Bryant 454 User Manual

Installation Instructions
454
SIZE 36
SERIES W
GAS-FIRED AIR CONDITIONER
Installation of the Model 454 Gas Air Con ditioning unit consists of the following steps:
I. Locating and Mounting the Unit
II. Connecting Chilled Water Lines III. Making Electrical Connections IV . Making Gas Connections
VI. Checking the Unit Operation
VII. Adjusting Gas Input
VIII. Balancing the System
DC . Freezing Weather Protection
Each of the above steps is discussed in detail in this instruction. Read the entire instruc -
tion before starting the installation.
Multiple Chillers and Cooling Coils
bri|ant
I
39454D1
4/25/69
■■1
When it is planned to connect two or more chillers or coils, additional piping and electrical information is required and should be obtained from your Bryant Distributor. When making multiple chiller installations, it is recommended that only 454 chillers be interconnected. The use of other model chil lers with the 454 in a multiple system should
be avoided.
Operation at Atmospheric Pressure
The chilled water tank on this unit is vented
to the atmosphere; consequently, the chilled water circuit operates at or near atmospheric pressure.
Therefore, conventional piping practices for a closed, pressurized system do not apply for this unit.
NOTE: When the water chiller is piped to a boiler as described below, the indoor coil operates at or near atmospheric pressure
when used for cooling; it may be pressurized when it is used with the boiler for heating.
Figure 1 - Model 454 Gas Air Conditioner
When this chiller is piped with a boiler to form a combination heating and cooling sys ­tern, provisions must be made for a positive shut-off between the chiller tank and the boiler.
When the boiler is in operation, the chiller tank must be by-passed. A sedime: must be installed when a common pipe (|oni and boiler.
When the chiller is i:
of course, should be b;
DO HOT
LOCATING AND M
The unit is designed for outdoor installation. It may be located at ground level or on a
roof. Consult local or other applicable codes for information concerning proximity to property lines, height above roof, obstruc tions, etc.
36/454
- 2 -
Mounting Base
Clearances
The unit is supported on 3 rails attached to
the bottom of the base. These rails extend
the full width of jiie unit as shown in the dimensional drawing on page 2 .
The recommended types of mounting bases
for all installations are:
a . Precast concrete lintels . Use three lintels run the depth of the unit;
one each under the right and left end and one at the center of the unit.
b, Concrete blocks . Use a block under each corner plus a block
under each of the two long sides midway be tween the corner blocks . Arrange the blocks so that the center rail as well as the front and back rail is supported.
c . Concrete slab. Minimum thickness 4 inches.
CAUTION: ALWAYS USE NON-COMBUSTIBLE
MATERIAL FOR THE BASE.
)
The condenser coil is located at the front of the unit with the condenser air inlet through the rear fan opening and the discharge through the louvered front panel.
The minimum clearance between the back of the unit and a wall is 15 inches. If the over hang is less than 7 feet above the unit, the unit must be mounted outside a plumb line
from the eaves of the overhang. The clear ance on the right and left ends should be a
minimum of 2 feet to provide access for servicing.
AVOID
OPEN
WINDOWS
SLEEPING
QUARTERS
LIVING AREA
Figure 2 - Locating the Unit
I—I AVOID
u:
GARAGE
ELLS
GOOD
location:
AIR FLOW
r
15
MINIMUM
I. CONNECTING CHILLED WATER LINES
Refer to the following information: 'Multiple Chillers and Cooling Coils", page 1; "Operation
at Atmospheric Pressure, " page 1; and "Cold Weather Protection, " page 8.
TABLE
Nominal Pipe Size
Inches
Polyethylene Pipe
3/4
1
* Note: Values shown in the above table are for one direction only, and using Bryant water coils. Total length of pipe,
from chiller to coil and return, would be double the values shown. Values apply to single unit installations only. All distances shown are calculated on the predication that only long elbows are used. Galvanized well head elbows are used with the polyethylene pipe. When using plastic hose, avoid any sharp bends that would tend to restrict or stop the flow of water.
Allowable Distance* between Coil Models 404, 405, 406, 407, 408 and Chiller
Size 36
65 ft
280 ft
Bryant Quick Connect
Plastic Hose
Size 36
45 ft
- 3 -
Copper Pipe
Size 36 Size 36
Galvanized Pipe
67 ft
' 260 ft
87 ft
304 ft
36/454
Materials
1 . Chilled Water Piping
a. Use Bryant quick connect plastic hose. b. Polyethylene pipe - satisfactory substi
tute; use medium density flexible pipe whose wall thickness approximates Schedule 40 pipe (Commercial Standard CS 255-63). Pipe must be made from virgin material. Do not use pipe manu
factured from re-claimed material. c . Copper - satisfactory substitute . d. Brass - satisfactory substitute.
2. Fittings a. Galvanized - use when possible.
b. Brass - satisfactory substitute .
WATER FLOW RATE
AT VARIOUS EXTERNAL PRESSURES
Table II - Model 36-454
Water Flow Rate
GPM
2.0
3.0
'4.0
5.0
6.0 23.8
7.0
7.5
8.0
9.0
10.0 19.7
11.0 18.6
Pressure External to Unit
Ft Water Std RPM
25.9
25.5
25.0
24.5
23.0
22.5
22.0
21.0
Pipe Length and Diameter
Table I shows the maximum length of pipe of different diameters that can be used between the pump discharge and the coil inlet and still maintain minimum allowable (design) water
flow rate.
1. Multiply table values by two to obtain the
total length of pipe from chiller to coU and
return.
2. Length is measured along the pipe path and therefore includes vertical distance be tween the water coil and the chiller.
3. Lengths shown in Table I are based on using a total of eight well head fittings in the entire water line (chiller to coil and return). Lengths are predicated on the use of a Bryant matching water coil. For greater distances
use larger size pipe.
4. For calculating chilled water pipe size for coils not listed use friction loss method with allowance for coil pressure loss. Refer to coil instructions for pressure loss at design water flow rate. Refer to Table II showing available head with standard pump drive. For additional pump head consult your Bryant Distributor.
Insulation
1. Insulate both supply and return lines .
2. Material should be of good quality and be covered with a good vapor barrier. Armaflex or equivalent is recommended. Use 1/2-inch wall thickness .(Plastic hose is pre-insulated.)
36/454
Height of Coil above Unit
For the Model 36-454 the maximum vertical distance from chiller to top of coil is 21 feet. For greater heights an adjustable water pump
pulley kit is available, Part No. 65070D01.
Water Coil Connections
1. If the cooling coil is used in connection with a heating unit and the heating unit is not approved for installation downstream from the cooling coil, install the cooling coil in parallel with or downstream from the heating unit. This will avoid condensation in the heat ing unit. If the coil and heating unit are in stalled in parallel, the dampers or other means used to control flow of air should be adequate to prevent chilled air from entering
the heating unit; if manually operated, the
dampers shall be equipped with some means
to prevent operation of either unit uiiless the
dampers are in full heat or full cool position.
2. If the coil is located in a warm air stream,
do not connect polyethylene pipe directly to the coil. Connect a minimum of 24 inches of copper or galvanized pipe to both the coil in let and outlet; then connect the polyethylene pipe to these nipples . Note: not required when using Bryant quick connect plastic hose.
3. On installations where the water in the outside piping freezes and the coil is in a heated air stream, precautions must be taken
to provide for water expansion. The connect ing polyethylene pipe acts as an expansion vessel if there is sufficient footage in the
- 4 -
Loading...
+ 7 hidden pages