Before proceeding to install Models 342 and 342S Unit
Heaters, refer to Bryant form Ho, 39003D1 “Froeaduree for
Gas Appliances” (packaged with the equipment) for in
formation concerning combustion, venting, piping, and
other standard installation practices. The current edition of
the American National Standard “Installation of Gas Ap
pliances and Gas piping”, Z21.30, takes precedence over all
other reference publications pertinent to this -installation
instruction. Both models arc shipped factory-assembled,
Installation comprises the following;
* I. Inspection
* IL Location and Suspension
* III, piping '
lY, .
*** V. Venting
VL Startup'arid Adjustment
VII, Service 0;and„
=<To perform; .these -sepi^iops for installation steps-), jrefer t.
the ■;apprOpriath;''settiQhs^ Pr^atit' farm No.' 3&003D1
(packaged '■ With'ixfhis^ ^ .;.■■■ ■, ■ ^ '■ ■■ -
.' SPECIAL airplaneaMANQAR AND : ; 1
. (5ARAGE APPLICATION PRECAUTIONS •
NOTE.:
cr aft ; Hangars, ” ahd^^HjFr'A ■; :NpT,;i':8g 2 ' Standard. .for
Gar ages; ” - . ''""uO.., .I.; 7 '■'.'li,'Ui'' 'A ■ '[,■ A ■', 1.,
7 ■ .''hoiisedah:,;,'-the' .h angar 'must ;be' ■ in aint'ained " >.■ ;'i■■ ,i X 'i
■2. A'^mmimumyclearanqe':''.oi/$;%et';::^^^^ .the
bottom" ,'o.f ^thd '.'healtei:' ■ih./'hthef. .isepf ion^ .'pio^the ■.■;aircritft,
hangar, such '¿S' ofhe'es' ''an'd '¿hops' Vliich ■'''bb'fh muni cate .with areas used for servicing or storage, must be
maintained.
A-The heater;imn-Si .also be gg'lQcated. th;at it is.protected.'._____
from damage'by aircraft or other objects such as cranes 5, A service clearance of 18 inches at the rear and 12 ihor movable scaffoldings. In addition, it must be located ches from any obstruction at the bottom of the heatdr
"to be accessible for servicing and adjustment. must be maintained, " '
..........
Figure 1
4, A clearance of 6 inches from combustible maiterial
must be maintained from the top and the sidep of thd
...........
heater. ■;.'/:
39342D.PT3
11/1V4
i ' 7 ; COMPONENT ; •.
.Bryant Auto Pilot ...'..e ,
■Bryant'Gas 'Valve:!'■. ;■., ,'. ■ „"
Gas Pressure .Begulator"! /
. Transformer.: '.„..X;-...
,d0D%'5hutpff..j,'.;'j.:>.,-:
■H=A'-643;Bryàn!f Gas ,’Valv.e wjthÙntsBral gae pressure rsgulatpr .is used ;on -IÌ4.'Hiid D5 ibf sizes 30 thru IBO; A-641 Gas Valve wimoUt regulator
Used on-D2 for all 'sizes. -A-64l with separate gas ‘pressute Tegulator 'is'used on D4 and D5 for sises 175 'thru 40G. ■ ■ '
^The above ratings are approved for altitudes to. 2000 ft. For elevations above 2000 ft, reduce ratings 4% for each 1000 ft above sea level.
=i=’i=Effective throw aa shown is the horizontal distance in feet that the heated airstream travels from the outlet of the unit heater with louvers
positioned for maximum throw with air reaching the floor, Spread or width of the air pattern is approximately 20% of the'maximum throw.
For additional spread, use vertical louvers, Above data are test results,
For general location and suspension information, refer to
Section II of Bryant form No, 33008Dl. b addition, the
following precautions should bs observed when selecting a
; mounting site,
1. Direct heated airstream toward area having greatest
heat loss.
2. For multiple installations, locate heaters so that each
will warm a specific area. Arrange so that the overall
air pattern results in a continuous circular flow of
warm air throughout the space,
3. Do not locate the heater in areas where combustion air
is limited,
4. If located in spaces equipped with exhaust fans,
provide sufficient makeup air.
5. Two l/2"inch pipe tappings are provided in the top
casing for use in suspending the heater. Use pipe
unions to join the unit heater to the ceiling hangar,
6. Do not lift the heater by the motor mount, manifold, or
louvers. Use a rope sling whenever this is possible.
IV. WIRING.
Make all electrical connections in accordance with the
National Electric Code and any_locaI codes .that may apply.
The unit must be grounded electrically in accordance with
the National Electric Code and local codes governing such
installations. A permanent and uninterrupted or unbroken
trical fault should occur.
If aluminum conductors are to be used, the wire size selec
ted must have a Current capacity not less than that of the
copper wire specified and must not create a voltage drop be
tween the service panel and the unit in excess of 2% of the
unit rated voltage. As a minimum, aluminum wire must be
treated to prevent oxidation.
With electric power turned off, recheck all electrical con
nections (both factory and field) for tightness. Be sure to
check power supply connections, especially if aluminum
conductors are used.
The unit heater is completely wired at the factory and is
ready for connections to a 116/60/1 power source. See
wiring diagram.
The heat anticipator on the thermostat should be set at 0.8
amps.
VI. STARTUP AND ADJUSTMENT
NOTE; Remove burner hold-down shipping bracket.
1. Start unit using procedure outlined on lighting instruc™
tion plate attached to heater.
2, Adjust pilot flame. Adjusting screw under screw cap on
pilot valve is used for this purpose,
For D4 controls, flame should be long enough for good
impingement on metal element of Bryant automatic
pilot. For D5 and D2 controls, flame should surround
thermocouple element of pilot and extend downward
to include 3/S to 1/2 inch of thermocouple. Flame
should never come in contact with any part of thermo
couple lead wire.
To adjust pilot flame on units equipped with Model AG43 valve, adjustment screw is located in pilot outlet
portion of valve body. Remove capscrew, make
..... .nsoe.gsai'y. .adjustment, and replace capscrew,...
Attach low-voltage test light to electrical leads of
gaa valve. With thermostat set above room tem
perature, close manual pilot valve. If light goes out
when pilot cools, pilot is functioning properly. Test
light should go out within 45 seconds after pilot gas
supply is turned off.
Check Operation of temperature limit control. Do this
by allowing burners to operate while fan is not running
to see that limit switch opens.
— 3 —
S E P / 0 9 / 2 0 0 8 / T D E 0 3 : 3 3 P M
UTC TECH PUB
P A X N o , 3 1 7 2 4 0 5 6 6 2
Check all connections in gas piping for leaks. Use soap-
and-water solution.
VIL SERVICE AND MAINTENANCE
1. Pilot Orifice - is located in bottom fitting of pilot and is
K readily accessible for inspection and cleaning.
3. Main Burner Orifices - Orifice is readily unscrewed
from manifold after burner is removed,
3. Removing Main Burners - Lift rear of burner and push
it away from manifold enough to disengage orifice spud
from mixer shield. Then pull down and out of heater.
End of burner away from manifold seats in slotted
burner support. It is necessary to lift burner out of this
slot before attempting to push burner back. See Figure
12.
NOTE: Disconnect the pilot tubing and wires to remove the
burner that holds the pilot. However, it is not necessary to
remove the pilot itself from the burner.
SIZES 30 THRU 150 UNIT HEATER WIRING DIAGRAMS
4. Cleaning - Heat exchanger tubes should be inspected
at regular intervals and cleaned when necessary.
a. Shut off gas and electricity. Heater should be cool.
b. Loosen two knurled-head screws to release rear
access door. Door will hang down freely.
c. Disconnect pilot tube and wireg.
d. Remove main burners and pilot.
e. Use stiff brush to scrub heat exchanger tubes.
Remove all loose scale and any soot that may have
collected.
f. Replace burners and pilot. Reconnect pilot tube
and wires.
g. Unit is now ready for relighting.
5. Oiling - Oil fan motor (s) yearly, or more often, with
enough drops of SAE No. 20 nondetergent oil to
overflow oil cup; or every 2 years, or more often, with
Anderol L-465* obtainable in tubes from your dealer.
(Bryant P/N 7O291D01). See FTB143.
*Lehigh Chemical Company
Figure 3^With 733 Pilot ihstaííed
Transformer6BPilot with Auto.
1A
Pan Relay—N.O,Ignition Coil
SG
ЗАFan Motor
3A1Fan Motor
Fan Motor
3A2
3CFan Motor
Automatic Gas Valve
5A
0APilot Switch—No.O.If wires are replaced, use 18 AWG
(None on Propane)150“
:: : 4—УУ1Ш FIIQÍ installed
LEGEND
7KTemp Limit Control—
SPOT—N.C.
7PPressure Switch^—
SPST—N.O.
11AResistor
C., 3/64-inch thick insulation.
— 4 -
S E P / 0 9 / 2 0 0 8 / T U E 0 3 : 3 3 P M
UTC TECH PUB
SIZES 175 THRU 250 UNIT HEATER WIRING DIAGRAMS
F A X N o , 3 1 7 2 4 0 5 6 6 2
Figure 5—With 733 Pilot Installed
SIZE 300 UNIT HEATER WIRING DIAGRAMS
Figure 6—With 732 Pilot Installed
1A Tran3fùi‘rYier
2G Fan Relay—N,0.
3A. Fan Motor
Fan Motor
3A2
Fan Motor
3C
Automatic Gas Valve
5A
Pilot Switch—N.O.
6A
(None on Propane)
LEGEND
^ 5 -
6B Pilot with Auto.
Ignition Coil
7K Temp Limit Control—
SPOT—N,C,
Pressure Switch —
7P
S PST—N.O,
IIAResistor
If wires are replaced, use 18 AWG
C„ 3/64-inch thick insulation.
150^
S E P / 0 9 / 2 0 0 8 / T U E 0 3 : 3 4
Figure 9—With 733 Pilot InstalledFigure 10—With 732 Pilot Installed
UTC TECH PUB
SIZE 400 UNIT HEATER WIRING DIAGRAMS
LEGEND
1ATransformer
2GFan Relay—^N.0,
3C1 Fan Motor
F$n MotorSPST^N.;0,
3CS
5AAutomatic Gas Valve
Pilot Switch—N.O.
6A
{Nons on Propane)
6BPilot with Auto.,
Ignition Coil
7K
7P
11AResistor
1S0°
F A X N o , 3 1 7 2 4 0 5 6 6 2
Tamp Limit Control—
SPOT—N.C.
Pressure Switch—
If wires are replaced, use 19 AWG
C,, 3/64-inch thick insulation.
6-
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.