Bryant 333B-AV-036060-AA-JA Troubleshooting Manual

troubleshooting guide
DELUXE 2-STAGE GAS-FIRED INDUCED-COMBUSTION FURNACES WITH PSC OR ICM BLOWER MOTORS
Cancels: New SM04-3
8-95
INDEX
PAGE
Instructions .....................................................................................1
General........................................................................................1-3
Furnace Model Nomenclature........................................................2
Example..........................................................................................3
Sequence of Operation................................................................3-6
Adaptive Heating Mode—Single-Stage Thermostat
with 2-Stage Heating........................................................3-4
Non-Adaptive Heating Mode—Two-Stage Thermostat
Cooling Mode........................................................................4-5
Continuous Blower Mode.........................................................5
Heat Pump Mode...................................................................5-6
Defrost.......................................................................................6
Component Test........................................................................6
Service Information Label .............................................................7
Start Here........................................................................................8
Rapid Flashing LED ......................................................................9
Improper Cooling Airflow........................................................9-11
High-Heat Temperature Rise Too Low.......................................11
Status Code 11—No Previous Code ...........................................12
Status Code 12—Blower On After Power Up............................12
Status Code 13—Limit (LS) or Flame Rollout (FRS) Switch
Lockout.......................................................13-14
Status Code 14—Ignition Lockout..............................................14
Status Code 21—Gas Heating Lockout.................................14-15
Status Code 22—Abnormal Flame-Proving Signal....................15
Status Code 23—Low-Heat Pressure Switch Did Not Open.....15
Status Code 24—Secondary Voltage Fuse Is Open..............16-17
Status Code 31—High-Heat Pressure Switch or Relay Did
Not Close or Reopened..............................18-19
Status Code 32—Low-Heat Pressure, Draft Safeguard, or
Auxiliary Limit (Downflow Only) Switch
Did Not Close or Reopened......................20-22
Status Code 33—Limit (LS) or Flame Rollout (FRS) Switch
Is Open.......................................................22-24
Status Code 34—Ignition-Proving Fault................................24-25
Status Code 43—Low-Heat Pressure, Draft Safeguard, or
Auxiliary Limit Switch Open While
High-Heat Pressure Switch Is Closed.......26-27
Status Code 45—Replace Control...............................................27
Cleanup and Start-Up Instructions ..............................................28
APPENDIX A—Board Layout and Wiring Schematics.......29-31
APPENDIX B—ICM Blower Motor Description and
Operation.....................................................32-35
APPENDIX C—Pressure Check Diagram..................................36
APPENDIX D—Quick Reference Troubleshooting Guide........37
APPENDIX E—Static Pressure Reading Location
Diagrams......................................................38-39
APPENDIX F—Thermostat Staging Algorithm....................40-41
APPENDIX G—Quick Reference Information ..........................42
APPENDIX H—Twinning .....................................................43-45
INSTRUCTIONS
This guide uses your expertise and observations to lead you to the trouble spot as efficiently as possible. This is only intended as a guide and should not be used blindly. Your experience and expertise are of high value when troubleshooting this unit. Do not disregard all of your instincts.
The 2-stage furnace control was designed with diagnostic capa­bilities built in. A RED LED is used to flash a status code which will lead you to 1 of the sections as listed in the Index.
You should ALWAYS begin in the START HERE section (see Index for page number) which will guide you to the appropriate section where a minimal number of steps will be used to correct the problem. If you are very experienced at how this furnace operates, you can use the Quick Reference Troubleshooting Guide in Appendix D to isolate the problem. Once in a section, read the ACTION. An ACTION may have a number in the GO TO column. Do whatever the ACTION says, then proceed to the step indicated in the GO TO column.
If the ACTION is a question (a question will have a number in the YES or NO column), answer it YES or NO. If the answer is YES, go to the step indicated in the YES column. If the answer is NO, go to the step indicated in the NO column.
Let’s try our guide out using the EXAMPLE table on page 3, and see how it works. Suppose that the problem is a defective low-heat pressure switch (forexample the contacts will not open). This is an internal problem and cannot simply be seen. We go to the START HERE section to Step 1.
GENERAL
The furnace must havea 115-vacpower supplyproperly connected and grounded. Correct polarity must be maintained to enable gas heating operation.
The gas service pressure must not exceed 0.5 psig (14-in.wc), and be no less than 0.16 psig (4.5-in.wc).
Thermostat wire connections to furnace at R and W/W1 are the minimum required for gas heating operation. W2 must be con­nected for 2-stage heating thermostats. Y/Y2 and G are required to be connected to furnace for cooling and heat pumps. G is required for continuous fan. C stats. These connections must be made at 24-vac terminal block on furnace control. (See Appendix A.) O is required for heat pumps for ICM blower motors only. Y1 is required for 2-stage cooling and 2-stage heat pumps for ICM blower motors only. The O and Y1 connections must be made to ICM furnaces’ orange and blue leads flagged "O" and "Y1", respectively.
These furnaces can be installed with either a single-stage heating or a 2-stage heating thermostat.
For single-stage thermostats, connect thermostat R to W/W1 at furnace control terminal block. For single-stage thermostats, the control determines (based on lengths of previous heating on and off cycles) when to operate in low- and high-gas heat for optimum comfort. (See Appendix F.) Setup switch-2 (SW-2) must be in factory-shipped OFF position.
OM-24V is required for some clock thermo-
—1—
JA—Aluminized Heat Exchanger
Variation
Series
A—USA Unit
Brand Name
040—40,000
060—60,000
065—65,000
1000 of Heating Btu Input
080—80,000
085—85,000
100—100,000
105—105,000
120—120,000
125—125,000
024—800 CFM
036—1200 CFM
Nominal Cooling CFM @ 0.5 Total ESP
042—1400 CFM
048—1600 CFM
060—2000 CFM
V—Nat. Gas, HSI
Variation
80% EFFICIENT NON-CONDENSING FURNACE MODELS AND NOMENCLATURE
333B A V 036 060 A A JA
300 Numbers—Gas Furnace
Model Number Description
400 Numbers—Gas Furnace
Models Gas Control / Ignition
2-Stage, Variable-Speed ICM
333BAV—80% Efficient, Upflow and Horizontal,
2-Stage, PSC Motor
330AAV—80% Efficient, Upflow,
2-Stage, PSC Motor
331AAV—80% Efficient, Downflow and Horizontal,
Low NOx, California Units (JAV)
x
2-Stage, PSC Motor, Low NO
330JAV—80% Efficient, Upflow and Horizontal,
x
2-Stage, Variable-Speed, ICM, Low NO
333JAV—80% Efficient, Upflow and Horizontal,
A—110v-125v, Single Phase, 60Hz
Electrical Supply
x
PSC Motor, Low NO
331JAV—80% Efficient, Downflow, 2-Stage,
—2—
EXAMPLE
START HERE SECTION
STEP ACTION YES NO GO TO
Step 1 tells us to remove control door first and NOT TO REMOVE THE
1.
2.
4.
5.
6. Step 6 tells us to go to Status Code 23 section. INDEX
BLOWER DOOR because it will erase status codes stored in memory. It then asks the question, "Is RED LED status light on?" If low-heat pressure switch was defective, a low-heat pressure switch did not open, and a status code would be flashing, so the answer is YES. We go to Step 2.
Step 2 asks the question, "Is RED LED status light blinking rapidly without a pause?" If low-heat pressure switch was defective, a low-heat pressure switch did not open, and a status code would be flashing, so the answer is NO. We go to Step 4.
Step 4 asks the question, "Is RED LED status light blinking ON/OFF slowly with a combination of short and long flashes?" If low-heat pressure switch was de­fective, a low-heat pressure switch did not open, and a status code would be flashing, so the answer is YES. We go to Step 5.
Step 5 tells us to determine the status code. The status code is a 2 digit num­ber with the first digit determined by the number of short flashes and the sec­ond digit by the number of long flashes. So we count the short and long flashes and see that status code 23 is flashing and go to Step 6.
219 —
34 —
57 —
—— 6
If a 2-stage heating thermostat is to be used, move SW-2 to ON position at end of furnace installation. This overrides the built-in control process for selecting high and low fire and allows the 2-stage thermostat to select gas heating modes. W2 from thermo­stat must be connected to W2 on control terminal block.
CAUTION: This furnace is equipped with a manual reset limit switch in the gas control area. The switch will open and shut off power to the gas valve, if a flame rollout or overheating condition occurs in the gas control area. DO NOT bypass the switch. Correct inadequate combustion-air supply, component failure, or restricted flue gas passageway before resetting the switch.
Before operating furnace, check each manual reset switch for continuity. If necessary, press and release the button to reset the switch.
SEQUENCE OF OPERATION
Using schematic diagrams in Appendix A, follow the sequence of operation through the different modes. Read and follow diagram very carefully.
NOTE: Permanent-split-capacitor (PSC) motors and G.E. Inte­grated Control Motors (ICM) operate differently. PSC motors are basically fixed-multiple-speed motors, that is they operate within small ranges of speed. The ranges, usually 4, can be selected by connecting to different 115-vac motor wires. The speed ranges are small, about 100 RPM wide, and are dependent on the motor’s synchronous speed (1200 for most furnaces). The characteristics of PSC motors limit selections to fixed speeds between about 700 and 1100 RPM. The ICMmotor speeds are infinitely variable from 300 to 1400 RPM and are dynamically controlled to precisely control airflow CFM. The start and stop characteristics of PSC and ICM motors differ in that PSC motors ramp up to speed rapidly and coast to a stop slowly. ICM motors ramp up to speed at a controlled rate to reduce start-up noise perception (4 to 11 sec, depending on target operating CFM). ICM ramp-down time is the same as ramp-up time. ICM ramp-up and ramp-down times are additive to blower on and off delays, respectively. The PSC motor is energized with 115 vac only when operating. The ICM is energized with 115 vac whenever power is available at furnace control, but operates only when 24-vac motor control input(s) are ON. Other motor differences will be included in the following information.
NOTE: If a power interruption occurs during a "call for heat" (W/W1 or W/W1-and-W2) and if thermostat is still calling for gas heating, the control starts a 90-sec blower-only ON period 2 sec
after power is restored. The red LED will flash status code 12 during the 90-sec period, after which LED will be on continuously as long as no faults are detected. PSC motors operate at low-gas­heat or high-gas-heat CFM, respectively. ICM motors operate at low-gas-heat CFM in both cases. After the 90-sec period, furnace responds to thermostat normally.
Blower door must be installed for power to be conducted through blower door interlock switch ILK to furnace control CPU, trans­former TRAN, inducer motor IDM, blower motor BLWM, hot surface ignitor HSI, and gas valve GV.
I. ADAPTIVE HEATING MODE—SINGLE-STAGE THERMOSTAT WITH 2-STAGE HEATING
NOTE: With high-heat-only switch SW-1 in OFF position, low-
heat-only switch SW-2 selects either low-heat-only operation mode when on (see section II below), or adaptive heating mode when off in response to a call for heat. (See Appendix F.) When high-heat-only switch SW-1 is in ON position, it always initiates high-gas-heat operation when R-W/W1 circuitis closed,regardless of setting of low-heat-only switch SW-2.
These furnaces can operate as a 2-stage furnace with a single-stage thermostat because furnace control CPU includes a programmed adaptive sequence of controlled operation, which selects low-gas­heat or high-gas-heat operation. This selection is based upon the stored history of the lengths of previous gas heating on/off periods of the single-stage thermostat.
The furnace starts up in either low- or high-gas heat. If furnace starts up in low-gas heat, thecontrol CPU determines low-gas-heat on time (from 0to 16minutes) whichis permittedbefore switching to high-gas heat.
If power is interrupted, stored history is erased. When this happens, the control CPU selects low-gas heat for 16 minutes and then switches to high-gas heat, as long as thermostat continues to call for heat. Subsequent selection is based on stored history of thermostat cycle times.
When wall thermostat "calls for heat," R-W/W1 circuit closes. The furnace control performs a self-check, verifies low-heat and high-heat pressure switches’ contacts LPS and HPS are open, and starts inducer motor IDM in low speed or high speed as appropri­ate.
1. Inducer prepurge period—As inducer motor IDM comes up to low speed or high speed, low-heat (and high-heat) pressure switch contacts LPS (and HPS) close to begin a 15-sec prepurge period.
2. Ignitor warm-up—At the end of prepurge period, the hot surface ignitor HSI is energized for a 17-sec ignitor warm-up period.
—3—
3. Trial-for-ignition sequence—When ignitor warm-up period is completed, main gas valve relay contacts MGVR-1 and
-2 (and high-heat pressure switch relay HPSR) close to energize low-heat gas valve solenoid(s) GV and humidifier terminal HUM. The gas valve opens, and 24-vac power is supplied for a field-installed humidifier at terminals HUM
OM-24V. The low-heat (and high-heat) gas valve
and C solenoid(s) GV permit(s) gas flow to burners where it is ignited. After 5 sec, ignitor HSI is de-energized, and a 2-sec flame-proving period begins. If high-heat pressure switch HPS fails to close on a call for high-gas heat and low-heat pressure switch LPS closes, furnace operates at low-heat gas flow rate until high-heat pressure switch closes.
4. Flame-proving—When burner flame is proved at flame­proving sensor electrode FSE, the control CPU begins blower on delay period and continues to hold gas valve GV open. If burner flame is not proved within 2 sec, the control CPU closes gas valve GV, and the control CPU repeats ignition sequence for up to 3 more trials-for-ignition before going to ignition lockout. LOCKOUT IS RESET AUTO­MATICALLY after 3 hr, or by momentarily interrupting 115-vac power to furnace, or by interrupting 24-vac power at SEC1 or SEC2 to control CPU (not at W/W1, G, R, etc.). Opening thermostat R-W circuit will not reset an ignition lockout. If flame is proved when flame should not be present, the control CPU locks out of gas heating mode and operates inducer motor IDM on high speed until flame is no longer proved.
5. Blower on delay—If burner flame is proven, 45 sec after gas valve GV is opened, blower motor BLWM is energized at appropriate heating airflow, low-gas-heat or high-gas­heat CFM. Simultaneously, EAC terminals EAC-1 and EAC-2 are energized with 115 vac and remain energized as long as blower motor BLWM is operating.
6. Switching from low- to high-gas heat—If furnace control CPU switches from low-gas heat to high-gas heat, the control CPU switches inducer motor IDM speed from low to high. The high-heat pressure switch relay HPSR closes. When inducer motor IDM provides sufficient pressure to close high-heat pressure switch HPS, high-heat gas valve solenoid GV is energized. Blower motor BLWM switches to high-gas-heat airflow 5 sec after control CPU switches from low-gas heat to high-gas heat.
7. Switching from high- to low-gas heat—The control CPU will not switch from high-gas heat to low-gas heat while thermostat R-W circuit is closed when a single-stage thermostat is used.
8. Blower off delay—When thermostat is satisfied, R-W circuit opens, de-energizing gas valve GV, stopping gas flow to burners, and de-energizing humidifier terminals HUM and C
OM-24V. Inducer motorIDM remains energized
for a 5-sec post-purge period. A PSC blower motor BLWM continues operating at the same airflow for 90, 135, 180, or 225 sec (depending on selection at blower off delay switches SW-3 and SW-4). An ICM blower motor BLWM which had been operating at low- or high-gas-heat airflow operates at low-gas-heat airflow for 90 sec. If selected off delay period exceeds 90 sec, ICM blower motor BLWM operates at continuous blower airflow for remainder of off delay period. The furnace control CPU is factory set for a 135-sec blower off delay.
II. NON-ADAPTIVE HEATING MODE—TWO-STAGE THERMOSTAT WITH 2-STAGE HEATING
NOTE: The low-heat-only switch SW-2 in ON position selects
low-heat-only operation mode in response to closing thermostat R-W1 circuit when high-heat-only switch SW-1 is in OFF posi-
tion. Closing thermostat R to W1 and W2 circuits is required for high-gas-heat operation. When high-heat-only switch SW-1 is in ON position, it always initiates high-gas-heat operation when R-W1 circuit is closed, regardless of setting of low-heat-only switch SW-2 and regardless of whether R-W2 circuit is closed or open.
The start-up and shutdown functions and delays described in Section I apply to 2-stage heating mode as well, except for switching from low- to high-gas heat and vice versa.
1. When wall thermostat "calls for heat," R-W/W1 circuit closes for low-gas heat or R to W1-and-W2 circuits close for high-gas heat. The furnace control performs a self­check, verifies low-heat and high-heat pressure switches’ contacts LPS and HPS are open, and starts inducer motor IDM in low speed or high speed as appropriate.
2. Switching from low- to high-gas heat—If thermostat R-W/W1 circuit for low-gas heat is closed and R-W2 circuit for high-gas heat closes, the control CPU switches inducer motor IDM speed from low to high. High-heat pressure switch relay HPSR closes. When inducer motor IDM provides sufficient pressure to close high-heat pressure switch HPS, high-heat gas valve solenoid GV is energized. Blower motor BLWM switches to high-gas-heat airflow 5 sec after R-W2 circuit closes.
3. Switching from high- to low-gas heat—If thermostat R-W2 circuit for high-gas heat opens and R-W/W1 circuit for low-gas heat remains closed, the control CPU switches inducer motor IDM speed from high to low. High-heat pressure switch relay HPSR opens to de-energize high-heat gas valve solenoid GV. When inducer motor IDM reduces pressure sufficiently, high-heat pressure switch HPS opens. Low-heat gas valve solenoid GV remains energized as long as low-heat pressure switch LPS remains closed. Blower motor BLWM switches to low-gas-heat airflow 5 sec after R-W2 circuit opens.
III. COOLING MODE
1. Single-Speed Cooling Outdoor Unit a. The thermostat closes R to G-and-Y circuits. The R-Y
circuit starts outdoor unit, and R to G-and-Y/Y2 circuits operate furnace blower motor BLWM on cooling air­flow.
b. EAC terminals EAC-1 and EAC-2 are energized with
115 vac when blower motor BLWM is operating.
c. When thermostat is satisfied, R to G-and-Y circuits
open. The outdoor unit stops, and furnace blower motor BLWM continues operating at cooling airflow for an additional 90 sec.
2. Two-Speed Cooling Outdoor Unit a. The thermostat closes R to G-and-Y1 circuits for low
cooling or closes R to G-and-Y1-and-Y/Y2 circuits for high cooling. The R to Y1 circuits operate outdoor unit on low-cooling speed.
PSC—The R-G circuit operates furnace blower motor
BLWM at low-cooling airflow (same airflow as for low-gas heat and continuous blower).
ICM—The R to G-and-Y1 circuit operates furnace
blower motor BLWM at low-cooling airflow (65% of single-speed cooling airflow; different airflow than for low-gas heat).
The R to Y1-and-Y2 circuits operate outdoor unit on high-cooling airflow, and R to G-and-Y2 (-and-Y1, for ICM) circuits operate furnace blower motor BLWM at high-cooling airflow.
—4—
PSC—Two-speed high-cooling airflow is 100% of
single-speed cooling airflow.
ICM—Two-speed high-cooling airflow is 105% of
single-speed cooling airflow.
NOTE: Y1 is found in outdoor unit. The furnace controls blower motor BLWM airflow by sensing only G (PSC) or G-and-Y1 (ICM) for low-cooling airflow and Y/Y2 (PSC) or G-and-Y1-and­Y/Y2 (ICM) for high-cooling airflow.
b. EAC terminals EAC-1 and EAC-2 are energized with
115 vac when blower motor BLWM is operating at either cooling airflow.
c. When thermostat is satisfied, R to G-and-Y1 or
R to G-and-Y1-and-Y/Y2 circuits open. The outdoor unit stops, and furnace blower continues operating at the same cooling airflow for an additional 90 sec.
IV. CONTINUOUS BLOWER MODE
1. When R-G circuit is closed by thermostat, blower motor BLWM operates at:
PSC—Low-gas-heat airflow (identical to low-cooling air-
flow).
ICM—Low, Med, or High (50%, 65%, or 100% of single-
speed cooling airflow; different than low-gas-heat airflow). Low, Med, and High selection is described in Set-Up Procedures section of Appendix B.
Terminals EAC-1 and EAC-2 are energizedwith 115 vac as long as blower motor BLWM is operating.
2. During a "call for heat," blower motor BLWM stops during ignitor warm-up (17 sec), ignition (7 sec), and blower on delay (45 sec), allowing furnace heat exchangers to heat up quickly, after which blower motor BLWM operates at appropriate gas heating airflow.
3. The blower motor BLWM reverts to continuous blower airflow after heating cycle is completed.
PSC—In high-gas heat, the furnace control CPU holds
blower motor BLWM at high-gas-heat airflow dur­ing selected blower off delay period before reverting to continuous blower airflow.
ICM—In high-gas heat, the furnace control CPU and ICM
motor control hold blower motorBLWM atlow-gas­heat airflow for a 90-sec blower off delay period (irrespective of selected blower off delay) before reverting to continuous blower airflow.
4. When thermostat "calls for low-cooling," blower motor operates as follows:
PSC—The blower motor BLWM continues to operate at
low-cooling (continuous blower) airflow.
ICM—The blower motor BLWM switches to low-cooling
airflow or selected continuous-blower airflow, whichever is greater. Note that a "HI" selection for continuous blower airflow WILL provide more than normal airflow during 2-speed low-cooling.
5. When thermostat is satisfied, blower motor operates as follows:
PSC—The blower motor BLWM continues to operate at
continuous blower airflow.
ICM—The blower motor BLWM switches to continuous
blower airflow.
6. When thermostat "calls for high-cooling," blower motor BLWM operates at high-cooling airflow. When thermostat is satisfied, blower motor BLWM operates an additional 2 sec at high-cooling airflow before reverting back to con­tinuous blower airflow.
7. When R-G circuit is opened, blower motor BLWM contin­ues operating for an additional 90 sec, if no other function requires blower motor BLWM operation.
V. HEAT PUMP MODE NOTE: A dual-fuel thermostat or accessory interface kit is
required with single-speedheat pumps. See dual-fuel thermostator interface kit Installation Instructions for single-speed heat pump thermostat and interface connections. No interface kit is needed for 2-speed heat pumps. See 2-speed heat pump Installation Instruc­tions to determine whether a standard or dual-fuel heat pump thermostat is required and for thermostat connections.
1. Single-Speed Heat Pump Cooling a. The thermostat and interface kit close R to G-and-Y/Y2
(-and-O with an ICM blower motor) circuit(s) to operate furnace blower motor BLWM at cooling airflow. The Y/Y2 input to furnace control is necessary to provide adequate cooling airflow.
b. EAC terminals EAC-1 and EAC-2 are energized with
115 vac when blower motor BLWM is operating.
c. When thermostat is satisfied, furnace blower motor
BLWM continues operating at cooling airflow for an additional 90 sec.
2. Two-Speed Heat Pump Cooling a. PSC—The thermostat R-G circuit operates furnace
blower motor BLWM at low-cooling airflow.
ICM—The thermostat R to G-and-Y1-and-O circuits
operate furnace blower motor BLWM at low­cooling airflow.
b. The thermostat R to G-and-Y/Y2 (-and-Y1-and-O with
an ICM blower motor) circuits operate furnace blower motor BLWM at high-cooling airflow.
PSC—100% of single-speed cooling airflow. ICM—105% of single-speed cooling airflow. NOTE: The furnace controls blower airflow by sensing: (1.) Only G for low-cooling airflow with a PSC blower
motor.
(2.) G, Y1, and O for low-cooling airflow with an ICM
blower motor.
(3.) Y2 (with or without Y1) for single-speed cooling or
2-speed high-cooling airflow with a PSC blower motor.
(4.) G, Y1, Y/Y2, and O for 2-speed high-cooling
airflow with an ICM blower motor.
c. EAC terminals EAC-1 and EAC-2 are energized with
115 vac when blower motor BLWM is operating at either cooling airflow.
d. When thermostat is satisfied, furnace blower motor
BLWM continues operating at the same cooling airflow for an additional 90 sec.
3. Single-Speed Heat Pump Heating a. The thermostat (and accessory interface kit) R to G-and-
Y/Y2 circuits operate furnace blower motor BLWM at heat pump heating airflow (identical to cooling airflow with a PSC blower motor). Heating airflow is same as cooling airflow for Airflow Selector HP-EFFY selection and 90% of cooling airflow for HP-CMFT selection.
b. EAC terminals EAC-1 and EAC-2 are energized with
115 vac when blower motor BLWM is operating.
c. When thermostat is satisfied, furnace blower motor
BLWM continues operating at the same heat pump heating airflow for an additional 90 sec.
—5—
4. Two-Speed Heat Pump Heating a. The thermostat closes R to Y1-and-G circuit for low-heat
and operates furnace blower motor BLWM at heat pump low-heating airflow (identical to low-cooling airflow with PSC and may not be identical to low-cooling airflow with ICM, depending on selection at Airflow Selector). Closing R-Y/Y2 circuit to furnace (with Y1 and G for ICM) provides blower motor BLWM heat pump high-heating airflow.
NOTE: The furnace controls blower motor BLWM airflow by sensing:
(1.) Only G for heat pump low-heating airflow with a
PSC blower motor.
(2.) G and Y1 for heat pump low-heating airflow with
an ICM blower motor.
(3.) Y/Y2 for heat pump high-heating airflow with a
PSC blower motor.
(4.) G, Y1, and Y/Y2 for heat pump high-heating
airflow (105% of single-speed heating airflow) with an ICM blower motor.
b. EAC terminals EAC-1 and EAC-2 are energized with
115 vac when blower motor BLWM is operating at either heating airflow.
c. When thermostat is satisfied, furnace blower motor
BLWM continues operating at the same heating airflow for an additional 90 sec.
d. Opening only R-Y/Y2 circuit switches blower motor
BLWM to heat pump low-heating airflow.
VI. DEFROST
1. When furnace control R to W/W1-and-Y/Y2 circuits are closed, furnace control CPU continues blower motor BLWM operation at heat pump heating airflow until end of prepurge period, then stops BLWM until end of HSI ignitor on period (22 sec).
2. When installed with a heat pump, furnace control CPU automatically holds blower off time to 22 sec during HSI ignitor on period. After 17 sec of HSI ignitor on period, a
trial-for-ignition sequence occurs as describedabove forgas heating. After flame is proved and without a blower on delay, blower motor BLWM then operates at high-gas-heat airflow during defrost. For both single-speed and 2-speed heat pumps, defrost mode is in high-gas heat only.
3. When furnace control R-W/W1 circuit is opened, furnace control CPU begins normal inducer post purge period and blower motor BLWM continues operating for blower off delay period. If R-G circuit remains closed, blower motor BLWM reverts to continuous blower operation.
VII. COMPONENT TEST
The furnace features a component test system to help diagnose a system problem in the case of a component failure. To initiate component test procedure, ensure that there are no thermostat inputs to control and all time delays have expired. Short TWIN/TEST terminal to ground or C
OM-24V for 1 to 4 sec. (See
Appendix A.) NOTE: The component test feature will not operate if control is
receiving any thermostat signals or until all time delays have expired. The ICM blower motor speed ramp-up will slightly delay blower response times.
The component test sequence is as follows:
1. The furnace control performs a self-check, operates inducer motor on low speed for 7 sec and on high speed for 7 sec, then stops.
2. The hot surface ignitor is energized for 15 sec, then de-energized.
3. The blower motor operates at continuous fan (PSC­only—low-gas-heat / heat pump low-heating / low-cooling) airflow for 7 sec.
4. The blower motor operates at high-gas-heat airflow for 7 sec. The gas valve and humidifier terminal HUM are not energized for safety reasons.
5. The blower motor operates at single-speed cooling/heat pump heating airflow (or 2-speed heat pump high­heat/high-cooling) for 7 sec, then stops.
NOTE: The EAC terminals are energized when blower is oper­ating.
—6—
WARNING
Service should be performed only by qualified persons.
SERVICE
If status code recall is needed, do not remove power or blower door.
LED CODE STATUS
CONTINUOUS OFF Check for 115V at L1 and L2, and 24V at SEC1 and SEC2. CONTINUOUS ON Control has 24V power. RAPID FLASHING Line voltage polarity reversed. If twinned, 24V power
to one furnace may be out of phase with power to other furnace.
EACH OF THE FOLLOWING STATUS CODES IS A TWO-DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.
11 NO PREVIOUS CODE - Stored status codes are erased when power (115V or
24V) to control is interrupted or 48 hours after each fault is cleared.
12 BLOWER ON AFTER POWER UP - Blower runs for 90 seconds, if unit is
powered up during a call for heat (R-W/W1 closed). Note: 2-sec. ON-delay.
13 LIMIT OR FLAME ROLL-OUT (FRS) SWITCH LOCKOUT - Auto-reset after
three hours. FRS switch requires manual-reset. Check for: - Refer to #33
14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34. 21 GAS HEATING LOCKOUT - Control will NOT auto-reset.
Check for: - Mis-wired gas valve - Defective control (valve relay)
22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is
de-energized. Inducer will run until fault is cleared. Check for: - Leaky gas valve - Stuck-open gas valve
23 LOW- OR HIGH-HEAT PRESSURE SWITCH DID NOT OPEN
Check for: - Obstructed pressure tubing
- Defective pressure switch (stuck closed)
24 SECONDARY VOLTAGE FUSE IS OPEN
Check for: - Short-circuit in secondary voltage (24V) wiring
31 HIGH-HEAT PRESSURE SWITCH OR RELAY DID NOT CLOSE OR
REOPENED Check for: -Control relay may be defective - Refer to #32
32 LOW-HEAT PRESSURE, DRAFT SAFEGUARD , OR AUX-LIMIT
(DOWNFLOW ONLY*) SWITCH DID NOT CLOSE OR REOPENED
Check for: - Proper vent sizing (and condensate pitch with side-wall vent)
- Low inducer voltage (115v) * Blower motor and capacitor
- Defective inducer motor - Defective pressure switch
- Excessive wind - Restricted vent
- Inadequate combustion air supply
- Disconnected or obstructed pressure tubing
33 LIMIT OR FLAME ROLL-OUT (FRS) SWITCH IS OPEN - FRS switch
requires manual-reset. Check for: - Inadequate combustion air supply (FRS switch only)
- Dirty filter or restricted duct system - Loose blower wheel
- Defective switch or connections
- Blower motor or capacitor failure
34 IGNITION-PROVING FAULT - Control will retry three times before lockout #14.
Check for: - Oxide buildup on flame-proving sensor (clean with fine sandpaper).
- Proper flame-proving microamps (0.5 minimum)
- Proper control ground continuity
- Flame-proving sensor must be ungrounded
- Smooth flame carryover and ignition - Manual valve(s) OFF
43 LOW-HEAT PRESSURE, DRAFT SAFEGUARD, OR AUXILIARY LIMIT
SWITCH OPEN WHILE HIGH-HEAT PRESSURE SWITCH IS CLOSED
Check for: - Disconnected or obstructed pressure tubing
- Defective pressure switch (stuck open)
- Refer to #32 and #33
45 REPLACE CONTROL
320893-101 REV. A
A94169
Fig. 1—Service Information Label
—7—
START HERE—IF A PROBLEM EXISTS, THE SERVICE TECHNICIAN SHOULD ALWAYS BEGIN TROUBLESHOOTING HERE.
SPECIAL NOTE: ALL VOLTMETERS ARE NOT THE SAME; YOUR VOLTAGE READINGS WILL VARY. THIS APPLIES TO THE ENTIRE CONTENT OF THIS TROUBLESHOOTING MANUAL. THEY ARE NOT ABSOLUTE VALUES. CORRECT 115-VAC VOLTAGE, CURRENT, AND POWER MEASUREMENTS CANNOT BE MADE ON ICM FURNACES UNLESS USING A TRUE RMS METER.
STEP ACTION YES NO GO TO
Remove control door first. DO NOT REMOVE BLOWER DOOR! Removing
1.
2. Is RED LED status light blinking rapidly without a pause? 3 4
3. Go to page number indicated in Index for RAPID FLASHING LED. INDEX
4.
5.
6. Go to page number indicated in Index for section covering the status code. INDEX
7.
8.
9.
10. Does problem appear to be low cooling airflow? 11 12
11.
12.
13. Does furnace respond to the call for heat? 14 28
14.
15.
16.
17.
18.
19. Make sure power is being supplied to furnace. 20
20.
21.
22. Do you have 115 vac across L1 and L2? 24 23
23.
24. Do you have 24 vac across SEC-1 and SEC-2? 25 26
25. Replace 2-stage furnace control. 18
26. Do you have 115 vac across PR1 and PR2? 27 25
27.
28. Do you have 24 vac across W/W1 and C
29.
blower door interrupts power (115-vac or 24-vac) and erases previous status codes stored in memory. Is RED LED status light on?
Is RED LED status light blinking ON/OFF slowly with a combination of short and long flashes?
Determine status code. The status code is a 2 digit number with the first digit determined by the number of short flashes and the second digit by the number of long flashes.
To retrieve previous codes, no thermostat inputs to control must be present and all time delays must have expired. Disconnect 1 of the RED main limit wires 1 to 4 sec until RED LED status light goes out, then reconnect it and read status code. To recover additional codes repeat this procedure. The 2-stage furnace control is capable of retaining 5 previous status codes. NOTE: DO NOT leave RED wire disconnected for longer than 4 sec as control will assume an over-temperature condition exists and will respond with indoor blower operation.
Was there a previous status code other than code 11? NOTE: Status codes are erased after 48 hr or whenever power (115-vac or 24­vac) is interrupted.
Go to page number indicated in Index for section covering the first previous sta­tus code.
Go to page number indicated in Index for section covering IMPROPER COOL­ING AIRFLOW.
Set thermostat to call for heat and set thermostat fan control to AUTO position if equipped.
Observe operation of furnace for 20 minutes or until RED LED status light starts blinking.
Does RED LED status light blink ON/OFF slowly with a combination of short and long flashes?
Is temperature rise below range specified on rating plate when unit is operating in high heat? NOTE: If temperature rise is above range specified on rating plate, refer to Start-Up and Adjustment section in Installation, Start-Up, and Operating Instruc­tions.
Go to page number indicated in Index for section covering HIGH HEAT TEM­PERATURE RISE TOO LOW (COLD BLOW).
Go to page number indicated in Index for CLEANUP AND START-UP IN­STRUCTIONS.
Check fuses, breakers, or manual disconnects to be sure they are correctly set. If not, reset them and go back to Step 1.
Remove blower door and depress door switch. Use a piece of tape to hold switch closed.
Turn power off. Check continuity of power leads and door switch. If necessary repair power leads and/or replace door switch.
Replace transformer. If transformer fails again, replace transformer and 2-stage furnace control.
OM-24V on 2-stage furnace control? 25 29
You have a defective thermostat or a break in wiring between thermostat and furnace. Fix problem.
219 —
57 —
—— 6
—— 8
910 —
INDEX
INDEX
—— 13
—— 15
516 —
17 18
INDEX
INDEX
—— 21
—— 22
—— 18
—— 18
—— 18
—8—
RAPID FLASHING LED—INDICATES LINE VOLTAGE POLARITY IS REVERSED, OR THE TRANSFORMERS ARE OUT OF PHASE IN TWINNED UNITS.
STEP ACTION YES NO GO TO
1. Is this furnace twinned with another furnace? 7 2
2.
3. Do you have 115 vac across L2 and chassis ground? 4 6
4. Line voltage polarity is reversed. Fix problem. 5
5.
6. Replace 2-stage furnace control. 5
7.
8. Is RED LED status light blinking rapidly in only 1 of the twinned units? 9 16
9. Are fuses, breakers, or manual disconnects to problem unit correctly set? 11 10
10. Fix problem. —— 5
11. Are Master and Slave Auxiliary Limit switches properly set? 12 10
12. Do you have 115 vac across L1 and L2 in problem unit? 13 15
13. Do you have 24 vac across SEC-1 and SEC-2 in problem unit? 6 14
14. Replace transformer. 5
15.
16.
17.
18.
19.
Remove blower door and depress door switch. Use a piece of tape to hold switch closed.
Go to page number indicated in Index for CLEANUP AND START-UP IN­STRUCTIONS.
Remove blower doors and depress door switch in each unit. Use tape to hold switches closed.
Turn power off to both units. Check continuity of power leads and door switch in problem unit. If necessary repair power leads and/or replace door switch in problem unit.
Check furnace circuit breaker location in service panel. On single-phase (residential) systems, each furnace circuit breaker should be located directly across from each other in service panel, or each furnace circuit breaker should be located on the same side of service panel, but must skip 1 space to be connected to the same leg of the 1-phase power supply. On 3-phase (commercial) systems, each furnace circuit breaker should be lo­cated directly across from each other in service panel, or each furnace circuit breaker should be located on the same side of service panel, but must skip 2 spaces to be connected to the same leg of the 3-phase power supply.
Check 115-vac power lead connections at 2-stage furnace control of each fur­nace. The BLACK lead goes to L1 and the WHITE lead goes to L2.
Check 115-vac transformer lead connections at 2-stage furnace control of each furnace. The BLACK lead goes to PR1 and the WHITE lead goes to PR2.
If circuit breaker location and 115-vac wiring is correct, reverse transformer sec­ondary lead connections SEC-1 and SEC-2 in master furnace.
—— 3
INDEX
—— 8
—— 5
—— 17
—— 18
—— 19
—— 5
IMPROPER COOLING AIR FLOW—GENERALLY, THIS INDICATES THE Y/Y2 THERMOSTAT LEAD IS NOT CONNECTED TO Y/Y2 AT FURNACE, OR BLOWER MOTOR HAS FAILED.
STEP ACTION YES NO GO TO
1.
2.
3. Make sure thermostat fan control is in AUTO position if equipped. 4
4. Do you have 24 vac across Y/Y2 and C
5.
6. Fix problem. —— 7
7.
8. Does blower motor turn on? Wait several sec to verify. 31 9
9. Remove tape from door switch and turn power off at main disconnect. 10
10. Does blower wheel rub against blower housing? 6 11
11. Does blower wheel turn freely? 12 13
12. Is blower wheel firmly mounted on motor shaft? 14 6
13.
14.
15.
16. Make sure thermostat fan control is in AUTO position if equipped. 17
17. Does furnace have a variable-speed ICM blower motor? 18 24
Remove blower door and depress door switch. Use a piece of tape to hold switch closed.
Set thermostat to call for cooling. If thermostat does not have G connection, jumper across thermostat terminals R and G.
OM-24V on 2-stage furnace control? 8 5
You have a defective thermostat, or a break in wiring between thermostat and furnace, or the Y/Y2 thermostat terminal is not wired to thermostat.
Go to page number indicated in Index for CLEANUP AND START-UP IN­STRUCTIONS.
Replace blower motor. On variable-speed ICM blower motors, inspect electron­ics portion of failed motor for water damage. If present, find source of water and fix. Check A-coil and/or humidifier.
Turn power back on. Depress door switch. Use a piece of tape to hold switch closed.
Set thermostat to call for cooling. If thermostat does not have G connection, jumper across thermostat terminals R and G.
—— 2
—— 3
—— 6
INDEX
—— 7
—— 15
—— 16
—9—
STEP ACTION YES NO GO TO
18. Do you have 115 vac across BLACK and WHITE power leads at blower motor. 20 19
19.
STEP TERMINAL CONNECTIONS* VOLTAGE ACTION
20.
21.
22.
23.
STEP ACTION YES NO GO TO
24. Do you have 115 vac across HI-COOL and high voltage COMMON? 26 25
25. Replace 2-stage furnace control. 7
26. Remove tape from door switch and turn power off at main disconnect. 27
27.
28.
29.
30.
31. Does furnace have a variable-speed ICM blower motor? 34 32
32. Do you have 115 vac across HI-COOL and high voltage COMMON? 33 25
33.
STEP TERMINAL CONNECTIONS* VOLTAGE ACTION
34.
35.
36.
37.
STEP ACTION YES NO GO TO
38.
39.
40.
You have an open wire or bad terminal on either the BLACK or WHITE wire between 2-stage furnace control and blower motor, or the power choke (if equipped) failed. Fix problem.
PL4-1
YELLOW (+)
PL4-2
BLUE (+)
PL4-5
RED (+)
PL7-2
YELLOW (+)
PL7-12
BLUE (+)
PL7-13
RED (+)
PL7-1
YELLOW (+)
PL7-11
GREEN (+)
PL7-14
RED (+)
PL9-14
YELLOW (+)
PL9-15
GREEN (+)
PL9-12
RED (+)
Note location of all blower leads, then disconnect blower motor leads from 2-stage furnace control and capacitor.
Do you have continuity between the following motor leads:
• RED to WHITE
• YELLOW to WHITE
• BROWN to BROWN
• BLUE to WHITE
• BLACK to WHITE
• BROWN to WHITE
Replace capacitor. If problem still exists after replacing capacitor, replace blower motor.
Replace blower motor. If problem still exists after replacing blower motor, re­place capacitor.
• Check blower motor speed selection. Refer to Appendix E to evaluate external static.
• Check filter(s) and ductwork for restrictions.
• Check outdoor unit for correct suction pressure and verify charge.
PL4-1
YELLOW (+)
PL7-2
YELLOW (+)
PL7-1
YELLOW (+)
PL9-14
YELLOW (+)
Is YELLOW COOL SIZE jumper on EZ-SELECT airflow control set to match needed tons for cooling or heat pump system? (See Table 1.)
Set YELLOW COOL SIZE jumper on EZ-SELECT airflow control to match needed tons for cooling or heat pump system? (See Table 1.)
Note position of GREEN CONTINUOUS-FAN CFM jumper on EZ-SELECT air­flow control, then disconnect it.
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
PL4-3
BLACK (-)
PL4-3
BLACK (-)
PL4-3
BLACK (-)
PL7-10
BLACK (-)
PL7-10
BLACK (-)
PL7-10
BLACK (-)
PL7-8
BLACK (-)
PL7-8
BLACK (-)
PL7-9
BLACK (-)
PL9-3
BLACK (-)
PL9-3
BLACK (-)
PL9-1
BLACK (-)
PL4-3
BLACK (-)
PL7-10
BLACK (-)
PL7-8
BLACK (-)
PL9-3
BLACK (-)
-5 vdc to -10 vdc
-5 vdc to -13 vdc
24 vac
-5 vdc to -10 vdc
-5 vdc to -13 vdc
24 vac
-5 vdc to -10 vdc
5 vdc to 10 vdc
24 vac
-5 vdc to -10 vdc
5 vdc to 10 vdc
24 vac
-5 vdc to -10 vdc
-5 vdc to -10 vdc
-5 vdc to -10 vdc
-5 vdc to -10 vdc
If voltages are correct, go to Step 21. If not, replace 2-stage furnace control.
If voltages are correct, go to Step 22. If not, repair or replace ICM blower harness.
If voltages are correct, go to Step 23. If not, replace EZ­SELECT airflow control.
If voltages are correct, replace ICM blower motor. If not, repair or replace ICM blower harness.
If voltages are correct, go to Step 35. If not, replace 2-stage furnace control.
If voltages are correct, go to Step 36. If not, repair or replace ICM blower harness.
If voltages are correct, go to Step 37. If not, replace EZ­SELECT airflow control.
If voltages are correct, go to Step 38. If not, repair or replace ICM blower harness.
—— 7
—— 28
29 30
—— 7
—— 7
—— 7
40 39
—— 7
—— 41
—10—
STEP ACTION YES NO GO TO
41. Disconnect Y/Y2 thermostat lead from 2-stage furnace control. 42
42.
43.
Does blower motor change speed after Y/Y2 thermostat lead was disconnected from 2-stage furnace control?
Reconnect GREEN CONTINUOUS-FAN CFM jumper on EZ-SELECT airflow control to position noted earlier.
45 43
—— 44
44. Replace ICM blower motor. 7
45.
46.
* (+) and (-) designate Volt Ohm Meter Leads
Reconnect GREEN CONTINUOUS-FAN CFM jumper on EZ-SELECT airflow control to position noted earlier.
• Check filter(s) and ductwork for restrictions.
• Check outdoor unit for correct suction pressure and verify charge.
—— 46
—— 7
TABLE 1—COOLING AND HEAT PUMP SIZE SELECTIONS
TONS (12,000 BTUH) 1-1/2 2 2-1/2 3 3-1/2 4 5
Upflow/Horizontal
Unit Size
COOL SIZES (YELLOW WIRE)
036060 LO M-LO M-HI HI 048080 LO M-LO M-HI HI 060100 LO M-LO M-HI HI 060120 LO M-LO M-HI HI
NOTE: Confirm CFM/ton selection on EZ-SELECT airflow control.
HIGH-HEAT TEMPERATURE RISE TOO LOW—GENERALLY, THIS INDICATES THE HI SOLENOID IN GAS VALVE GV HAS FAILED OR FURNACE IS EXTREMELY UNDERFIRED.
STEP ACTION YES NO GO TO
Remove blower door. Make sure thermostat is NOT calling for heat. Note cur­rent settings for setup switches SW-1 and SW-2, then set SW-1 and SW-2 to
1.
2. Depress door switch. Use a piece of tape to hold switch closed. 3
3. Set thermostat to call for heat or jumper R and W/W1 thermostat terminals. 4
4.
5.
6. Is high-heat rate approximately the same as low-heat rate? 7 11
7.
8.
9.
10. Replace gas valve. —— 9
11. Is high-heat rate within 2% of that specified on rating plate? 13 12
12.
13. Is outdoor condensing unit operating during heating cycle? 16 14
14.
15. Check return air ducts in unheated spaces for leaks. 9
16. Fix problem. —— 9
OFF position. On variable-speed units, check VIOLET wire pin connection on EZ-SELECT airflow control for conformance with PIN marked on lower right of furnace rating plate. Set RED gas heat temperature rise jumper on MID.
When furnace is running in low heat, clock low-heat gas rate. You have 16 min­utes on this first call for heat before unit switches to high heat. On propane in­stallations, check manifold pressure.
When furnace is running in high heat, clock high-heat gas rate. On propane in­stallations, check manifold pressure.
Do you have 24 vac across gas valve terminals HI and C
OM-24V on 2-stage fur-
nace control during high heat? You have an open wire or bad terminal on BROWN wire from high-heat pres-
sure switch HPS to gas valve GV. Repair it or replace harness. Go to page number indicated in Index for CLEANUP AND START-UP IN-
STRUCTIONS.
Ensure gas inlet pressure and burner orifice are correct, then adjust gas valve to proper rate. If it cannot be adjusted to proper rate, replace gas valve.
Check temperature rise and external static pressure with blower door in place. Temperature rise should be mid-range or higher than midpoint of range stated on furnace rating plate. External static pressure must not exceed 0.5 in. wc for PSC and 0.7 in. wc for ICM motors. If return temperature is below 60°F, con­densation may form on heat exchangers. If left uncorrected, failure will result.
—— 2
—— 5
—— 6
10 8
—— 9
INDEX
—— 9
—— 15
—11—
Status Code 11
NO PREVIOUS CODE—STORED STATUS CODES ARE ERASED AFTER 48 HR OR WHENEVER POWER SOURCE (115-VAC OR 24-VAC) IS INTERRUPTED. RUN SYSTEM THROUGH A HEATING OR COOLING CYCLE TO CHECK SYSTEM.
Status Code 12
BLOWER ON AFTER POWERUP—BLOWER WILLRUN FOR90 SEC WHEN FURNACEPOWER ISINTERRUPTED ANDLATER RESTORED DURING A CALLFOR HEAT(R-W/W1 CLOSED).IF THISSTATUS CODEREPEATS EVERYCOUPLE OFMINUTES, IT IS PROBABLY CAUSED BY A DIRECT SHORT IN PRESSURE SWITCH CIRCUITS, GAS VALVEGV, WIRING TO GASVALVE GV, OR HUMIDIFIER COIL.
STEP ACTION YES NO GO TO
1.
2. Depress door switch. Use piece of tape to hold switch closed. 3
3.
4.
5.
6. Do you have less than 90 vac across PR1 and PR2 on 2-stage furnace control? 7 10
7.
8. Fix problem. —— 9
9.
10. Disconnect R thermostat lead. 11
11.
12. Replace transformer. 9
13.
14. Does hot surface ignitor HSI come on during cycle? 15 19
15. Disconnect humidifier lead from HUM terminal on 2-stage furnace control. 16
16.
17.
18.
19. There is a direct short in YELLOW wire from low-heat pressure switch LPS. 8
20. While unit is operating in low heat, jumper R and W2 thermostat terminals. 21
21.
22. Disconnect BROWN wire to gas valve GV. 23
23. Does furnace still abruptly shut down as described in Step 21? 25 24
24. Replace gas valve. —— 9
25.
26.
Remove blower door and disconnect W/W1 thermostat lead from 2-stage fur­nace control.
Set thermostat to call for heat and set thermostat fan control to AUTO position if equipped. Reconnect W/W1 thermostat lead to 2-stage furnace control.
Does furnace keep repeating the following cycle? Induced draft motor IDM runs, induced draft motor IDM stops, blower motor BLWM runs for 90 sec while RED LED status light flashes status code 12.
Do you have less than 17 vac across R and C trol?
Make sure wire gage between main fuse box and furnace complies with wire size specification in Installation, Start-Up, and Operating Instructions.
Go to page number indicated in Index for CLEANUP AND START-UP IN­STRUCTIONS.
Do you have less than 19 vac across R and C trol?
The thermostat and/or thermostat wires are loading down transformer. Replace thermostat or repair thermostat wires.
Does furnace still alternately cycle induced draft motor IDM and blower motor BLWM as described in Step 4.
There is a direct short in wiring to humidifier solenoid coil, diode bridge (if used), or humidifier solenoid coil.
There is a short in gas valve GV or wiring to gas valve GV. Refer to Appendix G to check gas valve GV.
Does furnace abruptly shut down with no inducer post-purge and then run blower motor BLWM for 90 sec while RED LED status light flashes status code
12.
There is a direct short to ground in GRAY or BROWN wires connected to high­heat pressure switch HPS.
Power to furnace was probably interrupted, or line voltage was too low during a call for heat. This is normal operation. Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.
OM-24V on 2-stage furnace con-
OM-24V on 2-stage furnace con-
—— 2
—— 4
520 —
614 —
—— 8
INDEX
12 13
—— 9
18 17
—— 8
—— 8
22 26
—— 8
INDEX
—12—
Status Code 13
LIMIT (LS) OR FLAME ROLLOUT (FRS) SWITCH LOCKOUT—THIS STATUS CODE INDICATES THAT LIMIT SWITCH OPENED 5 TIMES FOR AT LEAST 3 MINUTESEACH TIME DURING 1 THERMOSTAT CYCLE. THE 2-STAGE FURNACE CONTROL WILL AUTO-RESET IN 3 HR. FLAME ROLLOUT SWITCH FRS REQUIRES MANUAL-RESET.
STEP ACTION YES NO GO TO
1.
2. Depress door switch. Use piece of tape to hold switch closed. 3
3. Set thermostat to call for heat or jumper R and W/W1 thermostat terminals. 4
4. Does blower motor turn on within 1 minute of ignition? 28 5
5.
6. Does blower wheel rub against blower housing? 7 9
7. Fix problem. —— 8
8.
9. Does blower wheel turn freely? 10 11
10. Is blower wheel firmly mounted on motor shaft? 12 7
11.
12.
13. Does furnace have a variable-speed ICM blower motor? 14 21
14. Do you have 115 vac across BLACK and WHITE power leads at blower motor. 16 15
15.
16. Wait 1 minute after burners ignite before proceeding to step 17. 17
STEP TERMINAL CONNECTIONS* VOLTAGE ACTION
17.
18.
19.
20.
STEP ACTION YES NO GO TO
21. Do you have 115 vac across LO-GAS-HEAT and high voltage COMMON? 23 22
22. Replace 2-stage furnace control. 8
23. Remove tape from door switch and turn power off at main disconnect. 24
24.
25.
Remove blower door. Make sure thermostat is NOT calling for heat. This action resets control.
Remove tape from door switch, turn power off at main disconnect, and remove jumper across R and W/W1.
Go to page number indicated in Index for CLEANUP AND START-UP IN­STRUCTIONS.
Replace blower motor. On variable-speed ICM blower motors, inspect electron­ics portion of failed motor for water damage. If present, find source of water and fix. Check A-coil and/or humidifier.
Turn power back on. Depress door switch. Use a piece of tape to hold switch closed, then jumper R and W/W1 thermostat terminals.
You have an open wire or bad terminal on either the BLACK or WHITE wire between 2-stage furnace control and blower motor, or the power choke (if equipped) failed. Fix problem.
HUM
WHITE (+)
PL4-2
BLUE (+)
PL4-5
RED (+)
PL7-12
BLUE (+)
PL7-13
RED (+)
PL7-11
GREEN (+)
PL7-14
RED (+)
PL9-2
WHITE (+)
PL9-15
GREEN (+)
PL9-12
RED (+)
Note location of all blower leads, then disconnect blower motor leads from 2-stage furnace control and capacitor.
Do you have continuity between the following motor leads:
• RED to WHITE
• YELLOW to WHITE
• BROWN to BROWN
• BLUE to WHITE
• BLACK to WHITE
• BROWN to WHITE
to
to
to
to
to
to
to
to
to
to
C
OM-24V
(-)
PL4-3
BLACK (-)
PL4-3
BLACK (-)
PL7-10
BLACK (-)
PL7-10
BLACK (-)
PL7-8
BLACK (-)
PL7-9
BLACK (-)
PL9-3
BLACK (-)
PL9-3
BLACK (-)
PL9-1
BLACK (-)
24 vac
-5 vdc to -13 vdc
24 vac
-5 vdc to -13 vdc
24 vac
5 vdc to 10 vdc
24 vac
24 vac
5 vdc to 10 vdc
24 vac
If voltages are correct, go to Step 18. If not, replace 2-stage furnace control.
If voltages are correct, go to Step 19. If not, repair or replace ICM blower harness.
If voltages are correct, go to Step 20. If not, replace EZ­SELECT airflow control.
If voltages are correct, replace ICM blower motor. If not, repair or replace ICM blower harness.
—— 2
—— 6
INDEX
—— 8
—— 13
—— 8
—— 25
26 27
—13—
STEP ACTION YES NO GO TO
26.
27.
28. Does furnace have a variable-speed ICM blower motor? 30 29
29.
STEP TERMINAL CONNECTIONS* VOLTAGE ACTION
30.
31.
STEP ACTION YES NO GO TO
32.
33.
34. Replace ICM blower motor. 8
* (+) and (-) designate Volt Ohm Meter Leads
Replace capacitor. If problem still exists after replacing capacitor, replace blower motor.
Replace blower motor. If problem still exists after replacing blower motor, re­place capacitor.
Lockout was caused by excessive return-air restriction. Check filter and return­air grilles for blockage. Add more return-air openings if necessary. Use Appen­dix E to evaluate external static pressure.
HUM
WHITE (+)
PL9-2
WHITE (+)
Make sure blower off delay is set to 135 sec or more, then disconnect W/W1 thermostat lead from 2-stage furnace control.
Does blower motor change speed 90 sec after W/W1 thermostat lead was dis­connected from 2-stage furnace control.
to
to
C
OM-24V
(-)
PL9-3
BLACK (-)
24 vac
24 vac
If voltages are correct, go to Step 31. If not, replace 2-stage furnace control.
If voltages are correct, go to Step 32. If not, repair or replace ICM blower harness.
—— 8
—— 8
—— 8
—— 33
29 34
Status Code 14
IGNITION LOCKOUT—THIS STATUS CODE INDICATES FURNACE FAILED TO IGNITE GAS AND/OR PROVE FLAME IN 4 ATTEMPTS. THE 2-STAGE FURNACE CONTROL WILL AUTO-RESET IN 3 HR. REFER TO STATUS CODE 34.
Status Code 21
GAS HEATING LOCKOUT—THIS STATUS CODE INDICATES MAIN GAS VALVE RELAY MGVR ON 2-STAGE FURNACE CONTROL IS STUCK CLOSED, OR THERE IS A MISWIRE/SHORT TO GAS VALVE WIRING. THE 2-STAGE FURNACE CONTROL WILL NOT AUTO-RESET.
STEP ACTION YES NO GO TO
1. Turn power off and set thermostat to OFF position. Then turn power back on. 2
2. Does status code 21 flash? 3 6
3. There is a miswire or short to gas valve wiring. 4
4. Fix problem. —— 5
5.
6. Does a different status code flash? 7 8
7. Go to page number indicated in Index for section covering the status code. INDEX
8.
9. Jumper R and W/W1 thermostat terminals. 10
10. Does status code 21 start flashing when low-heat pressure switch LPS makes? 11 12
11. Replace 2-stage furnace control. 5
12. Does a different status code flash? 7 13
13.
14. Jumper R, W/W1, and W2 thermostat terminals on 2-stage furnace control. 15
15.
16. Replace gas valve. —— 5
17. Cycle furnace several times to check for intermittent operation. 18
Go to page number indicated in Index for CLEANUP AND START-UP IN­STRUCTIONS.
Remove blower door and depress door switch. Use a piece of tape to hold switch closed.
Disconnect jumper wire across R and W/W1 thermostat terminals and wait until blower stops.
Does status code 21 start flashing when high-heat pressure switch HPS makes?
INDEX
—— 9
—— 14
16 17
—14—
Loading...
+ 32 hidden pages