Bryant 452W User Manual

Installation Instructions
452W
SIZE 90
Series E
GAS-FIRED AIR CONDITIONER

Important—Read before Installing

1. Check all local or other applicable codes for in formation concerning proximity to property lines, height above roof, obstructions, etc.
2. Be sure the power supply available (voltage, frequency, and phase) corresponds to that specified on the unit rating plate.
3. Check the electrical service provided by the utility for the building to be sure that the service capacity is sufficient to handle the load imposed by this unit.
4. Refer to the regulations of the serving gas sup
plier and the local building, heating, plumbing, or other codes in effect in the area in which in stallation is to be made.
5. Refer to the dimensional drawing on page 2 for
location of electrical, gas, and chilled-water con nections prior to setting the unit in place.
C^els: 39452D70
FIL
OP
DO NOl
REMOV
bri|ant
39452D80 2/15/73
I

GENERAL

Model 90-452W is a gas-fired air-cooled absorption
unit designed to satisfy the cooling needs of com mercial and industrial buildings. This absorption unit supplies chilled water for cooling with Bryant’s indoor
and outdoor coil assemblies.

Multiple Chillers and Cooling Coils

When it is planned to connect two or more chillers or coils, additional piping and electrical information is required and should be obtained from your Bryant Distributor. When making multiple chiller in stallations, it is recommended that only Models 452 and 452W be interconnected. Interconnection of sizes 60, 90, and 120 is permissible, but the use of other model chillers with Models 452 and 452W in a multiple system should be avoided.

Operation at Atmospheric Pressure

The chilled-water tank on this unit is vented to the atmosphere; consequently, the chilled-water circuit operates at atmospheric pressure. Therefore, con
ventional piping practices for a closed, pressurized system do not apply for this unit.
NOTE: When the water chiller is piped to a boiler as
described below, the indoor coil operates at or near atmospheric pressure when used for cooling; the in door coil may be pressurized when it is used with the boiler for heating.
Figure 1 - Model 90-452W Gas Air Conditioner
When this chiller is piped with a boiler to form a com
bination heating and cooling system, provisions must be made for a positive shutoff between the chiller tank and the boiler.
When the boiler is in operation, the^ chiller tank must be bypassed. A sediment strainer must be installed at
the chiller tank inlet when a common pipe connects the chiller tank and boiler.
When the chiller is in operation the boiler, of course, should be bypassed.

Installation

Installation of the Model 90-452W, Series E Gas Chiller unit consists of the following steps:
I. Locating and Mounting the Unit
II. Connecting Chilled-Water Lines
III. Making Electrical Connections
IV. Making Gas Connections
V. Chilled-Water System
VI. Checking the Unit Operation
VII. Adjusting Gas Input
VIII. Balancing the System
Each of the above steps is discussed in detail in this
instruction. Read the entire instruction before starting
the installation.
AIR OUT
Figure 2 - Dimensionai Drawing

RATiNGS AND PERFORMANCE

MODEL Unit Rating Plate (Voltage-Hertz-Phase) Cooling Capacity Gas Input Condenser Air Delivery Chilled-Water Flow Rate (Nominal) Max Head at Nominal Water Flow Ft Water Electrical Input KW 2.5 Fan Motor (2) HP & SF
Voltage Hertz-Phase Capacitor (370 Volts)
Hydraulic Pump Motor
Voltage-Hertz-Phase
Alternate Hydraulic Pump Motor HP & SF
Voltage-Hertz-Phase
Chilled-Water Pump HP & SF
Voltage-Hertz-Phase
Refrigerant
Amount Total Solution
Bryant Sound Rating
Approximate Shipping Weight
Btuh Btuh
CFM
GPM 18.75
mfd 10 7.5
HP & SF
Type
Lbs 18 Lbs
SRN
Lbs
200-60-1 230-60-1
90,000 90,000
246,000 246,000
10,000 10,000
37 37
1/2 & 1.0 1/2 & 1.0
200/230-60-1 200/230-60-1
1 & 1.25
200-60-1
1 & 1.25
200-60-1
1/3 & 1.35
200-230-60-1 200-230-60-1
R717
55 22
1317
COIL CLEANING ACCESS PANEL
90-452W
Series E
1-1/2 & 1.25
208/230-60-1
1/3 & 1.35
4
-5
18.75
2.5
1 & 1.25
230-60-1
R717
18 55 22
1317
CONNECTIONS
MODEL Unit Rating Plate (Voltage-Hertz-Phase)
**Maximum Line Length
Control Circuit Volts 24 24
External Power Available VA Gas Supply Connection Size Chilled-Water Supply (NPT) Chilled-Water Return (NPT) Inches 1 FPT Equalizer Line (NPT)
*If other than 75 °C copper conductor is used, determine size from unit ampacity and the National Electric Code.
Voltage drop of wire selected must be less than 2% of unit rated voltage.
**Length shown is for one way along the wire path from unit to service panel.
Unit Ampacity for Electrical Conductor Sizing Amps
*Min Branch Circuit Wire Size
Recommended Fuse Size
AWG No.
Amps 35 35
Ft
Inches 3/4 NPT 3/4 NPT Inches
Inches 1-1/2FPT 1-1/2FPT
200-60-1
1-1/4FPT
90-452W Series E
230-60-1
19.25 26.2 12 10
71 115
5 5
1-1/4FPT
1 FPT
— 2.
REFRIGERANT RESTRICTORS HIGH-PRESSURE
(CHILLER INLET) LIMIT SWITCH RECTIFIER
SECONDARY HI-TEMP LIMIT SWITCH
AMBISTAT
PILOT PRESSURE SWITCH
REGULATOR
MANUAL SHUT-OFF VALVE
GAS VALVE
MAINTENANCE
LABEL
GENERATOR PILOT HI-TEMP LIMIT SWITCH
Figure 3 - Unit Front View With Access Panels Removed
VALVE C
S' .
IL
' V"
CHILLED­WATER TANK
VALVE E
---------
PUMP DISCHARGE ------­TANK
PUMP HEATER
A72597
VALVE A
■ VALVE D
Figure 4 - Unit Left-Side View With
Access Panel Removed
3
HYDRAULIC SOLUTION PUMP PUMPS MOTOR
Figure 5 - Unit Right-Side View With
Access Panel Removed

I. LOCATING AND MOUNTING UNIT

The absorption unit is approved for outdoor in stallation only and may be located at ground level or on the roof. Consult local or other applicable codes for information concerning proximity to property lines, height above roof, obstructions, etc.
3. Leave sufficient clearance (6 inches minimum) between unit base and roof for proper air cir culation when installing unit on a roof. Use precast concrete lintels or concrete blocks as described in paragraph 2, or use steel beams. Check local codes. Refer to NBFU code for In stallation of Heat Producing Appliances.

A. Mounting Base

1. USE NONCOMBUSTIBLE MATERIALS.
2. Suggested types of mounting base for ground in stallation ;
a. Precast concrete lintels. Use three lintels the
depth of unit, one each under right and left end of unit, and one at center of unit.
b. Concrete blocks. Use one block at each corner
of unit plus blocks under the two long sides midway between the corner blocks.
c. Concrete slab. Minimum thickness 4 inches.

II. CONNECTING CHILLED-WATER LINES

B. Clearances

1. Absorption unit should have a minimum clear ance of 2 feet on all sides from any adjacent obstruction.
2. Avoid locating the unit where hot condenser air can impinge on nearby obstructions and mix with
the inlet air supply. The condenser air discharges upward. The unit should be located outside of the plumb line from any overhang when the distance from the overhang to the top of the unit is less than 7 feet.
Refer to “Multiple Chillers and Cooling Coils,” page 1; “Operation at Atmospheric Pressure,” page 1; and “Chilled-Water System”, page 7, before making any chilled-water connections.
1

TABLE I

^Allowable Distance Between Coil & Chiller
Nominal
Pipe Size
(Inches)
1 30 1-1/4 1-1/2
NOTE; Values shown in Table I are for one direction only. The total length of pipe from chiller to coil and return would be double the values given. The above table applies to single unit installations only.

A. Materials

NOTE: Black iron pipe must not be used for chilled-
water piping.
1. Piping a. Polyethylene Plastic Pipe - use medium den
sity flexible pipe whose wall thickness approximates Schedule 40 pipe (Commercial Standard CS 255-63). Pipe must be virgin plastic. Do not use pipe manufactured from reclaimed plastic.
b. Copper—satisfactory substitute.
Polyethylene
Pipe
(Feet)
205 490
1. Multiply table values by two to obtain total length of pipe from chiller to coil and return.
2. Length is measured along pipe path and therefore includes vertical distance between water coil and chiller.
3. Lengths shown in Table I are based on using a total of eight galvanized wellhead elbows in en tire water line (chiller to coil and return). Lengths are predicated on use of a Bryant matching water coil. For greater distances, use larger pipe or add a pump. Consult your Bryant Distributor for additional information.
Copper
Pipe
(Feet)
51 165 388
Galvanized
Pipe
(Feet)
54 220 492
c. Galvanized—satisfactory substitute.
2. Fittings a. Galvanized—use when possible.
b. Brass—satisfactory substitute.
c. Nylon—satisfactory substitute.

B. Pipe Length and Diameter

Table I shows maximxom length of pipe of different diameters that can be used between the pump discharge and the coil inlet and still maintain minimum allowable (design) water flow rate.

C. Insulation

1. Insulate supply and return lines separately.
2. Material should be of good quality and be covered with a good vapor barrier. Armaflex or equivalent is recommended.
Wall thickness; 1/2 inch.

D. Height of Coil above Absorption Unit

Practical coil elevation is limited only by the at
mospheric pressure supported hydraulic head.
— 4

E. Water Coil Connections

1. If cooling coil is used in connection with heating unit, and heating unit is not approved for in stallation downstream from cooling coil, install
cooling coil in parallel with, or downstream of, heating unit. This will avoid condensation in heating unit. If coil and heating unit are in stalled in parallel, dampers or other means used to control flow of air should be adequate to prevent chilled air from entering heating unit, and if manually operated, shall be equipped with
means to prevent operating of either unit unless
dampers are in full heat or cool positions.
2. If coil is located in warm air stream, do not con nect polyethylene pipe directly to coil. Connect minimum of 24 inches of copper or galvanized pipe to both coil inlet and outlet. Then connect plastic pipe to these nipples.
3. Precautions must be taken to provide for water expansion on installations where outside piping is subject to freezing temperatures and coil is in a
heated air stream. The connecting polyethylene plastic pipe acts as an expansion vessel if there is
enough footage of this pipe in heated space (space not subject to freezing temperatures). Table II shows minimum lengths (total inlet and outlet) of plastic piping of various diameters
required to provide adequate expansion volume.
If total plastic chilled-water line footage in heated space is not as long as minimum value shown in Table II, tee off additional length of polyethylene pipe to either side of coil to meet required footage. Cap open end of added polyethylene pipe.
Low-voltage (24-V) wires from thermostat con trol enter directly into control box through knockout in panel on right side. Low-voltage wires are connected at terminal block. See Figure 6 for location of control box components.
6. Figm-e 9 is a line-to-line wiring diagram of unit.
7. Disconnect chilled-water pump electrical leads at power relay in control box before energizing
unit when ready to check field wiring. Do not
operate pump dry.

TABLE II

Nominal Pipe Size
(Inches)
1 60 1-1/4 35 1-1/2

III. MAKING ELECTRICAL CONNECTIONS

Length of Plastic Pipe
(Feet)
25
1. Make all electrical connections in accordance with the National Electrical Code and any local ordinances or codes that might apply.
2. The unit must be electrically grounded in ac cordance with the National Electrical Code, ANSI Cl dated 1968 when installed.
3. Provide separate power supply for air con ditioner.
4. Provide fused disconnect switch within sight of, and not more than 50 feet from, absorption unit.
Use 35-amp standard fuse or 25-amp fusetron.
5. Unit ■ is shipped from the factory completely
wired. Connection of the power supply to power relay is made directly into control box through knockout in corner panel on right side of unit.
Figure 6 - Control Box Components

IV. MAKING GAS CONNECTIONS

Consult local gas company before making any gas connections. In case of conflict with this instruction, local requirements should be followed. This appliance is not suitable for use with conventional venting systems.
Refer to the American National Standard for In stallation of Gas Appliances and Gas Piping Z21.30 dated 1964, in the absence of local building codes.
Before selecting the size and type of pipe that is to be used for installing the absorption unit, be sure to check with local gas company for the necessary in formation. The size of the gas pipe to be. used between meter and unit will depend upon the length of run and the allowable pressure loss established by the utility.
The gas connection to the unit is made to the 3/4-inch shutoff valve at the control manifold. The supply pipe enters the unit through an opening in the corner panel
5
DRIP LEG WITHIN STRUCTURE
A70676

Figure 7 - Drip Leg Location

on the right side. Install a drip leg trap in the gas sup
ply riser leading to the unit. The following are pertinent recommendations:
1. Avoid low spots in long runs of horizontal pipe. It is best to grade all pipe 1/4 inch for every 15 feet
to prevent traps. All horizontal runs should grade
downward to risers. Use risers to connect to unit and to meter.
2. Install drip leg in riser leading to unit. Drip leg
will serve as trap for dirt and condensate. Install
drip legs where condensate will not freeze. See Figure 7 for drip leg location.
3. Install wrench-type shutoff valve in gas supply
line within sight of, and convenient to, unit.
4. Place ground joint union close to unit between gas controls manifold and wrench-type shutoff
valve.
5. Support all piping with appropriate hangers.
Maximum distance between hangers should be
10 feet.
6. Joint compound (pipe dope) which is resistant to action of liquefied petroleum gases should be ap
plied sparingly and only to male threads of joints.
7. After all gas pipe connections are made, purge
lines and check for leakage. Turn off power sup ply to unit when purging lines to prevent glow coil in reignition pilot from being energized. Use
a soap-and-water solution for leak-checking.
WARNING: Never use maiclies. candles, or other
.sources ol' ignition to check for gas leakage.

Pilot

Both natural gas and propane gas units are equipped
with an automatic reignition pilot. The pilot will light
automatically when supplied with gas and is elec
trically energized. Light the pilot using the procedure outlined on the
lighting instruction plate attached to the generator. However, when lighting the pilot for the first time, perform the following additional steps:
1. If supply line was not purged prior to connecting unit, it will be full of air. Because venting air through small pilot port is a lengthy process, it is
recommended that pilot supply line be discon
nected at pilot shutoff valve and supply line be allowed to purge until odor of gas is detected.
WARNING: Never purge gas lines inii) the com
bustion chamber.
Immediately upon detection of gas odor, recon
nect pilot supply tube. Allow 5 minutes to elapse
and light pilot in accordance with instructions on
lighting plate.
2. Pilot flame should be soft blue in color and of sufficient length to provide good impingement on unimetal of Bryant pilot. Flame should, extend upward between carryover ports of two adjacent burners.
3. If pilot flame does not have appearance described above, adjust it by means of manual pilot shutoff valve.
a. The valve is equipped with an adjustable
screw. Turn handle to full open position, and
— 6
remove screw cap to expose adjustable screw.
Turn adjusting screw until flame has desired appearance,
b. Replace screw cap.

V. CHILLED-WATER SYSTEM

CAUTION: Do nol run the pump dry. Freezing con
ditions will not damage the pump; however, do mu at tempt to operate the pump when i-hiller or chilled­water lines are h'ozen.

Corrosion Protection

The components of the chilled-water circuit must be protected from corrosion by the addition of an inhibitor to the chilled-water system. Chilled-Water Additive P/N 62875D1 must be added when water only, or when water and methanol antifreeze, are used in the chilled-water system.
The package of Chilled-Water Additive P/N 62875D1 supplied with the unit is sufficient for systems con
taining up to 15 gallons. For systems larger than 15 gallons, add one package for each additional 15­gallon capacity or fraction thereof. To estimate the capacity of the chilled-water system, refer to Table III.

TABLE III

Water Capacity in Gallons

90-452W Chiller Bryant 18,000-Btuh Coil 0.6 Bryant 36,000-Btuh Coil Bryant 48,000-Btuh Coil Bryant 90,000-Btuh Coil 2.5 1 ft of 1-inch pipe 0.05 1 ft of 1-1/4-inch pipe 0.08 1 ft of 1-1/2-inch pipe 0.11
CAUTION: l)i> Ilf' .tdil ; n> ■ hillid-« ;iu i :nltliii\i
9.7
1.0
1.25
when Ucar-17 is used for freeze proieetion. Ucar-I7 contains adequate inhibitor when used in the recom
mended concentration as shown in Tables IV and \'.

Freezing Weather Protection

Freeze protection is normally required only on those
systems that
(a) Use hard piping (copper and galvanized) (b) Use polyethylene tubing without sufficient
length of tubing in conditioned space.

TABLE IV

^Minimum
Concentration
Antifreeze
Methanol 20
Ucar-17
*For protection at various outdoor ambients, refer to Table V. NOTE 1—^Ucar-17 is the only approved type of permanent (glycol­base) antifreeze recommended for freeze protection of Model 90­452W Chiller.
(Percent of Voiume)
33
Type
Chilled-
Water Additive
Borax & Chromate
(P/N 62875D1)
None^
(See Note 1)

TABLE V

Lowest Winter
Outdoor
Temperature (°F)
20 15 10 33 5 0
-5
-10
-15 42
-20 45
-25 47
-30
Percent of Antifreeze
Concentration (% of Vol.)
Ucar-17 Methanol
33 20 33
33 33 36
39
49
20 22 26 29
32 34 36 38 43 44
(c) Must be operated dtiring winter as well as
summer.
(d) Have cooling coil located in unheated area
where freezing could occur, such as rooftop unit.
Table IV lists the minimum amount of concentration,
and the type of chilled-water additive to use when
required.

Adjusting Chilled-Water Level

1. Turn off gas at main manual shutoff valve and turn off electrical power at disconnect switch.
WARNING: To prevent bodily iiijnry. di.sconnecr con-
dejKser fans motor leads in the connol box.
2. Remove left-side access panel, then remove hand hole cover located on top of chiller tank. See Figure 8.
3. Disconnect water line at chiller inlet. (When in stalling chilled-water lines, it is advisable to leave this connection open until lines have been flushed.)
4. Fill tank with tap water until distributor pan at top is covered with water. A garden hose is useful for this operation.
5. Turn on electrical power to unit and start pump. Continue to supply water to tank and operate pump until all foreign matter has been flushed from lines, then remove garden hose.
6. Turn off pump. Reconnect water line at chiller inlet.
7. Add water to tank until tank is approximately half full. Replace hand hole cover.
8. Start pump and check for leaks.
9. Adjust operating water level with piunp running. This is accomplished by removing drain plug.
Operating water level is properly adjusted when water ceases to flow from drain opening. Replace drain plug and turn off pump.
10. Refer to section on “Freezing Weather Protec tion” on page 7. If freeze protection is not
required, omit Steps 11 and 12, and proceed with
Step 13. If freeze protection is required, decide on
— 7 —
type antifreeze to use. Step ll.gives procedure for adding Ucar-17 antifreeze. Step 12 covers procedure for adding methanol antifreeze.
11. Adding Ucar-17 - Calculate capacity of chilled­water circuit by using information given in Table III. Refer to Table V and determine amount of antifreeze required. Drain out amount of water equal to amount of antifreeze to be added. Add antifreeze, then check operating level and correct. Omit Steps 12, 13, and 14.
NOTE: Do not use any chilled-water additive when
Ucar -17 is used in the recommended concentration.
12. Adding methanol antifreeze - Calculate capacity of the chilled-water circuit by using information given in Table III. Refer to Table V and deter mine amount of antifreeze required. Drain out
amount of water equal to amount of antifreeze to be added. Add antifreeze, then check operating level and correct.
NOTE: Methanol antifreeze does not contain an inhibitor; therefore, add the required amount of Chilled-Water Additive P/N 62875D1 as described in Step 13.
13. Remove hand hole cover and add contents of Chilled-Water Additive Package P/N 62875D1 to chiller tank. Package supplied is sufficient for systems up to 15 gallons. For systems larger than 15-gallon capacity, add one package for each ad ditional 15 gallons or fraction thereof.
14. Replace hand hole cover. Turn on pump. Pump should operate a minimum of 10 minutes to dissolve all chilled-water additive.
15. Turn off electrical power at disconnect switch. Reconnect condenser fans motor leads in control box. Turn on power at disconnect switch.
16. Replace access panel. Chiller is now ready for operation.

VI. CHECKING THE UNIT OPERATION

1. Be sure manual gas valve is off. Light pilots as described on Instruction Plate.
2. Turn on manual gas valve with thermostat sub
base switch levers on “cool” and “auto.” Set ther mostat below room temperature. To check correct operation of electrical circuit, observe operation of gas valve, condenser fan motors, hydraulic pump, and indoor fan. Set thermostat
above room temperature and observe that unit
shuts off properly.
3. Check indoor fan operation by setting thermostat subbase fan switch lever to “on.” Indoor fan
should operate continually with thermostat set above or below room temperature.
4. To place system in operation, open main manual gas valve, replace all panels, and set thermostat
at desired temperature.

Control Circuit Description

Refer to Figiire 9. Note that 24 volts (transformer secondary voltage) is applied to chiller terminals R
and F whenever power is supplied to unit. When ther mostat calls for cooling, chiller terminal R is con nected to chiller terminal Y through thermostat.

Automatic Pilot Reignition

The automatic pilot reignition circuit consists of the
1-ohm resistor (llAl), pilot pressure switch (7P), and the pilot and ignition coil assembly (6B). The pilot pressure switch (7P) contacts close when gas is turned on to the unit and current flows from chiller terminal R, through the 1-ohm resistor (llAl), pilot pressure switch (7P), the glow coil of the pilot assembly (6B) via the pilot’s normally closed contacts to chiller ter minal F, and lights the pilot.
Approximately one minute after the pilot is ignited, heat from pilot will cause normally open contacts of the pilot to close and the normally closed contacts to open.
If the pilot should go out, the normally open pilot contacts (which were closed when the pilot was ignited) will reopen, deenergizing the power relay (2D) and the magnetic gas valve (5B). This will cause all motors (3A1, 3A2, 3Cl & 3C2) to stop and the gas
valve to close. The normally closed pilot contacts
(which were opened by heat from the pilot) will close and complete the current path to reignite the pilot.
Figure 8 - Chiller Tank

Cooling Operation

Two current paths are provided from chiller terminal Y to chiller terminal F when the thermostat calls for cooling and the pilots are ignited as described above.
Current flows from chiller terminal Y, through the
power relay winding (2D) and through the closed con tacts of the pilot (6B) to chiller terminal F. The energized power relay winding (2D) causes the power relay contacts (2D) to close and starts the two fan motors (3Cl & 3C2), the hydraulic pump motor (3A1), and the water pump motor (3A2).
Tapped Primary Transformer
IB
Pump Heater Relay (SPST-NC)
2B
Power Relay (DPST)
2D
Circuit Breaker
2J
(Lockout Relay) Motor (Hydraulic Pump)
3A1 3A2 - Motor (Water Pump)
3C1 - Motor (Fan) (PSC)
3C2 - Motor (Fan) (PSC)
5B - Gas Valve (Magnetic)
6B - Pilot (Reignition)
7A - High-Pressure Limit Switch
(Auto. Reset) (SPST)
7H1 - Limit Switch (High-Temp
Cont) (SPST)
7H2 - Limit Switch (Sec, High-Temp.
Manual Reset) (SPST)
If any of the original wire, as supplied, must be replaced, use the same or equivalent wire.

Figure 9 - Model 90-452W Wiring Diagram

7L - Ambistat (Part Load Control)
(SPST)
7P - Pressure Switch (Pilot Gas) (SPST)
11A1 - Resistor 11A2 - Pump Heater
Current also flows from chiller terminal Y, through the high-temperature limit switch (7H1), the closed contacts of the circuit breaker (2J), part load control
(7L), high-pressme switch (7A), secondary high-
temperature limit switch (7H2), the gas valve coil
(5B), and to chiller terminal F. The energized gas
valve coil opens the gas valve and supplies gas to the generator burners.

Part Load Control

The part load control (7L) circuit is an automatic
recycling type of temperature sensitive switch. Con nected to the switch is a long capillary tube that is in
serted in the chilled-water supply line. The part load
control switch contacts open when the chilled-water supply temperature drops below 40±1°F. The opening of the part load control switch contacts deenergizes the gas valve and shuts off the gas supply to the burners. The power relay (2D) remains
energized and the fan motors (3Cl & 3C2) hydraulic
prnnp motor (3A1), and the water pump motor (3A2)
will continue to run.
The part load control switch contacts will close again when the chilled-water temperature rises to 42 ± 1 °F. The magnetic gas valve will be reenergized and turn the gas on again.

High-Temperature Cutoff

The high-temperature cutoff circuit includes a high­temperature limit switch (7H1), located in the front of the generator, plus a circuit breaker (2J) that is located in the control box.
If the generator becomes overheated, the high­temperature limit switch (7H1) will open, providing a current path through the heater element of the circuit breaker (2J). This current flow through the heater causes the normally closed contacts of the circuit breaker to open, removing the 24-volts potential from the magnetic gas valve. The deenergized gas valve will
turn off the gas supply to the burners.
The control box cover must be removed to reset the circuit breaker. Pressing the red “reset” button resets
the circuit breaker.
A secondary high-temperature limit switch (7H2) is
connected in the Y leg of the control circuit to insure the closing of the gas valve in the event the generator overheats and the high-temperatme limit switch
(7H1) does not open. The secondary high-temperature
limit switch is located on the generator header and must be reset manually.

Hydraulic Pump Heater

Model 90-452W is equipped with a hydraulic pump
— 9
TABLE VI—Manifold Pressure
(Inches W.C.)
Specific Gravity
0.59 0.61 0.63
0)
900
3' 03
950
>
1000 3.1” 3.2”
OQ
1025 3.0” 3.1” 1050 2.8” 2.9” 1100 2.6” 2.7”
For manifold pressures exceeding 3.0 inches ±¡.3 inches, consult
your Bryant Distributor.
3.9”
3.5”
4.0”
3.6”
4.1”
3.7”
3.3” 3.4” 3.5”
3.2”
3.0”
2.8”
0.65
4.2”
3.8”
3.3”
3.1” 3.2”
2.9”
0.67
4.3”
3.9”
3.4”
3.0”
heater circuit that permits operation of the unit at
outdoor ambient temperatures down to -30°F. The pump heater circuit consists of a hydraulic pump heater (11A2) and a pump heater relay (2B).
The pump heater is connected in series with the nor mally closed contacts of the pump heater relay. Current flows through the heater only when there is no demand for cooling hy the thermostat. When the thermostat calls for cooling, the pump heater relay winding is energized and opens the normally closed contacts of the pump heater relay and removes the power supply voltage from the pump heater.

VII. ADJUSTING GAS INPUT

The gas input must be checked and adjusted if necessary to agree with that shown on the rating plate of the unit (246,000 Btuh). The burners are equipped
with fixed orifices drilled as follows; Natural gas No.
36 drill; Propane gas No. 52 drill.
The natm-al gas units are equipped with adjustable gas pressure regulators set at factory for 3.0-inches
w.c. manifold pressure. The propane gas units are not
equipped with a pressure regulator. Check natural gas units by one of the following
methods:
1. Measxrre gas at meter. Be sure all other gas ap
pliances are turned off. Increase or decrease in put to burners by adjustment of gas pressure regulator.
2. Set manifold pressure according to Table VI for Btu value and specific gravity of gas to be sup
plied to unit. Connect manometer to 1/8-inch pressure tap on manifold and, with unit in operation, set correct pressure by adjustment of gas pressure regulator.
Example: Natrual Gas
1025 Btu
0.63 Specific Gravity
1. From Table VI, manifold pressure is 3.2 inches
w.c.
2. With manometer connected to manifold, set pressure at 3.2 inches by adjusting gas pressure regulator.
Check propane gas units as follows:
The burner orifices are sized for rated input with a manifold pressure of 11.0 inches w.c. Connect manometer to 1/8-inch pressure tap on unit manifold and adjust regulator at supply tank to provide a manifold pressure of 11.0 inches w.c.
CAUTION: The unit may be run for short periods with the panel removed. Proloiif;ed operatioti with panels removed sliould not he attempted.

VIII. BALANCING THE SYSTEM

After the unit is operating and the input has been measured and adjusted to agree with the rating plate requirements, balance the system.
Any approved method of checking the a:irflow over the water coil may be utilized. Reference is made to the Bryant Service Manual on Gas Air Conditioning for a review of standard methods. Do not purge non condensibles or check solution level.
— 10
NOTE 1: Field wire from terminal “F” at chiller unit must extend through hole at furnace terminal “F” and connect to cooling relay as shown. If cooling relay is factory-installed, remove lead from terminal “X.” Strip end, and connect as shown.
NOTE 2: This wiring procedure will not allow manual fan operation if chiller unit power is turned off.

Figure 10 - Connecting 90-452W Chiller to Models 190- or 220-394, Series E, F, or G Furnace

THERMOSTAT P/N 34427D54
THERMOSTAT SUBBASE P/N 34427D59
LV I
___J__J___
r
T“1
MODEL 379 CONTROL BOX
1
------
1
MODEL 90-452 TERMINAL BLOCK
-------------
FIELD LOW-VOLTAGE WIRING

Figure 11 - Connecting 90-452W Chiller to Model 90W-379 Furnace

— 11 —
FIELD LOW-VOLTAGE WIRING.
-----------------------
^^E^LD_HIGH-VOLTAGE
MODEL 884
THERMOSTAT AND SUBBASE P/N 34427D031
V

Figure 12 - Connecting 90-452W Chiller to Models 90-412 or 90-415 Fan Coil Unit

12
Loading...