Bryant 330JAV, 331JAV User Manual

service and
330JAV
maintenance procedures
PLUS 80 2-STAGE GAS-FIRED INDUCED-COMBUSTION FURNACES
NOTE: Read the entire instruction manual before starting the installation.
This symbol indicates a change since the last issue.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS.....................................................1
INTRODUCTION..........................................................................2
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE ................................................................................2
Cleaning and/or Replacing Air Filter.......................................2
Blower Motor and Wheel.........................................................3
Cleaning Heat Exchanger.........................................................4
Electrical Controls and Wiring.................................................6
WIRING DIAGRAMS...................................................................7
TROUBLESHOOTING .................................................................7
EFFICIENCY RATING CERTIFIED
331JAV
Series D
Cancels: SP04-65 SP04-73
11-01
r
o
p
C
o
r
r
e
i
r
r
a
C
R
E
G
I
S
I
T
S
O
9
0
REGISTERED QUALITY SYSTEM
Fig. 1—Model 330JAV Horizontal
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified person­nel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, tags, and labels attached to or shipped with the unit and other safety precautions that may apply.
a
t
i
o
n
CERTIFIED
®
E
R
0
1
M
R
I
F
D
E
3
8
8
2
A
#
A95137
A94086
Fig. 2—Model 331JAV Downflow
A94085
Fig. 3—Model 330JAV Upflow
Follow all safety codes. In the United States, follow all safety codes including the National Fuel Gas Code (NFGC) NFPA No. 54-1999/ANSI Z223.1-1999. In Canada, refer to the current edition of the National Standard of Canada CAN/CGA-B149.1­and .2-M00 Natural Gas and Propane Gas Installation Codes (NSCNGPIC) and Amendment No. 1. Wear safety glasses and work gloves. Have fire extinguisher available during start-up and adjustment procedures and service calls.
—1—
Recognize safety information. This is the safety-alert symbol . When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING: The ability to properly perform mainte-
nance on this equipment requires certain expertise, me-
chanical skills, tools, and equipment. If you do not
possess these, do not attempt to perform any maintenance
on this equipment other than those procedures recom-
mended in the Users Manual. A FAILURE TO FOL-
LOW THIS WARNING COULD RESULT IN POS-
SIBLE DAMAGE TO THIS EQUIPMENT, SERIOUS
PERSONAL INJURY, OR DEATH.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible equip­ment failure, it is essential that periodic maintenance be performed on this equipment. Consult your local dealer as to proper frequency of maintenance and availability of a maintenance contract.
WARNING: Never store anything on, near, or in contact with furnace, such as:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds, plastic or plastic containers, gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids.
3. Paint thinners and other painting compounds, paper bags or other paper products. A failure to follow this warning could result in corrosion of the heat exchanger, fire, personal injury, or death.
INTRODUCTION
These procedures are for size 60,000 through 120,000 Btuh units.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE
CAUTION: Electrostatic discharge can affect electronic
components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electro­static potential.
1. Disconnect all power to the furnace. DO NOT TOUCH
THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODYS ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a persons hand during grounding will be satisfactorily discharged.
3. After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch un­grounded objects, etc.).
4. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touch­ing control or wires.
5. Use this procedure for installed and uninstalled (un­grounded) furnaces.
6. Before removing a new control from its container, dis­charge your bodys electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1. through 5. before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects.
WARNING: Turn off gas and electrical supplies to unit before performing any maintenance or service on it. Follow operating instructions on label attached to fur­nace. A failure to follow this warning could result in personal injury.
The minimum maintenance that should be performed on this equipment is as follows:
1. Check and clean air filter each month or more frequently if required. Replace if torn.
2. Check blower motor and wheel for cleanliness each heating and cooling season. Clean as necessary.
3. Check electrical connections for tightness and controls for proper operation each heating season. Service as necessary.
CAUTION: As with any mechanical equipment, per­sonal injury can result from sharp metal edges, etc.; therefore, be careful when removing parts.
I. CLEANING AND/OR REPLACING AIR FILTER
The air filter arrangement may vary depending on the application. NOTE: If the filter has an airflow direction arrow, the arrow must
point toward the blower.
WARNING: Never operate unit without a filter or with filter access door removed. A failure to follow this warning could result in fire, personal injury, or death.
To clean or replace filters, proceed as follows:
1. Downflowfilters installed in return-air duct. (see Fig. 4.) a. Turn off electrical supply before removing blower access
door. b. Remove blower access door. c. Reach up behind top plate, tilt filters toward center of
return-air plenum, remove filters. Replace filters if torn
or damaged.. d. Furnaces are equipped with permanent, washable filters. e. Clean filters by spraying tap water through filter from
opposite direction of airflow.
2
INSTALLATION
POSITION
OF FILTERS
RETURN-AIR
PLENUM
AIRFLOW
MOUNTING
SCREWS
RELIEF
BOX
GAS
VALVE
CONTROL
FLUE COLLAR
BLOCKED VENT SAFEGUARD
PRESSURE SWITCH
FLUE COLLECTOR BOX
ACCESS DOOR
A88486
Fig. 4Downflow Filter Arrangement
f. Rinse and let dry. Oiling or coating of filters is not
recommended or required. g. Reinstall filters. h. Replace blower access door and turn on electrical supply
to furnace.
2. Upflow/Horizontal–filters installed in media cabinet adja­cent to furnace (See Fig. 5.)
a. Turn off electrical supply to furnace b. Remove filter cabinet door. c. Slide filter out of cabinet. d. If equipped with permanent, washable filter, clean filter
by spraying cold tap water through filter in opposite direction of airflow. Rinse filter and let dry. Oiling or coating of the filter is not recommended.
e. If equipped with factory-specified disposable media
filter, replace only with media filter having the same part
number and size. f. Slide filter into cabinet. g. Replace filter cabinet door. h. Turn on electrical supply to furnace.
3. Upflow/Horizontal–filter(s) installed in side(s) and/or bot­tom of blower compartment (See Fig. 5.)
a. Turn off electrical supply before removing blower and
control access doors.
b. Release filter retainer from clip at front of furnace
casing. (See Fig. 5.) For side return, clips may be used
on either or both sides of the furnace. c. Slide filter out. d. Clean filters by spraying tap water through filter from
opposite direction of airflow.
FILTER RETAINER
WASHABLE FILTER FURNACE
A00293
WASHABLE FILTER OR DISPOSIBLE MEDIA FILTER IN FILTER CABINET
HUMHUM
C
24V
OM
GRYW
Fig. 5Model 330JAV Upflow
e. Rinse and let dry. Oiling or coating of filter is not
recommended or required. f. Place filter in furnace. g. Replace blower and control access doors and turn on
electrical supply to furnace.
II. BLOWER MOTOR AND WHEEL
The following items should be performed by a qualified service technician:
For long life, economy, and high efficiency, clean accumulated dirt and grease from blower wheel and motor annually.
The inducer and blower motors are pre-lubricated and require no additional lubrication. These motors can be identified by the absence of oil ports on each end of the motor.
Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Remove blower access door.
3. Downflow only: a. Disconnect vent connector from furnace flue collar. (See
Fig. 6.) b. Remove internal vent pipe enclosure cover. c. Disconnect and remove short piece of vent pipe from
within furnace. d. Disconnect and remove vent pipe enclosure. Push bot-
tom side backward to release tabs.
NOTE: Vent pipe is SCREWED and RTV sealed to relief box.
4. Disconnect blower leads from furnace control. Note wire color and location for reassembly. Also, disconnect auxil­iary limit switch leads (downflow only, if present). All other factory wires can be left connected, but field thermostat connections may need to be disconnected de­pending on their length and routing.
5. Remove 2 screws securing control and transformer support to furnace.
6. Hang control and transformer support to front of furnace casing.
3
FLUE COLLAR
NOTE: Refer to Table 1 for motor speed lead relocation if leads were not identified before disconnection.
VENT PIPE
AUXILIARY
LIMIT
SWITCH
MOUNTING
SCREWS
RELIEF
BOX
ENCLOSURE
CONTROL
DRAFT SAFEGUARD SWITCH
PRESSURE SWITCHES
MANUAL RESET LIMIT SWITCHES
A99092
Fig. 6Model 331JAV Downflow
7. Remove screws holding blower assembly to blower deck and slide blower assembly out of furnace.
8. Clean blower wheel and motor using a vacuum with soft brush attachment. Do not remove or disturb balance weights (clips) on blower wheel blades. The blower wheel should not be dropped or bent as balance will be affected.
9. If greasy residue is present on blower wheel, remove wheel from the blower housing and wash it with an appropriate degreaser. To remove wheel: a. Mark blower wheel location on shaft before disassembly
to ensure proper reassembly.
b. Loosen setscrew holding blower wheel on motor shaft.
NOTE: Mark blower mounting arms, motor, and blower housing so motor and each arm is positioned at the same location during reassembly.
c. Mark blower wheel orientation and cutoff plate location
to ensure proper reassembly.
d. Remove screws securing cutoff plate and remove cutoff
plate from housing.
e. Remove bolts holding motor mounts to blower housing
and slide motor and mounts out of housing. Disconnect capacitor and ground wire attached to blower housing before removing motor.
f. Remove blower wheel from housing.
10. Reassemble motor and blower by reversing items 9a through 9f. Be sure to reattach ground wire.
11. Reinstall blower assembly in furnace.
12. Reinstall control box and support assembly in furnace.
13. Reconnect blower leads to furnace control and auxiliary limit switch leads (downflow only). Refer to furnace wiring diagram, and connect thermostat leads if previously disconnected. (See Fig. 11.)
TABLE 1SPEED SELECTOR
COLOR SPEED
Black High Cool
Yellow (When Present) Medium High Spare
Blue Medium Low Heat
Red Low Spare
White Common C
Orange (When Present) Medium Spare
FACTORY-
ATTACHED
TO
OM
CAUTION: Heating speed selection MUST be adjusted to provide proper temperature rise as specified on the rating plate. Failure to adjust the heating speed may shorten heat exchanger life.
14. Reinstall internal vent pipe and enclosure on downflow furnaces only by reversing items 3a through 3c.
NOTE: A releasing agent such as PAM cooking spray or equiva­lent (must not contain corn or canola oil, aromatic or halogenated hydrocarbons or inadequate seal may occur) and RTV sealant (G.E. 162, 6702, or Dow-Corning 738) are needed before starting installation. DO NOT substitute any other type of RTV sealant. G.E. 162 (P771-9003) is available through RCD in 3-oz tubes.
15. Reinstall vent connector to furnace flue collar. After fully assembling vent connector to furnace flue collar, securely fasten vent connector to flue collar with 2 field-supplied, corrosion-resistant, sheet metal screws located 180 degrees apart and midway up the collar.
16. Turn on electrical supply. Manually close blower access door switch. Use a piece of tape to hold switch closed. Check for proper rotation and speed changes between heating and cooling by jumpering R to W and then R to Y on furnace control thermostat terminals.
WARNING: Blower access door switch opens 115-v power to furnace control. No component operation can occur. Caution must be taken when manually closing this switch for service purposes. Failure to follow this warn­ing could result in electrical shock, personal injury, or death.
NOTE: If thermostat terminals are jumpered before blower ac­cess door switch is closed, blower will run for 90 sec before beginning a heating or cooling cycle.
17. If furnace is operating properly, remove tape to release blower access door switch, replace blower access door.
III. CLEANING HEAT EXCHANGER
The following steps should be performed by a qualified service technician:
NOTE: If the heat exchangers get a heavy accumulation of soot and carbon, they should be replaced rather than trying to clean them thoroughly due to their intricate design. A build-up of soot and carbon indicates that a problem exists which needs to be corrected, such as improper adjustment of manifold pressure, insufficient or poor quality combustion air, incorrect size, or damaged manifold orifice(s), improper gas, or a restricted heat exchanger. Action must be taken to correct the problem. If it becomes necessary to clean heat exchanger because of light dust or corrosion proceed as follows:
4
1. Turn gas and power to furnace to OFF.
2. Remove control and blower access doors.
3. Disconnect vent connector from furnace flue collar.
4. Disconnect internal vent pipe and enclosure on downflow furnaces only.
a. Remove vent pipe enclosure cover. b. Disconnect and remove short piece of vent pipe from
within furnace.
NOTE: Vent pipe is SCREWED and RTV sealed to relief box.
c. Remove vent pipe enclosure by removing screw in upper
back. Push bottom side backward to release tabs.
5. Remove 2 screws that secure relief box. (See Fig. 5 or 6.)
6. Disconnect wires to the following components. Mark wires to aid in reconnection of:
a. Draft safeguard switch. b. Inducer motor. c. Pressure switch(es). d. Limit overtemperature switch(es). e. Gas valve. f. Hot surface ignitor. g. Flame-sensing electrode. h. Flame rollout switch(es), if applicable.
7. Remove complete inducer assembly and relief box from furnace.
8. Remove screws that secure flue collector box to center panel. Be careful not to damage collector box.
9. Remove cell outlet plates.
IMPORTANT: Replace screws in center panel before cleaning.
10. Remove burner assembly and cell inlet plates.
IMPORTANT: Replace screws in center panel before cleaning. NOTE: Be very careful when removing burner assembly to avoid
breaking ignitor. See Fig. 7 for correct ignitor location.
11. Using field-provided small wire brush, steel spring cable, reversible electric drill, and vacuum cleaner, clean cells as follows:
a. Assemble wire brush and steel spring cable.
(1.) Use 48 in. of 1/4-in. diameter high-grade steel
spring cable (commonly known as drain clean-out or Roto-Rooter® cable).
(2.) Use 1/4-in. diameter wire brush (commonly known
as 25-caliber rifle cleaning brush).
NOTE: The materials needed in items (1.) and (2.) can usually be purchased at local hardware stores.
(3.) Insert twisted wire end of brush into end of spring
cable, and crimp tight with crimping tool or strike with ball-peen hammer. TIGHTNESS IS VERY IMPORTANT.
(4.) Remove metal screw fitting from wire brush to
allow insertion into cable.
b. Clean each heat exchanger cell.
(1.) Attach variable-speed, reversible drill to end of
spring cable (end opposite brush).
(2.) Insert brush end of cable into upper opening of cell
and slowly rotate with drill. DO NOT force cable. Gradually insert at least 36 in. of cable into 2 upper passes of cell. (See Fig. 8.)
11
CELL PANEL
HOT SURFACE IGNITOR ASSEMBLY
C
IGNITOR
L
7
"
8
C
BURNER
L
IGNITOR ASSEMBLY
32
"
A93347
BURNER
13
"
32
Fig. 7Position of Ignitor to Burner
A91252
Fig. 8Cleaning Heat Exchanger Cell
(3.) Work cable in and out of cell 3 or 4 times to obtain
sufficient cleaning. DO NOT pull cable with great force. Reverse drill and gradually work cable out.
(4.) Insert brush end of cable in lower opening of cell,
and proceed to clean 2 lower passes of cell in same manner as 2 upper passes.
(5.) Repeat foregoing procedures until each cell in
furnace has been cleaned.
(6.) Using vacuum cleaner, remove residue from each
cell.
(7.) Using vacuum cleaner with soft brush attachment,
clean burner assembly.
(8.) Reinstall cell outlet plates and screws FIRST; then,
reinstall cell inlet plates and burner assembly. Care must be exercised to center burners in cell openings.
12. Remove old sealant from center panel and collector box flange and apply new sealant to collector box flange and reinstall on center panel, making sure all screws are secure.
5
1-STAGE THERMOSTAT TERMINALS
WYRG
W2
COM
W/W1
Y/Y2
R G
NOTES: 1. Connect Y-terminal as shown for proper operation.
BLK
WHT
115-V FUSED
DISCONNECT
SWITCH
(WHEN REQUIRED)
BLK
WHT
GND
TWO-WIRE
HEATING-
ONLY
GND
JUNCTION BOX
CONTROL
FURNACE
FIVE
WIRE
BOX
24-V
TERMINAL
BLOCK
Fig. 9Heating and Cooling Application Wiring Diagram
for Single-Stage Thermostats and Single-Speed Condensing Units
NOTE: A releasing agent such as PAM cooking spray or equiva-
lent (must not contain corn or canola oil, aromatic or halogenated hydrocarbons or inadequate seal may occur) and RTV sealant (G.E. 162, 6702, or Dow-Corning 738) are needed before starting installation. DO NOT substitute any other type of RTV sealant. G.E. 162 (P771-9003) is available through RCD in 3-oz tubes.
13. Reinstall relief box and inducer assembly.
NOTE: If inducer assembly gasket is damaged, use RTV sealant to seal inducer assembly to collector box.
14. Reconnect wires to the following components: a. Draft safeguard switch. b. Inducer motor. c. Pressure switches. d. Limit overtemperature switch(es). e. Gas valve. f. Hot surface ignitor. g. Flame-sensing electrode. h. Flame rollout switch(es), if applicable.
15. Reinstall internal vent pipe and enclosure on downflow furnaces only by reversing items 4a through 4c.
NOTE: A releasing agent such as PAM cooking spray or equivalent (must not contain corn or canola oil, aromatic or halogenated hydrocarbons or inadequate seal may occur) and RTV sealant (G.E. 162, 6702, or Dow-Corning 738) are needed before starting installation. DO NOT substitute any other type of RTV sealant. G.E. 162 (P771-9003) is available through RCD in 3-oz tubes.
16. Reinstall vent connector to furnace flue collar. After fully assembling vent connector to furnace flue collar, securely fasten vent connector to flue collar with 2 field-supplied, corrosion-resistant, sheet metal screws located 180 degrees apart and midway up the collar.
17. Replace blower access door only.
18. Turn power and gas to ON.
FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-V WIRING
C
GND
GND
CONDENSING
UNIT
2. Some thermostats require a "C" terminal connection as shown.
3. If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.
FIELD-SUPPLIED
FUSED DISCONNECT
208/230- OR 460-V THREE PHASE
GND
208/230-V SINGLE PHASE
GND
19. Set thermostat and check furnace for proper operation.
20. Verify blower airflow and speed changes between heating and cooling.
21. Check for gas leaks.
22. Replace control door.
WARNING: Never use a match or other open flame to check for gas leaks. Use a soap-and-water solution. A failure to follow this warning could result in fire, personal injury, or death.
IV. ELECTRICAL CONTROLS AND WIRING NOTE: There may be more than 1 electrical supply to unit.
The electrical ground and polarity for 115-v wiring must be maintained properly. Refer to Fig. 9 and 10 for field wiring information and to Fig. 11 for unit wiring information. If the polarity is NOT correct, the furnace control will display rapid flashing on the status LED and prevent heat operation. The control system also requires an earth ground for proper operation of the microprocessor.
With power disconnected to unit, check all electrical connections for tightness. Tighten all screws on electrical connections. If any smoky or burned connections are noticed, disassemble the connec­tion, clean all parts and stripped wire, and reassemble properly and securely. Electrical controls are difficult to check without proper instrumentation; therefore, reconnect electrical power to unit and observe unit through 1 complete operating cycle.
The 24-v circuit contains an automotive-type, 3-amp fuse located on the main control. Any 24-v electrical shorts during installation, service, or maintenance could cause this fuse to blow. If fuse replacement is required, use ONLY a 3-amp fuse. The control will display code 24 when fuse needs replacement.
The control in this furnace is equipped with an LED status light to aid in installation, servicing, and troubleshooting. It can be viewed through the sight glass or window on blower access door. The control indicates status with the LED on continuously, rapid
A99071
6
BLK
WHT
115-V FUSED
DISCONNECT
BLK
WHT
GND
JUNCTION BOX
SWITCH
(WHEN REQUIRED)
FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-V WIRING
2-STAGE THERMOSTAT TERMINALS
SEVEN
W1 R
W2 Y2 G Y1
C
WIRE
THREE-WIRE
HEATING-
ONLY
GND
CONTROL
BOX
W2
COM
W/W1
Y/Y2
R G
24-V
GND
C Y1
Y2
2-SPEED CONDENSING UNIT
TERMINAL
BLOCK
FURNACE
NOTES: 1. Connect Y-terminal as shown for proper operation.
2. Some thermostats require a "C" terminal connection as shown.
3. If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.
Fig. 10Heating and Cooling Application Wiring Diagram
for 2-Stage Thermostats and/or 2-Speed Condensing Units
FIELD-SUPPLIED
FUSED DISCONNECT
GND
GND
GND
208/230- OR 460-V THREE PHASE
208/230-V SINGLE PHASE
A99072
flashing, or a code composed of 2 digits. (The first digit is the number of short flashes, the second is the number of longs flashes.) Refer to service label on blower compartment door for code explanations and useful troubleshooting suggestions. (See Fig. 12.)
It is important to note that power to furnace must not be interrupted and furnace blower door must not be removed until the LED status code(s) is recorded. When power to control is interrupted, status memory is erased.
The control will store up to 5 previous codes but will not store non-current codes longer than 48 hr. To retrieve previous codes, if present, no thermostat inputs to control must be present and all time delays must expire. Remove 1 of the red main limit wires 1 to 4 sec until the LED light goes out, then reconnect it. (See Fig. 5 and 6.) (Do not leave red wire disconnected for longer than 4 sec as control will assume an overtemperature condition exists and will respond with indoor blower operation.) This places control in status recall mode and displays first code stored in memory. Record code and repeat the disconnect and reconnect of red wire, recording each code until code 11 is displayed indicating no additional faults. After last code is displayed or after 2 minutes in the code recall mode, the control will return to normal standby mode.
Use any recorded fault codes, service label, and troubleshooting diagram on following pages to diagnose and correct any problem condition.
WIRING DIAGRAMS
Refer to Fig. 9, 10, and 11 for appropriate wiring diagrams.
TROUBLESHOOTING
Refer to service label. (See Fig. 12.) The Troubleshooting Guide can be a useful tool in isolating furnace operation problems. Beginning with the word Start,answer each question and follow the appropriate arrow to the next item.
The Guide will help you identify the problem or failed component. After replacing any component, verify correct operation sequence. More information is available in a seperate Troubleshooting Guide for 2-stage Gas-Fired Induced-Combustion Furnaces.
7
8
LS
RED
HEAT SET-UP SWITCH
NORM HI HT LO HT
BLOWER­OFF DELAY (SEC.)
90 SEC 135 SEC 180 SEC 225 SEC
RED
FRS1
(WHEN USED)
SWITCH 12
*
ON
OFF
SWITCH
3
*
ON
OFF
FRS2
OFF
ON
4
2-STAGE FURNACE CONTROL
OFF
ON
FACTORY
SETTINGS
*
BLOWER-OF F DE LAY
34
BLOWER-OFF DELAY LOW-HEAT ONLY
2 1
HIGH-HEA T ONLY
ON
OFF
W2 Com
W/W1 Y/Y2 R G HUM
24V
LPS
NOTE #8
ORN
RED
ORN
RED
ORN
ORN
DSS
ALS1
(WHEN USED)
NOTE #6
ALS2
ORN
RED
RED
TWIN TEST
YEL
LGPS
NOTE #8
FSE
(WHEN USED)
WHT
YEL
BLK
WHT
321
YEL
BLU
BRN
GRY
HI-COOL
GRN/YEL
BLU
1
TJ
2
M
3
S
LED
HI-GAS
HEAT
P1
LO-GAS HEAT
11 10
SPARE
12
SEC1
SEC2
LEGEND
ALS1 AUXILIARY LIMIT SWITCH, OVERTEMP. MANUAL RES ET, SPST (N.C.) ALS2 AUXILIARY LIMIT SWITCH, OVERTEMP. AUTO RESET, SPST (N.C.) BHI / LOR BLOWER MOTOR SPEED CH ANG E RELA Y, SPDT BHT / CLR BLOWER MOTOR SPEE D C HAN GE R ELA Y, SPDT BLWM BLOWER MOTOR, 4 or 5 -SPEED, PERMANENT-SPLIT-CAPACITOR BLWR BLOWER MOTOR RELAY, SPST (N.O.) CAP CAPACITOR CPU MICROPROCESSOR AND CIRCUITRY DSS DRAFT SAFEGUARD SWITCH (N.C.) EAC-1 ELECTRONIC AIR CLEANER CONNECTION (115 VAC, 1 AMP MAX.) EAC-2 ELECTRONIC AIR CLEANER CONNECTION (COMMON) FRS1 FLAME RO L L OUT SW ITCH OV ERTEM P . MANUA L RESET, SPST (N .C .) FRS2 FLAME RO L L OUT SW ITCH OV ERTEM P . MANUA L RESET, SPST (N .C .) FSE FLAME-PROVING SENSOR ELECTRODE FU1 FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED FU2 FUSE, FIELD INSTALLED GV GAS VALVE, REDUNDANT LOW-HEAT OPERATORS, 2-STAGE HPS HIGH-HEAT PRESSURE SWITCH, SPST (N.O.) HPSR HIGH-HEAT PRESSURE SW ITCH RE LAY, SPST (N.C.) HSI HOT-SURFACE IGNITER (115 VAC) HSIR HOT-SURFACE IGNITOR RELAY, SPST (N.O.) HUM 24VAC HUMIDIFIER CONNECTION (0.5 AMP. MAX.) IDM INDUCED DRAFT MOTOR, 2-SPEED, SHADED-POLE IDR INDUCER MOTOR RELAY, SPST (N.O.) IHI / LOR INDUCER MOTOR SPEED CHANGE RELAY, SPDT ILK BLOWE R D O O R IN TE R L OC K S W IT C H , SP S T (N .O .) JB JUNCTION BOX LED LIGHT-EMITTING DIODE FOR STATUS CODES LGPS LOW GAS-PRESSURE SWITCH, SPST (N.O.) LPS LOW-HEAT PRESSURE SWITCH, SPST (N.O.) LS LIMIT SWITCH, OVERTEMPERA TUR E-AU TO R ESE T, SPST (N.C.)
CONNECTION DIAGRAM
GRY
BLK
PL2
PR1 PR2
L1 L2
COMMON
EAC-2
EAC-1
SPARE
FU1
GRY
BRN
IDM
HSI
PL6
RED
12
BLK
123
WHT
RED
BLK
87 9
NOTE #15
MED LO
BLU
MGVR MAIN G AS V ALVE RELA Y, DPST (N.O.) PL1 12-CIRCUIT CONNECTOR
PL2 9-CIRCUIT CONNECTOR PL3 3-CIRCUIT IDM CONNECTOR PL6 2-CIRCUIT HSI CONNECTOR SW1 HIGH-HEAT-ONLY SWITCH, SPST (MANUAL) SW2 LOW-HEAT-ONLY SWITCH, SPST (MANUAL) SW3 & 4 BLOWER-OFF DELAY SETTING SWITCHES,
TJ TW IN N IN G JUMPER , S PD T F O R M A IN OR TRAN TRANSFOR MER-115VAC/24VAC
TWIN/TEST 1-CIRCUIT TWINNING B U S S C O N NECTO R,
HPS
BLU
GRN/YEL
GRN/YEL
ILK
WHT
BLK
WHT
PL3
WHT
BLK
WHT
NOTE #4
COM WHT
HI
BLK YELMED HI
MED
ORN
BLU
LO
RED
RED
-
1 = VALVE
SPST (MANUAL) SECONDARY STATUS (MANUAL CHANGE OVER)
ALSO STATUS CODE RECALL JUNCTION TERMINAL CONTROL TERMINAL FACTORY POWER WIRING (115VAC) FACTORY CONTROL WIRING (24VAC) FIELD POWER WIRING (115VAC) FIELD CONTROL WIRING (24VAC) CONDUCTOR ON CONTROL FIELD WIRING SCREW TERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE
HI
BRN
P
SWITCH (WHEN REQ ’D)
JB
L1
L2
CAP
BRN
-
2 = HUM ID IF IER
*
GV
C
M
GRN/YEL
FUSED DISCONNECT
NOTE #1
BLK
FU2
WHT GND
WHT
BRN
TRAN
GRN/YEL
BLWM
RED
*
*
TO 115VAC FIELD DISCONNECT SWITCH
BLK
BLU
ILK
L1
BLWR
HSIR
IDR
FU1
NOTE #5
TWIN TEST
W/W1
C
EQUIPMEN T GROUND
BHT / CLR
EAC-1
IHI / LOR
PR1
SEC1
HUM
R
S
M
SW1
W2
Y/Y2
G
OM
NOTES:
1. Use only copper w ire betw een th e disconn ect sw itch and the u n it.
2. If any of the original wire, as supplied, must be replaced, use the same or equivalent type wire.
3. Inducer (IDM) and blow er (BLWM) motors contain internal auto-reset thermal overload switches.
4. Blower motor speed selections are for average conditions. See Installation Instructions for details on optimum speed selection.
5. Replace only with a 3-AMP fuse.
6. Auxiliary limit switches (ALS1 & 2) used on some horizontal and some downflow models.
7. This wire must be conn e cted to fur na ce s h e et m e ta l for control to prove flame.
8. Factory connected when LGPS not used.
BHI / LOR
EAC-2
115VAC
TRAN 24VAC
TWINNING JUMPER TJ
HI-COOL
MGVR-2
COMMON
PR2
SEC2
CPU
SW4
NOTE #1
(NATURAL GAS & PROPANE)SCHEMATIC DIAGRAM
LO-GAS-HEAT
HI-GAS-HEAT
SPARE SPARE
SW3
MED LO
MED HI
HPSR
MGVR-1
SW2
9. Symbols are an electrical representation only.
10. BLOWER-ON DELAY: Gas heating 45 seconds,
11. Cooling/Heat Pump BLOWER-OFF DELAY is 90
12. IGNITION-LOC K O U T w ill occur after four
13. Control must be grounded at pin 10 of 12-pin
14. NA - Not Applicable
15. Spare terminal and wire not available on som e
LO
NOTE #15
HIMED NOTE #4
3
PL2
PL6
9
4
PL3
7 8
1
N/A
5 6
N/A
2
N/A
12
2
FRS1
(WHEN USED)
3
9 6
PL1
5
NOTE #8
4
1
10
NOTE#7
7
N/A
8
11
N/A
Cooling/Heat Pump 2 seco nd s. seconds. cons e c utive u n s ucces s f u l t rials-for - ig n it i o n .
Control will auto matically reset af ter thre e ho urs . connector.
applications. Insulate connector if n ot available.
COM
1 2
2 1
3
ALS2
NOTE #8 LPS
(WHEN USED)
LGPS
M
GV
C
BRN
COM
HI
HPS P
HSI
CAP
LO
FRS2
FSE
DSS
L2
BLWM
BRN
IDM
LS
ALS1
HI
Fig. 11Unit Wiring Diagram
324459-101 REV. D
A01365
SERVICE
If status code recall is needed, do not remove power or blower door. Briefly remove and then reconnect one main limi t wire to display stored status code.
LED CODE
CONTINUOUS OFF CONTIN UOUS ON RAPID FLASHING
Each of the following status codes is a two-digit number with the first digit determi ned b y the number of short flashes and the second digit by the number of long flashes.
11 NO PREVIOUS CODE - Stored status codes are erased when power (115VAC or
24VAC) to control is interrupted or 48 hours after each fault is cleared.
12 BLOWER ON AFTER POWER UP (115VAC or 24VAC) - Blower runs for 90 seconds,
if unit is po wered up during a call for h eat (R-W closed).
13 LIMIT OR FLAM E R O L L-OUT SWITCH LOCK O U T - Control will auto reset after three
hours. Reset switch or replace fuse link. Refer to #33.
14 IGNITION LOCKOUT - Control will au to-re se t afte r three hou rs. Ref er t o #34 . 21 GAS HEATING LOCKOUT - Control will NOT auto-reset.
Check for: - Mis-wired gas valve - Defective control (valve relay)
22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is de-
energized. Induce r will run until fault is cleared. Check for:
- Leaky gas valve - Stuck-open gas valve
23 PRESSURE SWITCH DID NOT OPEN Check for:
- Obstructed pressure tubing - Pressure switch stuck closed.
24 SECONDAR Y VOLTAGE FU SE IS OPEN Check for: - Short-circuit in secondary
voltage (24VAC) wiring
31 HIGH-HEAT PRESSURE SWITCH OR RELAY DID NOT CLOSE OR REOPENED
Check for: -Control relay may be defective - Refer to #32
32 LOW-HEAT PRESSURE, DRAFT SAFEGUARD (when used),OR AUX-LIMIT(when used*)
SWITCH DID NOT CLOSE OR REOPENED (DOWNFLOW ONLY*) If open longer than
five minutes, inducer shu ts off for 15 minutes before retry . If it opens after trial for ignition period, blower will com e on for 90 second recycle delay. Check for:
*- Defective blower motor or capacitor - Restricted vent
- Proper vent sizing - Low inducer voltage (115VAC)
- Disconnected or obstructed pressure tubing - Excessive wind
- Defective inducer motor - Defective pressure switch
- Inadequate combustion air supply - Low propane inlet gas pressure
33 LIMIT OR FLAM E R OL L -O U T SW I TC H IS OPEN - If open longer than three minutes,
code changes to #13. Flame roll-out switch requires manual reset. Check for:
- Dirty filter or restricted duct system . - Loose blower wheel.
- Defective blower motor or capacitor. - Defective switch or connections.
- Inadequate combustion air supply (Flame roll-out switch or fuse link open).
- Open flame roll-out switch, or fuse link. Manual reset or replace.
34 IGNITION PROVING FAILURE - Control will try three more times before locko ut #14
occurs. If flamesignal is lost after trial for ignit ion period, blower will come on for 90 second recycle delay . Check for:
- Gas valve defective or gas valve turned off.
- Oxide buildup on flame sensor (clean with fine steel wool).
- Proper flame sense current (.5 microamps D.C. min., 4.0 - 6.0 nom. in HIGH HEAT).
- Green wire MUST be c onnected to furnace sheet metal.
- Flame sensor must be ungrounded. - Manual valve shut-off.
- Defe ctive hot surface ignitor - Control ground continuity.
- Inadequate flame carryover or rough ignition. - Low inlet gas pressure.
43 LOW-HEAT PRESSURE, DRAFT SAFEGUARD (when used), OR AUX-LIMIT (when used*)
SWITCH OPEN WHILE HIGH-HEAT PRESSURE SWITCH IS CLOSED Check for:
- Pressure switch stuck open - Disconn ected or obstructed pressure tubing
- Refer to #32 and #33 - Low propane inlet gas pressure
45 REPLACE CONTROL
- Check for 115VA C at L1 and L2, and 24VAC at SEC1 and SEC2 .
- Control has 24VAC power.
- Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instruc tions.
COMPONENT TEST
OM
C
W2
24 V
To initiate the component self-test sequence, shut off the room thermostat or disconne ct the "R" therm o sta t lea d. Br iefly sho rt th e TW IN /T EST te rm ina l to the Com24V terminal. Status LED will turn o ff. NON-CONDEN SING FU RNACE: The control will turn ON the inducer motor low speed, then high speed and remain on high speed for the entire test. The other components will be ON for 7 to 15 seconds: Hot surface ignitor, Low heat blower speed, High heat blower speed, High cooling blower speed. CONDENSING FURNACE: The inducer motor will start in high speed and remain on high speed until the end of the test, then shift to low speed for 7 to 15 seconds. All other components w ill be tested in the same sequence as the N ON - CONDENSING.
W/W1
Y/Y2
GR
STA TUS
TWIN
TEST
HUM
Fig. 12Service Label
LED
12 - CIRCUIT CONNECTOR
320893-101 REV. F
A01368
9
NOTES:
Refer to information label on blower compartment door
1. for procedure for use of LED status codes and problem solving suggestions. LED indicator is viewed through window in blower
2. compartment door. If 115-vac power is de-energized or interrupted during a
3. call for heat, the indoor blower will run for 90 sec before a gas heating cycle begins – Code 12. After replacing any component, verify correct operating
4. sequence.
START
Turn thermostat OFF.
On furnace control, note current settings for setup switches 1 (SW-1) and 2 (SW-2) then set SW-1 to OFF
and SW-2 to ON.
Cycle 115-v power
off for 3 sec, then on.
Continuous LED?
Yes
Set thermostat to call for heat.
Set FAN to AUTO mode.
Draft inducer motor starts.
Yes
Is Code 22 displayed?
Yes
Flame present when not normal.
Replace gas valve.
15-sec inducer pre-purge.
Yes
Ignitor warms up and glows
orange/yellow; 17-sec warm-up.
Yes
Main burners ignite.
Yes
Main burners stay on.
Yes
Indoor blower motor starts on
heating speed after 45-sec
warm-up period.
Yes
Furnace runs until call for
heat ends.
Yes
Turn thermostat to OFF; gas valve
shuts off burners; 5-sec inducer
post purge.
Yes
Indoor blower motor stops after
90, 135, 180, or 225 sec.
Yes
Heating sequence of operation
complete. Remove blower door,
move setup switch 1 (SW-1) to ON
position and repeat process to check
high-stage gas heat operation.
(When finished return SW-1
SW-2 to original desired settings.)
No
No
No
No
No
No
No
No
No
No
and
TROUBLESHOOTING
GUIDE
If LED is flashing rapidly, check line voltage polarity. If Code 24 is displayed, check for blown fuse. If LED is OFF, check line voltage and 24-v transformer. If Code 45 is displayed, replace control.
Is indoor blower on ?
No
24v should be present across Com and W at furnace control. If not, check for:
1. Open thermostat.
2. Open 24-v fuse (FU1) – Code 24.
3. Failed transformer. If Code 23 is displayed, the pressure switch(es) is stuck closed.
Replace switch and/or check pressure tube for blockage. System malfunction – Code 21.
115v should be present at the inducer motor. If so, replace inducer motor. If not, check 115-v wiring.
If Code 32 is displayed check for:
1. Open gas inlet pressure switch (when used).
2. Open pressure switch (LPS) and/or tube – Code 32.
3. Open draft safeguard switch (DSS) – Code 32.
4. Open auxiliary switch (ALS)(downflow only) – Code 32.
5. Check all low-voltage wiring connections. 115v should be present at the ignitor. If so, replace the ignitor; if not,
check 115-vac wiring to ignitor. LPS, DSS, or ALS open while HPS if closed (high-gas-heat only) –
Code 43.
Control will attempt to light burners 4 times (approximately 1 minute between attempts – Code 34). Voltage is present at the gas valve for 7 sec during each ignition trial. System will lockout after 4 attempts.
Is the gas valve control knob or switch in the OPEN or ON position? 24v should be present across the gas valve terminals C and M/P (and C and HI for high-stage gas test) during the 7 sec ignition trial. If not, check all low-voltage wiring connections to valve.
If 24v are present, and main gas does not flow:
1. Supply pressure between 4.5- and 13.6-in. wc. If not, adjust supply pressure.
2. If supply pressure is between 4.5- and 13.6-in. wc, replace gas valve.
Check ignitor position. Check burner carryover gap. Check gas supply pressure (4.5-in. wc minimum). Check manifold pressure (1.3- to 1.7-in. wc for low-stage gas;
3.2- to 3.8-in. wc for high-stage gas). Check for proper orifice size.
Is Code 31 (high-gas-heat only), 32, 33, or 34 displayed? Check code information label to diagnose.
Check polarity of 115-v power at J-box and control. Twinned furnace polarities must match – rapid flashing LED.
Check ground continutity from J-box to control. Check flame sensor microamps (4.0 nominal; 0.5 minimum for
control to recognize flame).
115v should be present at the blower motor. If so, check capacitor. If capacitor is OK, replace blower motor. If 115v are not present at the blower motor, check all 115-v wiring to motor.
If not, check for:
1. Satisfied thermostat.
2. Open inlet gas pressure switch (when used).
3. Open pressure switch (LPS) – Code 32.
4. Open draft safeguard switch (DSS) – Code 32.
5. Open auxilliary limit (ALS)(downflow only) – Code 32.
6. Open 24-v fuse (FU1) – Code 24.
7. Open limit switch (LS) – Code 13 or 33.
8. Open flame rollout switch (FRS) – Code 13 or 33.
9. Check 115-v line voltage – LED off. Check for sources of electrical noise interference (electronic air
cleaners, nearby TV, or radio antennas).
If inducer and burners continue to operate, check for 24v at the gas valve. If 24v are present, verify that the thermostat is open across R and W. If no voltage is present, turn the gas valve control knob or switch to the OFF position. Replace gas valve.
24v should be present across R and Com. If not, check for:
1. Open limit switch (LS) – Code 13 or 33.
2. Open flame rollout switch (FRS) – Code 13 or 33. 24v should not be present across R and G. If so, set thermostat
FAN to AUTO mode.
WARNING
!
ELECTRICAL SHOCK HAZARD
ONLY QUALIFIED AND TRAINED SERVICE PERSONNEL SHOULD
PERFORM THIS PROCEDURE
24v should be present across R
Yes
No
No
No
No
No
No
No
No
and Com. If not, check for:
Open flame rollout switch
1. (FRS) – Code 33. Open limit switch (LS) –
2.
Code 33.
Check all low-voltage wiring
3. connections.
Replace control only if all checks
Replace control only if Code 45 is
displayed, or if all checks are OK.
Replace control only if Code 45 is
displayed, or if all checks are OK.
Replace control if Code 45 is dis-
played, or if all checks are OK.
Clean flame sensor if microamps
are below nominal.
Replace control only if Code 45 is
displayed, or if all checks are OK.
Replace control only if Code 45 is
displayed, or if all checks are OK.
Replace control only if Code 45 is
displayed, or if all checks are OK.
Replace control only if Code 45 is
displayed, or if all checks are OK.
No
are OK.
A97544
10
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:
Unit Familiarization Maintenance
Installation Overview • Operating Sequence
A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book.
Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-962-9212
[ ] Packaged Service Training [ ] Classroom Service Training
A94328
11
© 2001 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231
12
Printed in U.S.A. sp0473 Catalog No. 5333-025
Loading...