Installation Instructions
479
Sizes 180 & 240
Series D
ALL WEATHER HEATING and COOLING UNIT
Figure 1—Model 479,
Cancels: 39479D6
brqant
39479D8
9/20/71
I
A70680
Important - Read before Installing
1. Check all local or other applicable codes for infor
mation concerning proximity to property lines, height
above roof, obstructions, etc.
2. Be sure the power supply available (voltage,
frequency and phase) corresponds to that specified on
the unit.
3. Check the electrical service provided by the utility
for the building to be sure that the service capacity is
sufficient to handle the load imposed by this unit.
4. Refer to the regulations of the serving gas supplier
and the local building, heating, plumbing or other
codes in effect in the area in which installation is to
be made.
5. Refer to the dimensionah drawing on page 2 for
electrical, gas, duct and drain connections prior to set
ting the unit in place.
GENERAL
The Bryant Model 479 is an all weather heating and
cooling unit designed for outdoor installation only. It
can be installed at ground level or on a rooftop. The
479 is factory assembled, pre-wired and charged with
the primary refrigerant. Installation consists of the
following:
Locating the Unit
I.
Installing Vent Caps
II.
III. Duct Connections
IV.
Gas Connections
V. Electrical Connections
VI. Chilled Water System
VII. Start-Up and Adjustments
VIII. Furnace Operation
IX, Cooling Operation
X.
Maintenance
Read the entire Installation Instructions before star
ting installation.
I. LOCATE AND MOUNT THE UNIT
The condenser air discharges upward; therefore,
avoid locations where obstructions will deflect the hot
condenser discharge air back into the condenser inlet
air supply. In all cases, the condenser should be at
least 2 feet from any wall or obstruction and outside
of the plumb line from any overhang.
Use caution to prevent damage when moving the unit.
Use an adequate rope or cable sling and keep the unit
in an upright position at all times during rigging and
moving operations.
CAUTION: Protect the top and sides so that the
rigging sling will not damage the unit.
22|^
.THERMOMETER WELL (4)
15
Í16
SIZE
180
240
A B
175 68
195 88
C
39-1/8 16-15/16
39-13/16
Approximate Shipping Weights
180-479.
240-479.
...
..........
...
..................
...................
...............
....
4900 lbs.
5700 lbs,
D
21-1/32
fil
lio
V M.RT GAS
CONNECTION
28á
f4-
-76-^
f
/3;
ERT. DRAIN CONNECTION
18-^
Figure 2—Dimensional Drawing
HEATING RATINGS and CAPACITIES 180/240-479
Input 1st stage
Output 1st Stage
Input 1st and 2nd Stage
Output 1st and 2nd Stage
Approved Temp Rise
Model 180-479
Model 240-479
-B-
®16
66^
TABLE I
Btuh
Btuh
Btuh
Btuh 337,000
°F 45 - 75
°F 20 - 50
225,000
168,000
450,000
TABLE II
COOLING RATINGS and CAPACITIES
MODEL 180-479 240-479
Capacity (Total Cooling) Btuh
Air Flow
External Static Pressure
Entering Air Temperature
Entering Water Temperature
Gas Input (Total)
Electrical Input (Total)
Refrigerant Type
Amount per Chiller Lbs.
Total Solution per Chiller Lbs. 55 79
CFM
In. wg. 0.3 0.4
°F
°F
Btuh 450,000 600,000
KW 5.0
180,000
6,000 8,000
80/67 80/67
45 45
R717
18
240,000
6.0
R717
26
-2-
Mounting Bases
The mounting base should comply with local codes
and be made of noncombustible material. The recom
mended types of mounting bases for all installations
are:
a. Precase concrete lintels. Use three lintels run the
depth of the unit; one under the right end, one under
the left end, and one at the center of the unit.
b. Steel beams. Use three I-beams run the depth of
the unit; one under each end and one at the center.
c. Concrete Slab. A minimum thickness of four inches
is required.
Rooftop Installation
When installing the 479 on a roof or other com
bustible material, use noncombustible supports and
allow a 6 inch clearance beneath the unit’s subbase
for proper air circulation. Be sure the roof construc
tion will support the weight of the equipment. Locate
the unit above a load-bearing wall whenever possible.
Condensate Drain
The 479 is furnished with a 3/4 inch FPT drain con
nection. If the installation requires draining the con
densate away from the roof of the building, connect
tubing, pipe, hose or trough and pitch downward one
inch for every ten feet of horizontal run.
Ground Level Installation
The 479 should be placed on a concrete slab at least 4
inches thick. Level the unit on the slab and be sure
there is adequate drainage away from its base.
Clearances
The minimum clearances are 6 inches from the duct
side and 24 inches from all other sides.
II. INSTALLING VENT CAPS
The vent cap assemblies are packaged and shipped in
the heating section coil compartment. Install the vent
cap assemblies as follows. See Figure 3.
1. Remove the cover on each of the vents on the roof
of the unit.
2. Use the FAJ5606B screws supplied with the assem
blies to fasten the base section of the vent cap assem
bly.
3. Remove the three self-tapping screws in the top
cover, located approximately 7 inches behind each
vent cap. Attach one of the air deflectors in this
location for each vent cap, using the screws removed.
III. DUCT CONNECTIONS
Before attaching the ducting to the unit, remove the
sheet metal panel that is used to protect the outlet
and return openings. The ductwork may be screwed or
bolted to the unit flange with suitable gaskets to in
sure a weathertight seal. Be sure the sheet metal
overlaps the flange on the unit.
CAUTION: Take care not to puncture the evaporator
coil when drilling the duct flange.
All duct work external of the structure must be
properly insulated and water-proofed.
All openings in the structure must be properly flashed
and vibration isolated in accordance with local codes
and good building practices. Supply and return duct
work should be provided with an approved vibration
eliminator. The vibration eliminator must be located
within the structure.
IV. GAS CONNECTIONS
The gas supply pipe for the Model 479 should be a
direct line from the gas meter or propane supply tank.
The gas supply pipe should terminate at the unit with
a tee.
The size of the gas pipe used depends upon the length
of run and allowable pressure loss established by the
utility. Never use pipe smaller than the gas connection
to the unit manifold.
The following are pertinent recommendations:
1. Avoid low spots in long runs of pipe. It is best to
grade all pipe 1/4 inch in every 15 feet to prevent
traps. All horizontal runs should grade up to risers.
2. A drip leg must be provided at any point in the line
of pipe where condensate may collect. Such drip leg or
drip legs shall be installed in locations readily ac
cessible to permit cleaning or emptying. The drip legs
should not be located where they are subject to
freezing. See Figure 4. Check local codes for size and
capacity of drip legs.
3. Three manual shutoff valves should be installed;
one valve between the gas supply pipe and heating
section, and one between each chiller and the gas sup
ply pipe.
4. A ground joint union should be installed between
the individual gas controls manifold and each manual
shutoff valve.
DRIP LEG
WITHIN'STRUCTURE
Figure 4—Drip Leg Location
5. The joint compound (pipe dope) used must be
resistant to the action of propane gas.
6. Support all piping with appropriate hangers. Use a
minimum of one hanger every ten feet.
7. After all gas connections are made, check for
leakage using soap and water solution, or leak-check
unit in accordance with local utility regulations.
WARNING: NEVER USE A MATCH OR OPEN
FLAME FOR LEAK TESTING.
Purging Gas Lines
After making all gas connections and checking for
leaks, it is now necessary to purge the supply lines to
eliminate trapped air.
WARNING: NEVER PURGE GAS LINES INTO
THE COMBUSTION CHAMBERS OF THE FUR
NACE OR CHILLERS.
1. With the furnace manual gas valve and pilot
shutoff valve closed, disconnect the pilot supply tube
at the pilot shutoff valve on the furnace.
2. Open the manual shutoff valve; then open the pilot
shutoff valve and allow the supply line to purge until
the odor of gas is detected. Immediately upon detec
ting a gas odor, turn off the gas and reconnect the
pilot supply tube. Allow at least five minutes to elapse
before lighting pilot.
3. Purge the gas line to each chiller in the same man
ner as described for the furnace.
V. ELECTRICAL CONNECTIONS
The Model 479 requires a 3 wire, 230 volt, 60 cycle, 3
phase power supply. Check the unit rating plate to
make sure the power supply meets all the electrical
specifications. Electrical connections must be made in
accordance with the National Electrical Code and the
electrical code of the local area.
The field high voltage connections are made to the
disconnect box located between the two chillers at the
right end of the unit.
The field low voltage wiring consists of running seven
wires from the thermostat subbase to the low voltage
terminal block in the furnace. See Figure 5 for low
voltage field wiring.
Thermostat P/N 34427D55
and
Subhase P/N 34427D59
-4-