Bryant 120 User Manual

312A
2 --- S t a ge D e lux e I n d u ce d --- C o m b u s ti o n 4---Way Multipoise Furnace
Installation, Start--up, Operating and
Service and M a int e nanc e
Instructions Series 120/C
SAFETY CONSIDERATIONS 2........................
CODES AND STANDARDS 5..........................
Safety 5...........................................
General Installation 5................................
Combustion and Ventilation Air 5......................
Duct Systems 5.....................................
Acoustical Lining and Fibrous Glass Duct 5...............
Gas Piping and Gas Pipe Pressure Testing 5...............
Electrical Connections 5..............................
Venting 5.........................................
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
LOCATION 6.......................................
AIR FOR COMBUSTION AND VENTILATION 8.........
INSTALLATION 10..................................
UPFLOW INSTALLATION 10......................
DOWNFLOW INSTALLATION 11...................
HORIZONTAL INSTALLATION 11..................
FILTER ARRANGEMENT 15.......................
AIR DUCTS 15...................................
GAS PIPING 18..................................
ELECTRICAL CONNECTIONS 21..................
VENTING 26....................................
START--UP, ADJUSTMENT, AND SAFETY CHECK 35.....
General 35........................................
Start--Up Procedures 35..............................
Adjustments 36.....................................
Check Safety Controls 40.............................
Checklist 41.......................................
SERVICE AND MAINTENANCE PROCEDURES 45.....
Introdution 46....................................
Care and Maintenance 46...........................
Sequence of Operation 51...........................
Wiring Diagrams 54...............................
Troubleshooting 54................................
ama
ISO 9001:2000
CERTIFIED
REGISTERED
NOTE: Read the entire instruction manual before starting the installation.
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1--2006E, with permission of National Fire Protection Association, Quincy, MA 02269 and American Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI on the referenced subject, which is represented only by the standard in its entirety.
28-7/8"
25-1/4"
22-9/16"
JUNCTION BOX LOCATION
WIRE ENTRY
3-15/16"
LEFT HAND GAS
ENTRY
7/8" DIA. ACCESSORY
21-5/8"
BOTTOM INLET
24"
CASING
1-11/16"
24-7/8"
5-1/2"
4-13/16"
8-9/16"
ALTERNATE
JUNCTION BOX
VENT OUTLET
5 PLACES (TYP)
3-3/4"
2-7/16" 1-5/16"
1-1/8"
A
D
F
E
13/16"
LOCATIONS (TYP)
5-1/2"
11/16"
AIRFLOW
19"
OUTLET
1/2" DIA. K.O.THERMOSTAT WIRE ENTRY
1-3/4" DIA.RIGHT HAND GAS ENTRY
7/8" DIA. K.O. WIRE ENTRY
7/8" DIA. ACCESSORY
1-1/2"
22-1/16"
SIDE INLET
13/16"
11/16"
14-7/8"
1-1/4"
1"
312A
26-1/8"
(FLUE COLLAR)
5-15/16"
7/8" DIA
ACCESSORY
NOTES:
1. Two additional 7/8-in. diameter holes are located in the top plate.
2. Minimum return-air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters. a. For 800 CFM-16-in. round or 14 1/2 x 12-in. rectangle. b. For 1200 CFM-20-in. round or 14 1/2 x 19 1/2-in. rectangle. c. For 1600 CFM-22-in. round or 14 1/2 x 22-in. rectangle. d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
1/2" DIA THERMOSTAT
33-5/16"
11/16"
NOTES:
1. Two additional 7/8---in. diameter holes are located in the top plate.
2. Minimum return --- air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters. a. For 800 CFM---16--- in. round or 14 1/2 x 12--- in. rectangle. b. For 1200 CFM---20 ---in. round or 14 1/2 x 19 1/2--- in. rectangle. c. For 1600 CFM---22 ---in. round or 14 1/2 x 22--- in. rectangle. d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific u se of single side inlets. The use of both sidein­lets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airfl ow requirements above 1800 CFM.
Fig. 1 -- Dimensional Drawing
7-3/4"
9-5/8"
11-1/2"
A04037
SAFETY CONSIDERATIONS
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation, serious injury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use could cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified service agency must use only factory--authorized and listed kits or accessories when modifying this product.
!
CAUTION
FURNACE RELIABILITY HAZARD
Improper installation or misapplication of furnace may require excessive servicing or cause premature component failure.
Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in literature, on tags, and on labels attached to or shipped with furnace and other safety precautions that may apply. These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require these instructions as a minimum for a safe installation.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.
Wear safety glasses and work gloves. Have fire extinguisher available during start--up and adjustment procedures and service calls.
This is the safety--alert symbol
. When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify hazards which may result in minor personal injury or
2
Table 1 – Dimensions (In.)
A
FURNACE SIZE
045--- 08/024045 14--- 3/16 12--- 9/16 12--- 11/16 9--- 5/16 4 116 16 045--- 12/036045 14--- 3/16 12--- 9/16 12--- 11/16 9--- 5/16 4 119 16 070--- 08/024070 14--- 3/16 12--- 9/16 12--- 11/16 9--- 5/16 4 120 16 070--- 12/036070 14--- 3/16 12--- 9/16 12--- 11/16 9--- 5/16 4 124 16 070--- 16/048070 17--- 1/2 15--- 7/8 16 11 --- 9/16 4 138 16 090--- 14/042090 17--- 1/2 15--- 7/8 16 11 --- 9/16 4 136 16 090--- 16/048090 21 19--- 3/8 19 --- 1/2 13---5/16 4 151 20 090--- 20/060090 21 19--- 3/8 19 --- 1/2 13---5/16 4 156 20 110--- 12/036110 17--- 1/2 15--- 7/8 16 11 --- 9/16 4 144 16 110--- 16/048110 21 19--- 3/8 19 --- 1/2 13---5/16 4 158 20 110--- 22/066110 21 19--- 3/8 19 --- 1/2 13---5/16 4 163 20 135--- 16/048135 21 19--- 3/8 19 --- 1/2 13---5/16 4† 163 20 135--- 22/066135 24--- 1/2 22--- 7/8 23 15 --- 1/16 4† 174 24 155--- 20/060155 24--- 1/2 22--- 7/8 23 15 --- 1/16 4† 181 24
* 5” or 6” vent connector may be required in some cases. { 135 and 155 size furnaces require five---inch or larger vents. Use a 4---5 or 4---6 inch vent adapter between furnace and vent connector.
CABINET
WIDTH
(IN.)
D
SUPPLY--- AIR
WIDTH (IN.)
E
RETURN---AIR
WIDTH (IN.)
product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
1. Use only with type of gas approved for this furnace. Refer to the furnace rating plate 2. Install this furnace only in a
2. Install this furnace only in a location and position as specified in the “Location” section of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in “Air for Combustion and Ventilation” section.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the “Venting” section of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the “Gas Piping” section.
6. Always install furnace to operate within the furnace’s intended temperature--rise range with a duct system which has an external static pressure within the allowable range, as specified in the “Start--Up, Adjustments, and Safety Check” section. See furnace rating plate.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. See “Air Ducts” section.
8. A gas-- fired furnace for installation in a residential garage must be installed as specified in the warning box in the “Location” section.
9. The furnace may be used for construction heat provided that the furnace installation and operation complies with the first CAUTION in the LOCATION section of these instructions.
10. These Multipoise Gas--Fired Furnaces are CSA (formerly A.G.A. and C.G.A.) design--certified for use with natural and propane gases (see furnace rating plate) and for installation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages. The furnace is factory--shipped for use with natural gas. A CSA (A.G.A. and C.G.A.) listed accessory gas conversion kit is required
F
C.L. TOP AND
BOTTOM FLUE
COLLAR (IN.)
FLUE
COLLAR*
(IN.)
SHIP WT. (LB)
11. See Fig. 2 for required clearances to combustible construction.
12. Maintain a 1--in. clearance from combustible materials to supply air ductwork for a distance of 36 inches horizontally from the furnace. See NFPA 90B or local code for further requirements.
13. These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. In downflow installations, factory accessory floor base MUST be used when installed on combustible materials and wood flooring. Special base is not required when this furnace is installed on manufacturer’s Coil Assembly Part No. CD5 or CK5, or when Coil Box Part No. KCAKC is used. See Fig. 2 for clearance to combustible construction information.
INTRODUCTION
The Series 120/C 4--way multipoise Category I fan--assisted furnace is CSA (formerly A.A.A.. and C.G.A.) design--certified. A Category I fan--assisted furnace is an appliance equipped with an integral mechanical means to either draw or force products of combustion through the combustion chamber and/or heat exchanger. The furnace is factory--shipped for use with natural gas. This furnace is not approved for installation in mobile homes, recreational vehicles, or outdoors.
These furnaces shall not be installed directly on carpeting, tile, or any other combustible material other than wood flooring. For downflow installations, a factory accessory floor base must be used when installed on combustible materials and wood flooring. This special base is not required when this furnace is installed on the manufacturer’s coil assembly, or when the manufacturer’s coil box is used. See Fig. 2 for clearance to combustible material information.
This furnace is designed for minimum continuous return--air temperature of 60_F db or intermittent operation down to 55_F db such as when used with a night setback thermostat. Return-- air temperature must not exceed 80_F db. Failure to follow these return-- air temperature limits may affect reliability of heat exchangers, motors, and controls. (See Fig. 3.)
For accessory installation details, refer to the applicable instruction literature.
NOTE: Remove all shipping brackets and materials before operating the furnace.
to convert furnace for use with propane gas.
FILTER
MEDIA CABINET SIZE (IN.)
312A
3
312A
INSTALLATION
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
DISTANCE MINIMALE EN POUCES AUX CONSTRUCTIONS COMBUSTIBLES
This forced air furnace is equipped for use with
natural gas at altitudes 0-10,000 ft (0-3,050m).
An accessory kit, supplied by the manufacturer, shall be used to convert to propane gas use or may be required for some natural gas applications.
This furnace is for indoor installation in a building constructed on site.
This furnace may be installed on combustible
flooring in alcove or closet at minimum clearance as indicated by the diagram from combusitble material.
This furnace may be used with a Type B-1 Vent
and may be vented in common with other gas fired appliances.
Cette fournaise à air pulsé est équipée pour utilisation avec gaz naturel et altitudes comprises entre 0-3,050m (0-10,000 pi).
Utiliser une trousse de conversion, fournie par le fabricant, pour passer au gaz propane ou pour certaines installations au gaz naturel.
This furnace is approved for UPFLOW, DOWNFLOW, and HORIZONTAL installations.
Cette fournaise est approuvée pour l 'installation HORIZONTALE et la circulation d 'air VERS LE HAUT et VERS LE BAS.
Clearance arrows do not change with furnace orientation.
0"
B
A
A
C
R
K
R
I
È
R
E
E
D
I
S
É
T
Ô
C
0"
*
1"
Les fléches de dégagement
l 'orientation de la fournaise.
TOP / PLE NUM
DESSUS / CHAMBRE D'AIR
E
C
E
A
S
N
I
A
R
U
N
F
R
U
T
FO
N
O
T
R
N
F
A
V
A
F
R
O
A
N
V
T
A
N
T
3"
Cette fournaise est prévue pour être installée dans un bâtiment construit sur place.
Cette fournaise peut être installée sur un plancher combustible dans une alcôve ou dans un garde-robe en respectant le minimum d'espace libre des matériaux combustibles, tel
´
indiqué sur le diagramme.
qu
Cette fournaise peut être utilisée avec un
´
évacuation de Type B-1 ou connectée
conduit d au conduit ommun d 'autres appareils à gaz.
Vent Clearance to combustibles:
For Single Wall vents 6 inches (6 po). For Type B-1 vent type 1 inch (1 po).
Dégagement de l´évent avec combustibles:
Pour conduit d´évacuation à paroi simple 6 po (6 inches). Pour conduit d
BOTTOM
DESSOUS
"
0
´
évacuation de Type B-1 1 po (1 inch).
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
DOWNFLOW POSITIONS:
Installation on non-combusibible floors only.
For Installation on combustible flooring only when installed on special base, Part No. KGASB0201ALL,
Coil Assembly, Part No. CD5 or CK5, or Coil Casing, Part No. KCAKC.
18 inches front clearance required for alcove.
Ø
Indicates supply or return sides when furnace is in the horizontal position. Line contact only permissible
*
between lines formed by intersections of the Top and two Sides of the furnace jacket, and building joists, studs or framing.
DÉGAGEMENT MINIMUM EN POUCES AVEC ÉLÉMENTS
DE CONSTRUCTION COMBUSTIBLES
POUR LA POSITION COURANT DESCENDANT:
Pour l´installation sur plancher non combustible seulement.
´
installation sur un plancher combustible seulement quand on utilise la base spéciale, pièce
Pour l
nº KGASB0201ALL, l nº KCAKC.
Dans une alcôve, on doit maintenir un dégagement à l
Ø
La poistion indiquée concerne le côté d
*
position horizontale.
Le contact n
´
est permis qu´entre les lignes formées par les intersections du dessus et des
deux côtés de la cherrise de la fournaise et les solives, montant sous cadre de charpente.
´
ensemble serpentin, pièce nº CD5 ou CK5, ou le carter de serpentin, pièce
´
´
entrée ou de retour quand la fournaise est dans la
avant de 18 po (450mm).
327590-101 REV. C
ne change pas avec
0"
E
D
*
I
È
S
T
Ô
C
S
E
R
E
N
V
I
T
R
C
E
E
T
I
E
N
24"
MIN
Ø
Clearance in inches Dégagement (po).
MIN
Fig. 2 -- Clearances to Combustibles
4
A04123
80
60
A04036
Fig. 3 -- Return Air Temperature
CODES AND STANDARDS
Follow all national and local codes and standards in addition to these instructions. The installation must comply with
regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction.
In the United States and Canada, follow all codes and standards for the following:
Step 1 — Safety
S US: National Fuel Gas Code (NFGC) NFPA 54--2006/ANSI
Z223.1--2006 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B
S CANADA: CSA B149.1--00 National Standard of Canada
Natural Gas and Propane Installation Code (CAN/CSA--B149.1--05)
Step 2 — General Installation
S US: Current edition of the NFGC and the NFPA 90B. For
copies, contact the National Fire Protection Association Inc., Batterymarch Park,Quincy, MA 02269; (www.NFPA.org) or for only the NFGC, contact the American Gas Association, 400 N. Capitol Street, N.W., Washington DC 20001 (www.AGA.org.)
S CANADA: CAN/CSA--B149.1--05. For a copy, contact
Standard Sales, CSA International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, M9W 1R3 Canada Step
Step 3 — Combustion and Ventilation Air
S US: Section 8.3 of the NFGC, Air for Combustion and
Ventilation
S CANADA: Part 7 of CAN/CSA--B149.1--05, Venting Systems
and Air Supply for Appliances
Step 4 — Duct Systems
S US and CANADA: Air Conditioning Contractors Association
(ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 2001 Fundamentals Handbook Chapter 34 or 2000 HVAC Systems and Equipment Handbook Chapters 9 and 16.
Step 5 — Acoustical Lining and Fibrous Glass Duct
S US and CANADA: current edition of SMACNA and NFPA
90B as tested by UL Standard 181 for Class I Rigid Air Ducts
Step 6 — Gas Piping and Gas Pipe Pressure Testing
S US: NFGC; chapters 5, 6, and 7 and National Plumbing Codes S CANADA: CAN/CSA--B149.1--05 Parts 4, 5, 6 and 9 and
Appendices A, B, E and H.
Step 7 — Electrical Connections
S US: National Electrical Code (NEC) ANSI/NFPA 70--2006 S CANADA: Canadian Electrical Code CSA C22.1
Step 8 — Venting
S US: NFGC; chapters 12 and 13 S CANADA: CAN/CSA--B149.1--05 Part 8 and Appendix C
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
!
CAUTION
FURNACE RELIABILITY HAZARD
Improper installation or service of furnace may cause premature furnace component failure.
Electrostatic discharge can affect electronic components. Follow the Electrostatic Discharge Precautions Procedure listed below during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple disconnects may be required. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing to recharge your body with static electricity (for example; DO NOT move or shuffle your feet, do not touch ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with static electricity), firmly touch a clean, unpainted metal surface of the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded) furnaces.
6. Before removing a new control from its container, discharge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 4 before bringing the control or yourself in contact with the furnace. Put all used and new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) mayalsobeusedtopreventESDdamage.
312A
5
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED ABOVE THE
312A
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
LOCATION
GENERAL
This multipoise furnace is shipped in packaged configuration. Some assembly and modifications are required when used in any of the four applications shown in Fig. 4.
NOTE: For high--altitude installations, the high--altitude conversion kit MUST be installed at or above 5500 ft above sea level. Obtain high--altitude conversion kit from your area authorized distributor.
This furnace must: S be installed so the electrical components are protected from
water.
S not be installed directly on any combustible material other than
wood flooring (refer to SAFETY CONSIDERATIONS).
S be located close to the chimney or vent and attached to an air
distribution system. Refer to Air Ducts section.
S be provided ample space for servicing and cleaning. Always
comply with minimum fire protection clearances shown on the furnace clearance to combustible construction label.
!
WARNING
CARBON MONOXIDE POISONING AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death, and furnace damage.
Corrosive or contaminated air may cause failure of parts containing flue gas, which could leak into the living space. Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products. Do not install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are met, in addition to all local codes and ordinances.
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
A02097
Fig. 4 -- Multipoise Orientations
The following types of furnace installations may require OUTDOOR AIR for combustion due to chemical exposures:
S Commercial buildings S Buildings with indoor pools S Laundry rooms S Hobby or craft rooms, and S Chemical storage areas
If air is exposed to the following substances, it should not be used for combustion air, and outdoor air may be required for
combustion:
S Permanent wave solutions S Chlorinated waxes and cleaners S Chlorine based swimming pool chemicals S Water softening chemicals S De-- icing salts or chemicals S Carbon tetrachloride S Halogen type refrigerants S Cleaning solvents (such as perchloroethylene) S Printing inks, paint removers, varnishes, etc. S Hydrochloric acid S Cements and glues S Antistatic fabric softeners for clothes dryers
S Masonry acid washing materials
All fuel--burning equipment must be supplied with air for fuel combustion. Sufficient air must be provided to avoid negative pressure in the equipment room or space. A positive seal mu st be made between the furnace cabinet and the return--air duct to prevent pulling air from the burner area and from draft safeguard opening.
6
!
WARNING
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
When the furnace is installed in a residential garage, the burners and ignition sources must be located at least 18 inches above the floor. The furnace must be located or protected to avoid damage by vehicles. When the furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, the furnace must be installed in accordance with the NFGC or CAN/CSA--B149.1--05. (See Fig. 5.)
Fig. 6 -- Prohibit Installation on Back
!
CAUTION
A02054
18-IN. MINIMUM
TO BURNERS
A93044
Fig. 5 -- Installation in a Garage
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect return-- air ducts to the back of the furnace. (See Fig. 6.)
PROPERTY DAMAGE HAZARD
Improper use or installation of this furnace may cause premature component failure. This gas furnace may be used for construction heat provided that:
--The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame roll--out and/or drawing combustion products into the structure.
--The furnace is controlled by a thermostat. It may not be ”hot wired” to provide heat continuously to the structure without thermostatic control.
--Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
--The temperature of the return air to the furnace is maintained between 55_F(13_C) and 80_F(27_C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
--The air temperature rise is within the rated rise range on the furnace rating plate, and the gas input rate has been set to the nameplate value.
--The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
--The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
--Verify proper furnace operating conditions including ignition, gas input rate, air temperature rise, and venting according to these installation instructions.
312A
LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with, or on the downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with the furnace, dampers or other flow control must prevent chilled air from entering the furnace. If the dampers are manually operated, they must be
7
equipped with means to prevent operation of either unit unless the damper is in the full--heat or full--cool position.
AIR FOR COMBUSTION AND
VENTILATION
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:
U.S. installations: Section 8.3 of the NFGC, Air for Combustion and Ventilation, and applicable provisions of the local building codes.
Canadian installations: Part 8 of the CAN/CSA--B149.1--05, Venting Systems and Air Supply for Appliances and all authorities having jurisdiction.
!
CAUTION
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage.
312A
Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make--up air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to Carbon Monoxide Poisoning Hazard warning in venting section of these instructions to determine if an adequate amount of make--up air is available.
The requirements for combustion and ventilation air depend upon whether or not the furnace is located in a space having a volume of at least 50 cubic feet per 1,000 Btuh input rating for all gas appliances installed in the space.
S Spaces having less than 50 cubic feet per 1,000 Btuh require the
Outdoor Combustion Air Method.
S Spaces having at least 50 cubic feet per 1,000 Btuh may use the
Indoor Combustion Air, Standard or Known Air Infiltration Method.
Outdoor Combustion Air
1. Provide the space with sufficient air for proper combustion, ventilation, and dilution of flue gases using permanent horihorizontal or vertical duct(s) or opening(s) directly communicating with the outdoors or spaces that freely communicate with the outdoors.
2. Fig. 7 illustrates how to provide TWO OUTDOOR OPENINGS, one inlet and one outlet combustion and ventilation air opening, to the outdoors.
a. One opening MUST commence within 12 in. (300 mm)
of the ceiling and the second opening MUST commence within 12 in. (300 mm) of the floor.
b. Size openings and ducts per Fig. 7 and Table 2.
c. TWO HORIZONTAL DUCTS require 1 square inch of
free area per 2,000 Btuh (1,100 mm2/kW) of combined input for all gas appliances in the space per Fig. 7 and Tab le 2.
d. TWO OPENINGS OR VERTICAL DUCTS require 1
square inch of free area per 4,000 Btuh (550 mm2/kW) for combined input of all gas appliances in the space per Fig. 7 and Table 2.
3. ONE OUTDOOR OPENING requires:
a. 1 square inch offreearea per 3,000 Btuh (734 mm2/kW)
for combined input of all gas appliances in the space per Tab le 2 a nd
b. Not less than the sum of the areas of all vent connectors
in the space.
Method
Table 2 – Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors
TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING
FURNACE
INPUT
(BTUH)
44,000 22 6 14.7 5 11 4 66,000 33 7 22 6 16.5 5
88,000 44 8 29.3 7 22 6 110,000 55 9 36.7 7 27.5 6 132,000 66 10 44 8 33 7 154,000 77 10 51.3 9 38.5 8
FURNACE WATER HEATER TOTAL INPUT
110,000 + 30,000 = (140,000 divided by 4,000) = 35.0 Sq. In. for each two Vertical Ducts or Openings
66,000 + 40,000 = (106,000 divided by 3,000) = 35.3 Sq. In. for a Single Duct or Opening 88,000 + 30,000 = (118,000 divided by 2,000) = 59.0 Sq. In. for each of two Horizontal Ducts
(1 SQ. IN./2,000 BTUH)
(1,100 SQ. MM/KW)
Free Area of
Opening and Duct
(Sq. In.)
Round Duct
(in. Dia)
(1 SQ. IN./3,000 BTUH)
(734 SQ. MM/KW)
Free Area of
Opening and Duct
(sq. In.)
8
Round Duct
(in. Dia)
TWO OPENINGS OR VERTICAL
Free Area of
Opening and Duct
(Sq. In.)
DUCTS
(1 SQ. IN./4,000 BTUH)
(550 SQ. MM/KW)
Round Duct
(In. Dia)
DUCTS
*
OUTDOORS
TO
1 SQ IN. PER 4000 BTUH*
CIRCULATING AIR
DUCTS
VENT THROUGH ROOF
12 MAX
1 SQ IN. PER 2000 BTUH*
DUCTS
TO
OUTDOORS
1 SQ IN. PER 2000 BTUH*
12 MAX
CIRCULATING AIR DUCTS
Minimum dimensions of 3 in.
Use any of the following
NOTE:
combinations of openings: A & B C & D D & E F & G
B
A
AIR DUCTS
CIRCULATING
OPENINGS SHALL BE
OF COMBUSTION AIR
CLEARANCE IN FRONT
D
VENT THROUGH ROOF
AT LEAST 3 IN.
OUTDOORS
C
DUCT
TO
E
12 MAX
F
G
1 SQ IN. PER 4000 BTUH*
Fig. 7 -- Air for Combustion, Ventilation and Dilution for
Outdoors
12 MAX
1 SQ IN.
PER 4000
BTUH*
OUTDOORS
1 SQ IN.
PER
4000
BTUH*
12 MAX
A03174
12" MAX
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
INTERIOR
HEATED
SPACE
CIRCULATING AIR DUCTS
* Minimum opening size is 100 sq in. with minimum dimensions of 3 in.
Minimum of 3 in. . when type-B1 vent is used.
UNCONFINED SPACE
6" MIN (FRONT)
1 SQ IN. PER 1000 BTUH* IN DOOR
OPENINGS SHALL BE AT LEAST 3 IN.
OR WALL
CLEARANCE IN FRONT OF COMBUSTION AIR
12" MAX
A03175
Fig. 8 -- Air for Combustion, Ventilation, and Dilution from
Indoors
312A
The opening shall commence within 12 in. (300 mm) of the ceiling. Appliances in the space shall have clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (150 mm) from the front. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
Indoor Combustion Air Known --Air--Infiltration Rate
E NFPA & AGA Standard and
Methods
Indoor air is permitted for combustion, ventilation, and dilution, if the Standard or Known--Air--Infiltration Method is used.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in death and/or personal injury.
Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases. The furnace combustion air supply must be provided in accordance with this instruction manual.
The Standard Method:
1. The space has no less volume than 50 cubic feet per 1,000 Btuh of the maximum input ratings for all gas appliances installed in the space and
2. The air infiltration rate is not known to be less than 0.40 air changes per hour (ACH).
The Known Air Infiltration Rate Method shall be used, if the infiltration rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of ACH and shall be determined per Table 3 or Equations 1 and 2. Determine the minimum required volume for each appliance in the space and add the volumes together to get the total minimum required volume for the space.
9
Table 3 – Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors
OTHER THAN FAN--- ASSISTED TOTAL
ACH
0.60 1,050 1,400 1,750 1,100 1,650 2,200 2,750 3,300 3,850
0.50 1,260 1,680 2,100 1,320 1,980 2,640 3,300 3,960 4,620
0.40 1,575 2,100 2,625 1,650 2,475 3,300 4,125 4,950 5,775
0.30 2,100 2,800 3,500 2,200 3,300 4,400 5,500 6,600 7,700
0.20 3,150 4,200 5,250 3,300 4,950 6,600 8,250 9,900 11,550
0.10 6,300 8,400 10,500 6,600 9,900 13,200 16,500 19,800 23,100
0.00 NP NP NP NP NP NP NP NP NP
NP = Not Permitted
Table 3--Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI
Z223.1--2006/NFPA 54--2006, 9.3.2.2:
1. For other than fan-- assisted appliances, such as a draft hood--equipped water heater:
312A
Volume
2. For fan--assisted applicances such as this furnace:
Volume
If:
= combined input of all other than fan--assisted
I
other
= combined input of all fan--assisted appliances in
I
fan
ACH = air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the Standard Method and to the Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if:
a. There are no closable doors between rooms.
b. Combining spaces on same floor level. Each opening
shall have free area of at least 1 in.2/1,000 Btuh (2,000 mm2/kW) of the total input rating of all gas appliances in the space, but not less than 100 in.2 (0.06 m2). One opening shall commence within 12 in. (300 mm) of the ceiling and the second opening shall commence within 12 in. (300 mm) of the floor. The minimum dimension of air openings shall be at least 3 in. (80 mm). (See Fig.
8.)
c. Combining space on different floor levels. The volumes
of spaces on different floor levels shall be considered as communicating spaces if connected by one or more permanent openings in doors or floors having free area of at least 2 in.2/1,000 Btuh (4,400 mm2/kW) of total input rating of all gas appliances.
2. An attic or crawlspace may be considered a space that freely communicates with the outdoors provided there are adequate permanent ventilation openings directly to outdoors having free area of at least 1--in.2/4,000 Btuh of total input rating for all gas appliances in the space.
3. In spaces that use the Indoor Combustion Air Method, infiltration should be adequate to provide air for combustion, permanent ventilation and dilution of flue gases. However, in buildings with unusually tight
(1,000s BTUH GAS INPUT RATE)
30 40 50 44 66 88 110 132 154
SpaceVolume(ft3)
21ft
=
Other
Fan
appliances in Btuh/hr
Btuh/hr
=
ACH
15ft ACH
3
3
I
other
1000 Btu/hr
I
fan
1000 Btu/hr
A04002
A04003
Combination of Indoor and Outdoor
1. Indoor openings shall compy with the Indoor
2. Outdoor openings shall be located as required in the
3. Outdoor openings shall be sized as follows:
UPFLOW INSTALLATION
Bottom Return Air
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom
2. Rotate bottom filler panel downward to release holding
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. This panel MUST be in place when only side return air is used.
NOTE: Side return--air openings can be used in UPFLOW and most HORIZONTAL configurations. Do not use side return--air openings in DOWNFLOW configuration.
FAN--- ASSISTED TOTAL
(1,000s BTUH GAS INPUT RATE)
construction, additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section. Unusually tight construction is defined as Construction with:
a. Walls and ceilings exposed to the outdoors have a
continuous, sealed vapor barrier. Openings are gasketed or sealed and
b. Doors and openable windows are weatherstripped and
c. Other openings are caulked or sealed. These include
joints around window and door frames, between sole plates and floors, between wall-- ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc.
Air
Combustion Air Method below and,
Outdoor Combustion Air Method mentioned previously
and,
a. Calculate the Ratio of all Indoor Space volume divided
by required volume for Indoor Combustion Air Method below.
b. Outdoor opening size reduction Factor is 1 minus the
Ratio in a. above.
c. Minimum size of Outdoor openings shall be the size
required in Outdoor Combustion Air Method above multiplied by reduction Factor in b. above. The minimumdimension of air openingsshallbenot lessthan 3in.(80mm).
INSTALLATION
Inlet
filler panel. (See Fig. 9.)
tabs.
Inlet
10
A02098
Fig. 9 -- Removing Bottom Closure Panel
Leveling Legs (If Desir
ed)
In upflow position with side return inlet(s), leveling legs may be used. (See Fig. 10.) Install field--supplied, 5/16 X 1--1/2 in. (max) corrosion --resistant machine bolts, washers and nuts.
NOTE: Bottom closure must be used when leveling legs are used. It may be necessary to remove and reinstall bottom closure panel to install leveling legs. To remove bottom closure panel, see item 1 in Bottom Return Air Inlet section in Step 1 above.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each bottom corner of furnace. (See Fig. 10.)
2. For each leg, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.
5. Reinstall bottom closure panel if removed.
5
⁄16″
5
⁄16″
1 3⁄4″
3
⁄4″
1
5
⁄16″
5
⁄16″
3
1
⁄4″
3
1
⁄4″
A02071
Fig. 10 -- Leveling Legs
DOWNFLOW INSTALLA
TION
NOTE: For downflow applications, this furnace is approved for
use on combustible flooring when any one of the following 3 accessories are used:
S Special Base, KGASB S Cased Coil Assembly Part No. CD5 or CK5 S Coil Box Part No. KCAKC
1. Determine application being installed from Table 4.
2. Construct hole in floor per Table 4 and Fig. 11.
3. Construct plenum to dimensions specified in Table 4 and Fig. 11.
4. If downflow subbase, KGASB is used, install as shown in Fig. 12. If Coil Assembly Part No. CD5 or CK5 or Coil Box Part No. KCAKC is used, install as shown in Fig. 13.
NOTE: It is recommended that the perforated supply--air duct flanges be completely folded over or removed from furnace when installing the furnace on a factory --supplied cased coil or coil box. To remove the supply--air duct flange, use wide duct pliers or hand seamers to bend flange back and forth until it breaks off. Be careful of sharp edges. (See Fig. 14.)
Bottom Return Air
Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
HORIZONTAL INSTALLA
TION
The furnace can be installed horizontally in an attic or crawl space on either the left--hand (LH) or right--hand (RH) side. The furnace can be hung from floor joists, rafters or trusses or installed on a non--combustible platform, blocks, bricks or pad.
!
WARNING
FIRE, EXPLOSION, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect return-- air ducts to the back of the furnace.
Suspended Furnace Support
The furnace may be supported under each end with threaded rod, angle iron or metal plumber’s strap as shown. (See Fig. 15 and
16.) Secure angle iron to bottom of furnace as shown. Heavy--gauge sheet metal straps (plumber’s straps) may be used to suspend the furnace from each bottom corner. To prevent screws from pulling out, use 2 #8 x .--in. screw into the side and 2 #8 x .--in. screw in the bottom of the furnace casing for each strap. (See Fig. 15 and 16.)
If the screws are attached to ONLY the furnace sides and not the bottom, the straps must be vertical against the furnace sides and not pull away from the furnace sides, so that the strap attachment screws are not in tension (are loaded in shear) for reliable support.
Platform Furnace
Support
Construct working platform at location where all required furnace clearances are met. (See Fig. 2 and 17.) For furnaces with 1--in. clearance requirement on side, set furnace on non--combustible blocks, bricks or angle iron. For crawlspace installations, if the furnace is not suspended from the floor joists, the ground
312A
11
underneath furnace must be level and the furnace set on blocks or bricks.
Roll--Out Pr
otection
Provide a minimum 17--3/4 in. X 22 in. piece of sheet metal for flame roll--out protection in front of burner area for furnaces closer than 12 inches above the combustible deck or suspended furnaces closer than 12 inches to joists. The sheet metal MUST extend underneath the furnace casing by 1 in. with the door removed.
The bottom closure panel on furnaces of widths 17--1/2 in. and larger may be used for flame roll--out protection when bottom of furnace is used for return air connection. See Fig. 17 for proper orientation of roll--out shield.
Bottom Return Air
Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
312A
1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air
Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. This panel MUST be in place when side return air inlet(s) are used without a bottom return air inlet.
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
A096285
Fig. 12 -- Furnace, Plenum, and Subbase installed on a
Combustible Floor
A
PLENUM
OPENING
B
OPENING
D
FLOOR
C
Fig. 11 -- Floor and Plenum Opening Dimensions
A096283
FURNACE
CD5 OR CK5
COIL ASSEMBLY
OR KCAKC
COIL BOX
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
A04140
A04140
Fig. 13 -- Furnace, Plenum, and Coil Assembly or Coil Box
Installed on a Combustible Floor
12
FURNACE
D
CASING
WIDTH
14–3/16
17–1/2
21
24--- 1/2
Table 4 – Opening dimensions (In.)
APPLICATION
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring (KGASB
subbase not required)
Downflow applications on combustible flooring
(KGASB subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on combustible flooring
(KGASB subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on combustible flooring
(KGASB subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on Combustible flooring
(KGASB subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box
(KGASB subbase not required)
PLENUM OPENING FLOOR OPENING
A B C D
12--- 11/16 21--- 5/8 13---5/16 22--- 1/4
12--- 9/16 19 13--- 3/16 19--- 5/8
11--- 13/16 19 13 --- 7/16 20 ---5/8
12--- 5/16 19 13--- 5/16 20
16 21--- 5/8 16 ---5/8 22---1/4
15--- 7/8 19 16---1/2 19 --- 5/8
15--- 1/8 19 16---3/4 20 --- 5/8
15--- 1/2 19 16---1/2 20
19--- 1/2 21 --- 5/8 20--- 1/8 22 --- 1/4
19--- 3/8 19 20 19--- 5/8
18--- 5/8 19 20---1/4 20 --- 5/8
19 19 20 20
23 21--- 1/8 23 ---5/8 22---1/4
22--- 7/8 19 23---1/2 19 --- 5/8
22--- 1/8 19 23---3/4 20 --- 5/8
22--- 1/2 19 23---1/2 20
312A
UPFLO
90û
120û
MIN
W OWNFLOW
YES
YES
NOT RECOMMENDED
D
120û MIN
Fig. 14 -- Duct Flanges
YES
YES
NOT RECOMMENDED
13
HORIZONTAL
90û
120û
MIN
YES
YES
NOT RECOMMENDE
A02329
OUTER DOOR ASSEMBLY
1
/4
" THREADED ROD
4 REQ.
312A
8" MIN FOR DOOR REMOVAL
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS REQ. PER ROD
Fig. 15 -- Horizontal Unit Suspension
SECURE ANGLE IRON TO BOTTOM OF FURNACE WITH 3 #8 x TYPICAL FOR 2 SUPPORTS
1
1
/4
1" SQUARE, 1 OR UNI-STRUT MAY BE USED
" x 1
1
/4
" x
/4
" ANGLE IRON
3
/4
" SCREWS
METHOD 2 USE (42) #8 x 3/4 SHEET METAL SCREWS TYPICAL FOR EACH STRAPS.THE STRAPS SHOULD BE VERTICAL AGAINST THE FURNACE SIDES AND NOT PULL AWAY FROM THE FURNACE SIDES.
A02345
METHOD 1 FOLD ALL STRAPS UNDER FURNACE AND SECURE WTH (42) #8 x 3/4 SHEET METAL SCREWS (2 SCREWS IN SIDE AND 2 SCREWS IN BOTTOM).
Fig. 16 -- Horizontal Suspension with Straps
14
A03176
LINE CONTACT ONLY PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF THE TOP AND TWO SIDES OF THE FURNACE JACKET AND BUILDING JOISTS, STUDS, OR FRAMING.
GAS ENTRY
TYPE-B VENT
17 3/4
OVER ALL
4 3/4
UNDER DOOR
1 UNDER FURNACE
EXTEND OUT 12OUT FROM FACE OF DOOR
17 3/4
22
EQUIPMENT MANUAL
SHUT-OFF GAS VALVE
SEDIMENT
TRAP
UNION
SHEET METAL
Fig. 17 -- Typical Attic Installation
Not all horizontal furnaces are approved for side return air connections. (See Fig. 20.)
FILTER
ARRANGEMENT
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, or death.
Never operate a furnace without a filter or with filter access door removed.
There are no provisions for an internal filter rack in these furnaces. An external filter rack is required.
This furnace is shipped with a factory--supplied Media Filter Cabinet. The Media Filter Cabinet uses either a factory--supplied standard 1--inch filter or 4--inch wide Media Filter which can be purchased separately.
Refer to the instructions supplied with Media Cabinet for assembly and installation options.
DUCTS
AIR
General Requir
ements
The duct system should be designed and sized according to accepted national standards such as those published by: Air Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or consult The Air Systems Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system design CFM at the design external static pressure. The furnace airflow rates are provided in Table 5--Air Delivery CFM (With Filter).
When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
6MIN*
30-IN. MIN WORK AREA
* WHEN USED WITH SINGLE WALL VENT CONNECTIONS
312A
A03177
Secure ductwork with proper fasteners for type of ductwork used. Seal supply-- and return--duct connections to furnace with code approved tape or duct sealer.
NOTE: Flexible connections should be used between ductwork and furnace to prevent transmission of vibration.
Ductwork passing through unconditioned space should be insulated to enhance system performance. When air conditioning is used, a vapor barrier is recommended.
Maintain a 1--in. clearance from combustible materials to supply air ductwork for a distance of 36 in. horizontally from the furnace. See NFPA 90B or local code for further requirements.
Ductwork Acoustical Tr NOTE: Metal duct systems that do not have a 90_ elbow and 10
ft of main duct to the first branch take--off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
Supply Air
Connections
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks.
Upflow and Horizontal
Connect supply--air duct to flanges on furnace supply--air outlet. Bend flange upward to 90_ with wide duct pliers. (See Fig. 14.) The supply--air duct must be connected to ONLY the furnace supply--outlet--air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing side to attach supply air duct, humidifier, or other accessories. All accessories MUST be connected to duct external to furnace main casing.
eatment
Furnaces
15
Table 5 – Air Delivery -- CFM (With Filter)*
312A
FURNACE
SIZE
045--- 08 /
024045
045--- 12 /
036045
070--- 081 /
024070
070--- 12 /
036070
070--- 16 /
048070
090--- 14 /
042090
090--- 16 /
048090
090--- 20 /
060090
110--- 12 /
036110
110--- 16 /
048110
RETURN---AIR
INLET
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom Only
Both Side or 1 Side & Bottom
1Side Only
Bottom or
Side(s)
Bottom or
Side(s)
SPEED
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
EXTERNAL STATIC PRESSURE (IN. WC)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
1120
930 820 725
1465 1295 1150 1030
860
1140
915 795 690
1440 1180 1015
885 695
1840 1610 1460 1260 1065
1650 1515 1385 1205
2060 1710 1470 1260 1030
2380 2185 1905 1595 1340
2485 2175 1845 1540 1280
2420 2160 1850 1530 1290
1625 1510 1360 1195
2055 1750 1545 1300 1050
1075
890 785 690
1400 1260 1120 1010
835
1105
885 770 665
1400 1165 1020
885 700
1790 1575 1430 1240 1040
1600 1485 1360 1180
2000 1695 1475 1365 1025
2295 2115 1865 1565 1310
2415 2130 1815 1515 1250
2345 2110 1815 1490 1250
1575 1470 1335 1180
1990 1725 1525 1290 1045
1020
850 750 655
1325 1210 1085
980 810
1055
855 740 630
1355 1150 1010
880 700
1730 1535 1400 1215 1015
1535 1440 1320 1160
1930 1665 1450 1245 1020
2205 2045 1815 1530 1280
2330 2070 1770 1475 1220
2265 2045 1765 1455 1220
1515 1415 1295 1155
1910 1670 1490 1275 1015
960 805 700 605
1250 1155 1040
945 780
1010
825 700 590
1300 1125
990 865 690
1670 1485 1360 1180
985
1465 1380 1260 1120
1835 1585 1390 1225
990
2105 1960 1740 1485 1225
2230 2000 1720 1435 1190
2165 1960 1710 1420 1190
1445 1355 1250 1115
1815 1605 1445 1235
975
895 750 650 555
1175 1090
985 895 745
955 785 655 550
1240 1085
965 845 670
1605 1435 1315 1145
955
1385 1300 1195 1065
1755 1480 1335 1165
940
2005 1875 1670 1430 1170
2135 1930 1655 1385
115
2070 1885 1635 1375
115
1355 1285 1180 1065
1695 1515 1355 1165
935
815 680 585 495
1085 1015
920 835 700
885 725 600 475
1170 1030
925 815 640
1530 1370 1260
110 915
1285 1220 1120 1005
1620 1390 1230 1090
890
1900 1770 1590 1355 1120
2030 1840 1580 1335 1105
1960 1790 1560 1320 1110
1260 1185 1100
980
1575 1400 1260 1085
880
720 600 505 405
980 930 835 765 635
815 655 510 415
1090
970 875 770 600
1450 1305 1205 1040
875
1175 1115 1025
925
1490 1245 1120
995 810
1775 1655 1490 1275 1040
1920 1740 1500 1270 1035
1850 1695 1480 1250 1040
1165 1070
985 860
1425 1255 1135 1005
815
605 500 400 305
860 830 740 685 555
715 530 420 340
1000
890 800 700 540
1370 1230 1130
985 825
1055
990 915 810
1315 1110 1005
880 720
1650 1535 1390 1160
955
1790 1620 1395 1175
945
1720 1570 1380 1160
950
990 890 810 740
1230 1120 1020
895 715
455 345 235
--- ---
725 700 620 570 445
545 420 325 245
890 785 700 605 460
1275 1145 1055
915 765
895 830 710 630
1115
955 855 750 615
1510 1400 1245 1055
850
1645 1495 1270 1045
845
1570 1445 1250 1055
835
785 725 670 605
1090
975 880 750 610
340 195
--- ---
--- ---
560 545 510 345 260
390 280
--- ---
--- ---
745 645 560 475 345
1170 1055
965 835 695
645 600 565 510
910 775 690 600 500
1335 1240 1110
920 750
1485 1345 1090
915 745
1420 1305 1110
905 740
595 530 475 410
910 785 750 620 515
16
High
M e d ---
Bottom Only
110--- 22 /
066110
*A filter is required for each return---air inlet. Airflow performance included 1---in. washable filter media such as contained in factory---authorized accessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.
--- --- Indicates unstable operating conditions.
Bottom Sides or
1 Side & Bottom
1Side Only
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High High
M e d ---
High Me-
dium
M e d --- L ow
Low
2530 2225 1895 1565 1320
--- ---
2205
2485 2155 1830 1520 1275
2460 2190 1885 1555 1295
--- ---
2175
2430 2135 1830 1505 1260
2380 2135 1865 1535 1265
2415 2120
2360 2100 1810 1490 1240
2285 2075 1820 1505 1235
2330 2065
2270 2040 1780 1470 1210
2200 1995 1770 1465 1205
2235 1975
2175 1970 1730 1430 1180
2085 1910 1700 1410 1160
2125 1900
2070 1885 1665 1385 1135
1970 1805 1610 1350 1105
1995 1790
1950 1790 1595 1330 1090
1835 1695 1520 1265 1035
1860 1685
1825 1680 1505 1250 1025
1695 1565 1410 1175
950
1735 1580
1685 1560 1395 1165
930
1545 1430 1290 1050
870
1605 1460
1535 1420 1275 1055
840
312A
17
Table 5 -- Air Delivery -- CFM (With Filter)* (Cont.)
FURNACE
SIZE
135--- 16 /
048135
135--- 22 /
066135
312A
155--- 20 /
060155
*A filter is required for each return---air inlet. Airflow performance included 1---in. washable filter media such as contained in factory---authorized accessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.
--- --- Indicates unstable operating conditions.
RETURN---AIR
INLET
Bottom
or
Side(s)
Bottom
Only
Bottom Sides
or
1 Side & Bottom
1SideOnly
Bottom Only
Both Sides Or 1
Side & Bottom
1SideOnly
SPEED
High M e d --- H ig h M e d --- L ow
Low
High M e d --- H ig h M e d --- L ow
Low
High M e d --- H ig h M e d --- L ow
Low
High M e d --- H ig h M e d --- L ow
Low
High M e d --- H ig h M e d --- L ow
Low
High M e d --- H ig h
High M e d --- H ig h
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
2090 1790 1545 1325 2485 2195 1880 1640
--- --­2180 1880 1640
2320 2125 1845 1640
2465 2115 1800 1570
--- --­2155
--- --­2140
2010 1755 1525 1320 2400 2150 1850 1635
--- --­2145 1850 1635
2250 2065 1825 1620
2430 2105 1790 1565
--- --­2135
--- --­2095
NOTE: For horizontal applications, the top--most flange may be bent past 90_ to allow the evaporator coil to hang on the flange temporarily while the remaining attachment and sealing of the
EXTERNAL STATIC PRESSURE (IN. WC)
1930 1705 1500 1295 2310 2090 1820 1615
2385 2060 1820 1615
2155 1995 1765 1580
2375 2075 1770 1550
2375 2095
2260 2040
1835 1640 1450 1265 2215 2000 1780 1585
2305 2010 1780 1585
2055 1910 1710 1540
2305 2030 1735 1525
2285 2040
2180 1975
1710 1550 1380 1210 2110 1920 1715 1530
2195 1945 1715 1530
1970 1815 1650 1485
2230 1980 1695 1495
2200 1975
2085 1890
1590 1465 1315 1150 2000 1825 1635 1465
2085 1865 1635 1465
1855 1710 1570 1410
2110 1910 1640 1445
2105 1895
1975 1810
1470 1360 1215
995 1880 1720
1540 1370
1960 1765 1540 1370
1725 1610 1475 1330
2000 1830 1570 1370
1995 1790
1865 1705
1335 1210 1005
865 1725 1565
1415 1255
1825 1660 1415 1255
1600 1490 1370 1220
1865 1725 1465 1270
1870 1685
1740 1595
horizontal furnaces are approved for side return air connections. (See Fig. 20.)
PIPING
GAS
coil are performed.
Downflow
Connect supply--air duct to supply--air outlet on furnace. Bend flange inward past 90_ with wide duct pliers. (See Fig. 14.) The supply--air duct must be connected to ONLY the furnace supplyoutlet or air conditioning coil casing (when used). When installed on combustible material, supply--air duct must be connected to ONLY the accessory subbase, KGASB0201ALL, or a factory approved air conditioning coil casing. DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected to duct
Furnaces
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
external to furnace casing.
Return Air
FIRE HAZARD
Failure to follow this warning could cause personal injury, death and/or property damage.
Never connect return--air ducts to the back of the furnace.
Connections
!
WARNING
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Use proper length of pipe to avoid stress on gas control manifold and a gas leak.
Follow instructions below.
1025
945 855
745 1535 1405
1290 1150
1670 1515 1290 1150
1450 1340 1240 1080
1725 1590 1345 1175
1730 1550
1605 1480
835 785 670
540 1355 1255
1160 1040
1465 1325 1160 1040
1280 1175 1100
960 1545
1425 1225 1070
1570 1400
1455 1325
Downflow Furnaces
The return--air duct must be connected to return--air opening (bottom inlet) as shown in Fig. 1. DO NOT cut into casing sides (left or right). Side opening is permitted for only upflow and most horizontal furnaces. Bypass humidifier connections should be made at ductwork or coil casing sides exterior to furnace. (See Fig. 19.) Upflow and Horizontal Furnaces The return--air duct must be connected to bottom, sides (left or right), or a combination of bottom and side(s) of main furnace casing as shown in Fig. 1. Bypass humidifier may be attached into unused return air side of the furnace casing. (See Fig. 18 and 20.) Not all
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to protect gas valve inlet from water and debris could result in death, personal injury and/or property damage.
Gas valve inlet and/or inlet pipe must remain capped until gas supply line is permanently installed to protect the valve from moisture and debris. Also, install a sediment trap in the gas supply piping at the inlet to the gas valve.
18
Loading...
+ 40 hidden pages