Bryant 396G User Manual

i nsta I lation i nstructions
COUNTERFLOW GAS-FIRED FORCED-AIR FURNACE
Before installing the fiimace, refer to "Procedure for Gas­Fired Furnaces” (packaged with the equipment) for informa tion concerning combustion, venting, piping, and other stan dard installation practices. Further reference is made to the ciurrent edition of the American National Standard Z223.1 National Fuel Gas Code.
Each furnace is shipped from the factory completely assem bled with multispeed direct-drive blower and wired ready for counterflow indoor heating installation only. All sizes feature a printed-circuit board control center with easy-to­read, low-voltage terminal strip to ensure proper connec tions.
The efficiency rating of the furnace is a product thermal efficiency rating determined under continuous operating conditions independent of any installed system.
CAUTION: Do not install furnace in a corrosive or contami
nated atmosphere. Make sure all combustion and circulating air requirements listed in "Procedure for Gas-Fired Fur naces” are adhered to, in addition to, all local codes and ordinances.
The design of the counterflow gas-fired furnace is A.G.A. cer
tified for installation on combustible flooring (with optional floor base), in alcoves, basements, closets, or utility rooms. This furnace line is mobile home, recreation vehicle, or outdoors.
TABLE i-CLEARANCES (In Inches)
Sizes
Sides—Single-Wall Vent
Type-B Double-Wall Vent
Back Top of Plenum Vent Connector—Single-Wall
Front—Combustion Air
Service
INTRODUCTION
not A.G.A. certified for installation in a
050 075 thru 150
1
0
1
1
0 0
1 1
Type-B Double-Wall
6 6 1 6 6
1
30 30
Cancels: 40396DP5-A
and 40396DP6-A
I ! '
I" r,
----- ! .- i
40396DP7-A
1/15/80
Ipip Í
A78593
Figure 1—Model 396G036075 With Optional
Vent Damper Installed
Installation comprises the following:
I. Inspection
II. Location, Ventilation, and Air for Combustion
III. Gas Piping
IV. Venting
All of the above steps are covered in general by the like-num bered sections of the "Procedure for Gas-Fired Furnaces” booklet packaged with the furnace; therefore, these Installa tion Instructions will contain only supplementary informa tion applicable to installing the furnace.
In addition, the following sections deal specifically with in stallation of the 396G:
V. Supply-Air Plenum Installation
VI. Electrical
VII. Sequence of Operation
VIII. Filter
IX. Startup and Adjustment
X. Care and Maintenance
For accessory installation details, refer to applicable in stallation literature.
RDP Company, Division of Carrier Corp.
V. SUPPLY-AIR PLENUM INSTALLATION
A. Installation on a concrete slab
1. See Figure 2 for dimensions and location of supply-air opening in furnace bottom.
2. Construct hole in floor per dimensions in Figure 3 eind Table IV.
3. Place plenum and furnace as shown in Figure 4.
B. Installation on a combustible floor
1. Read Installation Instructions packaged with combusti ble floor base.
2. Cut and frame hole in floor per dimensions in Table I of Installation Instructions packaged with combustible floor
base. If this requires cutting of a floor joist, tie ends of cut
joist into adjacent joists so that proper floor support will be
maintained.
3. Assemble and install combustible floor base per instruc tions packaged with base.
4. When completed, combustible floor base, plenum, and
furnace (or coil casing when used) should be installed as shown in Figure 6.
г/

TABLE ll-DIMENSIONS (in Inches)

ir
ф
пг
.Q..
Г'
KNOCKOUT
ДиХ GAS
INLET
A78595
Size 024050 14-3/16 000075 036075 000100 .
. 048100
000125 048125 060150

Figure 2—Dimensional Drawing

TABLE lil-RATINGS AND PERFORMANCE*

Size
024050 50,000 40,000 45-75 0.50 620 000075 036075 45-75 0.50 925 000100 100,000 80,000 048100 000125 125,000 100,000 70-100 0.20 048125 060150 150,000 120,000 55-85 0.50 1850
Input
Btuh
75,000 60,000 70-100 0.12 700
Bonnet
Capacity
Btuh
Temp
Rise
Range
70-100
60-90 0.50 990 60-90 0.50 1235
Heating Cooling
Ext Static
Pressure
0.20 870
Ft3/Min
1090
*The above ratings are certified for altitudes to 2000 ft. For elevations above 2000 ft, reduce ratings 4% for each 1000 ft above sea level.
A
IT-1/2
. 17-1/2
17-1/2­17-1/2
21 21 19-3/8
24-1/2
Ext Static
Pressure Ft3/Min
0.5
0.5 1255 1/3-SP
0.5 1630
0.5 1620
0.5
D
12-9/16
15-7/8 15-7/8 15-7/8 15-7/8 19-3/8
22-13/16
800
1/10-SP 146
1/5-SP 185
2075
E Vent
12-11/16
16- 4 16 16 5
16 19-1/2 19-1/2
23 6
Motor
HP&
Type
1/3-SP 127
1/5-SP 161
1/2-PSC 1/2-PSC
1/2-PSC 225
Approx
Ship.
Weight
155 168 186
4 4 5
5 5
HOLE IN
FLOOR
3
Figure 3 — Floor Opening for
Concrete Siab

TABLE IV —OPENING DIMENSIONS

Furnace Size 024050 13-1/8 19-5/8 000075, 036075,
000100, & 048100 000125 & 048125 19-7/8 19-5/8 20-15/16 060150
These dimensions apply when a Model 518A Evaporator Coil casing
is to be installed.
A В
16-7/16
23-7/16 19-5/8
Heat-Only Heat/Cool*
19-5/8
20-15/16 20-15/16
20-15/16
VI. ELECTRICAL CONNECTIONS A. Line-Voltage Wiring
IMPORTANT: Before proceeding with the electrical connec
tions, make certain that voltage, frequency, and phase cor respond to that specified on the unit rating plate. Also, check to be sure that the service provided by the utility is sufficient to handle the additional load imposed by this equipment. Re fer to the unit rating plate for equipment electrical require ments.
CAUTION: Do not connect aluminum wire between discon
nect switch and furnace. See Figure 8 for wiring diagram showing the proper field
high- and low-voltage wiring. Make all electrical connec tions in accordance with the National Electrical Code and any local codes or ordinances that might apply.
-2-
Figure 5—Combustible Floor Base
Set the thermostat heat anticipator at 0.5 for a furnace with a BDP Model 646A Gas Valve; 0.6 for a furnace with an Essex Model 242 Gas Valve; 0.2 when a Model 997A Vent Damper is installed — no matter which of these gas valves is used. If additional controls are connected in the thermostat circuit,
their amp draw must be added to this setting. A failure to make this setting will result in improper operation of the system.
For accurate reading, check the amp draw at the ther mostat with an ammeter. A failure to make this setting will result in improper operation of the system.
The room thermostat should be located where it will be in the natural circulation path of room air. Avoid locations where the thermostat would be exposed to cold-air infiltra tion, drafts from windows, doors, or other openings leading to the outside, or exposure to air currents from warm- or cold-air registers; or to exposure where the natural circula tion of the air is cut off—such as behind doors, above or below mantels, shelves, etc.
The thermostat should not be exposed to heat from nearby fireplaces, radios, televisions, lamps, or rays from the sun. Nor should the thermostat be mounted on a wall containing
pipes or warm-air ducts, or a flue or vent that could affect its operation and prevent it from properly controlling the room temperature. Any hole in the plaster or panel through which the wires pass from the thermostat should be adequately sealed with suitable material to prevent drafts from affect
ing the thermostat.
Figure 6—Furnace, Plenum, and
Base Installed on a Combustible Floor
Use a separate fused branch electrical circuit for this furnace. A disconnecting means must be located within sight of, and readily accessible to, the furnace. In some areas, the imit door switch may qualify as the disconnecting means.
WARNING: The furnace must be electrically grounded in
accordance with local codes, the National Electric Code, and ANSI C1-1978. Do not use gas piping as an electrical ground.
If line-voltage wiring to the unit is encased in a nonmetallic
sheath, connect the incoming ground wire to the grounding wire inside the furnace J-box. If metallic conduit is used, it will serve as the ground.
B. Low-Voltage Wiring
Make field low-voltage connections at the low-voltage ter
minal strip. See Figure 8.
NOTE; Use AWG No. 18 “color-coded” copper thermostat
wire for lengths up to 100 ft. Above 100 ft, use AWG No. 16
wire.
A79077
Figure 7—Printed-Circuit Control Center
Figure 8—Heating and Cooling Application Wiring Diagram
-3-
A78461
Loading...
+ 5 hidden pages