313AAV/JAV Plus 80x
4--Way Multipoise
Induced Combustion Gas Furnace
Input Capacities: 45,000 thru 135,000 Btuh, Series B
Product Data
STANDARD FEATURES
S ECM blower motor included
S Noise elimination combustion system
S SmartEvapt can lower the humidity level in the home by
S Certified to leak 2 percent or less of its nominal air
nearly 10%
conditioning CFM delivered when pressurized to 1--In.
Water Gauge with all present air inlets, air outlets, and
condensate drain port(s) sealed.
A10256
THE BRYANT Plus 80x GAS FURNACE
The Plus 80x Deluxe 4--Way Multipoise Gas Furnace offers
outstanding features in an 80% AFUE furnace.
Deluxe features include: an ECM motor which enhances SEER
performance up to 1.5 points*, a third fan relay for discrete
continuous fan speed, the ability to change continuous fan speeds
from the thermostat (Fan on Plust), dehumidify mode, fault code
storage, and more. The Plus 80x is very quiet thanks to a new
combustion design that eliminates noise, rather than just muffle or
box it in. Applications are easy with 4--way multipoise design,
through--the--furnace downflow venting, 13 different venting
options, and an overall design for easy service access. An inner
blower door is provided for tighter sealing in sensitive applications.
The 313JAV is approved for use in Low NOx Air Quality
Management Districts.
S Four--position furnace: Upflow, Horizontal Right,
Horizontal Left, Downflow
Thirteen different vent options
S Compact design only 33--1/3 in. (847 mm) tall
S Microprocessor based “smart” control center
t
Fan on Plus
thermostat
Adjustable heating air temperature rise
Dehumidify mode
Enhanced diagnostics with LED and reflective sight glass,
non--volatile fault code memory, and self--test feature
On--board fuse for transformer protection
S Patented blocked vent safeguard to ensure proper furnace
venting
S Insulated blower compartment
S HYBRID HEAT® Dual Fuel System compatible
S All models are chimney friendly when used with accessory
vent kit
S Perfect Lightt Igniter
S Residential installations eligible for consumer financing
through the Comfort Credit Program
-- Continuous Fan speed adjustable from
*as compared to the Air Conditioning Heating and Refrigeration Institute’s standard coil---only ratings when paired with selected Bryant evaporator coils.
1
Page 2
BRYANT ACCESSORIES
CONTROLS:
THERMOSTATS
AND ZONING
Available in programmable and
non-programmable models,
Bryant thermostats maintain a
constant, comfortable temperature level in the home.
For the ultimate in home comfort,
Bryant’s 2, 4, and 8-zone systems
allow temperature control of individual “zones” of the home. This is
accomplished through a series of
electronic dampers and
313AAV/JAV
remote room sensors.
4-zone system is shown.
A97432
The
C04009
MECHANICAL
OR ELECTRONIC
AIR CLEANER
Cleans the air of smoke, dirt, and
many pollens commonly found.
Saves decorating and cleaning
expenses by keeping carpets,
furniture, and drapes cleaner.
Electronic air cleaner is shown.
MODEL HUMCCLFP
A01484
HUMIDIFIER
By adding moisture to winter-dry
air, a Bryant humidifier can often
improve comfort and keep
furniture, rugs, and draperies in
better condition. Moisturizing
household air also helps to retain
normal body heat and provides
comfort at lower temperatures.
A08153
ACCESSORIES
ELECTRONIC AIR CLEANER
(EAC)
Model EACB
AIR PURIFIERModels GAPAAXBB1625, GAPAAXBB2025
MECHANICAL AIR CLEANERModels EZXCAB, FILCAB
HUMIDIFIERModel HUM
HEAT RECOVERY
VENTILATOR
ENERGY RECOVERY
VENTILATOR
Model HRV
Model ERV
UV LIGHTSModel UVL
F o r u s e w i t h 1 --- s p e e d A i r C o n d i t i o n e r --- d e g . F / C , A u t o C h a n g e o v e r --- T 6 --- N A C , T 2 --- N A C
T H E R M O S T A T --N O N --- P R O G R A M M A B L E
F o r u s e w i t h 1 --- s p e e d H e a t P u m p --- d e g . F / C , A u t o C h a n g e o v e r --- T 6 --- N H P, T 2 --- N H P *
F o r u s e w i t h 2 --- s p e e d A i r C o n d i t i o n e r --- d e g . F / C , A u t o C h a n g e o v e r --- T 6 --- N R H *
For use with multi --- use / stage configurations --- deg. F/C, Auto Changeover/Temperature and
H u m i d i t y C o n t r o l --- T 6 --- P R H
{
F o r u s e w i t h 1 --- s p e e d A i r C o n d i t i o n e r --- d e g . F / C , A u t o C h a n g e o v e r , 7 --- D a y P r o g r a m m a b l e --T 6 --- PA C
F o r u s e w i t h 1 --- s p e e d H e a t P u m p --- d e g . F / C , A u t o C h a n g e o v e r , 7 --- D a y P r o g r a m m a b l e --T6--- PHP*
T H E R M O S T A T --PROGRAMMABLE
F o r u s e w i t h 2 --- s p e e d A i r C o n d i t i o n e r --- d e g . F / C , A u t o C h a n g e o v e r , 7 --- D a y P r o g r a m m a b l e --T 6 --- P R H *
F o r u s e w i t h 1 --- s p e e d A i r C o n d i t i o n e r --- d e g . F / C , 5 --- 2 D a y P r o g r a m m a b l e --- T 6 --- P A C
F o r u s e w i t h m u l t i --- s t a g e a p p l i c a t i o n s --- d e g . F / C , A u t o C h a n g e o v e r , 7 --- D a y P r o g r a m m a b l e ---
T 2 --- P H P
}
F o r m u l t i --- u s e / s t a g e c o n f i g u r a t i o n s --- d e g . F / C , A u t o C h a n g e o v e r , 7 --- D a y P r o g r a m m a b l e /
Temperature and Humidity Control ---T6 --- PRH
{
Zone Perfect 3--- Zone kit --- ZONEBB3ZAC01, ZONEBB3ZHP01
ZONING CONTROL
2 --- Z o n e P e r f e c t P l u s k i t / T e m p e r a t u r e a n d H u m i d i t y C o n t r o l --- Z O N E B B 2 K I T 0 1 --- B
4 --- Z o n e P e r f e c t P l u s k i t / T e m p e r a t u r e a n d H u m i d i t y C o n t r o l --- Z O N E B B 4 K I T 0 1 --- B
8 --- Z o n e P e r f e c t P l u s k i t / T e m p e r a t u r e a n d H u m i d i t y C o n t r o l --- Z O N E B B 8 K I T 0 1 --- B
*Model HP and 2S thermostat must be field converted to air conditioner operation.
{Thermidistatt Control can be configured for multiple use and staging. It must be configured for each specific application.
}Dual Fuel thermostat is used with furnace and heat pump application.
2
Page 3
BRYANT ACCESSORIES
DESCRIPTION 313AAV/JAVPAR T NO.024045048070048090060110060135
FILCABBB0016XX
Media Filter Cabinet
Cartridge Media Filter
EZ Flex Media Filter with End Caps
Replacement EZ Flex Filter Media
External Bottom Return
Filter Rack
External Side Return Filter RackKGAFR0801SREXXXXX
Unframed Filter 3/4 --- in. (19 mm)
Flue ExtensionKGAFE0112UPHXXXXX
Combustible Floor BaseKGASB0201ALLXXXXX
Downflow Vent GuardKGBVG0101DFGXXXXX
Vent Extension KitKGAVE0101DNHXXXXX
Chimney Adapter KitKGACA02014FCXXXX
Chimney Adapter KitKGACA02015FCX
N a t u r a l --- t o --- P r o p a n e C o n v e r s i o n K i t *KGANP4601ALLXXXXX
P r o p a n e --- t o --- N a t u r a l C o n v e r s i o n K i t *KGAPN3901ALLXXXXX
Label KitKGALB0101KITXXXXX
Gas Orifice Kit (Qty 50)
FILCABBB0020XX
FILCABBB0024X
FILBBCAR0016XX
FILBBCAR0020XX
FILBBCAR0024X
EXPXXUNV0016XX
EXPXXUNV0020XX
EXPXXUNV0024X
EXPXXFIL0016XX
EXPXXFIL0020XX
EXPXXFIL0024X
KGAFR0401B14X
KGAFR0501B17X
KGAFR0601B21XX
KGAFR0701B24X
KGAWF1301UFR {SS
KGAWF1401UFRSS
KGAWF1501UFRS
KGAWF1306UFR {XX
KGAWF1406UFRXX
KGAWF1506UFRX
KGAHA0150N42
KGAHA0250N43
(factory supplied)
KGAHA0350N44
KGAHA0450N45
KGAHA0550N46
KGAHA1550N47
KGAHA1650N48
KGAHA0650P54
KGAHA0750P55
KGAHA0850P56
KGAHA5750125
KGAHA5750130
See Installation Instructions for model, altitude, and heat value usages.
313AAV/JAV
*Factory ---authorized and field --- instal led. Gas conversion kits are CSA (AGA/CGA) recognized.
{Suitable for Side Retu rn Filter Rack.
X --- A c c e s s o r y
S --- S t a n d a r d
3
Page 4
PHYSICAL DATA
UNIT SIZE024045048070048090060110060135
OUTPUT CAPACITY
BTUH
( N o n --- w e a t h e r i z e d I C S )
INPUT BTUH
AFUE%N o n --- w e a t h e r i z e d I C S80.080.080.080.080.0
SHIPPING WEIGHT LB. (KG)104 (47)126 (57)140 (64)152 (69)163 (74)
CERTIFIED TEMP RISE RANGE ˚_F(_C)
CERTIFIED EXT STATIC
PRESSURE (IN. In. W.C.)
AIRFLOW CFM
LIMIT CONTROLSPST
HEATING BLOWER CONTROLSolid --- State Time Operation
BURNERS (Monoport)23456
GAS CONNECTION SIZE1 / 2 --- i n . N P T
GAS VALVE(Redundant) ManufacturerW h i t e --- R o d g e r s
*Gas input ratings are certified for elevations to 2000 ft. (610 M)*. In USA, For elevations above 2000 ft. (610 M), reduce ratings 4 percent for each 1000 f t. (305
M) above sea level. Refer to National Fuel Gas Code NFPA 54/ANSI Z223.1 ---2009 Table F.4 or furnace Installation Instructions.
{Capacity in accordance with U.S. Government DOE test procedures.
}Airflow shown is for bottom only return ---air supply. For air delivery above 1800 CFM, see Air Delivery Table for other options. A filter is required foreach
return---air supply. An airflow reduction of up to 7 percent may occur when using a Bryant 4---5/16 in. (110 mm) high efficiency media filter.
ICS - -- Isolated Combustion System
313JAV Upflow; all 313AAV36,00053,00072,00090,000107,000
UNIT SIZE024045048070048090060110060135
DIRECT---DRIVE MOTOR Hp (ECM --- 5 Speed)1/23/43/411
MOTOR FULL LOAD AMPS6.88.48.410.910.9
R P M ( N o m i n a l ) --- S P E E D S1050--- 51050 ---51050 --- 51050 --- 51050 ---5
BLOWER WHEEL DIAMETER x WIDTHS --- IN (MM)
58DLA/DLX
A02169
A02169
10 x 6
(254 x 152)
11 x 8
(279 x 203)
A08063
10X10
(254 x 254)
11 x 11
(279 x 279)
11 x 11
(279 x 279)
A02170
REWOLB RECUDNIDRAOB LORTNOCREGNAHCXE TAEH
4
Page 5
SEE NOTES: 1,2,4,7,8,9
UPFLOW
A02058
SEE NOTES: 1,2,3,4,7,8,9
UPFLOWDOWNFLOW
A02059
SEE NOTES: 1,2,4,5,7,8,9
A02061
313AAV/JAV
SEE NOTES:1,2,3,4,5,7,8,9
DOWNFLOW
SEE NOTES: 1,2,3,4,7,8,9
DOWNFLOW
A02063A02060
SEE NOTES: 1,2,4,5,6,7,8,9
DOWNFLOW
Ven ti ng N ote s
1. For common vent, vent connector sizing and vent material: United States, latest edition of the National Fuel Gas Code (NFGC),
NFPA54/ANSI Z223.1.
2. Immediately increase to 5--in. (127 mm) vent connector outside furnace casing when 5--in. (127 mm) vent connector required, refer to
Note 1.
3. Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace, except when
Downflow Vent Guard is used in downflow position.
4. Type B vent where required, refer to Note 1.
5. 4--in. (102 mm) single wall vent must be used inside furnace casing and the Downflow Vent Guard Kit.
6. Accessory Downflow Vent Guard Kit required in downflow installations with bottom vent configuration.
7. Chimney Adapter Kit required for exterior masonry chimney applications. Refer to Chimney Adapter Kit for sizing and complete
application details.
8. Secure vent connector to furnace elbow with (2) corrosion--resistant sheet metal screws, space approximately 180_ apart.
9. Secure all other single wall vent connector joints with (3) corrosion--resistant screws spaced approximately 120_ apart. Secure Type B
vent connectors per vent connector manufacturer’s recommendations.
5
A02062
Page 6
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL RIGHT
A02068A02070
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL RIGHT
313AAV/JAV
SEE NOTES: 1,2,4,7,8,9
HORIZONTAL RIGHT
A02069
SEE NOTES: 1,2,4,7,8,9
HORIZONTAL LEFT
A02064
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL LEFTHORIZONTAL LEFT
A02066
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL LEFT
SEE NOTES: 1,2,4,5,7,8,9
6
A02065
A02067
Page 7
AIR DELIVERY -- CFM (WITH FILTER)*
UNIT SIZE
024045
048070
048090
060110
060135
*A filter is required for each return ---air inlet. Airflow performance incl uded 3/4 ---in. (19 mm) washable filter media such as contain ed in factory --- authorized accessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 In. W.C. available external static pressure.
* Permissible limits of the voltage range at which the unit operates satisfactorily.
{ Time ---delay type is recommended.
}Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
V O LT S ---
H E R T Z ---
PHASE
OPERATING VOLTAGE
RANGE
*
MaximumMinimum
MAXIMUM
UNIT AMPS
MAXIMUM WIRE
LENGTH FT (M)
MAXIMUM FUSE
OR CKT BKR
}
AMPS
MINIMUM
{
WIRE GAGE
7
Page 8
DIMENSIONS
A
B
[736.9]
29
Ø7/8
[22.2]
ACCESSORY
5 15/16
[150.7]
28.39
[721.2]
Ø7/8
[22.2]
ACCESSORY
14 7/8
[337.3]
(BOTH SIDES)
Ø7/8
[22.2]
ACCESSORY
Ø7/8
[22.2]
ACCESSORY
Ø1 3/4
[44.5]
GAS ENTRY
Ø1/2
[12.7]
THERMOSTAT WIRE ENTRY
22 1/16
[560]
SIDE INLET
(BOTH SIDES)
11 7/16
[290.7]
9 11/16
[245.4]
[197.8]
7 13/16
Ø7/8
[22.2]
J.BOX PROVISION
Ø7/8
[22.2]
JUNCTION BOX
LOCATION
Ø1 3/4
[44.5]
GAS ENTRY
1 15/16
[49.2]
1
[25.4]
1 1/4
[31.8]
29 9/16
[750.7]
1 15/16
[49.2]
5 5/8
[143.3]
5 7/16
[138.5]
6 13/16
[172.3]
Ø1/2
[12.7]
THERMOSTAT WIRE ENTRY
19
[481.7]
OUTLET
D
21.6
[549.5]
BOTTOM INLET
C
33 1/4
[843.9]
9 9/16
[243.3]
3/4
[19.1]
5 7/8
[148.5]
3 7/16
[86.8]
9 7/8
[250.7]
27 3/4
[704.7]
2 5/16
[59]
FRONT OF CASING
TOP OF CASING
4 13/16
[122.2]
27 3/4
[704.7]
5 7/8
[148.5]
8 5/8
[219]
5 1/2
[140.3]
8 7/16
[213.5]
FRONT OF CASING
TOP OF CASING
6.1
[155.7]
2 1/16
[51.6]
5.1
[130.5]
1.7
[43.5]
Ø7/8
[22.2]
ACCESSORY (2)
AIR FLOW
AIR FLOW
BOTTOM RETURN
WIDTH
AIR FLOW
KNOCK OUTS FOR
VENTING(5
PLACES)
27 3/4
[704.7]
33 1/4
[843.9]
313AAV/JAV
1. Two additional 7/8--in. (22 mm) dia. knockouts are located in the top plate.
2. Minimum return--air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters.
3. Minimum return--air opening at furnace.
5.1
[130.5]
2 1/16
[51.6]
1.7
[43.5]
Ø7/8
[22.2]
9 7/8
[250.7]
8 7/16
[213.5]
5 15/16
[150.7]
5 1/2
[140.3]
AIR FLOW
ACCESSORY
THERMOSTAT WIRE ENTRY
ACCESSORY
21.6
[549.5]
BOTTOM INLET
28.39
[721.2]
29
[736.9]
Ø7/8
[22.2]
[22.2]
ACCESSORY (2)
FRONT OF CASING
1 15/16
[49.2]
2 5/16
3 7/16
[59]
[86.8]
5 7/8
[148.5]
TOP OF CASING
Ø7/8
Ø1/2
[12.7]
[155.7]
Ø7/8
[22.2]
JUNCTION BOX
LOCATION
Ø1 3/4
[44.5]
GAS ENTRY
6.1
AIR FLOW
A
BOTTOM RETURN
WIDTH
TOP OF CASING
3/4
[19.1]
29 9/16
[750.7]
9 9/16
[243.3]
27 3/4
[704.7]
KNOCK OUTS FOR
VENTING(5
PLACES)
5 7/8
[148.5]
5 7/16
[138.5]
4 13/16
[122.2]
J.BOX PROVISION
ACCESSORY
6 13/16
[172.3]
5 5/8
[143.3]
1 15/16
[49.2]
Ø7/8
[22.2]
Ø7/8
[22.2]
FRONT OF CASING
8 5/8
[219]
AIR FLOW
19
[481.7]
OUTLET
Ø1/2
[12.7]
THERMOSTAT WIRE ENTRY
Ø1 3/4
[44.5]
GAS ENTRY
Ø7/8
[22.2]
ACCESSORY
22 1/16
[560]
SIDE INLET
(BOTH SIDES)
7 13/16
[197.8]
14 7/8
[337.3]
(BOTH SIDES)
[25.4]
9 11/16
[245.4]
1 1/4
[31.8]
a. For 800 CFM--16--in. (406 mm) round or 14--1/2 x 12--in. (368 x 305 mm) rectangle.
b. For 1200 CFM--20--in. (508 mm) round or 14--1/2 x 19--1/3 in. (368 x 491 mm)rectangle.
c. For 1600 CFM--22--in. (559 mm) round or 14--1/2 x 22--1/16--in. (368 x 560 mm) rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a
combination of 1 side and the bottom, or the bottom of single side inlets. The use of both side inlets, a combination of one side and the bottom, or the bottom only
will ensure adequate return air openings for airflow requirements above 1800 CFM.
*135 size furnaces require a 5 or 6 ---in. (127 or 152 mm) vent. Use a vent adapter between furnace and vent stack. See Installation Instructions for complete
install ation requirements.
8
ACCESSORY-
MEDIA CABINET
SIZE
IN (MM)
Page 9
313AAV/JAV
A10269
I
G
S
E
N
D
Always Ask For
Use of the AHRI Certified TM Mark indicates a
manufacturer’s participation in the program. For
verification of certification for individual products,
go to www.ahridirectory.org.
9
C
E
R
D
E
I
T
F
I
Page 10
TYPICAL WIRING SCHEMATIC
A
FIVE WIRE
THREE-WIRE
HEATING-ONLY
BLOWER DOOR SWITCH
BLK
WHT
115-V FIELD-
SUPPLIED
DISCONNECT
313AAV/JAV
GND
BLK
WHT
GND
AUXILIARY
J-BOX
FURNACE
NOTE 2
W
C
R
O
N
T
G
R
O
COM
L
Y/Y2
24-V
TERMINAL
BLOCK
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
WCRGY
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
DISCONNECT
208/230- OR
460-V
THREE
PHASE
208/230-V
SINGLE
PHASE
NOTE 1
CONDENSING
GND
UNIT
TWO
WIRE
NOTES:Connect Y-terminal in furnace as shown for proper blower operation.
1.
2.
Some thermostats require a "C" terminal connection as shown.
3.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
A99440
MODEL NUMBER NOMENCLATURE
V
Bryant Type Code
Gas Furnace, 4--- Way
Multipoise, 80%
F i x e d --- C a p a c i t y
Furnish a _________________ fixed capacity gas--fired furnace
for use with natural gas or propane (factory authorized conversion
kit required for propane); furnish cold air return plenum.
Quality Assurance
Unit will be designed, tested and constructed to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will be 3rd party certified by CSA to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will carry the CSA Blue Star® label.
Unit efficiency testing will be performed per the current DOE test
procedure as listed in the Federal Register.
Unit will be certified for capacity and efficiency and listed in the
latest AHRI Consumer’s Directory of Certified Efficiency Ratings.
Unit will carry the current Federal Trade Commission Energy
Guide efficiency label.
Delivery, Storage and Handling
Unit shall be shipped as single package only and is stored and
handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)
U.S. only. Warranty certificate available upon request.
PRODUCTS
Equipment
Components shall include: slow--opening gas valve to reduce
ignition noise, regulate gas flow, with electric switch gas shut--off;
flame proving sensor, hot surface igniter, pressure switch assembly;
flame rollout switch, blower and inducer assembly, 40va
transformer; low--voltage (heating) (heating/ cooling) thermostat.
Blower Wheel and Blower Motor
Galvanized blower wheel shall be centrifugal type, statically and
dynamically balanced. Blower motor of ECM type shall be
permanently lubricated with sealed bearings, of _______hp, and
shall be multiple--speed direct drive. Blower motor shall be soft
mounted to the blower scroll to reduce vibration transmission.
Filters
Furnace may have reusable--type filters. Filter shall be _______ in
(x) _______in. (mm). An accessory high--efficiency media filter is
available as an option. _______________ Media Filter.
Casing
Casing shall be of .030 in. (.76 mm) thickness minimum,
pre--painted galvanized steel.
Inducer Motor
Inducer motor shall be soft mounted to reduce vibration
transmission.
Draft Safeguard Switch
Draft Safeguard Switch (blocked vent safeguard) shall be factory
installed to reduce the possibility of vent gas infiltration due to a
blocked or restricted vent pipe.
Heat Exchangers
Heat exchangers shall be a 4--Pass 20 gage aluminized steel of
fold--and--crimp sectional design when applied operating under
negative pressure.
Controls
Control shall include a micro--processor based integrated electronic
control board with at least 11 service troubleshooting codes
displayed via enhanced flashing LED diagnostic light on the
control, a self--test feature that checks all major functions of the
furnace within one minute, and a replaceable automotive--type
circuit protection fuse. Multiple operational settings available
including, separate blower speeds for heating, cooling and
continuous fan. Continuous fan speed may be adjusted from the
thermostat. Features will also include temporary reduced airflow in
the cooling mode for improved dehumidification when a
Thermidistatt Control is selected as the thermostat.