Sequence of Operation51...........................
Wiring Diagrams54...............................
Troubleshooting54................................
ama
ISO 9001:2000
CERTIFIED
REGISTERED
NOTE: Read the entire instruction manual before starting the
installation.
Portions of the text and tables are reprinted from NFPA 54/ANSI
Z223.1--2006E, with permission of National Fire Protection
Association, Quincy, MA 02269 and American Gas Association,
Washington DC 20001. This reprinted material is not the
complete and official position of the NFPA or ANSI on the
referenced subject, which is represented only by the standard in
its entirety.
28-7/8"
25-1/4"
22-9/16"
JUNCTION BOX
LOCATION
WIRE ENTRY
3-15/16"
LEFT HAND GAS
ENTRY
7/8" DIA. ACCESSORY
21-5/8"
BOTTOM INLET
24"
CASING
1-11/16"
24-7/8"
5-1/2"
4-13/16"
8-9/16"
ALTERNATE
JUNCTION BOX
VENT OUTLET
5 PLACES (TYP)
3-3/4"
2-7/16"
1-5/16"
1-1/8"
A
D
F
E
13/16"
LOCATIONS (TYP)
5-1/2"
11/16"
AIRFLOW
19"
OUTLET
1/2" DIA. K.O.THERMOSTAT
WIRE ENTRY
1-3/4" DIA.RIGHT HAND
GAS ENTRY
7/8" DIA. K.O. WIRE ENTRY
7/8" DIA. ACCESSORY
1-1/2"
22-1/16"
SIDE INLET
13/16"
11/16"
14-7/8"
1-1/4"
1"
312A
26-1/8"
(FLUE COLLAR)
5-15/16"
7/8" DIA
ACCESSORY
NOTES:
1. Two additional 7/8-in. diameter holes are located in the top plate.
2. Minimum return-air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters.
a. For 800 CFM-16-in. round or 14 1/2 x 12-in. rectangle.
b. For 1200 CFM-20-in. round or 14 1/2 x 19 1/2-in. rectangle.
c. For 1600 CFM-22-in. round or 14 1/2 x 22-in. rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets
a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
1/2" DIA THERMOSTAT
33-5/16"
11/16"
NOTES:
1. Two additional 7/8---in. diameter holes are located in the top plate.
2. Minimum return --- air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent
diameters.
a. For 800 CFM---16--- in. round or 14 1/2 x 12--- in. rectangle.
b. For 1200 CFM---20 ---in. round or 14 1/2 x 19 1/2--- in. rectangle.
c. For 1600 CFM---22 ---in. round or 14 1/2 x 22--- in. rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific u se of single side inlets. The use of both sideinlets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airfl ow requirements above 1800 CFM.
Fig. 1 -- Dimensional Drawing
7-3/4"
9-5/8"
11-1/2"
A04037
SAFETY CONSIDERATIONS
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous
operation, serious injury, death, or property damage.
Improper installation, adjustment, alteration, service,
maintenance, or use could cause carbon monoxide
poisoning, explosion, fire, electrical shock, or other
conditions which may cause personal injury or property
damage. Consult a qualified service agency, local gas
supplier, or your distributor or branch for information or
assistance. The qualified service agency must use only
factory--authorized and listed kits or accessories when
modifying this product.
!
CAUTION
FURNACE RELIABILITY HAZARD
Improper installation or misapplication of furnace may
require excessive servicing or cause premature component
failure.
Application of this furnace should be indoors with special
attention given to vent sizing and material, gas input rate,
air temperature rise, unit leveling, and unit sizing.
Installing and servicing heating equipment can be hazardous due
to gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations
must be performed by trained service personnel. When working
on heating equipment, observe precautions in literature, on tags,
and on labels attached to or shipped with furnace and other safety
precautions that may apply. These instructions cover minimum
requirements and conform to existing national standards and
safety codes. In some instances, these instructions exceed certain
local codes and ordinances, especially those that may not have
kept up with changing residential construction practices. We
require these instructions as a minimum for a safe installation.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts and servicing furnaces.
Wear safety glasses and work gloves. Have fire extinguisher
available during start--up and adjustment procedures and service
calls.
This is the safety--alert symbol
. When you see this symbol
on the furnace and in instructions or manuals, be alert to the
potential for personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify hazards which may result in minor personal injury or
* 5” or 6” vent connector may be required in some cases.
{ 135 and 155 size furnaces require five---inch or larger vents. Use a 4---5 or 4---6 inch vent adapter between furnace and vent connector.
CABINET
WIDTH
(IN.)
D
SUPPLY--- AIR
WIDTH (IN.)
E
RETURN---AIR
WIDTH (IN.)
product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
1. Use only with type of gas approved for this furnace. Refer
to the furnace rating plate 2. Install this furnace only in a
2. Install this furnace only in a location and position as
specified in the “Location” section of these instructions.
3. Provide adequate combustion and ventilation air to the
furnace space as specified in “Air for Combustion and
Ventilation” section.
4. Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system only, as
specified in the “Venting” section of these instructions.
5. Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for
the detection of leaks to check all connections, as specified
in the “Gas Piping” section.
6. Always install furnace to operate within the furnace’s
intended temperature--rise range with a duct system which
has an external static pressure within the allowable range,
as specified in the “Start--Up, Adjustments, and Safety
Check” section. See furnace rating plate.
7. When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled
by duct(s) sealed to the furnace casing and terminating
outside the space containing the furnace. See “Air Ducts”
section.
8. A gas-- fired furnace for installation in a residential garage
must be installed as specified in the warning box in the
“Location” section.
9. The furnace may be used for construction heat provided
that the furnace installation and operation complies with
the first CAUTION in the LOCATION section of these
instructions.
10. These Multipoise Gas--Fired Furnaces are CSA (formerly
A.G.A. and C.G.A.) design--certified for use with natural
and propane gases (see furnace rating plate) and for
installation in alcoves, attics, basements, closets, utility
rooms, crawlspaces, and garages. The furnace is
factory--shipped for use with natural gas. A CSA (A.G.A.
and C.G.A.) listed accessory gas conversion kit is required
F
C.L. TOP AND
BOTTOM FLUE
COLLAR (IN.)
FLUE
COLLAR*
(IN.)
SHIP WT. (LB)
11. See Fig. 2 for required clearances to combustible
construction.
12. Maintain a 1--in. clearance from combustible materials to
supply air ductwork for a distance of 36 inches
horizontally from the furnace. See NFPA 90B or local
code for further requirements.
13. These furnaces SHALL NOT be installed directly on
carpeting, tile, or any other combustible material other
than wood flooring. In downflow installations, factory
accessory floor base MUST be used when installed on
combustible materials and wood flooring. Special base is
not required when this furnace is installed on
manufacturer’s Coil Assembly Part No. CD5 or CK5, or
when Coil Box Part No. KCAKC is used. See Fig. 2 for
clearance to combustible construction information.
INTRODUCTION
The Series 120/C 4--way multipoise Category I fan--assisted
furnace is CSA (formerly A.A.A.. and C.G.A.) design--certified.
A Category I fan--assisted furnace is an appliance equipped with
an integral mechanical means to either draw or force products of
combustion through the combustion chamber and/or heat
exchanger. The furnace is factory--shipped for use with natural
gas. This furnace is not approved for installation in mobile
homes, recreational vehicles, or outdoors.
These furnaces shall not be installed directly on carpeting, tile, or
any other combustible material other than wood flooring. For
downflow installations, a factory accessory floor base must be
used when installed on combustible materials and wood flooring.
This special base is not required when this furnace is installed on
the manufacturer’s coil assembly, or when the manufacturer’s coil
box is used. See Fig. 2 for clearance to combustible material
information.
This furnace is designed for minimum continuous return--air
temperature of 60_F db or intermittent operation down to 55_F
db such as when used with a night setback thermostat. Return-- air
temperature must not exceed 80_F db. Failure to follow these
return-- air temperature limits may affect reliability of heat
exchangers, motors, and controls. (See Fig. 3.)
For accessory installation details, refer to the applicable
instruction literature.
NOTE: Remove all shipping brackets and materials before
operating the furnace.
to convert furnace for use with propane gas.
FILTER
MEDIA
CABINET
SIZE (IN.)
312A
3
312A
INSTALLATION
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
DISTANCE MINIMALE EN POUCES AUX CONSTRUCTIONS COMBUSTIBLES
This forced air furnace is equipped for use with
natural gas at altitudes 0-10,000 ft (0-3,050m).
An accessory kit, supplied by the
manufacturer, shall be used to convert to propane
gas use or may be required for some natural gas
applications.
This furnace is for indoor installation in a
building constructed on site.
This furnace may be installed on combustible
flooring in alcove or closet at minimum clearance
as indicated by the diagram from combusitble
material.
This furnace may be used with a Type B-1 Vent
and may be vented in common with other gas
fired appliances.
Cette fournaise à air pulsé est équipée
pour utilisation avec gaz naturel et altitudes
comprises entre 0-3,050m (0-10,000 pi).
Utiliser une trousse de conversion, fournie par
le fabricant, pour passer au gaz propane ou pour
certaines installations au gaz naturel.
This furnace is approved for UPFLOW, DOWNFLOW, and
HORIZONTAL installations.
Cette fournaise est approuvée pour l 'installation HORIZONTALE
et la circulation d 'air VERS LE HAUT et VERS LE BAS.
Clearance arrows
do not change with
furnace orientation.
0"
B
A
A
C
R
K
R
I
È
R
E
E
D
I
S
É
T
Ô
C
0"
*
1"
Les fléches de dégagement
l 'orientation de la fournaise.
TOP / PLE NUM
DESSUS / CHAMBRE D'AIR
E
C
E
A
S
N
I
A
R
U
N
F
R
U
T
FO
N
O
T
R
N
F
A
V
A
F
R
O
A
N
V
T
A
N
T
3"
Cette fournaise est prévue pour être
installée dans un bâtiment construit sur place.
Cette fournaise peut être installée sur
un plancher combustible dans une alcôve ou
dans un garde-robe en respectant le minimum
d'espace libre des matériaux combustibles, tel
´
indiqué sur le diagramme.
qu
Cette fournaise peut être utilisée avec un
´
évacuation de Type B-1 ou connectée
conduit d
au conduit ommun d 'autres appareils à gaz.
Vent Clearance to combustibles:
For Single Wall vents 6 inches (6 po).
For Type B-1 vent type 1 inch (1 po).
Dégagement de l´évent avec combustibles:
Pour conduit d´évacuation à paroi simple 6 po (6 inches).
Pour conduit d
BOTTOM
DESSOUS
"
0
†
´
évacuation de Type B-1 1 po (1 inch).
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
DOWNFLOW POSITIONS:
Installation on non-combusibible floors only.
†
For Installation on combustible flooring only when installed on special base, Part No. KGASB0201ALL,
Coil Assembly, Part No. CD5 or CK5, or Coil Casing, Part No. KCAKC.
18 inches front clearance required for alcove.
Ø
Indicates supply or return sides when furnace is in the horizontal position. Line contact only permissible
*
between lines formed by intersections of the Top and two Sides of the furnace jacket, and building joists,
studs or framing.
DÉGAGEMENT MINIMUM EN POUCES AVEC ÉLÉMENTS
DE CONSTRUCTION COMBUSTIBLES
POUR LA POSITION COURANT DESCENDANT:
Pour l´installation sur plancher non combustible seulement.
†
´
installation sur un plancher combustible seulement quand on utilise la base spéciale, pièce
Pour l
nº KGASB0201ALL, l
nº KCAKC.
Dans une alcôve, on doit maintenir un dégagement à l
Ø
La poistion indiquée concerne le côté d
*
position horizontale.
Le contact n
´
est permis qu´entre les lignes formées par les intersections du dessus et des
deux côtés de la cherrise de la fournaise et les solives, montant sous cadre de charpente.
´
ensemble serpentin, pièce nº CD5 ou CK5, ou le carter de serpentin, pièce
´
´
entrée ou de retour quand la fournaise est dans la
avant de 18 po (450mm).
327590-101 REV. C
ne change pas avec
0"
E
D
*
I
È
S
T
Ô
C
S
E
R
E
N
V
I
T
R
C
E
E
T
I
E
N
24"
MIN
Ø
Clearance in inches
Dégagement (po).
MIN
Fig. 2 -- Clearances to Combustibles
4
A04123
80
60
A04036
Fig. 3 -- Return Air Temperature
CODES AND STANDARDS
Follow all national and local codes and standards in addition
to these instructions. The installation must comply with
regulations of the serving gas supplier, local building, heating,
plumbing, and other codes. In absence of local codes, the
installation must comply with the national codes listed below and
all authorities having jurisdiction.
In the United States and Canada, follow all codes and standards
for the following:
Step 1 — Safety
SUS: National Fuel Gas Code (NFGC) NFPA 54--2006/ANSI
Z223.1--2006 and the Installation Standards, Warm Air Heating
and Air Conditioning Systems ANSI/NFPA 90B
SCANADA: CSA B149.1--00 National Standard of Canada
SUS: Current edition of the NFGC and the NFPA 90B. For
copies, contact the National Fire Protection Association Inc.,
Batterymarch Park,Quincy, MA 02269; (www.NFPA.org) or for
only the NFGC, contact the American Gas Association, 400 N.
Capitol Street, N.W., Washington DC 20001 (www.AGA.org.)
SUS: Section 8.3 of the NFGC, Air for Combustion and
Ventilation
S CANADA: Part 7 of CAN/CSA--B149.1--05, Venting Systems
and Air Supply for Appliances
Step 4 — Duct Systems
S US and CANADA: Air Conditioning Contractors Association
(ACCA) Manual D, Sheet Metal and Air Conditioning
Contractors National Association (SMACNA), or American
Society of Heating, Refrigeration, and Air Conditioning
Engineers (ASHRAE) 2001 Fundamentals Handbook Chapter
34 or 2000 HVAC Systems and Equipment Handbook Chapters
9 and 16.
Step 5 — Acoustical Lining and Fibrous Glass Duct
SUS and CANADA: current edition of SMACNA and NFPA
90B as tested by UL Standard 181 for Class I Rigid Air Ducts
Step 6 — Gas Piping and Gas Pipe Pressure Testing
S US: NFGC; chapters 5, 6, and 7 and National Plumbing Codes
SCANADA: CAN/CSA--B149.1--05 Parts 4, 5, 6 and 9 and
Appendices A, B, E and H.
Step 7 — Electrical Connections
S US: National Electrical Code (NEC) ANSI/NFPA 70--2006
S CANADA: Canadian Electrical Code CSA C22.1
Step 8 — Venting
S US: NFGC; chapters 12 and 13
S CANADA: CAN/CSA--B149.1--05 Part 8 and Appendix C
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
!
CAUTION
FURNACE RELIABILITY HAZARD
Improper installation or service of furnace may cause
premature furnace component failure.
Electrostatic discharge can affect electronic components.
Follow the Electrostatic Discharge Precautions Procedure
listed below during furnace installation and servicing to
protect the furnace electronic control. Precautions will
prevent electrostatic discharges from personnel and hand
tools which are held during the procedure. These
precautions will help to avoid exposing the control to
electrostatic discharge by putting the furnace, the control,
and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple disconnects
may be required. DO NOT TOUCH THE CONTROL OR
ANY WIRE CONNECTED TO THE CONTROL PRIOR
TODISCHARGINGYOURBODY’S
ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the
furnace chassis which is close to the control. Tools held in
a person’s hand during grounding will be satisfactorily
discharged.
3. After touching the chassis, you may proceed to service the
control or connecting wires as long as you do nothing to
recharge your body with static electricity (for example;
DO NOT move or shuffle your feet, do not touch
ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body
with static electricity), firmly touch a clean, unpainted
metal surface of the furnace again before touching control
or wires.
5. Use this procedure for installed and uninstalled
(ungrounded) furnaces.
6. Before removing a new control from its container,
discharge your body’s electrostatic charge to ground to
protect the control from damage. If the control is to be
installed in a furnace, follow items 1 through 4 before
bringing the control or yourself in contact with the
furnace. Put all used and new controls into containers
before touching ungrounded objects.
7. An ESD service kit (available from commercial sources)
mayalsobeusedtopreventESDdamage.
312A
5
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED ABOVE THE
312A
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
LOCATION
GENERAL
This multipoise furnace is shipped in packaged configuration.
Some assembly and modifications are required when used in any
of the four applications shown in Fig. 4.
NOTE:For high--altitude installations, the high--altitude
conversion kit MUST be installed at or above 5500 ft above sea
level. Obtain high--altitude conversion kit from your area
authorized distributor.
This furnace must:
Sbe installed so the electrical components are protected from
water.
S not be installed directly on any combustible material other than
wood flooring (refer to SAFETY CONSIDERATIONS).
S be located close to the chimney or vent and attached to an air
distribution system. Refer to Air Ducts section.
Sbe provided ample space for servicing and cleaning. Always
comply with minimum fire protection clearances shown on the
furnace clearance to combustible construction label.
!
WARNING
CARBON MONOXIDE POISONING AND UNIT
DAMAGE HAZARD
Failure to follow this warning could result in personal
injury or death, and furnace damage.
Corrosive or contaminated air may cause failure of parts
containing flue gas, which could leak into the living space.
Air for combustion must not be contaminated by halogen
compounds, which include fluoride, chloride, bromide, and
iodide. These elements can corrode heat exchangers and
shorten furnace life. Air contaminants are found in aerosol
sprays, detergents, bleaches, cleaning solvents, salts, air
fresheners, and other household products. Do not install
furnace in a corrosive or contaminated atmosphere. Make
sure all combustion and circulating air requirements are met,
in addition to all local codes and ordinances.
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
A02097
Fig. 4 -- Multipoise Orientations
The following types of furnace installations may require
OUTDOOR AIR for combustion due to chemical exposures:
S Commercial buildings
S Buildings with indoor pools
S Laundry rooms
S Hobby or craft rooms, and
S Chemical storage areas
If air is exposed to the following substances, it should not be used
for combustion air, and outdoor air may be required for
combustion:
S Permanent wave solutions
S Chlorinated waxes and cleaners
S Chlorine based swimming pool chemicals
S Water softening chemicals
S De-- icing salts or chemicals
S Carbon tetrachloride
S Halogen type refrigerants
S Cleaning solvents (such as perchloroethylene)
S Printing inks, paint removers, varnishes, etc.
S Hydrochloric acid
S Cements and glues
S Antistatic fabric softeners for clothes dryers
S Masonry acid washing materials
All fuel--burning equipment must be supplied with air for fuel
combustion. Sufficient air must be provided to avoid negative
pressure in the equipment room or space. A positive seal mu st be
made between the furnace cabinet and the return--air duct to
prevent pulling air from the burner area and from draft safeguard
opening.
6
!
WARNING
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
When the furnace is installed in a residential garage, the
burners and ignition sources must be located at least 18
inches above the floor. The furnace must be located or
protected to avoid damage by vehicles. When the furnace is
installed in a public garage, airplane hangar, or other
building having a hazardous atmosphere, the furnace must
be installedin accordance withthe NFGC or
CAN/CSA--B149.1--05. (See Fig. 5.)
Fig. 6 -- Prohibit Installation on Back
!
CAUTION
A02054
18-IN. MINIMUM
TO BURNERS
A93044
Fig. 5 -- Installation in a Garage
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Do not install the furnace on its back or hang furnace with
control compartment facing downward. Safety control
operation will be adversely affected. Never connect
return-- air ducts to the back of the furnace. (See Fig. 6.)
PROPERTY DAMAGE HAZARD
Improper use or installation of this furnace may cause
premature component failure. This gas furnace may be used
for construction heat provided that:
--The furnace is permanently installed with all electrical
wiring, piping, venting and ducting installed according to
these installation instructions. A return air duct is provided,
sealed to the furnace casing, and terminated outside the
space containing the furnace. This prevents a negative
pressure condition as created by the circulating air blower,
causing a flame roll--out and/or drawing combustion
products into the structure.
--The furnace is controlled by a thermostat. It may not be
”hot wired” to provide heat continuously to the structure
without thermostatic control.
--Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and
other construction materials. It also prevents the
entrainment of drywall dust into combustion air, which can
cause fouling and plugging of furnace components.
--The temperature of the return air to the furnace is
maintained between 55_F(13_C) and 80_F(27_C), with
no evening setback or shutdown. The use of the furnace
while the structure is under construction is deemed to be
intermittent operation per our installation instructions.
--The air temperature rise is within the rated rise range on
the furnace rating plate, and the gas input rate has been set
to the nameplate value.
--The filters used to clean the circulating air during the
construction process must be either changed or thoroughly
cleaned prior to occupancy.
--The furnace, ductwork and filters are cleaned as necessary
to remove drywall dust and construction debris from all
HVAC system components after construction is completed.
--Verify proper furnace operating conditions including
ignition, gas input rate, air temperature rise, and venting
according to these installation instructions.
312A
LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with, or on the
downstream side of the unit to avoid condensation in the heat
exchangers. When installed parallel with the furnace, dampers or
other flow control must prevent chilled air from entering the
furnace. If the dampers are manually operated, they must be
7
equipped with means to prevent operation of either unit unless
the damper is in the full--heat or full--cool position.
AIR FOR COMBUSTION AND
VENTILATION
Provisions for adequate combustion, ventilation, and dilution air
must be provided in accordance with:
U.S. installations: Section 8.3 of the NFGC, Air for Combustion
and Ventilation, and applicable provisions of the local building
codes.
Canadian installations: Part 8 of the CAN/CSA--B149.1--05,
Venting Systems and Air Supply for Appliances and all
authorities having jurisdiction.
!
CAUTION
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage.
312A
Air for combustion must not be contaminated by halogen
compounds, which include fluoride, chloride, bromide, and
iodide. These elements can corrode heat exchangers and
shorten furnace life. Air contaminants are found in aerosol
sprays, detergents, bleaches, cleaning solvents, salts, air
fresheners, and other household products.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
The operation of exhaust fans, kitchen ventilation fans,
clothes dryers, attic exhaust fans or fireplaces could create a
NEGATIVE PRESSURE CONDITION at the furnace.
Make--up air MUST be provided for the ventilation devices,
in addition to that required by the furnace. Refer to Carbon
Monoxide Poisoning Hazard warning in venting section of
these instructions to determine if an adequate amount of
make--up air is available.
The requirements for combustion and ventilation air depend upon
whether or not the furnace is located in a space having a volume
of at least 50 cubic feet per 1,000 Btuh input rating for all gas
appliances installed in the space.
S Spaces having less than 50 cubic feet per 1,000 Btuh require the
Outdoor Combustion Air Method.
S Spaces having at least 50 cubic feet per 1,000 Btuh may use the
Indoor Combustion Air, Standard or Known Air Infiltration
Method.
Outdoor Combustion Air
1. Provide the space with sufficient air for proper
combustion, ventilation, and dilution of flue gases using
permanent horihorizontal or vertical duct(s) or opening(s)
directly communicating with the outdoors or spaces that
freely communicate with the outdoors.
2. Fig. 7 illustrates how to provide TWO OUTDOOR
OPENINGS, one inlet and one outlet combustion and
ventilation air opening, to the outdoors.
a. One opening MUST commence within 12 in. (300 mm)
of the ceiling and the second opening MUST commence
within 12 in. (300 mm) of the floor.
b. Size openings and ducts per Fig. 7 and Table 2.
c. TWO HORIZONTAL DUCTS require 1 square inch of
free area per 2,000 Btuh (1,100 mm2/kW) of combined
input for all gas appliances in the space per Fig. 7 and
Tab le 2.
d. TWO OPENINGS OR VERTICAL DUCTS require 1
square inch of free area per 4,000 Btuh (550 mm2/kW)
for combined input of all gas appliances in the space per
Fig. 7 and Table 2.
3. ONE OUTDOOR OPENING requires:
a. 1 square inch offreearea per 3,000 Btuh (734 mm2/kW)
for combined input of all gas appliances in the space per
Tab le 2 a nd
b. Not less than the sum of the areas of all vent connectors
in the space.
Method
Table 2 – Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors
110,000+30,000= (140,000 divided by 4,000)=35.0 Sq. In. for each two Vertical Ducts or Openings
66,000+40,000= (106,000 divided by 3,000)=35.3 Sq. In. for a Single Duct or Opening
88,000+30,000= (118,000 divided by 2,000)=59.0 Sq. In. for each of two Horizontal Ducts
(1 SQ. IN./2,000 BTUH)
(1,100 SQ. MM/KW)
Free Area of
Opening and Duct
(Sq. In.)
Round Duct
(in. Dia)
(1 SQ. IN./3,000 BTUH)
(734 SQ. MM/KW)
Free Area of
Opening and Duct
(sq. In.)
8
Round Duct
(in. Dia)
TWO OPENINGS OR VERTICAL
Free Area of
Opening and Duct
(Sq. In.)
DUCTS
(1 SQ. IN./4,000 BTUH)
(550 SQ. MM/KW)
Round Duct
(In. Dia)
DUCTS
*
OUTDOORS
TO
1 SQ IN.
PER 4000
BTUH*
CIRCULATING AIR
DUCTS
VENT THROUGH ROOF
12″ MAX
1 SQ IN.
PER 2000
BTUH*
DUCTS
TO
OUTDOORS
1 SQ IN.
PER 2000
BTUH*
12″ MAX
CIRCULATING AIR DUCTS
Minimum dimensions of 3 in.
Use any of the following
NOTE:
combinations of openings:
A & B C & D D & E F & G
B
A
AIR DUCTS
CIRCULATING
OPENINGS SHALL BE
OF COMBUSTION AIR
CLEARANCE IN FRONT
D
VENT
THROUGH
ROOF
AT LEAST 3 IN.
OUTDOORS
C
DUCT
TO
E
12″ MAX
F
G
1 SQ IN.
PER 4000
BTUH*
Fig. 7 -- Air for Combustion, Ventilation and Dilution for
Outdoors
12″
MAX
1 SQ IN.
PER
4000
BTUH*
OUTDOORS
1 SQ IN.
PER
4000
BTUH*
12″
MAX
A03174
12" MAX
1 SQ IN.
PER 1000
BTUH* IN DOOR
OR WALL
INTERIOR
HEATED
SPACE
CIRCULATING AIR DUCTS
* Minimum opening size is 100 sq in. with
minimum dimensions of 3 in.
†
Minimum of 3 in. . when type-B1 vent is used.
UNCONFINED
SPACE
6" MIN
(FRONT)
1 SQ IN.
PER 1000
BTUH* IN DOOR
OPENINGS SHALL BE AT LEAST 3 IN.
OR WALL
CLEARANCE IN FRONT OF COMBUSTION AIR
†
12" MAX
A03175
Fig. 8 -- Air for Combustion, Ventilation, and Dilution from
Indoors
312A
The opening shall commence within 12 in. (300 mm) of the
ceiling. Appliances in the space shall have clearances of at least 1
in. (25 mm) from the sides and back and 6 in. (150 mm) from the
front. The opening shall directly communicate with the outdoors
or shall communicate through a vertical or horizontal duct to the
outdoors or spaces (crawl or attic) that freely communicate with
the outdoors.
Indoor Combustion Air
Known --Air--Infiltration Rate
E NFPA & AGA Standard and
Methods
Indoor air is permitted for combustion, ventilation, and dilution,if the Standard or Known--Air--Infiltration Method is used.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in death and/or
personal injury.
Many homes require air to be supplied from outdoors for
furnace combustion, ventilation, and dilution of flue gases.
The furnace combustion air supply must be provided in
accordance with this instruction manual.
The Standard Method:
1. The space has no less volume than 50 cubic feet per 1,000
Btuh of the maximum input ratings for all gas appliances
installed in the space and
2. The air infiltration rate is not known to be less than 0.40
air changes per hour (ACH).
The Known Air Infiltration Rate Method shall be used, if the
infiltration rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The
minimum required volume of the space varies with the number of
ACH and shall be determined per Table 3 or Equations 1 and 2.
Determine the minimum required volume for each appliance in
the space and add the volumes together to get the total minimum
required volume for the space.
9
Table 3 – Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors
Table 3--Minimum Space Volumes were determined by using
the following equations from the National Fuel Gas Code ANSI
Z223.1--2006/NFPA 54--2006, 9.3.2.2:
1. For other than fan-- assisted appliances, such as a draft
hood--equipped water heater:
312A
Volume
2. For fan--assisted applicances such as this furnace:
Volume
If:
= combined input of all other than fan--assisted
I
other
= combined input of all fan--assisted appliances in
I
fan
ACH = air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the Standard Method and
to the Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if:
a. There are no closable doors between rooms.
b. Combining spaces on same floor level. Each opening
shall have free area of at least 1 in.2/1,000 Btuh (2,000
mm2/kW) of the total input rating of all gas appliances
in the space, but not less than 100 in.2 (0.06 m2). One
opening shall commence within 12 in. (300 mm) of the
ceiling and the second opening shall commence within
12 in. (300 mm) of the floor. The minimum dimension
of air openings shall be at least 3 in. (80 mm). (See Fig.
8.)
c. Combining space on different floor levels. The volumes
of spaces on different floor levels shall be considered as
communicating spaces if connected by one or more
permanent openings in doors or floors having free area
of at least 2 in.2/1,000 Btuh (4,400 mm2/kW) of total
input rating of all gas appliances.
2. An attic or crawlspace may be considered a space that
freely communicates with the outdoors provided there are
adequate permanent ventilation openings directly to
outdoors having free area of at least 1--in.2/4,000 Btuh of
total input rating for all gas appliances in the space.
3. In spaces that use the Indoor Combustion Air Method,
infiltration should be adequate to provide air for
combustion, permanent ventilation and dilution of flue
gases. However, in buildings with unusually tight
(1,000s BTUH GAS INPUT RATE)
304050446688110132154
SpaceVolume(ft3)
21ft
=
Other
Fan
appliances in Btuh/hr
Btuh/hr
=
ACH
15ft
ACH
3
3
I
other
1000 Btu/hr
I
fan
1000 Btu/hr
A04002
A04003
Combination of Indoor and Outdoor
1. Indoor openings shall compy with the Indoor
2. Outdoor openings shall be located as required in the
3. Outdoor openings shall be sized as follows:
UPFLOW INSTALLATION
Bottom Return Air
These furnaces are shipped with bottom closure panel installed in
bottom return--air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,
perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom
2. Rotate bottom filler panel downward to release holding
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air
These furnaces are shipped with bottom closure panel installed in
bottom return--air opening. This panel MUST be in place when
only side return air is used.
NOTE: Side return--air openings can be used in UPFLOW and
most HORIZONTAL configurations. Do not use side return--air
openings in DOWNFLOW configuration.
FAN--- ASSISTED TOTAL
(1,000s BTUH GAS INPUT RATE)
construction, additional air MUST be provided using the
methods described in the Outdoor Combustion Air
Method section. Unusually tight construction is defined as
Construction with:
a. Walls and ceilings exposed to the outdoors have a
continuous, sealed vapor barrier. Openings are gasketed
or sealed and
b. Doors and openable windows are weatherstripped and
c. Other openings are caulked or sealed. These include
joints around window and door frames, between sole
plates and floors, between wall-- ceiling joints, between
wall panels, at penetrations for plumbing, electrical and
gas lines, etc.
Air
Combustion Air Method below and,
Outdoor Combustion Air Method mentioned previously
and,
a. Calculate the Ratio of all Indoor Space volume divided
by required volume for Indoor Combustion Air
Method below.
b. Outdoor opening size reduction Factor is 1 minus the
Ratio in a. above.
c. Minimum size of Outdoor openings shall be the size
required in Outdoor Combustion Air Method above
multiplied by reduction Factor in b. above. The
minimumdimension of air openingsshallbenot lessthan
3in.(80mm).
INSTALLATION
Inlet
filler panel. (See Fig. 9.)
tabs.
Inlet
10
A02098
Fig. 9 -- Removing Bottom Closure Panel
Leveling Legs (If Desir
ed)
In upflow position with side return inlet(s), leveling legs may be
used. (See Fig. 10.) Install field--supplied, 5/16 X 1--1/2 in. (max)
corrosion --resistant machine bolts, washers and nuts.
NOTE: Bottom closure must be used when leveling legs are
used. It may be necessary to remove and reinstall bottom closure
panel to install leveling legs. To remove bottom closure panel, see
item 1 in Bottom Return Air Inlet section in Step 1 above.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in
each bottom corner of furnace. (See Fig. 10.)
2. For each leg, install nut on bolt and then install bolt and
nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install
flat washer if desired.)
4. Adjust outside nut to provide desired height, and tighten
inside nut to secure arrangement.
5. Reinstall bottom closure panel if removed.
5
⁄16″
5
⁄16″
1 3⁄4″
3
⁄4″
1
5
⁄16″
5
⁄16″
3
1
⁄4″
3
1
⁄4″
A02071
Fig. 10 -- Leveling Legs
DOWNFLOW INSTALLA
TION
NOTE: For downflow applications, this furnace is approved for
use on combustible flooring when any one of the following 3
accessories are used:
S Special Base, KGASB
S Cased Coil Assembly Part No. CD5 or CK5
S Coil Box Part No. KCAKC
1. Determine application being installed from Table 4.
2. Construct hole in floor per Table 4 and Fig. 11.
3. Construct plenum to dimensions specified in Table 4 and
Fig. 11.
4. If downflow subbase, KGASB is used, install as shown in
Fig. 12. If Coil Assembly Part No. CD5 or CK5 or Coil
Box Part No. KCAKC is used, install as shown in Fig. 13.
NOTE: It is recommended that the perforated supply--air duct
flanges be completely folded over or removed from furnace when
installing the furnace on a factory --supplied cased coil or coil box.
To remove the supply--air duct flange, use wide duct pliers or
hand seamers to bend flange back and forth until it breaks off. Be
careful of sharp edges. (See Fig. 14.)
Bottom Return Air
Inlet
These furnaces are shipped with bottom closure panel installed in
bottom return--air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,
perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom
filler panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding
tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
HORIZONTAL INSTALLA
TION
The furnace can be installed horizontally in an attic or crawl space
on either the left--hand (LH) or right--hand (RH) side. The furnace
can be hung from floor joists, rafters or trusses or installed on a
non--combustible platform, blocks, bricks or pad.
!
WARNING
FIRE, EXPLOSION, AND CARBON MONOXIDE
POISONING HAZARD
Failure to follow this warning could result in personal
injury, death, or property damage.
Do not install the furnace on its back or hang furnace with
control compartment facing downward. Safety control
operation will be adversely affected. Never connect
return-- air ducts to the back of the furnace.
Suspended Furnace Support
The furnace may be supported under each end with threaded rod,
angle iron or metal plumber’s strap as shown. (See Fig. 15 and
16.) Secure angle iron to bottom of furnace as shown.
Heavy--gauge sheet metal straps (plumber’s straps) may be used
to suspend the furnace from each bottom corner. To prevent
screws from pulling out, use 2 #8 x .--in. screw into the side and 2
#8 x .--in. screw in the bottom of the furnace casing for each strap.
(See Fig. 15 and 16.)
If the screws are attached to ONLY the furnace sides and not the
bottom, the straps must be vertical against the furnace sides and
not pull away from the furnace sides, so that the strap attachment
screws are not in tension (are loaded in shear) for reliable support.
Platform Furnace
Support
Construct working platform at location where all required furnace
clearances are met. (See Fig. 2 and 17.) For furnaces with 1--in.
clearance requirement on side, set furnace on non--combustible
blocks, bricks or angle iron. For crawlspace installations, if the
furnace is not suspended from the floor joists, the ground
312A
11
underneath furnace must be level and the furnace set on blocks or
bricks.
Roll--Out Pr
otection
Provide a minimum 17--3/4 in. X 22 in. piece of sheet metal for
flame roll--out protection in front of burner area for furnaces
closer than 12 inches above the combustible deck or suspended
furnaces closer than 12 inches to joists. The sheet metal MUST
extend underneath the furnace casing by 1 in. with the door
removed.
The bottom closure panel on furnaces of widths 17--1/2 in. and
larger may be used for flame roll--out protection when bottom of
furnace is used for return air connection. See Fig. 17 for proper
orientation of roll--out shield.
Bottom Return Air
Inlet
These furnaces are shipped with bottom closure panel installed in
bottom return--air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,
perform the following:
312A
1. Tilt or raise furnace and remove 2 screws holding bottom
filler panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding
tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air
Inlet
These furnaces are shipped with bottom closure panel installed in
bottom return--air opening. This panel MUST be in place when
side return air inlet(s) are used without a bottom return air inlet.
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
A096285
Fig. 12 -- Furnace, Plenum, and Subbase installed on a
Combustible Floor
A
PLENUM
OPENING
B
OPENING
D
FLOOR
C
Fig. 11 -- Floor and Plenum Opening Dimensions
A096283
FURNACE
CD5 OR CK5
COIL ASSEMBLY
OR KCAKC
COIL BOX
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
A04140
A04140
Fig. 13 -- Furnace, Plenum, and Coil Assembly or Coil Box
Installed on a Combustible Floor
12
FURNACE
D
CASING
WIDTH
14–3/16
17–1/2
21
24--- 1/2
Table 4 – Opening dimensions (In.)
APPLICATION
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring (KGASB
subbase not required)
Downflow applications on combustible flooring
(KGASB subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on combustible flooring
(KGASB subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on combustible flooring
(KGASB subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on Combustible flooring
(KGASB subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box
(KGASB subbase not required)
PLENUM OPENINGFLOOR OPENING
ABCD
12--- 11/1621--- 5/813---5/1622--- 1/4
12--- 9/161913--- 3/1619--- 5/8
11--- 13/161913 --- 7/1620 ---5/8
12--- 5/161913--- 5/1620
1621--- 5/816 ---5/822---1/4
15--- 7/81916---1/219 --- 5/8
15--- 1/81916---3/420 --- 5/8
15--- 1/21916---1/220
19--- 1/221 --- 5/820--- 1/822 --- 1/4
19--- 3/8192019--- 5/8
18--- 5/81920---1/420 --- 5/8
19192020
2321--- 1/823 ---5/822---1/4
22--- 7/81923---1/219 --- 5/8
22--- 1/81923---3/420 --- 5/8
22--- 1/21923---1/220
312A
UPFLO
90û
120û
MIN
WOWNFLOW
YES
YES
NOT
RECOMMENDED
D
120û
MIN
Fig. 14 -- Duct Flanges
YES
YES
NOT
RECOMMENDED
13
HORIZONTAL
90û
120û
MIN
YES
YES
NOT
RECOMMENDE
A02329
OUTER DOOR
ASSEMBLY
1
/4
" THREADED ROD
4 REQ.
312A
8" MIN FOR DOOR
REMOVAL
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS
REQ. PER ROD
Fig. 15 -- Horizontal Unit Suspension
SECURE ANGLE
IRON TO BOTTOM
OF FURNACE WITH
3 #8 x
TYPICAL FOR 2 SUPPORTS
1
1
/4
1" SQUARE, 1
OR UNI-STRUT MAY BE USED
" x 1
1
/4
" x
/4
" ANGLE IRON
3
/4
" SCREWS
METHOD 2
USE (42) #8 x 3/4 SHEET
METAL SCREWS TYPICAL
FOR EACH STRAPS.THE
STRAPS SHOULD BE
VERTICAL AGAINST THE
FURNACE SIDES AND NOT
PULL AWAY FROM THE
FURNACE SIDES.
A02345
METHOD 1
FOLD ALL STRAPS UNDER
FURNACE AND SECURE WTH
(42) #8 x 3/4 SHEET METAL SCREWS
(2 SCREWS IN SIDE AND 2 SCREWS
IN BOTTOM).
Fig. 16 -- Horizontal Suspension with Straps
14
A03176
LINE CONTACT ONLY PERMISSIBLE BETWEEN
LINES FORMED BY INTERSECTIONS OF
THE TOP AND TWO SIDES OF THE FURNACE
JACKET AND BUILDING JOISTS,
STUDS, OR FRAMING.
GAS
ENTRY
TYPE-B
VENT
17 3/4
″ OVER ALL
4 3/4
″ UNDER DOOR
1″ UNDER FURNACE
EXTEND OUT 12″ OUT
FROM FACE OF DOOR
17 3/4
22
EQUIPMENT MANUAL
SHUT-OFF GAS VALVE
SEDIMENT
TRAP
UNION
SHEET
METAL
Fig. 17 -- Typical Attic Installation
Not all horizontal furnaces are approved for side return air
connections. (See Fig. 20.)
FILTER
ARRANGEMENT
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury, or death.
Never operate a furnace without a filter or with filter access
door removed.
There are no provisions for an internal filter rack in these
furnaces. An external filter rack is required.
This furnace is shipped with a factory--supplied Media Filter
Cabinet. The Media Filter Cabinet uses either a factory--supplied
standard 1--inch filter or 4--inch wide Media Filter which can be
purchased separately.
Refer to the instructions supplied with Media Cabinet for
assembly and installation options.
DUCTS
AIR
General Requir
ements
The duct system should be designed and sized according to
accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and
Air Conditioning Contractors National Association (SMACNA)
or American Society of Heating, Refrigerating and Air
Conditioning Engineers (ASHRAE) or consult The Air Systems
Design Guidelines reference tables available from your local
distributor. The duct system should be sized to handle the
required system design CFM at the design external static pressure.
The furnace airflow rates are provided in Table 5--Air Delivery
CFM (With Filter).
When a furnace is installed so that the supply ducts carry air
circulated by the furnace to areas outside the space containing the
furnace, the return air shall also be handled by duct(s) sealed to
the furnace casing and terminating outside the space containing
the furnace.
6″ MIN*
″
″
30-IN. MIN
WORK AREA
* WHEN USED WITH
SINGLE WALL VENT
CONNECTIONS
312A
A03177
Secure ductwork with proper fasteners for type of ductwork used.
Seal supply-- and return--duct connections to furnace with code
approved tape or duct sealer.
NOTE: Flexible connections should be used between ductwork
and furnace to prevent transmission of vibration.
Ductwork passing through unconditioned space should be
insulated to enhance system performance. When air conditioning
is used, a vapor barrier is recommended.
Maintain a 1--in. clearance from combustible materials to supply
air ductwork for a distance of 36 in. horizontally from the
furnace. See NFPA 90B or local code for further requirements.
Ductwork Acoustical Tr
NOTE: Metal duct systems that do not have a 90_ elbow and 10
ft of main duct to the first branch take--off may require internal
acoustical lining. As an alternative, fibrous ductwork may be used
if constructed and installed in accordance with the latest edition of
SMACNA construction standard on fibrous glass ducts. Both
acoustical lining and fibrous ductwork shall comply with NFPA
90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
Supply Air
Connections
For a furnace not equipped with a cooling coil, the outlet duct
shall be provided with a removable access panel. This opening
shall be accessible when the furnace is installed and shall be of
such a size that the heat exchanger can be viewed for possible
openings using light assistance or a probe can be inserted for
sampling the air stream. The cover attachment shall prevent leaks.
Upflow and Horizontal
Connect supply--air duct to flanges on furnace supply--air outlet.
Bend flange upward to 90_ with wide duct pliers. (See Fig. 14.)
The supply--air duct must be connected to ONLY the furnace
supply--outlet--air duct flanges or air conditioning coil casing
(when used). DO NOT cut main furnace casing side to attach
supply air duct, humidifier, or other accessories. All accessories
MUST be connected to duct external to furnace main casing.
eatment
Furnaces
15
Table 5 – Air Delivery -- CFM (With Filter)*
312A
FURNACE
SIZE
045--- 08 /
024045
045--- 12 /
036045
070--- 081 /
024070
070--- 12 /
036070
070--- 16 /
048070
090--- 14 /
042090
090--- 16 /
048090
090--- 20 /
060090
110--- 12 /
036110
110--- 16 /
048110
RETURN---AIR
INLET
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom Only
Both Side or 1
Side & Bottom
1Side Only
Bottom or
Side(s)
Bottom or
Side(s)
SPEED
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
EXTERNAL STATIC PRESSURE (IN. WC)
0.10.20.30.40.50.60.70.80.91.0
1120
930
820
725
1465
1295
1150
1030
860
1140
915
795
690
1440
1180
1015
885
695
1840
1610
1460
1260
1065
1650
1515
1385
1205
2060
1710
1470
1260
1030
2380
2185
1905
1595
1340
2485
2175
1845
1540
1280
2420
2160
1850
1530
1290
1625
1510
1360
1195
2055
1750
1545
1300
1050
1075
890
785
690
1400
1260
1120
1010
835
1105
885
770
665
1400
1165
1020
885
700
1790
1575
1430
1240
1040
1600
1485
1360
1180
2000
1695
1475
1365
1025
2295
2115
1865
1565
1310
2415
2130
1815
1515
1250
2345
2110
1815
1490
1250
1575
1470
1335
1180
1990
1725
1525
1290
1045
1020
850
750
655
1325
1210
1085
980
810
1055
855
740
630
1355
1150
1010
880
700
1730
1535
1400
1215
1015
1535
1440
1320
1160
1930
1665
1450
1245
1020
2205
2045
1815
1530
1280
2330
2070
1770
1475
1220
2265
2045
1765
1455
1220
1515
1415
1295
1155
1910
1670
1490
1275
1015
960
805
700
605
1250
1155
1040
945
780
1010
825
700
590
1300
1125
990
865
690
1670
1485
1360
1180
985
1465
1380
1260
1120
1835
1585
1390
1225
990
2105
1960
1740
1485
1225
2230
2000
1720
1435
1190
2165
1960
1710
1420
1190
1445
1355
1250
1115
1815
1605
1445
1235
975
895
750
650
555
1175
1090
985
895
745
955
785
655
550
1240
1085
965
845
670
1605
1435
1315
1145
955
1385
1300
1195
1065
1755
1480
1335
1165
940
2005
1875
1670
1430
1170
2135
1930
1655
1385
115
2070
1885
1635
1375
115
1355
1285
1180
1065
1695
1515
1355
1165
935
815
680
585
495
1085
1015
920
835
700
885
725
600
475
1170
1030
925
815
640
1530
1370
1260
110
915
1285
1220
1120
1005
1620
1390
1230
1090
890
1900
1770
1590
1355
1120
2030
1840
1580
1335
1105
1960
1790
1560
1320
1110
1260
1185
1100
980
1575
1400
1260
1085
880
720
600
505
405
980
930
835
765
635
815
655
510
415
1090
970
875
770
600
1450
1305
1205
1040
875
1175
1115
1025
925
1490
1245
1120
995
810
1775
1655
1490
1275
1040
1920
1740
1500
1270
1035
1850
1695
1480
1250
1040
1165
1070
985
860
1425
1255
1135
1005
815
605
500
400
305
860
830
740
685
555
715
530
420
340
1000
890
800
700
540
1370
1230
1130
985
825
1055
990
915
810
1315
1110
1005
880
720
1650
1535
1390
1160
955
1790
1620
1395
1175
945
1720
1570
1380
1160
950
990
890
810
740
1230
1120
1020
895
715
455
345
235
--- ---
725
700
620
570
445
545
420
325
245
890
785
700
605
460
1275
1145
1055
915
765
895
830
710
630
1115
955
855
750
615
1510
1400
1245
1055
850
1645
1495
1270
1045
845
1570
1445
1250
1055
835
785
725
670
605
1090
975
880
750
610
340
195
--- ---
--- ---
560
545
510
345
260
390
280
--- ---
--- ---
745
645
560
475
345
1170
1055
965
835
695
645
600
565
510
910
775
690
600
500
1335
1240
1110
920
750
1485
1345
1090
915
745
1420
1305
1110
905
740
595
530
475
410
910
785
750
620
515
16
High
M e d ---
Bottom Only
110--- 22 /
066110
*A filter is required for each return---air inlet. Airflow performance included 1---in. washable filter media such as contained in factory---authorized accessory filter
rack. To determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.
--- --- Indicates unstable operating conditions.
Bottom Sides or
1 Side & Bottom
1Side Only
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High
High
M e d ---
High Me-
dium
M e d --- L ow
Low
2530
2225
1895
1565
1320
--- ---
2205
2485
2155
1830
1520
1275
2460
2190
1885
1555
1295
--- ---
2175
2430
2135
1830
1505
1260
2380
2135
1865
1535
1265
2415
2120
2360
2100
1810
1490
1240
2285
2075
1820
1505
1235
2330
2065
2270
2040
1780
1470
1210
2200
1995
1770
1465
1205
2235
1975
2175
1970
1730
1430
1180
2085
1910
1700
1410
1160
2125
1900
2070
1885
1665
1385
1135
1970
1805
1610
1350
1105
1995
1790
1950
1790
1595
1330
1090
1835
1695
1520
1265
1035
1860
1685
1825
1680
1505
1250
1025
1695
1565
1410
1175
950
1735
1580
1685
1560
1395
1165
930
1545
1430
1290
1050
870
1605
1460
1535
1420
1275
1055
840
312A
17
Table 5 -- Air Delivery -- CFM (With Filter)* (Cont.)
FURNACE
SIZE
135--- 16 /
048135
135--- 22 /
066135
312A
155--- 20 /
060155
*A filter is required for each return---air inlet. Airflow performance included 1---in. washable filter media such as contained in factory---authorized accessory filter
rack. To determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.
--- --- Indicates unstable operating conditions.
RETURN---AIR
INLET
Bottom
or
Side(s)
Bottom
Only
Bottom Sides
or
1 Side & Bottom
1SideOnly
Bottom Only
Both Sides Or 1
Side & Bottom
1SideOnly
SPEED
High
M e d --- H ig h
M e d --- L ow
Low
High
M e d --- H ig h
M e d --- L ow
Low
High
M e d --- H ig h
M e d --- L ow
Low
High
M e d --- H ig h
M e d --- L ow
Low
High
M e d --- H ig h
M e d --- L ow
Low
High
M e d --- H ig h
High
M e d --- H ig h
0.10.20.30.40.50.60.70.80.91.0
2090
1790
1545
1325
2485
2195
1880
1640
--- --2180
1880
1640
2320
2125
1845
1640
2465
2115
1800
1570
--- --2155
--- --2140
2010
1755
1525
1320
2400
2150
1850
1635
--- --2145
1850
1635
2250
2065
1825
1620
2430
2105
1790
1565
--- --2135
--- --2095
NOTE: For horizontal applications, the top--most flange may be
bent past 90_ to allow the evaporator coil to hang on the flange
temporarily while the remaining attachment and sealing of the
EXTERNAL STATIC PRESSURE (IN. WC)
1930
1705
1500
1295
2310
2090
1820
1615
2385
2060
1820
1615
2155
1995
1765
1580
2375
2075
1770
1550
2375
2095
2260
2040
1835
1640
1450
1265
2215
2000
1780
1585
2305
2010
1780
1585
2055
1910
1710
1540
2305
2030
1735
1525
2285
2040
2180
1975
1710
1550
1380
1210
2110
1920
1715
1530
2195
1945
1715
1530
1970
1815
1650
1485
2230
1980
1695
1495
2200
1975
2085
1890
1590
1465
1315
1150
2000
1825
1635
1465
2085
1865
1635
1465
1855
1710
1570
1410
2110
1910
1640
1445
2105
1895
1975
1810
1470
1360
1215
995
1880
1720
1540
1370
1960
1765
1540
1370
1725
1610
1475
1330
2000
1830
1570
1370
1995
1790
1865
1705
1335
1210
1005
865
1725
1565
1415
1255
1825
1660
1415
1255
1600
1490
1370
1220
1865
1725
1465
1270
1870
1685
1740
1595
horizontal furnaces are approved for side return air connections.
(See Fig. 20.)
PIPING
GAS
coil are performed.
Downflow
Connect supply--air duct to supply--air outlet on furnace. Bend
flange inward past 90_ with wide duct pliers. (See Fig. 14.) The
supply--air duct must be connected to ONLY the furnace
supplyoutlet or air conditioning coil casing (when used). When
installed on combustible material, supply--air duct must be
connected to ONLY the accessory subbase, KGASB0201ALL, or
a factory approved air conditioning coil casing. DO NOT cut
main furnace casing to attach supply side air duct, humidifier, or
other accessories. All accessories MUST be connected to duct
Furnaces
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection
of leaks to check all connections.
external to furnace casing.
Return Air
FIRE HAZARD
Failure to follow this warning could cause personal injury,
death and/or property damage.
Never connect return--air ducts to the back of the furnace.
Connections
!
WARNING
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Use proper length of pipe to avoid stress on gas control
manifold and a gas leak.
Follow instructions below.
1025
945
855
745
1535
1405
1290
1150
1670
1515
1290
1150
1450
1340
1240
1080
1725
1590
1345
1175
1730
1550
1605
1480
835
785
670
540
1355
1255
1160
1040
1465
1325
1160
1040
1280
1175
1100
960
1545
1425
1225
1070
1570
1400
1455
1325
Downflow Furnaces
The return--air duct must be connected to return--air opening
(bottom inlet) as shown in Fig. 1. DO NOT cut into casing sides
(left or right). Side opening is permitted for only upflow and most
horizontal furnaces. Bypass humidifier connections should be
made at ductwork or coil casing sides exterior to furnace. (See
Fig. 19.) Upflow and Horizontal Furnaces The return--air duct
must be connected to bottom, sides (left or right), or a
combination of bottom and side(s) of main furnace casing as
shown in Fig. 1. Bypass humidifier may be attached into unused
return air side of the furnace casing. (See Fig. 18 and 20.) Not all
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to protect gas valve inlet from water and debris
could result in death, personal injury and/or property
damage.
Gas valve inlet and/or inlet pipe must remain capped until
gas supply line is permanently installed to protect the valve
from moisture and debris. Also, install a sediment trap in the
gas supply piping at the inlet to the gas valve.
18
Loading...
+ 40 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.