Bryant 120 User Manual

Page 1
312A
2 --- S t a ge D e lux e I n d u ce d --- C o m b u s ti o n 4---Way Multipoise Furnace
Installation, Start--up, Operating and
Service and M a int e nanc e
Instructions Series 120/C
SAFETY CONSIDERATIONS 2........................
CODES AND STANDARDS 5..........................
Safety 5...........................................
General Installation 5................................
Combustion and Ventilation Air 5......................
Duct Systems 5.....................................
Acoustical Lining and Fibrous Glass Duct 5...............
Gas Piping and Gas Pipe Pressure Testing 5...............
Electrical Connections 5..............................
Venting 5.........................................
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
LOCATION 6.......................................
AIR FOR COMBUSTION AND VENTILATION 8.........
INSTALLATION 10..................................
UPFLOW INSTALLATION 10......................
DOWNFLOW INSTALLATION 11...................
HORIZONTAL INSTALLATION 11..................
FILTER ARRANGEMENT 15.......................
AIR DUCTS 15...................................
GAS PIPING 18..................................
ELECTRICAL CONNECTIONS 21..................
VENTING 26....................................
START--UP, ADJUSTMENT, AND SAFETY CHECK 35.....
General 35........................................
Start--Up Procedures 35..............................
Adjustments 36.....................................
Check Safety Controls 40.............................
Checklist 41.......................................
SERVICE AND MAINTENANCE PROCEDURES 45.....
Introdution 46....................................
Care and Maintenance 46...........................
Sequence of Operation 51...........................
Wiring Diagrams 54...............................
Troubleshooting 54................................
ama
ISO 9001:2000
CERTIFIED
REGISTERED
NOTE: Read the entire instruction manual before starting the installation.
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1--2006E, with permission of National Fire Protection Association, Quincy, MA 02269 and American Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI on the referenced subject, which is represented only by the standard in its entirety.
Page 2
28-7/8"
25-1/4"
22-9/16"
JUNCTION BOX LOCATION
WIRE ENTRY
3-15/16"
LEFT HAND GAS
ENTRY
7/8" DIA. ACCESSORY
21-5/8"
BOTTOM INLET
24"
CASING
1-11/16"
24-7/8"
5-1/2"
4-13/16"
8-9/16"
ALTERNATE
JUNCTION BOX
VENT OUTLET
5 PLACES (TYP)
3-3/4"
2-7/16" 1-5/16"
1-1/8"
A
D
F
E
13/16"
LOCATIONS (TYP)
5-1/2"
11/16"
AIRFLOW
19"
OUTLET
1/2" DIA. K.O.THERMOSTAT WIRE ENTRY
1-3/4" DIA.RIGHT HAND GAS ENTRY
7/8" DIA. K.O. WIRE ENTRY
7/8" DIA. ACCESSORY
1-1/2"
22-1/16"
SIDE INLET
13/16"
11/16"
14-7/8"
1-1/4"
1"
312A
26-1/8"
(FLUE COLLAR)
5-15/16"
7/8" DIA
ACCESSORY
NOTES:
1. Two additional 7/8-in. diameter holes are located in the top plate.
2. Minimum return-air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters. a. For 800 CFM-16-in. round or 14 1/2 x 12-in. rectangle. b. For 1200 CFM-20-in. round or 14 1/2 x 19 1/2-in. rectangle. c. For 1600 CFM-22-in. round or 14 1/2 x 22-in. rectangle. d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
1/2" DIA THERMOSTAT
33-5/16"
11/16"
NOTES:
1. Two additional 7/8---in. diameter holes are located in the top plate.
2. Minimum return --- air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters. a. For 800 CFM---16--- in. round or 14 1/2 x 12--- in. rectangle. b. For 1200 CFM---20 ---in. round or 14 1/2 x 19 1/2--- in. rectangle. c. For 1600 CFM---22 ---in. round or 14 1/2 x 22--- in. rectangle. d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific u se of single side inlets. The use of both sidein­lets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airfl ow requirements above 1800 CFM.
Fig. 1 -- Dimensional Drawing
7-3/4"
9-5/8"
11-1/2"
A04037
SAFETY CONSIDERATIONS
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation, serious injury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use could cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified service agency must use only factory--authorized and listed kits or accessories when modifying this product.
!
CAUTION
FURNACE RELIABILITY HAZARD
Improper installation or misapplication of furnace may require excessive servicing or cause premature component failure.
Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in literature, on tags, and on labels attached to or shipped with furnace and other safety precautions that may apply. These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require these instructions as a minimum for a safe installation.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.
Wear safety glasses and work gloves. Have fire extinguisher available during start--up and adjustment procedures and service calls.
This is the safety--alert symbol
. When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify hazards which may result in minor personal injury or
2
Page 3
Table 1 – Dimensions (In.)
A
FURNACE SIZE
045--- 08/024045 14--- 3/16 12--- 9/16 12--- 11/16 9--- 5/16 4 116 16 045--- 12/036045 14--- 3/16 12--- 9/16 12--- 11/16 9--- 5/16 4 119 16 070--- 08/024070 14--- 3/16 12--- 9/16 12--- 11/16 9--- 5/16 4 120 16 070--- 12/036070 14--- 3/16 12--- 9/16 12--- 11/16 9--- 5/16 4 124 16 070--- 16/048070 17--- 1/2 15--- 7/8 16 11 --- 9/16 4 138 16 090--- 14/042090 17--- 1/2 15--- 7/8 16 11 --- 9/16 4 136 16 090--- 16/048090 21 19--- 3/8 19 --- 1/2 13---5/16 4 151 20 090--- 20/060090 21 19--- 3/8 19 --- 1/2 13---5/16 4 156 20 110--- 12/036110 17--- 1/2 15--- 7/8 16 11 --- 9/16 4 144 16 110--- 16/048110 21 19--- 3/8 19 --- 1/2 13---5/16 4 158 20 110--- 22/066110 21 19--- 3/8 19 --- 1/2 13---5/16 4 163 20 135--- 16/048135 21 19--- 3/8 19 --- 1/2 13---5/16 4† 163 20 135--- 22/066135 24--- 1/2 22--- 7/8 23 15 --- 1/16 4† 174 24 155--- 20/060155 24--- 1/2 22--- 7/8 23 15 --- 1/16 4† 181 24
* 5” or 6” vent connector may be required in some cases. { 135 and 155 size furnaces require five---inch or larger vents. Use a 4---5 or 4---6 inch vent adapter between furnace and vent connector.
CABINET
WIDTH
(IN.)
D
SUPPLY--- AIR
WIDTH (IN.)
E
RETURN---AIR
WIDTH (IN.)
product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
1. Use only with type of gas approved for this furnace. Refer to the furnace rating plate 2. Install this furnace only in a
2. Install this furnace only in a location and position as specified in the “Location” section of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in “Air for Combustion and Ventilation” section.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the “Venting” section of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the “Gas Piping” section.
6. Always install furnace to operate within the furnace’s intended temperature--rise range with a duct system which has an external static pressure within the allowable range, as specified in the “Start--Up, Adjustments, and Safety Check” section. See furnace rating plate.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. See “Air Ducts” section.
8. A gas-- fired furnace for installation in a residential garage must be installed as specified in the warning box in the “Location” section.
9. The furnace may be used for construction heat provided that the furnace installation and operation complies with the first CAUTION in the LOCATION section of these instructions.
10. These Multipoise Gas--Fired Furnaces are CSA (formerly A.G.A. and C.G.A.) design--certified for use with natural and propane gases (see furnace rating plate) and for installation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages. The furnace is factory--shipped for use with natural gas. A CSA (A.G.A. and C.G.A.) listed accessory gas conversion kit is required
F
C.L. TOP AND
BOTTOM FLUE
COLLAR (IN.)
FLUE
COLLAR*
(IN.)
SHIP WT. (LB)
11. See Fig. 2 for required clearances to combustible construction.
12. Maintain a 1--in. clearance from combustible materials to supply air ductwork for a distance of 36 inches horizontally from the furnace. See NFPA 90B or local code for further requirements.
13. These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. In downflow installations, factory accessory floor base MUST be used when installed on combustible materials and wood flooring. Special base is not required when this furnace is installed on manufacturer’s Coil Assembly Part No. CD5 or CK5, or when Coil Box Part No. KCAKC is used. See Fig. 2 for clearance to combustible construction information.
INTRODUCTION
The Series 120/C 4--way multipoise Category I fan--assisted furnace is CSA (formerly A.A.A.. and C.G.A.) design--certified. A Category I fan--assisted furnace is an appliance equipped with an integral mechanical means to either draw or force products of combustion through the combustion chamber and/or heat exchanger. The furnace is factory--shipped for use with natural gas. This furnace is not approved for installation in mobile homes, recreational vehicles, or outdoors.
These furnaces shall not be installed directly on carpeting, tile, or any other combustible material other than wood flooring. For downflow installations, a factory accessory floor base must be used when installed on combustible materials and wood flooring. This special base is not required when this furnace is installed on the manufacturer’s coil assembly, or when the manufacturer’s coil box is used. See Fig. 2 for clearance to combustible material information.
This furnace is designed for minimum continuous return--air temperature of 60_F db or intermittent operation down to 55_F db such as when used with a night setback thermostat. Return-- air temperature must not exceed 80_F db. Failure to follow these return-- air temperature limits may affect reliability of heat exchangers, motors, and controls. (See Fig. 3.)
For accessory installation details, refer to the applicable instruction literature.
NOTE: Remove all shipping brackets and materials before operating the furnace.
to convert furnace for use with propane gas.
FILTER
MEDIA CABINET SIZE (IN.)
312A
3
Page 4
312A
INSTALLATION
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
DISTANCE MINIMALE EN POUCES AUX CONSTRUCTIONS COMBUSTIBLES
This forced air furnace is equipped for use with
natural gas at altitudes 0-10,000 ft (0-3,050m).
An accessory kit, supplied by the manufacturer, shall be used to convert to propane gas use or may be required for some natural gas applications.
This furnace is for indoor installation in a building constructed on site.
This furnace may be installed on combustible
flooring in alcove or closet at minimum clearance as indicated by the diagram from combusitble material.
This furnace may be used with a Type B-1 Vent
and may be vented in common with other gas fired appliances.
Cette fournaise à air pulsé est équipée pour utilisation avec gaz naturel et altitudes comprises entre 0-3,050m (0-10,000 pi).
Utiliser une trousse de conversion, fournie par le fabricant, pour passer au gaz propane ou pour certaines installations au gaz naturel.
This furnace is approved for UPFLOW, DOWNFLOW, and HORIZONTAL installations.
Cette fournaise est approuvée pour l 'installation HORIZONTALE et la circulation d 'air VERS LE HAUT et VERS LE BAS.
Clearance arrows do not change with furnace orientation.
0"
B
A
A
C
R
K
R
I
È
R
E
E
D
I
S
É
T
Ô
C
0"
*
1"
Les fléches de dégagement
l 'orientation de la fournaise.
TOP / PLE NUM
DESSUS / CHAMBRE D'AIR
E
C
E
A
S
N
I
A
R
U
N
F
R
U
T
FO
N
O
T
R
N
F
A
V
A
F
R
O
A
N
V
T
A
N
T
3"
Cette fournaise est prévue pour être installée dans un bâtiment construit sur place.
Cette fournaise peut être installée sur un plancher combustible dans une alcôve ou dans un garde-robe en respectant le minimum d'espace libre des matériaux combustibles, tel
´
indiqué sur le diagramme.
qu
Cette fournaise peut être utilisée avec un
´
évacuation de Type B-1 ou connectée
conduit d au conduit ommun d 'autres appareils à gaz.
Vent Clearance to combustibles:
For Single Wall vents 6 inches (6 po). For Type B-1 vent type 1 inch (1 po).
Dégagement de l´évent avec combustibles:
Pour conduit d´évacuation à paroi simple 6 po (6 inches). Pour conduit d
BOTTOM
DESSOUS
"
0
´
évacuation de Type B-1 1 po (1 inch).
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
DOWNFLOW POSITIONS:
Installation on non-combusibible floors only.
For Installation on combustible flooring only when installed on special base, Part No. KGASB0201ALL,
Coil Assembly, Part No. CD5 or CK5, or Coil Casing, Part No. KCAKC.
18 inches front clearance required for alcove.
Ø
Indicates supply or return sides when furnace is in the horizontal position. Line contact only permissible
*
between lines formed by intersections of the Top and two Sides of the furnace jacket, and building joists, studs or framing.
DÉGAGEMENT MINIMUM EN POUCES AVEC ÉLÉMENTS
DE CONSTRUCTION COMBUSTIBLES
POUR LA POSITION COURANT DESCENDANT:
Pour l´installation sur plancher non combustible seulement.
´
installation sur un plancher combustible seulement quand on utilise la base spéciale, pièce
Pour l
nº KGASB0201ALL, l nº KCAKC.
Dans une alcôve, on doit maintenir un dégagement à l
Ø
La poistion indiquée concerne le côté d
*
position horizontale.
Le contact n
´
est permis qu´entre les lignes formées par les intersections du dessus et des
deux côtés de la cherrise de la fournaise et les solives, montant sous cadre de charpente.
´
ensemble serpentin, pièce nº CD5 ou CK5, ou le carter de serpentin, pièce
´
´
entrée ou de retour quand la fournaise est dans la
avant de 18 po (450mm).
327590-101 REV. C
ne change pas avec
0"
E
D
*
I
È
S
T
Ô
C
S
E
R
E
N
V
I
T
R
C
E
E
T
I
E
N
24"
MIN
Ø
Clearance in inches Dégagement (po).
MIN
Fig. 2 -- Clearances to Combustibles
4
A04123
Page 5
80
60
A04036
Fig. 3 -- Return Air Temperature
CODES AND STANDARDS
Follow all national and local codes and standards in addition to these instructions. The installation must comply with
regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction.
In the United States and Canada, follow all codes and standards for the following:
Step 1 — Safety
S US: National Fuel Gas Code (NFGC) NFPA 54--2006/ANSI
Z223.1--2006 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B
S CANADA: CSA B149.1--00 National Standard of Canada
Natural Gas and Propane Installation Code (CAN/CSA--B149.1--05)
Step 2 — General Installation
S US: Current edition of the NFGC and the NFPA 90B. For
copies, contact the National Fire Protection Association Inc., Batterymarch Park,Quincy, MA 02269; (www.NFPA.org) or for only the NFGC, contact the American Gas Association, 400 N. Capitol Street, N.W., Washington DC 20001 (www.AGA.org.)
S CANADA: CAN/CSA--B149.1--05. For a copy, contact
Standard Sales, CSA International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, M9W 1R3 Canada Step
Step 3 — Combustion and Ventilation Air
S US: Section 8.3 of the NFGC, Air for Combustion and
Ventilation
S CANADA: Part 7 of CAN/CSA--B149.1--05, Venting Systems
and Air Supply for Appliances
Step 4 — Duct Systems
S US and CANADA: Air Conditioning Contractors Association
(ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 2001 Fundamentals Handbook Chapter 34 or 2000 HVAC Systems and Equipment Handbook Chapters 9 and 16.
Step 5 — Acoustical Lining and Fibrous Glass Duct
S US and CANADA: current edition of SMACNA and NFPA
90B as tested by UL Standard 181 for Class I Rigid Air Ducts
Step 6 — Gas Piping and Gas Pipe Pressure Testing
S US: NFGC; chapters 5, 6, and 7 and National Plumbing Codes S CANADA: CAN/CSA--B149.1--05 Parts 4, 5, 6 and 9 and
Appendices A, B, E and H.
Step 7 — Electrical Connections
S US: National Electrical Code (NEC) ANSI/NFPA 70--2006 S CANADA: Canadian Electrical Code CSA C22.1
Step 8 — Venting
S US: NFGC; chapters 12 and 13 S CANADA: CAN/CSA--B149.1--05 Part 8 and Appendix C
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
!
CAUTION
FURNACE RELIABILITY HAZARD
Improper installation or service of furnace may cause premature furnace component failure.
Electrostatic discharge can affect electronic components. Follow the Electrostatic Discharge Precautions Procedure listed below during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple disconnects may be required. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing to recharge your body with static electricity (for example; DO NOT move or shuffle your feet, do not touch ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with static electricity), firmly touch a clean, unpainted metal surface of the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded) furnaces.
6. Before removing a new control from its container, discharge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 4 before bringing the control or yourself in contact with the furnace. Put all used and new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) mayalsobeusedtopreventESDdamage.
312A
5
Page 6
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED ABOVE THE
312A
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
LOCATION
GENERAL
This multipoise furnace is shipped in packaged configuration. Some assembly and modifications are required when used in any of the four applications shown in Fig. 4.
NOTE: For high--altitude installations, the high--altitude conversion kit MUST be installed at or above 5500 ft above sea level. Obtain high--altitude conversion kit from your area authorized distributor.
This furnace must: S be installed so the electrical components are protected from
water.
S not be installed directly on any combustible material other than
wood flooring (refer to SAFETY CONSIDERATIONS).
S be located close to the chimney or vent and attached to an air
distribution system. Refer to Air Ducts section.
S be provided ample space for servicing and cleaning. Always
comply with minimum fire protection clearances shown on the furnace clearance to combustible construction label.
!
WARNING
CARBON MONOXIDE POISONING AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death, and furnace damage.
Corrosive or contaminated air may cause failure of parts containing flue gas, which could leak into the living space. Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products. Do not install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are met, in addition to all local codes and ordinances.
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
A02097
Fig. 4 -- Multipoise Orientations
The following types of furnace installations may require OUTDOOR AIR for combustion due to chemical exposures:
S Commercial buildings S Buildings with indoor pools S Laundry rooms S Hobby or craft rooms, and S Chemical storage areas
If air is exposed to the following substances, it should not be used for combustion air, and outdoor air may be required for
combustion:
S Permanent wave solutions S Chlorinated waxes and cleaners S Chlorine based swimming pool chemicals S Water softening chemicals S De-- icing salts or chemicals S Carbon tetrachloride S Halogen type refrigerants S Cleaning solvents (such as perchloroethylene) S Printing inks, paint removers, varnishes, etc. S Hydrochloric acid S Cements and glues S Antistatic fabric softeners for clothes dryers
S Masonry acid washing materials
All fuel--burning equipment must be supplied with air for fuel combustion. Sufficient air must be provided to avoid negative pressure in the equipment room or space. A positive seal mu st be made between the furnace cabinet and the return--air duct to prevent pulling air from the burner area and from draft safeguard opening.
6
Page 7
!
WARNING
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
When the furnace is installed in a residential garage, the burners and ignition sources must be located at least 18 inches above the floor. The furnace must be located or protected to avoid damage by vehicles. When the furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, the furnace must be installed in accordance with the NFGC or CAN/CSA--B149.1--05. (See Fig. 5.)
Fig. 6 -- Prohibit Installation on Back
!
CAUTION
A02054
18-IN. MINIMUM
TO BURNERS
A93044
Fig. 5 -- Installation in a Garage
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect return-- air ducts to the back of the furnace. (See Fig. 6.)
PROPERTY DAMAGE HAZARD
Improper use or installation of this furnace may cause premature component failure. This gas furnace may be used for construction heat provided that:
--The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame roll--out and/or drawing combustion products into the structure.
--The furnace is controlled by a thermostat. It may not be ”hot wired” to provide heat continuously to the structure without thermostatic control.
--Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
--The temperature of the return air to the furnace is maintained between 55_F(13_C) and 80_F(27_C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
--The air temperature rise is within the rated rise range on the furnace rating plate, and the gas input rate has been set to the nameplate value.
--The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
--The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
--Verify proper furnace operating conditions including ignition, gas input rate, air temperature rise, and venting according to these installation instructions.
312A
LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with, or on the downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with the furnace, dampers or other flow control must prevent chilled air from entering the furnace. If the dampers are manually operated, they must be
7
Page 8
equipped with means to prevent operation of either unit unless the damper is in the full--heat or full--cool position.
AIR FOR COMBUSTION AND
VENTILATION
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:
U.S. installations: Section 8.3 of the NFGC, Air for Combustion and Ventilation, and applicable provisions of the local building codes.
Canadian installations: Part 8 of the CAN/CSA--B149.1--05, Venting Systems and Air Supply for Appliances and all authorities having jurisdiction.
!
CAUTION
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage.
312A
Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make--up air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to Carbon Monoxide Poisoning Hazard warning in venting section of these instructions to determine if an adequate amount of make--up air is available.
The requirements for combustion and ventilation air depend upon whether or not the furnace is located in a space having a volume of at least 50 cubic feet per 1,000 Btuh input rating for all gas appliances installed in the space.
S Spaces having less than 50 cubic feet per 1,000 Btuh require the
Outdoor Combustion Air Method.
S Spaces having at least 50 cubic feet per 1,000 Btuh may use the
Indoor Combustion Air, Standard or Known Air Infiltration Method.
Outdoor Combustion Air
1. Provide the space with sufficient air for proper combustion, ventilation, and dilution of flue gases using permanent horihorizontal or vertical duct(s) or opening(s) directly communicating with the outdoors or spaces that freely communicate with the outdoors.
2. Fig. 7 illustrates how to provide TWO OUTDOOR OPENINGS, one inlet and one outlet combustion and ventilation air opening, to the outdoors.
a. One opening MUST commence within 12 in. (300 mm)
of the ceiling and the second opening MUST commence within 12 in. (300 mm) of the floor.
b. Size openings and ducts per Fig. 7 and Table 2.
c. TWO HORIZONTAL DUCTS require 1 square inch of
free area per 2,000 Btuh (1,100 mm2/kW) of combined input for all gas appliances in the space per Fig. 7 and Tab le 2.
d. TWO OPENINGS OR VERTICAL DUCTS require 1
square inch of free area per 4,000 Btuh (550 mm2/kW) for combined input of all gas appliances in the space per Fig. 7 and Table 2.
3. ONE OUTDOOR OPENING requires:
a. 1 square inch offreearea per 3,000 Btuh (734 mm2/kW)
for combined input of all gas appliances in the space per Tab le 2 a nd
b. Not less than the sum of the areas of all vent connectors
in the space.
Method
Table 2 – Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors
TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING
FURNACE
INPUT
(BTUH)
44,000 22 6 14.7 5 11 4 66,000 33 7 22 6 16.5 5
88,000 44 8 29.3 7 22 6 110,000 55 9 36.7 7 27.5 6 132,000 66 10 44 8 33 7 154,000 77 10 51.3 9 38.5 8
FURNACE WATER HEATER TOTAL INPUT
110,000 + 30,000 = (140,000 divided by 4,000) = 35.0 Sq. In. for each two Vertical Ducts or Openings
66,000 + 40,000 = (106,000 divided by 3,000) = 35.3 Sq. In. for a Single Duct or Opening 88,000 + 30,000 = (118,000 divided by 2,000) = 59.0 Sq. In. for each of two Horizontal Ducts
(1 SQ. IN./2,000 BTUH)
(1,100 SQ. MM/KW)
Free Area of
Opening and Duct
(Sq. In.)
Round Duct
(in. Dia)
(1 SQ. IN./3,000 BTUH)
(734 SQ. MM/KW)
Free Area of
Opening and Duct
(sq. In.)
8
Round Duct
(in. Dia)
TWO OPENINGS OR VERTICAL
Free Area of
Opening and Duct
(Sq. In.)
DUCTS
(1 SQ. IN./4,000 BTUH)
(550 SQ. MM/KW)
Round Duct
(In. Dia)
Page 9
DUCTS
*
OUTDOORS
TO
1 SQ IN. PER 4000 BTUH*
CIRCULATING AIR
DUCTS
VENT THROUGH ROOF
12 MAX
1 SQ IN. PER 2000 BTUH*
DUCTS
TO
OUTDOORS
1 SQ IN. PER 2000 BTUH*
12 MAX
CIRCULATING AIR DUCTS
Minimum dimensions of 3 in.
Use any of the following
NOTE:
combinations of openings: A & B C & D D & E F & G
B
A
AIR DUCTS
CIRCULATING
OPENINGS SHALL BE
OF COMBUSTION AIR
CLEARANCE IN FRONT
D
VENT THROUGH ROOF
AT LEAST 3 IN.
OUTDOORS
C
DUCT
TO
E
12 MAX
F
G
1 SQ IN. PER 4000 BTUH*
Fig. 7 -- Air for Combustion, Ventilation and Dilution for
Outdoors
12 MAX
1 SQ IN.
PER 4000
BTUH*
OUTDOORS
1 SQ IN.
PER
4000
BTUH*
12 MAX
A03174
12" MAX
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
INTERIOR
HEATED
SPACE
CIRCULATING AIR DUCTS
* Minimum opening size is 100 sq in. with minimum dimensions of 3 in.
Minimum of 3 in. . when type-B1 vent is used.
UNCONFINED SPACE
6" MIN (FRONT)
1 SQ IN. PER 1000 BTUH* IN DOOR
OPENINGS SHALL BE AT LEAST 3 IN.
OR WALL
CLEARANCE IN FRONT OF COMBUSTION AIR
12" MAX
A03175
Fig. 8 -- Air for Combustion, Ventilation, and Dilution from
Indoors
312A
The opening shall commence within 12 in. (300 mm) of the ceiling. Appliances in the space shall have clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (150 mm) from the front. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
Indoor Combustion Air Known --Air--Infiltration Rate
E NFPA & AGA Standard and
Methods
Indoor air is permitted for combustion, ventilation, and dilution, if the Standard or Known--Air--Infiltration Method is used.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in death and/or personal injury.
Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases. The furnace combustion air supply must be provided in accordance with this instruction manual.
The Standard Method:
1. The space has no less volume than 50 cubic feet per 1,000 Btuh of the maximum input ratings for all gas appliances installed in the space and
2. The air infiltration rate is not known to be less than 0.40 air changes per hour (ACH).
The Known Air Infiltration Rate Method shall be used, if the infiltration rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of ACH and shall be determined per Table 3 or Equations 1 and 2. Determine the minimum required volume for each appliance in the space and add the volumes together to get the total minimum required volume for the space.
9
Page 10
Table 3 – Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors
OTHER THAN FAN--- ASSISTED TOTAL
ACH
0.60 1,050 1,400 1,750 1,100 1,650 2,200 2,750 3,300 3,850
0.50 1,260 1,680 2,100 1,320 1,980 2,640 3,300 3,960 4,620
0.40 1,575 2,100 2,625 1,650 2,475 3,300 4,125 4,950 5,775
0.30 2,100 2,800 3,500 2,200 3,300 4,400 5,500 6,600 7,700
0.20 3,150 4,200 5,250 3,300 4,950 6,600 8,250 9,900 11,550
0.10 6,300 8,400 10,500 6,600 9,900 13,200 16,500 19,800 23,100
0.00 NP NP NP NP NP NP NP NP NP
NP = Not Permitted
Table 3--Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI
Z223.1--2006/NFPA 54--2006, 9.3.2.2:
1. For other than fan-- assisted appliances, such as a draft hood--equipped water heater:
312A
Volume
2. For fan--assisted applicances such as this furnace:
Volume
If:
= combined input of all other than fan--assisted
I
other
= combined input of all fan--assisted appliances in
I
fan
ACH = air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the Standard Method and to the Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if:
a. There are no closable doors between rooms.
b. Combining spaces on same floor level. Each opening
shall have free area of at least 1 in.2/1,000 Btuh (2,000 mm2/kW) of the total input rating of all gas appliances in the space, but not less than 100 in.2 (0.06 m2). One opening shall commence within 12 in. (300 mm) of the ceiling and the second opening shall commence within 12 in. (300 mm) of the floor. The minimum dimension of air openings shall be at least 3 in. (80 mm). (See Fig.
8.)
c. Combining space on different floor levels. The volumes
of spaces on different floor levels shall be considered as communicating spaces if connected by one or more permanent openings in doors or floors having free area of at least 2 in.2/1,000 Btuh (4,400 mm2/kW) of total input rating of all gas appliances.
2. An attic or crawlspace may be considered a space that freely communicates with the outdoors provided there are adequate permanent ventilation openings directly to outdoors having free area of at least 1--in.2/4,000 Btuh of total input rating for all gas appliances in the space.
3. In spaces that use the Indoor Combustion Air Method, infiltration should be adequate to provide air for combustion, permanent ventilation and dilution of flue gases. However, in buildings with unusually tight
(1,000s BTUH GAS INPUT RATE)
30 40 50 44 66 88 110 132 154
SpaceVolume(ft3)
21ft
=
Other
Fan
appliances in Btuh/hr
Btuh/hr
=
ACH
15ft ACH
3
3
I
other
1000 Btu/hr
I
fan
1000 Btu/hr
A04002
A04003
Combination of Indoor and Outdoor
1. Indoor openings shall compy with the Indoor
2. Outdoor openings shall be located as required in the
3. Outdoor openings shall be sized as follows:
UPFLOW INSTALLATION
Bottom Return Air
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom
2. Rotate bottom filler panel downward to release holding
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. This panel MUST be in place when only side return air is used.
NOTE: Side return--air openings can be used in UPFLOW and most HORIZONTAL configurations. Do not use side return--air openings in DOWNFLOW configuration.
FAN--- ASSISTED TOTAL
(1,000s BTUH GAS INPUT RATE)
construction, additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section. Unusually tight construction is defined as Construction with:
a. Walls and ceilings exposed to the outdoors have a
continuous, sealed vapor barrier. Openings are gasketed or sealed and
b. Doors and openable windows are weatherstripped and
c. Other openings are caulked or sealed. These include
joints around window and door frames, between sole plates and floors, between wall-- ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc.
Air
Combustion Air Method below and,
Outdoor Combustion Air Method mentioned previously
and,
a. Calculate the Ratio of all Indoor Space volume divided
by required volume for Indoor Combustion Air Method below.
b. Outdoor opening size reduction Factor is 1 minus the
Ratio in a. above.
c. Minimum size of Outdoor openings shall be the size
required in Outdoor Combustion Air Method above multiplied by reduction Factor in b. above. The minimumdimension of air openingsshallbenot lessthan 3in.(80mm).
INSTALLATION
Inlet
filler panel. (See Fig. 9.)
tabs.
Inlet
10
Page 11
A02098
Fig. 9 -- Removing Bottom Closure Panel
Leveling Legs (If Desir
ed)
In upflow position with side return inlet(s), leveling legs may be used. (See Fig. 10.) Install field--supplied, 5/16 X 1--1/2 in. (max) corrosion --resistant machine bolts, washers and nuts.
NOTE: Bottom closure must be used when leveling legs are used. It may be necessary to remove and reinstall bottom closure panel to install leveling legs. To remove bottom closure panel, see item 1 in Bottom Return Air Inlet section in Step 1 above.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each bottom corner of furnace. (See Fig. 10.)
2. For each leg, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.
5. Reinstall bottom closure panel if removed.
5
⁄16″
5
⁄16″
1 3⁄4″
3
⁄4″
1
5
⁄16″
5
⁄16″
3
1
⁄4″
3
1
⁄4″
A02071
Fig. 10 -- Leveling Legs
DOWNFLOW INSTALLA
TION
NOTE: For downflow applications, this furnace is approved for
use on combustible flooring when any one of the following 3 accessories are used:
S Special Base, KGASB S Cased Coil Assembly Part No. CD5 or CK5 S Coil Box Part No. KCAKC
1. Determine application being installed from Table 4.
2. Construct hole in floor per Table 4 and Fig. 11.
3. Construct plenum to dimensions specified in Table 4 and Fig. 11.
4. If downflow subbase, KGASB is used, install as shown in Fig. 12. If Coil Assembly Part No. CD5 or CK5 or Coil Box Part No. KCAKC is used, install as shown in Fig. 13.
NOTE: It is recommended that the perforated supply--air duct flanges be completely folded over or removed from furnace when installing the furnace on a factory --supplied cased coil or coil box. To remove the supply--air duct flange, use wide duct pliers or hand seamers to bend flange back and forth until it breaks off. Be careful of sharp edges. (See Fig. 14.)
Bottom Return Air
Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
HORIZONTAL INSTALLA
TION
The furnace can be installed horizontally in an attic or crawl space on either the left--hand (LH) or right--hand (RH) side. The furnace can be hung from floor joists, rafters or trusses or installed on a non--combustible platform, blocks, bricks or pad.
!
WARNING
FIRE, EXPLOSION, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect return-- air ducts to the back of the furnace.
Suspended Furnace Support
The furnace may be supported under each end with threaded rod, angle iron or metal plumber’s strap as shown. (See Fig. 15 and
16.) Secure angle iron to bottom of furnace as shown. Heavy--gauge sheet metal straps (plumber’s straps) may be used to suspend the furnace from each bottom corner. To prevent screws from pulling out, use 2 #8 x .--in. screw into the side and 2 #8 x .--in. screw in the bottom of the furnace casing for each strap. (See Fig. 15 and 16.)
If the screws are attached to ONLY the furnace sides and not the bottom, the straps must be vertical against the furnace sides and not pull away from the furnace sides, so that the strap attachment screws are not in tension (are loaded in shear) for reliable support.
Platform Furnace
Support
Construct working platform at location where all required furnace clearances are met. (See Fig. 2 and 17.) For furnaces with 1--in. clearance requirement on side, set furnace on non--combustible blocks, bricks or angle iron. For crawlspace installations, if the furnace is not suspended from the floor joists, the ground
312A
11
Page 12
underneath furnace must be level and the furnace set on blocks or bricks.
Roll--Out Pr
otection
Provide a minimum 17--3/4 in. X 22 in. piece of sheet metal for flame roll--out protection in front of burner area for furnaces closer than 12 inches above the combustible deck or suspended furnaces closer than 12 inches to joists. The sheet metal MUST extend underneath the furnace casing by 1 in. with the door removed.
The bottom closure panel on furnaces of widths 17--1/2 in. and larger may be used for flame roll--out protection when bottom of furnace is used for return air connection. See Fig. 17 for proper orientation of roll--out shield.
Bottom Return Air
Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
312A
1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air
Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. This panel MUST be in place when side return air inlet(s) are used without a bottom return air inlet.
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
A096285
Fig. 12 -- Furnace, Plenum, and Subbase installed on a
Combustible Floor
A
PLENUM
OPENING
B
OPENING
D
FLOOR
C
Fig. 11 -- Floor and Plenum Opening Dimensions
A096283
FURNACE
CD5 OR CK5
COIL ASSEMBLY
OR KCAKC
COIL BOX
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
A04140
A04140
Fig. 13 -- Furnace, Plenum, and Coil Assembly or Coil Box
Installed on a Combustible Floor
12
Page 13
FURNACE
D
CASING
WIDTH
14–3/16
17–1/2
21
24--- 1/2
Table 4 – Opening dimensions (In.)
APPLICATION
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring (KGASB
subbase not required)
Downflow applications on combustible flooring
(KGASB subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on combustible flooring
(KGASB subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on combustible flooring
(KGASB subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on Combustible flooring
(KGASB subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box
(KGASB subbase not required)
PLENUM OPENING FLOOR OPENING
A B C D
12--- 11/16 21--- 5/8 13---5/16 22--- 1/4
12--- 9/16 19 13--- 3/16 19--- 5/8
11--- 13/16 19 13 --- 7/16 20 ---5/8
12--- 5/16 19 13--- 5/16 20
16 21--- 5/8 16 ---5/8 22---1/4
15--- 7/8 19 16---1/2 19 --- 5/8
15--- 1/8 19 16---3/4 20 --- 5/8
15--- 1/2 19 16---1/2 20
19--- 1/2 21 --- 5/8 20--- 1/8 22 --- 1/4
19--- 3/8 19 20 19--- 5/8
18--- 5/8 19 20---1/4 20 --- 5/8
19 19 20 20
23 21--- 1/8 23 ---5/8 22---1/4
22--- 7/8 19 23---1/2 19 --- 5/8
22--- 1/8 19 23---3/4 20 --- 5/8
22--- 1/2 19 23---1/2 20
312A
UPFLO
90û
120û
MIN
W OWNFLOW
YES
YES
NOT RECOMMENDED
D
120û MIN
Fig. 14 -- Duct Flanges
YES
YES
NOT RECOMMENDED
13
HORIZONTAL
90û
120û
MIN
YES
YES
NOT RECOMMENDE
A02329
Page 14
OUTER DOOR ASSEMBLY
1
/4
" THREADED ROD
4 REQ.
312A
8" MIN FOR DOOR REMOVAL
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS REQ. PER ROD
Fig. 15 -- Horizontal Unit Suspension
SECURE ANGLE IRON TO BOTTOM OF FURNACE WITH 3 #8 x TYPICAL FOR 2 SUPPORTS
1
1
/4
1" SQUARE, 1 OR UNI-STRUT MAY BE USED
" x 1
1
/4
" x
/4
" ANGLE IRON
3
/4
" SCREWS
METHOD 2 USE (42) #8 x 3/4 SHEET METAL SCREWS TYPICAL FOR EACH STRAPS.THE STRAPS SHOULD BE VERTICAL AGAINST THE FURNACE SIDES AND NOT PULL AWAY FROM THE FURNACE SIDES.
A02345
METHOD 1 FOLD ALL STRAPS UNDER FURNACE AND SECURE WTH (42) #8 x 3/4 SHEET METAL SCREWS (2 SCREWS IN SIDE AND 2 SCREWS IN BOTTOM).
Fig. 16 -- Horizontal Suspension with Straps
14
A03176
Page 15
LINE CONTACT ONLY PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF THE TOP AND TWO SIDES OF THE FURNACE JACKET AND BUILDING JOISTS, STUDS, OR FRAMING.
GAS ENTRY
TYPE-B VENT
17 3/4
OVER ALL
4 3/4
UNDER DOOR
1 UNDER FURNACE
EXTEND OUT 12OUT FROM FACE OF DOOR
17 3/4
22
EQUIPMENT MANUAL
SHUT-OFF GAS VALVE
SEDIMENT
TRAP
UNION
SHEET METAL
Fig. 17 -- Typical Attic Installation
Not all horizontal furnaces are approved for side return air connections. (See Fig. 20.)
FILTER
ARRANGEMENT
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, or death.
Never operate a furnace without a filter or with filter access door removed.
There are no provisions for an internal filter rack in these furnaces. An external filter rack is required.
This furnace is shipped with a factory--supplied Media Filter Cabinet. The Media Filter Cabinet uses either a factory--supplied standard 1--inch filter or 4--inch wide Media Filter which can be purchased separately.
Refer to the instructions supplied with Media Cabinet for assembly and installation options.
DUCTS
AIR
General Requir
ements
The duct system should be designed and sized according to accepted national standards such as those published by: Air Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or consult The Air Systems Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system design CFM at the design external static pressure. The furnace airflow rates are provided in Table 5--Air Delivery CFM (With Filter).
When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
6MIN*
30-IN. MIN WORK AREA
* WHEN USED WITH SINGLE WALL VENT CONNECTIONS
312A
A03177
Secure ductwork with proper fasteners for type of ductwork used. Seal supply-- and return--duct connections to furnace with code approved tape or duct sealer.
NOTE: Flexible connections should be used between ductwork and furnace to prevent transmission of vibration.
Ductwork passing through unconditioned space should be insulated to enhance system performance. When air conditioning is used, a vapor barrier is recommended.
Maintain a 1--in. clearance from combustible materials to supply air ductwork for a distance of 36 in. horizontally from the furnace. See NFPA 90B or local code for further requirements.
Ductwork Acoustical Tr NOTE: Metal duct systems that do not have a 90_ elbow and 10
ft of main duct to the first branch take--off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
Supply Air
Connections
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks.
Upflow and Horizontal
Connect supply--air duct to flanges on furnace supply--air outlet. Bend flange upward to 90_ with wide duct pliers. (See Fig. 14.) The supply--air duct must be connected to ONLY the furnace supply--outlet--air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing side to attach supply air duct, humidifier, or other accessories. All accessories MUST be connected to duct external to furnace main casing.
eatment
Furnaces
15
Page 16
Table 5 – Air Delivery -- CFM (With Filter)*
312A
FURNACE
SIZE
045--- 08 /
024045
045--- 12 /
036045
070--- 081 /
024070
070--- 12 /
036070
070--- 16 /
048070
090--- 14 /
042090
090--- 16 /
048090
090--- 20 /
060090
110--- 12 /
036110
110--- 16 /
048110
RETURN---AIR
INLET
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom Only
Both Side or 1 Side & Bottom
1Side Only
Bottom or
Side(s)
Bottom or
Side(s)
SPEED
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
EXTERNAL STATIC PRESSURE (IN. WC)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
1120
930 820 725
1465 1295 1150 1030
860
1140
915 795 690
1440 1180 1015
885 695
1840 1610 1460 1260 1065
1650 1515 1385 1205
2060 1710 1470 1260 1030
2380 2185 1905 1595 1340
2485 2175 1845 1540 1280
2420 2160 1850 1530 1290
1625 1510 1360 1195
2055 1750 1545 1300 1050
1075
890 785 690
1400 1260 1120 1010
835
1105
885 770 665
1400 1165 1020
885 700
1790 1575 1430 1240 1040
1600 1485 1360 1180
2000 1695 1475 1365 1025
2295 2115 1865 1565 1310
2415 2130 1815 1515 1250
2345 2110 1815 1490 1250
1575 1470 1335 1180
1990 1725 1525 1290 1045
1020
850 750 655
1325 1210 1085
980 810
1055
855 740 630
1355 1150 1010
880 700
1730 1535 1400 1215 1015
1535 1440 1320 1160
1930 1665 1450 1245 1020
2205 2045 1815 1530 1280
2330 2070 1770 1475 1220
2265 2045 1765 1455 1220
1515 1415 1295 1155
1910 1670 1490 1275 1015
960 805 700 605
1250 1155 1040
945 780
1010
825 700 590
1300 1125
990 865 690
1670 1485 1360 1180
985
1465 1380 1260 1120
1835 1585 1390 1225
990
2105 1960 1740 1485 1225
2230 2000 1720 1435 1190
2165 1960 1710 1420 1190
1445 1355 1250 1115
1815 1605 1445 1235
975
895 750 650 555
1175 1090
985 895 745
955 785 655 550
1240 1085
965 845 670
1605 1435 1315 1145
955
1385 1300 1195 1065
1755 1480 1335 1165
940
2005 1875 1670 1430 1170
2135 1930 1655 1385
115
2070 1885 1635 1375
115
1355 1285 1180 1065
1695 1515 1355 1165
935
815 680 585 495
1085 1015
920 835 700
885 725 600 475
1170 1030
925 815 640
1530 1370 1260
110 915
1285 1220 1120 1005
1620 1390 1230 1090
890
1900 1770 1590 1355 1120
2030 1840 1580 1335 1105
1960 1790 1560 1320 1110
1260 1185 1100
980
1575 1400 1260 1085
880
720 600 505 405
980 930 835 765 635
815 655 510 415
1090
970 875 770 600
1450 1305 1205 1040
875
1175 1115 1025
925
1490 1245 1120
995 810
1775 1655 1490 1275 1040
1920 1740 1500 1270 1035
1850 1695 1480 1250 1040
1165 1070
985 860
1425 1255 1135 1005
815
605 500 400 305
860 830 740 685 555
715 530 420 340
1000
890 800 700 540
1370 1230 1130
985 825
1055
990 915 810
1315 1110 1005
880 720
1650 1535 1390 1160
955
1790 1620 1395 1175
945
1720 1570 1380 1160
950
990 890 810 740
1230 1120 1020
895 715
455 345 235
--- ---
725 700 620 570 445
545 420 325 245
890 785 700 605 460
1275 1145 1055
915 765
895 830 710 630
1115
955 855 750 615
1510 1400 1245 1055
850
1645 1495 1270 1045
845
1570 1445 1250 1055
835
785 725 670 605
1090
975 880 750 610
340 195
--- ---
--- ---
560 545 510 345 260
390 280
--- ---
--- ---
745 645 560 475 345
1170 1055
965 835 695
645 600 565 510
910 775 690 600 500
1335 1240 1110
920 750
1485 1345 1090
915 745
1420 1305 1110
905 740
595 530 475 410
910 785 750 620 515
16
Page 17
High
M e d ---
Bottom Only
110--- 22 /
066110
*A filter is required for each return---air inlet. Airflow performance included 1---in. washable filter media such as contained in factory---authorized accessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.
--- --- Indicates unstable operating conditions.
Bottom Sides or
1 Side & Bottom
1Side Only
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High High
M e d ---
High Me-
dium
M e d --- L ow
Low
2530 2225 1895 1565 1320
--- ---
2205
2485 2155 1830 1520 1275
2460 2190 1885 1555 1295
--- ---
2175
2430 2135 1830 1505 1260
2380 2135 1865 1535 1265
2415 2120
2360 2100 1810 1490 1240
2285 2075 1820 1505 1235
2330 2065
2270 2040 1780 1470 1210
2200 1995 1770 1465 1205
2235 1975
2175 1970 1730 1430 1180
2085 1910 1700 1410 1160
2125 1900
2070 1885 1665 1385 1135
1970 1805 1610 1350 1105
1995 1790
1950 1790 1595 1330 1090
1835 1695 1520 1265 1035
1860 1685
1825 1680 1505 1250 1025
1695 1565 1410 1175
950
1735 1580
1685 1560 1395 1165
930
1545 1430 1290 1050
870
1605 1460
1535 1420 1275 1055
840
312A
17
Page 18
Table 5 -- Air Delivery -- CFM (With Filter)* (Cont.)
FURNACE
SIZE
135--- 16 /
048135
135--- 22 /
066135
312A
155--- 20 /
060155
*A filter is required for each return---air inlet. Airflow performance included 1---in. washable filter media such as contained in factory---authorized accessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.
--- --- Indicates unstable operating conditions.
RETURN---AIR
INLET
Bottom
or
Side(s)
Bottom
Only
Bottom Sides
or
1 Side & Bottom
1SideOnly
Bottom Only
Both Sides Or 1
Side & Bottom
1SideOnly
SPEED
High M e d --- H ig h M e d --- L ow
Low
High M e d --- H ig h M e d --- L ow
Low
High M e d --- H ig h M e d --- L ow
Low
High M e d --- H ig h M e d --- L ow
Low
High M e d --- H ig h M e d --- L ow
Low
High M e d --- H ig h
High M e d --- H ig h
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
2090 1790 1545 1325 2485 2195 1880 1640
--- --­2180 1880 1640
2320 2125 1845 1640
2465 2115 1800 1570
--- --­2155
--- --­2140
2010 1755 1525 1320 2400 2150 1850 1635
--- --­2145 1850 1635
2250 2065 1825 1620
2430 2105 1790 1565
--- --­2135
--- --­2095
NOTE: For horizontal applications, the top--most flange may be bent past 90_ to allow the evaporator coil to hang on the flange temporarily while the remaining attachment and sealing of the
EXTERNAL STATIC PRESSURE (IN. WC)
1930 1705 1500 1295 2310 2090 1820 1615
2385 2060 1820 1615
2155 1995 1765 1580
2375 2075 1770 1550
2375 2095
2260 2040
1835 1640 1450 1265 2215 2000 1780 1585
2305 2010 1780 1585
2055 1910 1710 1540
2305 2030 1735 1525
2285 2040
2180 1975
1710 1550 1380 1210 2110 1920 1715 1530
2195 1945 1715 1530
1970 1815 1650 1485
2230 1980 1695 1495
2200 1975
2085 1890
1590 1465 1315 1150 2000 1825 1635 1465
2085 1865 1635 1465
1855 1710 1570 1410
2110 1910 1640 1445
2105 1895
1975 1810
1470 1360 1215
995 1880 1720
1540 1370
1960 1765 1540 1370
1725 1610 1475 1330
2000 1830 1570 1370
1995 1790
1865 1705
1335 1210 1005
865 1725 1565
1415 1255
1825 1660 1415 1255
1600 1490 1370 1220
1865 1725 1465 1270
1870 1685
1740 1595
horizontal furnaces are approved for side return air connections. (See Fig. 20.)
PIPING
GAS
coil are performed.
Downflow
Connect supply--air duct to supply--air outlet on furnace. Bend flange inward past 90_ with wide duct pliers. (See Fig. 14.) The supply--air duct must be connected to ONLY the furnace supplyoutlet or air conditioning coil casing (when used). When installed on combustible material, supply--air duct must be connected to ONLY the accessory subbase, KGASB0201ALL, or a factory approved air conditioning coil casing. DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected to duct
Furnaces
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
external to furnace casing.
Return Air
FIRE HAZARD
Failure to follow this warning could cause personal injury, death and/or property damage.
Never connect return--air ducts to the back of the furnace.
Connections
!
WARNING
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Use proper length of pipe to avoid stress on gas control manifold and a gas leak.
Follow instructions below.
1025
945 855
745 1535 1405
1290 1150
1670 1515 1290 1150
1450 1340 1240 1080
1725 1590 1345 1175
1730 1550
1605 1480
835 785 670
540 1355 1255
1160 1040
1465 1325 1160 1040
1280 1175 1100
960 1545
1425 1225 1070
1570 1400
1455 1325
Downflow Furnaces
The return--air duct must be connected to return--air opening (bottom inlet) as shown in Fig. 1. DO NOT cut into casing sides (left or right). Side opening is permitted for only upflow and most horizontal furnaces. Bypass humidifier connections should be made at ductwork or coil casing sides exterior to furnace. (See Fig. 19.) Upflow and Horizontal Furnaces The return--air duct must be connected to bottom, sides (left or right), or a combination of bottom and side(s) of main furnace casing as shown in Fig. 1. Bypass humidifier may be attached into unused return air side of the furnace casing. (See Fig. 18 and 20.) Not all
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to protect gas valve inlet from water and debris could result in death, personal injury and/or property damage.
Gas valve inlet and/or inlet pipe must remain capped until gas supply line is permanently installed to protect the valve from moisture and debris. Also, install a sediment trap in the gas supply piping at the inlet to the gas valve.
18
Page 19
Fig. 18 -- Upflow Return Air Configurations and Restrictions
Fig. 19 -- Downflow Return Air Configurations and Restrictions
A02075
A02163
312A
Fig. 20 -- Horizontal Return Air Configurations and Restrictions
19
A02162
Page 20
Gas piping must be installed in accordance with national and local codes. Refer to current edition of NFGC in the U.S. and the CAN/CSA--B149.1--05 in Canada.
Table 6 – Maximum Capacity of Pipe*
NOMINAL
IRON PIPE SIZE
(IN.)
1/2 0.622 175 120 97 82 73
3/4 0.824 360 250 200 170 151
1 1.049 680 465 375 320 285
1 --- 1 / 4 1.380 1400 950 770 660 580
1 --- 1 / 2 1.610 2100 1460 1180 990 900
* Cubic ft of natural gas per hr for gas pressures of 0.5 psig (14 --- in. wc) or less and a pressure drop of 0.5 ---in wc (based on a 0.60 specific gravity gas). Ref: Table 12.2 ANSI Z223 ---2006/NFPA 54---2006.
INTERNAL DIAMETER
(IN.)
LENGTH OF PIPE (FT)
10 20 30 40 50
Installations must be made in accordance with all authorities having jurisdiction. If possible, the gas supply line should be a separate line running directly from meter to furnace.
312A
NOTE: In the state of Massachusetts:
1. Gas supply connections MUST be performed by a licensed plumber or gas fitter.
2. When flexible connectors are used, the maximum length shall not exceed 36 inches (915 mm).
3. When lever handle type manual equipment shutoff valves are used, they shall be T--handle valves.
4. The use of copper tubing for gas piping is NOT approved by the state of Massachusetts.
Refer to Table 6 for recommended gas pipe sizing. Risers must be used to connect to furnace and to meter. Support all gas piping with appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft Joint compound (pipe dope) should be applied sparingly and only to male threads of joints. Pipe dope must be resistant to the action of propane gas.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
If local codes allow the use of a flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously served another gas appliance. Black iron pipe shall be installed at the furnace gas control valve and extend a minimum of 2 in. outside the furnace.
!
CAUTION
test pressure DOES NOT exceed maximum 0.5 psig (14--in. wc) stated on gas control valve. (See Fig. 54.) Some installations require gas entry on right side of furnace (as viewed in upflow). (See Fig. 21 and 22.)
A05028
Fig. 21 -- Right Side Gas Entry Example 1
90° Elbow
2" Nipple
Street Elbow
Gas Valve
A02327
Fig. 22 -- Right Side Gas Entry Example 2
Install a sediment trap in riser leading to furnace as shown in Fig.
23. Connect a capped nipple into lower end of tee. Capped nipple should extend below level of furnace gas controls. Place a ground joint union between furnace gas control valve manifold and exterior manual equipment gas shutoff valve.
GAS SUPPLY
MANUAL SHUTOFF VALV E (REQUIRED
SEDIMENT TRAP
UNION
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in furnace damage.
Connect gas pipe to furnace using a backup wrench to avoid damaging gas controls and burner misalignment.
An accessible manual equipment shutoff valve MUST be installed external to furnace casing and within 6 ft of furnace. A 1/8--in. NPT plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual equipment shutoff valve.
NOTE: The furnace gas control valve inlet pressure tap connection is suitable to use as test gauge connection providing
A02035
Fig. 23 -- Typical Gas Pipe Arrangement
A 1/8--in. NPT plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual equipment shutoff valve.
20
Page 21
NOTE 2
WC Y RG
W2
COM
W/W1
NOTE 1
Y/Y2
R
G
NOTES: 1.
BLK
WHT
GND
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
BLK
WHT
JUNCTION BOX
FIVE
WIRE
THREE-WIRE
HEATING-
ONLY
CONTROL
BOX
FURNACE
24-VOLT
TERMINAL
BLOCK
Fig. 24 -- Field Wiring Diagram
Piping should be pressure and leak tested in accordance with NFGC in the United States or CAN/CSA--B149.1--05 in Canada, local, and national plumbing and gas codes before the furnace has been connected. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace.
If pressure exceeds 0.5 psig (14--in. wc), gas supply pipe must be disconnected from furnace and capped before and during supply pipe pressure test. If test pressure is equal to or less than 0.5 psig (14--in. wc), turn off electric shutoff switch located on furnace gas control valve and accessible manual equipment shutoff valve before and during supply pipe pressure test. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace.
The gas supply pressure shall be within the maximum and minimum inlet supply pressures marked on the rating plate with the furnace burners ON and OFF.
ELECTRICAL
CONNECTIONS
FIELD 24-VOLT WIRING FIELD 115-, 208/230-, 460-VOLT WIRING FACTORY 24-VOLT WIRING FACTORY 115-VOLT WIRING
1-STAGE THERMOSTAT TERMINALS
CONDENSING
UNIT
Connect Y/Y2-terminal as shown for proper operation. Some thermostats require a "C" terminal connection as shown.
2. If any of the original wire, as supplied, must be replaced, use
3. same type or equivalent wire.
!
FIELD-SUPPLIED
FUSED DISCONNECT
208/230- OR 460-VOLT THREE PHASE
208/230­VOLT SINGLE
GND
PHASE
WARNING
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
The cabinet MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70--2006 and Canadian Electrical Code CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire, conduit approved for electrical ground or a listed, grounded power cord (where permitted by local code) when installed in accordance with existing electrical codes. Refer to the power cord manufacturer’s ratings for proper wire gauge. Do not use gas piping as an electrical ground.
312A
A95236
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Blower access panel door switch opens 115--v power to control. No component operation can occur. Do not bypass or close switch with panel removed.
See Fig. 24 for field wiring diagram showing typical field 115--v wiring. Check all factory and field electrical connections for tightness.
Field--supplied wiring shall conform with the limitations of 63_F (33_C) rise.
!
CAUTION
FURNACE MAY NOT OPERATE HAZARD
Failure to follow this caution may result in intermittent furnace operation.
Furnace control must be grounded for proper operation or else control will lock out. Control must remain grounded through green/yellow wire routed to gas valve and manifold bracket screw.
115 -- V WIRING
Verify that the voltage, frequency, and phase correspond to that specified on unit rating plate. Also, check to be sure that service provided by utility is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 7 for equipment electrical specifications.
21
Page 22
Table 7 – Electrical Data
V O LT S ---
H E R T Z ---
PHASE
1 1 5 --- 6 0 --- 1 127 104 5.3 045 --- 08/024045 7.42 49 15 14 1 1 5 --- 6 0 --- 1 127 104 7.1 045 --- 12/036045 9.67 38 15 14 1 1 5 --- 6 0 --- 1 127 104 5.2 070 --- 08/024070 7.22 51 15 14 1 1 5 --- 6 0 --- 1 127 104 7.3 070 --- 12/036070 9.90 37 15 14 1 1 5 --- 6 0 --- 1 127 104 10.1 070--- 16/048070 13.42 27 15 14 1 1 5 --- 6 0 --- 1 127 104 8.2 090 --- 14/042090 10.84 34 15 14 1 1 5 --- 6 0 --- 1 127 104 9.9 090 --- 16/048090 13.0 28 15 14 1 1 5 --- 6 0 --- 1 127 104 12.9 090--- 20/060090 16.70 34 20 12 1 1 5 --- 6 0 --- 1 127 104 8.2 110 --- 12/036110 10.76 34 15 14 1 1 5 --- 6 0 --- 1 127 104 10.1 110--- 16/048110 13.19 28 15 14 1 1 5 --- 6 0 --- 1 127 104 13.7 110--- 22/066110 17.60 32 20 12 1 1 5 --- 6 0 --- 1 127 104 10.2 135--- 16/048135 13.28 27 15 14 1 1 5 --- 6 0 --- 1 127 104 14.5 135--- 22/066135 18.61 30 20 12 1 1 5 --- 6 0 --- 1 127 104 15.0 155--- 20/060155 19.34 29 20 12
* Permissible limits of the voltage ran ge at which the unit operates satisfactorily.
312A
# Unit ampacity = 125% of lar gest operating component’s full load amps plus 100% of all other potential operating components (EAC, humidifier,
etc.) full load amps.
{ Time---delay type is recommended. } Length shown is as measured 1 way along wire path between unit and service panel for maximum 2% voltage drop.
U.S. Installations: Make all electrical connections in accordance with National Electrical Code (NEC) ANSI/NFPA 70--2006 and any local codes or ordinances that might apply.
Canadian Installations: Make all electrical connections in
OPERATING VOLTAGE
RANGE
MAX* MIN.*
MAX UNIT
AMPS
FURNACE
SIZE
UNIT
AMPACITY#
4. Fasten J--Box to casing with the two screws removed in Step 1.
5. Route J-- Box wires within furnace away from sharp edges, rotating parts, and hot surfaces.
MAXIMUM
WIRE
LENGTH
(ft)‡
MAXIMUM
FUSE OR CKT BKR
AMPS†
accordance with Canadian Electrical Code CSA C22.1 or authorities having jurisdiction.
MINIMUM
WIRE
GAUGE
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.
Use a separate branch electrical circuit with a properly sized fuse or circuit breaker for this furnace. See Table 7 for wire size and fuse specifications. A readily accessible means of electrical disconnect must be located within sight of the furnace.
NOTE: Proper polarity must be maintained for 115--v wiring. If polarity is incorrect, control LED status indicator light will flash rapidly and furnace will NOT operate.
J--BOX RELOCA
TION
NOTE: If factory location of J--Box is acceptable, go to next
section (ELECTRICAL CONNECTION TO J--BOX).
NOTE: On 14” wide casing models, the J--Box shall not be relocated to other side of furnace casing when the vent pipe is routed within the casing.
1. Remove and save two screws holding J--Box. (See Fig.
25.)
NOTE: The J--Box cover need not be removed from the J--Box in order to move the J--Box. Do NOT remove green ground screw inside J--Box. The ground screw is not threaded into the casing flange and can be lifted out of the clearance hole in casing while swinging the front edge of the J--box outboard of the casing.
2. Cut wire tie on loop in furnace wires attached to J--Box.
3. Move J--Box to desired location.
TWO
A02099
Fig. 25 -- Relocating J--Box
ELECTRICAL CONNECTION TO
J--BOX
Field-- Supplied Electrical Box on Furnace J--Box Bracket. See Fig. 26.
1. Remove cover from furnace J--Box.
2. Attach electrical box to furnace J--Box bracket with at least two field--supplied screws through holes in electrical box into holes in bracket. Use blunt--nose screws that will not pierce wire insulation.
3. Route furnace power wires through holes in electrical box and J--Box bracket, and make field--wire connections in electrical box. Use best practices (NEC in U.S. and CSA C22.1 in Canada) for wire bushings, strain relief, etc.
4. Route and secure field ground wire to green ground screw on J--Box bracket.
5. Connect line voltage leads as shown in Fig. 24.
22
Page 23
6. Reinstall cover to J--Box. Do not pinch wires between cover and bracket.
Electrical Box on Furnace Casing Side. See Fig.
!
WARNING
FIRE OR ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
If field--supplied manual disconnect switch is to be mounted on furnace casing side, select a location where a drill or fastener cannot damage electrical or gas components.
Fig. 26 -- Field--Supplied Electrical Box on Furnace Casing
1. Select and remove a hole knockout in the casing where the electrical box is to be installed.
NOTE: Check that duct on side of furnace will not interfere with installed electrical box.
2. Remove the desired electrical box hole knockout and position the hole in the electrical box over the hole in the furnace casing.
3. Fasten the electrical box to casing by driving two fieldsupplied screws from inside electrical box into casing steel.
4. Remove and save two screws holding J--Box. (See Fig.
25.)
26.
A03221
5. Pull furnace power wires out of 1/2--inch diameter hole in J--Box. Do not loosen wires from strain--relief wire--tie on outside of J--Box.
6. Route furnace power wires through holes in casing and electrical box and into electrical box.
7. Pull field power wires into electrical box.
8. Remove cover from furnace J--Box.
9. Route field ground wire through holes in electrical box and casing, and into furnace J--Box.
10. Reattach furnace J--Box to furnace casing with screws removedinStep4.
11. Secure field ground wire to J--Box green ground screw.
12. Complete electrical box wiring and installation. Connect line voltage leads as shown in Fig. 24. Use best practices (NEC in U.S. and CSA C22.1 in Canada) for wire bushings, strain relief, etc.
13. Reinstall cover to J--Box. Do not pinch wires between cover and bracket.
POWER CORD INSTALLATION IN FURNACE
NOTE: Power cords must be able to handle the electrical
requirements listed in Table 7. Refer to power cord manufacturer’s listings.
1. Remove cover from J--Box.
2. Route listed power cord through 7/8--inch diameter hole in J--Box.
3. Secure power cord to J--Box bracket with a strain relief bushing or a connector approved for the type of cord used.
4. Secure field ground wire to green ground screw on J--Box bracket.
5. Connect line voltage leads as shown in Fig. 24.
6. Reinstall cover to J--Box. Do not pinch wires between cover and bracket.
BX. CABLE INSTALLATION IN FURNACE
1. Remove cover from J--Box.
2. Route BX cable into 7/8--inch diameter hole in J--Box.
3. Secure BX cable to J--Box bracket with connectors approved for the type of cable used.
4. Secure field ground wire to green ground screw on J--Box bracket.
5. Connect line voltage leads as shown in Fig. 24.
6. Reinstall cover to J--Box. Do not pinch wires between cover and bracket.
24--V
WIRING
Make field 24--v connections at the 24--v terminal strip. (See Fig.
34.) Connect terminal Y/Y2 as shown in Fig. 27--33 for proper cooling operation. Use only AWG No. 18, color--coded, copper thermostat wire.
The 24--v circuit contains an automotive--type, 3--amp. fuse located on the control. Any direct shorts during installation, service, or maintenance could cause this fuse to blow. If fuse replacement is required, use ONLY a 3--amp. fuse of identical size.
J--BOX
J--BOX
312A
23
Page 24
312A
See notes 2, 5, 8, 10, 11 and 12 on the page following these figures
Fig. 27 -- Two--Stage Furnace with Two--Speed Air
Conditioner
A03179
See notes 1, 2, 3, 4, 6, 8, 9, 10, 12, 13 and 15 on the page following these figures
A03178
Fig. 29 -- Two--Stage Furnace with Two--Speed Heat Pump
(Dual Fuel)
See notes 1, 2, 4, 6, 7, 9, 10, 11, and 15 on the page following these figures
A03180
Fig. 28 -- Two--Stage Furnace with Single--Speed Heat Pump
(Dual Fuel)
See notes 1, 2, 4, 11, 14, 15, and 16 on the page following these figures
Fig. 30 -- Dual Fuel Thermostat with Two--Stage Furnace
and Single--Speed Heat Pump
24
A03181
Page 25
7
See notes 1, 2, 3, 4, 12, 13, 14, 15, and 17 on the page following these figures
A03182
Fig. 31 -- Dual Fuel Thermostat with Two--Stage Furnace
and Two--Speed Heat Pump
See notes 1 and 2 on the page following these figures
Fig. 33 -- Single--Stage Thermostat with Two--Stage Furnace and Two--Speed Air Conditioner
See notes 2, 11, and 12 on the page following these figures
A03183
Fig. 32 -- Two--Stage Thermostat with Two--Stage Furnace
and Two--Speed Air Conditioner
A03184
312A
NOTES: F o r Figu r e s 25 --- 31
1. Heat pump MUST have a high pressure switch for dual fuel appl ications.
2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
3. Outdoor Air Temperature Sensor must be attached in all dual fuel applications.
4. Dip switch No. 1 on Thermidistat shou ld be set in OFF position for air conditioner installations. This is factory default.
5. Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations.
6. Dip switch No. 2 on Thermidistat should be set in OFF position for single ---speed compressor operation. This is factory default.
7. Dip switch No. 2 on Thermidistat should be set in ON position for two ---speed compressor operation.
8. Configuration Option No. 10 “Dual Fuel Selection” must be turned ON in all dual fuel applications.
9. NO connection should be made to the furnace HUM terminal when using a Thermidistat.
10. Optional connection: If wire is connected, dip switch SW1---2 on furnace control should be set in ON position to allow Thermidistat/Thermostat to control furnace staging.
11. Optional connection: If wire is connected, ACRDJ jumper on furnace control should be removed to allow Thermidistat/Thermostat to control outdoorunit staging.
12. When using both a two---stage furnace and a two---stage heat pump, the furnace must control its own high---stage heating operation via furnace control algorithm.
13. The RVS Sensing terminal “L” should not be connected. This is internally used to sense defrost operation.
14. DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE POINT” option on the two ---speed h eat pump control board. This is controlled internally by the Thermidistat/Dual Fuel Thermostat.
15. Dip switch D on Dual Fuel Thermostat should be set in OFF position for single---speed compressor operation. This is factory default.
16. Dip switch D on Dual Fuel Thermostat should be set in ON position for two --- speed compressor operation.
25
Page 26
ACCESSORIES
1. Electronic Air Cleaner (EAC) Connect an accessory Electronic Air Cleaner (if used) using 1/4--in female quick connect terminals to the two male 1/4--in quick--connect terminals on the control board marked EAC-- 1 and EAC--2. The terminals are rated for 115VAC, 1.0 amps maximum and are energized during blower motor operation. (See Fig. 34.)
2. Humidifier (HUM) Connect an accessory 24 VAC, 0.5 amp. maximum humidifer (if used) to the 1/4--in male quick--connect HUM terminal and COM--24V screw terminal on the control board thermostat strip. The HUM terminal is energized when gas valve relay (GVR) is energized. (See Fig. 34.)
NOTE: A field--supplied, 115 --v controlled relay connected to EAC terminals may be added if humidifier operation is desired during blower operation.
312A
SETUP SWITCHES
LOW-HEAT ONLY AND
BLOWER OFF-DELAY
ON
W2
Y1 DHUM G COM
OFF
1 2 3
LHT OFF DLY
NOTE: DO NOT connect furnace control HUM terminal to HUM (humidifier) terminal on Thermidistat, Zone Controller or similar device. See Thermidistatt, Zone Controller, thermostat, or controller manufacturer’s instructions for proper connection.
VENTING
The furnace shall be connected to a listed factory built chimney or vent or a clay--tile lined masonry or concrete chimney. Venting into an unlined masonry chimney or concrete chimney is prohibited. When an existing Category I furnace is removed or replaced, the original venting system may no longer be sized to properly vent the attached appliances. An improperly sized Category I venting system could cause the formation of condensate in the furnace and vent, leakage of condensate and combustion products, and spillage of combustion products into the living space.
TWINNING AND/OR COMPONENT TEST
TERMINAL
ACRDJ - AIR CONDITIONING
RELAY DISABLE JUMPER
24-V-THERMOSTAT TERMINALS
HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP MAX.)
3-AMP FUSE
LED OPERATION &
DIAGNOSTIC LIGHT
115-VAC (L2) NEUTRAL
CONNECTIONS
HI HEAT
LO HEAT
BLOWER SPEED
SELECTION TERMINALS
24V
WW1 Y/Y2 R
S
E
L
EAC-2
BLW
HI HEAT LO HEAT
SPARE-1
SPARE-2
TEST/TWIN
HUM
0.5-AMP024 VAC
FUSE 3-AMP
A
T
T
SEC-1 SEC-2
U
S
C
O
E
D
NEUTRAL-L2
COOL
SPARE-1 SPARE-2
Fig. 34 -- Furnace Control--PSC Blower Motor
ACRDJ
PLT
PL1
1
BHT/CLRBHI/LOR
1-AMP@115 VAC
EAC-1 PR-1
COOL
D
BLWR
L1
115-VAC (L1) LINE
VOLTAGE CONNECTION
EAC-1 TERMINAL
(115-VAC 1.0 AMP MAX.)
IDR
PL2
1
PL3 1
HSIR
HSI HI LO
TRANSFORMER 24-VAC
CONNECTIONS
PL1 - LOW VOLTAGE MAIN
HARNESS CONNECTOR
PL3
IHI/LOR
IDM
PL2 - HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
A02017
26
Page 27
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CSA B149.1, Natural Gas and Propane Installation Code and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas--fired burning appliance to their previous conditions of use.
Vent system or vent connectors may need to be resized. Vent systems or vent connectors must be sized to approach minimum size as determined using appropriate table found in the NFGC or CAN/CSA--B149.1--05.
GENERAL VENTING
Follow all safety codes for proper vent sizing and installation requirements, including local building codes, the National Fuel Gas Code ANSI Z223.1--2006/NFPA 54--2006 (NFGC), Parts 10 and 13 in the United States or the National Standard of Canada, Natural Gas and Propane Installation Code CSA--B149.1--00 (CAN/CSA--B149.1--05), Section 8 and Appendix C in Canada, the local building codes, and furnace and vent manufacturers’ instructions.
These furnaces are design-- certified as Category I furnaces in accordance with ANSI Z21.47--2003/CSA 2.3--2003 and operate with a non--positive vent static pressure to minimize the potential for vent gas leakage. Category I furnaces operate with a flue loss not less than 17% to minimize the potential for condensation in the venting system. These furnaces are approved for common venting and multi--story venting with other fan assisted or draft
REQUIREMENTS
hood equipped appliances in accordance with the NFCG or the CAN/CSA--B149.1--05, local building codes, and furnace and vent manufacturers’ instructions.
The following information and warning must be considered in addition to the requirements defined in the NFGC or the CAN/CSA--B149.1--05.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Do not bypass the draft safeguard switch, as an unsafe condition could exist which must be corrected.
1. If a vent (common or dedicated) becomes blocked, the furnace will be shut off by the draft safeguard switch located on the vent elbow.
2. Two--stage furnaces require Type B vent connectors outside the casing in all configurations. Single wall vent connector may be used inside the furnace casing with the transition to Type B vent outside the furnace casing. Size the connector so that the FAN-- Min vent connector capacity is equal to or lower than the low fire rate of the furnace and the FAN--Max vent connector capacity is equal to or higher than the furnace high fire rate.
3. Do not vent this Category I furnace into a single wall dedicated or common vent. The dedicated or common vent is considered to be the vertical portion of the vent system that terminates outdoors.
4. Vent connectors serving Category I furnaces shall not be connected into any portion of a mechanical draft system operating under positive pressure.
5. In the US: Do not vent this appliance with any solid fuel burning appliance. In Canada: Check with the authority having jurisdiction for approval on use with solid fuel burning appliance.
6. Category I furnaces must be vented vertically or nearly vertically unless equipped with a listed mechanical venter. See the SIDEWALL VENTING section.
7. Do not vent this appliance into an unlined masonry chimney. Refer to Chimney Inspection Chart, Fig. 35.
MASONRY CHIMNEY
NOTE: These furnaces are CSA design--certified for use in
exterior tile--lined masonry chimneys with a factory accessory Chimney Adapter Kit. Refer to the furnace rating plate for correct kit usage. The Chimney Adapter Kits are for use with ONLY furnaces having a Chimney Adapter Kit number marked on the furnace rating plate.
If a clay tile--lined masonry chimney is being used and it is exposed to the outdoors below the roof line, relining might be required. Chimneys shall conform to the Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances ANSI/NFPA 211--2003 in the United States and to a Provincial or Territorial Building Code in Canada (in its absence, the National Building Code of Canada) and must be in good condition.
U.S.A.--Refer to Sections 13.1.9 and 13.2.20 of the NFGC or the authority having jurisdiction to determine whether relining is required. If relining is required, use a properly sized listed metal liner, Type--B vent, or a listed alternative venting design.
NOTE: See the NFGC, 13.1.9 and 13.2.20 regarding alternative venting design and the exception, which cover installations such as the Chimney Adapter Kits KGACA02014FC and KGACA02015FC, which are listed for use with these furnaces.
REQUIREMENTS
312A
27
Page 28
CHIMNEY INSPECTION CHART
For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211
Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances in the U.S.A. or to the Canadian
installation Code CSA-B149.1 in Canada.
312A
Crown
condition:
Missing mortar
or brick?
No
Is chimney
property lined with
clay tile liner?
Ye s
Is liner and top seal in good
condition?
Ye s
Debris
in cleanout?
Mortar, tile, metal vent,
fuel oil residue?
Ye s
No
Ye s
No
Rebuild
crown.
Repair
liner or top seal
or reline chimney as
necessary.
Repair
Mortar
or tile
debris?
Reline
Ye s
Remove mortar
and tile debris
No
Clay
tile misalignment,
missing sections,
gaps?
No
Condensate
drainage at bottom
of chimney?
No
Chimney
exposed to
outdoors below
roof line?
No
Chimney is
acceptable for use.
Remove metal vent
or liner.
Ye s
lined with properly
sized, listed liner or
Ye s
Ye s
No
No
Is chimney
Type-B vent?
Ye s
Is chimney
to be dedicated to
a single
furnace?
Consult
Part B of
chimney adapter venting
instructions for
application
suitability.
Suitable
Ye s
Install chimney
adapter per
instructions.
No
chimney adapter venting
Not Suitable
Not Suitable
Consult
Part C of
instructions for
application
suitability
Line chimney with property
sized, listed flexible metal
liner or Type-B vent per
NFGC or NSCNGPIC Vent
Sizing Tables and liner or
vent manufacturer’s
Installation instructions.
Suitable
Install chimney
adapter per
instructions.
Fig. 35 -- Chimney Inspection Chart
28
A03206
Page 29
The Chimney Adapter Kit is a listed alternative venting system for these furnaces. See the kit instructions for complete details.
Canada (and U.S.A.)--This furnace is permitted to be vented into a clay tile--lined masonry chimney that is exposed to the outdoors below the roof line, provided:
1. Vent connector is Type--B double--wall, and
2. This furnace is common vented with at least 1 draft hoodequipped appliance, and
3. The combined appliance input rating is less than the maximum capacity given in Table 8, and
4. The input rating of each space heating appliance is greater than the minimum input rating given in Table 9 for the local 99% Winter Design Temperature. Chimneys having internal areas greater than 38 square inches require furnace input ratings greater than the input ratings of these furnaces. See footnote at bottom of Table 9, and
5. The authority having jurisdiction approves.
If all of these conditions cannot be met, an alternative venting design shall be used, such as the listed chimney adapter kit with a furnace listed for use with the kit, a listed chimney--lining system, or a Type--B common vent.
Inspections before the sale and at the time of installation will determine the acceptability of the chimney or the need for repair and/or (re)lining. Refer to Fig. 35 to perform a chimney inspection. If the inspection of a previously used tile--lined chimney:
a. Shows signs of vent gas condensation, the chimney
should be relined in accordance with local codes and the authority having jurisdiction. The chimney should be relined with a listed metal liner, Type--B vent, or a listed chimney adapterkitshallbeusedto reducecondensation. If a condensate drain is required by local code, refer to the NFGC, Section 10.9 for additional information on condensate drains.
b. Indicates the chimney exceeds the maximum permissible
sizein thetables, the chimney should berebuilt or relined to conform to the requirements of the equipment being installed and the authority having jurisdiction.
A chimney without a clay tile liner, which is otherwise in good condition, shall be rebuilt to conform to ANSI/NFPA 211 or be lined with a UL listed (ULC listed in Canada) metal liner or UL listed Type--B vent. Relining with a listed metal liner or Type--B vent is considered to be a vent--in--a--chase.
If a metal liner or Type--B vent is used to line a chimney, no other appliance shall be vented into the annular space between the chimney and the metal liner.
Exterior Masonry Chimney FAN + NA Installations with Type-- B Double--Wall V Connectors
ENFPA & AGA
T
ent
Table 8 – Combined Appliance Maximum Input Rating in
Thousands of BTUH per Hour
VENT HEIGHT
(FT)
6 74 119 178 257
8 80 130 193 279 10 84 138 207 299 15 NR 152 233 334 20 NR NR 250 368 30 NR NR NR 404
INTERNAL AREA OF CHIMNEY
(SQ. IN.)
12 19 28 38
Table 9 – Minimum Allowable Input Rating of Space--Heat-
ing Appliance in Thousands of BTUH per Hour
VENT HEIGHT
(FT)
6 0 55 99 141
8 52 74 111 154
10 NR 90 125 169
15 NR NR 167 212
20 NR NR 212 258
30 NR NR NR 362
6 NR 78 121 166
8 NR 94 135 182
10 NR 111 149 198
15 NR NR 193 247
20 NR NR NR 293
30 NR NR NR 377
Temperature: --- 10 to 4_F*
6 NR NR 145 196
8 NR NR 159 213
10 NR NR 175 231
15 NR NR NR 283
20 NR NR NR 333
30 NR NR NR NR
Temperature: --- 11_Forlower
Not recommended for any vent configuration.
*The 99% Winter Design Dry--- Bulb (db) temperatures are found in the 1993 ASHRAE Fundamentals Handbook, Chapter 24, Table 1 (United States) and 2 (Canada), or use the 99.6% heating db temperatures found in th e 1997 or 2001 ASHRAE Fundamentals Handbook, Climatic Design Information chapter, Table 1A (United States) and 2A (Canada).
INTERNAL AREA OF CHIMNEY
(SQ. IN.)
12 19 28 38
Local 99% Winter Design
Temperature: 17 to 26_F
Local 99% Winter Design
Temperature: 5 to 16_F*
Local 99% Winter Design
Local 99% Winter Design
APPLIANCE APPLICATION REQUIREMENTS
Appliance operation has a significant impact on the performance of the venting system. If the appliances are sized, installed, adjusted, and operated properly, the venting system and/or the appliances should not suffer from condensation and corrosion. The venting system and all appliances shall be installed in accordance with applicable listings, standards, and codes.
The furnace should be sized to provide 100% of the design heating load requirement plus any margin that occurs because of furnace model size capacity increments. Heating load estimates can be made using approved methods available from Air Conditioning Contractors of America (Manual J); American Society of Heating, Refrigerating, and Air--Conditioning Engineers; or other approved engineering methods. Excessive over--sizing of the furnace could cause the furnace and/or vent to fail prematurely. When a metal vent or metal liner is used, the vent must be in good condition and be installed in accordance with the vent manufacturer’s instructions.
To prevent condensation in the furnace and vent system, the following precautions must be observed:
1. The return-- air temperature must be at least 60_F db except
for brief periods of time during warm--up from setback at no lower than 55_F(13_C) db or during initial start--up from a standby condition.
2. Adjust the gas input rate per the installation instructions. Low gas input rate causes low vent gas temperatures,
29
312A
Page 30
causing condensation and corrosion in the furnace and/or venting system. Derating is permitted only for altitudes above 2000 ft
3. Adjust the air temperature rise to the midpoint of the rise range or slightly above. Low air temperature rise can cause low vent gas temperature and potential for condensation problems.
4. Set the thermostat heat anticipator or cycle rate to reduce short cycling.
Air for combustion must not be contaminated by halogen compounds which include chlorides, fluorides, bromides, and iodides. These compounds are found in many common home products such as detergent, paint, glue, aerosol spray, bleach, cleaning solvent, salt, and air freshener, and can cause corrosion of furnaces and vents. Avoid using such products in the combustion--air supply. Furnace use during construction of the building could cause the furnace to be exposed to halogen compounds, causing premature failure of the furnace or venting system due to corrosion.
312A
Vent dampers on any appliance connected to the common vent can cause condensation and corrosion in the venting system. Do not use vent dampers on appliances common vented with this furnace.
ADDITIONAL VENTING REQUIREMENTS
A 4 in. round vent elbow is supplied with the furnace. A 5 in. or 6 in. vent connector may be required for some model furnaces. A field--supplied 4 in. to 5 in. or 4 in. to 6 in. sheet metal increaser fitting is required when 5 in. or 6 in. vent connector is used. See Fig. 36--48 Venting Orientation for approved vent configurations.
See Venting Notes after Fig. 48.
SEE NOTES: 1,2,3,4,7,8,9 on the pages following these figures
Fig. 37 -- Upflow Application--Vent Elbow Right
A03209
SEE NOTES: 1,2,4,7,8,9 on the page following these figures
Fig. 36 -- Upflow Application--Vent Elbow Up
A03208
SEE NOTES:1,2,3,4,5,7,8,9 on the page following these figures
A03210
Fig. 38 -- Downflow Application--Vent Elbow Up then Left
30
Page 31
SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures
SEE NOTES:1,2,3,4,5,7,8,9
312A
on the page following these figures.
Fig. 39 -- Downflow Application--Vent Elbow Up
SEE NOTES: 1,2,4,5,6,7,8,9,10 on the page following these figures
A03211
A03212
Fig. 41 -- Downflow Application--Vent Elbow Up then Right
SEE NOTES: 1,2,4,7,8,9 on the page following these figures
A03213
Fig. 42 -- Horizontal Left Application -- Vent Elbow Left
A03207
Fig. 40 -- Downflow Application--Vent Elbow Left then Up
SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures
Fig. 43 -- Horizontal Left Application -- Vent Elbow Right
then Up
31
A03214
Page 32
SEE NOTES: 1,2,4,7,8,9 on the page following these figures
SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures
Fig. 44 -- Horizontal Right Application -- Vent Elbow Right
312A
SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures
Fig. 45 -- Horizontal Left Application -- Vent Elbow Up
A03218
A03215
A03216
Fig. 46 -- Horizontal Left Application -- Vent Elbow Right
SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures
A03219
Fig. 47 -- Horizontal Right Application -- Vent Elbow Left
then Up
SEE NOTES: 1,2,4,5,7,8,9
A02068
Fig. 48 -- Horizontal Right Application--Vent Elbow Left
NOTES: Venting Notes for Fig. 36---48
1. For common vent, vent connector sizing and vent material: United States--- ---use the NFGC Canada--- --- use the CAN/CSA---B149.1 ---05
2. Immediately increase to 5---inch or 6---inch vent connector outside furnace casing when 5---inch vent connector is required, refer to Note 1 above.
3. Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace, except when KGAVG0101DFG, Downflow VentGuardKit,isusedinthedownflowposition.
4. Type ---B vent where required, refer to Note 1 above.
5. Four ---inch single ---wall (26 ga. min.) vent must be used inside furnace casing and when the KGAVG0101DFG Downflow Vent Guard Kit is used external to the furnace.
6. Accessory Downflow Vent Guard Kit, KGAVG0101DFG required in downflow installations with lower vent configuration.
7. Chimney Adapter Kit may be required for exterior masonry chimney applications. Refer to Chimney Adapter Kit, KGACA02014FC or KGACA02015FC, for sizing and complete application details.
8. Secure vent connector to furnace elbow with (2) corrosion---resistant sheet metal screws, spaced approximately 180_ apart.
9. Secure all other single wall vent connector joints with (3) corrosion resistant screws spaced approximately 120_ apart. Secure Type --- B vent connectors per vent connector manufacturer’s recommendations.
10. The total height of the vent and connector shall be at least seven feet for the 154,000 Btuh gas input rate model when installed in a downflow application with furnace elbow turned to left side with the connector elbow outside furnace casing pointing upward. (See Fig. 41.)
32
Page 33
Caution!! For the following applications, use the minimum vertical heights as specified below.
For all other applications, follow exclusively the National Fuel Gas Code
FURNACE
ORIENTATION
Downflow
Horizontal Left
Horizontal Left
Horizontal Left
Downflow
Downflow
NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC. *4 in. inside casing or vent guard **Including 4 in. vent section(s)
VENT ORIENTA-
TION
Vent elbow left, then
up Fig. 40
Vent elbow right,
then up Fig. 43
Vent Elbow up Fig.
44
Vent elbow right Fig.
45
Vent elbow up then
left Fig. 38
Vent elbow up, then
right Fig. 41
FURNACE IN-
PUT(BTUH/HR)
154,000 132,000
110,000(036/--- 12 only)
154,000 132,000 154,000 132,000
154,000 5 7
110,000 (036/--- 12 only) 5 10
110,000 (036/--- 12 only) 5 10
MINIMUM VENT
DIAMETER (IN.)*
5 12
5 7
5 7
MINIMUM VERTICAL VENT
HEIGHT (FT)**
312A
Fig. 49 -- Using Tin Snips to Cut Tie Points
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.
NOTE: Vent connector length for connector sizing starts at furnace vent elbow. The 4 inch vent elbow is shipped for upflow configuration and may be rotated for other positions. Remove the 3 screws that secure vent elbow to furnace, rotate furnace vent elbow to position desired, re--install screws. The factory--supplied vent elbow does NOT count as part of the number of vent connector elbows.
The vent connector can exit the door through one of 5 locations on the door.
1. Attach the single wall vent connector to the furnace vent elbow, and fasten the vent connector to the vent elbow with at least two field--supplied, corrosion--resistant, sheet metal screws located 180_ apart.
NOTE: An accessory flue extension KGAFE0112UPH is available to extend from the furnace elbow to outside the furnace casing. If flue extension is used, fasten the flue extension to the vent elbow with at least two field--supplied, corrosion--resistant, sheet metal screws located 180_ apart. Fasten the vent connector
A04127
to the flue extension with at least two field--supplied, corrosion resistant sheet metal screws located 180_ apart.
2. Vent the furnace with the appropriate connector as shown in Fig. 36--48.
3. Orient the door to determine the correct location of the door knockout to be removed.
4. Remove the correct U--shaped knockout in door.
NOTE: A number of techniques can be used to remove these knockouts as seen in Fig. 49 through 53. The knockout in the bottom of the door is unique due to its flanging and is more easily removed by first cutting the two tie points at the edge of the door, using aviation--type tin snips. (See Fig. 49.) A sharp blow to the rounded end of the knockout (See Fig. 50.) will separate more tie points and allow the knockout to be pulled loose. (See Fig. 51.) Remove all burrs any sharp edges.
For the rectangular J--box knockout, use tin snips along the door edge and use a sharp blow with a hammer to remove the knockout. Remove any burrs and sharp edges.
For the knockouts in the other locations on the door (top and sides), tin snips can also be used along the door edges; however, the preferred method is to use a hammer and screwdriver to strike a sharp blow (See Fig. 52.) directly to the knockout tie points or use a hammer in the upper left corner of the desired knockout. (See Fig. 53.) Remove any burrs and sharp edges.
NOTE: If a knockout does not come out after two sharp blows, pull and snip as needed to remove the knockout. Additional blows may cause damage to the door.
33
Page 34
312A
Fig. 50 -- Rounded End of Knockout
A04128
A04130
Fig. 52 -- Hammer and Screwdriver Used for Knockout
A04131
Fig. 53 -- Remove Knockout with Hammer
!
CAUTION
BURN HAZARD
Failure to follow this caution may cause personal injury.
Hot vent pipe is within reach of small children when installed in downflow position.
See the following instruction.
Fig. 51 -- Knockout Pulled Loose
A04129
An accessory Vent Guard Kit, KGAVG0101DFG is REQUIRED for downflow applications for use where the vent exits through the lower portion of the furnace casing door. Refer to the Vent Guard Kit Instructions for complete details.
The horizontal portion of the venting system shall slope upwards not less than 1/4--in. per linear ft (21 mm/m) from the furnace to the vent and shall be rigidly supported every 5 ft or less with metal hangers or straps to ensure there is no movement after installation.
SIDEWALL VENTING
This furnace is not approved for direct sidewall horizontal venting.
In the U.S.: Per section 10.3.4 of the NFGC, any listed mechanical venter may be used, when approved by the authority having jurisdiction.
34
Page 35
In Canada: Per section 8.24.2 of the CAN/CSA--B149.1--05, any listed mechanical venter may be used, when approved by the authority having jurisdiction.
Select the listed mechanical venter to match the Btuh input of the furnace being vented. Follow all manufacturers installation requirements for venting and termination included with the listed mechanical venter.
START--UP, ADJUSTMENT, AND SAFETY
CHECK
Step 1 — General
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
This furnace is equipped with manual reset limit switches in the gas control area. The switches open and shut off power to the gas valve if a flame roll--out or overheating condition occurs in the gas control area. DO NOT bypass the switches. Correct problem before resetting the switches.
1. Maintain 115--v wiring and ground. Improper polarity will result in rapid flashing LED and no furnace operation.
2. Make thermostat wire connections at the 24--v terminal block on the furnace control. Failure to make proper connections will result in improper operation. (See Fig.
24.)
3. Gas supply pressure to the furnace must be greater than
4.5--in. wc (0.16 psig ) but not exceed 14--in. wc (0.5 psig).
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.
4. Check all manual--reset switches for continuity.
5. Install blower compartment door. Door must be in place to operate furnace.
6. Setup switch descriptions The 2 stage furnace has DIP switches used to select thermostat staging and blower off delay timings. For switch locations on Furnace control board, See Fig. 34 and 58.
7. Setup switch descriptions -- See Table 10.
Step 2 — Start--Up Procedures
1. Purge gas lines after all connections have been made.
2. Check gas lines for leaks.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, or death. Blower access door switch opens 115--v power to control. No component operation can occur unless switch is closed. Caution must be taken when manually closing this switch for service purposes.
3. To Begin Component Self--Test: Remove blower access door. Disconnect the thermostat R lead from furnace control board. Manually close blower door switch. Short (jumper) the COM--24v terminal on control to the TEST/TWIN 3/16--inch quick--connect terminal on control until the LED goes out (approximately 2 sec). Gas valve and humidifier will not be turned on. Remove jumper from terminals. (See Fig. 34 and Table
10.)
NOTE: The furnace control allows all components, except the gas valve, to be run for short period of time. This feature helps diagnose a system problem in case of a component failure. Component test feature will not operate if any thermostat signal is present at the control.
Refer to service label attached to furnace or See Fig. 57.
Component test sequence is as follows:
a. LED will display previous status code 4 times.
b. Inducer motor starts on high--speed and continues to run
until Step g of component test sequence.
c. Hot surface igniter is energized for 15 sec., then off.
d. Blower motor operates on LO--HEAT speed for 10 sec.
e. Blower motor operates on HI--HEAT speed for 10 sec.
f. Blower motor operates on COOL speed for 10 sec. g. Inducer motor goesto low--speed for 10 sec., then stops.
h. Reconnect R lead to furnace control board, remove tape
from blower door switch and re--install blower door.
4. Operate furnace per instruction on inner door.
5. Verify furnace shut down by lowering thermostat setting below room temperature.
6. Verify furnace restarts by raising thermostat setting above room temperature.
312A
!
WARNING
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could cause personal injury, death and/or property damage.
Never purge a gas line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for the purpose of checking leakage. Use a soap--and--water solution to check for leakage.
35
Page 36
Table 10 – 2--Stage Furnace Setup Switch Description
SETUP
SWITCH NO.
S W --- 1 Adaptive Heat Mode OFF
S W --- 2 Blower OFF delay ON or OFF
S W --- 3 Blower OFF delay ON or OFF
SWITCH
NAME
Step 3 — Adjustments
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in injury, death and/or property damage.
312A
DO NOT bottom out gas valve regulator adjusting screw. This can result in unregulated manifold pressure and result in excess over--fire and heat exchanger failures.
!
CAUTION
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace life.
DO NOT re--drill orifices. Improper drilling (burrs, out--of round holes, etc.) can cause excessive burner noise and misdirection of burner flames. This can result in flame impingement of heat exchangers, causing failures. (See Fig.
50.)
Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft Furnace input rate must be within +/--2% of furnace rating plate input. For altitudes above 5500 ft, a field--supplied high altitude pressure switch is required.
1. Determine the correct gas input rate.
In the U.S.:
The input rating for altitudes above 2,000 ft must be re­duced by 4% for each 1,000 ft above sea level. For installations below 2000 ft, refer to the unit rating plate. For installations above 2000 ft, multiply the input on the rating plate by the derate multiplier in Table 11 for the cor­rect input rate.
EXAMPLE: 88,000 BTUH INPUT FURNACE INSTALLED AT 4300 FT
Derate Furnace Input Rate
Furnace Input Rate X Multiplier = at Installation
at Sea Level Factor Altitude
88,000 X 0.90 = 79,200
In Canada: The input rating must be reduced by 10% for altitudes of 2,000 ft to 4,500 ft above sea level by an authorized Gas Conversion Station or Dealer. To determine correct input rate for altitude, see example and use 0.90 as derate multiplier factor.
2. Determine the correct orifice and manifold pressure adjustment. All models in all positions except Low NOx
NORMAL
POSITION
DESCRIPTION
When OFF, allows 2- -- stage operation with a single stage thermostat.
Turn ON when using 2 stage thermostat to allow Low Heat opera ---
tion when R to W/W1 closes and High Heat operation when R to
Control blower OFF delay time. Used in conjunction with SW---3.
Control blower OFF delay time. Used in conjunction with SW---2.
OF USE
W/W1 and W2 close.
See Table 14.
See Table 14.
models in downflow and horizontal positions use Table 15 (22,000 BTUH per burner).
Table 11 – Altitude Derate Multiplier for U.S.A.
ALTITUDE
(FT)
0–2000 0 1.00 2001–3000 8–12 0.90 3001–4000 12–16 0.86 4001–5000 16–20 0.82 5001–6000 20–24 0.78 6001–7000 24–28 0.74 7001–8000 28–32 0.70 8001–9000 32–36 0.66
9001–10,000 36–40 0.62
* Derate multiplier factors are based on midpoint altitude for altitude range.
%
OF DERATE
DERATE MULTIPLIER
FACTOR*
Low NOx models in downflow or horizontal positions MUST use Table 16 (21,000 BTUH per burner). See input listed on rating plate.
a. Obtain average yearly gas heat value (at installed altitude)
from local gas supplier.
b. Obtain average yearly gas specific gravity from local gas
supplier.
c. Find installation altitude in Table 15 or 16.
d. Find closest natural gas heat value and specific gravity
in Table 15 or 16
e. Follow heat value and specific gravity lines to point of
intersection to find orifice size and low--and high--heat manifold pressure settings for proper operation.
f. Check and verify burner orifice size in furnace. NEVER
ASSUME ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
g. Replace orifice with correct size, if required by Table 15
or 16. Use only factory--supplied orifices. See EXAMPLE 2.
EXAMPLE 2: (0--2000 ft altitude)
For 22,000 Btuh per burner application, use Table 15.
Heating value = 1000 Btuh/cu ft
Specific gravity = 0.62
Therefore: Orifice No. 43*
Manifold pressure: 3.7--in. wc for high--heat
1.6--in. wc for low--heat
* Furnace is shipped with No. 43 orifices. In this example
all main burner orifices are the correct size and do not need
to be changed to obtain proper input rate.
3. Adjust manifold pressure to obtain low fire input rate. (See Fig. 54.)
36
Page 37
a. Turn gas valve ON/OFF switch to OFF.
b. Remove manifold pressure tap plug from gas valve.
c. Connect a water column manometer or similar device to
manifold pressure tap.
d. Turn gas valve ON/OFF switch to ON.
e. Move setup switch LHT (SW--1) on furnace control to
ON position to lock furnace in low--heat operation. (See Fig. 34 and Table 10.)
f. Manually close blower door switch.
g. Jumper R and W/W1 thermostat connections on control
to start furnace. (See Fig. 34.)
h. Remove regulator adjustment cap from low--heat gas
valve pressure regulators. (See Fig. 54.) Turn low--heat adjusting screw (3/16 in. or smaller flat tipped screwdriver) counterclockwise (out) to decrease input rate or clockwise (in) to increase input rate.
c. Measure time (in sec) for gas meter to complete 1
revolution and note reading. The 2 or 5 cubic feet dial provides a more accurate measurement of gas flow.
d. Refer to Table 12 for cubic ft of gas per hr.
e. Multiply gas rate cu ft/hr by heating value (Btuh/cu ft)
to obtain input. If clocked rate does not match required input from Step 1, increase manifold pressure to increase input or decrease manifold pressure to decrease input. Repeat steps b through e until correct low heat input is achieved. Re--install low--heat regulator seal cap on gas valve.
5. Set low--heat temperature rise. The furnace must operate within the temperature rise ranges specified on the furnace rating plate. Do not exceed temperature rise ranges specified on unit rating plate for high--and low--heat. Determine the temperature rise as follows:
NOTE: Blower access door must be installed when taking temperature rise reading. Leaving blower access door off will result in incorrect temperature measurements.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect 115--v electrical power before changing speed tap.
312A
A06667
Fig. 54 -- Redundant Automatic Gas Control Valve
NOTE: DO NOT set low--heat manifold pressure less than
1.4--in wc or more than 1.7--in. wc for natural gas. If manifold pressure is outside this range, change main burner orifices.
i. Install low--heat regulator adjustment cap.
j. Leave manometer or similar device connected and
proceed to Step 4.
NOTE: If orifice hole appears damaged or it is suspected to have been re--drilled, check orifice hole with a numbered drill bit of correct size. Never re--drill an orifice. A burr--free and squarely aligned orifice hole is essential for proper flame characteristics.
4. Verify natural gas low--heat input rate by clocking meter.
NOTE: Gas valve regulator adjustment caps must be in place for proper input to be clocked.
a. Turn off all other gas appliances and pilots served by the
meter.
b. Run for 3 minutes in low--heat operation.
BURNER
ORIFICE
Fig. 55 -- Orifice Hole
a. Verify unit is running in low heat per Step 4. Place
thermometers in return and supply ducts as close to furnace as possible. Be sure thermometers do not see radiant heat from heat exchangers. Radiant heat affects temperature rise readings. This practice is particularly important with straight--run ducts.
b. When thermometer readings stabilize, subtract return--air
temperaturefrom supply--airtemperatureto determineair temperature rise.
NOTE: If the temperature rise is outside this range, first check:
(1.) Gas input for low heat operation. (2.) Derate for altitude if applicable.
(3.) Return and supply ducts for excessive restrictions
causing static pressures greater than 0.50--in. wc.
37
A93059
Page 38
Table 12 – Gas Rate (cu ft/hr)
312A
SECONDS
FOR
REVOLUTION
1
10 360 720 1800 50 72 144 360 11 327 655 1636 51 71 141 355 12 300 600 1500 52 69 138 346 13 277 555 1385 53 68 136 340 14 257 514 1286 54 67 133 333 15 240 480 1200 55 65 131 327 16 225 450 1125 56 64 129 321 17 212 424 1059 57 63 126 316 18 200 400 1000 58 62 124 310 19 189 379 947 59 61 122 305 20 180 360 900 60 60 120 300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231 30 120 240 600 80 45 90 225 31 116 232 581 82 44 88 220 32 113 225 563 84 43 86 214 33 109 218 545 86 42 84 209 34 106 212 529 88 41 82 205 35 103 206 514 90 40 80 200 36 100 200 500 92 39 78 196 37 97 195 486 94 38 76 192 38 95 189 474 96 38 75 188 39 92 185 462 98 37 74 184 40 90 180 450 100 36 72 180 41 88 176 439 102 35 71 178 42 86 172 429 104 35 69 173 43 84 167 419 106 34 68 170 44 82 164 409 108 33 67 167 45 80 160 400 110 33 65 164 46 78 157 391 112 32 64 161 47 76 153 383 116 31 62 155 48 75 150 375 120 30 60 150 49 73 147 367
SIZE OF TEST DIAL
1 CU FT 2 CU FT 5 CU FT 1 CU FT 2 CU FT 5 CU FT
SECONDS
FOR
REVOLUTION
1
SIZE OF TEST DIAL
c. Adjust air temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise. Decrease blower speed to increase temperature rise. For low heat, speed selection can be low (factory setting), med--low, or med (5--speed blowers only).
d. Remove thermostat jumpers and release Blower Access
Door Switch.
e. To change motor speed selection for low heat, remove
blower motor lead from control LO--HEAT terminal. (See Fig. 34.) Select desired blower motor speed lead from 1 of the other terminals and relocate it to the LO--HEAT terminal. (See Table 13 for lead color identification). Reconnect original lead to SPARE terminal.
f. Repeat steps a through e.
!
CAUTION
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace life.
Recheck temperature rise. It must be within limits specified on the rating plate. Recommended operation is at the midpoint of rise range or slightly above.
g. When correct low heat input rate and temperature rise is
achieved, proceed to Step 6.
6. Adjust Manifold Pressure to Obtain High Heat Rate
a. Remove high fire regulator adjustment cap from gas
valve pressure regulator.
b. Manually close blower access door switch.
c. Jumper R, W/W1 and W2 thermostat connections on
control to run furnace in high heat. (See Fig. 34.)
d. d. Turn high--heat adjustingscrew (3/16 in. orsmallerflat
tipped screwdriver) counterclockwise (out) to decrease input rate or clockwise (in) to increase rate.
e. Re--install high--fire adjustment caps.
f. Leave manifold or similar device connected and proceed
to Step 7.
NOTE: DO NOT set high--heat manifold pressure less than
3.2--in. wc or more than 3.8--in. wc for natural gas. If manifold pressure is outside this range, change main burner orifices.
7. Verify natural gas high heat input rate by clocking meter.
NOTE: Gas valve regulator adjustment caps must be in place for proper input to be clocked.
a. Turn off all other gas appliances and pilots served by the
meter.
b. Run for 3 minutes in high--heat operation.
c. Measure time (in sec) for gas meter to complete 1
revolution and note reading.
d. Refer to Table 12 for cubic ft of gas per hr.
e. Multiply gas rate cu ft/hr by heating value (Btuh/cu ft)
to obtain input.
NOTE: Using the 2 cu. ft or 5 cu. ft gas meter dial provides greater accuracy in verifying gas input rate.
38
Page 39
If clocked rate does not match required input from Step 1, increase manifold pressure to increase input or decrease manifold pressure to decrease input. Repeat steps b through e until correct high heat input is achieved. Re--install high--heat regulator seal cap on gas valve.
8. Set high heat temperature rise. Jumper R to W/W1 and W2 to check high--gas--heat temperature rise. Do not exceed temperature rise ranges specified on furnace rating plate for high heat. The furnace must operate within the temperature rise ranges specified on the furnace rating plate. Determine the air temperature rise as follows:
NOTE: Blower access door must be installed when taking temperature rise reading. Leaving blower access door off will result in incorrect temperature measurements.
a. Verify the furnace is operating in high heat per Step 6.
Place thermometers in return and supply ducts as close to furnace as possible. Be sure thermometers do not see radiant heat from heat exchangers. Radiant heat affects temperature rise readings. This practice is particularly important with straight--run ducts.
b. When thermometer readings stabilize, subtract return--air
temperaturefrom supply--airtemperatureto determineair temperature rise.
NOTE: If the temperature rise is outside this range, first check:
(1.) Gas input for low--and high--heat operation.
(2.) Derate for altitude if applicable.
(3.) Return and supply ducts for excessive restrictions
causing static pressures greater than 0.50--in. wc.
(4.) Dirty filter.
c. Adjust air temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise. Decrease blower speed to increase temperature rise. For high heat, speed selection can be med--high, med (5--speed blowers only), or med--low (factory setting).
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect 115--v electrical power before changing speed tap.
d. To change motor speed selection for high heat, remove
blowermotor leadfrom controlHI--HEAT terminal.(See Fig. 34.) Select desired blower motor speed lead from 1 of the other terminals and relocate it to the HI--HEAT terminal. DO NOT use the low--heat tap that was already set. (See Table 13 for lead color identification). Reconnect original lead to SPARE terminal.
e. Repeat steps a thru e.
f. When correct high heat input rate and temperature rise is
achieved, turn gas valve ON/OFF switch to OFF. g. Release Blower Access Door switch.
h. Remove manometer or similar device from gas valve.
i. Re--install manifold pressure tap plug in gas valve (use
3/16 in. head allen wrench). (See Fig 54.)
!
WARNING
FIRE HAZARD
Failure to reinstall manifold pressure tap plug in gas valve could result in personal injury, property damage or death.
Reinstall manifold pressure tap plug in gas valve to prevent gas leak.
j. Remove thermostat jumper wire from furnace control
board.
k. Turn LHT switch OFF.
l. Turn gas valve ON/OFF switch to ON.
m. Proceed to Step 9, “Set Blower Off Delay” before
installing blower access door.
!
CAUTION
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace life.
Recheck temperature rise. It must be within limits specified on the rating plate. Recommended operation is at the midpoint of rise range or slightly above.
9. Set Blower Off Delay
a. Remove Blower Access Door if installed.
b. Turn Dip switch 2 and 3 ON or OFF for desired blower
off delay. (See Table 14 and Fig 34.)
10. Set thermostat heat anticipator.
a. Mechanical thermostat -- Set thermostat heat anticapator
to match the amp. draw of the electrical components in the R--W/W1 circuit. Accurate amp. draw readings can be obtainedatthewires normallyconnectedto thermostat subbase terminals, R and W. The thermostat anticipator should NOT be in the circuit while measuring current.
(1.) Set LHT switch on furnace control board to ON.
(2.) Remove thermostat from sub--base or from wall.
(3.) Connect an amp. meter as shown in Fig. 56 across
the R and W subbase terminals or R and W wires at wall.
(4.) Record amp. draw across terminals when furnace is
in low heat and after blower starts.
(5.) Set heat anticipator on thermostat per thermostat
instructions and install on subbase or wall.
(6.) Turn LHT switch OFF. (7.) Install blower access door.
b. Electronic thermostat: Set cycle rate for 3 cycles per hr.
11. Set airflow CFM for cooling Select the desired blower motor speed lead for cooling airflow. See Table 5--Air Delivery--CFM (With Filter). See Table 13 for lead color identification.
Table 13 – Speed Selection
COLOR SPEED AS SHIPPED
White Common BLW Black High COOL
Yellow M e d --- H ig h SPARE
Orange† Med SPARE
Blue M e d --- L o w HI---HEAT
* Continuous---blower speed ---as shipped default { Not all models equipped with 5 speed motors
39
Red Low* LO HEAT
312A
Page 40
Table 14 – 2--Stage Furnace Blower OFF delay Setup Switch
312A
DESIRED HEATING MODE
BLOWER OFF DELAY (SEC.)
90 OFF OFF 120 OFF ON 150 ON OFF 180 ON ON
EXAMPLE:
THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED (ANITICIPATOR, CLOCK, ETC., MUST BE OUT OF CIRCUIT.)
R Y W G
10 TURNS
FROM UNIT 24-V CONTROL TERMINALS
5.0 AMPS ON AMMETER 10 TURNS AROUND JAWS
SETUP SWITCH
S W --- 2
HOOK-AROUND AMMETER
0.5 AMPS FOR THERMOSTAT
=
ANTICIPATOR SETTING
SETUP SWITCH
S W --- 3
Fig. 56 -- Amp. Draw Check with Ammeter
Step 4 — Check Safety Controls
The flame sensor, gas valve, and pressure switch were all checked in the Start--up procedure section as part of normal operation.
1. Check Main Limit Switch(es) This control shuts off combustion system and energizes air--circulating blower motor, if furnace overheats. By using this method to check limit control, it can be established that limit is functioning properly and will operate if there is a restricted return--air supply or motor failure. If limit control does not function during this test, cause must be determined and corrected.
a. Run furnace for at least 5 minutes.
b. Gradually block off return air with a piece of cardboard
or sheet metal until the limit trips.
c. Unblock return air to permit normal circulation.
d. Burners will re--light when furnace cools down.
2. Check draft safeguard switch. The purpose of this control is to cause the safe shutdown of the furnace during certain blocked vent conditions.
a. Verify vent pipe is cool to the touch.
b. Disconnect power to furnace and remove ventconnector
from furnace vent elbow.
c. Restore power to furnace and set room thermostat above
room temperature.
d. After normal start--up, allow furnace to operate for 2
minutes, then block vent elbow in furnace 80% of vent area with a piece of flat sheet metal.
e. Furnace should cycleoffwithin2 minutes.Ifgas does not
shut off within 2 minutes, determine reason draft
A96316
safeguard switch did not function properly and correct condition.
f. Remove blockage from furnace vent elbow.
g. Switch will auto--reset when it cools.
h. Re--install vent connector.
NOTE: Should switch remain open longer than 3 minutes, furnace control board will lockout the furnace for 3 hours. To reset furnace control board, turn thermostat below room temperature or from HEAT to OFF and turn 115--v power OFF, then back ON.
3. Check Pressure Switch(es) This control proves operation of the draft inducer blower.
a. Turn off 115--v power to furnace.
b. Disconnect inducer motor lead wires from wire harness.
c. Turn on 115--v power to furnace.
d. Set thermostat to “call for heat” and wait 1 minute. When
pressure switch is functioning properly, hot surface igniter should NOT glow and control diagnostic light flashes a status code 32. Ifhot surfaceigniter glowswhen inducer motor is disconnected, shut down furnace immediately.
e. Determine reason pressure switch did not function
properly and correct condition.
f. Turn off 115--v power to furnace.
g. Reconnect inducer motor wires, replace outer door, and
turn on 115--v power.
h. Blower will run for 90 seconds before beginning thecall
for heat again.
i. Furnace should ignite normally.
40
Page 41
Step 5 — Checklist
1. Put away tools and instruments. Clean up debris.
2. Verify that switches for LHT and OFF--DELAY are blower OFF--DELAY are selected as desired.
3. Verify that blower and burner access doors are properly installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturerfs instructions.
6. Review User’s Guide with owner.
7. Attach literature packet to
furnace.
312A
41
Page 42
Table 15 – Orifice Size and Manifold Pressure for Gas Input Rate
(Tabulated Data Based on 22,000 Btuh High--Heat/14,500 Btuh for Low--Heat per Burner, Derated 4% for Each 1000 Ft Above Sea
Level)
ALTITUDE RANGE
(FT)
U.S.A.
and
Canada
ALTITUDE RANGE
312A
U.S.A.
and
Canada
ALTITUDE RANGE
U.S.A.
Only
ALTITUDE RANGE
U.S.A.
Only
ALTITUDE RANGE
U.S.A.
Only
* Orifice numbers 43 are factory installed
0 to 2000
(FT)
U.S.A.
Altitudes
2001 to
3000 or
Canada
Altitudes
2001 to
4500
(FT)
3001 to
4000
(FT)
4001 to
5000
(FT)
5001 to
6000
AVG. GAS
HEAT VALUE
(BTUH/CU
FT)
900 42 3.5/1.5 42 3.6/1.6 42 3.7/1.6 41 3.5/1.5 925 42 3.3/1.4 42 3.4/1.5 42 3.5/1.5 42 3.7/1.6 950 43 3.8/1.7 42 3.3/1.4 42 3.4/1.5 42 3.5/1.5
975 43 3.6/1.6 43 3.8/1.6 42 3.2/1.4 42 3.3/1.4 1000 43 3.5/1.5 43 3.6/1.6 43 3.7/1.6 43 3.8/1.7 1025 43 3.3/1.4 43 3.4/1.5 43 3.5/1.5 43 3.6/1.6 1050 44 3.6/1.6 43 3.2/1.4 43 3.4/1.5 43 3.5/1.5 1075 44 3.4/1.5 44 3.5/1.5 43 3.2/1.4 43 3.3/1.4 1100 44 3.3/1.4 44 3.4/1.5 44 3.5/1.5 43 3.2/1.4
AVG. GAS
HEAT VALUE
(BTUH/CU
FT)
800 42 3.4/1.5 42 3.5/1.5 42 3.6/1.6 42 3.7/1.6
825 42 3.2/1.4 42 3.3/1.4 42 3.4/1.5 42 3.5/1.5
850 43 3.7/1.6 43 3.8/1.6 42 3.2/1.4 42 3.3/1.4
875 43 3.5/1.5 43 3.6/1.6 43 3.7/1.6 43 3.8/1.7
900 43 3.3/1.4 43 3.4/1.5 43 3.5/1.5 43 3.6/1.6
925 44 3.5/1.5 43 3.2/1.4 43 3.3/1.4 43 3.4/1.5
950 44 3.4/1.5 44 3.5/1.5 44 3.6/1.6 43 3.2/1.4
975 44 3.2/1.4 44 3.3/1.4 44 3.4/1.5 44 3.5/1.5 1000 45 3.7/1.6 45 3.8/1.7 44 3.2/1.4 44 3.4/1.5
AVG. GAS
HEAT VALUE
(BTUH/CU
FT)
775 42 3.2/1.4 42 3.3/1.4 42 3.4/1.5 42 3.5/1.5
800 43 3.6/1.6 43 3.8/1.6 42 3.2/1.4 42 3.3/1.4
825 43 3.4/1.5 43 3.5/1.5 43 3.7/1.6 43 3.8/1.6
850 43 3.2/1.4 43 3.3/1.4 43 3.4/1.5 43 3.6/1.5
875 44 3.5/1.5 44 3.6/1.6 43 3.3/1.4 43 3.4/1.5
900 44 3.3/1.4 44 3.4/1.5 44 3.5/1.5 43 3.2/1.4
925 45 3.8/1.6 44 3.2/1.4 44 3.3/1.5 44 3.4/1.5
950 46 3.8/1.6 45 3.7/1.6 45 3.8/1.7 44 3.3/1.4
AVG. GAS
HEAT VALUE
(BTUH/CU
FT)
750 43 3.6/1.6 43 3.8/1.6 42 3.2/1.4 42 3.3/1.4
775 43 3.4/1.5 43 3.5/1.5 43 3.6/1.6 43 3.8/1.6
800 43 3.2/1.4 43 3.3/1.4 43 3.4/1.5 43 3.5/1.5
825 44 3.4/1.5 44 3.6/1.5 43 3.2/1.4 43 3.3/1.4
850 44 3.2/1.4 44 3.4/1.5 44 3.5/1.5 44 3.6/1.6
875 45 3.7/1.6 45 3.8/1.7 44 3.3/1.4 44 3.4/1.5
900 46 3.7/1.6 46 3.8/1.7 45 3.7/1.6 44 3.2/1.4
925 46 3.5/1.5 46 3.6/1.6 46 3.7/1.6 46 3.8/1.7
AVG. GAS HEAT VALUE AT ALTITUDE
(BTUH/CU
FT)
725 43 3.4/1.5 43 3.5/1.5 43 3.6/1.6 43 3.7/1.6 750 43 3.2/1.4 43 3.3/1.4 43 3.4/1.5 43 3.5/1.5 775 44 3.4/1.5 44 3.5/1.5 43 3.2/1.4 43 3.3/1.4 800 44 3.2/1.4 44 3.3/1.4 44 3.4/1.5 44 3.5/1.5 825 46 3.8/1.7 45 3.8/1.6 44 3.2/1.4 44 3.3/1.4 850 46 3.6/1.6 46 3.7/1.6 46 3.8/1.7 45 3.8/1.6 875 47 3.8/1.7 46 3.5/1.5 46 3.6/1.6 46 3.7/1.6 900 47 3.6/1.6 47 3.8/1.6 46 3.4/1.5 46 3.5/1.5
0.58 0.60 0.62 0.64
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold Pressure
0.58 0.60 0.62 0.64 Manifold
Pressure
0.58 0.60 0.62 0.64 Manifold
Pressure
0.58 0.60 0.62 0.64 Manifold
Pressure
0.58 0.60 0.62 0.64
Manifold Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold Pressure
Manifold Pressure
Manifold Pressure
Manifold Pressure
Manifold Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold Pressure
Manifold Pressure
Manifold Pressure
Manifold Pressure
Manifold Pressure
42
Page 43
Table 15 -- Orifice Size and Manifold Pressure for Gas Input Rate (cont.)
(Tabulated Data Based on 22,000 Btuh High-- Heat/14,500 Btuh for Low--Heat per Burner, Derated 4% for Each 1000 Ft Above Sea
Level)
AVG. GAS
ALTITUDE RANGE
(FT)
U.S.A.
Only
ALTITUDE RANGE
U.S.A.
Only
ALTITUDE RANGE
U.S.A.
Only
ALTITUDE RANGE
U.S.A.
Only
* Orifice numbers 43 are factory installed
6001 to
7000
(FT)
7001 to
8000
(FT)
8001 to
9000
(FT)
9001 to
10,000
HEAT VALUE AT ALTITUDE
(BTUH/CU
FT)
675 43 3.4/1.5 43 3.5/1.5 43 3.6/1.6 43 3.7/1.6 700 44 3.6/1.6 43 3.3/1.4 43 3.4/1.5 43 3.5/1.5 725 44 3.4/1.5 44 3.5/1.5 44 3.6/1.6 43 3.2/1.4 750 45 3.8/1.7 44 3.3/1.4 44 3.4/1.5 44 3.5/1.5 775 46 3.7/1.6 45 3.7/1.6 45 3.8/1.7 44 3.2/1.4 800 46 3.5/1.5 46 3.6/1.6 46 3.8/1.6 45 3.7/1.6 825 47 3.7/1.6 46 3.4/1.5 46 3.5/1.5 46 3.6/1.6 850 47 3.5/1.5 47 3.6/1.6 47 3.8/1.6 46 3.4/1.5
AVG. GAS HEAT VALUE AT ALTITUDE
(BTUH/CU
FT)
650 44 3.6/1.6 43 3.2/1.4 43 3.4/1.5 43 3.5/1.5 675 44 3.3/1.5 44 3.5/1.5 44 3.6/1.6 43 3.2/1.4 700 45 3.8/1.6 44 3.2/1.4 44 3.3/1.4 44 3.4/1.5 725 46 3.7/1.6 46 3.8/1.7 45 3.7/1.6 44 3.2/1.4 750 46 3.4/1.5 46 3.6/1.5 46 3.7/1.6 46 3.8/1.6 775 47 3.6/1.6 47 3.8/1.6 46 3.4/1.5 46 3.6/1.5 800 47 3.4/1.5 47 3.5/1.5 47 3.7/1.6 47 3.8/1.6 825 48 3.7/1.6 48 3.8/1.6 47 3.4/1.5 47 3.6/1.5
AVG. GAS HEAT VALUE AT ALTITUDE
(BTUH/CU
FT)
625 44 3.3/1.5 44 3.5/1.5 44 3.6/1.6 43 3.2/1.4 650 45 3.7/1.6 44 3.2/1.4 44 3.3/1.4 44 3.4/1.5 675 46 3.6/1.6 46 3.8/1.6 45 3.7/1.6 45 3.8/1.7 700 47 3.8/1.7 46 3.5/1.5 46 3.6/1.6 46 3.7/1.6 725 47 3.6/1.6 47 3.7/1.6 47 3.8/1.7 46 3.5/1.5 750 48 3.8/1.7 47 3.5/1.5 47 3.6/1.6 47 3.7/1.6 775 48 3.6/1.5 48 3.7/1.6 48 3.8/1.7 47 3.5/1.5
AVG. GAS HEAT VALUE AT ALTITUDE
(BTUH/CU
FT)
600 45 3.7/1.6 45 3.8/1.7 44 3.3/1.4 44 3.4/1.5 625 46 3.6/1.6 46 3.7/1.6 46 3.8/1.7 45 3.8/1.6 650 47 3.8/1.6 46 3.4/1.5 46 3.6/1.5 46 3.7/1.6 675 47 3.5/1.5 47 3.6/1.6 47 3.7/1.6 46 3.4/1.5 700 48 3.7/1.6 48 3.8/1.7 47 3.5/1.5 47 3.6/1.6 725 48 3.5/1.5 48 3.6/1.6 48 3.7/1.6 48 3.8/1.7
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold Pressure
0.58 0.60 0.62 0.64
Manifold Pressure
0.58 0.60 0.62 0.64
Manifold Pressure
0.58 0.60 0.62 0.64
Manifold Pressure
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold Pressure
Manifold Pressure
Manifold Pressure
Manifold Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold Pressure
Manifold Pressure
Manifold Pressure
Manifold Pressure
312A
43
Page 44
Table 16 – Orifice Size and Manifold Pressure for Gas Input Rate
(Tabulated Data Based on 21,000 Btuh High--Heat/14,500 Btuh for Low--Heat Per Burner, Derated 4% for Each 1000 Ft Above Sea
level)
ALTITUDE RANGE
(FT)
U.S.A.
and
Canada
ALTITUDE RANGE
312A
U.S.A.
and
Canada
ALTITUDE RANGE
U.S.A.
Only
ALTITUDE RANGE
U.S.A.
Only
ALTITUDE RANGE
U.S.A.
Only
* Orifice numbers 43 are factory installed
0to
2000
(FT)
U.S.A.
Altitudes
2001 to 3000 or
Canada
Altitudes
2001 to
4500
(FT)
3001 to
4000
(FT)
4001 to
5000
(FT)
5001 to
6000
AVG. GAS
HEAT VALUE
(BTUH/CU F T)
900 42 3.2/1.5 42 3.3/1.6 42 3.4/1.6 42 3.5/1.7 925 43 3.7/1.8 43 3.8/1.8 42 3.2/1.5 42 3.3/1.6 950 43 3.5/1.7 43 3.6/1.7 43 3.7/1.8 43 3.8/1.8
975 43 3.3/1.6 43 3.4/1.6 43 3.5/1.7 43 3.7/1.7 1000 44 3.6/1.7 43 3.3/1.6 43 3.4/1.6 43 3.5/1.7 1025 44 3.4/1.6 44 3.6/1.7 43 3.2/1.5 43 3.3/1.6 1050 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5 1075 45 3.8/1.8 44 3.2/1.5 44 3.3/1.6 44 3.4/1.6 1100 46 3.8/1.8 45 3.7/1.8 44 3.2/1.5 44 3.3/1.6
AVG. GAS
HEAT VALUE
(BTUH/CU F T)
800 43 3.8/1.8 42 3.2/1.5 42 3.3/1.6 42 3.4/1.6
825 43 3.5/1.7 43 3.7/1.7 43 3.8/1.8 42 3.2/1.5
850 43 3.3/1.6 43 3.5/1.6 43 3.6/1.7 43 3.7/1.8
875 43 3.2/1.5 43 3.3/1.6 43 3.4/1.6 43 3.5/1.7
900 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5 43 3.3/1.6
925 44 3.2/1.5 44 3.3/1.6 44 3.5/1.6 44 3.6/1.7
950 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6
975 46 3.7/1.8 46 3.8/1.8 45 3.8/1.8 44 3.2/1.5 1000 46 3.5/1.7 46 3.6/1.7 46 3.8/1.8 45 3.7/1.8
AVG. GAS
HEAT VALUE
(BTUH/CU F T)
775 43 3.5/1.7 43 3.7/1.7 43 3.8/1.8 42 3.2/1.5
800 43 3.3/1.6 43 3.4/1.6 43 3.5/1.7 43 3.7/1.7
825 44 3.6/1.7 43 3.2/1.5 43 3.3/1.6 43 3.4/1.6
850 44 3.4/1.6 44 3.5/1.7 44 3.6/1.7 43 3.2/1.5
875 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7
900 46 3.8/1.8 45 3.8/1.8 44 3.2/1.5 44 3.3/1.6
925 46 3.6/1.7 46 3.7/1.8 45 3.7/1.8 45 3.8/1.8
950 46 3.4/1.6 46 3.5/1.7 46 3.7/1.7 46 3.8/1.8
AVG. GAS
HEAT VALUE
(BTUH/CU F T)
750 43 3.3/1.6 43 3.4/1.6 43 3.5/1.7 43 3.6/1.7
775 44 3.6/1.7 43 3.2/1.5 43 3.3/1.6 43 3.4/1.6
800 44 3.3/1.6 44 3.4/1.6 44 3.6/1.7 43 3.2/1.5
825 45 3.8/1.8 44 3.2/1.5 44 3.4/1.6 44 3.5/1.6
850 46 3.8/1.8 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6
875 46 3.5/1.7 46 3.7/1.7 46 3.8/1.8 45 3.7/1.8
900 47 3.8/1.8 46 3.5/1.7 46 3.6/1.7 46 3.7/1.8
925 47 3.6/1.7 47 3.7/1.8 47 3.8/1.8 46 3.5/1.7
AVG. GAS HEAT VALUE AT ALTITUDE
(BTUH/CU F T)
725 44 3.5/1.7 43 3.2/1.5 43 3.3/1.6 43 3.4/1.6 750 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5 775 45 3.7/1.8 44 3.2/1.5 44 3.3/1.6 44 3.4/1.6 800 46 3.7/1.8 46 3.8/1.8 45 3.8/1.8 44 3.2/1.5 825 46 3.5/1.7 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8 850 47 3.7/1.8 47 3.8/1.8 46 3.5/1.7 46 3.6/1.7 875 47 3.5/1.7 47 3.6/1.7 47 3.7/1.8 46 3.4/1.6 900 48 3.8/1.8 47 3.4/1.6 47 3.5/1.7 47 3.7/1.7
0.58 0.60 0.62 0.64
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold Pressure
0.58 0.60 0.62 0.64 Manifold
Pressure
0.58 0.60 0.62 0.64 Manifold
Pressure
0.58 0.60 0.62 0.64 Manifold
Pressure
0.58 0.60 0.62 0.64 Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
Manifold Pressure
Manifold Pressure
Manifold Pressure
Manifold Pressure
Manifold Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold Pressure
Manifold Pressure
Manifold Pressure
Manifold Pressure
Manifold Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold Pressure
Manifold Pressure
Manifold Pressure
Manifold Pressure
44
Page 45
Table 16 -- Orifice Size and Manifold Pressure for Gas Input Rate (cont.)
(Tabulated Data Based on 21,000 Btuh High--Heat/14,500 Btuh for Low--Heat Per Burner, Derated 4% for Each 1000 Ft Above
Sea level)
AVG. GAS
ALTITUDE RANGE
(FT)
U.S.A.
Only
ALTITUDE RANGE
U.S.A.
Only
ALTITUDE RANGE
U.S.A.
Only
ALTITUDE RANGE
U.S.A.
Only
* Orifice numbers 43 are factory installed
6001 to
7000
(FT)
7001 to
8000
(FT)
8001 to
9000
(FT)
9001 to
10,000
HEAT VALUE AT ALTITUDE
(BTUH/CU F T)
675 44 3.5/1.7 43 3.2/1.5 43 3.3/1.6 43 3.4/1.6 700 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5 725 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6 750 46 3.6/1.7 46 3.8/1.8 45 3.7/1.8 45 3.8/1.8 775 46 3.4/1.6 46 3.5/1.7 46 3.6/1.7 46 3.8/1.8 800 47 3.6/1.7 47 3.8/1.8 46 3.4/1.6 46 3.5/1.7 825 47 3.4/1.6 47 3.5/1.7 47 3.6/1.7 47 3.8/1.8 850 48 3.7/1.7 48 3.8/1.8 47 3.4/1.6 47 3.5/1.7
AVG. GAS
HEAT VALUE
AT ALTITUDE )
650 44 3.3/1.6 44 3.4/1.6 44 3.5/1.7 43 3.2/1.5 675 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6 700 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8 45 3.8/1.8 725 47 3.8/1.8 46 3.5/1.7 46 3.6/1.7 46 3.7/1.8 750 47 3.5/1.7 47 3.7/1.8 47 3.8/1.8 46 3.5/1.6 775 48 3.8/1.8 47 3.4/1.6 47 3.6/1.7 47 3.7/1.7 800 48 3.6/1.7 48 3.7/1.8 48 3.8/1.8 47 3.4/1.6 825 48 3.3/1.6 48 3.5/1.6 48 3.6/1.7 48 3.7/1.8
625 45 3.7/1.8 45 3.8/1.8 44 3.3/1.6 44 3.4/1.6 650 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8 45 3.8/1.8 675 47 3.8/1.8 46 3.4/1.6 46 3.5/1.7 46 3.7/1.7 700 47 3.5/1.7 47 3.6/1.7 47 3.7/1.8 46 3.4/1.6 725 48 3.7/1.8 48 3.8/1.8 47 3.5/1.7 47 3.6/1.7 750 48 3.5/1.7 48 3.6/1.7 48 3.7/1.8 48 3.8/1.8 775 49 3.8/1.8 48 3.4/1.6 48 3.5/1.7 48 3.6/1.7
AVG GAS HEAT VALUE AT ALTITUDE
(BTU/CU FT)
600 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8 45 3.7/1.8 625 47 3.7/1.8 47 3.8/1.8 46 3.5/1.7 46 3.6/1.7 650 47 3.4/1.6 47 3.6/1.7 47 3.7/1.8 47 3.8/1.8 675 48 3.6/1.7 48 3.8/1.8 47 3.4/1.6 47 3.5/1.7 700 48 3.4/1.6 48 3.5/1.7 48 3.6/1.7 48 3.7/1.8 725 49 3.7/1.8 49 3.8/1.8 48 3.4/1.6 48 3.5/1.7
0.58 0.60 0.62 0.64
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold Pressure
0.58 0.60 0.62 0.64 Manifold
Pressure
0.58 0.60 0.62 0.64 Manifold
Pressure
0.58 0.60 0.62 0.64 Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
Manifold Pressure
Manifold Pressure
Manifold Pressure
Manifold Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold Pressure
Manifold Pressure
Manifold Pressure
Manifold Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold Pressure
Manifold Pressure
Manifold Pressure
Manifold Pressure
SERVICE AND MAINTENANCE
!
PROCEDURES
WARNING
312A
!
WARNING
FIRE, PERSONAL INJURY AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
The ability to properly perform maintenance on this equipment requires certain knowledge, mechanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recommended in the User’s Manual.
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death, or property damage.
Before servicing, disconnect all electrical power to furnace. Verify proper operation after servicing.
45
Page 46
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in improper unit operation or failure of unit components.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Step 1 — Introduction
GENERAL
These instructions are written as if the furnace is installed in an upflow application. An upflow furnace application is where the blower is located below the combustion and controls section of the furnace, and conditioned air is discharged upward. Since this furnace can be installed in any of the 4 positions shown in Fig. 4, you must revise your orientation to component location
312A
accordingly.
ELECTRICAL CONTROLS AND
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
There may be more than one electrical supply to the furnace. Check accessories and cooling unit for additional electrical supplies that must be shut off during furnace servicing.
The electrical ground and polarity for 115--v wiring must be properly maintained. Refer to Fig. 24 for field wiring information and to Fig. 58 for furnace wiring information.
NOTE: If the polarity is not correct, the STATUS LED on the control will flash rapidly and prevent the furnace from heating. The control system also requires an earth ground for proper operation of the control and flame--sensing electrode.
The 24--v circuit contains an automotive--type, 3--amp. fuse located on the control. (See Fig. 32.) Any shorts of the 24--v wiring during installation, service, or maintenance will cause this fuse to blow. If fuse replacement is required, use ONLY a 3--amp. fuse. The control LED will display status code 24 when fuse needs to be replaced.
Proper instrumentation is required to service electrical controls. The control in this furnace is equipped with a Status Code LED (Light--Emitting Diode) to aid in installation, servicing, and troubleshooting. It can be viewed through the sight glass in blower access door. The furnace control LED is either ON continuously, rapid flashing, or a code composed of 2 digits. The first digit is the number of short flashes, the second digit is the number of long flashes.
For an explanation of status codes, refer to service label located on blower access door or Fig. 57, and the troubleshooting guide which can be obtained from your distributor.
See Fig. 62 for a brief Troubleshooting guide.
For Controls with an Amber
The stored status codes will NOT be erased from the control memory, if 115-- or 24--v power is interrupted. The control will store up to five (5) status codes.
1. To retrieve status codes, proceed with the following:
NOTE: NO thermostat signal may be present at control, and all blower--OFF delays must be completed.
WIRING
LED
a. Leave 115--v power to furnace turned on.
b. Remove outer access door.
c. Look into blower access door sight glass for currentLED
status. Removing blower access door will open blower access doorswitch and terminate 115--v power to control so that status code is not displayed.
d. BRIEFLY remove insulated terminal wire from the draft
safeguard (DSS) switch until LED goes out, then reconnect it.
NOTE: If wire to DSS is disconnected longer than 4 sec, main blower starts, and retrieval request is ignored.
2. When above items have been completed, the LED flashes status code 4 times. Record this status code for further troubleshooting. After the LED flashes status code four times, BRIEFLY remove wire again from DSS switch until LED goes out, then reconnect it to retrieve previous status code (if available). Repeat as needed for more previous status codes or until Code 11 appears.
Step 2 — Care and Maintenance
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Never store anything on, near, or in contact with the furnace, such as:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds, plastic or plastic containers, gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids.
3. Paint thinners and other painting compounds, paper bags, or other paper products. Explosure to these materials could lead to corrosion of the heat exchanger.
For continuing high performance and to minimize possible furnace failure, periodic maintenance must be performed on this furnace. Consult your local dealer about proper frequency of maintenance and the availability of a maintenance contract.
!
WARNING
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
Turn off the gas and electrical supplies to the unit before performing any maintenance or service. Follow the operating instructions on the label attached to the furnace.
!
WARNING
CARBON MONOXIDE POISONING AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Never operate unit without a filter or with filter access door removed.
46
Page 47
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.
The minimum maintenance on this furnace is as follows:
1. Check and clean air filter each month or more frequently if required. Replace if torn.
2. Check blower motor and wheel for cleanliness each heating and cooling season. Clean as necessary.
3. Check electrical connections for tightness and controls for proper operation each heating season. Service as necessary.
4. Inspect burner compartment before each heating season for rust, corrosion, soot or excessive dust. If necessary, have furnace and burner serviced by a qualified service agency.
5. Inspect the vent pipe/vent system before each heating season for rust, corrosion, water leakage, sagging pipes or broken fittings. Have vent pipes/vent system serviced by a qualified service agency.
6. Inspect any accessories attached to the furnace such as a humidifier or electronic air cleaner. Perform any service or maintenance to the accessories as recommended in the accessory instructions.
If stat us code recall is needed, briefl y remove then reconnect one main limit wire to di splay last st ored status code. On RED LED boards do not remove power or blower door before init iating st atus code recall.
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WI TH THE FIRST DIGIT DETERMI NED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.
11 NO PR EVIOUS CODE - Stored status code is erased automatically af ter 72 hours.
On RED LED boards stored status codes can also be erased when power (115 VAC or 24 VAC) to control is interrupted.
12 BLOWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for the
selected blower off-delay time, if unit is powered up during a call for heat (R-W/W1 closed) or (R-W/W1) opens during blower on-delay.
13 LIMIT CIRCUIT LOCKOUT - Lockout occurs if a limit, dra ft safeguard, flame rollout,
or blocked vent switch (if used) is open longer than 3 minutes.
- Control will auto reset after three hours. - Refer to #33.
14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34. 21 GAS H EATING LOCKOUT - Control will NOT auto reset.
Check for: - Mis-wired gas v alve - Defective control (valve relay)
22 ABNORMA L FLAME-PROVING SIGNAL - Flame is proved while gas v alve is de-
energized. Inducer will run until fault is cleared. Check for:
- Leaky gas valve - Stuck-open gas valve
23 PRES SURE SWITCH DID NOT OPEN Check for: - Obstructed pressure tubing
24 SECO NDARY VOLTAGE FUSE IS OPEN Check for: - Short circuit in secondary
voltage (24VAC) wiring.
31 HIGH-H EAT PRESSURE SWITCH OR RELAY DID NOT CLOSE OR REOPENED
Control relay may be defective, ref er to status code #32
COMPONENT TEST
To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST/TWIN terminal to the "Com 24V" terminal. Status LED will flash last status code and then turn ON the inducer motor. The inducer motor will start in HIGH speed and remain on HIGH speed until the end of the test then shift to LOW speed for 7 to 15 seconds. The hot s urface igniter, blower motor LO HEAT speed, blower motor HI HEAT speed, and blower motor COOL speed will be turned ON for 10-15 seconds each. Gas Valve and Humidifier will not be turned on. When the blower is turned OFF the inducer will be switched to low-speed for 10 seconds.
LED CODE
CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2. CONTINUOUS ON - Control has 24VAC power. RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions.
- Pressure switch stuck closed
STATUS
32 LOW-HEAT PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than
five minutes, inducer shuts off for 15 minutes before retry. If opens during blower on-delay period, blower will come on for the selected blower off-delay. Check for:
- Excessive wind - Restricted vent - Defective inducer motor
- Proper vent sizing - Defective pressure switch - Low inducer voltage (115 VAC)
- Inadequate combustion air supply - Low inlet gas pressure (if LGPS u sed)
- Disconnected or obstructed pressure tubing
33 LIMIT CIRCUIT FAULT - Indicates a limit, draft safeguard, flame rollout, or blocked vent
switch (if used) is open. Blower will r un for 4 minutes or until open switch remakes whichever is longer. If open longer th an 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts off. Flame rollout switch and BVSS require manual reset. Check for: - Dirty filter or restricted duct system
- Defective blower motor or capacitor - Proper vent sizing - Restricted vent
- Defective switch or connections - Loose blower wheel - Excessive wind
- Inadequate combustion air supply (Flame Roll-out Switch open).
34 IGNITION PROVING FAILURE - Control wil l try three more times before lockout #14 occurs.
If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Oxide buildup on fla me sensor (clean with fine stee l wool)
- Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal)
- Manual valve shut-off - Control ground continuity
- Gas valve defective or gas valve turned off - Low inlet gas pressure
- Inadequate flame carryover or rough ignition - Defective Hot Surface Ignitor
- Flame sensor must not be grounded
- Green/Yellow wire MUST be connected to furnace sheet metal
43 LOW-HEAT PRESSURE SWITCH OPEN WHILE HIGH-HEAT PRESSURE SWITCH IS
CLOSED - Ch eck for: - Disconnected or obstructed pressure tubing
- Mis-wired pressure switches - Low-heat pressure switch stuck open
- Low inlet gas pressure (if LGPS used)
45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour lockout due to;
- Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.
Fig. 57 -- Service Label
327598-101 REV. C
SERVICE
312A
A04210
47
Page 48
312A
A07125
Fig. 58 -- Wiring Diagram
48
Page 49
CLEANING AND/OR REPLACING AIR FILTER
The air filter arrangement will vary depending on the application. NOTE: If the filter has an airflow direction arrow, the arrow
must point towards the blower.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.
Media cabinet filter procedures:
NOTE: Media Cabinet is included with two--stage furnace.
Table 17 – Filter size information (in.)
FURNACE
CASING
WIDTH
14--- 1/2 16 X 25 X 1 14 X 25 X 1 Cleanable*
17--- 1/2 16 X 25 X 1 16 X 25 X 1 Cleanable*
21 16 X 25 X 1 20 X 25 X 1 Cleanable*
24 16 X 25 X 1 24 X 25 X 1 Cleanable*
*Recommended
1. Turn off electrical supply to furnace before removing filter access door.
2. Remove filter cabinet door.
3. Slide filter out of cabinet.
4. If equipped with permanent, washable 1--in filter, clean filter by spraying cold tap water through filter in opposite direction of airflow. Rinse filter and let dry. Oiling or coating of the filter is not recommended. See Table 17 for size information.
5. If equipped with factory--specified disposable media filter, replace only with media filter having the same part number and size. For expandable replacement media, refer to the instructions included with the replacement media. If equipped with accessory KGAFR0301ALL external filter rack. See Table 17.
6. Slide filter into cabinet.
7. Replace filter cabinet door.
8. Turn on electrical supply to furnace.
BLOWER MOTOR AND
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Blower access door switch opens 115--v power to control. No component operation can occur unless switch is closed. Caution must be taken when manually closing this switch for service purposes.
NOTE: The blower wheel should not be dropped or bent as balance will be affected.
FILTER SIZE
Side Return
Bottom Re -
turn
WHEEL
WARNING
FILTER TYPE
The following steps should be performed by a qualified service agency.
To ensure long life and high efficiency, clean accumulated dirt and grease from blower wheel and motor annually.
The inducer and blower motors are pre--lubricated and require no additional lubrication. These motors can be identified by the absence of oil ports on each end of the motor.
Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Loosen the thumbscrew from outer door and remove outer door.
3. For downflow or horizontal furnaces having vent pipes within the furnace that pass in front of the blower access door:
a. Disconnect vent connector from furnace vent elbow.
b. Disconnect and remove short piece of vent pipe from
within furnace.
4. Remove 2 screws from blower access door and remove blower access door.
5. Disconnect blower leads from furnace control. Record wire color and location for reassembly. All other factory wires can be left connected, but field thermostat connections may need to be disconnected depending on their length and routing.
6. Remove 2 screws holding control box to blower shelf.
7. Hang control box from front of furnace casing and away from blower compartment.
8. Remove 2 screws holding blower assembly to blower deck and slide blower assembly out of furnace.
9. Clean blower wheel and motor using a vacuum with soft brush attachment. Blower wheel blades may be cleaned with a small paint or flux brush. Do not remove or disturb balance weights (clips) on blower wheel blades.
10. Vacuum any loose dust from blower housing, wheel and motor.
11. If a greasy residue is present on blower wheel, remove wheel from the blower housing and wash it with an appropriate degreaser. To remove wheel:
NOTE: Before disassembly, mark blower mounting arms, motor, and blower housing so motor and each arm is positioned at the same location during reassembly.
a. Disconnectcapacitorwires(ifequipped)and ground wire
attached to blower housing.
b. Remove screws securing cutoff plate and remove cutoff
plate from housing.
c. Loosen set screw holding blower wheel on motor shaft
(160+/--20 in.--lb. when reassembling).
d. Remove bolts holding motor to blowerhousing and slide
motorout of wheel (40+/--10 in.--lb. when reassembling).
e. Remove blower wheel from housing. f. Clean wheel and housing.
12. Reassemble motor and blower by reversing steps 11e, through 11a. Be sure to reattach ground wire to the blower housing.
13. Verify that blower wheel is centered in blower housing and set screw contacts the flat portion of the motor shaft. Loosen set screw on blower wheel and reposition if necessary.
14. Spin the blower wheel by hand to verify that the wheel does not rub on the housing.
15. Reinstall blower assembly in furnace.
312A
49
Page 50
16. Reinstall control box assembly in furnace.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in shortened heat exchanger life.
Heating fan speed(s) MUST be adjusted to provide proper air temperature rise as specified on the rating plate. Recommended operation is at the midpoint of the rise range or slightly above. Refer to “SET TEMPERATURE RISE” under START--UP, ADJUSTMENT, and SAFETY CHECK.
NOTE: Refer to Table 13 for motor speed lead relocation if leads were not identified before disconnection.
17. Reconnect blower leads to furnace control. Refer to
312A
furnace wiring diagram, and connect thermostat leads if previously disconnected.
18. To check blower for proper rotation:
a. Turn on electrical supply.
b. Manually close blower access door switch.
NOTE: If thermostat terminals are jumpered at the time blower access door switch is closed, blower will run for 90 sec before beginning a heating or cooling cycle.
c. Perform component self--test as shown at the bottom of
the SERVICE label, located on the front of blower access door.
d. Verify blower is rotating in the correct direction.
19. If furnace is operating properly, RELEASE BLOWER ACCESS DOOR SWITCH. Remove any jumpers or reconnect any disconnected thermostat leads. Replace blower access door.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, or death.
Blower access door switch opens 115--v power to furnace control. No component operation can occur unless switch is closed. Exercise caution to avoid electrical shock from exposed electrical components when manually closing this switch for service purposes.
them thoroughly. A build--up of soot and carbon indicates that a problem exists which needs to be corrected, such as improper adjustment of manifold pressure, insufficient or poor quality combustion air, incorrect size or damaged manifold orifice(s), improper gas, or a restricted heat exchanger. Action must be taken to correct the problem.
If it becomes necessary to clean the heat exchangers because of dust or corrosion, proceed as follows:
1. Turn OFF gas and electrical power to furnace.
2. Remove outer access door.
3. Disconnect vent connector from furnace vent elbow.
4. For downflow or horizontal furnace having an internal vent pipe, remove internal vent pipe within the casing.
5. Disconnect wires to the following components. Mark wires to aid in reconnection of (be careful when disconnecting wires from switches because damage may occur):
a. Draft safeguard switch.
b. Inducer motor.
c. Pressure switches.
d. Limit overtemperature switch.
e. Gas valve. f. Hot surface igniter.
g. Flame--sensing electrode h. Flame rollout switches.
6. Remove screws that fasten the collector box assembly to the cell panel. Be careful not to damage the collector box. Inducer assembly and elbow need not be removed from collector box.
7. Disconnect gas line from gas manifold.
8. Remove the 5 screws that attach the burner assembly to the cell panel. The gas valve and individual burners need not be removed from support assembly. Remove NOx baffles if installed.
NOTE: Be very careful when removing burner assembly to avoid breaking igniter. See Fig. 59 and 60 for correct igniter location.
9/32˝
5/16˝
20. Downflow or horizontal furnaces with vent pipe through furnace only:
a. Install and connect short pieceof vent pipe inside furnace
to existing vent.
b. Connect vent connector to vent elbow.
21. Turn on gas supply and cycle furnace through one complete heating and cooling cycle. Verify the furnace temperature rise as shown in Adjustments Section. Adjust temperature rise as shown in Adjustments Section. If outdoor temperature is below 70_F, turn off circuit breaker to outdoor unit before running furnace in the cooling cycle. Turn outdoor circuit breaker on after completing cooling cycle.
CLEANING HEAT
The following steps should be performed by a qualified service agency:
NOTE: If the heat exchangers get a heavy accumulation of soot
and carbon, they should be replaced rather than trying to clean
EXCHANGER
A05025
Fig. 59 -- Igniter Position--Side View
9. Using field--provided 25-- caliber rifle cleaning brush, 36--in. long 1/4” diameter steel spring cable, a variable speed, reversible electric drill, and vacuum cleaner, clean cells as follows:
50
Page 51
a. Remove metal screw fitting from wire brush to allow
insertion into cable.
b. Insert the twisted wire end of brush into end of spring
cable, and crimp tight with crimping tool or crimp by striking with ball--peen hammer. TIGHTNESS ISVERY IMPORTANT.
NOTE: The materials needed in item 9 can usually be purchased at local hardware stores.
(1.) Attach variable--speed, reversible drill to the end of
spring cable (end opposite brush).
(2.) Insert brush end of cable into the outlet opening of
cell and slowly rotate with drill. DO NOT force cable. Gradually insert cable into upperpass of cell. (See Fig. 61.)
(3.) Work cable in and out of cell 3 or 4 times to obtain
sufficient cleaning. DO NOT pull cable with great force. Reverse drill and gradually work cable out.
(4.) Insert brush end of cable in burner inlet opening of
cell, and proceed to clean 2 lower passes of cell in same manner as upper pass.
(5.) Repeat foregoing procedures until each cell in
furnace has been cleaned.
(6.) Using vacuum cleaner, remove residue from each
cell.
(7.) Using vacuum cleaner with soft brush attachment,
clean burner assembly.
(8.) Clean flame sensor with fine steel wool. (9.) Install NOx baffles (if removed.)
(10.) Reinstall burner assembly. Center burners in cell
openings.
10. Remove old sealant from cell panel and collector box flange.
11. Spray releasing agent on the heat exchanger cell panel where collector box assembly contacts cell panel.
NOTE: A releasing agent such as cooking spray or equivalent (must not contain corn or canola oil, aromatic or halogenated hydrocarbons or inadequate seal may occur) and RTV sealant (G.E. 162, 6702, or Dow--Corning 738) are needed before starting installation. DO NOT substitute any other type of RTV sealant. G.E. 162 (P771--9003) is available through RCD in 3--oz. tubes.
12. Apply new sealant to flange of collector box and attach to cell panel using existing screws, making sure all screws are secure.
13. Reconnect wires to the following components (Use connection diagram on wiring label, if wires were not marked for reconnection locations.):
a. Draft safeguard switch.
b. Inducer motor.
c. Pressure switches.
d. Limit overtemperature switch.
e. Gas valve.
f. Hot surface igniter. g. Flame--sensing electrode.
h. Flame rollout switches.
14. Reinstall internal vent pipe, if applicable.
15. Reinstall vent connector on furnace vent elbow. Securely fasten vent connector to vent elbow with 2 field--supplied, corrosion --resistant, sheet metal screws located 180_ apart.
1-7/8”
A01026
Fig. 60 -- Igniter Position -- Top View
A91252
Fig. 61 -- Cleaning Heat Exchanger Cell
16. Replace blower access door only, if it was removed.
17. Set thermostat above room temperature and check furnace for proper operation.
18. Verify blower airflow and speed changes between heating and cooling.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Never use a match or other open flame to check for gas leaks. Use a soap--and--water solution.
19. Check for gas leaks.
20. Replace outer access door.
Step 3 — Sequence of Operation
NOTE: Furnace control must be grounded for proper operation
or control will lockout. Control is grounded through green wire connected to gas valve and burner bracket screw. Using the schematic diagram in Fig. 58, follow the sequence of operation through the different modes. Read and follow the wiring diagram very carefully.
NOTE: If a power interruption occurs during a call for heat (W/W1 or W/W1--and--W2), the control run the blower for the selected blower off--delay period two seconds after power is restored and if the thermostat is still calling for gas heating. The LED light will flash code 12 during this period, after which the LED will be ON continuous, as long as no faults are detected. After this period, the furnace will respond to the thermostat normally.
The blower door must be installed for power to be conducted through the blower door interlock switch ILK to the furnace
312A
51
Page 52
control CPU, transformer TRAN, inducer motor IDM, blower motor BLWM, hot--surface igniter HSI, and gas valve GV.
1. Two--Stage Heating (Adaptive mode) with
Single--Stage Thermostat
(See Fig. 24 or 33 for thermostat connections)
NOTE: The low--heat only switch (LHT) selects either the low--heat only operation mode when ON, (see item 2. below) or the adaptive heating mode when OFF in response to a call for heat. (See Fig. 34.) When the W2 thermostat terminal is energized it will always cause high--heat operation when the R to W circuit is closed, regardless of the setting of the low--heat only switch. This furnace can operate as a two--stage furnace with a single-- stage thermostat because the furnace control CPU includes a programmed adaptive sequence of controlled operation, which selects low--heat or high--heat operation. This selection is based upon the stored history of the length of previous gas--heating periods of the single--stage thermostat.
The furnace will start up in either low-- or high--heat. If the furnace starts up in low--heat, the control CPU determines the
312A
low--heat on--time (from 0 to 16 minutes) which is permitted before switching to high--heat.
If the power is interrupted, the stored history is erased and the control CPU will select low--heat for up to 16 minutes and then switch to high--heat, as long as the thermostat continues to call for heat. Subsequent selection is based on stored history of the thermostat cycle times.
The wall thermostat “calls for heat”, closing the R to W circuit. The furnace control performs a self--check, verifies the low--heat and high--heat pressure switch contacts LPS and HPS are open, and starts the inducer motor IDM in high--speed.
a. Inducer Prepurge Period
(1.) If the furnace control CPU selects low--heat
operation the inducer motor IDM comes up to speed, the low--heat pressure switch LPS closes, and the furnace control CPU begins a 15--second prepurge period. After the low--heat pressureswitch re--closes the furnace control CPU will begin a 15--second prepurgeperiod,and continue to run the inducer motor IDM at high--speed.
(2.) If the furnace control CPU selects high--heat
operation, the inducer motor IDM remains running at high--speed, and the high--heat pressure switch relay HPSR is de--energized to close the NC contact. When sufficient pressure is available the high--heat pressure switch HPS closes, and the high--heat gas valve solenoid GV--HI is energized. The furnace control CPU begins a 15--second prepurge period after the low--heat pressure switch LPS closes. If the high--heatpressure switch HPS fails to close and the low-- heat pressure switch LPS closes, the furnace will operate at low--heat gas flow rate until the high--heat pressure switch closes for a maximum of 2 minutes after ignition.
b. Igniter Warm--Up--At the end of the prepurge period,
the (Hot Surface Igniter) HSI is energized for a 17--second igniter warm--up period.
c. Trial--for--Ignition Sequence--When the igniter
warm--up period is completed the main gas valve relay contacts GVR--1 and --2 close to energize the gas valve solenoid GV--M, the gas valve opens, and 24 vac power is supplied for a field--installed humidifier at the HUM terminal.The gas valve solenoidGV--M permitsgasflow to the burners whereitis ignitedby the HSI. Five sec after the GVR closes, a 2--sec flame proving period begins. The HSI igniter will remain energized until the flame is sensed or until the 2--sec flame proving period begins. If
the furnace control CPU selects high--heat operation, the high--heat gas valve solenoid GV--HI is also energized.
d. Flame--Proving--When theburner flameis proved at the
flame--proving sensor electrode FSE, the inducer motor IDM switches to low--speed unless running at high--speed, and the furnace control CPU begins the blower--ON delay period and continues to hold the gas valve GV--M open. If the burner flame is not proved within two seconds, the control CPU will close the gas valve GV--M,and thecontrol CPU will repeatthe ignition sequence for up to three more Trials-- For--Ignition before going to Ignition-- Lockout. Lockout will be reset automatically after three hours, by momentarily interrupting 115 vac power to the furnace, or by interrupting 24 vac power at SEC1 orSEC2 to thefurnace controlCPU (not atW/W1, G, R,etc.). If flame is proved when flame should not be present, the furnace control CPU will lock out of Gas--Heating mode and operate the inducermotor IDM on highspeed until flameisno longer proved.
e. Blower--ON Delay --If the burner flame is proven the
blower--ON delay for low--heat and high--heat are as follows: Low--Heat--45 seconds after the gas valve GV--M is energized the blower motor (BLWM) is energized at LO HEAT speed. High--Heat--25 seconds after the gas valve GV--M is energized the BLWM is energized at HI HEAT speed. Simultaneously, the electronic air cleaner (EAC--1) terminal isenergized and remains energized as long asthe BLWM is energized.
f. Switching from Low--to High--Heat--If the furnace
control CPU switches from low--heat to high--heat, the furnace control CPU will switch the inducer motor IDM speed from low to high. The high--heat pressure switch relay HPSR is de--energized to close the NC contact. When sufficient pressure is available the high--heat pressure switch HPS closes, and the high--heat gas valve solenoid GV--HI is energized. The blower motor BLWM will switch to HI HEAT speed five seconds after the furnace control CPU switches from low--heat to high--heat.
g. Switching from High-- to Low--Heat--The furnace
control CPU will not switch from high--heat to low--heat while thethermostat R--to--W circuit is closed when using a singlestage thermostat.
h. Blower--OFF Delay--When thethermostatis satisfied, the
R to W circuit is opened, de--energizing the gas valve GV--M, stopping gas flow to the burners, and de--energizing the humidifier terminal HUM. The inducer motor IDM will remain energized for a5--second post--purge period. The blower motor BLWM and air cleaner terminal EAC--1 will remain energized for 90, 120, 150, or 180 seconds (depending on selection at blower--OFF delay switches). The furnace control CPU is factory--set for a 120--second blower--OFF delay.
2. Two-- Stage Thermostat and Two--Stage Heating (See Fig. 32 for thermostat connections)
NOTE: In this mode the LHT must be ON to select the low--heat only operation mode in response to closing the thermostat R--to--W1 circuit. Closing the thermostat R--to--W1--and--W2 circuits always causes high--heat operation, regardless of the setting of the low--heat--only switch.
The wall thermostat “calls for heat”, closing the R--to--W1 circuit for low--heat or closing the R--to--W1 and--W2 circuits for high--heat. The furnace control performs a self--check, verifies the
52
Page 53
low-- heat and high--heat pressure switch contacts LPS and HPS are open, and starts the inducer motor IDM in high--speed.
The start up and shut down functions and delays described in item 1. above apply to the 2--stage heating mode as well, except for switching from low-- to high--Heat and vice versa.
a. Switching from Low-- to High--Heat--If the thermostat
R--to-- W1 circuit is closed and the R--to--W2 circuit closes, the furnace control CPU will switch the inducer motor IDM speed from low to high. The high--heat pressure switch relay HPSR is de--energized to close the NC contact. When sufficient pressure is available the high--heat pressure switch HPS closes,and the high--heat gas valve solenoid GV--HI is energized. The blower motorBLWM willswitch to HI HEAT speed five seconds after the R--to--W2 circuit closes.
b. Switching from High-- to Low--Heat--If the thermostat
R--to--W2 circuitopens, and theR--to--W1 circuitremains closed, the furnace control CPU will switch the inducer motor IDM speed from high to low. The high--heat pressure switch relay HPSR is energized to open the NC contact and de--energizethehigh--heatgasvalvesolenoid GV--HI.When the inducer motor IDM reduces pressure sufficiently, the high-- heat pressure switch HPS will open. The gas valve solenoid GV--M will remain energized as long as the low--heat pressure switch LPS remains closed. The blower motor BLWM will switch to LO HEAT speed five seconds after the R--to--W2 circuit opens.
3. Cooling Mode--The thermostat “calls for cooling.” a. Single--Speed Cooling--
(See Fig. 28 for thermostat connections) The thermostat closes the R--to--G--and--Y circuits. The R--to-- Y circuit starts the outdoor unit, and the R--to--G--and--Y/Y2 circuits start the furnace blower motor BLWM on COOL speed. The electronic air cleaner terminal EAC--1 is energized with 115 vac when theblower motor BLWM isoperating.
When the thermostat is satisfied, the R--to --G and--Y circuits are opened. The outdoor unit will stop, and the furnace blower motor BLWM willcontinue operatingon the COOL speed for an additional 90 seconds. Jumper Y/Y2 to DHUM to reduce the cooling off--delay to 5 seconds. (See Fig. 25.)
b. Single--Stage Thermostat and Two--Speed Cooling
(Adaptive Mode)
(See Fig. 33 for thermostat connections) This furnace can operate a two --speed cooling unit with a single--stage thermostat because the furnace control CPU includes a programmed adaptive sequence of controlled operation, which selects low--cooling or high--cooling operation. This selection isbased upon the stored history of the length of previouscooling period of the single--stage thermostat.
NOTE: The air conditioning relay disable jumper ACRDJ must be connected to enable the adaptive cooling mode in response to a call for cooling. (See Fig. 34.) When ACRDJ is in place, the furnace control CPU can turn on the air conditioning relay ACR to energize the Y/Y2 terminal and switch the outdoor unit to high--cooling.
The furnace control CPU can start up the cooling unit in either low-- or high--cooling. If starting up in low--cooling, the furnace control CPU determines the low--cooling on--time (from 0 to 20 minutes) which is permitted before switching to high--cooling. If the power is interrupted, the stored history is erased and the furnace control CPU will select low--cooling for up to 20 minutes and then energize the air conditioning relay ACR to energize the
Y/Y2 terminal and switch the outdoor unit to high--cooling, as long as the thermostat continues to call for cooling. Subsequent selection is based on stored history of the thermostat cycle times. The wall thermostat “calls for cooling”, closing the R--to--G--and--Y circuits. The R--to--Y1 circuit starts the outdoor unit on low--cooling speed, and the R--to--G--and--Y1 circuits starts the furnace blower motor BLWM at low--cool speed (same speed as LO HEAT). If the furnace control CPU switches from low--cooling to high--cooling, the furnace control CPU will energize the air conditioning relay ACR. When the air conditioning relay ACR is energized the R--to--Y1--and--Y2 circuits switch the outdoor unit to high--cooling speed, and the R--to--G--and--Y1--and--Y/Y2 circuits switch the furnace blower motor BLWM to COOL speed.
NOTE: When transitioning from low--cooling to high--cooling the outdoor unit compressor will shut down for 1 minute while the BLWM continues to run at low--cool speed (same speed as LO--HEAT) until the outdoor unit compressor comes back on at high speed.
The electronic air cleaner terminal EAC--1 is energized with 115 vac whenever the blower motor BLWM is operating. When the thermostat is satisfied, the R--to--G--and--Y circuit are opened. The outdoor unit stops, and the furnace blower BLWM and electronic air cleaner terminal EAC--1 will remain energized for an additional 90 seconds. Jumper Y1 to DHUM to reduce the cooling off--delay to 5 seconds. (See Fig. 34.)
c. Two--Stage Thermostat and Two--Speed Cooling (See
Fig. 32 for thermostat connections)
NOTE: The air conditioning relay disable jumper ACRDJ must be disconnected to allow thermostat control of the outdoor unit staging. (See Fig. 34.)
The thermostat closes the R--to--G--and --Y1 circuits for low--cooling or closes the R--to--G--and--Y1--and--Y2 circuits for high--cooling. The R--to--Y1 circuit starts the outdoor unit on low--cooling speed, and the R--to--G--and--Y1 circuit starts the furnace blower motor BLWM on low-- cool speed (same speed as LO HEAT). The R--to--Y1--and--Y2 circuits start the outdoor unit on high--cooling speed, and the R--to--G--and-- Y/Y2 circuits start the furnace blower motor BLWM on COOL speed. The electronic air cleaner terminal EAC--1 is energized with 115 vac whenever the blower motor BLWM is operating. When the thermostat is satisfied, the R-- to-- G--and--Y1 or R--to--G--and--Y1--and--Y2 circuits are opened. The outdoor unit stops, and the furnace blower BLWM and electronic air cleaner terminal EAC--1 will remain energized for an additional 90 seconds. Jumper Y1 to DHUM to reduce the cooling off--delay to 5 seconds. (See Fig. 34.)
4. Thermidistat Mode (See Fig. 27 -- 29 for Thermidistat connections) The dehumidification output, DHUM on the Thermidistat should be connected to the furnace control thermostat terminal DHUM. When there is a dehumidify demand, the DHUM input is activated, which means 24 vac signal is removed from the DHUM input terminal. In other words, the DHUM input logic is reversed. The DHUM input is turned ON when no dehumidify demand exists. Once 24 vac is detected by the furnace control on the DHUM input, the furnace control operates in Thermidistat mode. If the DHUM input is low for more than 48 hours, the furnace control reverts back to non --Thermidistat mode. The cooling operation described in item 3. above also applies to operation with a Thermidistat. The exceptions are listed below:
a. Low cooling -- When the R--to--G--and--Y1 circuit is
closed and there is a demand for dehumidification,the furnace blower motor BLWM will continue running at low-- cool speed (same speed as LO HEAT).
312A
53
Page 54
312A
b. High cooling --When the R-- to--G--and--Y/Y2 circuit is
closed and there is a demand for dehumidification,the furnace blower motor BLWM will drop the blower speed from COOL to HI HEAT for a maximum of 10 minutes before reverting back to COOL speed. If there is still a demand for dehumidification after 20 minutes, the furnace control CPU will drop the blower speed back to HI HEAT speed. This alternating 10--minute cycle will continue as long as there is a call for cooling.
c. Cooling off--delay -- When the gcall for coolingh is
satisfied and there is a demand for dehumidification, the cooling blower--off delay is decreased from 90 seconds to 5 seconds.
5. Continuous Blower Mode When the R--to--G circuit is closed by the thermostat, the blower motor BLWM will operate on continuous--blower speed (can be set to LO HEAT, HI HEAT, or COOL speed). Factory default is LO HEAT speed. Terminal EAC--1 is energized as long as the blower motor BLWM is energized. During a call for heat, the blower BLWM will stop during igniter warm--up (17 seconds), ignition (7 seconds), and blower--ON delay (45 seconds in low--heat, and 25 seconds in high--heat), allowing the furnace heat exchangers to heat up more quickly, then restarts at the end of the blower--ON delay period at LO HEAT or HI HEAT speed respectively. The blower motor BLWM will revert to continuous--blower speed after the heating cycle is completed. In high--heat, the furnace control CPU will hold the blower motor BLWM at HI HEAT speed during the selected blower--OFF delay period before reverting to continuous--blower speed. When the thermostat “calls for low--cooling”, the blower motor BLWM will switch to operate at low--cool speed (same speed as LO HEAT). When the thermostat is satisfied, the blower motor BLWM will operate an additional 90 seconds on low--cool speed before reverting back to continuous--blower speed. When the thermostat “calls for high--cooling”, the blower motor BLWM will operate at COOL speed. When the thermostat is satisfied, the blower motor BLWM will operate an additional 90 seconds on COOL speed before reverting back to continuous--blower speed. When the R--to--G circuit is opened, the blower motor BLWM will continue operating for an additional 5 seconds, if no other function requires blower motor BLWM operation.
Continuous Blower Speed Selection from Thermostat
To select different continuous--blower speeds from the room thermostat, momentarily turn off the FAN switch or pushbutton on the room thermostat for 1--3 seconds after the blower motor BLWM is operating. The furnace control CPU will shift the continuous--blower speed from the factory setting of LO HEAT to HI HEAT speed. Momentarily turning off the FAN switch again at the thermostat will shift the continuous--blower speed from HI HEAT to COOL. Repeating the procedure will shift the continuous--blower speed from COOL to LO HEAT speed. The selection can be changed as many times as desired and is stored in the memory to be automatically used following a power interruption.
NOTE: If the blower--off delay is set to the maximum, the adjustable continuous--fan feature is locked (i.e., fan speed cannot be changed from its current setting).
6. Heat Pump (See Fig. 28 through 31 for thermostat connections) When installed with a heat pump, the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles. When the R--to-- W/W1--and--Y1 or R--to--W/W1--and--Y1--and--G circuits are energized the furnace control CPU will switch to or turn on the blower motor BLWM at low--cool speed (same speed as LO HEAT), and begin a low-- heat cycle. The blower motor BLWM will remain on until the end of the prepurge period, then shut off for 24 seconds then come back on at LO HEAT speed. When the W/W1 input signal disappears, the furnace control begins a normal inducer post--purge period and the blower remains running at LO HEAT speed. If the R--to-- W/W1--and--Y1--and--G signals disappear at the same time, the blower motor BLWM will remain on for the selected blower-- OFF delay period. If the R--to--W/W1--and--Y1 signals disappear, leaving the G signal, the blower motor BLWM will remain on for the selected blower--OFF delay period then switch to continuous--blower speed. When the R--to--W/W1--and--Y/Y2, R--to--W/W1--and-­Y / Y 2 -- a n d -- G , R -- t o -- W / W 1 -- a n d -- Y 1 -- a n d -- Y / Y 2 , o r R--to--W/W1--and-- Y1--and--Y/Y2--and--G circuits are energized the furnace control CPU will switch to or turn on the blower motor BLWM at COOL speed, and begin a high--heat cycle. The blower motor BLWM will remain on until the end of the prepurge period, then shut off for 24 seconds then come back on at HI HEAT speed. When the W/W1 input signal disappears, the furnace control begins a normal inducer post--purge period and the blower switches to COOL speed after a 3 second delay. If t h e R -- t o -- W / W 1 -- a n d -- Y / Y 2 -- a n d -- G o r R -- t o -- W / W 1 -- a n d
--Y1--and-- Y/Y2--and--G signals disappear at the same time, the blower motor BLWM will remain on for the selected blower--OFF delay period. If the R--to--W/W1-­a n d -- Y / Y 2 o r R -- t o -- W / W 1 -- a n d -- Y 1 -- a n d -- Y / Y 2 s i g n a l s disappear, leaving the G signal, the blower motor BLWM will remain on for the selected blower-- OFF delay period then switch to continuous--blower speed.
Step 4 — Wiring Diagrams
Refer to wiring diagram, Fig. 58.
Step 5 — Troubleshooting
Refer to the service label. (See Fig. 57—Service Label.) The Troubleshooting Guide can be a useful tool in isolating furnace operation problems. Beginning with the word “Start,” answer each question and follow the appropriate arrow to the next item.
The Guide will help to identify the problem or failed component. After replacing any component, verify correct operation sequence.
54
Page 55
A02107A
NO
Is door switch closed?
NO
YES
Is door switch closed?
NO
YES
TROUBLESHOOTING GUIDE
Is circuit breaker closed?
NO
Is there 115V going to switch?
NO
YES
Check for continuity in wire from circuit
breaker to furnace.
YES
Replace door switch.
YES
Is 24V present at W/W1, W2, Y1, Y/Y2 or G
thermostat terminals on the furnace control?
NO
Does the control respond to W/W1, W2, Y1,
Y/Y2, and G (24V) thermostat signals?
NO
YES
Disconnect all the thermostat wires from the
furnace control.
YES
Run system through a low-heat, high-heat,
or cooling cycle to check operation. Status
NO
The thermostat is not compatible with the
furnace control. Either install a ballast resistor,
connect the Com24V thermostat terminal to
Does the problem repeat when using a
jumper wire?
YES
codes are erased after 72 hours. On RED
LED boards stored status codes can also be
erased whenever (115V or 24V) is interrupted.
Replace furnace control.
the thermostat, or replace the thermostat.
312A
NO
Close circuit breaker and go back to START.
Replace transformer.
Check room thermostat or
interconnecting cable.
Fig. 62 -- Troubleshooting Guide 2--Speed
Is there 115V at L1 and L2?
NO
START
Is LED status light on?
Is there 24V at SEC-1 and SEC-2?
YES
Replace furnace control.
Check for correct line voltage polarity. If
units are twinned, check for proper low-
voltage (24V) transformer phasing.
YES
NO
Is LED status light blinking rapidly
without a pause?
To recall status code briefly remove and reconnect one RED wire from the
draft safeguard switch to display stored status code. On RED LED control do
not remove power or blower access panel before initiating status code recall.
You can also recall the previous status code by momentarily shorting the
TEST/TWIN terminal to Com24V terminal until the LED goes out. LED will
flash the status code of the previous fault or status code #11 (1 short and 1
long flash) if there was no previous fault. After the control repeats the code
4 times, the control will start the component test sequence. Once indicated
the control will turn ON at HI HEAT speed. The inducer will run for the entire
component test. The HSI, blower motor LO HEAT speed, HI HEAT speed, and
COOL speed will run for 10 – 15 seconds each. Gas valve and humidifier will
not be turned on. When the blower motor is turned OFF the inducer will be
switched to low-speed for 10 seconds.
NO
YES
Is LED status light blinking ON/OFF slowly
with a combination of short and long flashes?
Determine status code. The status code is a
2 digit number with the first digit determined
by the number of short flashes and the second
digit by the number of long flashes?
55
Was there a previous status code other
than #11?
YES
Go to section below for the status code that
was flashed.
Page 56
reset after 1 hour lockout due to:
45 CONTROL CIRCUITRY LOCKOUT Auto-
- Flame circuit failure.
- Gas valve relay stuck open.
- Software check error.
Reset power to clear lockout. Replace
control if code repeats.
Check for continuity in the harness and igniter.
Replace furnace control.
Replace defective component.
Check connections. If OK, replace control.
Check that all gas valves are turned on.
Replace valve.
Check for:
- Inadequate flame carryover or rough
ignition.
- Low inlet gas pressure.
- Proper firing rate.
(.045” nominal)
- Blocked or incorrect carry- over gap.
Allow blower to come on and repeat test to
check for intermittent operation.
Check connections and retry. If current is
near typical value (4.0-6.0 nominal) and
burners will not stay on, repeat check in high-
heat. If burners will still not stay on replace
control. If burners operate in high-heat then
switch to low-heat, check manifold pressure.
If OK, check burner carryover and flame
sensor location.
A05001
Replace electrode.
Replace furnace control.
312A
NO
tube.
WHILE HIGH-HEAT PRESSURE
SWITCH IS CLOSED - Check for:
- Low-heat pressure switch stuck open.
- Disconnected or obstructed pressure
- Miswired pressure switches.
- Low inlet gas pressure (if LGPS used).
43 LOW-HEAT PRESSURE SWITCH OPEN
NOT CLOSE OR REOPENED – If open
longer than 5 minutes, inducer shuts off
for 15 minutes before retry. If opens
during blower on-delay period, blower
will come on for the selected blower off-
delay. Check for:
- Proper vent sizing.
- Low inlet gas pressure (if LGPS used).
- Low inducer voltage (115V).
- Inadequate combustion air supply.
32 LOW-HEAT PRESSURE SWITCH DID
YES
Unplug igniter harness from control and
initiate another component test sequence.
Check for 115V between pin 1 and
NEUTRAL-L2 on the control. Was 115V
present for the 15 second period?
tubing.
- Disconnected or obstructed pressure
- Defective inducer motor.
- Defective pressure switch.
- Excessive wind.
- Restricted vent.
NO
YES
Reconnect the R thermostat lead and set
thermostat to call for heat. Connect voltmeter
across gas valve connections. Does gas
valve receive 24V?
Blower will run for 4 minutes or until
limit, draft safeguard, flame rollout, or
blocked vent shutoff switch* (if used) is
open.
open switch remakes whichever is longer.
If open longer than 3 minutes, code
33 LIMIT CIRCUIT FAULT – Indicates the
NO
YES
Does gas valve open and allow gas to flow?
changes to lockout #13. If open less
than 3 min. status code #33 continues
to flash until blower shuts off. Flame
rollout switch and BVSS requires manual
NO
YES
Do the main burners ignite?
reset. Check for:
- Dirty filter or restricted duct system.
- Defective blower motor or capacitor.
- Loose blower wheel.
- Defective switch or connections.
YES
NO
Do the main burners stay on?
(flame rollout switch open).
- Restricted vent.
- Inadequate combustion air supply
- Proper vent sizing.
- Excessive wind.
NO
YES
Repeat call for heat and check flame sensor
current during trial for ignition period. Is the
DC microamps below 0.5?
Clean flame sensor with fine steel wool and
recheck current. Nominal current is 4.0 to
6.0 microamps.
NO
is not sensed during the trial for ignition
period, the control will repeat the ignition
sequence 3 more times before lockout
#14 occurs. If flame signal is lost during
the blower on-delay period, blower will
come on for the selected blower off-delay.
Check the following items first before
34 IGNITION PROVING FAILURE – If flame
NO
Is current near typical value?
to furnace sheet metal.
proceeding to the next step.
- Gas valve turned off.
- Green/Yellow wire MUST be connected
- Flame sensor must not be grounded.
- Manual shut-off valve.
NO
YES
YES
Will main burners ignite and stay on?
YES
To determine whether the problem is in
the gas valve, igniter, or flame sensor
the system can be operated in the
component test mode to check the igniter.
First remove the R thermostat connection
from the control and initiate the
Fixed.
component test sequence. Does the
igniter glow orange/white by the end of
the 15 second warm-up period?
Fig. 63 -- Troubleshooting Guide 2--Speed
* Blocked vent shutoff switch used in Chimney Adapter Kit
are erased after 72 hours. On RED LED
boards stored status codes can also be
erased whenever power (115V or 24V)
is interrupted. Run system through a
low-heat, high-heat, or cooling cycle to
check system.
(115V OR 24V) – Normal operation.
Blower runs for the selected blower off-
11 NO PREVIOUS CODE – Stored codes
12 BLOWER ON AFTER POWER UP –
delay, if unit is powered up during a call
for heat (R-W/W1 closed) or when (R-
W/W1 opens) during the blower on-delay
period.
occurs if the limit, draft safeguard, flame
rollout, or blocked vent switch* (if used)
is open longer than 3 minutes. Control will
auto-reset after 3 hours. See code 33.
13 LIMIT CIRCUIT LOCKOUT – Lockout
ignite gas and prove flame in 4 attempts.
14 IGNITION LOCKOUT – System failed to
Control will auto-reset after 3 hours. See
status code 34.
control.
power and wait 5 minutes to retry.
Check for:
- Stuck closed gas valve relay on
- Miswire or short to gas valve wire.
Flame is proved while gas valve is de-
energized. Inducer will run until fault is
cleared. Check for:
- Stuck open or leaky gas valve.
Check for:
- Obstructed pressure tube.
- Pressure switch stuck closed.
21 GAS HEATING LOCKOUT – Tur n off
22 ABNORMAL FLAME-PROVING SIGNAL
23 PRESSURE SWITCH DID NOT OPEN
(24V) wiring including thermostat
OPEN Check for:
- Short circuit in secondary voltage
24 SECONDARY VOLTAGE FUSE IS
leads. Disconnect thermostat leads
to isolate short circuit.
RELAY DID NOT CLOSE OR
31 HIGH-HEAT PRESSURE SWITCH OR
REOPENED - Check for:
- Control relay may be defective.
- Gas valve is miswired.
- See status code 32.
56
Page 57
57
Page 58
E2007 B ryant Heating & Cooling Systems 7310 W. Mo rris St. Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 02/07
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
58
Catalog No. II312A--- 4 5 --- 8
Replaces: II312A--- 45--- 7
Loading...