Bryant 349HAV Series, 349HAV036050, 349HAV036075, 349HAV048075, 349HAV048100 Installation, Start-up, And Operating Instructions Manual

...
Page 1
installation, start-up, and operating instructions
HORIZONTAL INDUCED-COMBUSTION GAS FURNACE SIZES 050—125, SERIES B
NOTE: Read the entire instruction manual before starting the installation.
This symbol → indicates a change since the last issue.
INDEX
Page
SAFETY CONSIDERATIONS ................................................1-2
Clearances From Combustible Materials.................................1
INTRODUCTION.......................................................................2-3
Dimensional Drawing...............................................................2
General......................................................................................3
Furnace Location Relative to Cooling Equipment..................3
Hazardous Locations.................................................................3
AIR FOR COMBUSTION AND VENTILATION...................3-5
General...................................................................................3-4
Unconfined Space.....................................................................4
Confined Space......................................................................4-5
Contaminated Combustion Air.................................................5
INSTALLATION........................................................................5-9
Duct Work Recommendations..................................................5
Horizontal Attic Installation.....................................................6
Horizontal Crawlspace Installation ..........................................6
Filter Arrangement....................................................................6
Gas Piping..............................................................................6-7
Reversing Procedure..............................................................7-9
ELECTRICAL CONNECTIONS.............................................9-11
115-v Wiring........................................................................9-11
Wiring Diagram......................................................................10
24-v Wiring.............................................................................11
Accessories..............................................................................11
General Venting Requirements.........................................11-12
Pre-Installation Vent System Inspection................................12
Removal of Existing Furnace from Common
Venting System..................................................................12
Metal Vent Installations..........................................................12
Masonry Chimney Installations..............................................12
Multistory Installations...........................................................12
Sidewall Venting Installations................................................12
SEQUENCE OF OPERATION...................................................13
Heating Mode..........................................................................13
Cooling Mode .........................................................................13
START-UP, ADJUSTMENT, AND SAFETY CHECK.......13-18
General....................................................................................13
Remove Shipping Bracket......................................................13
Purge Gas Lines......................................................................13
Operational Checkout .............................................................13
Adjustments .......................................................................14-17
Adjust Pilot Flame..................................................................14
Set Gas Input Rate ............................................................14-17
Set Temperature Rise..............................................................17
Set Blower Off Delay.............................................................17
Set Thermostat Heat Anticipator............................................17
Check Safety Controls.......................................................17-18
349HAV
Cancels: II 349H-50-4 II 349H-50-5
®
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified person­nel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
TABLE 1—ATTIC, CLOSET*, OR ALCOVE CLEARANCES
FROM COMBUSTIBLE MATERIALS (IN.)
UNIT SIZE 050, 075, 100, & 125
Sides 6 Back 6 Top of Plenum 2 Vent Connector 6 Front Casing 6† Front Service 30
* For closet installations, refer to Air for Combustion and Ventilation section. † Measured from end of inducer motor.
WARNING: Failure to comply with all of the above clearances will create a fire hazard.
→
Follow all safety codes. In the United States, follow all safety codes including the National Fuel Gas Code (NFGC) NFPA No. 54-1996/ANSI Z223.1-1996 and the Installation Standards, Warm Air Heating and Air Conditioning Systems (NFPA 90B) ANSI/NFPA 90B. In Canada, refer to the current edition of the National Standard of Canada CAN/CGA-B149.1- and .2-M95 Natural Gas and Propane Installation Codes (NSCNGPIC). Wear safety glasses and work gloves. Have fire extinguisher available during start-up and adjustment procedures and service calls.
Recognize safety information. This is the safety-alert symbol When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU­TION. These words are used with the safety-alert symbol. DAN­GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage.
ama
CANADIAN GAS ASSOCIATION
APPROVED
R
6-98
.
—1—
Page 2
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residen­tial construction practices. We require these instructions as a minimum for a safe installation.
INTRODUCTION
The design of the 349HAV Horizontal Induced-Combustion Gas Furnace is A.G.A./C.G.A. certified as a Category I furnace for natural and propane gases and for installation in alcoves, base­ments, crawlspaces, utility rooms, and attics. The design of the horizontal gas-fired furnace is A.G.A./C.G.A. certified for instal­lation on noncombustible floors. This furnace may be installed on combustible wood flooring, however, it may not be installed directly on carpeting, tile, or other combustible material other than wood. The design of this furnace line is not A.G.A. certified for installation in recreational vehicles, manufactured housing (mobile homes), or outdoors. The furnace is shipped as a packaged unit, complete with burners and controls, and requires a 115-v line voltage connection to junction box, a thermostat hook-up as shown in the wiring diagram, and a gas line connection. The furnace is shipped in the horizontal left configuration (for right-to-left airflow) but is easily converted to the horizontal right configuration (for left-to-right airflow). Refer to Reversing Procedure section for details. The furnace is designed to interface with split system cooling equipment (approved by UL) to provide year-round air condition­ing. The blower is sized for both heating and cooling, and the furnace control includes a cooling fan relay.
Before installing the furnace, refer to the current edition of the NFGC and the NFPA 90B. Canadian installations must be installed in accordance NSCNGPIC and all authorities having jurisdiction. For a copy of the NFGC NFPA54/Z223.1, contact International Approval Services U.S. Inc., 8501 E. Pleasant Valley Road, Cleveland, OH 44131 or National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269. For a copy of NFPA 90B, contact National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269.
Before installing furnace in Canada, refer to the current edition of the NSCNGPIC. Contact Standards Department of Canadian Gas Association, 55 Scarsdale Road, Don Mills, Ontario, Canada M3B 2R3. Canadian installations must be made in accordance with CAN/CGA-B149 Installation Codes and authorities having juris­diction.
→
Installations must comply with the regulations of the serving gas supplier and the local building, heating, plumbing, or other codes in effect in the area in which the installation is made. In the absence of local codes, the installation must conform with the NFGC, NFPA No. 54-1996/ANSI Z223.1-1996.
CAUTION: Application of this furnace should be in­doors with special attention given to vent sizing and material, gas input rate, air temperature rise, and unit sizing. Improper installation or misapplication of the furnace can require excessive servicing or cause prema­ture component failure.
(EXTEND BLOWER DOOR)
5
⁄8″
D ( NUMBER OF CELLS)
3 1⁄2″
1 3⁄4″
T-STAT
CONNECTION
1
⁄2-IN. GAS CONNECTION
A
19 1⁄2″
5
⁄16″
B
7
5 5⁄8″
(HIGH AIR FLOW UNITS ONLY)
2 1⁄2″
10″
⁄8″
26 5⁄8″
19 1⁄4″
7″
(2 PLACES)
7
⁄8-IN. ELECTRICAL
CONNECTION
28 7⁄8″
50″
C
4-IN. DIA VENT CONNECTION
18″
5
4 9⁄16″
6 5⁄16″
4 1⁄8″
⁄8″
1 7⁄8″
5
⁄16″
B
21 3⁄8″
23 1⁄8″
7
⁄8″
A
AIR FLOW
5 7⁄8″
DIMENSIONS (IN.)
UNIT DIMENSIONS
UNIT SIZE
Length
036050 50 13-1/2 23-1/8 11-5/8 21-3/8 Flush 2 112 036075 50 13-1/2 23-1/8 11-5/8 21-3/8 Flush 3 121 048075 50 13-1/2 23-1/8 11-5/8 21-3/8 1 3 125 048100 50 17 23-1/8 15-1/8 21-3/8 Flush 4 141 060100 50 17 23-1/8 15-1/8 21-3/8 1 4 149 060125 50 20-1/2 23-1/8 18-5/8 21-3/8 Flush 5 161
* High airflow units only.
Width
A
Height
DUCT SUPPLY
AND RETURN
OPENINGS
Width
B
Height C D
EXTENDED
BLOWER
DOOR*
NUMBER OF HEAT
EXCHANGERS
Fig. 1—Dimensional Drawing
A96068
NET
WEIGHT
(LB)
—2—
Page 3
This furnace is designed for a minimum continuous return-air temperature of 60°F db or intermittent operation down to 55°F db such as when used with a night setback thermostat. Return-air temperature must not exceed a maximum of 85°F db.
WARNING: Improper installation, adjustment, alter-
ation, service, maintenance, or use can cause carbon
monoxide poisoning, explosion, fire, electrical shock, or
other conditions which may cause personal injury or
property damage. Consult a qualified installer, service
agency, local gas supplier, your distributor, or your
branch for information or assistance. The qualified in-
staller or agency must use only factory-authorized and
listed kits or accessories when modifying this product.
Failure to follow this warning could result in electrical
shock, fire, personal injury, or death.
Locate furnace where available electrical and gas supplies meet the specifications on furnace rating plate.
Line contact is only permissible between lines formed by the intersection of furnace top and front and back sides and building joists, studs, or framing. (See Fig. 2.)
ROOF
LINE CONTACT ONLY PERMISSIBLE BETWEEN TOP CORNERS OF FURNACE AND BUILDING JOISTS, STUDS, OR FRAMING.
For accessory installation details, refer to the applicable installa­tion literature. NOTE: Remove all shipping brackets and materials before oper­ating furnace.
LOCATION
I. GENERAL
CAUTION: Do not install furnace in a corrosive or
contaminated atmosphere. Make sure all combustion and
circulating air requirements are followed, in addition to
all local codes and ordinances.
Do not use this furnace during construction when adhe-
sives, sealers, and/or new carpets are being installed. If
the furnace is required during construction, use clean
outside air for combustion and ventilation. Compounds of
chlorine and fluorine when burned with combustion air
form acids which cause corrosion of the heat exchangers
and metal vent system. Some of these compounds are
found in paneling and dry wall adhesives, paints, thin-
ners, masonry cleaning materials, and many other sol-
vents commonly used in the construction process. Exces-
sive exposure to contaminated combustion air will result
in safety and performance related problems.
This furnace may be located in an attic, basement, crawlspace, alcove, or suspended from the ceiling of a utility room or basement.
WARNING: Do not install the furnace on its back or
side. Safety control operation will be adversely affected.
Never connect return-air ducts to the back of the furnace.
Failure to follow this warning could result in a fire,
personal injury, or death.
KEEP ALL INSULATING MATERIAL CLEAR OF FURNACE. INSULATING MATERIAL MAY BE COMBUSTIBLE.
A96069
Fig. 2—Attic Installation Showing Point Contact
For attic installations, the passageway and servicing area adjacent to furnace should be floored.
If furnace is to be installed in a crawlspace, consult local codes. Use of a concrete pad 1 to 2 in. thick is recommended.
II. FURNACE LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with or on the downstream side of the furnace to avoid condensation in the heat exchanger. When installed parallel with a furnace, dampers or other means used to control the flow of air must prevent chilled air from entering the furnace. If the dampers are manually operated, they must be equipped with a means to prevent operation of either unit unless the damper is in the full-heat or full-cool position.
III. HAZARDOUS LOCATIONS
When furnace is installed in a residential garage, it must be installed so that the burners and ignition source are located a minimum of 18 in. above the floor. Furnace must be located or protected to avoid physical damage by vehicles.
When furnace is installed in a public garage, airplane hangar, or another building having a hazardous atmosphere, the unit must be installed in accordance with the requirements of the National Fire Protection Association, Inc.
WARNING: Do not place combustible material on fur­nace jacket. Failure to comply with this warning will cause an explosion.
When a furnace is installed so that the supply ducts carry air to areas outside the space containing the furnace, return air must also be handled by duct(s) sealed to furnace casing and terminating outside the space containing furnace to ensure there will not be a negative pressure condition within the equipment room or space. This furnace must be located so electrical components are pro­tected from water. Locate furnace close to the chimney/vent and as near the center of air distribution system as possible. The furnace should not be connected to an operating chimney that also serves a solid fuel burning appliance. Provide ample space for servicing and cleaning. Always comply with the minimum fire protection clearances shown on the unit rating plate and in Table 1. A clurance of at least 30 in. should be provided at front of unit for servicing.
WARNING: This furnace is not watertight and is not designed for outdoor installation. This furnace shall be installed in such a manner as to protect the electrical components from water. Outdoor installation would lead to a hazardous electrical condition and premature com­ponent failure.
AIR FOR COMBUSTION AND VENTILATION
I. GENERAL
Provisions for adequate combustion and ventilation air must be provided in accordance with Section 5.3, Air for Combustion and Ventilation, of the NFGC, or applicable provisions of local building codes.
—3—
Page 4
Canadian installations must be installed in accordance with the NSCNGPIC and all authorities having jurisdiction.
WARNING: Do not block combustion air openings in furnace. Any blockage will result in improper combustion and may result in a fire hazard or unsafe condition.
CAUTION: Air for combustion must not be contami­nated by halogen compounds which include fluoride, chloride, bromide, and iodide. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products. Excessive exposure to contaminated combustion air will result in safety and performance related problems.
CAUTION: The operation of exhaust fans, kitchen ven­tilation fans, clothes dryers, or fireplaces could create a negative pressure condition at the furnace. Make-up air must be provided for the ventilation devices, in addition to that required by the furnace.
The furnace shall be installed in a location in which the facilities for ventilation permit satisfactory combustion of gas, proper venting, and maintenance of ambient temperature at safe limits under normal conditions of use. The furnace shall be located so as not to interfere with proper circulation of air.
In addition to air needed for combustion, process air must be provided as required for cooling of equipment or material, con­trolling dew point, heating, drying, oxidation or dilution, safety exhaust, and odor control. Air must be supplied for ventilation, including all air required for comfort and proper working condi­tions for personnel.
CAUTION: Whenever this furnace is installed in an area along with 1 or more gas appliances, the total Btuh input of all appliances must be included when determining the free area requirements for combustion and ventilation openings.
The requirements for combustion and ventilation air depend upon whether the furnace is located in a confined or unconfined space.
II. UNCONFINED SPACE
An unconfined space must have at least 50 cu ft for each 1000 Btuh of input for all appliances such as furnaces, clothes dryer, water heaters, etc. in that space. Rooms communicating with the space in which the appliances are installed through openings not furnished with doors are considered a part of the unconfined space.
If the unconfined space is of unusually tight construction, air for combustion and ventilation MUST come from either the outdoors or spaces freely communicating with the outdoors. Combustion and ventilation openings must be sized the same as for a confined
space. A minimum opening with a total of at least 1 sq in. per 5000 Btuh of total input rating for all equipment must be provided. Return air must not be taken from the room unless an equal or greater amount of air is supplied to the room.
III. CONFINED SPACE
A confined space has less than 50 cu ft for each 1000 Btuh of the total input ratings of all appliances installed in that space.
A confined space MUST have 2 permanent openings, 1 within 12 in. of the ceiling and the other within 12 in. of the floor.
NOTE: In determining the free area of an opening, the blocking effect of the louvers, grilles, and screens must be considered. If the free area of a louver or grille design is unknown, assume that wood louvers have a 20 percent free area and metal louvers or grilles have a 60 percent free area. Screens, when used, must not be smaller than 1/4-in. mesh. Louvers and grilles must be constructed so they cannot be closed.
A. All Air from Inside the Structure:
1. Each opening MUST have at least 1 sq in. of free area per 1000 Btuh of the total input for all equipment within the confined space, but not less than 100 sq in. per opening.
For Example:
349HAV FURNACE
INPUT BTUH
50,000 100
75,000 100 100,000 100 125,000 125
FREE AREA PER
OPENING (SQ IN.)
2. If the building is of unusually tight construction, in addition to the 2 permanent openings that freely communicate with an unconfined space, a permanent opening directly commu­nicating with the outdoors should be provided. This opening should have a minimum free area of 1 sq in. per 5000 Btuh of total input rating for all equipment in the enclosure.
3. If the furnace is installed on a raised platform to provide a return-air plenum, and return air is taken directly from the hallway or space adjacent to the furnace, all air for combustion must come from outdoors.
B. All Air from Outdoors:
1. If combustion air is taken from outdoors through vertical ducts, the openings and ducts MUST have at least 1 sq in. of free area per 4000 Btuh of the total input for all equipment within the confined space.
For Example:
349HAV FURNACE
INPUT BTUH
50,000 12.5 4
75,000 18.8 5 100,000 25.0 6 125,000 31.3 7
FREE AREA PER
OPENING (SQ IN.)
ROUND PIPE
(IN. DIA)
2. If combustion air is taken from the outdoors through horizontal ducts, the openings and ducts MUST have at least 1 sq in. of free area per 2000 Btuh of the total input for all equipment within the confined space.
—4—
Page 5
For Example:
349HAV FURNACE
INPUT BTUH
50,000 25.0 6
75,000 37.5 7 100,000 50.0 8 125,000 62.5 9
FREE AREA PER
OPENING (SQ IN.)
ROUND PIPE
(IN. DIA)
When ducts are used, they must be of the same cross-sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular ducts must not be less than 3 in.
IV. CONTAMINATED COMBUSTION AIR
Contaminated combustion air must be avoided in order not to adversely affect the long term life of furnace, especially heat exchanger and burners.
The recommended source of combustion air is to use the outdoor air supply. Use of indoor air in most applications is acceptable as long as there is no exposure to the types of installation or substances listed below and all provisions for indoor combustion air meet the requirements for combustion air supply indicated in the NFGC Section 5.3; CAN1-B149 Installation Codes; and/or any applicable local codes.
A. Installations Requiring Outdoor Combustion Air
1. The following types of installations require OUTDOOR AIR for combustion due to chemical exposures:
a. Commercial buildings b. Buildings with indoor pools c. Furnaces installed in laundry rooms d. Furnaces installed in hobby or craft rooms e. Furnaces installed near chemical storage areas
2. Exposure to the following substances in the combustion air supply also require OUTDOOR AIR for combustion:
a. Permanent wave solutions b. Chlorinated waxes or cleaners c. Chlorine based swimming pool chemicals d. Water softening chemicals e. De-icing salts or chemicals f. Carbon tetrachloride g. Halogen-type refrigerants h. Cleaning solvents (such as perchloroethylene) i. Printing inks, paint removers, varnishes, etc. j. Hydrochloric acid k. Cements and glues l. Anti-static fabric softeners for clothes dryers m. Masonry acid washing materials
The following recommendations should be followed when install­ing duct work:
1. Install locking type dampers in all branches of individual ducts to balance out system. Dampers should be adjusted to impose proper static at outlet of furnace.
2. Noncombustible flexible duct connectors are recommended to connect both supply- and return-air ducts to furnace.
3. In cases where return-air grille is located close to fan inlet, there should be at least one 90° air turn between fan and inlet grille. Further reduction in sound can be accomplished by installing acoustical air turning vanes and/or lining inside of duct with acoustical material.
4. It is recommended that outlet duct be provided with a removable access panel. The opening shall be accessible when furnace is installed and shall be of such a size that heat exchanger can be viewed for possible openings using light assistance or so a probe can be inserted for sampling air stream. The access panel shall be designed so as to prevent leaks when locked in position. If an air conditioning coil is installed, access panel to coil can be used for this purpose.
CAUTION: Air openings, intake and outlet pipes, return-air grilles, and warm air registers must not be obstructed.
WARNING: When supply ducts carry air circulated by furnace to areas outside spaces containing furnace, return air shall also be handled by a duct sealed to furnace casing and terminating outside space containing furnace. Incorrect duct work termination and sealing will create a hazardous condition which could lead to bodily harm.
5. When installing furnace with cooling equipment for year­round operation, the following recommendations must be followed for series or parallel airflow:
a. In series airflow applications, coil is mounted after
furnace in an enclosure in supply-air stream. The furnace blower is used for both heating and cooling airflow.
WARNING: The coil MUST be installed on air dis­charge side of furnace. Under no circumstances should airflow be such that cooled, conditioned air can pass over furnace heat exchanger. This will cause condensation in heat exchanger and possible failure of heat exchanger which could lead to a fire hazard and/or a hazardous condition which may lead to bodily harm. Heat exchanger failure due to improper installation may not be covered by warranty.
INSTALLATION I. DUCT WORK RECOMMENDATIONS IMPORTANT: This furnace is equipped with a metal heat
exchanger shipping bracket which must be removed before install­ing furnace. The No. 10 screws which fasten bracket to furnace will interfere with attachment of outlet duct if not removed. Remove bracket by removing No. 10 screws located on bottom panel duct supply flange, rotating bracket forward and lifting out.
The proper sizing of warm air ducts is necessary to ensure satisfactory furnace operation. Duct work should be in accordance with the latest editions of U.S. NFPA-90A (Air Conditioning Systems) and NFPA-90B (Warm Air Heating and Air Condition­ing Systems) or Canadian equivalent.
b. In parallel airflow installation, dampers must be pro-
vided to direct air over furnace heat exchanger when heat is desired and over cooling coil when cooling is desired.
IMPORTANT: The dampers should be adequate to prevent cooled air from entering furnace. If manually operated, dampers must be equipped with means to prevent operation of either cooling unit or furnace unless damper is in full cool or full heat position.
—5—
Page 6
SHEET
30-IN. MIN WORK AREA
METAL
Fig. 3—Typical Attic Installation
24″
24″
A96070
II. HORIZONTAL ATTIC INSTALLATION
The furnace can be installed horizontally for either left- or right-side supply. See Fig. 3 for a typical attic installation and Reversing Procedure section for reversing airflow direction.
CAUTION: In attic installations, it is necessary to keep insulation at least 12 in. away from any furnace opening. Some types of insulating materials are combustible.
1. Construct a working platform on location where all required furnace clearances are met. (See Table 1 and Fig. 3.)
2. Position furnace in desired location.
3. Connect gas supply pipe. See Fig. 4 for typical gas piping.
4. Connect supply- and return-air ducts.
5. Install 24- X 24-in. sheet metal shield on platform in front of controls as shown in Fig. 3.
III. HORIZONTAL CRAWLSPACE INSTALLATION
The furnace can be installed horizontally for either left- or right-side supply. In a crawlspace, the furnace can either be hung from floor joists or installed on suitable blocks or a pad. The furnace can be suspended using steel pipe straps around each end of furnace. These straps should be attached to furnace with sheet metal screws and to floor joists with lag bolts. A framed assembly of angle iron suspended with all-thread rod of suitable diameter may be used to support the length of furnace. Refer to Fig. 1 for size and weight of furnace. Care must be taken to allow for blower door access.
The horizontal crawlspace installation is very similar to the attic. Refer to Horizontal Attic Installation section, items 2, 3, 4, and 5. A 24- X 24-in. sheet metal shield must be installed above the controls for crawlspace installations. Extend sheet metal shield over furnace top far enough to cover gas pipe entry hole.
IV. FILTER ARRANGEMENT
CAUTION: Never operate the unit without a filter or
with the filter removed. Failure to follow this caution can result in a fire, personal injury, or death.
A factory-supplied filter and wire filter retainer are shipped with furnace. After return-air duct has been connected to furnace, install filter in blower compartment, just ahead of return-air plenum, and secure it with wire filter retainer. The cross-mesh binding side of filter should face blower. Refer to Table 2 for filter sizes.
TABLE 2—FILTER SIZE (IN.)
UNIT SIZE FILTER SIZE
036050 13X23 036075 13X23 048075 13X23 048100 16-1/2 X 23 060100 16-1/2 X 23 060125 20X23
V. GAS PIPING
Gas piping must be installed in accordance with national and local codes. Refer to the current edition of the NFGC.
Canadian installations must be installed in accordance with the NSCNGPIC and all authorities having jurisdiction.
Gas piping shall be of such size and so installed as to provide a supply of gas sufficient to meet maximum demands without undue loss of pressure between gas meter and furnace. It is recommended that the gas supply line be a separate line running directly from meter to furnace, unless existing gas line is of ample capacity. Refer to Table 3 for recommended gas pipe sizing. Risers must be used to connect to furnace and to meter.
Support all piping with appropriate straps, hangers, etc. Use a minimum of 1 hanger every 72 in.
Joint compounds (pipe dope) should be applied sparingly and only to male threads of joints. This pipe dope must be resistant to the action of propane gas.
—6—
Page 7
TABLE 3—MAXIMUM CAPACITY OF PIPE*
NOMINAL
IRON
PIPE SIZE
(IN.)
1/2 0.622 175 120 97 82 73 3/4 0.824 360 250 200 170 151
1 1.049 680 465 375 320 285 1-1/4 1.380 1400 950 770 660 580 1-1/2 1.610 2100 1460 1180 1993 900
*Cu ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table 10-2 NFPA 54-1996.
INTERNAL
DIAMETER (IN.)
LENGTH OF PIPE (FT)
10 20 30 40 50
NOTE: In order to make proper adjustments, minimum and maximum gas supply pressure limits shown on rating plate must not be exceeded.
Install a sediment trap in riser leading to furnace. The trap can be installed by connecting a tee to riser leading to furnace, so that the straight-through section of tee is vertical.
Then connect a capped nipple into lower end of tee. The capped nipple should extend below the level of gas controls. Place a ground joint union between gas control manifold and manual gas shutoff valve. (See Fig. 4.)
Piping should be pressure tested in accordance with local and national plumbing and gas codes before furnace has been attached. If test pressure exceeds 0.5 psig (14-in. wc), the gas supply pipe must be disconnected from furnace and capped before pressure test. If test pressure is equal to or less than 0.5 psig (14-in. wc), close manual shutoff valve located on gas valve before pressure test. It is recommended that the ground joint union be loosened before pressure testing.
CAUTION: Use a backup wrench when connecting the gas pipe to the furnace to avoid damaging gas controls.
After all connections have been made, purge the lines and check for leakage.
WARNING: Never purge a line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for the purpose of checking leakage. Use a soap-and-water solution to check for leakage. Failure to follow this warning could result in a fire, explosion, personal injury, or death.
VI. REVERSING PROCEDURE
GAS
SUPPLY
MANUAL
SHUTOFF
VALVE
SEDIMENT
TRAP
THIS DRIP LEG MUST BE
INSTALLED WITH THE PIPE
CAP A MINIMUM OF 1 IN.
FROM FLOOR TO PERMIT
REMOVAL
UNION
A96071
Fig. 4—Typical Gas Piping
CAUTION: If a flexible connector is required or al-
lowed by the authority having jurisdiction, black iron pipe shall be installed at the gas valve and extend a minimum of 2 in. outside the furnace casing.
An accessible manual shutoff valve MUST be installed upstream of furnace gas controls and within 72 in. of furnace. A 1/8-in. NPT plugged tapping, accessible for test gage connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual shutoff valve. (The manifold pressure tap on gas control meets this requirement.)
WARNING: Use the proper length of pipes to avoid stress on the gas control manifold. A failure to follow this warning could result in a gas leak resulting in a fire, explosion, personal injury, or death.
Before any system of gas piping is finally put into service, it should be carefully tested to determine if it is gas tight. The piping must stand a pressure of 6 in. of mercury for a period of 10 minutes or as required by local authority.
WARNING: Before proceeding with field reversal, en­sure that all electrical power is turned off and that all gas piping is shut off and disconnected from the furnace. Failure to do so could result in an extremely hazardous condition and bodily harm.
This furnace may be field reversed allowing for a horizontal right configuration (left-to-right airflow) instead of the factory posi­tioned horizontal left configuration (right-to-left airflow). (See Fig.
5.) Field reversal is accomplished in a convenient 3-step process.
1. Invert furnace so top panel is down.
2. Adjust manifold and burner opening plate.
3. Wire alternate limit switch.
A. Invert The Furnace
1. Carefully flip furnace on its top panel. Care should be taken not to drop unit or let it rest on 1 of its ends.
2. Controls should now appear as in right-hand view of Fig. 5.
B. Adjust Manifold and Burner Opening Plate
1. Remove front and back burner removal covers located on front and rear center panels.
2. Cut wire tie securing violet-colored rollout switch wires and ignition wire to manifold assembly.
3. Disconnect all wires from gas valve.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
4. Remove both manifold retention places from burner box and remove burner/manifold assembly. While removing burner/manifold assembly, disconnect violet-colored rollout switch wires from rollout switch. (See Fig. 6.)
5. On burner/manifold assembly, remove 2 screws that fasten rollout switch bracket to rollout switch base bracket. (See Fig. 7.)
—7—
Page 8
ALTERNATE LIMIT SWITCH
BLOWER
DOOR
BLOWER
DOOR
ALTERNATE
LIMIT
SWITCH
CONTROL LAYOUT (AS SHIPPED)
Fig. 5—Control Layout for Reversal
Fig. 6—Removing Burner/Manifold Assembly
SWITCH BRACKET
CONTROL LAYOUT (FIELD REVERSED)
A91387
A96073
REMOVE
BASE BRACKET
A92306
Fig. 7—Rollout Switch Assembly
6. With rollout switch base bracket still attached to burner/manifold assembly, turn assembly over so that pilot burner is on top.
7. Place rollout switch bracket on rollout switch base so face of switch is oriented toward heat exchanger.
8. Fasten bracket to base with screws removed in item 5. (See Fig. 8.)
9. Remove burner opening inlet plate from inside burner box and reinstall in burner box with word TOP (stamped on part) in up position. (See Fig. 9.)
10. Replace manifold retention plate on side of furnace opposite controls.
11. Before installing manifold, reconnect violet-colored rollout switch wires to rollout switch.
12. Install burner/manifold assembly making sure manifold bracket slides under manifold retention plate.
A96074
Fig. 8—Reattaching Rollout Switch Bracket
A96075
Fig. 9—Reversing Burner Opening Inlet Plate
13. Install manifold retention plate nearest gas valve. The burner/manifold assembly should now be firmly attached to furnace.
14. Reconnect wires to gas valve. Refer to furnace wiring diagram.
—8—
Page 9
15. Secure gas valve wires to manifold assembly with wire tie.
16. Replace burner removal covers on respective sides of furnace.
17. Remove front blower door and reinstall so instructional labels are rightside up.
NOTE: On high airflow models (75,000 and 100,000 Btuh), the front and rear blower doors must be interchanged so that the instructional labels are rightside up on both sides of furnace. Move blower door knob to new front blower door.
C. Wire Alternate Limit Switch
1. Disconnect wires from limit switch located on front center panel and reconnect wires to alternate limit switch on right front panel. (See right-hand view of Fig. 5.)
2. Replace control box cover.
CAUTION: Do not connect aluminum wire between the disconnect switch and the furnace. Use only copper wire.
Make all electrical connections in accordance with the National Electric Code ANSI/NFPA 70-1996 and any local codes or ordinances that might apply.
For Canadian installations, all electrical connections must be made in accordance with CSA C22.1 Canadian Electrical Code, or authorities having jurisdiction.
When replacing any original wiring, use only 105°C, AWG No. 16 copper wire.
→
Use a separate, fused branch electrical circuit containing a properly sized fuse or circuit breaker for this furnace. See Table 4 for wire size and specifications. A disconnecting means must be located within sight of and readily accessible to the furnace.
WARNING: Limit switch wires MUST be moved to the alternate limit switch when reversing the furnace to ensure safe operation. Failure to follow this warning may result in a hazardous operating condition.
ELECTRICAL CONNECTIONS
See Fig. 10 for a wiring diagram showing the proper field 115- and 24-v wiring connections. Check all electrical connections (both factory and field) for tightness. In all instances, wiring to be done and any replacement wire shall conform with the temperature limitation for Type T wire (63°F/35°C rise).
I. 115-V WIRING
Before proceeding with electrical connections, make certain that voltage, frequency, and phase correspond to that specified on unit rating plate. Also, check to be sure that service provided by utility is sufficient to handle load imposed by this equipment. Refer to rating plate or to Table 4 for equipment electrical specifications.
NOTE 4
115-V
SINGLE
PHASE
GND
115-V
FIELD-SUPPLIED
DISCONNECT
FIVE
WIRE
THREE-WIRE
HEATING
ONLY
GND
24-V
TERMINAL
BLOCK
WRCGY
W
R
G
C Y
WARNING: The cabinet must have an uninterrupted or unbroken ground according to National Electrical Code, ANSI/NFPA 70-1996, Canadian Electrical Code, CSA C22.1, or local codes to minimize personal injury if an electrical fault should occur. This ground may consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in an electrical shock, fire, or death.
NOTE: Proper polarity must be maintained for 115-v wiring for ignition control to function properly. Connect "hot" wire H and "ground" wire G as shown in Fig. 11.
CAUTION: If manual disconnect switch is to be mounted on the furnace, select a location where a drill or fastener will not contact electrical or gas components.
FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-, 208/230-, 460-V WIRING
THERMOSTAT TERMINALS
GND
CONDENSING
UNIT
TWO WIRE
FIELD-SUPPLIED DISCONNECT
208/230- OR 460-V THREE PHASE
GNDGND
208/230-V SINGLE PHASE
GND
NOTE :
→ Fig. 10—Heating and Cooling Application Wiring Diagram
1. Connect Y-terminal as shown for proper cooling operation.
2. If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.
3. Proper polarity must be maintained for 115-v wiring.
4. Some thermostats require a "C" terminal connection as shown.
A98302
—9—
Page 10
PRINTED CIRCUIT
LINE V
BOARD WIRINGBKBL
24V LINE V
FACTORY WIRING
24V LINE V
FIELD WIRING
24V
ORANGE WIRE NUT GROUND
UNUSED MOTOR
LEAD
UNUSED MOTOR
LEAD
LEGEND
CONTINUOUS LOW SPEED FAN OPTIONS
CONSTANT
HEAT
COOL
CONSTANT
HEAT COOL
CONTINUOUS LOW SPEED FAN WITH
OPTIONAL INTERUPT FAN SWITCH
CONSTANT
HEAT
COOL
CONSTANT
HEAT COOL
BR GR OR RD RD/BK VI WH YL
FAN SWITCH
FAN SWITCH
BLACK BLUE BROWN GREEN ORANGE RED RED/BLACK STRIPE VIOLET WHITE YELLOW
JUMPER
LOW MED
HIGH
LOW MED HIGH
LOW MED HIGH
LOW MED HIGH
LOW SPEED
HEAT CONNECTION
MEDIUM SPEED
HEAT CONNECTION
LOW SPEED
HEAT CONNECTION
MEDIUM SPEED
HEAT CONNECTION
L
LIMIT
P
PRESSURE SWITCH
ROS
ROLL OUT SWITCH*
BI
BLOWER INTERLOCK
CU
CONDENSING UNIT MANUAL RESET
*
T
TRANSFORMER
F1
LOW VOLT. FUSE
N2
N2
N2
N2
TSTAT24V
GNDFT
NOTES:
1. Make field power supply connections to black and white wires capped with orange wire nuts.
2. WARNING---unit must be grounded. Wiring must conform to NEC and local codes.
3. If any of the original wire, as supplied with the furnace, must be replaced, it must be replaced with wiring material having a temperature rating of at least 105°C and be a minimum of 16 gage AWG copper strand wire.
4. Connect required motor lead to heat terminal on circuit board to deliver a temperature rise within the range specified on the rating label. Connect unused leads to the unused motor leads.
5. Set the heat anticipator on the thermostat at .40 amps.
6. Low voltage fuse 5 amp automotive type littlefuse 257005 or buss ATCS.
7. Both EAC and HUM terminals are 115v.
ROS
N.O.
PRESSURE SW.
CN23-3
COM
PS1 PS2 W1
N.C.
CN23-5
SV9501 HOT SURFACE PILOT
IGNITION SYSTEM CONTROL
CN23-2
CONTROL
LIMIT
CN23-1
X
24VAC
TRANSFORMER
CONDENSING
C
S2
K3
(115VAC)
N4
D1
N3
CN23-6
ST9120C2010 ELECTRONIC
FAN TIMER
W
G
C
R
Y
UNIT
TSTAT
GND
K2
COOL
INDUCER
MOTOR
S1
BI
GND
K1K2
100, 125
HEAT
50, 75
MED
CIRCULATION
LOW
HI
FAN
N2
N1
L1(H)
(DISCONNECT ON HOT LEG)
L2(N)115 VAC 1Ø 60 HZ POWER SUPPLY
POWER SUPPLY 115 VAC 1 PH 60 HZ (DISCONNECT ON HOT LEG)
L2 (N)
L1 (H)
50, 75K INPUT
100, 125K INPUT
71
72
W
N
T
I
1 2
Honeywell
SEE NOTE 7
CU
C
GYW
R
ST9120C-16
RD
WYGR
HORIZONTAL GAS FURNACE WITH HONEYWELL ST9120C FAN TIMER & SV9501 SMART VALVE
FACTORY SET
HEATING SPEED
50 & 75K INPUTS-LOW (L)
100 & 125K INPUTS-MEDIUM (M)
GND
WH
BI
12
S
D1
HUM EAC N N
UNUSED
MOTOR
LEADS
N
1
NEUTRAL
CIR BLWR
CONT
COOL
HEAT
F1
4C32
GND
1
XFMR
X
SEC
SEE NOTE 6
RD
BR
→ Fig. 11—Wiring Diagram
321
6
54
ENLARGED TOP VIEW 6-PIN PLUG (CN23)
INDOOR BLOWER & MOTOR
BK
BL
RD/BK WH
YL
OR
BR
BR
CAP.
C
L
H
M
43
21
WH
SV9501
BL
L
YL
VI
—10—
BK
PILOT
12 12 12 12
60 SEC
90 SEC 120 SEC 150 SEC
DELAY OFF DIP SWITCH SETTINGS
INDUCER BLOWER
BK
BL
24V COM
24V PRESS. SW
24V HOT
OUTPUT
EFT
VI
P
ROS
*
VI
A98303
Page 11
→ TABLE 4—ELECTRICAL DATA
UNIT SIZE
HERTZ—
PHASE
036050 115—60—1 127 104 9.3 14 30 15 036075 115—60—1 127 104 9.9 14 28 15 048075 115—60—1 127 104 11.3 14 25 15 048100 115—60—1 127 104 9.9 14 28 15 060100 115—60—1 127 104 13.1 12 34 20 060125 115—60—1 127 104 11.3 14 25 15
* Permissible limits of the voltage range at which the unit will operate satisfactorily. † Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop. ‡ Time-delay type is recommended.
VOLTS—
OPERATING
VOLTAGE RANGE
Max* Min*
MAX UNIT
AMPS
MIN
WIRE
SIZE
MAX WIRE
LENGTH†
(FT)
MAX FUSE
OR CIRCUIT
BREAKER‡ AMPS
II. 24-V WIRING
Make field 24-v thermostat connections at the 24-v terminal block. Connect Y terminal as shown in Fig. 10 for proper cooling operation. The 24-v control board is marked for easy connection of field wiring. (See Fig. 12.)
3
1
S
T
W
I
N
DI 1
S
2 HUM EAC
SPEED
MOTOR
UNUSED
UP
N
LEADS
NEUTRAL
CIR
NN
CY
234 C
BLWR
COOL
HEAT
CONT
CG
YW R
XX
SEC
XFMR
5
A96103
Fig. 12—Control Board
NOTE: Use AWG No. 18 color coded copper thermostat wire for
lengths up to 100 ft. For wire lengths over 100 ft, use AWG No. 16 wire.
III. ACCESSORIES
Install accessories per manufacturer’s instructions. Other than wiring for thermostat, a minimum of type T wire (63°F/35°C rise) must be used.
1. Electronic Air Cleaner (EAC) Two 1/4-in. quick-connect terminals marked EAC and N
are provided for EAC connection. (See Fig. 12.) These terminals are energized with 115v (0.5-amp maximum) during blower motor operation.
2. Humidifier (HUM) Two 1/4-in. quick-connect terminals marked HUM and N
are provided for 115-v humidifier connection. (See Fig. 12.) These terminals are energized with 115v (0.5-amp maxi­mum) during any call for heat.
Cycle test furnace and accessories twice to ensure proper opera­tion.
VENTING
I. GENERAL VENTING REQUIREMENTS
→
Venting for furnace should be to the outside and in accordance with local codes or requirements of local utility. In the absence of local codes, venting should conform to the NFGC Part 7 or CAN/CGA-B149 Installation Codes Section 7, the vent manufac­turer’s Installation Instructions, and the A.G.A./GAMA Venting Tables supplied with furnace.
These furnaces are equipped with induced-combustion blowers and are classified as Category I forced air furnaces in accordance with ANSI/A.G.A. Z21.47 and C.G.A. 2.3 Central Furnace Stan­dards. Category I furnaces use non-positive, non-condensing vent systems, and may be connected to lined masonry chimneys which have been sized and installed per the enclosed procedures. Cat­egory I furnaces can not be vented into a vent system with any Category II, III, or IV appliance. It must be vented vertically or nearly vertically, unless installed with a listed mechanical venter in accordance with horizontal venting instructions in the Horizontal Venting section below. A Category I furnace must not be con­nected to any portion of a mechanical draft system operating under positive pressure.
Venting of these furnaces into a lined masonry chimney could form flue gas condensate due to cold surfaces and oversizing. If condensate is present in the masonry chimney, a drain must be provided to prevent condensate flow into the vent connector and furnace. (Refer to the NFGC, Section 7.9 for additional informa­tion on condensate drains.) Field experience on induced­combustion furnaces has shown that venting through a properly sized Type B-1 vent significantly reduces vent condensation. Condensate is acidic and could corrode vent materials. Therefore, the manufacturer suggests (but does not require) that these furnaces be connected to vent systems constructed of Type B-1 vent material.
The vent must be terminated with a listed vent cap or roof assembly. This venting must be installed in accordance with the vent manufacturer’s Installation Instructions and be in accordance with all local and/or national codes.
The following requirements are provided for a safe venting system:
1. Be sure chimney flue is clear of any dirt or debris.
2. Be sure chimney is not servicing an open fireplace.
3. Never reduce pipe size below outlet size of furnace without checking the NFGC Venting Tables supplied with furnace.
4. All pipe should be supported using proper clamps and/or straps. These supports should be at least every 4 ft.
5. All horizontal runs of pipe should slope upward at least 1/4 in. per ft from furnace to vent terminal.
—11—
Page 12
6. All runs of pipe should be as short as possible with as few turns as possible.
7. Seams should be tightly joined and checked for leaks.
8. The flue pipe must not extend into chimney but be flush with inside wall.
9. The chimney or vent pipe must extend at least 3 ft above the highest point where it passes through a roof of a building and at least 2 ft higher than any portion of a building within a horizontal distance of 10 ft. It shall also extend at least 5 ft. above highest connected equipment flue collar.
II. PRE-INSTALLATION VENT SYSTEM INSPECTION
Before furnace is installed, it is highly recommended that any existing vent system be completely inspected.
For a chimney or Type B vent, this should include the following:
1. Inspection for any deterioration in chimney or Type B vent. If deterioration is discovered, the chimney must be repaired or Type B vent must be replaced.
2. Inspection to ascertain that vent system is clear and free of obstructions. Any blockage must be cleared before install­ing furnace.
3. Cleaning chimney or Type B vent if previously used for venting a solid fuel burning appliance or fireplace.
4. Confirming that all unused chimney or Type B vent connections are properly sealed.
5. Verification that chimney is properly lined and sized per applicable codes.
III. REMOVAL OF EXISTING FURNACES FROM COMMON VENT SYSTEMS
If furnace being replaced was connected to a common vent system with other appliances, the following steps shall be followed with each appliance connected to the venting system placed in opera­tion, while any other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch as required in the NFGC or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion, and other deficiencies which could cause an unsafe condition.
3. In so far as is practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so appliance shall operate continuously.
5. Test for draft hood equipped appliance spillage at the draft hood relief opening after 5 minutes of main burner opera­tion. Use the flame of a match or candle.
6. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace damp­ers, and any other gas-burning appliance to their previous conditions of use.
7. If improper venting is observed during any of above tests, the venting system must be corrected.
Vent system or vent connectors may need to be resized. For any other appliances when resizing vent systems or vent connectors, system or connector must be sized to approach minimum size as determined using appropriate table found in the NFGC or NSC­NGPIC.
IV. METAL VENT INSTALLATIONS
The furnace is approved for use with Type B vent that terminates through the roof. Refer to the NFGC Venting Tables supplied with furnace for proper sizing and setup of this furnace with Type B vent for a dedicated vent system or a common vented system.
V. MASONRY CHIMNEY INSTALLATIONS
This furnace can be common vented into an existing tile lined masonry chimney provided:
1. The chimney is currently serving at least 1 drafthood equipped appliance.
2. The vent connectors and chimney are sized in accordance with the NFGC Venting Tables supplied with furnace.
Before venting this furnace into a chimney, check chimney for deterioration and repair if necessary.
This furnace must not be vented into a chimney serving a separate appliance designed to burn solid fuel.
Type B vent connector must be used on all installations. It must be sized per the NFGC Venting Tables supplied with furnace.
VI. MULTISTORY INSTALLATIONS
For multistory installations, refer to Appendix G of the NFGC or Canadian Standard CAN/CGA-B149. Additional vent connectors should be sized per the enclosed instructions.
VII. SIDEWALL VENTING INSTALLATIONS A. General
This furnace is A.G.A. and C.G.A. designed certified for sidewall venting through an outside wall by use of the following auxiliary draft inducer:
Field Controls Company Model No. DGF-2 sidewall vent­ing kit.
Follow Installation Instructions supplied with DGF-2 kit. The minimum vent length is 5 ft and the maximum is 60 ft.
B. Location Requirements for Sidewall Venting
Locate vent terminal adhering to the following minimum clear­ances:
1. Vent terminal must be located at least 1 ft above the grade or at least 1 ft above normal expected snowfall.
2. Avoid installing vent terminal above public walkways. If this is not possible, install terminal at least 7 ft above walkway.
3. Vent terminal should be at least 4 ft to the side of and at least 1 ft above doors and windows.
4. Vent terminal should be at least 3 ft above any forced air inlet located within 10 ft.
5. Vent terminal should be located at least 6 ft from the combustion-air intake of another appliance.
6. Vent terminal should be located at least 4 ft above any electric or gas meters, regulators, and relief equipment.
—12—
Page 13
SEQUENCE OF OPERATION
Using the schematic diagram in Fig. 11, follow the sequence of operation through the different modes. This furnace has a unique control system. Read and follow the wiring diagram very carefully.
I. HEATING MODE
When wall thermostat calls for heat, the R-W circuit closes.
1. Inducer start-up sequence—Power from transformer ener­gizes fan control board. The fan control energizes the induced-draft blower motor. Pressure switch P normally open contacts close to energize ignition module.
2. Ignition module self-check—Upon being energized, the ignition module performs a 2-sec self-check. The ignition module checks for the presence of flame. If flame is present when it should not be, the module energizes the blower. The gas pilot valve remains closed, and ignitor is not energized. If no flame is detected, the module initiates the ignition sequence.
3. Ignition sequence—The ignition module energizes the hot surface pilot ignitor. The module then checks for a missing or broken ignitor. If ignitor is faulty, there is no further system response. If ignitor is functional, the pilot gas valve is energized and gas is allowed to flow to pilot where it is ignited. A flame sensing period then begins.
4. Flame sensing—Pilot flame is sensed through the ignition module’s flame sensing rod. If pilot flame is not sensed, the ignitor remains energized, and pilot gas valve remains open. If this is due to a gas interruption, the system continues its attempt to light pilot until gas is restored and unit lights or system is turned off. When pilot flame is sensed, the main gas valve opens and the pilot flame lights the burners. The blower on delay period then begins.
5. Blower on delay—The fan control starts blower after 30 sec. The blower on delay is not adjustable.
6. Blower off delay—When thermostat is satisfied, the circuit between R and W is broken, de-energizing gas valve and stopping gas flow to burners. The blower motor remains energized 60, 90, 120, or 150 sec depending on blower off delay selection (factory shipped set for 60-sec delay).
7. Post purge—Inducer motor remains energized for 5 sec after burners are extinguished.
II. COOLING MODE
When wall thermostat calls for cooling, the R-G and R-Y circuits close. The R-Y circuit starts outdoor condensing unit, and the combined R-Y and R-G circuits start furnace blower motor on cooling speed.
When thermostat is satisfied, the R-G and R-Y circuits are broken. The furnace blower de-energizes immediately.
START-UP, ADJUSTMENT, AND SAFETY CHECK
I. GENERAL
1. The furnace must have a 115-v power supply properly connected and grounded.
NOTE: Proper polarity must be maintained for correct operation.
2. Thermostat wire connections at R, W, Y, and C must be made at the 24-v terminal block on control board.
3. The gas service pressure must not exceed 0.5 psig (14-in. wc), but must be no less than 0.16 psig (4.5-in. wc) for natural gas.
II. REMOVE SHIPPING BRACKET
The furnace is equipped with a metal blower wheel shipping bracket which MUST be removed before putting furnace into operation. To remove this bracket:
1. Remove blower access panel.
2. Remove 2 mounting screws.
3. Slide bracket off blower wheel hub.
4. Replace blower panel.
III. PURGE GAS LINES
If not previously done, purge the lines after all connections have been made and check for leaks.
WARNING: Never purge a line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for the purpose of checking leakage. Use a soap-and-water solution to check for leakage. Failure to follow this warning could result in a fire, explosion, personal injury, or death.
CAUTION: Many soaps used for leak testing are corro­sive to certain metals. Piping must be rinsed thoroughly with clean water after leak check has been completed.
IV. OPERATIONAL CHECKOUT
This furnace is equipped with an automatic hot surface pilot ignition control and does not require lighting of a pilot for furnace operation.
WARNING: Do not attempt to manually light pilot. Failure to follow this warning can lead to electrical shock which could result in bodily harm.
The automatic gas valve controls the flow of gas to both the pilot
→
and main burners. The manual switch built into automatic valve body has 2 positions: OFF and ON.
→
To shut off gas manually, turn switch from ON to OFF position. When in OFF position, main burners and pilot are extinguished.
After duct work connections have been made, gas piping and electrical wiring completed, and furnace had been properly vented, unit should be started and adjusted for proper operation. Check off the following items as they are completed.
1. Make sure all electrical power is off.
2. Check all wiring using proper wiring diagram on inside of control box cover.
3. Turn on electrical power to unit.
4. Turn gas valve manual switch to ON position.
→
5. Set thermostat above room temperature.
6. The hot surface ignitor should heat up to an orange glow and ignite pilot. If flame sensor detects a proper flame, main burners will ignite. If main burners do not ignite, see Adjust Pilot Flame section below.
7. When main burners ignite, proceed to Set Gas Input Rate section.
—13—
Page 14
V. ADJUSTMENTS A. Adjust Pilot Flame
Pilot assembly should be located as shown in Fig. 13. Adjust pilot flame to envelop the flame sensor for a distance of 3/8 to 1/2 in. (See Fig. 14.) The adjusting screw for pilot flame is located on main gas control. (See Fig. 15.)
A96078
Fig. 13—Position of Pilot Assembly to Burner
d. Find natural gas heat value and specific gravity in Table
5.
e. Follow heat value line and specific gravity line to point
of intersection to find orifice size and manifold pressure settings for proper operation at given natural gas condi­tion.
f. Check and verify orifice size in furnace. NEVER AS-
SUME THE ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
EXAMPLE: Heat value = 1025 Btu/cu ft Specific gravity = 0.62. Therefore: Orifice No. 40 or 41*
Manifold Pressure 3.3 or 3.5 in. wc * The furnace is shipped with No. 42 orifices. In this example all main burner orifices must be changed and manifold pressure must be adjusted.
3
⁄8″ TO 1⁄2″
FLAME SENSING ROD
HOT SURFACE IGNITOR
A96077
Fig. 14—Position of Pilot Flame to Flame Sensor
B. Set Gas Input Rate
WARNING: Never set furnace input rate above that
shown on rating plate. Failure to follow this warning could lead to premature heat exchanger failure and a hazardous furnace operating condition and result in serious bodily injury or loss of life.
There are 2 methods of adjusting gas input rate. The preferred method is by using Table 5 and item 1. The second method is by clocking the gas meter and using item 2. Item 2 must be used for altitudes above 2000 ft.
1. Determine natural gas orifice size and manifold pressure for correct input using Table 5.
a. Obtain average yearly heat value for local gas supply. b. Obtain average yearly specific gravity for local gas
supply.
c. Verify the furnace model. Table 5 can only be used for
model 349HAV Furnaces.
g. Proceed to item 3 to adjust manifold pressure.
2. Determine natural gas input rate by clocking gas meter.
NOTE: Be sure all pressure tubing, vent pipes, and burner enclosure plates are in place when checking input.
a. Obtain average yearly heat value for local gas supply.
NOTE: Be sure heating value of gas used for calculations is correct for your altitude. Consult local gas utility for altitude adjustments of gas heating value.
b. Turn off all other gas appliances and pilots. c. Start furnace and let it run for 3 minutes. d. Measure time (in sec) for gas meter test dial to complete
1 revolution. e. Refer to Table 6 for cu ft of gas per hr. f. Multiply gas rate (cu ft/hr) by heating value (Btu/cu ft).
Obtain heating value from local gas utility.
EXAMPLE: Btu heating input = Btu/cu ft X cu ft/hr Heating value of gas = 1070 Btu/cu ft Time for 1 revolution of 2-cu-ft dial = 72 sec Gas rate = 100 cu ft/hr (from Table 6) Btu heating input = 100 X 1070 = 107,000 Btuh.
g. Measured gas input must not exceed gas input on unit
rating plate.
(1.) High-altitude installations (United States
only)—Gas input on rating plate is for altitudes up to 2000 ft. Ratings for altitudes over 2000 ft must be 4 percent less for each 1000 ft above sea level. To obtain the altitude adjusted rating, adjust the mani­fold pressure (see item 3), and replace the main burner orifices as needed (see item 4). Refer to NFGC Appendix F, Table F-4 for proper orifice sizing at high altitudes.
(2.) High-altitude installations (Canada only)—The Ca-
nadian ratings are approved for altitudes up to 2000 ft for natural and propane gases. High-altitude ratings are from 2000 ft to 4500 ft above sea level. See Table 7 for nominal burner orifice size. High­altitude input ratings include a 10 percent derate as required by Canadian standards.
h. Proceed to item 3 to adjust manifold pressure.
—14—
Page 15
TABLE 5—MODEL 349HAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT RATE
(TABULATED DATA BASED ON ALTITUDES UP TO 2000 FT AND 25,000 BTUH PER BURNER)
GAS HEAT SPECIFIC GRAVITY OF NATURAL GAS
VALUE 0.56 0.58 0.60 0.62 0.64 0.66 0.68 0.70 0.72
Orf.
Mnfld
Orf.
Mnfld
Orf.
(Btu/cu ft)
860
875
890
905
920
935
950
965
980
995
1010
1025
1040
1055
1070
1085
1100
No.
37 38
—
37 38 39
38 39
—
38 39 40
38 39 40
39 40 41
39 40 41
40 41
—
40 41
—
41 42
—
41 42
—
41 42
—
42
— —
42 — —
42 — —
42 — —
43 — —
Press
3.3
3.6 —
3.2
3.5
3.8
3.4
3.7 —
3.3
3.6
3.8
3.2
3.4
3.7
3.3
3.5
3.8
3.2
3.4
3.7
3.3
3.6 —
3.2
3.5 —
3.4
3.8 —
3.3
3.7 —
3.2
3.6 —
3.4 — —
3.4 — —
3.3 — —
3.2 — —
3.8 — —
No.
37 38 —
37 38 —
37 38 39
38 39 —
38 39 40
38 39 40
39 40 —
39 40 41
40 41 —
40 41 —
41 42 —
41 42 —
41 42 —
42 — —
42
— —
42
— —
42
— —
Press
3.4
3.8 —
3.3
3.6 —
3.2
3.5
3.8
3.4
3.7 —
3.3
3.6
3.8
3.2
3.4
3.7
3.3
3.6 —
3.2
3.4
3.7
3.3
3.6 —
3.2
3.5 —
3.4
3.8 —
3.3
3.7 —
3.2
3.6 —
3.5 — —
3.4 — —
3.3 — —
3.2 — —
No.
36 37
—
37 38
—
37 38
—
37 38 39
38 39
—
38 39 40
38 39 40
39 40
— 39
40 41
40 41 —
40 41 —
40 41 42
41 42 —
41 42 —
42 — —
42 — —
42 — —
Mnfld Press
3.2
3.5 —
3.4
3.8 —
3.3
3.6 —
3.2
3.5
3.8
3.4
3.7 —
3.3
3.6
3.8
3.2
3.5
3.7
3.3
3.6 —
3.2
3.5
3.7
3.4
3.6 —
3.3
3.5 —
3.2
3.4
3.8
3.3
3.7 —
3.2
3.6 —
3.5 — —
3.4 — —
3.3 — —
Orf. No.
36 37 —
36 37 —
37 38 —
37 38 —
37 38 39
38 39 —
38 39 40
38 39 40
39 40 —
39 40 41
39 40 41
40 41 —
40 41 42
41 42 —
41 42 —
41 42 —
42 — —
Mnfld Press
3.3
3.7 —
3.2
3.5 —
3.4
3.8 —
3.3
3.6 —
3.2
3.5
3.8
3.4
3.7 —
3.3
3.6
3.8
3.2
3.5
3.7
3.4
3.6 —
3.3
3.5
3.8
3.2
3.4
3.6
3.3
3.5 —
3.2
3.4
3.8
3.3
3.7 —
3.2
3.6 —
3.2
3.5 —
3.4 — —
Orf.
No.
36 37
—
36 37
—
36 37
—
37 38
—
37 38
—
37 38 39
38 39
—
38 39 40
38 39 40
39 40
—
39 40 41
39 40 41
40 41
—
40 41 42
41 42 —
41 42 —
41 42 —
Mnfld Press
3.4
3.8 —
3.3
3.6 —
3.2
3.5 —
3.4
3.8 —
3.3
3.6 —
3.2
3.5
3.8
3.4
3.7 —
3.3
3.6
3.8
3.2
3.5
3.7
3.4
3.6 —
3.3
3.5
3.8
3.2
3.4
3.7
3.3
3.6 —
3.2
3.4
3.8
3.4
3.7 —
3.3
3.6 —
3.2
3.5 —
Orf. No.
36 — —
36 37 —
36 37 —
36 37 —
37 38 —
37 38 —
37 38 39
38 39 —
38 39 40
38 39 40
39 40 —
39 40 41
39 40 41
40 41 —
40 41 42
41 42 —
41 42 —
Mnfld Press
3.5 — —
3.4
3.8 —
3.3
3.6 —
3.2
3.5 —
3.4
3.7 —
3.3
3.6 —
3.2
3.5
3.8
3.4
3.7 —
3.3
3.6
3.8
3.2
3.5
3.7
3.4
3.6 —
3.3
3.5
3.8
3.2
3.4
3.7
3.3
3.6 —
3.2
3.5
3.8
3.4
3.7 —
3.3
3.6 —
Orf. No.
35 36 —
36 — —
36 37 —
36 37 —
36 37 —
37 38 —
37 38 —
37 38 39
38 39 —
38 39 40
38 39 40
39 40 —
39 40 41
39 40 41
40 41 —
40 41 42
41 42 —
Mnfld Press
3.2
3.6 —
3.5 — —
3.4
3.7 —
3.3
3.6 —
3.2
3.5 —
3.4
3.7 —
3.3
3.6 —
3.2
3.5
3.8
3.4
3.7 —
3.3
3.6
3.8
3.2
3.5
3.7
3.4
3.6 —
3.3
3.5
3.8
3.2
3.4
3.7
3.3
3.6 —
3.2
3.5
3.8
3.4
3.7 —
Orf. No.
34 35 36
35 36 —
36 — —
36 37 —
36 37 —
36 37 38
37 38 —
37 38 —
37 38 39
38 39 —
38 39 40
38 39 40
39 40 —
39 40 41
39 40 41
40 41
—
40 41
—
Mnfld Press
3.2
3.3
3.7
3.2
3.6 —
3.5 — —
3.4
3.7 —
3.3
3.6 —
3.2
3.5
3.8
3.4
3.7 —
3.3
3.6 —
3.2
3.5
3.8
3.4
3.7 —
3.3
3.6
3.8
3.2
3.5
3.7
3.4
3.6 —
3.3
3.5
3.8
3.2
3.4
3.7
3.3
3.6 —
3.2
3.5 —
Orf. No.
34 35 —
34 35 36
35 36 —
36 37 —
36 37 —
36 37 —
36 37 38
37 38 —
37 38 —
37 38 39
38 39 —
38 39 40
38 39 40
39 40 —
39 40 41
39 40 41
40 41
—
Mnfld Press
3.3
3.4 —
3.2
3.3
3.7
3.2
3.6 —
3.5
3.8 —
3.4
3.7 —
3.3
3.6 —
3.2
3.5
3.8
3.4
3.7 —
3.3
3.6 —
3.2
3.5
3.8
3.4
3.7 —
3.3
3.6
3.8
3.2
3.5
3.7
3.4
3.6 —
3.3
3.5
3.8
3.2
3.4
3.7
3.3
3.6 —
—15—
Page 16
SECONDS
FOR 1
REVOLUTION
10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49
TABLE 6—GAS RATE CU FT/HR
1800 1636 1500 1385 1286 1200 1125 1059
10 0
947 900 857 818 783 750 720 692 667 643 621 600 581 563 545 529 514 500 486 474 462 450 439 429 419 409 400 391 383 375 367
SECONDS
FOR 1
REVOLUTION
50 51 52 53 54 55 56 57 58 59 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96
98 100 102 104 106 108
110 112 116 120
SIZE OF TEST DIAL
1
cu ft2cu ft5cu ft
72 71 69 68 67 65 64 63 62 61 60 58 56 54 53 51 50 48 47 46 45 44 43 42 41 40 39 38 38 37 36 35 35 34 33 33 32 31 30
SIZE OF TEST DIAL
1
cu ft2cu ft5cu ft
360
720
327
655
300
600
277
555
257
514
240
480
225
450
212
424
200
400
189
379
180
360
171
343
164
327
157
313
150
300
144
288
138
277
133
267
129
257
124
248
120
240
116
232
113
225
109
218
106
212
103
206
100
200
97
195
95
189
92
185
90
180
88
176
86
172
84
167
82
164
80
160
78
157
76
153
75
150
73
147
144 141 138 136 133 131 129 126 124 122 120 116 112 109 106 103 100
97 95 92 90 88 86 84 82 80 78 76 75 74 72 71 69 68 67 65 64 62 60
360 355 346 340 333 327 321 316 310 305 300 290 281 273 265 257 250 243 237 231 225 220 214 209 205 200 196 192 188 184 180 178 173 170 167 164 161 155 150
IGNITOR
CONNECTOR
IGNITION SYSTEM CONTROL SWITCH
IGNITION MODULE
PILOT
ADJUSTMENT
(UNDER CAP
SCREW)
PILOT
OUTLET
INLET PRESSURE TAP
GAS PRESSURE REGULATOR
MANIFOLD
PRESSURE
TAP
ADJUSTMENT (UNDER CAP SCREW)
→ Fig. 15—Honeywell SmartValve
d. Replace cap that conceals gas valve regulator adjustment
screw.
CAUTION: Be sure burner enclosure front is in place after adjustments have been made.
e. Look through openings in burner enclosure and check
burner flame. The main burner flame should be clear blue, almost transparent. (See Fig. 16.)
BURNER FLAMEPILOT FLAME
A98304
TABLE 7—CANADIAN ORIFICE SIZE
GAS
SEA LEVEL
0-2000 FT
Natural 42 43
Propane 54 55
HIGH ALTITUDE
2000-4500 FT
3. Adjust gas input.
NOTE: The gas valve has been nominally set at 3.5-in. wc for natural gas.
a. Remove cap that conceals adjustment screw for gas
valve regulator. (See Fig. 15.)
b. Turn adjusting screw either counterclockwise (out) to
decrease input rate or clockwise (in) to increase rate. When adjusting input rate, DO NOT set manifold pressure less than 3.2-or more than 3.8-in. wc for natural gas. Make any major adjustments by changing main burner orifices.
WARNING: DO NOT redrill orifices. Improper drilling (burrs, out-of-round holes, etc.) can cause excessive burner noise and misdirection of burner flames. This can result in flame impingement of the burners and heat exchangers causing failures.
NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check the orifice hole with the correct size numbered drill bit. Never redrill an orifice. A burr-free and squarely aligned orifice hole is essential for proper flame charac­teristics.
c. Measure adjusted gas input rate using method outlined in
item 2.
BURNER
MANIFOLD
A84076
Fig. 16—Pilot and Burner Flames
4. Change burner orifice (if necessary). The furnace is supplied with standard orifices for the gas
shown on rating plate. If orifices need to be changed to achieve proper input rate, proceed as follows:
a. Remove manifold pipe cover and burner removal
cover/air inlet plate. b. Remove manifold retention plate. c. Pull manifold/burner assembly out past support pins and
remove assembly.
—16—
Page 17
NOTE: It is only necessary to remove 1 manifold retention plate to gain access to burners.
d. Remove burners from assembly and change orifices as
required.
e. Reinstall assembly by reversing the procedure in items a
through d making sure that assembly is securely mounted under manifold retention plate on opposite side of unit.
CAUTION: Care must be taken when removing pilot burner in order not to damage pilot gas line or hot surface ignitor.
f. After securing manifold assembly, replace all other
components and/or wiring making sure that all connec­tions and screws are tightened properly.
C. Set Temperature Rise
The furnace must not be operated outside the range of temperature rise specified on unit rating plate. Determine air temperature rise as follows:
a. Place thermometers in return and supply ducts as near
furnace as possible. Be sure thermometers do not "see" heat exchanger so that radiant heat does not affect readings. This practice is particularly important with straight-run ducts.
b. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine air temperature rise.
c. Adjust temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise. De­crease blower speed to increase temperature rise.
WARNING: Disconnect the electrical power before changing the speed tap. Failure to follow this warning could result in personal injury.
d. To change motor speed taps, remove the motor tap lead
and relocate it on the desired terminal on the plug in terminal block/speed selector located at the blower motor. (See Table 8.)
TABLE 8—BLOWER SPEED SELECTION
SPEED TAP NO.
Common 1
High 2
Medium 3
Low 4
CAUTION: Recheck the temperature rise. It must be
within limits specified on the unit rating plate. Recom­mended operation is at midpoint of rise or above.
D. Set Blower Off Delay
The blower off delay may be adjusted for a 60- (factory setting), 90-, 120-, or 150-sec delay. Set the DIP switches on the control board to obtain desired time delay. (See Fig. 17.)
E. Set Thermostat Heat Anticipator
12
60 Sec
DELAY OFF DIP SWITCH SETTINGS
12
12 1212
90 Sec
120 Sec
12
150 Sec
A95115
Fig. 17—Blower Off Delay Settings
THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED (ANITICIPATOR, CLOCK, ETC., MUST BE OUT OF CIRCUIT.)
HOOK-AROUND AMMETER
R Y W G
10 TURNS
FROM UNIT 24-V CONTROL TERMINALS
EXAMPLE:
5.0 AMPS ON AMMETER 10 TURNS AROUND JAWS
0.5 AMPS FOR THERMOSTAT
=
ANTICIPATOR SETTING
A96316
Fig. 18—Amp Draw Check with Ammeter
Fig. 18 illustrates an easy method of obtaining these measure­ments. The amp reading should be taken after blower motor has started. See thermostat manufacturer’s instructions for adjusting heat anticipator and for varying heating cycle length.
VI. CHECK SAFETY CONTROLS A. Check Primary Limit Control
The heat sensing switch performs as the furnace high temperature limit switch. If furnace overheats for any reason, the limit switch opens, breaking circuit to main gas valve. If limit is activated check for a restriction in duct system (dirty filters, blocked duct work, closed registers, etc.). The blower motor is energized and as unit cools, limit switch closes. This relights main burners, but unless overheating condition is corrected, furnace will cycle on limit. Corrective action must be taken.
The recommended method of checking limit control is to gradually block off return air after furnace has been operating for a period of at least 5 minutes. As soon as limit control has shut off burners, return-air opening should be unblocked to permit normal air circulation. By using this method to check limit control, it can be established that limit is functioning properly and will operate if there is a restricted circulating air supply or motor failure. If limit control does not function during this test, the cause must be determined and corrected.
B. Check Pressure Switch (Blocked-Vent Shutoff Switch)
This control proves operation of the draft inducer. Check switch operation as follows:
1. Turn off 115-v power to furnace.
2. Remove control box cover and disconnect inducer motor lead wires from control board.
—17—
Page 18
3. Turn on 115-v power to furnace.
4. Set thermostat to call for heat. When pressure switch is functioning properly, ignitor should not glow. If ignitor glows when inducer motor is disconnected, shut down furnace immediately. Determine the reason pressure switch did not function properly and correct the condition.
5. Turn off 115-v power to furnace.
6. Reconnect inducer motor lead, reinstall control box cover, and turn on 115-v power supply.
C. Flame Rollout Switch
This furnace is equipped with a manual reset flame rollout shutoff switch which is attached to burner/manifold assembly. In the event that a blockage prevents venting of flue gases from heat exchanger, the switch detects conditions that would produce a flame rollout
and shuts off power to automatic gas valve before there is furnace damage or a flame rollout outside of furnace cabinet. The loss of power to gas valve shuts off gas burners, however, blower is still controlled by fan and limit switch and operates until heat ex­changer temperatures have cooled.
CHECKLIST
1. Put away tools and instruments. Clean up debris. Verify that blower and control access panels are properly installed.
2. Cycle test furnace with room thermostat.
3. Check operation of accessories per manufacturer’s instruc­tions.
4. Review User’s Guide with owner.
5. Leave literature packet near furnace.
—18—
Page 19
—19—
Page 20
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:  • Unit Familiarization • Maintenance  • Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book.  Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog. 
CALL FOR FREE CATALOG 1-800-962-9212
[ ] Packaged Service Training [ ] Classroom Service Training
A94328
© 1998 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231
—20—
Printed in U.S.A. 349h505 Catalog No. 5334-900
Loading...