motor pulley. Bearings shall be sealed, permanently lubricated, ball-bearing type.
REFRIGERANT SYSTEM: Refrigerant system shall include
strainer assembly, fixed orifice feed system, and service gage
connections on suction line, liquid line, and compressor discharge line.
phase, 60 Hz. The unit shall be capable of satisfac-
vtov.
Btuh or greater, and sensible capacity shall be
Btuh or greater at conditions ofcfm evapo-
F dry bulb,F wet
F dry bulb. Total
Btuh/Watt.
FILTER SECTION: Filter section shall consist of factoryinstalled low velocity, 2-in. thick throwaway fiberglass filters of
commercially available sizes. Filter access panel shall provide
tool-less filter removal.
v,
CONTROLS: Unit shall be complete with self-contained lowvoltage control circuit. Safeties shall include compressor overtemperature and overcurrent.
APPROVALS: The unit shall be CSA (036-072) or UL Canada
(090-150) design certified and UL tested and certified. All wiring
shall be in accordance with NEC, and units shall meetASHRAE
Standard 62. The unit shall be rated in accordance with ARI
Standards 210/240 or 360 and 270. Units shall be designed to
conform to NRCA standards. Insulation and adhesive shall
meet NFPA 90A requirements for flame spread and smoke
generation.
OPTIONS: Factory-installed integrated economizer shall include all hardware and controls to provide cooling using outdoor
air alone, or in conjunction with mechanical cooling. Dampers
shall be low leakage type, not to exceed 3% leakage at
1.0 in. wg pressure differential. Economizer shall be capable of
introducing up to 100% outdoor air and shall be equipped with a
barometric relief damper. Economizer controls shall be dry-bulb
(variable sliding plate type economizer) or enthalpy (parallelopposed blade type economizer) type. Damper shall close on
power loss.
Other factory-installed options shall include: 25% and 100%
manual outdoor-air dampers, controls upgrade kit, condenser
coil grille, and alternate evaporator-fan motors (036-060,
120,150) and/or drives (036-060,090,120,150).
ACCESSORIES: Field-installed accessories shall include:
Variable sliding plate type economizer, roof curb (14 or 24 in.),
two-position dampers, 25% and 50% manual outdoor-air dampers, low ambient kit, short cycle circuit protection, thermostats
and subbases, condenser coil hail guard, enthalpy control, electric resistance heaters, single point packages, controls upgrade
kit, thru-the-bottom power connection package, condenser coil
grille, head pressure control, fan/filter status, and enthalpy control sensor.
65
ENGINEERS’ SPECIFICATION GUIDE — MODELS 559F180-300 (15 TO 25 TONS)
GENERAL: Furnish and install single-package, outdoor rooftopmounted, electrically controlled cooling unit utilizing reciprocating compressor(s) for cooling. Unit shall discharge supply air
vertically or horizontally as shown on the contract drawings.
Nominal unit electrical characteristics shall be
3 phase, 60 Hz. The unit shall be capable of satisfactory operation within voltage limits of
COOLING CAPACITY: Total cooling capacity of the unit shall
be
rator air entering unit at
bulb and condenser entering air of
design conditions shall be a minimum of
CABINET: The cabinet shall be constructed of galvanized steel,
bonderized and coated with a prepainted baked enamel finish.
COMPRESSOR: Compressor(s) shall be of the semi-hermetic
type with crankcase heaters, and shall have spring vibration isolators and dual independent refrigeration circuits (216-300).
CONDENSER SECTION: The condenser coils shall have aluminum plate fins mechanically bonded to seamless copper
tubes with all joints brazed. Condenser fan shall be of the directdriven propeller type and shall discharge air vertically. Fan shall
have permanently lubricated bearings.
EVAPORATOR SECTION: Evaporator coils shall have aluminum plate fins mechanically bonded to seamless copper tubes
with all joints brazed. Evaporator fan shall be belt driven as
shown on the equipment drawings. Motor bearings shall be
sealed, permanently lubricated, ball-bearing type.
REFRIGERANT SYSTEM: Refrigerant system shall include filter drier, fixed orifice feed system, and service gage connections on suction line, liquid line, and compressor discharge line,
as well as low-pressure and high-pressure protection.
Btuh or greater, and sensible capacity shall be
Btuh or greater at conditions ofcfm evapo-
vtov.
F dry bulb,F wet
F dry bulb. Total
Btuh/Watt.
FILTER SECTION: Filter section shall consist of factoryinstalled low velocity, 2-in. thick throwaway fiberglass filters of
commercially available sizes. Filter access panel shall be easy
access.
v,
CONTROLS: Unit shall be complete with self-contained lowvoltage control circuit. Safeties shall include compressor overtemperature and overcurrent.
APPROVALS: The unit shall be ETL and ETL Canada tested
and certified. All wiring shall be in accordance with NEC, and
units shall meet ASHRAE Standard 62. The unit (except 300)
shall be rated in accordance with ARI Standards 360 and 270.
Units shall be designed to conform to NRCA standards. Insulation and adhesive shall meet NFPA 90A requirements for flame
spread and smoke generation.
OPTIONS: Factory-installed integrated economizer shall include all hardware and controls to provide cooling using outdoor
air alone, or in conjunction with mechanical cooling. Dampers
shall be low leakage type, not to exceed 2% leakage at
1.0 in. wg pressure differential. Economizer shall be capable of
introducing up to 100% outdoor air and shall be equipped with a
gravity relief damper. Economizer controls shall be dry-bulb
type.
On all units where the factory-installed economizer is not chosen, the factory-installed manual outdoor-air damper shall be
included.
ACCESSORIES: Field-installed accessories shall include:
Economizer, roof curbs (14 or 24 in.), horizontal adapter, twoposition damper, low ambient kit, short cycle circuit protection,
thermostats and subbases, enthalpy control sensor, winter start
time-delay relay, electric resistance heaters, barometric relief
damper, power exhaust, and head pressure control device.
66
Bryant
Air Conditioning
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
UNIT MUST BE INSTALLED IN ACCORDANCE
WITH INSTALLATION INSTRUCTIONS
Copyright 1996 Carrier Corporation
Printed in U.S.A.6/96CATALOG NO. BY-3255-818
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.