Bryant 451A User Manual

nstallation Instructions
451
SERIES A
GAS-FIRED AIR CONDITIONER
Installation of the Model 451 Gas Air Conditioning
Absorption unit consists of the following steps:
I. Locate and mount absorption unit.
II. Connect chilled water lines. III. Electrical connections. IV. Gas connections.
VII. Adjust gas input.
VIII. Balance system.
IX. Purge Non-Condensibles.
Each of the above steps is discussed in detail in this irtstructiofl. Read entire instruction before starting installation.
Position unit and remove wooden shipping crate base as shown in Figure 1.
1. Saw wood stringers as shown.
FMijJTTJjyMl
39451D1
I
2. Remove unit access panels and remove 3 ship­ing bolts from crate base.
3. Tilt one end of unit and remove half-section of crate base; then reiiiove remaining section while tilting the other end.

I. LOCATE AND MOUNT ABSORPTION UNIT

The absorption unit may be located at ground lével or on the roof. Consult local codes for information concerning proximity to property lines, height above roof, obstructions, etc.

A. MOUNTING BASE

1. Use non-combustible materials.
2. Base should be large enough that unit will not
overhang.
3. A poured concrete slab, minimum 4" thick, is recommended for ground installation.
4. On roof installations leave süfficieíit clearance between unit base and roof top for proper air circu-
, lation.
5. A unit supported on concrete blocks will require a block at each corner plus a fifth block under the front, midway betweèn the front corner blocks.

B. CLEARANCES

See Figures 2 and 3 for typical locations.
1. Absorption unit should have a minimum clear ance of 2 feet on all sides from any adjacent ob struction.
2. Avoid locating the unit where hot condenser discharge air can impinge on nearby obstructions and mix with the inlet air supply. The condenser air discharges upward at a small angle toward the front of the unit. With the condenser facing the wall the unit can be located at, or outside of the plumb line from any over-hang.
EH 451
Cancels: New
Effective 2/1/64,
Model A 36-451
46 31 52
54-451 55
B
C
38 59
D
E
9-1/16 23-9/64
11-1/16 28-3/4
F
G 26-1/8 17-5/16 32-7/16
22
H 3-7/64 3-39/64
Cooling Capacity Heat Input Condenser Air Delivery Water Flow (Min. Required)
Max. Frictional Loss Handled
by Chiller Pump
Max., Elevation of Coil
above Chiller Ft
Pump and Fan Drive
115V, 60 Cy., 1 Phase Minimum Wire Size * Refrigerant Type Refrigerant Amount Approximate Shipping Wt. Lb
EH 451
36-451
Btuh
Btuh Cfm Gpm
Ft Head 23 20
35,000 53,000
110,000 165,000
4,500 6,700
7.5 11
22
HP AWG
1/3
14 *
54-451
22
1/2
12 *
717 717
Lb
18
750
- 2
31
1,125
^Satisfactory where distance, measured along
wire path, between unit and connection into main panel does not exceed 100 ft. Where distances are longer, wire sizes should be increased accordingly.
TABLE
Nominal
Pipe Size
Inches
3/4 1 1-1/4
* Note: Values shown in above table are for one direction only. The total length of pipe from chiller to coil
and return would be double the above table values. The above table applies to single unit installations only.
Figure 1
Polyethy ene Pipe Copper Pipe
Size 36
40' 150' 530'
Size 54
45' 140' 40'
145'
Allowable Distance* between Coil and Chiller
Size 36
35'
Size 54
360' 100'
SLEEPING
AVOID
OPEN
WINDOWS
QUARTERS
LIVING
AREA
Galvanized Pipe
Size 36
25' 90'
370'
AVOID
'ells"
GARAGE
Size 54
30 '
90'
GOOD
LOCATION
II. CONNECT CHILLED WATER LINES
A. MATERIALS
Refer to section on “Cold Weather Protection” at the end of this instruction.
1. Piping
Figure 3
b. Copper - satisfactory substitute.
c. Galvanized - satisfactory substitute.
2. Fittings
a. Nylon - use when possible. b. Brass - satisfactory substitute.
c. Galvanized - satisfactory substitute.

B. PIPE LENGTH AND DIAMETER

Table I shows maximum length of pipe of different diameters that can be used between the pump dis
charge and the coil inlet and still maintain mini
mum allowable (design) water flow rate.
1. Multiply table values by two to obtain the total
length of pipe from chiller to coil ond return.
2. Length is measured along the pipe path and therefore includes vertical distance between the water coil and the chiller.
a. Polyethylene Plastic Pipe - use medium density flexible pipe whose wall thickness approximates Schedule 40 pipe (Commercial Standard CS 197-60). Pipe must be virgin plastic. Do not use pipe manu factured from re-claimed plastic.
- 3 -
3. Lengths shown in Table I are based on using a total of eight elbows in the entire water line (chiller to coil and return). Lengths are predicated on the use of a Bryant matching water coil. For greater distances use larger pipe or add a pump.
EH 451
CLARIFICATION
On page 4 of this Instruction under Section III Electric Connections, item 3 should read;
3. Provide a fused disconnect switch within sight of and not more than 50 feet from the absorption unit.
FIL
C

CORRECTION

Paragraph 6 on page 4 under Electric Connections should read as follows:
6. Disconnect pump electrical lead at terminal 7 in control box before energizing unit when ready to check field wiring. Do not operate the pump dry.
Figure 6 on page 8 is NOT correct. Use the wiring diagram below instead of that on page

FOR EH 451

o
<
I
E
o
Ui
O
O)
c

C. INSULATION

Ill, ELECTRIC CONNECTIONS

1. Insulate supply and return lines separately.
2. Material should be of good quality and be
covered with a good vapor barrier. Armaflex or equivalent is recommended.
Wall thickness: 1/2" wall thickness - south of 40 ° N. latitude 3/8" wall thickness - north of 40° N. latitude
D. HEIGHT OF COIL
ABOVE ABSORPTION UNIT
Maximum vertical distance from chiller outlet to
top of coil is 22 feet for both sizes. For greater
heights, a greater pumping head is required. In creasing the pipe size will not help.

E. WATER COIL CONNECTIONS

1. If coil is located in warm air stream, do not
connect polyethylene pipe directly to coil. Connect a minimum of 24 inches copper or galvanized pipe to both the coil inlet and outlet. Then connect the plastic pipe to these nipples.
2. On installations where the outside piping
freezes and the coil is in a heated air stream, pre cautions must be taken to provide for water expan sion. The connecting polyethylene plastic pipe acts as an expansion vessel if there is enough foot age of this pipe in the heated space (space not subject to freezing). The following table shows the minimum lengths (total inlet and outlet) of
plastic piping of various diameters that are re quired for both sizes of coils to provide adequate expansion volume.
1. Make all electric connections in accordance with the National Electrical Code and any local ordinances or codes that might apply.
2. Provide a separate power supply for the air
conditioner.
3. Provide a fused disconnect switch within easy
reach of the absorption unit.
Size 36 - use 30 amp. Standard fuse or 15 amp.
fusetron.
Size 54 - use 35 amp. standard fuse or 20 amp.
fusetron.
4. The absorption unit is shipped fully wired from the factory. Connection of 115V power and low
voltage connection to the thermostat control are required in the field. Before proceeding, inspect factory wiring for loose connections which may have resulted during shipment.
5. Figure 6 is the Wiring Diagram. Do not fasten power leads to hot tubing since wire insulation could be damaged and a short circuit could result.
6. Disconnect pump electrical leads at terminals 6 and 7 in control box before energizing unit when ready to check field wiring. Do not operate the
pump dry.

IV. GAS CONNECTIONS

Consult local gas company before making any gas connections. In case of conflict with this instruc tion, local requirements should be followed.
Nominal Pipe Size
Inches
%
1
Vk
Length of Plastic Pipe
in Feet
Size 36 Size 54
24
15
56 35
8.5 20
6.5
14.5
If the total plastic chilled water line footage in the heated space is not as long as the minimum values shown in the table, tee a vertical pipe of sufficient volume into either of the coil connec tions to provide for expansion, or the line should be drained.
EH 451
Before selecting the size and type of pipe that is
to be used for installing the absorption unit, be
sure to check with local gas company for the
necessary information. The size of the gas pipe
to be used will depend upon the length of run and
the allowable pressure loss established by the utility.
The gas connection to the unit is made at the com bination regulator-shut-off. On the size 36 use a
V2" X 3" nipple and then a elbow. The supply
pipe enters the knockout on the other end of the unit and will then be lined Up for final connection if the nipple and elbow are used as described. On the size 54 use aVi" x 2 "nipple and then a^/i" x
reducing ell and 3/4 inch pipe.
- 4 -
A wrench-type shut-off valve should be installed in the gas line within sight of, and convenient to, the 451. Provide a ground joint union upstream of
the combination regular shut-off, and preferably outside the unit.
Install a drip leg trap in the gas supply riser lead ing to the unit. After gas pipe connections have been made, purge the lines and check for leakage. Use a soap and water solution or other such mater ial.
Never use matches, candles, flame or other source of ignition to check leakage.

PILOT

Light the pilot using the procedure outlined on the Lighting Instruction Plate attached to generator. The pilot flame should be soft blue in color. The flame should be of sufficient length to provide good impingment on the unimetal element of the Bryant pilot. Flame should extend upward between the carry-over ports of the two adjacent burners.
If the pilot flame does not have the appearance described above, it may be adjusted by means of the manual pilot shut-off valve which is equipped with an adjustable screw. Turn the handle to the full-open position and remove the screw cap on the valve handle, thus exposing the adjustable screw. Turn adjusting screw until flame has the desired appearance. Replace screw cap.

V. CHARGING THE SYSTEM WITH WATER

Caution: Do not run the pump dry. Freezing condL
tions will not damage the pump; however, do not attempt to operate the pump when chiller or chilled water lines are frozen.
1. Turn off main manual gas shut-off valve.
2. Remove the filler cap from water chiller tank.
3. Disconnect line at chiller inlet. (When install ing the chilled water lines, it is advisable to leave this connection open until lines have been flushed).
4. Fill the tank with tap water by inserting a garden hose into the filler tube about 12 inches and running water into the chiller until it gushes out around the hose. See Figure 4.
5. Start pump. Allow pump to operate until all
foreign matter has been flushed from the pipes. Continue to supply water to the tank during this cleaning period.
Note: If water does not circulate when the pump is started, air may be trapped in the pump. Bleed the air from pump through the 1/8" slotted head bleed valve located on top of the pump discharge. Open valve with screw driver. Close valve when the trapped air is removed and water appears.
6. Turn off pump and hose. Make pipe connection to chiller inlet.
7. Turn on hose and fill tank until water gushes out around hose. Remove hose and replace filler cap.
8. Start pump and while water is circulating, check for leaks throughout the chilled water system.
9. Stop pump and remove filler cap. Insert one end of a piece of water hose into the tank at least 12". Insert a clean plastic or metal funnel in the other end of the hose.
10. Start pump and pour carton of borax into funnel. Flush borax into chiller with water from water hose used for filling until tank over-flows. Remove hose and replace filler cap. The package of borax supplied is sufficient for chilled water systems containing up to 20 gallons of water. For systems
- 5-
EH 451
larger than 20 gallon capacity, add one-half (1/2) package for each additional 10 gallon capacity or fraction thereof. (Consult Bryant distributor for estimating chilled water circuit capacities.)
11. The system is now ready to operate.
Note: The condenser fan belt is factory set and
is self-adjusting. No field adjustment is necessary.
VI. CHECK OUT AND OPERATION
1. Be sure main manual gas valve is off. Light
pilot as described on instruction plate.
2. Set thermostat to “cool”; set thermostat fan switch to “auto”; set thermostat below room temperature.
3. Turn on main electric switch to unit.
4. Check indoor fan operation by turning thermo stat fan switch to “on” for continuous fan opera
tion. Move thermostat above room temperature and
observe that the indoor fan remains on.
5. To place the system in operation, open the main manual gas valve, replace all panels, and set the thermostat at the desired temperature.
To measure gas input, proceed as follows:
1. Adjust primary air if necessary.
2. Measure the gas input at the meter. Be sure all other gas appliances are turned off. Input at the burners may be increased or decreased slightly by adjustment of the regulator in the burner supply
line.
Caution: Prolonged operation of the unit should
not be attempted with the panel off. The unit may be run for short periods with the panel re moved.
VIII. BALANCE THE SYSTEM
After the unit is in operation and the input has been measured and adjusted to agree with the rating plate requirements, balance the system.
Any approved method of checking the air flow over the water coil may be utilized. Reference is made to the Bryant Service Manual on Gas Air Condi tioners for a review of standard methods.
High Temperature Cut-Off
The high temperature circuit includes a high tem perature control located on the front of the gen erator plus a high temperature relay (lockout relay) located in the control box. If the generator
becomes overheated the contacts in the high temp control open, causing the high temp relay to go into lockout position. The gas valve closes, the fans and pump stop, and they will not recycle until the lockout relay is reset. To reset lockout relay turn electric power off and then back on. Be sure
to locate and correct cause of high temp cut-out.
VII. ADJUST GAS INPUT
Gas input should agree with that shown on the rating plate of the unit. The burners are equipped with fixed orifices intended to give the correct gas input with a manifold pressure of 3" w.c., using 1030 BTU natural gas of 0.63 S.G. Before
lighting burners, inspect to be sure that they have not become dislodged or cocked during shipment and installation.
IX. PURGE NON-CONDENSIBLES
Purging is accomplished through valve A on inlet tank and Valve D on purge pot.
Operate unit for a minimum of 15 minutes. While still operating, proceed as follows:
1. Attach adapter and purge line to Valve A.
2. Run purge line to bucket of water.
3. Remove cap and open valve A about 1/8 to 1/4
turn.
4. If non-condensibles are present, bubbles will rise to the surface of the water in the bucket.
5. Leave Valve A open as long as bubbles rise to the surface of the water. When non-condensibles are removed the bubbles will cease as ammonia
will be absorbed into the water.
6. Close Valve A.
7. Open Valve D about 1/8 turn. Usually there will be some solution trapped in the valve body, and this solution will be released as soon as the valve is opened.
EH 451 - 6
8. If non-condensibles are present they will follow the initial surge of solution. When solution re appears in quantity, the non-condensibles trapped in the purge pot have been released.
HA RD FI TT IM G-M AX .2 .
AD AP TER
9. Close Valve D.
The installation should now be complete.

FREEZING WEATHER PROTECTION

1. GAS AIR CONDITIONER

The Gas Air Conditioner has built-in freeze pro tection sufficient to protect the chiller and pump plus a small amount of external hard (non-plastic) pipe as shown in Figure 5.

2. CHILLED WATER PIPES

If hard pipe is used (instead of plastic) for the
chilled water lines, be sure that adequate steps are taken to prevent these pipes from bursting
when they are subjected to freezing temperatures.

3. BRYANT COIL

If the Bryant coil used with the absorption unit is subject to freezing it must be protected. Consult Bryant distributor for recommended procedure to follow.
PL AS TIC P IP E
AD AP TER
HA RD FI TT IN G-M AX .2 ;
HA RD NI PP LE MA X. L ENG TH 4 "
PL AN VI EW
Figure 5

4. OPERATION AT FREEZING TEMPERATURES

If the air conditioning system is required to operate under freezing conditions, consult your Bryant Distributor for special procedures to follow.
-7
EH 451
m
cn
PILOT iWITCH
Figure 6 - Unit Wiring Diagram - All Gases
POWER SUPPLY
5826301
i
1 i
115 VOLTS
..„.„y
д
СП
w
K
■t^
cn
0 o
o
o
Y G R 0
o
¿
MODEL 451
TERMINAL BLOCK
o
FAN
REMOTE
MOTOR
FAN RELAY
1
o
c)
FAN
K
) OJ
LIMIT
cj) c
)
-o o
RELAY
o
TH
TY PI CAL S EL F G EN ER ATI NG F URN AC E CON TR OL
115V
-------
PILOT
Q
P P
r
TYPICAL
FURNACE WITH MULTI-SPEED TAPPED BLOWER
11 -
EH 451
Loading...