Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV Service And Maintenance Procedures Manual

service and maintenance procedures
4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE
Cancels: SP05-36 SP05-42
®
ama
345MAV
Series B
5-99
A93040
NOTE: Read the entire instruction manual before performing any service or maintenance.
Index Page
SAFETY CONSIDERATIONS..................................................1-2
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS........2
GENERAL......................................................................................2
CARE AND MAINTENANCE................................................2-10
Cleaning and/or Replacing Air Filter ...................................2-3
Blower Motor and Wheel Maintenance................................3-4
Cleaning Burners ......................................................................4
Primary Heat Exchangers ................................................4-5
Secondary Heat Exchangers................................................5
Flushing Collector Box and Drainage System.....................5-7
Servicing Hot Surface Ignitor ..................................................7
Electrical Controls and Wiring.................................................7
Troubleshooting.....................................................................7-9
Checking Heat Tape Operation (If Applicable) ......................9
Winterizing..............................................................................10
WIRING DIAGRAM...................................................................11
SERVICE LABEL .......................................................................12
TROUBLESHOOTING GUIDE............................................13-14
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified person­nel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety codes including the National Fuel Gas Code (NFGC) NFPA 54-1996/ANSI Z223.1-1996 and the Installation Standards, Warm Air Heating and Air Conditioning Systems (NFPA 90B) ANSI/NFPA 90B. In Canada, refer to the CAN/CGA-B149.1- and .2-M95 National Standard of Canada, Natural Gas and Propane Installation Codes (NSCNGPIC). Wear safety glasses and work gloves. Have a fire extinguisher available during start-up and adjustment procedures and service calls.
CANADIAN GAS ASSOCIATION
APPROVED
R
As an ENERGY STAR® Partner, BRYANT has deter­mined that this product meets the ENERGY STAR® guide­lines for energy efficiency.
REGISTERED QUALITY SYSTEM
Fig. 1—Multipoise Furnace in Upflow Orientation
Recognize safety information. This is the safety-alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU­TION. These words are used with the safety-alert symbol. DAN­GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING: The ability to properly perform mainte­nance on this equipment requires certain expertise, me­chanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recom­mended in the User’s Manual. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN POSSIBLE DAMAGE TO THIS EQUIPMENT, SERIOUS PER­SONAL INJURY, OR DEATH.
A98187
.
—1—
WARNING: Never store anything on, near, or in contact with the furnace, such as:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds, plastic or plastic containers, gasoline, kero­sene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids.
3. Paint thinners and other painting compounds, paper bags, or other paper products. Failure to follow this warning can cause corrosion of the heat exchanger, fire, personal injury, or death.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
CAUTION: Electrostatic discharge can affect electronic
components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electro­static potential.
1. Disconnect all power to the furnace. DO NOT TOUCH
THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.
3. After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch un­grounded objects, etc.).
4. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touch­ing control or wires.
5. Use this procedure for installed and uninstalled (un­grounded) furnaces.
6. Before removing a new control from its container, dis­charge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
GENERAL
These instructions are written as if the furnace is installed in an upflow application. An upflow furnace application is where the blower is located below the combustion and controls section of the furnace, and conditioned air is discharged upward. Therefore, since this furnace can be installed in any of the 4 positions shown in Fig. 2, you must revise your orientation to component location accordingly.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible equip­ment failure, it is essential that maintenance be performed annually on this equipment. Consult your local dealer for maintenance and maintenance contract availability.
AIRFLOW
UPFLOW
AIRFLOW
HORIZONTAL
LEFT
DOWNFLOW
AIRFLOW
HORIZONTAL
RIGHT
AIRFLOW
A93041
Fig. 2—Multipoise Orientations
WARNING: Turn off the gas and electrical supplies to
the unit before performing any maintenance or service. Follow the operating instructions on the label attached to the furnace. Failure to follow this warning could result in personal injury or death.
The minimum maintenance that should be performed on this equipment is as follows:
1. Check and clean or replace air filter each month as required.
2. Check blower motor and wheel for cleanliness annually.
3. Check electrical connections for tightness and controls for proper operation each heating season. Service as necessary.
4. Check for proper condensate drainage. Clean as necessary.
5. Check for blockages in combustion-air and vent pipes annually.
6. Check burners for cleanliness annually.
CAUTION: Personal injury could result from sharp metal edges, etc. Use care when removing parts.
I. CLEANING AND/OR REPLACING AIR FILTER
The air filter arrangement may vary depending on the application or orientation.
CAUTION: Never operate unit without a filter or with the blower access panel removed. Failure to follow this warning could result in a fire or personal injury.
To clean or replace the filters, proceed as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access panel.
3. Release filter retainer wire. (See Fig. 3 and 4.)
4. Slide filter out of furnace.
5. Furnaces are equipped with permanent, washable filter(s). Clean filter by spraying cold tap water through filter in opposite direction of airflow.
6. Rinse filter and let dry. Oiling or coating of filter is not recommended.
—2—
WASHABLE FILTER
WASHABLE
FILTER
FILTER RETAINER
FILTER SUPPORT
FILTER RETAINER
A93046
Fig. 3—Bottom Filter Arrangement
7. Place filter in furnace.
8. Replace blower access panel and main furnace door.
9. Turn on electrical supply to furnace.
NOTE: If the filter has cross-mesh binding, the binding must face the blower. If the filter has an air direction arrow, the arrow must point toward the blower.
II. BLOWER MOTOR AND WHEEL MAINTENANCE
To ensure long life, economy, and high efficiency, clean accumu­lated dirt and grease from blower wheel and motor annually.
The inducer and blower motors are pre-lubricated and require no additional lubrication. These motors can be identified by the absence of oil ports on each end of the motor.
The following items should be performed by a qualified service technician.
Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access panel.
3. Disconnect wires. All factory wires can be left connected, but field thermostat
connections may need to be disconnected depending on their length and routing.
4. Position control box, transformer, and door switch assembly to right side of furnace casing.
5. If condensate trap is located in left- or right-hand side of furnace casing, proceed to item 6, otherwise remove trap and tubing as described below.
a. Disconnect field drain connection from condensate trap. b. Disconnect drain and relief port tubes from condensate
trap.
c. Remove condensate trap from blower shelf.
6. Remove screws securing blower assembly to blower shelf and slide blower assembly out of furnace.
7. Clean blower wheel and motor by using a vacuum with soft brush attachment. Be careful not to disturb balance weights (clips) on blower wheel vanes. Do not bend wheel or blades as balance will be affected.
8. If greasy residue is present on blower wheel, remove wheel from the blower housing and wash it with an appropriate degreaser. To remove wheel:
A93045
Fig. 4—Filter Installed for Side Inlet
a. Mark blower wheel location on shaft before disassembly
to ensure proper reassembly.
b. Loosen setscrew holding blower wheel on motor shaft.
NOTE: Mark blower mounting arms and blower housing so each arm is positioned at the same hole location during reassembly.
c. Mark blower wheel orientation and cutoff plate location
to ensure proper reassembly.
d. Remove screws securing cutoff plate and remove cutoff
plate from housing.
e. Remove bolts holding motor mounts to blower housing
and slide motor and mounts out of housing. Disconnect capacitor and ground wire attached to blower housing
before removing motor. f. Remove blower wheel from housing. g. Clean wheel per instructions on degreaser cleaner.
9. Reassemble motor and blower wheel by reversing items 8b through 8f. Ensure wheel is positioned for proper rotation. Be sure to reattach ground wire.
10. Reinstall blower assembly in furnace.
11. Reinstall condensate trap and tubing if previously removed. a. Reinstall condensate trap in hole in blower shelf. b. Connect condensate trap drain tubes. See Fig. 8 or tubing
diagram on main furnace door for proper tube location. (1.) Connect 1 tube (blue or blue and white striped)
from collector box.
(2.) Connect 1 tube (violet or unmarked) from inducer
housing.
(3.) Connect 1 tube (relief port, green or pink) from
collector box.
c. Connect field drain to condensate trap.
NOTE: Ensure tubes are not kinked or pinched, as this will affect operation.
12. Reinstall control box, transformer, and door switch assem­bly on blower shelf.
13. Reconnect wires. Refer to furnace wiring diagram, and connect thermostat
leads if previously disconnected. (See Fig. 16.)
NOTE: Refer to Table 1 for motor speed lead relocation if leads were not identified before disconnection.
—3—
TABLE 1—SPEED SELECTOR
COLOR SPEED
Black High Cool
Yellow (When Present) Medium High Spare
Blue Medium Low Heat
Red Low Spare
White Common Com
FACTORY
ATTACHED TO
CAUTION: Heating speed selection MUST be adjusted
to provide proper temperature rise as specified on the rating plate. Failure to adjust the heating speed may shorten heat exchanger life.
14. Turn on electrical supply. Manually close blower access panel door switch. Use a piece of tape to hold switch closed. Check for proper rotation and speed changes between heating and cooling by jumpering R to G and R to Y on control center thermostat terminals. (See Fig. 12.)
WARNING: Blower access panel door switch opens 115-v power to control center. No component operation can occur. Caution must be taken when manually closing this switch for service purposes. Failure to follow this warning could result in electrical shock, personal injury, or death.
15. If furnace is operating properly, release blower access panel door switch, replace blower access panel, and replace main furnace door.
III. CLEANING BURNERS
The following items should be performed by a qualified service technician. If the burners develop an accumulation of light dirt or dust, they may be cleaned by using the following procedure:
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Remove burner box cover.
4. Using backup wrench, disconnect gas supply pipe from gas valve.
5. Remove wires from gas valve. Note location for reassem­bly.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
6. Remove burner box pressure tube from gas valve regulator fitting.
7. Remove screws that secure manifold to burner box. (See Fig. 5.)
8. Remove manifold, orifices, and gas valve as 1 assembly.
9. Remove screws attaching burner assembly in burner box.
10. Remove burner assembly from burner box.
NOTE: All burners are attached to burner bracket and can be removed as 1 assembly.
11. Clean burners with soft brush and vacuum.
12. Reinstall manifold, orifice, and gas valve assembly in burner box. Ensure manifold seal grommet is installed properly and burners fit over orifices.
MANIFOLD MOUNTING SCREW
MANIFOLD
GAS VALVE REGULATOR FITTING
GAS VALVE
A93295
Fig. 5—Burner Box Assembly
13. Reconnect wires to gas valve. Refer to furnace wiring diagram for proper wire location.
14. Reinstall burner box pressure tube to gas valve regulator fitting.
15. Reinstall gas supply pipe to gas valve using backup wrench on gas valve to prevent rotation and improper orientation.
NOTE: Use propane gas resistant pipe dope to prevent gas leaks. DO NOT use Teflon tape.
WARNING: Gas valve switch or knob MUST be facing forward or tilted upward. Failure to follow this warning could result in property damage, personal injury, or death.
16. Replace burner box cover.
17. Turn on gas and electrical supplies to furnace.
18. Check for gas leaks.
WARNING: Never use matches, candles, flame, or other sources of ignition to check for gas leakage. Use a soap-and-water solution. Failure to follow this warning could result in a fire, personal injury, or death.
19. Replace main furnace door.
IV. CLEANING HEAT EXCHANGERS
The following items should be performed by a qualified service technician.
A. Primary Heat Exchangers
If the heat exchangers get an accumulation of light dirt or dust on the inside, they may be cleaned by the following procedure:
NOTE: If the heat exchangers get a heavy accumulation of soot and carbon, both the primary and secondary heat exchangers should be replaced rather than trying to clean them thoroughly due to their intricate design. A build-up of soot and carbon indicates that a problem exists which needs to be corrected, such as improper adjustment of manifold pressure, insufficient or poor quality combustion air, improper vent termination, incorrect size or damaged manifold orifice(s), improper gas, or a restricted heat exchanger (primary or secondary). Action must be taken to correct the problem.
—4—
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Disconnect wires or connectors to rollout switch, gas valve, ignitor, and flame sensor.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
4. Disconnect combustion-air intake pipe from intake housing.
5. Remove the pressure switch tube from intake housing.
6. Remove screws attaching intake housing to burner box, and rotate intake housing away from burner box for removal.
7. Using backup wrench, disconnect gas supply pipe from gas valve.
8. Disconnect pressure tubing from gas valve.
9. Remove 2 screws attaching top filler panel and rotate upwards to gain access to screws attaching burner box to cell panel.
10. Remove screws attaching burner box to cell panel. (See Fig.
5.)
NOTE: Burner box cover, manifold, gas valve, and burner assembly should be removed as 1 assembly.
11. Clean heat exchanger openings with a vacuum and a soft brush. (See Fig. 6.)
NOTE: After cleaning, inspect the heat exchangers to ensure they are free of all foreign objects that may restrict flow of combustion products.
12. Reverse items 4 through 10 for reassembly.
PRIMARY HX INLET OPENINGS
NOTE: Inspect combustion-air intake housing. If foamed gasket was removed, check for any damage. If gasket is damaged in any way, it must be repaired. To repair, remove damaged gasket section, apply sealant releasing agent such as PAM cooking spray or equivalent (must not contain corn or canola oil, aromatic or halogenated hydrocarbons or inadequate seal may occur) to burner box and apply a small bead of G.E. RTV 162, G.E. RTV 6702, or Dow-Corning RTV 738 sealant to edge of combustion-air intake housing. (See Fig. 7.)
RTV
PAM
A93087
Fig. 7—Combustion-Air Intake Housing Gasket
Repair
13. Refer to furnace wiring diagram and connect wires to rollout switch, gas valve, ignitor, and flame sensor.
14. Reconnect pressure switch tubes to gas valve and intake housing. Refer to tube routing label on main furnace door for proper tube location. Be sure tubes are not kinked. (See Fig. 8.)
15. Turn on gas and electrical supplies to furnace.
16. Check furnace operation through 2 complete heat operating cycles. Look through sight glass in burner enclosure to check burners. Burner flames should be clear blue, almost transparent. (See Fig. 9.)
17. Check for gas leaks.
A93080
Fig. 6—Cleaning Inlet Openings of Primary Heat
Exchangers
WARNING: The ground wire from the gas valve MUST
be attached to the burner box attachment screw. Failure to attach this ground wire to an adequate casing ground will cause the furnace control to lock out.
NOTE: Be sure burner box gasket is installed between burner box and cell panel. If gasket is damaged, replace it.
WARNING: Never use matches, candles, flame, or other sources of ignition to check for gas leakage. Use a soap-and-water solution. Failure to follow this warning could result in a fire, personal injury, or death.
18. Replace main furnace door.
B. Secondary Heat Exchangers NOTE: The condensing side (inside) of the secondary heat
exchangers CANNOT be serviced or inspected. A small number of bottom outlet openings can be inspected by removing the inducer assembly. See Flushing Collector Box and Drainage System section for details on removing inducer assembly.
V. FLUSHING COLLECTOR BOX AND DRAINAGE SYSTEM
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Disconnect inducer motor and pressure switch wires or connectors.
4. Disconnect pressure switch tubes.
5. Disconnect vent pipe from inducer housing outlet by loosening coupling clamp on inducer outlet.
6. Disconnect drain tube from inducer housing. (See Fig. 8.)
7. Remove inducer housing assembly by removing 4 bolts attaching assembly to cell panel.
—5—
Furnace is shipped from factory in upflow configuration. Pressure tube and drain tube routing MUST match the diagrams below.
Condensate Trap; Factory Installed
in Blower Shelf
(Blower access panel removed)
COLLECTO R BO X TU BE
(PINK)
COLLECTOR BOX TUBE
INDUCER HOUSING (MOLDE D) DRAIN TUBE
(BEHIND COLLECTOR BO X DRAIN T UBE)
FIELD-INSTALLED FACTORY-SUPP LIED
BURNER ENCLOSURE PRES SURE
REFERENCE TUBE ASSEMBLY
(GREEN)
COLLECTOR BOX DRAIN TUBE
(BLUE)
FIELD-INSTALLED
FACTORY-SUPP LIED DRAIN TUBE
COUPLING (LEFT DRAIN OPTION)
DRAIN TUBE
Condensate Trap on
LEFT Side
CAP
COLLECTO R BO X
TUBE (GREEN)
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRIPE D)
COLL ECTOR BOX EXTENSI ON TUBE
CONDENSATE TRAP
INDUCER HOUSING DRAIN TUBE (VIOLET)
T ube location when used on
HORIZONTAL - LEFT ap plication
AUXILIARY "J" BOX RE LOCATED HERE
BURNER ENCLOSURE
PRESSURE REFE RENCE
TUBE ASSEMBLY
COLLECTOR BOX EXTENSION DRAIN TUBE
PLUG
CAP
COLLECTOR BOX
EXTENSIO N TUBE
CONDENSATE TRAP
NOTE:
1. All tubing must be connected securely and routed to avoid kinks and traps.
2. Pressure tubing must always slope away from pressure switch to collector box connection as shown.
3. HORIZONTAL-LEFT installations require the collector box pressure tube to be relocated between the inducer housing and the blow er shelf to prevent a trap.Refer to the Installation Instructions for further details.
T ube location when used in UPFLOW application
BURNER ENCLOSURE
PRESSURE REFERENCE
TUBE ASSEMBLY
CAP
PLUG
COLLECTOR BOX DRAIN
TUBE
(BLUE & WHITE STRIPED )
CONDENSATE TRA P
FIELD-INSTALLED
FACTORY-SU PPL IE D DRAIN TUBE COUPLING (RIGHT DRAIN OPTION)
FIELD-INSTALLED
FACTORY-SUPPLIED 1/2-IN. CPVC STREET ELBOWS (2)
FOR LEFT DRAIN OPTION
COLLECTOR BOX TUBE
(PINK)
COLLECTOR BO X TUBE (GR EEN )
COLLECTOR BOX DRAIN TUB E
(BLUE)
CONDENSATE TRAP
T ube location when used in DOWNF LO W application
COLL ECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX DRAIN TUBE
DRAIN TUBE
COUPLING
PLUGGED END
PLUG
COLLECTOR BOX EXTENSIO N TUBE
COLL ECTOR BOX
TUBE ( PINK)
(BLUE & WHITE STRIPED )
COLLECTOR BOX
TUBE (GREEN)
INDUCER HOUSING
DRAIN TUBE
(VIOLET)
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX TUBE (PINK)
RELOCATE TUBE BET W EEN BLOWER
SHELF AND INDUCER HOU SING FOR
040,060, AN D 080 HEA TIN G IN P UT
FURNACES
COLLECTO R BO X D R AIN
TUBE
(BLUE & WHITE STRIPED)
INDUCER HOUSING DRAIN
TUBE (VIOLET)
DRAIN TUBE COUPLING
DRAIN TUBES ROUT ED IN
FRONT OF GAS VALVE
COLLECTOR BOX DRAIN TUB E
(BLUE)
PLUG
CAP
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX DRAIN TUBE
(BLUE AND WHITE STRIPED)
T ube location when used on
HORIZONTAL - RIGHT appl i cation
Fig. 8—Furnace Pressure and Drain Tubing Diagram
TUBE ROUTING
Condensate Trap on LEFT
Side Optional
BURNER ENCLOSURE
PRES SURE REFERENCE
TUBE ASSEMBLY
CAP
PLUG
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRIPED )
INDUCER HOUSING DRAIN TUBE
Condensate Trap on
PLUG
CAP
COLLECTOR BOX DRAIN TUB E
(BLUE)
COLL ECTOR BOX TUBE
(PINK)
COLLECTO R BO X TU BE
(GREEN)
COLLECTO R BO X EXT ENSION TUBE
BURNER ENCLOSURE PRES SURE
REFERENCE TUBE ASSEMBLY
CONDENSATE TRAP
COLLECTO R BO X
GAS VALVE
INDUCER HOUSING DRAIN TUBE (VIOLET)
EXTENSION DRAIN TUBE
COLLECTOR BOX EXTENSION TUBE
COLLECTOR BOX TUBE (PINK)
BURNER ENCLOSURE
PRESSURE REF ERENCE
TUBE ASSEMBL Y
COLLECTO R BO X EXTENSIO N TUBE
CONDENSATE TRAP
324999-201 REV. A
(LIT. BOTTOM)
(VIOLET)
RIGHT Side
A99102
BURNER FLAME
MANIFOLD
Fig. 9—Burner Flame
BURNER
A89020
—6—
8. Flush inside of collector box with water until discharge from condensate trap is clean and runs freely.
NOTE: Ensure the drain tube disconnected from the inducer housing is higher than the collector box opening or water will flow out tube.
9. Inspect inside area of collector box for any pieces of foreign materials and remove if present.
CAUTION: DO NOT use wire brush or other sharp object to inspect or dislodge materials in secondary heat exchangers as failure of the secondary heat exchanger will occur. Flush with water only.
10. Reassemble inducer assembly by reversing items 5-7.
Tighten the vent coupling clamp screw(s) to 15 in.-lb. torque.
NOTE: If seal between the inducer housing and the collector box is damaged in any way, it must be repaired. To repair, apply sealant releasing agent such as PAM cooking spray or equivalent (must not contain corn or canola oil, aromatic or halogenated
PAM
RTV
A93081
Fig. 10—Gasket on Collector Box
hydrocarbons or inadequate seal may occur) to inducer housing. (See Fig. 10.) Apply a small bead of G.E. RTV 162, G.E. RTV 6702, or Dow-Corning RTV 738 sealant to groove in collector box.
11. Refer to furnace wiring diagram and connect wires to inducer motor and pressure switch or connectors.
12. Reconnect pressure tubes to pressure switch. See diagram on main furnace door for proper location of tubes. Be sure tubes are not kinked. (See Fig. 8.)
13. Turn on gas and electrical supplies to furnace.
14. Check furnace operation through 2 complete heat operating cycles. Check area below inducer housing, vent pipe, and condensate trap to ensure no condensate leaks occur. If leaks are found, correct the problem.
15. Check for gas leaks.
WARNING: Never use matches, candles, flame, or other sources of ignition to check for gas leakage. Use a soap-and-water solution. Failure to follow this warning could result in a fire, personal injury, or death.
16. Replace main furnace door.
VI. SERVICING HOT SURFACE IGNITOR
The ignitor does NOT require annual inspection. Check ignitor resistance before removal.
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Disconnect ignitor wire connection.
4. Check ignitor resistance. a. Using an ohm meter, check resistance across both ignitor
leads in connector. b. Cold reading should be between 45 ohms and 90 ohms. c. If ohm reading is higher than 110 ohms, ignitor is
cracked and must be replaced.
5. Remove ignitor assembly.
a. Do not remove ignitor from bracket while assembly is in
furnace. Using a 1/4 in. nutdriver, remove screw secur­ing bracket and ignitor assembly to bottom of burner box. The screw in the bracket is always located toward outside of burner box. The screw may be hidden by inlet box or inlet pipe, but can be removed without removing either. After removing screw, slide ignitor and bracket toward outside of burner box and pull straight out.
CAUTION: The ignitor is fragile. DO NOT allow it to hit the side of the burner box opening while removing or replacing it.
b. Inspect ignitor for a white area indicating a crack may be
present. If found, replace ignitor.
NOTE: A small crack cannot be seen on a new ignitor. After a period of operation, a white area will be visible around the crack.
c. If replacement is required, replace ignitor on ignitor
bracket external to furnace to avoid damage as the silicon portion is very brittle and will easily crack or shatter.
d. To remove ignitor from ignitor bracket, remove screw
holding ignitor ceramic block to bracket and pull ce­ramic block out of bracket.
6. To replace ignitor/ignitor assembly, reverse items 5a through 5d.
7. Reconnect ignitor wire connection.
8. Turn on gas and electrical supplies to furnace.
9. Verify ignitor operation by initiating control board self-test feature or by cycling thermostat.
10. Replace main furnace door.
VII. ELECTRICAL CONTROLS AND WIRING
CAUTION: There may be more than 1 electrical supply
to the unit. Check accessories and cooling unit for additional electrical supplies.
The electrical ground and polarity for 115-v wiring must be maintained properly. Refer to Fig. 11 for field wiring information and to Fig. 15 for unit wiring information.
NOTE: If the polarity is not correct, the STATUS LED on the control center will flash rapidly and prevent the furnace from operating. The control system also requires an earth ground for proper operation of the control center and flame sensing.
The 24-v circuit contains an automotive-type, 3-amp fuse located on the control center. (See Fig. 12.) Any direct shorts of the 24-v wiring during installation, service, or maintenance will cause this fuse to blow. If fuse replacement is required, use ONLY a fuse of identical size.
With power to the unit disconnected, check all electrical connec­tions for tightness. Tighten all screws on electrical connections. If any smoky or burned connections are found, disassemble the connection, clean all parts, strip wire, and reassemble properly and securely.
Reconnect electrical supply to unit and observe unit through 1 complete operating cycle. Electrical controls are difficult to check without proper instrumentation; if there are any discrepancies in the operating cycle, contact your dealer and request service.
VIII. TROUBLESHOOTING
For an explanation of fault codes, refer to service label located on back of main furnace door or Fig. 16, and the Troubleshooting Guide.
—7—
BLK
WHT
WHT
GND
115-V
FIELD-SUPPLIED
DISCONNECT
THREE-WIRE
BLK
AUXILIARY J-BOX
FIVE
WIRE
HEATING-
ONLY
GND
CONTROL
BOX
FURNACE
NOTE 2
W
R
G
C Y
24-V
TERMINAL
BLOCK
FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-V WIRING
WCR GY
NOTE 1
THERMOSTAT TERMINALS
CONDENSING
FIELD-SUPPLIED DISCONNECT
GND
UNIT
TWO WIRE
NOTES: Connect Y-terminal as shown for proper operation.
1.
2.
Some thermostats require a "C" terminal connection as shown.
3.
If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.
Fig. 11—Field Wiring
208/230- OR 460-V THREE PHASE
208/230-V SINGLE PHASE
A98209
TEST/TWIN
3-AMP FUSE
115-VAC (L1)
POWER SUPPLY
HOT SURFACE
IGNITOR CONNECTOR
SEC-1
COOL
HEAT
24-V THERMOSTAT TERMINALS
HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX)
LED OPERATION &
OM
C
HUM
GRYW
24V
DIAGNOSTIC LIGHT
HARNESS CONNECTOR
24-V TRANSFORMER SEC-2 SPARE-1 BLOWER SPEED
SELECTION TERMINALS SPARE-2
EAC-1 EAC-ELECTRONIC AIR CLEANER
TERMINALS (115-VAC 1.5 AMP MAX) EAC-2
115-VAC (L2) NEUTRAL CONNECTION
INDUCER MOTOR CONNECTOR
Fig. 12—Control Center
A95086
—8—
The control center stores 1 fault code (the last fault to occur) for a period of 48 hrs or until the 115- or 24-v power is interrupted.
NOTE: Removing blower access panel will open blower access panel door switch and terminate 115-v power to control center, and fault code will be erased. Look into blower access panel sight glass for current LED status.
The unit’s component test is a useful troubleshooting tool since it displays the current status (fault code) of the furnace and func­tionally operates all furnace components except the gas valve. The component test and methods to initiate it are described below.
A. Component Test Sequence NOTE: All components are functionally operated except the gas
valve. When component test is initiated, the following sequence of events
occurs:
1. LED flashes a fault code 4 times.
2. Inducer motor starts and continues to run for remainder of component test.
3. Hot surface ignitor is energized for 15 sec, then de­energized.
4. Main blower operates at cooling speed for 10 sec, then turns off.
5. Main blower operates at heating speed for 10 sec, then turns off.
6. Inducer motor stops.
Component test can be initiated by one of the following proce­dures.
B. Initiating ComponentTest and Retrieving Fault Code By Removing Main Limit Switch Wire
NOTE: NO thermostat signal may be present at control center
and all blower time delay off periods must be completed.
1. Leave 115-v power to furnace turned on.
2. Remove main furnace door.
3. Look into blower access panel sight glass for current LED status.
NOTE: Leave blower access panel installed to maintain power to control center to view current LED status.
4. BRIEFLY remove either wire from the main limit switch until the LED goes out, then reconnect it.
CAUTION: Make sure limit switch wire does not con­tact any metallic component such as the gas valve. If wire is shorted, 3-amp fuse on control center will blow.
3. Manually close blower access panel door switch. Use a piece of tape to hold switch closed.
WARNING: Blower access panel door switch opens 115-v power to control center. No component operation can occur. Caution must be taken when manually closing this switch for service purposes. Failure to follow this warning could result in electrical shock, personal injury, or death.
4. BRIEFLY short (jumper) TEST, 1/4-in. quick-connect terminal on control center (adjacent to the LED diagnostic light) and the C
OM terminal on thermostat connection block.
(See Fig. 12.)
NOTE: If TEST to C
OM terminals are jumpered longer than 2 sec,
LED will flash rapidly, and retrieval request will be ignored.
5. When above items have been completed, the component test sequence will occur as described in the Component Test Sequence section above.
NOTE: Be sure to record the fault code which is flashed 4 times at start of component test for further troubleshooting.
6. After component test is completed and furnace is operating properly, release blower access panel door switch, replace blower access panel, and replace main furnace door.
IX. CHECKING HEAT TAPE OPERATION (IF APPLICABLE)
In applications where the ambient temperature around the furnace is 32°F or lower, freeze protection measures are required. If this application is where heat tape has been applied, check to ensure it will operate when low temperatures are present.
32°F MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED
NOTE: If wire to main limit is disconnected longer than 4 sec, the control senses limit circuit is open. Main blower will start and retrieval request will be ignored.
5. When above items have been completed, the component test sequence will occur as described in the Component Test Sequence section above.
NOTE: Be sure to record the fault code which is flashed 4 times at start of component test for further troubleshooting.
6. After component test is completed and LED is ON continu­ously indicating the furnace is ready to operate when a signal from the thermostat is received, replace main furnace door.
C. Initiating ComponentTest and Retrieving Fault Code By Jumpering Control TEST Terminal
1. Remove main furnace door.
2. Remove blower access panel.
A93058
CAUTION: If this furnace is installed in an uncondi­tioned space where the ambient temperatures may be 32°F or lower, freeze protection measures must be taken.
NOTE: Heat tape, when used, should be wrapped around the condensate drain trap and drain line. There is no need to use heat tape within the furnace casing. Most heat tapes are temperature activated, and it is not practical to verify the actual heating of the tape. Check the following:
1. Check for signs of physical damage to heat tape such as nicks, cuts, abrasions, gnawing by animals, etc.
—9—
A99119
Fig. 13—Inducer Housing Drain Tube
A99118
2. Check for discolored heat tape insulation. If any damage or discolored insulation is evident, replace heat tape.
3. Check that heat tape power supply circuit is on.
X. WINTERIZING
CAUTION: Freezing condensate left in the furnace will
damage the equipment.
If the furnace will be off for an extended period of time in a structure where the temperature will drop to 32°F or below, winterize as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door.
Fig. 14—Funnel in Drain and Antifreeze Running
Through Trap
3. Disconnect drain tube from inducer housing. (See Fig. 13.)
4. Insert funnel in drain tube and pour antifreeze, propylene glycol (RV, swimming pool antifreeze, or equivalent) into furnace until it is visible at point where condensate enters open drain. (See Fig. 14.)
5. Reconnect drain tube to inducer housing.
6. Replace main furnace door.
CAUTION: Do not use ethylene glycol (Prestone II antifreeze/coolant or equivalent automotive type). Failure of plastic components will occur.
—10—
SW2
PCB
SEE NOTE #10
(NO T O N ALL MODE LS)
BLOWER OFF DELAY
SELECTION CHART
90 SEC
BLOWER
OFF
DELAY
TEST/TWIN
SW1
HUM
G R Y W C
LED
ORN
OM
135 SEC
PL1
WHT
BLOWER
SPEED
SELECT
L2
PR2
WHT
WHT GRN
BLK
SEC-1
FU1
BRN
321 6
9
24 VAC-3A
COOL
HEAT
EAC-1
EAC-2
M
5 87
FUSE
CAP -2
4
SEC-2
SPARE-1
SPARE-2
C
OM
AUX
OL
1.5 AMP
BRN
IDM
180 SEC 225 SEC
GVR
HSIR IDR BLWR
PL2
VAC
120
L1
BLK
PR1
BLK
BLK
12
HSI
1 2
BLK
1
WHT
PL5
PL3
23
HI/LO
RELAY
1 2 3
WHT
GRN
PL4
LEGEND
BLWR BLOWER MOTOR RELAY, SPST-(N.O.) BLWM BLOWER MOTOR CAP CAPA CITOR CPU MICROPROCESSOR AND CIRCUITRY EAC-1 ELECTRONIC AIR CLEAN ER CONNEC TION (115 VAC 1.5 AMP MAX.) EAC-2 ELECTRONIC AIR CLEANER CO NNECTION (COMMO N) FRS FLAME ROLLOUT SW. -MANUAL RESET, SPST-(N.C.) FSE FLAME PROVING ELECTRODE FU1 FUSE, 3 AMP, AUT OM OTIVE BLADE TYPE, FACTORY INSTALLED FU2 FUSE OR CIRCUIT BREAKER CURRENT INTERRUPT DEVICE
(FIELD INSTALLED & SUPPLIED ) GND EQUIPMENT GROUND GV GAS VALVE-REDUNDANT OPERATORS GVR GAS VALVE RELAY, DPST-(N .O.) HI/LO BLOWER MOTO R SPEED CHANGE RELAY, SPDT HSI HOT SURFACE IGNITOR (115 VAC) HSIR HOT SURFACE IGNIT O R RELAY, SPST-(N.O.) HUM 24VAC HUMIDIFIER CONNECTION (.5 AMP. MAX.) IDM INDUCED DRAFT MOTOR IDR INDUCED DRAFT RELAY, SPST-(N.O.) ILK BLOWER ACCESS PANEL INTERLOCK SWITCH, SPST-(N.O.) JB JUNCTION BOX LED LIGHT-EMITTING DIODE F OR STATUS CODES LGPS LOW GAS PRESSURE SWITCH, SPST-(N.O.) LS LIMIT SWITCH, AUTO RESET, SPST(N.C.) OL AUTO-RESET INT ERNAL MOTO R OVERLOAD TEMP. SW. PCB PRINTED CIRCUIT BOARD
RED
WHT
BLK (HI)
YEL (MED HI)
NOTE #8
BLU (MED LO)
RED (LO)
WHT (COM)
(WHEN USED)
PRS
RED
LS
BLU
RED
OL
WHT
BLK
ILK
PL1 9-CIRCUIT CONNECTOR PL2 2-CIRCUIT PCB CONNECTOR PL3 3-CIRCUIT IDM CONNECTOR PL4 3-CIRCUIT IDM EXTENSION CO N NECTOR PL5 2-CIRCUIT HSI/PCB CONNECT OR PRS PRESSURE SWITCH, SPST-(N.O.) SW1 & 2 BLOWER OFF DELAY TEST/TWIN COMPONENT TEST & TWIN TERM INAL TRAN TRANSFORMER-115VAC/24VAC
LGPS
NOTE #6
BLU
FRS
FSE
RED
GRN
BLK
WHT
TRAN
WHT (COM)
BRN
START
BLWM
JB
GRN
GND
JUNCTION UNMARKED TERMINAL PCB TERMINAL FACTORY WIRING (115VAC) FACTORY WIRING (24VAC) FIELD WIRING (115VAC) FIELD WIRING (24VAC) CONDUCTOR ON PCB FIELD WIRING TERMINAL FIELD EARTH GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE
CAP -1
BRN
FUSED DISCONNECT
SWITCH (WHEN REQ'D)
WHT BLK GRN
1-M
GRN
NOTE #4
FU2
YEL
3-P
GV
2-C
NOTE #5
NEUTRAL
TO 115VAC FIELD DIS C ON NECT
NOTE #4
NOTE #12
L1
L1
ILK
L1
TEST/TWIN
HUM
R W
Y
G
C
OM
NEUTRAL
BLWR
HSIR
FU1
GND
EQUIPMENT GROUND
SPARE-2
HEAT
SPARE-1
HI/LO
EAC-1
EAC-2
IDR
PR1
TRAN
NOTE #7
SEC-1
GVR-2
HSIR
BLWR
IDR
CPU
COOL
PL2
115VAC
24VAC
HI/LO
NOTE #8
COM
1
SEC-2
GVR
GVR-1
NOTES:
1. IF ANY OF THE ORIGINAL EQUIPMENT WIRE IS REPLACED USE WIRE RATED FOR 105˚C.
2. INDUCER (IDM) AND BLOWER (BLWM) MOTORS CONTAIN INTERNAL AUTO-RESET THERMAL OVERLOAD SWITCHES (OL).
3. BLOWE R MOTOR SPEED SELECTIONS ARE FOR AVER AGE CO N D ITIO N S, SEE INSTAL LATION INSTRUCTIONS FOR DETAILS ON OPTIMUM SPEED SELECTION.
4. USE ONLY COPPER WIRE BETWEEN THE DISCONNECT SW ITCH AND THE FURNACE JUNCTION BOX (JB).
5. THIS WIRE MUST BE CONNECTED TO FURNACE SHEETMETAL FOR CONTRO L TO PRO V E FLAME.
6. FACTORY CONNECTED WHEN LGPS NOT USED.
7. REPLACE ONLY WITH A 3 AM P F U SE.
8. YELLOW LEAD NOT ON ALL MOTORS.
9. BLOWER-ON DELAY, GAS HEATING 60 SECONDS, COOLING OR HEAT PUMP 2 SECONDS.
10. BLOWER-OFF D ELAY, GAS H E A TIN G 90, 135, 180 OR 225 SECO N D S, COOLING OR HEAT PUMP 90 SECONDS. (135 SECONDS ONLY ON SOME M ODELS)
11. IGNITION-LOCK O UT WILL OCCUR AFTER FOUR CO NSECUTIVE UNSUCCE SSFUL TRIALS-FOR-IGNITION. CONTROL WILL AUTO-RESET AFTER THREE HOURS .
12. SOME MODELS MAY HAVE SPADE QU ICK CONNECT TERMINALS.
SCHEMA TIC DIAGRAM
(NATURAL GAS & PROPAN E)
LO
MED LO
MED HI
HI
OL
COM
1
HSI
2
PL52
1
PR2
1
3
3
PL3
2
2
FRS
7
1
LGPS
4
PL1
PRS
3
3-P
2
1-M
8
5 6
9
BRN
PL4
NOTE #6
322854-101 R EV . D (LIT)
START
M
CAP-1
BLWM
IDM
OL
AUX
CAP -2
(WHEN USED)
GV
2-C
NOTE #5
L2
BRN
LS
FSE
Fig. 15—Wiring Diagram
—11—
A99106
SERVICE
If status code recall is needed, do not remove pow er or b lower do or. Brie fly remove and then reconnect one main limit wire to display stored status code.
LED CODE
CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and CONTINUOUS ON - Con trol has 24V power.
RAPID FL ASHING - L ine voltage (115V ) polarity reversed. If twinn ed, refer to
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMB ER OF SHORT FLASHES A ND THE S ECO N D D IGIT BY THE NUMB ER O F LO NG F LASHES .
11 NO PREVIOUS CODE - Stor ed status codes are e ra sed when power
(115V or 24V) to control is interrupted or 48 hours after each fault is cleared.
12 BLOWER ON AFTER POWER U P (115V or 24V) - Blowe r runs for 90 s ec onds,
if unit is powered up dur ing a call for heat ( R -W closed).
13 LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT - Co ntrol will auto reset after
three hours unless flame roll-out switch o r f u se link is opened , r ef er to #33.
14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34. 21 GAS HEATING LOCKOUT - Control will NOT auto reset.
Chec k for: - Mis-wired gas valve -Defec t ive control (valve rel ay )
22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is
de-energized. Inducer will run until fault is cleared. Check for: - Leaky gas valve -Stuck-open gas valve
23 PRESSURE SWITCH (ES) DID NOT OPEN Check for:
- Obstructed pressure tubing. - Defective pressure switch (stuck closed).
24 SECONDARY VOLTAGE FUSE IS OPEN
Check for:- Short circuit in secondary voltage (24V) w ir ing.
31 PRESSURE, DRAFT SAFEGUARD, AUXILIARY-LIMIT (when used), OR BLOCKED
VENT SHUTOFF (when used) SWITCH DID NOT CLOSEOR REOPENED - If open
longer than five minutes, inducer shuts off for 15 minutes befo re retry. Check for: - Inadequate Combustion air supply.
- Proper v ent sizing and condensate pitch or sag
- Low inducer voltag e.
- Vent restriction or high winds.
- Disconnect ed or obstructed pre ssure tubing
- Defec t ive inducer motor o r st ar t capacitor.
- Defec t ive pressure switch o r connections. If it op ens after trial for ignition period , blower will come on for 90 second recycl e delay.
33 LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN - If open longer than three
minutes, code changes to #13. Flame roll-out switch requires manual reset. Check for: - Defective blower motor or capacitor.
- Dirty filter or restricted duct sy st em.
- Loose blower wheel.
- Defective switch or connec tions.
- Inadequate Combustion air supply (Flame Roll-out Switch or fuse link).
- Open Fla me Roll-out switch,or fuse link. Manu al r eset or replace.
34 IGNITION PROVING FAILUR E - Control will try three more times before a
lockout #14 oc curs. If flame signal lost after trial for ignition period, blower will come on for 90 second recycle delay. Check for:
- Oxide buildup on flame sensor (clean wit h f ine steel wool).
- Prope r fla me sense microam ps (.5 microamps D.C . min., 4.0 - 6.0 nomina l) .
- Gas valve defective or gas va lve turned off.
- Defective Hot Surface Ignitor
- Manual valve shut-off.
- Low inlet gas pressure.
- Green wire MUST be connected to furna ce sheet metal.
- Inadequate flame carr yov er or rough ignition.
SEC-2.
twinning k it instr u ct io ns .
COMPONENT TEST
To initia te the component test sequence,shut OFF the room thermo st at or disconnect the "R" thermostat lead. Briefly short the TEST terminal to the "Com 24V" terminal. Status LED will flash code and then tur n ON the inducer motor. The inducer motor will r un for the ent ire componen t test. The hot s u rf ace ignitor, blower motor-heat speed, and blower motor-coo l speed will be turned ON for 10-15 seconds each. Gas Valve and Humidifier will not be turned on.
6
3
9
2
8
5
1
7
4
STATUS
TEST
HUM
STATUS
Com
W
24V
Y
R
320615-102 R EV . J
G
A99107
Fig. 16—Service Label
—12—
NO
Close circuit breaker and
go back to start.
YES
Close door switch and go to start.Is red LED status light on? Is door switch closed?
NO
NO
Is circuit breaker closed?
NO
YES
YES
Is there 115v going to switch?
NO
YES
Is 24 vac present at W, Y, or G
terminals on the control?
Replace control if it does not
respond to 24-vac signal at W, Y,
or G screw terminals.
Check for continuity in wire from circuit
breaker to furnace.
NO
Check room thermostat or
interconnecting cable.
NO
YES
Replace door switch.Replace control center.
Replace transformer.
Does control respond to W, Y,
or G 24-vac thermostat signals?
Run system through a heating or
cooling cycle to check operation.
Status codes are erased after 48
hrs or whenever power (115v
or 24v) is interrupted.
NO
Troubleshooting Guide
YES
Is there 115v at L1 and L2?
NO
START
YES
Is there 24v at SEC-1 and SEC-2?
YES
Check for correct line voltage
polarity. If units are twinned,
check for proper low-voltage
(24v) transformer phasing.
Check for previous fault by
momentarily shorting the TEST
terminal and the C terminal until
the LED goes out. LED will flash
YES
NO
NO
Is red LED status light blinking
ON/OFF slowly with a
combination of short and long
Is red LED status light blinking
rapidly without a pause?
flashes?
—13—
the status code of any previous
fault or the code No. 11 (1 short
and 1 long flash) if no previous
fault. After the control repeats the
code 3 times, the control will go
through a brief component test
sequence. The inducer will start
and run for the entire component
test. The HSI, blower motor heat
speed, and blower motor cool
speed will run for 10-15 sec each.
YES
Determine status code. The
status code is a 2 digit number
with the first digit determined by
the number of short flashes and
the second digit by the number of
long flashes.
YES
Was there a previous fault code
other than No. 11?
Go to section with status code
determined.
A99123
Replace control center.
NO
YES
Unplug ignitor harness from control
center and inititate another
component test sequence. Check
for 115v between pins 1 and 2 on
the control center. Was 115v present
for the 17-sec period?
Check for continuity in the harness
and ignitor. Replace defective
component.
Check connections. If OK, replace
control center.
NO
Reconnect the R thermostat lead
and set thermostat to call for heat.
Connect voltmeter across gas valve
connections. Does gas valve
Check that all gas valves are turned
on. Replace valve.
NO
YES
receive 24v?
YES
Does gas valve open and allow gas
to flow?
NO
rough ignition.
• Low inlet gas pressure.
• Inadequate flame carryover on
Check for:
NO
YES
Do main burners ignite?
Repeat call for heat and check flame
sensor current during trial for ignition
NO
YES
Do main burners stay on?
Allow blower to come on and repeat
Check connections and retry. If
current is near typical value and
control will not stay on, replace
control center.
YES
period. Is the DC microamps
below 0.5?
test to check for intermittent
operation.
Replace electrode.
NO
Clean flame sensor with fine
sandpaper and recheck current.
Current is nominally 4.0 to 6.0 microamps.
Is current near typical value?
Replace control center.
NO
YES
YES
Will main burner ignite and stay on?
Fixed.
NOT CLOSE OR REOPEN - If
open longer than 5 minutes,
inducer shuts off for 15 minutes
31 PRESSURE SWITCH WILL
are erased after 48 hrs or
11 NO PREVIOUS FAULT - Faults
sag.
before retry.
Check for:
• Proper vent sizing or pitch or
whenever power (115v or 24v) is
interrupted. Run system through
a heating or cooling cycle to
check system.
connections. If it opens after
trial for ignition period, blower
will come on for 90 sec
• Vent restrictions or high winds.
• Defective inducer motor.
• Low line voltage (115v).
• Motor start capacitor.
• Low inlet gas pressure.
• Defective pressure switch or
UP (115V OR 24V) - Normal
operation. Blower will run for 90
sec when furnace power is
12 BLOWER ON AFTER POWER
recycle delay.
interrupted during a call for heat,
R-W closed.
13 LIMIT OR FLAME ROLLOUT
• Inadequate combustion air.
SWITCH IS OPEN - If
limit switch is open longer than 3
minutes, code changes to No. 13.
Check for:
• Blower motor failure.
33 LIMIT OR FLAME ROLLOUT
SWITCH LOCKOUT -
Limit switch was open longer
than 3 minutes. Auto-reset will
occur after 3 hrs. Flame rollout
switch requires manual reset.
See No. 33
14 IGNITION LOCKOUT - System
manual reset.
Inadequate combustion air
supply (flame rollout switch
• Motor start capacitor.
• Open flame rollout switch,
failed to ignite gas and prove
flame in 4 attempts. Control will
auto-reset in 3 hrs.
See No. 34
connections.
only).
• Dirty filter.
• Defective limit switch or
Turn off power and wait 5
minutes to retry.
Check for:
21 GAS HEATING LOCKOUT -
• Loose blower wheel.
If flame is not sensed during the
trial for ignition period, the control
will repeat the ignition sequence
3 more times before going into
lockout, No. 14.
If flame signal is lost after trial for
34 IGNITION PROVING FAILURE -
wire.
on control.
• Miswire or short to gas valve
• Stuck closed gas valve relay
SIGNAL - Flame was sensed
while gas valve was
de-energized. Inducer will run
22 ABNORMAL FLAME PROVING
NO
ignition period, blower will come
on for 90-sec recycle delay.
Check for the following items first
before proceding to the next step.
or leak.
until fault is cleared.
Check for:
• Stuck open gas valve solenoid
to furnace sheet metal.
• Gas valve turned off.
• Manual shut-off valve.
• Green wire must be connected
To determine whether the
problem is in the gas valve,
ignitor, or flame sensor, the
• Defective control center.
pressure tubing.
NOT OPEN - Check for:
• Disconnected or obstructed
23 PRESSURE SWITCH WILL
system can be operated in the
component test mode to check
the ignitor. First, remove the
R thermostat connection from the
control center and initiate the
component test sequence. Does
the ignitor glow orange/white hot
by the end of the 17-sec warm-up
period?
including thermostat leads
shorting to ductwork or
furnace cabinet. Disconnect
• Defective pressure switch.
OPEN - Check for:
• Short in low-voltage wiring
24 LOW-VOLTAGE FUSE IS
thermostat leads to isolate
YES
short circuit.
—14—
—15—
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:  • Unit Familiarization • Maintenance  • Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book.  Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog. 
CALL FOR FREE CATALOG 1-800-962-9212
[ ] Packaged Service Training [ ] Classroom Service Training
A94328
© 1999 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231
—16—
Printed in U.S.A. sp0542 Catalog No. 5334-506
Loading...