Installation Instructions
450D
Installation of the Model 450D Gas Air Conditioning
Absorption unit consists of the following steps:
I. Locate and mount absorption unit.
II. Connect chilled water lines.
III. Electrical connections.
IV. Gas connections.
V. Charge system with water.
VI. Check-out and Operation.
VII. Adjust gas input.
VIII. Balance system.
IX. Purge Non-Condensibles.
Each of the above steps is discussed in detail in this
instruction. Read entire instruction before starting in
stallation.
bPi|ont
I
ft
EPN 39450D1
Remove four shipping bolts holding absorption unit to
crate base before placing unit on permanent mounting
slab.
NOTE: Unit is shipped with condenser fan guard in
verted. Remove, place with convex side up and fasten.
I. LOCATE AND MOUNT^ABSORPTION UNIT
The absorption unit may be located at ground level'or
on the roof. Consult local codes for information con
cerning proximity to property lines, height above roof,
obstructions, etc.
A, MOUNTING BASE '
1. Use non-combustible materials.
2. Base should be large enough that unit will not
overhang.
3. Poured concrete slab, minimum 4” thick, recom
mended for ground installation. On roof installa
tions a metal plate is satisfactory. Leave 4” to
8” clearance between roof top and metal plate.
4. Mounting base should not obstruct drain holes
in base angle of unit. Drainage required to dis
pose of rain, melting snow, etc.
Certified in accordance cvith
A. G. A. APPROVED
B. CLEARANCES
See Figures 1 and 2 for typical locations.
1. Absorption unit should have a minimum clearance
of 2 feet on all sides from any adjacent obstruc
tion.
2. Avoid overhead obstruction. Place unit at least
2 feet from plumb line of any overhang.
3. Avoid locating the unit where hot condenser dis
charge air can impinge on nearby obstruction and
mix with the cooler inlet air. This is particularly
important when two units are placed side by side.
A.R.I. standard 2d0—58.
CERTIFICATION APPLIES
ONLY WHEN USED WITH
PROPER COMPONENTS AS
SPECIFIED BY MANUFAC
TURER.
EH 450-2
CANCELS: EH 450-1
EFFECTIVE 12/1/63
DIMENSIONS
RATINGS AND CAPACITIES
ELECTRICAL CONNECTION
WATER outlet'
O
GAS CONNECTION
SIZE
DIMENSIONS
MODEL
Cooling Capacity
Heat Input
Gas Connection Size
Condenser Air Delivery
Water Flow (Min. Required)
Max. Frictional Loss Handled by Chiller Pump
Max. Elevation of Coil Above Chiller
Condenser Fan Motor
115V, 60 Cy., 1 Phase
Pump
115V, 60 Cy., 1 Phase
Minimum Wire Size*
Refrigerant Type 717
Approximate Shipping Weight
*NOTE: Satisfactory where distance, measured along wire path, between unit and connection into main
panel does not exceed 100 ft. Where distances are longer, wire sizes should be increased ac
cordingly.
36
54 46-3/8
A
40-3/8 48 53
B
56
C D
60
5-5/16 15-1/2
7-1/16 18-3/8
Amount
E WATER INLET
1
1-1/4
36-450 D 54-450 D
BTUH 34,000 52,000
BTUH
INCHES
CFM
GPM 7.5
FT HEAD
FT 22 22
HP
HP
AWG 14 12
LB
LB
120,000
WATER OUTLET
1/2
4,500
23
1/3
1/8
24 42
1044 1544
1
1
180,000
3/4
6,700
11
20
1/2
1/8
717
EH 450
-2-
SLEEPING
AVOID
OPEN
WINDOWS
QTRS.
TABLE I . DISTANCE BETWEEN COIL AND CHILLER
LIVING
AREA
AVOID OVERHANG
Figure 2
□
AVOID
“ELLS"
GARAGE
7 PREVWUNG
WIND
GOOD
LOCATION
NOMINAL PIPE SIZE POLYETHYLENE
3/4
1
1-1/4
M/2
NOTES Values shown are for one direction only. Multiply by two to obtain the total length
of pipe from chiller to coil and return.
* Pipe lengths exceeding 75 feet may require additional chilled water additive. (See Section V,
this instruction.
II. CONNECT CHILLED WATER LINES
A. MATERIALS
Refer to section on “Cold Weather Protection” at the
end of this instruction.
1. Piping
a. Polyethylene Plastic Pipe - use medium density
flexible pipe whose wall thickness approximates
Schedule 40 pipe (Commercial Standard CS 197-
60). Pipe must be virgin plastic. Do not use
pipe manufactured from re-claimed plastic.
b. Copper - satisfactory substitute.
c. Galvanized - satisfactory substitute.
2. Fittings
a. Nylon - use when possible.
b. Brass - satisfactory substitute.
c. Galvanized - satisfactory substitute.
Feet
36 54
40
—
150 ^ 45
530 ^
145 *
1585 ^ 310 *
B. PIPE LENGTH AND DIAMETER
Table I shows maximum length of pipe of different
diameters that can be used between the pump dis
charge and the coil inlet and still maintain minimum
allowable (design) water flow rate.
1. Multiply table values by two to obtain the total
2. Length is measured along the pipe path and
3. Lengths shown in Table I are based on using a
COPPER
36
35
140 ^
360 ^
815a^
Feet
54 36 . 54
—
40
100^
205^
GALVANIZED
Feet
25
90 ^
—
30
370 ^ 90 ^
770 ^ 190 ^
length of pipe from chiller to coil and return.
therefore includes vertical distance between the
water coil and the chiller.
total of eight elbows in the entire water line
(chiller to coil and return). Lengths are predi
cated on the use of a Bryant matching water coil.
For greater distances use larger pipe or add a
pump.
EH 450
- 3 -