Sequence of Operation51...........................
Wiring Diagrams54...............................
Troubleshooting54................................
ama
ISO 9001:2000
CERTIFIED
REGISTERED
NOTE: Read the entire instruction manual before starting the
installation.
Portions of the text and tables are reprinted from NFPA 54/ANSI
Z223.1--2006E, with permission of National Fire Protection
Association, Quincy, MA 02269 and American Gas Association,
Washington DC 20001. This reprinted material is not the
complete and official position of the NFPA or ANSI on the
referenced subject, which is represented only by the standard in
its entirety.
Page 2
28-7/8"
25-1/4"
22-9/16"
JUNCTION BOX
LOCATION
WIRE ENTRY
3-15/16"
LEFT HAND GAS
ENTRY
7/8" DIA. ACCESSORY
21-5/8"
BOTTOM INLET
24"
CASING
1-11/16"
24-7/8"
5-1/2"
4-13/16"
8-9/16"
ALTERNATE
JUNCTION BOX
VENT OUTLET
5 PLACES (TYP)
3-3/4"
2-7/16"
1-5/16"
1-1/8"
A
D
F
E
13/16"
LOCATIONS (TYP)
5-1/2"
11/16"
AIRFLOW
19"
OUTLET
1/2" DIA. K.O.THERMOSTAT
WIRE ENTRY
1-3/4" DIA.RIGHT HAND
GAS ENTRY
7/8" DIA. K.O. WIRE ENTRY
7/8" DIA. ACCESSORY
1-1/2"
22-1/16"
SIDE INLET
13/16"
11/16"
14-7/8"
1-1/4"
1"
312A
26-1/8"
(FLUE COLLAR)
5-15/16"
7/8" DIA
ACCESSORY
NOTES:
1. Two additional 7/8-in. diameter holes are located in the top plate.
2. Minimum return-air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters.
a. For 800 CFM-16-in. round or 14 1/2 x 12-in. rectangle.
b. For 1200 CFM-20-in. round or 14 1/2 x 19 1/2-in. rectangle.
c. For 1600 CFM-22-in. round or 14 1/2 x 22-in. rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets
a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
1/2" DIA THERMOSTAT
33-5/16"
11/16"
NOTES:
1. Two additional 7/8---in. diameter holes are located in the top plate.
2. Minimum return --- air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent
diameters.
a. For 800 CFM---16--- in. round or 14 1/2 x 12--- in. rectangle.
b. For 1200 CFM---20 ---in. round or 14 1/2 x 19 1/2--- in. rectangle.
c. For 1600 CFM---22 ---in. round or 14 1/2 x 22--- in. rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific u se of single side inlets. The use of both sideinlets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airfl ow requirements above 1800 CFM.
Fig. 1 -- Dimensional Drawing
7-3/4"
9-5/8"
11-1/2"
A04037
SAFETY CONSIDERATIONS
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous
operation, serious injury, death, or property damage.
Improper installation, adjustment, alteration, service,
maintenance, or use could cause carbon monoxide
poisoning, explosion, fire, electrical shock, or other
conditions which may cause personal injury or property
damage. Consult a qualified service agency, local gas
supplier, or your distributor or branch for information or
assistance. The qualified service agency must use only
factory--authorized and listed kits or accessories when
modifying this product.
!
CAUTION
FURNACE RELIABILITY HAZARD
Improper installation or misapplication of furnace may
require excessive servicing or cause premature component
failure.
Application of this furnace should be indoors with special
attention given to vent sizing and material, gas input rate,
air temperature rise, unit leveling, and unit sizing.
Installing and servicing heating equipment can be hazardous due
to gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations
must be performed by trained service personnel. When working
on heating equipment, observe precautions in literature, on tags,
and on labels attached to or shipped with furnace and other safety
precautions that may apply. These instructions cover minimum
requirements and conform to existing national standards and
safety codes. In some instances, these instructions exceed certain
local codes and ordinances, especially those that may not have
kept up with changing residential construction practices. We
require these instructions as a minimum for a safe installation.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts and servicing furnaces.
Wear safety glasses and work gloves. Have fire extinguisher
available during start--up and adjustment procedures and service
calls.
This is the safety--alert symbol
. When you see this symbol
on the furnace and in instructions or manuals, be alert to the
potential for personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify hazards which may result in minor personal injury or
* 5” or 6” vent connector may be required in some cases.
{ 135 and 155 size furnaces require five---inch or larger vents. Use a 4---5 or 4---6 inch vent adapter between furnace and vent connector.
CABINET
WIDTH
(IN.)
D
SUPPLY--- AIR
WIDTH (IN.)
E
RETURN---AIR
WIDTH (IN.)
product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
1. Use only with type of gas approved for this furnace. Refer
to the furnace rating plate 2. Install this furnace only in a
2. Install this furnace only in a location and position as
specified in the “Location” section of these instructions.
3. Provide adequate combustion and ventilation air to the
furnace space as specified in “Air for Combustion and
Ventilation” section.
4. Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system only, as
specified in the “Venting” section of these instructions.
5. Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for
the detection of leaks to check all connections, as specified
in the “Gas Piping” section.
6. Always install furnace to operate within the furnace’s
intended temperature--rise range with a duct system which
has an external static pressure within the allowable range,
as specified in the “Start--Up, Adjustments, and Safety
Check” section. See furnace rating plate.
7. When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled
by duct(s) sealed to the furnace casing and terminating
outside the space containing the furnace. See “Air Ducts”
section.
8. A gas-- fired furnace for installation in a residential garage
must be installed as specified in the warning box in the
“Location” section.
9. The furnace may be used for construction heat provided
that the furnace installation and operation complies with
the first CAUTION in the LOCATION section of these
instructions.
10. These Multipoise Gas--Fired Furnaces are CSA (formerly
A.G.A. and C.G.A.) design--certified for use with natural
and propane gases (see furnace rating plate) and for
installation in alcoves, attics, basements, closets, utility
rooms, crawlspaces, and garages. The furnace is
factory--shipped for use with natural gas. A CSA (A.G.A.
and C.G.A.) listed accessory gas conversion kit is required
F
C.L. TOP AND
BOTTOM FLUE
COLLAR (IN.)
FLUE
COLLAR*
(IN.)
SHIP WT. (LB)
11. See Fig. 2 for required clearances to combustible
construction.
12. Maintain a 1--in. clearance from combustible materials to
supply air ductwork for a distance of 36 inches
horizontally from the furnace. See NFPA 90B or local
code for further requirements.
13. These furnaces SHALL NOT be installed directly on
carpeting, tile, or any other combustible material other
than wood flooring. In downflow installations, factory
accessory floor base MUST be used when installed on
combustible materials and wood flooring. Special base is
not required when this furnace is installed on
manufacturer’s Coil Assembly Part No. CD5 or CK5, or
when Coil Box Part No. KCAKC is used. See Fig. 2 for
clearance to combustible construction information.
INTRODUCTION
The Series 120/C 4--way multipoise Category I fan--assisted
furnace is CSA (formerly A.A.A.. and C.G.A.) design--certified.
A Category I fan--assisted furnace is an appliance equipped with
an integral mechanical means to either draw or force products of
combustion through the combustion chamber and/or heat
exchanger. The furnace is factory--shipped for use with natural
gas. This furnace is not approved for installation in mobile
homes, recreational vehicles, or outdoors.
These furnaces shall not be installed directly on carpeting, tile, or
any other combustible material other than wood flooring. For
downflow installations, a factory accessory floor base must be
used when installed on combustible materials and wood flooring.
This special base is not required when this furnace is installed on
the manufacturer’s coil assembly, or when the manufacturer’s coil
box is used. See Fig. 2 for clearance to combustible material
information.
This furnace is designed for minimum continuous return--air
temperature of 60_F db or intermittent operation down to 55_F
db such as when used with a night setback thermostat. Return-- air
temperature must not exceed 80_F db. Failure to follow these
return-- air temperature limits may affect reliability of heat
exchangers, motors, and controls. (See Fig. 3.)
For accessory installation details, refer to the applicable
instruction literature.
NOTE: Remove all shipping brackets and materials before
operating the furnace.
to convert furnace for use with propane gas.
FILTER
MEDIA
CABINET
SIZE (IN.)
312A
3
Page 4
312A
INSTALLATION
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
DISTANCE MINIMALE EN POUCES AUX CONSTRUCTIONS COMBUSTIBLES
This forced air furnace is equipped for use with
natural gas at altitudes 0-10,000 ft (0-3,050m).
An accessory kit, supplied by the
manufacturer, shall be used to convert to propane
gas use or may be required for some natural gas
applications.
This furnace is for indoor installation in a
building constructed on site.
This furnace may be installed on combustible
flooring in alcove or closet at minimum clearance
as indicated by the diagram from combusitble
material.
This furnace may be used with a Type B-1 Vent
and may be vented in common with other gas
fired appliances.
Cette fournaise à air pulsé est équipée
pour utilisation avec gaz naturel et altitudes
comprises entre 0-3,050m (0-10,000 pi).
Utiliser une trousse de conversion, fournie par
le fabricant, pour passer au gaz propane ou pour
certaines installations au gaz naturel.
This furnace is approved for UPFLOW, DOWNFLOW, and
HORIZONTAL installations.
Cette fournaise est approuvée pour l 'installation HORIZONTALE
et la circulation d 'air VERS LE HAUT et VERS LE BAS.
Clearance arrows
do not change with
furnace orientation.
0"
B
A
A
C
R
K
R
I
È
R
E
E
D
I
S
É
T
Ô
C
0"
*
1"
Les fléches de dégagement
l 'orientation de la fournaise.
TOP / PLE NUM
DESSUS / CHAMBRE D'AIR
E
C
E
A
S
N
I
A
R
U
N
F
R
U
T
FO
N
O
T
R
N
F
A
V
A
F
R
O
A
N
V
T
A
N
T
3"
Cette fournaise est prévue pour être
installée dans un bâtiment construit sur place.
Cette fournaise peut être installée sur
un plancher combustible dans une alcôve ou
dans un garde-robe en respectant le minimum
d'espace libre des matériaux combustibles, tel
´
indiqué sur le diagramme.
qu
Cette fournaise peut être utilisée avec un
´
évacuation de Type B-1 ou connectée
conduit d
au conduit ommun d 'autres appareils à gaz.
Vent Clearance to combustibles:
For Single Wall vents 6 inches (6 po).
For Type B-1 vent type 1 inch (1 po).
Dégagement de l´évent avec combustibles:
Pour conduit d´évacuation à paroi simple 6 po (6 inches).
Pour conduit d
BOTTOM
DESSOUS
"
0
†
´
évacuation de Type B-1 1 po (1 inch).
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
DOWNFLOW POSITIONS:
Installation on non-combusibible floors only.
†
For Installation on combustible flooring only when installed on special base, Part No. KGASB0201ALL,
Coil Assembly, Part No. CD5 or CK5, or Coil Casing, Part No. KCAKC.
18 inches front clearance required for alcove.
Ø
Indicates supply or return sides when furnace is in the horizontal position. Line contact only permissible
*
between lines formed by intersections of the Top and two Sides of the furnace jacket, and building joists,
studs or framing.
DÉGAGEMENT MINIMUM EN POUCES AVEC ÉLÉMENTS
DE CONSTRUCTION COMBUSTIBLES
POUR LA POSITION COURANT DESCENDANT:
Pour l´installation sur plancher non combustible seulement.
†
´
installation sur un plancher combustible seulement quand on utilise la base spéciale, pièce
Pour l
nº KGASB0201ALL, l
nº KCAKC.
Dans une alcôve, on doit maintenir un dégagement à l
Ø
La poistion indiquée concerne le côté d
*
position horizontale.
Le contact n
´
est permis qu´entre les lignes formées par les intersections du dessus et des
deux côtés de la cherrise de la fournaise et les solives, montant sous cadre de charpente.
´
ensemble serpentin, pièce nº CD5 ou CK5, ou le carter de serpentin, pièce
´
´
entrée ou de retour quand la fournaise est dans la
avant de 18 po (450mm).
327590-101 REV. C
ne change pas avec
0"
E
D
*
I
È
S
T
Ô
C
S
E
R
E
N
V
I
T
R
C
E
E
T
I
E
N
24"
MIN
Ø
Clearance in inches
Dégagement (po).
MIN
Fig. 2 -- Clearances to Combustibles
4
A04123
Page 5
80
60
A04036
Fig. 3 -- Return Air Temperature
CODES AND STANDARDS
Follow all national and local codes and standards in addition
to these instructions. The installation must comply with
regulations of the serving gas supplier, local building, heating,
plumbing, and other codes. In absence of local codes, the
installation must comply with the national codes listed below and
all authorities having jurisdiction.
In the United States and Canada, follow all codes and standards
for the following:
Step 1 — Safety
SUS: National Fuel Gas Code (NFGC) NFPA 54--2006/ANSI
Z223.1--2006 and the Installation Standards, Warm Air Heating
and Air Conditioning Systems ANSI/NFPA 90B
SCANADA: CSA B149.1--00 National Standard of Canada
SUS: Current edition of the NFGC and the NFPA 90B. For
copies, contact the National Fire Protection Association Inc.,
Batterymarch Park,Quincy, MA 02269; (www.NFPA.org) or for
only the NFGC, contact the American Gas Association, 400 N.
Capitol Street, N.W., Washington DC 20001 (www.AGA.org.)
SUS: Section 8.3 of the NFGC, Air for Combustion and
Ventilation
S CANADA: Part 7 of CAN/CSA--B149.1--05, Venting Systems
and Air Supply for Appliances
Step 4 — Duct Systems
S US and CANADA: Air Conditioning Contractors Association
(ACCA) Manual D, Sheet Metal and Air Conditioning
Contractors National Association (SMACNA), or American
Society of Heating, Refrigeration, and Air Conditioning
Engineers (ASHRAE) 2001 Fundamentals Handbook Chapter
34 or 2000 HVAC Systems and Equipment Handbook Chapters
9 and 16.
Step 5 — Acoustical Lining and Fibrous Glass Duct
SUS and CANADA: current edition of SMACNA and NFPA
90B as tested by UL Standard 181 for Class I Rigid Air Ducts
Step 6 — Gas Piping and Gas Pipe Pressure Testing
S US: NFGC; chapters 5, 6, and 7 and National Plumbing Codes
SCANADA: CAN/CSA--B149.1--05 Parts 4, 5, 6 and 9 and
Appendices A, B, E and H.
Step 7 — Electrical Connections
S US: National Electrical Code (NEC) ANSI/NFPA 70--2006
S CANADA: Canadian Electrical Code CSA C22.1
Step 8 — Venting
S US: NFGC; chapters 12 and 13
S CANADA: CAN/CSA--B149.1--05 Part 8 and Appendix C
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
!
CAUTION
FURNACE RELIABILITY HAZARD
Improper installation or service of furnace may cause
premature furnace component failure.
Electrostatic discharge can affect electronic components.
Follow the Electrostatic Discharge Precautions Procedure
listed below during furnace installation and servicing to
protect the furnace electronic control. Precautions will
prevent electrostatic discharges from personnel and hand
tools which are held during the procedure. These
precautions will help to avoid exposing the control to
electrostatic discharge by putting the furnace, the control,
and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple disconnects
may be required. DO NOT TOUCH THE CONTROL OR
ANY WIRE CONNECTED TO THE CONTROL PRIOR
TODISCHARGINGYOURBODY’S
ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the
furnace chassis which is close to the control. Tools held in
a person’s hand during grounding will be satisfactorily
discharged.
3. After touching the chassis, you may proceed to service the
control or connecting wires as long as you do nothing to
recharge your body with static electricity (for example;
DO NOT move or shuffle your feet, do not touch
ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body
with static electricity), firmly touch a clean, unpainted
metal surface of the furnace again before touching control
or wires.
5. Use this procedure for installed and uninstalled
(ungrounded) furnaces.
6. Before removing a new control from its container,
discharge your body’s electrostatic charge to ground to
protect the control from damage. If the control is to be
installed in a furnace, follow items 1 through 4 before
bringing the control or yourself in contact with the
furnace. Put all used and new controls into containers
before touching ungrounded objects.
7. An ESD service kit (available from commercial sources)
mayalsobeusedtopreventESDdamage.
312A
5
Page 6
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED ABOVE THE
312A
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
LOCATION
GENERAL
This multipoise furnace is shipped in packaged configuration.
Some assembly and modifications are required when used in any
of the four applications shown in Fig. 4.
NOTE:For high--altitude installations, the high--altitude
conversion kit MUST be installed at or above 5500 ft above sea
level. Obtain high--altitude conversion kit from your area
authorized distributor.
This furnace must:
Sbe installed so the electrical components are protected from
water.
S not be installed directly on any combustible material other than
wood flooring (refer to SAFETY CONSIDERATIONS).
S be located close to the chimney or vent and attached to an air
distribution system. Refer to Air Ducts section.
Sbe provided ample space for servicing and cleaning. Always
comply with minimum fire protection clearances shown on the
furnace clearance to combustible construction label.
!
WARNING
CARBON MONOXIDE POISONING AND UNIT
DAMAGE HAZARD
Failure to follow this warning could result in personal
injury or death, and furnace damage.
Corrosive or contaminated air may cause failure of parts
containing flue gas, which could leak into the living space.
Air for combustion must not be contaminated by halogen
compounds, which include fluoride, chloride, bromide, and
iodide. These elements can corrode heat exchangers and
shorten furnace life. Air contaminants are found in aerosol
sprays, detergents, bleaches, cleaning solvents, salts, air
fresheners, and other household products. Do not install
furnace in a corrosive or contaminated atmosphere. Make
sure all combustion and circulating air requirements are met,
in addition to all local codes and ordinances.
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
A02097
Fig. 4 -- Multipoise Orientations
The following types of furnace installations may require
OUTDOOR AIR for combustion due to chemical exposures:
S Commercial buildings
S Buildings with indoor pools
S Laundry rooms
S Hobby or craft rooms, and
S Chemical storage areas
If air is exposed to the following substances, it should not be used
for combustion air, and outdoor air may be required for
combustion:
S Permanent wave solutions
S Chlorinated waxes and cleaners
S Chlorine based swimming pool chemicals
S Water softening chemicals
S De-- icing salts or chemicals
S Carbon tetrachloride
S Halogen type refrigerants
S Cleaning solvents (such as perchloroethylene)
S Printing inks, paint removers, varnishes, etc.
S Hydrochloric acid
S Cements and glues
S Antistatic fabric softeners for clothes dryers
S Masonry acid washing materials
All fuel--burning equipment must be supplied with air for fuel
combustion. Sufficient air must be provided to avoid negative
pressure in the equipment room or space. A positive seal mu st be
made between the furnace cabinet and the return--air duct to
prevent pulling air from the burner area and from draft safeguard
opening.
6
Page 7
!
WARNING
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
When the furnace is installed in a residential garage, the
burners and ignition sources must be located at least 18
inches above the floor. The furnace must be located or
protected to avoid damage by vehicles. When the furnace is
installed in a public garage, airplane hangar, or other
building having a hazardous atmosphere, the furnace must
be installedin accordance withthe NFGC or
CAN/CSA--B149.1--05. (See Fig. 5.)
Fig. 6 -- Prohibit Installation on Back
!
CAUTION
A02054
18-IN. MINIMUM
TO BURNERS
A93044
Fig. 5 -- Installation in a Garage
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Do not install the furnace on its back or hang furnace with
control compartment facing downward. Safety control
operation will be adversely affected. Never connect
return-- air ducts to the back of the furnace. (See Fig. 6.)
PROPERTY DAMAGE HAZARD
Improper use or installation of this furnace may cause
premature component failure. This gas furnace may be used
for construction heat provided that:
--The furnace is permanently installed with all electrical
wiring, piping, venting and ducting installed according to
these installation instructions. A return air duct is provided,
sealed to the furnace casing, and terminated outside the
space containing the furnace. This prevents a negative
pressure condition as created by the circulating air blower,
causing a flame roll--out and/or drawing combustion
products into the structure.
--The furnace is controlled by a thermostat. It may not be
”hot wired” to provide heat continuously to the structure
without thermostatic control.
--Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and
other construction materials. It also prevents the
entrainment of drywall dust into combustion air, which can
cause fouling and plugging of furnace components.
--The temperature of the return air to the furnace is
maintained between 55_F(13_C) and 80_F(27_C), with
no evening setback or shutdown. The use of the furnace
while the structure is under construction is deemed to be
intermittent operation per our installation instructions.
--The air temperature rise is within the rated rise range on
the furnace rating plate, and the gas input rate has been set
to the nameplate value.
--The filters used to clean the circulating air during the
construction process must be either changed or thoroughly
cleaned prior to occupancy.
--The furnace, ductwork and filters are cleaned as necessary
to remove drywall dust and construction debris from all
HVAC system components after construction is completed.
--Verify proper furnace operating conditions including
ignition, gas input rate, air temperature rise, and venting
according to these installation instructions.
312A
LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with, or on the
downstream side of the unit to avoid condensation in the heat
exchangers. When installed parallel with the furnace, dampers or
other flow control must prevent chilled air from entering the
furnace. If the dampers are manually operated, they must be
7
Page 8
equipped with means to prevent operation of either unit unless
the damper is in the full--heat or full--cool position.
AIR FOR COMBUSTION AND
VENTILATION
Provisions for adequate combustion, ventilation, and dilution air
must be provided in accordance with:
U.S. installations: Section 8.3 of the NFGC, Air for Combustion
and Ventilation, and applicable provisions of the local building
codes.
Canadian installations: Part 8 of the CAN/CSA--B149.1--05,
Venting Systems and Air Supply for Appliances and all
authorities having jurisdiction.
!
CAUTION
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage.
312A
Air for combustion must not be contaminated by halogen
compounds, which include fluoride, chloride, bromide, and
iodide. These elements can corrode heat exchangers and
shorten furnace life. Air contaminants are found in aerosol
sprays, detergents, bleaches, cleaning solvents, salts, air
fresheners, and other household products.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
The operation of exhaust fans, kitchen ventilation fans,
clothes dryers, attic exhaust fans or fireplaces could create a
NEGATIVE PRESSURE CONDITION at the furnace.
Make--up air MUST be provided for the ventilation devices,
in addition to that required by the furnace. Refer to Carbon
Monoxide Poisoning Hazard warning in venting section of
these instructions to determine if an adequate amount of
make--up air is available.
The requirements for combustion and ventilation air depend upon
whether or not the furnace is located in a space having a volume
of at least 50 cubic feet per 1,000 Btuh input rating for all gas
appliances installed in the space.
S Spaces having less than 50 cubic feet per 1,000 Btuh require the
Outdoor Combustion Air Method.
S Spaces having at least 50 cubic feet per 1,000 Btuh may use the
Indoor Combustion Air, Standard or Known Air Infiltration
Method.
Outdoor Combustion Air
1. Provide the space with sufficient air for proper
combustion, ventilation, and dilution of flue gases using
permanent horihorizontal or vertical duct(s) or opening(s)
directly communicating with the outdoors or spaces that
freely communicate with the outdoors.
2. Fig. 7 illustrates how to provide TWO OUTDOOR
OPENINGS, one inlet and one outlet combustion and
ventilation air opening, to the outdoors.
a. One opening MUST commence within 12 in. (300 mm)
of the ceiling and the second opening MUST commence
within 12 in. (300 mm) of the floor.
b. Size openings and ducts per Fig. 7 and Table 2.
c. TWO HORIZONTAL DUCTS require 1 square inch of
free area per 2,000 Btuh (1,100 mm2/kW) of combined
input for all gas appliances in the space per Fig. 7 and
Tab le 2.
d. TWO OPENINGS OR VERTICAL DUCTS require 1
square inch of free area per 4,000 Btuh (550 mm2/kW)
for combined input of all gas appliances in the space per
Fig. 7 and Table 2.
3. ONE OUTDOOR OPENING requires:
a. 1 square inch offreearea per 3,000 Btuh (734 mm2/kW)
for combined input of all gas appliances in the space per
Tab le 2 a nd
b. Not less than the sum of the areas of all vent connectors
in the space.
Method
Table 2 – Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors
110,000+30,000= (140,000 divided by 4,000)=35.0 Sq. In. for each two Vertical Ducts or Openings
66,000+40,000= (106,000 divided by 3,000)=35.3 Sq. In. for a Single Duct or Opening
88,000+30,000= (118,000 divided by 2,000)=59.0 Sq. In. for each of two Horizontal Ducts
(1 SQ. IN./2,000 BTUH)
(1,100 SQ. MM/KW)
Free Area of
Opening and Duct
(Sq. In.)
Round Duct
(in. Dia)
(1 SQ. IN./3,000 BTUH)
(734 SQ. MM/KW)
Free Area of
Opening and Duct
(sq. In.)
8
Round Duct
(in. Dia)
TWO OPENINGS OR VERTICAL
Free Area of
Opening and Duct
(Sq. In.)
DUCTS
(1 SQ. IN./4,000 BTUH)
(550 SQ. MM/KW)
Round Duct
(In. Dia)
Page 9
DUCTS
*
OUTDOORS
TO
1 SQ IN.
PER 4000
BTUH*
CIRCULATING AIR
DUCTS
VENT THROUGH ROOF
12″ MAX
1 SQ IN.
PER 2000
BTUH*
DUCTS
TO
OUTDOORS
1 SQ IN.
PER 2000
BTUH*
12″ MAX
CIRCULATING AIR DUCTS
Minimum dimensions of 3 in.
Use any of the following
NOTE:
combinations of openings:
A & B C & D D & E F & G
B
A
AIR DUCTS
CIRCULATING
OPENINGS SHALL BE
OF COMBUSTION AIR
CLEARANCE IN FRONT
D
VENT
THROUGH
ROOF
AT LEAST 3 IN.
OUTDOORS
C
DUCT
TO
E
12″ MAX
F
G
1 SQ IN.
PER 4000
BTUH*
Fig. 7 -- Air for Combustion, Ventilation and Dilution for
Outdoors
12″
MAX
1 SQ IN.
PER
4000
BTUH*
OUTDOORS
1 SQ IN.
PER
4000
BTUH*
12″
MAX
A03174
12" MAX
1 SQ IN.
PER 1000
BTUH* IN DOOR
OR WALL
INTERIOR
HEATED
SPACE
CIRCULATING AIR DUCTS
* Minimum opening size is 100 sq in. with
minimum dimensions of 3 in.
†
Minimum of 3 in. . when type-B1 vent is used.
UNCONFINED
SPACE
6" MIN
(FRONT)
1 SQ IN.
PER 1000
BTUH* IN DOOR
OPENINGS SHALL BE AT LEAST 3 IN.
OR WALL
CLEARANCE IN FRONT OF COMBUSTION AIR
†
12" MAX
A03175
Fig. 8 -- Air for Combustion, Ventilation, and Dilution from
Indoors
312A
The opening shall commence within 12 in. (300 mm) of the
ceiling. Appliances in the space shall have clearances of at least 1
in. (25 mm) from the sides and back and 6 in. (150 mm) from the
front. The opening shall directly communicate with the outdoors
or shall communicate through a vertical or horizontal duct to the
outdoors or spaces (crawl or attic) that freely communicate with
the outdoors.
Indoor Combustion Air
Known --Air--Infiltration Rate
E NFPA & AGA Standard and
Methods
Indoor air is permitted for combustion, ventilation, and dilution,if the Standard or Known--Air--Infiltration Method is used.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in death and/or
personal injury.
Many homes require air to be supplied from outdoors for
furnace combustion, ventilation, and dilution of flue gases.
The furnace combustion air supply must be provided in
accordance with this instruction manual.
The Standard Method:
1. The space has no less volume than 50 cubic feet per 1,000
Btuh of the maximum input ratings for all gas appliances
installed in the space and
2. The air infiltration rate is not known to be less than 0.40
air changes per hour (ACH).
The Known Air Infiltration Rate Method shall be used, if the
infiltration rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The
minimum required volume of the space varies with the number of
ACH and shall be determined per Table 3 or Equations 1 and 2.
Determine the minimum required volume for each appliance in
the space and add the volumes together to get the total minimum
required volume for the space.
9
Page 10
Table 3 – Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors
Table 3--Minimum Space Volumes were determined by using
the following equations from the National Fuel Gas Code ANSI
Z223.1--2006/NFPA 54--2006, 9.3.2.2:
1. For other than fan-- assisted appliances, such as a draft
hood--equipped water heater:
312A
Volume
2. For fan--assisted applicances such as this furnace:
Volume
If:
= combined input of all other than fan--assisted
I
other
= combined input of all fan--assisted appliances in
I
fan
ACH = air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the Standard Method and
to the Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if:
a. There are no closable doors between rooms.
b. Combining spaces on same floor level. Each opening
shall have free area of at least 1 in.2/1,000 Btuh (2,000
mm2/kW) of the total input rating of all gas appliances
in the space, but not less than 100 in.2 (0.06 m2). One
opening shall commence within 12 in. (300 mm) of the
ceiling and the second opening shall commence within
12 in. (300 mm) of the floor. The minimum dimension
of air openings shall be at least 3 in. (80 mm). (See Fig.
8.)
c. Combining space on different floor levels. The volumes
of spaces on different floor levels shall be considered as
communicating spaces if connected by one or more
permanent openings in doors or floors having free area
of at least 2 in.2/1,000 Btuh (4,400 mm2/kW) of total
input rating of all gas appliances.
2. An attic or crawlspace may be considered a space that
freely communicates with the outdoors provided there are
adequate permanent ventilation openings directly to
outdoors having free area of at least 1--in.2/4,000 Btuh of
total input rating for all gas appliances in the space.
3. In spaces that use the Indoor Combustion Air Method,
infiltration should be adequate to provide air for
combustion, permanent ventilation and dilution of flue
gases. However, in buildings with unusually tight
(1,000s BTUH GAS INPUT RATE)
304050446688110132154
SpaceVolume(ft3)
21ft
=
Other
Fan
appliances in Btuh/hr
Btuh/hr
=
ACH
15ft
ACH
3
3
I
other
1000 Btu/hr
I
fan
1000 Btu/hr
A04002
A04003
Combination of Indoor and Outdoor
1. Indoor openings shall compy with the Indoor
2. Outdoor openings shall be located as required in the
3. Outdoor openings shall be sized as follows:
UPFLOW INSTALLATION
Bottom Return Air
These furnaces are shipped with bottom closure panel installed in
bottom return--air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,
perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom
2. Rotate bottom filler panel downward to release holding
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air
These furnaces are shipped with bottom closure panel installed in
bottom return--air opening. This panel MUST be in place when
only side return air is used.
NOTE: Side return--air openings can be used in UPFLOW and
most HORIZONTAL configurations. Do not use side return--air
openings in DOWNFLOW configuration.
FAN--- ASSISTED TOTAL
(1,000s BTUH GAS INPUT RATE)
construction, additional air MUST be provided using the
methods described in the Outdoor Combustion Air
Method section. Unusually tight construction is defined as
Construction with:
a. Walls and ceilings exposed to the outdoors have a
continuous, sealed vapor barrier. Openings are gasketed
or sealed and
b. Doors and openable windows are weatherstripped and
c. Other openings are caulked or sealed. These include
joints around window and door frames, between sole
plates and floors, between wall-- ceiling joints, between
wall panels, at penetrations for plumbing, electrical and
gas lines, etc.
Air
Combustion Air Method below and,
Outdoor Combustion Air Method mentioned previously
and,
a. Calculate the Ratio of all Indoor Space volume divided
by required volume for Indoor Combustion Air
Method below.
b. Outdoor opening size reduction Factor is 1 minus the
Ratio in a. above.
c. Minimum size of Outdoor openings shall be the size
required in Outdoor Combustion Air Method above
multiplied by reduction Factor in b. above. The
minimumdimension of air openingsshallbenot lessthan
3in.(80mm).
INSTALLATION
Inlet
filler panel. (See Fig. 9.)
tabs.
Inlet
10
Page 11
A02098
Fig. 9 -- Removing Bottom Closure Panel
Leveling Legs (If Desir
ed)
In upflow position with side return inlet(s), leveling legs may be
used. (See Fig. 10.) Install field--supplied, 5/16 X 1--1/2 in. (max)
corrosion --resistant machine bolts, washers and nuts.
NOTE: Bottom closure must be used when leveling legs are
used. It may be necessary to remove and reinstall bottom closure
panel to install leveling legs. To remove bottom closure panel, see
item 1 in Bottom Return Air Inlet section in Step 1 above.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in
each bottom corner of furnace. (See Fig. 10.)
2. For each leg, install nut on bolt and then install bolt and
nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install
flat washer if desired.)
4. Adjust outside nut to provide desired height, and tighten
inside nut to secure arrangement.
5. Reinstall bottom closure panel if removed.
5
⁄16″
5
⁄16″
1 3⁄4″
3
⁄4″
1
5
⁄16″
5
⁄16″
3
1
⁄4″
3
1
⁄4″
A02071
Fig. 10 -- Leveling Legs
DOWNFLOW INSTALLA
TION
NOTE: For downflow applications, this furnace is approved for
use on combustible flooring when any one of the following 3
accessories are used:
S Special Base, KGASB
S Cased Coil Assembly Part No. CD5 or CK5
S Coil Box Part No. KCAKC
1. Determine application being installed from Table 4.
2. Construct hole in floor per Table 4 and Fig. 11.
3. Construct plenum to dimensions specified in Table 4 and
Fig. 11.
4. If downflow subbase, KGASB is used, install as shown in
Fig. 12. If Coil Assembly Part No. CD5 or CK5 or Coil
Box Part No. KCAKC is used, install as shown in Fig. 13.
NOTE: It is recommended that the perforated supply--air duct
flanges be completely folded over or removed from furnace when
installing the furnace on a factory --supplied cased coil or coil box.
To remove the supply--air duct flange, use wide duct pliers or
hand seamers to bend flange back and forth until it breaks off. Be
careful of sharp edges. (See Fig. 14.)
Bottom Return Air
Inlet
These furnaces are shipped with bottom closure panel installed in
bottom return--air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,
perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom
filler panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding
tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
HORIZONTAL INSTALLA
TION
The furnace can be installed horizontally in an attic or crawl space
on either the left--hand (LH) or right--hand (RH) side. The furnace
can be hung from floor joists, rafters or trusses or installed on a
non--combustible platform, blocks, bricks or pad.
!
WARNING
FIRE, EXPLOSION, AND CARBON MONOXIDE
POISONING HAZARD
Failure to follow this warning could result in personal
injury, death, or property damage.
Do not install the furnace on its back or hang furnace with
control compartment facing downward. Safety control
operation will be adversely affected. Never connect
return-- air ducts to the back of the furnace.
Suspended Furnace Support
The furnace may be supported under each end with threaded rod,
angle iron or metal plumber’s strap as shown. (See Fig. 15 and
16.) Secure angle iron to bottom of furnace as shown.
Heavy--gauge sheet metal straps (plumber’s straps) may be used
to suspend the furnace from each bottom corner. To prevent
screws from pulling out, use 2 #8 x .--in. screw into the side and 2
#8 x .--in. screw in the bottom of the furnace casing for each strap.
(See Fig. 15 and 16.)
If the screws are attached to ONLY the furnace sides and not the
bottom, the straps must be vertical against the furnace sides and
not pull away from the furnace sides, so that the strap attachment
screws are not in tension (are loaded in shear) for reliable support.
Platform Furnace
Support
Construct working platform at location where all required furnace
clearances are met. (See Fig. 2 and 17.) For furnaces with 1--in.
clearance requirement on side, set furnace on non--combustible
blocks, bricks or angle iron. For crawlspace installations, if the
furnace is not suspended from the floor joists, the ground
312A
11
Page 12
underneath furnace must be level and the furnace set on blocks or
bricks.
Roll--Out Pr
otection
Provide a minimum 17--3/4 in. X 22 in. piece of sheet metal for
flame roll--out protection in front of burner area for furnaces
closer than 12 inches above the combustible deck or suspended
furnaces closer than 12 inches to joists. The sheet metal MUST
extend underneath the furnace casing by 1 in. with the door
removed.
The bottom closure panel on furnaces of widths 17--1/2 in. and
larger may be used for flame roll--out protection when bottom of
furnace is used for return air connection. See Fig. 17 for proper
orientation of roll--out shield.
Bottom Return Air
Inlet
These furnaces are shipped with bottom closure panel installed in
bottom return--air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,
perform the following:
312A
1. Tilt or raise furnace and remove 2 screws holding bottom
filler panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding
tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air
Inlet
These furnaces are shipped with bottom closure panel installed in
bottom return--air opening. This panel MUST be in place when
side return air inlet(s) are used without a bottom return air inlet.
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
A096285
Fig. 12 -- Furnace, Plenum, and Subbase installed on a
Combustible Floor
A
PLENUM
OPENING
B
OPENING
D
FLOOR
C
Fig. 11 -- Floor and Plenum Opening Dimensions
A096283
FURNACE
CD5 OR CK5
COIL ASSEMBLY
OR KCAKC
COIL BOX
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
A04140
A04140
Fig. 13 -- Furnace, Plenum, and Coil Assembly or Coil Box
Installed on a Combustible Floor
12
Page 13
FURNACE
D
CASING
WIDTH
14–3/16
17–1/2
21
24--- 1/2
Table 4 – Opening dimensions (In.)
APPLICATION
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring (KGASB
subbase not required)
Downflow applications on combustible flooring
(KGASB subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on combustible flooring
(KGASB subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on combustible flooring
(KGASB subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on Combustible flooring
(KGASB subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box
(KGASB subbase not required)
PLENUM OPENINGFLOOR OPENING
ABCD
12--- 11/1621--- 5/813---5/1622--- 1/4
12--- 9/161913--- 3/1619--- 5/8
11--- 13/161913 --- 7/1620 ---5/8
12--- 5/161913--- 5/1620
1621--- 5/816 ---5/822---1/4
15--- 7/81916---1/219 --- 5/8
15--- 1/81916---3/420 --- 5/8
15--- 1/21916---1/220
19--- 1/221 --- 5/820--- 1/822 --- 1/4
19--- 3/8192019--- 5/8
18--- 5/81920---1/420 --- 5/8
19192020
2321--- 1/823 ---5/822---1/4
22--- 7/81923---1/219 --- 5/8
22--- 1/81923---3/420 --- 5/8
22--- 1/21923---1/220
312A
UPFLO
90û
120û
MIN
WOWNFLOW
YES
YES
NOT
RECOMMENDED
D
120û
MIN
Fig. 14 -- Duct Flanges
YES
YES
NOT
RECOMMENDED
13
HORIZONTAL
90û
120û
MIN
YES
YES
NOT
RECOMMENDE
A02329
Page 14
OUTER DOOR
ASSEMBLY
1
/4
" THREADED ROD
4 REQ.
312A
8" MIN FOR DOOR
REMOVAL
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS
REQ. PER ROD
Fig. 15 -- Horizontal Unit Suspension
SECURE ANGLE
IRON TO BOTTOM
OF FURNACE WITH
3 #8 x
TYPICAL FOR 2 SUPPORTS
1
1
/4
1" SQUARE, 1
OR UNI-STRUT MAY BE USED
" x 1
1
/4
" x
/4
" ANGLE IRON
3
/4
" SCREWS
METHOD 2
USE (42) #8 x 3/4 SHEET
METAL SCREWS TYPICAL
FOR EACH STRAPS.THE
STRAPS SHOULD BE
VERTICAL AGAINST THE
FURNACE SIDES AND NOT
PULL AWAY FROM THE
FURNACE SIDES.
A02345
METHOD 1
FOLD ALL STRAPS UNDER
FURNACE AND SECURE WTH
(42) #8 x 3/4 SHEET METAL SCREWS
(2 SCREWS IN SIDE AND 2 SCREWS
IN BOTTOM).
Fig. 16 -- Horizontal Suspension with Straps
14
A03176
Page 15
LINE CONTACT ONLY PERMISSIBLE BETWEEN
LINES FORMED BY INTERSECTIONS OF
THE TOP AND TWO SIDES OF THE FURNACE
JACKET AND BUILDING JOISTS,
STUDS, OR FRAMING.
GAS
ENTRY
TYPE-B
VENT
17 3/4
″ OVER ALL
4 3/4
″ UNDER DOOR
1″ UNDER FURNACE
EXTEND OUT 12″ OUT
FROM FACE OF DOOR
17 3/4
22
EQUIPMENT MANUAL
SHUT-OFF GAS VALVE
SEDIMENT
TRAP
UNION
SHEET
METAL
Fig. 17 -- Typical Attic Installation
Not all horizontal furnaces are approved for side return air
connections. (See Fig. 20.)
FILTER
ARRANGEMENT
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury, or death.
Never operate a furnace without a filter or with filter access
door removed.
There are no provisions for an internal filter rack in these
furnaces. An external filter rack is required.
This furnace is shipped with a factory--supplied Media Filter
Cabinet. The Media Filter Cabinet uses either a factory--supplied
standard 1--inch filter or 4--inch wide Media Filter which can be
purchased separately.
Refer to the instructions supplied with Media Cabinet for
assembly and installation options.
DUCTS
AIR
General Requir
ements
The duct system should be designed and sized according to
accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and
Air Conditioning Contractors National Association (SMACNA)
or American Society of Heating, Refrigerating and Air
Conditioning Engineers (ASHRAE) or consult The Air Systems
Design Guidelines reference tables available from your local
distributor. The duct system should be sized to handle the
required system design CFM at the design external static pressure.
The furnace airflow rates are provided in Table 5--Air Delivery
CFM (With Filter).
When a furnace is installed so that the supply ducts carry air
circulated by the furnace to areas outside the space containing the
furnace, the return air shall also be handled by duct(s) sealed to
the furnace casing and terminating outside the space containing
the furnace.
6″ MIN*
″
″
30-IN. MIN
WORK AREA
* WHEN USED WITH
SINGLE WALL VENT
CONNECTIONS
312A
A03177
Secure ductwork with proper fasteners for type of ductwork used.
Seal supply-- and return--duct connections to furnace with code
approved tape or duct sealer.
NOTE: Flexible connections should be used between ductwork
and furnace to prevent transmission of vibration.
Ductwork passing through unconditioned space should be
insulated to enhance system performance. When air conditioning
is used, a vapor barrier is recommended.
Maintain a 1--in. clearance from combustible materials to supply
air ductwork for a distance of 36 in. horizontally from the
furnace. See NFPA 90B or local code for further requirements.
Ductwork Acoustical Tr
NOTE: Metal duct systems that do not have a 90_ elbow and 10
ft of main duct to the first branch take--off may require internal
acoustical lining. As an alternative, fibrous ductwork may be used
if constructed and installed in accordance with the latest edition of
SMACNA construction standard on fibrous glass ducts. Both
acoustical lining and fibrous ductwork shall comply with NFPA
90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
Supply Air
Connections
For a furnace not equipped with a cooling coil, the outlet duct
shall be provided with a removable access panel. This opening
shall be accessible when the furnace is installed and shall be of
such a size that the heat exchanger can be viewed for possible
openings using light assistance or a probe can be inserted for
sampling the air stream. The cover attachment shall prevent leaks.
Upflow and Horizontal
Connect supply--air duct to flanges on furnace supply--air outlet.
Bend flange upward to 90_ with wide duct pliers. (See Fig. 14.)
The supply--air duct must be connected to ONLY the furnace
supply--outlet--air duct flanges or air conditioning coil casing
(when used). DO NOT cut main furnace casing side to attach
supply air duct, humidifier, or other accessories. All accessories
MUST be connected to duct external to furnace main casing.
eatment
Furnaces
15
Page 16
Table 5 – Air Delivery -- CFM (With Filter)*
312A
FURNACE
SIZE
045--- 08 /
024045
045--- 12 /
036045
070--- 081 /
024070
070--- 12 /
036070
070--- 16 /
048070
090--- 14 /
042090
090--- 16 /
048090
090--- 20 /
060090
110--- 12 /
036110
110--- 16 /
048110
RETURN---AIR
INLET
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom Only
Both Side or 1
Side & Bottom
1Side Only
Bottom or
Side(s)
Bottom or
Side(s)
SPEED
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High
M e d --- L ow
Low
High
M e d ---
High Me-
dium
M e d --- L ow
Low
EXTERNAL STATIC PRESSURE (IN. WC)
0.10.20.30.40.50.60.70.80.91.0
1120
930
820
725
1465
1295
1150
1030
860
1140
915
795
690
1440
1180
1015
885
695
1840
1610
1460
1260
1065
1650
1515
1385
1205
2060
1710
1470
1260
1030
2380
2185
1905
1595
1340
2485
2175
1845
1540
1280
2420
2160
1850
1530
1290
1625
1510
1360
1195
2055
1750
1545
1300
1050
1075
890
785
690
1400
1260
1120
1010
835
1105
885
770
665
1400
1165
1020
885
700
1790
1575
1430
1240
1040
1600
1485
1360
1180
2000
1695
1475
1365
1025
2295
2115
1865
1565
1310
2415
2130
1815
1515
1250
2345
2110
1815
1490
1250
1575
1470
1335
1180
1990
1725
1525
1290
1045
1020
850
750
655
1325
1210
1085
980
810
1055
855
740
630
1355
1150
1010
880
700
1730
1535
1400
1215
1015
1535
1440
1320
1160
1930
1665
1450
1245
1020
2205
2045
1815
1530
1280
2330
2070
1770
1475
1220
2265
2045
1765
1455
1220
1515
1415
1295
1155
1910
1670
1490
1275
1015
960
805
700
605
1250
1155
1040
945
780
1010
825
700
590
1300
1125
990
865
690
1670
1485
1360
1180
985
1465
1380
1260
1120
1835
1585
1390
1225
990
2105
1960
1740
1485
1225
2230
2000
1720
1435
1190
2165
1960
1710
1420
1190
1445
1355
1250
1115
1815
1605
1445
1235
975
895
750
650
555
1175
1090
985
895
745
955
785
655
550
1240
1085
965
845
670
1605
1435
1315
1145
955
1385
1300
1195
1065
1755
1480
1335
1165
940
2005
1875
1670
1430
1170
2135
1930
1655
1385
115
2070
1885
1635
1375
115
1355
1285
1180
1065
1695
1515
1355
1165
935
815
680
585
495
1085
1015
920
835
700
885
725
600
475
1170
1030
925
815
640
1530
1370
1260
110
915
1285
1220
1120
1005
1620
1390
1230
1090
890
1900
1770
1590
1355
1120
2030
1840
1580
1335
1105
1960
1790
1560
1320
1110
1260
1185
1100
980
1575
1400
1260
1085
880
720
600
505
405
980
930
835
765
635
815
655
510
415
1090
970
875
770
600
1450
1305
1205
1040
875
1175
1115
1025
925
1490
1245
1120
995
810
1775
1655
1490
1275
1040
1920
1740
1500
1270
1035
1850
1695
1480
1250
1040
1165
1070
985
860
1425
1255
1135
1005
815
605
500
400
305
860
830
740
685
555
715
530
420
340
1000
890
800
700
540
1370
1230
1130
985
825
1055
990
915
810
1315
1110
1005
880
720
1650
1535
1390
1160
955
1790
1620
1395
1175
945
1720
1570
1380
1160
950
990
890
810
740
1230
1120
1020
895
715
455
345
235
--- ---
725
700
620
570
445
545
420
325
245
890
785
700
605
460
1275
1145
1055
915
765
895
830
710
630
1115
955
855
750
615
1510
1400
1245
1055
850
1645
1495
1270
1045
845
1570
1445
1250
1055
835
785
725
670
605
1090
975
880
750
610
340
195
--- ---
--- ---
560
545
510
345
260
390
280
--- ---
--- ---
745
645
560
475
345
1170
1055
965
835
695
645
600
565
510
910
775
690
600
500
1335
1240
1110
920
750
1485
1345
1090
915
745
1420
1305
1110
905
740
595
530
475
410
910
785
750
620
515
16
Page 17
High
M e d ---
Bottom Only
110--- 22 /
066110
*A filter is required for each return---air inlet. Airflow performance included 1---in. washable filter media such as contained in factory---authorized accessory filter
rack. To determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.
--- --- Indicates unstable operating conditions.
Bottom Sides or
1 Side & Bottom
1Side Only
High Me-
dium
M e d --- L ow
Low
High
M e d ---
High
High
M e d ---
High Me-
dium
M e d --- L ow
Low
2530
2225
1895
1565
1320
--- ---
2205
2485
2155
1830
1520
1275
2460
2190
1885
1555
1295
--- ---
2175
2430
2135
1830
1505
1260
2380
2135
1865
1535
1265
2415
2120
2360
2100
1810
1490
1240
2285
2075
1820
1505
1235
2330
2065
2270
2040
1780
1470
1210
2200
1995
1770
1465
1205
2235
1975
2175
1970
1730
1430
1180
2085
1910
1700
1410
1160
2125
1900
2070
1885
1665
1385
1135
1970
1805
1610
1350
1105
1995
1790
1950
1790
1595
1330
1090
1835
1695
1520
1265
1035
1860
1685
1825
1680
1505
1250
1025
1695
1565
1410
1175
950
1735
1580
1685
1560
1395
1165
930
1545
1430
1290
1050
870
1605
1460
1535
1420
1275
1055
840
312A
17
Page 18
Table 5 -- Air Delivery -- CFM (With Filter)* (Cont.)
FURNACE
SIZE
135--- 16 /
048135
135--- 22 /
066135
312A
155--- 20 /
060155
*A filter is required for each return---air inlet. Airflow performance included 1---in. washable filter media such as contained in factory---authorized accessory filter
rack. To determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.
--- --- Indicates unstable operating conditions.
RETURN---AIR
INLET
Bottom
or
Side(s)
Bottom
Only
Bottom Sides
or
1 Side & Bottom
1SideOnly
Bottom Only
Both Sides Or 1
Side & Bottom
1SideOnly
SPEED
High
M e d --- H ig h
M e d --- L ow
Low
High
M e d --- H ig h
M e d --- L ow
Low
High
M e d --- H ig h
M e d --- L ow
Low
High
M e d --- H ig h
M e d --- L ow
Low
High
M e d --- H ig h
M e d --- L ow
Low
High
M e d --- H ig h
High
M e d --- H ig h
0.10.20.30.40.50.60.70.80.91.0
2090
1790
1545
1325
2485
2195
1880
1640
--- --2180
1880
1640
2320
2125
1845
1640
2465
2115
1800
1570
--- --2155
--- --2140
2010
1755
1525
1320
2400
2150
1850
1635
--- --2145
1850
1635
2250
2065
1825
1620
2430
2105
1790
1565
--- --2135
--- --2095
NOTE: For horizontal applications, the top--most flange may be
bent past 90_ to allow the evaporator coil to hang on the flange
temporarily while the remaining attachment and sealing of the
EXTERNAL STATIC PRESSURE (IN. WC)
1930
1705
1500
1295
2310
2090
1820
1615
2385
2060
1820
1615
2155
1995
1765
1580
2375
2075
1770
1550
2375
2095
2260
2040
1835
1640
1450
1265
2215
2000
1780
1585
2305
2010
1780
1585
2055
1910
1710
1540
2305
2030
1735
1525
2285
2040
2180
1975
1710
1550
1380
1210
2110
1920
1715
1530
2195
1945
1715
1530
1970
1815
1650
1485
2230
1980
1695
1495
2200
1975
2085
1890
1590
1465
1315
1150
2000
1825
1635
1465
2085
1865
1635
1465
1855
1710
1570
1410
2110
1910
1640
1445
2105
1895
1975
1810
1470
1360
1215
995
1880
1720
1540
1370
1960
1765
1540
1370
1725
1610
1475
1330
2000
1830
1570
1370
1995
1790
1865
1705
1335
1210
1005
865
1725
1565
1415
1255
1825
1660
1415
1255
1600
1490
1370
1220
1865
1725
1465
1270
1870
1685
1740
1595
horizontal furnaces are approved for side return air connections.
(See Fig. 20.)
PIPING
GAS
coil are performed.
Downflow
Connect supply--air duct to supply--air outlet on furnace. Bend
flange inward past 90_ with wide duct pliers. (See Fig. 14.) The
supply--air duct must be connected to ONLY the furnace
supplyoutlet or air conditioning coil casing (when used). When
installed on combustible material, supply--air duct must be
connected to ONLY the accessory subbase, KGASB0201ALL, or
a factory approved air conditioning coil casing. DO NOT cut
main furnace casing to attach supply side air duct, humidifier, or
other accessories. All accessories MUST be connected to duct
Furnaces
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection
of leaks to check all connections.
external to furnace casing.
Return Air
FIRE HAZARD
Failure to follow this warning could cause personal injury,
death and/or property damage.
Never connect return--air ducts to the back of the furnace.
Connections
!
WARNING
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Use proper length of pipe to avoid stress on gas control
manifold and a gas leak.
Follow instructions below.
1025
945
855
745
1535
1405
1290
1150
1670
1515
1290
1150
1450
1340
1240
1080
1725
1590
1345
1175
1730
1550
1605
1480
835
785
670
540
1355
1255
1160
1040
1465
1325
1160
1040
1280
1175
1100
960
1545
1425
1225
1070
1570
1400
1455
1325
Downflow Furnaces
The return--air duct must be connected to return--air opening
(bottom inlet) as shown in Fig. 1. DO NOT cut into casing sides
(left or right). Side opening is permitted for only upflow and most
horizontal furnaces. Bypass humidifier connections should be
made at ductwork or coil casing sides exterior to furnace. (See
Fig. 19.) Upflow and Horizontal Furnaces The return--air duct
must be connected to bottom, sides (left or right), or a
combination of bottom and side(s) of main furnace casing as
shown in Fig. 1. Bypass humidifier may be attached into unused
return air side of the furnace casing. (See Fig. 18 and 20.) Not all
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to protect gas valve inlet from water and debris
could result in death, personal injury and/or property
damage.
Gas valve inlet and/or inlet pipe must remain capped until
gas supply line is permanently installed to protect the valve
from moisture and debris. Also, install a sediment trap in the
gas supply piping at the inlet to the gas valve.
18
Page 19
Fig. 18 -- Upflow Return Air Configurations and Restrictions
Fig. 19 -- Downflow Return Air Configurations and Restrictions
A02075
A02163
312A
Fig. 20 -- Horizontal Return Air Configurations and Restrictions
19
A02162
Page 20
Gas piping must be installed in accordance with national and
local codes. Refer to current edition of NFGC in the U.S. and the
CAN/CSA--B149.1--05 in Canada.
Table 6 – Maximum Capacity of Pipe*
NOMINAL
IRON
PIPE
SIZE
(IN.)
1/20.622175120978273
3/40.824360250200170151
11.049680465375320285
1 --- 1 / 41.3801400950770660580
1 --- 1 / 21.6102100 1460 1180990900
* Cubic ft of natural gas per hr for gas pressures of 0.5 psig (14 --- in. wc)
or less and a pressure drop of 0.5 ---in wc (based on a 0.60 specific gravity
gas). Ref: Table 12.2 ANSI Z223 ---2006/NFPA 54---2006.
INTERNAL
DIAMETER
(IN.)
LENGTH OF PIPE (FT)
1020304050
Installations must be made in accordance with all authorities
having jurisdiction. If possible, the gas supply line should be a
separate line running directly from meter to furnace.
312A
NOTE: In the state of Massachusetts:
1. Gas supply connections MUST be performed by a
licensed plumber or gas fitter.
2. When flexible connectors are used, the maximum length
shall not exceed 36 inches (915 mm).
3. When lever handle type manual equipment shutoff valves
are used, they shall be T--handle valves.
4. The use of copper tubing for gas piping is NOT approved
by the state of Massachusetts.
Refer to Table 6 for recommended gas pipe sizing. Risers must be
used to connect to furnace and to meter. Support all gas piping
with appropriate straps, hangers, etc. Use a minimum of 1 hanger
every 6 ft Joint compound (pipe dope) should be applied
sparingly and only to male threads of joints. Pipe dope must be
resistant to the action of propane gas.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
If local codes allow the use of a flexible gas appliance
connector, always use a new listed connector. Do not use a
connector which has previously served another gas
appliance. Black iron pipe shall be installed at the furnace
gas control valve and extend a minimum of 2 in. outside the
furnace.
!
CAUTION
test pressure DOES NOT exceed maximum 0.5 psig (14--in. wc)
stated on gas control valve. (See Fig. 54.) Some installations
require gas entry on right side of furnace (as viewed in upflow).
(See Fig. 21 and 22.)
A05028
Fig. 21 -- Right Side Gas Entry Example 1
90° Elbow
2" Nipple
Street Elbow
Gas Valve
A02327
Fig. 22 -- Right Side Gas Entry Example 2
Install a sediment trap in riser leading to furnace as shown in Fig.
23. Connect a capped nipple into lower end of tee. Capped nipple
should extend below level of furnace gas controls. Place a ground
joint union between furnace gas control valve manifold and
exterior manual equipment gas shutoff valve.
GAS
SUPPLY
MANUAL
SHUTOFF
VALV E
(REQUIRED
SEDIMENT
TRAP
UNION
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in furnace damage.
Connect gas pipe to furnace using a backup wrench to
avoid damaging gas controls and burner misalignment.
An accessible manual equipment shutoff valve MUST be
installed external to furnace casing and within 6 ft of furnace. A
1/8--in. NPT plugged tapping, accessible for test gauge
connection, MUST be installed immediately upstream of gas
supply connection to furnace and downstream of manual
equipment shutoff valve.
NOTE:The furnace gas control valve inlet pressure tap
connection is suitable to use as test gauge connection providing
A02035
Fig. 23 -- Typical Gas Pipe Arrangement
A 1/8--in. NPT plugged tapping, accessible for test gauge
connection, MUST be installed immediately upstream of gas
supply connection to furnace and downstream of manual
equipment shutoff valve.
20
Page 21
NOTE 2
WC YRG
W2
COM
W/W1
NOTE 1
Y/Y2
R
G
NOTES: 1.
BLK
WHT
GND
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
BLK
WHT
JUNCTION
BOX
FIVE
WIRE
THREE-WIRE
HEATING-
ONLY
CONTROL
BOX
FURNACE
24-VOLT
TERMINAL
BLOCK
Fig. 24 -- Field Wiring Diagram
Piping should be pressure and leak tested in accordance with
NFGC in the United States or CAN/CSA--B149.1--05 in Canada,
local, and national plumbing and gas codes before the furnace has
been connected. After all connections have been made, purge
lines and check for leakage at furnace prior to operating furnace.
If pressure exceeds 0.5 psig (14--in. wc), gas supply pipe must be
disconnected from furnace and capped before and during supply
pipe pressure test. If test pressure is equal to or less than 0.5 psig
(14--in. wc), turn off electric shutoff switch located on furnace gas
control valve and accessible manual equipment shutoff valve
before and during supply pipe pressure test. After all connections
have been made, purge lines and check for leakage at furnace
prior to operating furnace.
The gas supply pressure shall be within the maximum and
minimum inlet supply pressures marked on the rating plate with
the furnace burners ON and OFF.
ELECTRICAL
CONNECTIONS
FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-VOLT WIRING
1-STAGE
THERMOSTAT
TERMINALS
CONDENSING
UNIT
Connect Y/Y2-terminal as shown for proper operation.
Some thermostats require a "C" terminal connection as shown.
2.
If any of the original wire, as supplied, must be replaced, use
3.
same type or equivalent wire.
!
FIELD-SUPPLIED
FUSED DISCONNECT
208/230- OR
460-VOLT
THREE
PHASE
208/230VOLT
SINGLE
GND
PHASE
WARNING
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal
injury, death, or property damage.
The cabinet MUST have an uninterrupted or unbroken
ground according to NEC ANSI/NFPA 70--2006 and
Canadian Electrical Code CSA C22.1 or local codes to
minimize personal injury if an electrical fault should occur.
This may consist of electrical wire, conduit approved for
electrical ground or a listed, grounded power cord (where
permitted by local code) when installed in accordance with
existing electrical codes. Refer to the power cord
manufacturer’s ratings for proper wire gauge. Do not use
gas piping as an electrical ground.
312A
A95236
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Blower access panel door switch opens 115--v power to
control. No component operation can occur. Do not bypass
or close switch with panel removed.
See Fig. 24 for field wiring diagram showing typical field 115--v
wiring. Check all factory and field electrical connections for
tightness.
Field--supplied wiring shall conform with the limitations of 63_F
(33_C) rise.
!
CAUTION
FURNACE MAY NOT OPERATE HAZARD
Failure to follow this caution may result in intermittent
furnace operation.
Furnace control must be grounded for proper operation or
else control will lock out. Control must remain grounded
through green/yellow wire routed to gas valve and manifold
bracket screw.
115 -- V WIRING
Verify that the voltage, frequency, and phase correspond to that
specified on unit rating plate. Also, check to be sure that service
provided by utility is sufficient to handle load imposed by this
equipment. Refer to rating plate or Table 7 for equipment
electrical specifications.
* Permissible limits of the voltage ran ge at which the unit operates satisfactorily.
312A
# Unit ampacity = 125% of lar gest operating component’s full load amps plus 100% of all other potential operating components (EAC, humidifier,
etc.) full load amps.
{ Time---delay type is recommended.
} Length shown is as measured 1 way along wire path between unit and service panel for maximum 2% voltage drop.
U.S. Installations: Make all electrical connections in accordance
with National Electrical Code (NEC) ANSI/NFPA 70--2006 and
any local codes or ordinances that might apply.
Canadian Installations: Make all electrical connections in
OPERATING VOLTAGE
RANGE
MAX*MIN.*
MAX
UNIT
AMPS
FURNACE
SIZE
UNIT
AMPACITY#
4. Fasten J--Box to casing with the two screws removed in
Step 1.
5. Route J-- Box wires within furnace away from sharp edges,
rotating parts, and hot surfaces.
MAXIMUM
WIRE
LENGTH
(ft)‡
MAXIMUM
FUSE OR
CKT BKR
AMPS†
accordance with Canadian Electrical Code CSA C22.1 or
authorities having jurisdiction.
MINIMUM
WIRE
GAUGE
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death, or property damage.
Do not connect aluminum wire between disconnect switch
and furnace. Use only copper wire.
Use a separate branch electrical circuit with a properly sized fuse
or circuit breaker for this furnace. See Table 7 for wire size and
fuse specifications. A readily accessible means of electrical
disconnect must be located within sight of the furnace.
NOTE: Proper polarity must be maintained for 115--v wiring. If
polarity is incorrect, control LED status indicator light will flash
rapidly and furnace will NOT operate.
J--BOX RELOCA
TION
NOTE: If factory location of J--Box is acceptable, go to next
section (ELECTRICAL CONNECTION TO J--BOX).
NOTE: On 14” wide casing models, the J--Box shall not be
relocated to other side of furnace casing when the vent pipe is
routed within the casing.
1. Remove and save two screws holding J--Box. (See Fig.
25.)
NOTE: The J--Box cover need not be removed from the J--Box
in order to move the J--Box. Do NOT remove green ground
screw inside J--Box. The ground screw is not threaded into the
casing flange and can be lifted out of the clearance hole in casing
while swinging the front edge of the J--box outboard of the
casing.
2. Cut wire tie on loop in furnace wires attached to J--Box.
3. Move J--Box to desired location.
TWO
A02099
Fig. 25 -- Relocating J--Box
ELECTRICAL CONNECTION TO
J--BOX
Field-- Supplied Electrical Box on Furnace J--Box Bracket. See
Fig. 26.
1. Remove cover from furnace J--Box.
2. Attach electrical box to furnace J--Box bracket with at least
two field--supplied screws through holes in electrical box
into holes in bracket. Use blunt--nose screws that will not
pierce wire insulation.
3. Route furnace power wires through holes in electrical box
and J--Box bracket, and make field--wire connections in
electrical box. Use best practices (NEC in U.S. and CSA
C22.1 in Canada) for wire bushings, strain relief, etc.
4. Route and secure field ground wire to green ground screw
on J--Box bracket.
5. Connect line voltage leads as shown in Fig. 24.
22
Page 23
6. Reinstall cover to J--Box. Do not pinch wires between
cover and bracket.
Electrical Box on Furnace Casing Side. See Fig.
!
WARNING
FIRE OR ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury, death, or property damage.
If field--supplied manual disconnect switch is to be mounted
on furnace casing side, select a location where a drill or
fastener cannot damage electrical or gas components.
Fig. 26 -- Field--Supplied Electrical Box on Furnace Casing
1. Select and remove a hole knockout in the casing where the
electrical box is to be installed.
NOTE: Check that duct on side of furnace will not interfere with
installed electrical box.
2. Remove the desired electrical box hole knockout and
position the hole in the electrical box over the hole in the
furnace casing.
3. Fasten the electrical box to casing by driving two
fieldsupplied screws from inside electrical box into casing
steel.
4. Remove and save two screws holding J--Box. (See Fig.
25.)
26.
A03221
5. Pull furnace power wires out of 1/2--inch diameter hole in
J--Box. Do not loosen wires from strain--relief wire--tie on
outside of J--Box.
6. Route furnace power wires through holes in casing and
electrical box and into electrical box.
7. Pull field power wires into electrical box.
8. Remove cover from furnace J--Box.
9. Route field ground wire through holes in electrical box
and casing, and into furnace J--Box.
10. Reattach furnace J--Box to furnace casing with screws
removedinStep4.
11. Secure field ground wire to J--Box green ground screw.
12. Complete electrical box wiring and installation. Connect
line voltage leads as shown in Fig. 24. Use best practices
(NEC in U.S. and CSA C22.1 in Canada) for wire
bushings, strain relief, etc.
13. Reinstall cover to J--Box. Do not pinch wires between
cover and bracket.
POWER CORD INSTALLATION IN FURNACE
NOTE: Power cords must be able to handle the electrical
requirements listed in Table 7. Refer to power cord
manufacturer’s listings.
1. Remove cover from J--Box.
2. Route listed power cord through 7/8--inch diameter hole in
J--Box.
3. Secure power cord to J--Box bracket with a strain relief
bushing or a connector approved for the type of cord used.
4. Secure field ground wire to green ground screw on J--Box
bracket.
5. Connect line voltage leads as shown in Fig. 24.
6. Reinstall cover to J--Box. Do not pinch wires between
cover and bracket.
BX. CABLE INSTALLATION IN FURNACE
1. Remove cover from J--Box.
2. Route BX cable into 7/8--inch diameter hole in J--Box.
3. Secure BX cable to J--Box bracket with connectors
approved for the type of cable used.
4. Secure field ground wire to green ground screw on J--Box
bracket.
5. Connect line voltage leads as shown in Fig. 24.
6. Reinstall cover to J--Box. Do not pinch wires between
cover and bracket.
24--V
WIRING
Make field 24--v connections at the 24--v terminal strip. (See Fig.
34.) Connect terminal Y/Y2 as shown in Fig. 27--33 for proper
cooling operation. Use only AWG No. 18, color--coded, copper
thermostat wire.
The 24--v circuit contains an automotive--type, 3--amp. fuse
located on the control. Any direct shorts during installation,
service, or maintenance could cause this fuse to blow. If fuse
replacement is required, use ONLY a 3--amp. fuse of identical
size.
J--BOX
J--BOX
312A
23
Page 24
312A
See notes 2, 5, 8, 10, 11 and 12
on the page following these figures
Fig. 27 -- Two--Stage Furnace with Two--Speed Air
Conditioner
A03179
See notes 1, 2, 3, 4, 6, 8, 9, 10, 12, 13 and 15
on the page following these figures
A03178
Fig. 29 -- Two--Stage Furnace with Two--Speed Heat Pump
(Dual Fuel)
See notes 1, 2, 4, 6, 7, 9, 10, 11, and 15
on the page following these figures
A03180
Fig. 28 -- Two--Stage Furnace with Single--Speed Heat Pump
(Dual Fuel)
See notes 1, 2, 4, 11, 14, 15, and 16
on the page following these figures
Fig. 30 -- Dual Fuel Thermostat with Two--Stage Furnace
and Single--Speed Heat Pump
24
A03181
Page 25
7
See notes 1, 2, 3, 4, 12, 13, 14, 15, and 17
on the page following these figures
A03182
Fig. 31 -- Dual Fuel Thermostat with Two--Stage Furnace
and Two--Speed Heat Pump
See notes 1 and 2 on the page
following these figures
Fig. 33 -- Single--Stage Thermostat with Two--Stage Furnace and Two--Speed Air Conditioner
See notes 2, 11, and 12 on the
page following these figures
A03183
Fig. 32 -- Two--Stage Thermostat with Two--Stage Furnace
and Two--Speed Air Conditioner
A03184
312A
NOTES: F o r Figu r e s 25 --- 31
1. Heat pump MUST have a high pressure switch for dual fuel appl ications.
2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
3. Outdoor Air Temperature Sensor must be attached in all dual fuel applications.
4. Dip switch No. 1 on Thermidistat shou ld be set in OFF position for air conditioner installations. This is factory default.
5. Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations.
6. Dip switch No. 2 on Thermidistat should be set in OFF position for single ---speed compressor operation. This is factory default.
7. Dip switch No. 2 on Thermidistat should be set in ON position for two ---speed compressor operation.
8. Configuration Option No. 10 “Dual Fuel Selection” must be turned ON in all dual fuel applications.
9. NO connection should be made to the furnace HUM terminal when using a Thermidistat.
10. Optional connection: If wire is connected, dip switch SW1---2 on furnace control should be set in ON position to allow Thermidistat/Thermostat to control
furnace staging.
11. Optional connection: If wire is connected, ACRDJ jumper on furnace control should be removed to allow Thermidistat/Thermostat to control outdoorunit
staging.
12. When using both a two---stage furnace and a two---stage heat pump, the furnace must control its own high---stage heating operation via furnace control
algorithm.
13. The RVS Sensing terminal “L” should not be connected. This is internally used to sense defrost operation.
14. DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE POINT” option on the two ---speed h eat pump control board. This is controlled internally by
the Thermidistat/Dual Fuel Thermostat.
15. Dip switch D on Dual Fuel Thermostat should be set in OFF position for single---speed compressor operation. This is factory default.
16. Dip switch D on Dual Fuel Thermostat should be set in ON position for two --- speed compressor operation.
25
Page 26
ACCESSORIES
1. Electronic Air Cleaner (EAC)
Connect an accessory Electronic Air Cleaner (if used)
using 1/4--in female quick connect terminals to the two
male 1/4--in quick--connect terminals on the control board
marked EAC-- 1 and EAC--2. The terminals are rated for
115VAC, 1.0 amps maximum and are energized during
blower motor operation. (See Fig. 34.)
2. Humidifier (HUM)
Connect an accessory 24 VAC, 0.5 amp. maximum
humidifer (if used) to the 1/4--in male quick--connect
HUM terminal and COM--24V screw terminal on the
control board thermostat strip. The HUM terminal is
energized when gas valve relay (GVR) is energized. (See
Fig. 34.)
NOTE: A field--supplied, 115 --v controlled relay connected to
EAC terminals may be added if humidifier operation is desired
during blower operation.
312A
SETUP SWITCHES
LOW-HEAT ONLY AND
BLOWER OFF-DELAY
ON
W2
Y1 DHUM G COM
OFF
1 2 3
LHT
OFF
DLY
NOTE: DO NOT connect furnace control HUM terminal to
HUM (humidifier) terminal on Thermidistat, Zone Controller or
similar device. See Thermidistatt, Zone Controller, thermostat,
or controller manufacturer’s instructions for proper connection.
VENTING
The furnace shall be connected to a listed factory built chimney
or vent or a clay--tile lined masonry or concrete chimney. Venting
into an unlined masonry chimney or concrete chimney is
prohibited. When an existing Category I furnace is removed or
replaced, the original venting system may no longer be sized to
properly vent the attached appliances. An improperly sized
Category I venting system could cause the formation of
condensate in the furnace and vent, leakage of condensate and
combustion products, and spillage of combustion products into
the living space.
TWINNING AND/OR
COMPONENT TEST
TERMINAL
ACRDJ - AIR CONDITIONING
RELAY DISABLE JUMPER
24-V-THERMOSTAT
TERMINALS
HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP MAX.)
3-AMP FUSE
LED OPERATION &
DIAGNOSTIC LIGHT
115-VAC (L2) NEUTRAL
CONNECTIONS
HI HEAT
LO HEAT
BLOWER SPEED
SELECTION TERMINALS
24V
WW1 Y/Y2 R
S
E
L
EAC-2
BLW
HI HEATLO HEAT
SPARE-1
SPARE-2
TEST/TWIN
HUM
0.5-AMP024 VAC
FUSE 3-AMP
A
T
T
SEC-1SEC-2
U
S
C
O
E
D
NEUTRAL-L2
COOL
SPARE-1 SPARE-2
Fig. 34 -- Furnace Control--PSC Blower Motor
ACRDJ
PLT
PL1
1
BHT/CLRBHI/LOR
1-AMP@115 VAC
EAC-1PR-1
COOL
D
BLWR
L1
115-VAC (L1) LINE
VOLTAGE CONNECTION
EAC-1 TERMINAL
(115-VAC 1.0 AMP MAX.)
IDR
PL2
1
PL3 1
HSIR
HSI HI LO
TRANSFORMER 24-VAC
CONNECTIONS
PL1 - LOW VOLTAGE MAIN
HARNESS CONNECTOR
PL3
IHI/LOR
IDM
PL2 - HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
A02017
26
Page 27
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed into
operation could result in carbon monoxide poisoning or
death. The following steps shall be followed for each
appliance connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 or the CSA B149.1, Natural Gas
and Propane Installation Code and these instructions.
Determine that there is no blockage or restriction, leakage,
corrosion and other deficiencies, which could cause an
unsafe condition.
3. As far as practical, close all building doors and windows
and all doors between the space in which the appliance(s)
connected to the venting system are located and other
spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected
to the venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they are operating
at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat so
appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at
the draft hood relief opening after 5 minutes of main burner
operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above
tests, the venting system must be corrected in accordance
with the National Fuel Gas Code, ANSI Z223.1/NFPA 54
and/or CSA B149.1, Natural Gas and Propane Installation
Code.
9. After it has been determined that each appliance
connected to the venting system properly vents when tested
as outlined above, return doors, windows, exhaust fans,
fireplace dampers and any other gas--fired burning
appliance to their previous conditions of use.
Vent system or vent connectors may need to be resized. Vent
systems or vent connectors must be sized to approach minimum
size as determined using appropriate table found in the NFGC or
CAN/CSA--B149.1--05.
GENERAL VENTING
Follow all safety codes for proper vent sizing and installation
requirements, including local building codes, the National Fuel
Gas Code ANSI Z223.1--2006/NFPA 54--2006 (NFGC), Parts 10
and 13 in the United States or the National Standard of Canada,
Natural Gas and Propane Installation Code CSA--B149.1--00
(CAN/CSA--B149.1--05), Section 8 and Appendix C in Canada,
the local building codes, and furnace and vent manufacturers’
instructions.
These furnaces are design-- certified as Category I furnaces in
accordance with ANSI Z21.47--2003/CSA 2.3--2003 and operate
with a non--positive vent static pressure to minimize the potential
for vent gas leakage. Category I furnaces operate with a flue loss
not less than 17% to minimize the potential for condensation in
the venting system. These furnaces are approved for common
venting and multi--story venting with other fan assisted or draft
REQUIREMENTS
hood equipped appliances in accordance with the NFCG or the
CAN/CSA--B149.1--05, local building codes, and furnace and
vent manufacturers’ instructions.
The following information and warning must be considered in
addition to the requirements defined in the NFGC or the
CAN/CSA--B149.1--05.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
Do not bypass the draft safeguard switch, as an unsafe
condition could exist which must be corrected.
1. If a vent (common or dedicated) becomes blocked, the
furnace will be shut off by the draft safeguard switch
located on the vent elbow.
2. Two--stage furnaces require Type B vent connectors
outside the casing in all configurations. Single wall vent
connector may be used inside the furnace casing with the
transition to Type B vent outside the furnace casing. Size
the connector so that the FAN-- Min vent connector
capacity is equal to or lower than the low fire rate of the
furnace and the FAN--Max vent connector capacity is
equal to or higher than the furnace high fire rate.
3. Do not vent this Category I furnace into a single wall
dedicated or common vent. The dedicated or common
vent is considered to be the vertical portion of the vent
system that terminates outdoors.
4. Vent connectors serving Category I furnaces shall not be
connected into any portion of a mechanical draft system
operating under positive pressure.
5. In the US: Do not vent this appliance with any solid fuel
burning appliance. In Canada: Check with the authority
having jurisdiction for approval on use with solid fuel
burning appliance.
6. Category I furnaces must be vented vertically or nearly
vertically unless equipped with a listed mechanical venter.
See the SIDEWALL VENTING section.
7. Do not vent this appliance into an unlined masonry
chimney. Refer to Chimney Inspection Chart, Fig. 35.
MASONRY CHIMNEY
NOTE: These furnaces are CSA design--certified for use in
exterior tile--lined masonry chimneys with a factory accessory
Chimney Adapter Kit. Refer to the furnace rating plate for correct
kit usage. The Chimney Adapter Kits are for use with ONLY
furnaces having a Chimney Adapter Kit number marked on the
furnace rating plate.
If a clay tile--lined masonry chimney is being used and it is
exposed to the outdoors below the roof line, relining might be
required. Chimneys shall conform to the Standard for Chimneys,
Fireplaces, Vents, and Solid Fuel Burning Appliances
ANSI/NFPA 211--2003 in the United States and to a Provincial or
Territorial Building Code in Canada (in its absence, the National
Building Code of Canada) and must be in good condition.
U.S.A.--Refer to Sections 13.1.9 and 13.2.20 of the NFGC or the
authority having jurisdiction to determine whether relining is
required. If relining is required, use a properly sized listed metal
liner, Type--B vent, or a listed alternative venting design.
NOTE: See the NFGC, 13.1.9 and 13.2.20 regarding alternative
venting design and the exception, which cover installations such
as the Chimney Adapter Kits KGACA02014FCand
KGACA02015FC, which are listed for use with these furnaces.
REQUIREMENTS
312A
27
Page 28
CHIMNEY INSPECTION CHART
For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211
Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances in the U.S.A. or to the Canadian
installation Code CSA-B149.1 in Canada.
312A
Crown
condition:
Missing mortar
or brick?
No
Is chimney
property lined with
clay tile liner?
Ye s
Is
liner and top
seal in good
condition?
Ye s
Debris
in cleanout?
Mortar, tile, metal vent,
fuel oil residue?
Ye s
No
Ye s
No
Rebuild
crown.
Repair
liner or top seal
or reline chimney as
necessary.
Repair
Mortar
or tile
debris?
Reline
Ye s
Remove mortar
and tile debris
No
Clay
tile misalignment,
missing sections,
gaps?
No
Condensate
drainage at bottom
of chimney?
No
Chimney
exposed to
outdoors below
roof line?
No
Chimney is
acceptable for use.
Remove metal vent
or liner.
Ye s
lined with properly
sized, listed liner or
Ye s
Ye s
No
No
Is chimney
Type-B vent?
Ye s
Is chimney
to be dedicated to
a single
furnace?
Consult
Part B of
chimney adapter venting
instructions for
application
suitability.
Suitable
Ye s
Install chimney
adapter per
instructions.
No
chimney adapter venting
Not Suitable
Not Suitable
Consult
Part C of
instructions for
application
suitability
Line chimney with property
sized, listed flexible metal
liner or Type-B vent per
NFGC or NSCNGPIC Vent
Sizing Tables and liner or
vent manufacturer’s
Installation instructions.
Suitable
Install chimney
adapter per
instructions.
Fig. 35 -- Chimney Inspection Chart
28
A03206
Page 29
The Chimney Adapter Kit is a listed alternative venting system
for these furnaces. See the kit instructions for complete details.
Canada (and U.S.A.)--This furnace is permitted to be vented into
a clay tile--lined masonry chimney that is exposed to the outdoors
below the roof line, provided:
1. Vent connector is Type--B double--wall, and
2. This furnace is common vented with at least 1 draft
hoodequipped appliance, and
3. The combined appliance input rating is less than the
maximum capacity given in Table 8, and
4. The input rating of each space heating appliance is greater
than the minimum input rating given in Table 9 for the
local 99% Winter Design Temperature. Chimneys having
internal areas greater than 38 square inches require furnace
input ratings greater than the input ratings of these
furnaces. See footnote at bottom of Table 9, and
5. The authority having jurisdiction approves.
If all of these conditions cannot be met, an alternative venting
design shall be used, such as the listed chimney adapter kit with a
furnace listed for use with the kit, a listed chimney--lining system,
or a Type--B common vent.
Inspections before the sale and at the time of installation will
determine the acceptability of the chimney or the need for repair
and/or (re)lining. Refer to Fig. 35 to perform a chimney
inspection. If the inspection of a previously used tile--lined
chimney:
a. Shows signs of vent gas condensation, the chimney
should be relined in accordance with local codes and the
authority having jurisdiction. The chimney should be
relined with a listed metal liner, Type--B vent, or a listed
chimney adapterkitshallbeusedto reducecondensation.
If a condensate drain is required by local code, refer to
the NFGC, Section 10.9 for additional information on
condensate drains.
b. Indicates the chimney exceeds the maximum permissible
sizein thetables, the chimney should berebuilt or relined
to conform to the requirements of the equipment being
installed and the authority having jurisdiction.
A chimney without a clay tile liner, which is otherwise in good
condition, shall be rebuilt to conform to ANSI/NFPA 211 or be
lined with a UL listed (ULC listed in Canada) metal liner or UL
listed Type--B vent. Relining with a listed metal liner or Type--B
vent is considered to be a vent--in--a--chase.
If a metal liner or Type--B vent is used to line a chimney, no other
appliance shall be vented into the annular space between the
chimney and the metal liner.
Exterior Masonry Chimney FAN + NA
Installations with Type-- B Double--Wall V
Connectors
ENFPA & AGA
T
ent
Table 8 – Combined Appliance Maximum Input Rating in
Table 9 – Minimum Allowable Input Rating of Space--Heat-
ing Appliance in Thousands of BTUH per Hour
VENT HEIGHT
(FT)
605599141
85274111154
10NR90125169
15NRNR167212
20NRNR212258
30NRNRNR362
6NR78121166
8NR94135182
10NR111149198
15NRNR193247
20NRNRNR293
30NRNRNR377
Temperature: --- 10 to 4_F*
6NRNR145196
8NRNR159213
10NRNR175231
15NRNRNR283
20NRNRNR333
30NRNRNRNR
Temperature: --- 11_Forlower
Not recommended for any vent configuration.
*The 99% Winter Design Dry--- Bulb (db) temperatures are found in the
1993 ASHRAE Fundamentals Handbook, Chapter 24, Table 1 (United
States) and 2 (Canada), or use the 99.6% heating db temperatures found
in th e 1997 or 2001 ASHRAE Fundamentals Handbook, Climatic Design
Information chapter, Table 1A (United States) and 2A (Canada).
INTERNAL AREA OF CHIMNEY
(SQ. IN.)
12192838
Local 99% Winter Design
Temperature: 17 to 26_F
Local 99% Winter Design
Temperature: 5 to 16_F*
Local 99% Winter Design
Local 99% Winter Design
APPLIANCE APPLICATION REQUIREMENTS
Appliance operation has a significant impact on the performance
of the venting system. If the appliances are sized, installed,
adjusted, and operated properly, the venting system and/or the
appliances should not suffer from condensation and corrosion.
The venting system and all appliances shall be installed in
accordance with applicable listings, standards, and codes.
The furnace should be sized to provide 100% of the design
heating load requirement plus any margin that occurs because of
furnace model size capacity increments. Heating load estimates
can be made using approved methods available from Air
Conditioning Contractors of America (Manual J); American
Society of Heating, Refrigerating, and Air--Conditioning
Engineers; or other approved engineering methods. Excessive
over--sizing of the furnace could cause the furnace and/or vent to
fail prematurely. When a metal vent or metal liner is used, the
vent must be in good condition and be installed in accordance
with the vent manufacturer’s instructions.
To prevent condensation in the furnace and vent system, the
following precautions must be observed:
1. The return-- air temperature must be at least 60_F db except
for brief periods of time during warm--up from setback at
no lower than 55_F(13_C) db or during initial start--up
from a standby condition.
2. Adjust the gas input rate per the installation instructions.
Low gas input rate causes low vent gas temperatures,
29
312A
Page 30
causing condensation and corrosion in the furnace and/or
venting system. Derating is permitted only for altitudes
above 2000 ft
3. Adjust the air temperature rise to the midpoint of the rise
range or slightly above. Low air temperature rise can cause
low vent gas temperature and potential for condensation
problems.
4. Set the thermostat heat anticipator or cycle rate to reduce
short cycling.
Air for combustion must not be contaminated by halogen
compounds which include chlorides, fluorides, bromides, and
iodides. These compounds are found in many common home
products such as detergent, paint, glue, aerosol spray, bleach,
cleaning solvent, salt, and air freshener, and can cause corrosion
of furnaces and vents. Avoid using such products in the
combustion--air supply. Furnace use during construction of the
building could cause the furnace to be exposed to halogen
compounds, causing premature failure of the furnace or venting
system due to corrosion.
312A
Vent dampers on any appliance connected to the common vent
can cause condensation and corrosion in the venting system. Do
not use vent dampers on appliances common vented with this
furnace.
ADDITIONAL VENTING REQUIREMENTS
A 4 in. round vent elbow is supplied with the furnace. A 5 in. or
6 in. vent connector may be required for some model furnaces. A
field--supplied 4 in. to 5 in. or 4 in. to 6 in. sheet metal increaser
fitting is required when 5 in. or 6 in. vent connector is used. See
Fig. 36--48 Venting Orientation for approved vent configurations.
See Venting Notes after Fig. 48.
SEE NOTES: 1,2,3,4,7,8,9
on the pages following
these figures
Fig. 37 -- Upflow Application--Vent Elbow Right
A03209
SEE NOTES: 1,2,4,7,8,9
on the page following
these figures
Fig. 36 -- Upflow Application--Vent Elbow Up
A03208
SEE NOTES:1,2,3,4,5,7,8,9
on the page following
these figures
A03210
Fig. 38 -- Downflow Application--Vent Elbow Up then Left
30
Page 31
SEE NOTES: 1,2,4,5,7,8,9
on the page following
these figures
SEE NOTES:1,2,3,4,5,7,8,9
312A
on the page following
these figures.
Fig. 39 -- Downflow Application--Vent Elbow Up
SEE NOTES: 1,2,4,5,6,7,8,9,10
on the page following these figures
A03211
A03212
Fig. 41 -- Downflow Application--Vent Elbow Up then Right
SEE NOTES: 1,2,4,7,8,9 on the page
following these figures
A03213
Fig. 42 -- Horizontal Left Application -- Vent Elbow Left
A03207
Fig. 40 -- Downflow Application--Vent Elbow Left then Up
SEE NOTES: 1,2,4,5,7,8,9 on the page
following these figures
Fig. 43 -- Horizontal Left Application -- Vent Elbow Right
then Up
31
A03214
Page 32
SEE NOTES: 1,2,4,7,8,9 on the page
following these figures
SEE NOTES: 1,2,4,5,7,8,9 on the page
following these figures
Fig. 44 -- Horizontal Right Application -- Vent Elbow Right
312A
SEE NOTES: 1,2,4,5,7,8,9 on the page
following these figures
Fig. 45 -- Horizontal Left Application -- Vent Elbow Up
A03218
A03215
A03216
Fig. 46 -- Horizontal Left Application -- Vent Elbow Right
SEE NOTES: 1,2,4,5,7,8,9 on the page
following these figures
A03219
Fig. 47 -- Horizontal Right Application -- Vent Elbow Left
then Up
SEE NOTES: 1,2,4,5,7,8,9
A02068
Fig. 48 -- Horizontal Right Application--Vent Elbow Left
NOTES: Venting Notes for Fig. 36---48
1. For common vent, vent connector sizing and vent material: United States--- ---use the NFGC Canada--- --- use the CAN/CSA---B149.1 ---05
2. Immediately increase to 5---inch or 6---inch vent connector outside furnace casing when 5---inch vent connector is required, refer to Note 1 above.
3. Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace, except when KGAVG0101DFG, Downflow
VentGuardKit,isusedinthedownflowposition.
4. Type ---B vent where required, refer to Note 1 above.
5. Four ---inch single ---wall (26 ga. min.) vent must be used inside furnace casing and when the KGAVG0101DFG Downflow Vent Guard Kit is used external to
the furnace.
6. Accessory Downflow Vent Guard Kit, KGAVG0101DFG required in downflow installations with lower vent configuration.
7. Chimney Adapter Kit may be required for exterior masonry chimney applications. Refer to Chimney Adapter Kit, KGACA02014FC or KGACA02015FC, for
sizing and complete application details.
8. Secure vent connector to furnace elbow with (2) corrosion---resistant sheet metal screws, spaced approximately 180_ apart.
9. Secure all other single wall vent connector joints with (3) corrosion resistant screws spaced approximately 120_ apart. Secure Type --- B vent connectors per
vent connector manufacturer’s recommendations.
10. The total height of the vent and connector shall be at least seven feet for the 154,000 Btuh gas input rate model when installed in a downflow application
with furnace elbow turned to left side with the connector elbow outside furnace casing pointing upward. (See Fig. 41.)
32
Page 33
Caution!! For the following applications, use the minimum vertical heights as specified below.
For all other applications, follow exclusively the National Fuel Gas Code
FURNACE
ORIENTATION
Downflow
Horizontal Left
Horizontal Left
Horizontal Left
Downflow
Downflow
NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC. *4 in. inside casing or vent guard **Including 4 in. vent
section(s)
VENT ORIENTA-
TION
Vent elbow left, then
up Fig. 40
Vent elbow right,
then up Fig. 43
Vent Elbow up Fig.
44
Vent elbow right Fig.
45
Vent elbow up then
left Fig. 38
Vent elbow up, then
right Fig. 41
FURNACE IN-
PUT(BTUH/HR)
154,000
132,000
110,000(036/--- 12 only)
154,000
132,000
154,000
132,000
154,00057
110,000 (036/--- 12 only)510
110,000 (036/--- 12 only)510
MINIMUM VENT
DIAMETER (IN.)*
512
57
57
MINIMUM VERTICAL VENT
HEIGHT (FT)**
312A
Fig. 49 -- Using Tin Snips to Cut Tie Points
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts and servicing furnaces.
NOTE: Vent connector length for connector sizing starts at
furnace vent elbow. The 4 inch vent elbow is shipped for upflow
configuration and may be rotated for other positions. Remove the
3 screws that secure vent elbow to furnace, rotate furnace vent
elbow to position desired, re--install screws. The factory--supplied
vent elbow does NOT count as part of the number of vent
connector elbows.
The vent connector can exit the door through one of 5 locations
on the door.
1. Attach the single wall vent connector to the furnace vent
elbow, and fasten the vent connector to the vent elbow
with at least two field--supplied, corrosion--resistant, sheet
metal screws located 180_ apart.
NOTE:An accessory flue extension KGAFE0112UPH is
available to extend from the furnace elbow to outside the furnace
casing. If flue extension is used, fasten the flue extension to the
vent elbow with at least two field--supplied, corrosion--resistant,
sheet metal screws located 180_ apart. Fasten the vent connector
A04127
to the flue extension with at least two field--supplied, corrosion
resistant sheet metal screws located 180_ apart.
2. Vent the furnace with the appropriate connector as shown
in Fig. 36--48.
3. Orient the door to determine the correct location of the
door knockout to be removed.
4. Remove the correct U--shaped knockout in door.
NOTE: A number of techniques can be used to remove these
knockouts as seen in Fig. 49 through 53. The knockout in the
bottom of the door is unique due to its flanging and is more easily
removed by first cutting the two tie points at the edge of the door,
using aviation--type tin snips. (See Fig. 49.) A sharp blow to the
rounded end of the knockout (See Fig. 50.) will separate more tie
points and allow the knockout to be pulled loose. (See Fig. 51.)
Remove all burrs any sharp edges.
For the rectangular J--box knockout, use tin snips along the door
edge and use a sharp blow with a hammer to remove the
knockout. Remove any burrs and sharp edges.
For the knockouts in the other locations on the door (top and
sides), tin snips can also be used along the door edges; however,
the preferred method is to use a hammer and screwdriver to strike
a sharp blow (See Fig. 52.) directly to the knockout tie points or
use a hammer in the upper left corner of the desired knockout.
(See Fig. 53.) Remove any burrs and sharp edges.
NOTE: If a knockout does not come out after two sharp blows,
pull and snip as needed to remove the knockout. Additional
blows may cause damage to the door.
33
Page 34
312A
Fig. 50 -- Rounded End of Knockout
A04128
A04130
Fig. 52 -- Hammer and Screwdriver Used for Knockout
A04131
Fig. 53 -- Remove Knockout with Hammer
!
CAUTION
BURN HAZARD
Failure to follow this caution may cause personal injury.
Hot vent pipe is within reach of small children when
installed in downflow position.
See the following instruction.
Fig. 51 -- Knockout Pulled Loose
A04129
An accessory Vent Guard Kit, KGAVG0101DFG is REQUIRED
for downflow applications for use where the vent exits through
the lower portion of the furnace casing door. Refer to the Vent
Guard Kit Instructions for complete details.
The horizontal portion of the venting system shall slope upwards
not less than 1/4--in. per linear ft (21 mm/m) from the furnace to
the vent and shall be rigidly supported every 5 ft or less with
metal hangers or straps to ensure there is no movement after
installation.
SIDEWALL VENTING
This furnace is not approved for direct sidewall horizontal
venting.
In the U.S.: Per section 10.3.4 of the NFGC, any listed
mechanical venter may be used, when approved by the authority
having jurisdiction.
34
Page 35
In Canada: Per section 8.24.2 of the CAN/CSA--B149.1--05,
any listed mechanical venter may be used, when approved by the
authority having jurisdiction.
Select the listed mechanical venter to match the Btuh input of the
furnace being vented. Follow all manufacturers installation
requirements for venting and termination included with the listed
mechanical venter.
START--UP, ADJUSTMENT, AND SAFETY
CHECK
Step 1 — General
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
This furnace is equipped with manual reset limit switches in
the gas control area. The switches open and shut off power
to the gas valve if a flame roll--out or overheating condition
occurs in the gas control area. DO NOT bypass the
switches. Correct problem before resetting the switches.
1. Maintain 115--v wiring and ground. Improper polarity will
result in rapid flashing LED and no furnace operation.
2. Make thermostat wire connections at the 24--v terminal
block on the furnace control. Failure to make proper
connections will result in improper operation. (See Fig.
24.)
3. Gas supply pressure to the furnace must be greater than
4.5--in. wc (0.16 psig ) but not exceed 14--in. wc (0.5
psig).
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts and servicing furnaces.
4. Check all manual--reset switches for continuity.
5. Install blower compartment door. Door must be in place to
operate furnace.
6. Setup switch descriptions The 2 stage furnace has DIP
switches used to select thermostat staging and blower off
delay timings. For switch locations on Furnace control
board, See Fig. 34 and 58.
7. Setup switch descriptions -- See Table 10.
Step 2 — Start--Up Procedures
1. Purge gas lines after all connections have been made.
2. Check gas lines for leaks.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury, or death. Blower access door switch opens 115--v
power to control. No component operation can occur unless
switch is closed. Caution must be taken when manually
closing this switch for service purposes.
3. To Begin Component Self--Test:
Remove blower access door. Disconnect the thermostat R
lead from furnace control board. Manually close blower
door switch. Short (jumper) the COM--24v terminal on
control to the TEST/TWIN 3/16--inch quick--connect
terminal on control until the LED goes out (approximately
2 sec). Gas valve and humidifier will not be turned on.
Remove jumper from terminals. (See Fig. 34 and Table
10.)
NOTE: The furnace control allows all components, except the
gas valve, to be run for short period of time. This feature helps
diagnose a system problem in case of a component failure.
Component test feature will not operate if any thermostat signal is
present at the control.
Refer to service label attached to furnace or See Fig. 57.
Component test sequence is as follows:
a. LED will display previous status code 4 times.
b. Inducer motor starts on high--speed and continues to run
until Step g of component test sequence.
c. Hot surface igniter is energized for 15 sec., then off.
d. Blower motor operates on LO--HEAT speed for 10 sec.
e. Blower motor operates on HI--HEAT speed for 10 sec.
f. Blower motor operates on COOL speed for 10 sec.
g. Inducer motor goesto low--speed for 10 sec., then stops.
h. Reconnect R lead to furnace control board, remove tape
from blower door switch and re--install blower door.
4. Operate furnace per instruction on inner door.
5. Verify furnace shut down by lowering thermostat setting
below room temperature.
Failure to follow this warning could cause personal injury,
death and/or property damage.
Never purge a gas line into a combustion chamber. Never
use matches, candles, flame, or other sources of ignition for
the purpose of checking leakage. Use a soap--and--water
solution to check for leakage.
Failure to follow this warning could result in injury, death
and/or property damage.
312A
DO NOT bottom out gas valve regulator adjusting screw.
This can result in unregulated manifold pressure and result
in excess over--fire and heat exchanger failures.
!
CAUTION
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace
life.
DO NOT re--drill orifices. Improper drilling (burrs, out--of
round holes, etc.) can cause excessive burner noise and
misdirection of burner flames. This can result in flame
impingement of heat exchangers, causing failures. (See Fig.
50.)
Furnace gas input rate on rating plate is for installations at
altitudes up to 2000 ft Furnace input rate must be within +/--2%
of furnace rating plate input. For altitudes above 5500 ft, a
field--supplied high altitude pressure switch is required.
1. Determine the correct gas input rate.
In the U.S.:
The input rating for altitudes above 2,000 ft must be reduced by 4% for each 1,000 ft above sea level.
For installations below 2000 ft, refer to the unit rating
plate.
For installations above 2000 ft, multiply the input on the
rating plate by the derate multiplier in Table 11 for the correct input rate.
EXAMPLE:
88,000 BTUH INPUT FURNACE INSTALLED AT 4300 FT
DerateFurnace Input Rate
Furnace Input RateX Multiplier=at Installation
at Sea LevelFactorAltitude
88,000X0.90=79,200
In Canada: The input rating must be reduced by 10% for
altitudes of 2,000 ft to 4,500 ft above sea level by an
authorized Gas Conversion Station or Dealer. To
determine correct input rate for altitude, see example and
use 0.90 as derate multiplier factor.
2. Determine the correct orifice and manifold pressure
adjustment. All models in all positions except Low NOx
NORMAL
POSITION
DESCRIPTION
When OFF, allows 2- -- stage operation with a single stage thermostat.
Turn ON when using 2 stage thermostat to allow Low Heat opera ---
tion when R to W/W1 closes and High Heat operation when R to
Control blower OFF delay time. Used in conjunction with SW---3.
Control blower OFF delay time. Used in conjunction with SW---2.
OF USE
W/W1 and W2 close.
See Table 14.
See Table 14.
models in downflow and horizontal positions use Table 15
(22,000 BTUH per burner).
* Derate multiplier factors are based on midpoint altitude for altitude
range.
%
OF DERATE
DERATE MULTIPLIER
FACTOR*
Low NOx models in downflow or horizontal positions MUST
use Table 16 (21,000 BTUH per burner). See input listed on
rating plate.
a. Obtain average yearly gas heat value (at installed altitude)
from local gas supplier.
b. Obtain average yearly gas specific gravity from local gas
supplier.
c. Find installation altitude in Table 15 or 16.
d. Find closest natural gas heat value and specific gravity
in Table 15 or 16
e. Follow heat value and specific gravity lines to point of
intersection to find orifice size and low--and high--heat
manifold pressure settings for proper operation.
f. Check and verify burner orifice size in furnace. NEVER
ASSUME ORIFICE SIZE. ALWAYS CHECK AND
VERIFY.
g. Replace orifice with correct size, if required by Table 15
or 16. Use only factory--supplied orifices. See
EXAMPLE 2.
EXAMPLE 2: (0--2000 ft altitude)
For 22,000 Btuh per burner application, use Table 15.
Heating value = 1000 Btuh/cu ft
Specific gravity = 0.62
Therefore: Orifice No. 43*
Manifold pressure: 3.7--in. wc for high--heat
1.6--in. wc for low--heat
* Furnace is shipped with No. 43 orifices. In this example
all main burner orifices are the correct size and do not need
to be changed to obtain proper input rate.
3. Adjust manifold pressure to obtain low fire input rate. (See
Fig. 54.)
36
Page 37
a. Turn gas valve ON/OFF switch to OFF.
b. Remove manifold pressure tap plug from gas valve.
c. Connect a water column manometer or similar device to
manifold pressure tap.
d. Turn gas valve ON/OFF switch to ON.
e. Move setup switch LHT (SW--1) on furnace control to
ON position to lock furnace in low--heat operation. (See
Fig. 34 and Table 10.)
f. Manually close blower door switch.
g. Jumper R and W/W1 thermostat connections on control
to start furnace. (See Fig. 34.)
h. Remove regulator adjustment cap from low--heat gas
valve pressure regulators. (See Fig. 54.) Turn low--heat
adjusting screw (3/16 in. or smaller flat tipped
screwdriver) counterclockwise (out) to decrease input
rate or clockwise (in) to increase input rate.
c. Measure time (in sec) for gas meter to complete 1
revolution and note reading. The 2 or 5 cubic feet dial
provides a more accurate measurement of gas flow.
d. Refer to Table 12 for cubic ft of gas per hr.
e. Multiply gas rate cu ft/hr by heating value (Btuh/cu ft)
to obtain input. If clocked rate does not match required
input from Step 1, increase manifold pressure to increase
input or decrease manifold pressure to decrease input.
Repeat steps b through e until correct low heat input is
achieved. Re--install low--heat regulator seal cap on gas
valve.
5. Set low--heat temperature rise. The furnace must operate
within the temperature rise ranges specified on the furnace
rating plate. Do not exceed temperature rise ranges
specified on unit rating plate for high--and low--heat.
Determine the temperature rise as follows:
NOTE: Blower access door must be installed when taking
temperature rise reading. Leaving blower access door off will
result in incorrect temperature measurements.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Disconnect 115--v electrical power before changing speed
tap.
312A
A06667
Fig. 54 -- Redundant Automatic Gas Control Valve
NOTE: DO NOT set low--heat manifold pressure less than
1.4--in wc or more than 1.7--in. wc for natural gas. If manifold
pressure is outside this range, change main burner orifices.
i. Install low--heat regulator adjustment cap.
j. Leave manometer or similar device connected and
proceed to Step 4.
NOTE: If orifice hole appears damaged or it is suspected to have
been re--drilled, check orifice hole with a numbered drill bit of
correct size. Never re--drill an orifice. A burr--free and squarely
aligned orifice hole is essential for proper flame characteristics.
4. Verify natural gas low--heat input rate by clocking meter.
NOTE: Gas valve regulator adjustment caps must be in place for
proper input to be clocked.
a. Turn off all other gas appliances and pilots served by the
meter.
b. Run for 3 minutes in low--heat operation.
BURNER
ORIFICE
Fig. 55 -- Orifice Hole
a. Verify unit is running in low heat per Step 4. Place
thermometers in return and supply ducts as close to
furnace as possible. Be sure thermometers do not see
radiant heat from heat exchangers. Radiant heat affects
temperature rise readings. This practice is particularly
important with straight--run ducts.
b. When thermometer readings stabilize, subtract return--air
temperaturefrom supply--airtemperatureto determineair
temperature rise.
NOTE: If the temperature rise is outside this range, first check:
(1.) Gas input for low heat operation.
(2.) Derate for altitude if applicable.
(3.) Return and supply ducts for excessive restrictions
causing static pressures greater than 0.50--in. wc.
c. Adjust air temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise.
Decrease blower speed to increase temperature rise. For
low heat, speed selection can be low (factory setting),
med--low, or med (5--speed blowers only).
d. Remove thermostat jumpers and release Blower Access
Door Switch.
e. To change motor speed selection for low heat, remove
blower motor lead from control LO--HEAT terminal.
(See Fig. 34.) Select desired blower motor speed lead
from 1 of the other terminals and relocate it to the
LO--HEAT terminal. (See Table 13 for lead color
identification). Reconnect original lead to SPARE
terminal.
f. Repeat steps a through e.
!
CAUTION
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace
life.
Recheck temperature rise. It must be within limits specified
on the rating plate. Recommended operation is at the
midpoint of rise range or slightly above.
g. When correct low heat input rate and temperature rise is
achieved, proceed to Step 6.
6. Adjust Manifold Pressure to Obtain High Heat Rate
a. Remove high fire regulator adjustment cap from gas
valve pressure regulator.
b. Manually close blower access door switch.
c. Jumper R, W/W1 and W2 thermostat connections on
control to run furnace in high heat. (See Fig. 34.)
d. d. Turn high--heat adjustingscrew (3/16 in. orsmallerflat
tipped screwdriver) counterclockwise (out) to decrease
input rate or clockwise (in) to increase rate.
e. Re--install high--fire adjustment caps.
f. Leave manifold or similar device connected and proceed
to Step 7.
NOTE: DO NOT set high--heat manifold pressure less than
3.2--in. wc or more than 3.8--in. wc for natural gas. If manifold
pressure is outside this range, change main burner orifices.
7. Verify natural gas high heat input rate by clocking meter.
NOTE: Gas valve regulator adjustment caps must be in place for
proper input to be clocked.
a. Turn off all other gas appliances and pilots served by the
meter.
b. Run for 3 minutes in high--heat operation.
c. Measure time (in sec) for gas meter to complete 1
revolution and note reading.
d. Refer to Table 12 for cubic ft of gas per hr.
e. Multiply gas rate cu ft/hr by heating value (Btuh/cu ft)
to obtain input.
NOTE: Using the 2 cu. ft or 5 cu. ft gas meter dial provides
greater accuracy in verifying gas input rate.
38
Page 39
If clocked rate does not match required input from Step 1,
increase manifold pressure to increase input or decrease manifold
pressure to decrease input. Repeat steps b through e until correct
high heat input is achieved. Re--install high--heat regulator seal
cap on gas valve.
8. Set high heat temperature rise.
Jumper R to W/W1 and W2 to check high--gas--heat
temperature rise. Do not exceed temperature rise ranges
specified on furnace rating plate for high heat. The furnace
must operate within the temperature rise ranges specified
on the furnace rating plate.
Determine the air temperature rise as follows:
NOTE: Blower access door must be installed when taking
temperature rise reading. Leaving blower access door off will
result in incorrect temperature measurements.
a. Verify the furnace is operating in high heat per Step 6.
Place thermometers in return and supply ducts as close
to furnace as possible. Be sure thermometers do not see
radiant heat from heat exchangers. Radiant heat affects
temperature rise readings. This practice is particularly
important with straight--run ducts.
b. When thermometer readings stabilize, subtract return--air
temperaturefrom supply--airtemperatureto determineair
temperature rise.
NOTE: If the temperature rise is outside this range, first check:
(1.) Gas input for low--and high--heat operation.
(2.) Derate for altitude if applicable.
(3.) Return and supply ducts for excessive restrictions
causing static pressures greater than 0.50--in. wc.
(4.) Dirty filter.
c. Adjust air temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise.
Decrease blower speed to increase temperature rise. For
high heat, speed selection can be med--high, med
(5--speed blowers only), or med--low (factory setting).
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Disconnect 115--v electrical power before changing speed
tap.
d. To change motor speed selection for high heat, remove
blowermotor leadfrom controlHI--HEAT terminal.(See
Fig. 34.) Select desired blower motor speed lead from 1
of the other terminals and relocate it to the HI--HEAT
terminal. DO NOT use the low--heat tap that was already
set. (See Table 13 for lead color identification).
Reconnect original lead to SPARE terminal.
e. Repeat steps a thru e.
f. When correct high heat input rate and temperature rise is
achieved, turn gas valve ON/OFF switch to OFF.
g. Release Blower Access Door switch.
h. Remove manometer or similar device from gas valve.
i. Re--install manifold pressure tap plug in gas valve (use
3/16 in. head allen wrench). (See Fig 54.)
!
WARNING
FIRE HAZARD
Failure to reinstall manifold pressure tap plug in gas valve
could result in personal injury, property damage or death.
Reinstall manifold pressure tap plug in gas valve to prevent
gas leak.
j. Remove thermostat jumper wire from furnace control
board.
k. Turn LHT switch OFF.
l. Turn gas valve ON/OFF switch to ON.
m. Proceed to Step 9, “Set Blower Off Delay” before
installing blower access door.
!
CAUTION
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace
life.
Recheck temperature rise. It must be within limits specified
on the rating plate. Recommended operation is at the
midpoint of rise range or slightly above.
9. Set Blower Off Delay
a. Remove Blower Access Door if installed.
b. Turn Dip switch 2 and 3 ON or OFF for desired blower
off delay. (See Table 14 and Fig 34.)
10. Set thermostat heat anticipator.
a. Mechanical thermostat -- Set thermostat heat anticapator
to match the amp. draw of the electrical components in
the R--W/W1 circuit. Accurate amp. draw readings can
be obtainedatthewires normallyconnectedto thermostat
subbase terminals, R and W. The thermostat anticipator
should NOT be in the circuit while measuring current.
(1.) Set LHT switch on furnace control board to ON.
(2.) Remove thermostat from sub--base or from wall.
(3.) Connect an amp. meter as shown in Fig. 56 across
the R and W subbase terminals or R and W wires at
wall.
(4.) Record amp. draw across terminals when furnace is
in low heat and after blower starts.
(5.) Set heat anticipator on thermostat per thermostat
b. Electronic thermostat: Set cycle rate for 3 cycles per hr.
11. Set airflow CFM for cooling
Select the desired blower motor speed lead for cooling
airflow. See Table 5--Air Delivery--CFM (With Filter). See
Table 13 for lead color identification.
Table 13 – Speed Selection
COLORSPEEDAS SHIPPED
WhiteCommonBLW
BlackHighCOOL
YellowM e d --- H ig hSPARE
Orange†MedSPARE
BlueM e d --- L o wHI---HEAT
* Continuous---blower speed ---as shipped default
{ Not all models equipped with 5 speed motors
39
RedLow*LO HEAT
312A
Page 40
Table 14 – 2--Stage Furnace Blower OFF delay Setup Switch
312A
DESIRED HEATING MODE
BLOWER OFF DELAY (SEC.)
90OFFOFF
120OFFON
150ONOFF
180ONON
EXAMPLE:
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
R Y W G
10 TURNS
FROM UNIT 24-V
CONTROL TERMINALS
5.0 AMPS ON AMMETER
10 TURNS AROUND JAWS
SETUP SWITCH
S W --- 2
HOOK-AROUND
AMMETER
0.5 AMPS FOR THERMOSTAT
=
ANTICIPATOR SETTING
SETUP SWITCH
S W --- 3
Fig. 56 -- Amp. Draw Check with Ammeter
Step 4 — Check Safety Controls
The flame sensor, gas valve, and pressure switch were all checked
in the Start--up procedure section as part of normal operation.
1. Check Main Limit Switch(es)
This control shuts off combustion system and energizes
air--circulating blower motor, if furnace overheats. By
using this method to check limit control, it can be
established that limit is functioning properly and will
operate if there is a restricted return--air supply or motor
failure. If limit control does not function during this test,
cause must be determined and corrected.
a. Run furnace for at least 5 minutes.
b. Gradually block off return air with a piece of cardboard
or sheet metal until the limit trips.
c. Unblock return air to permit normal circulation.
d. Burners will re--light when furnace cools down.
2. Check draft safeguard switch.
The purpose of this control is to cause the safe shutdown
of the furnace during certain blocked vent conditions.
a. Verify vent pipe is cool to the touch.
b. Disconnect power to furnace and remove ventconnector
from furnace vent elbow.
c. Restore power to furnace and set room thermostat above
room temperature.
d. After normal start--up, allow furnace to operate for 2
minutes, then block vent elbow in furnace 80% of vent
area with a piece of flat sheet metal.
e. Furnace should cycleoffwithin2 minutes.Ifgas does not
shut off within 2 minutes, determine reason draft
A96316
safeguard switch did not function properly and correct
condition.
f. Remove blockage from furnace vent elbow.
g. Switch will auto--reset when it cools.
h. Re--install vent connector.
NOTE: Should switch remain open longer than 3 minutes,
furnace control board will lockout the furnace for 3 hours. To
reset furnace control board, turn thermostat below room
temperature or from HEAT to OFF and turn 115--v power OFF,
then back ON.
3. Check Pressure Switch(es)
This control proves operation of the draft inducer blower.
a. Turn off 115--v power to furnace.
b. Disconnect inducer motor lead wires from wire harness.
c. Turn on 115--v power to furnace.
d. Set thermostat to “call for heat” and wait 1 minute. When
pressure switch is functioning properly, hot surface
igniter should NOT glow and control diagnostic light
flashes a status code 32. Ifhot surfaceigniter glowswhen
inducer motor is disconnected, shut down furnace
immediately.
e. Determine reason pressure switch did not function
properly and correct condition.
f. Turn off 115--v power to furnace.
g. Reconnect inducer motor wires, replace outer door, and
turn on 115--v power.
h. Blower will run for 90 seconds before beginning thecall
for heat again.
i. Furnace should ignite normally.
40
Page 41
Step 5 — Checklist
1. Put away tools and instruments. Clean up debris.
2. Verify that switches for LHT and OFF--DELAY are
blower OFF--DELAY are selected as desired.
3. Verify that blower and burner access doors are properly
installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturerfs
instructions.
6. Review User’s Guide with owner.
7. Attach literature packet to
furnace.
312A
41
Page 42
Table 15 – Orifice Size and Manifold Pressure for Gas Input Rate
(Tabulated Data Based on 22,000 Btuh High--Heat/14,500 Btuh for Low--Heat per Burner, Derated 4% for Each 1000 Ft Above Sea
Failure to follow this warning could result in personal injury,
death and/or property damage.
The ability to properly perform maintenance on this
equipment requires certain knowledge, mechanical skills,
tools, and equipment. If you do not possess these, do not
attempt to perform any maintenance on this equipment other
than those procedures recommended in the User’s Manual.
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow this warning could result in personal injury
or death, or property damage.
Before servicing, disconnect all electrical power to furnace.
Verify proper operation after servicing.
45
Page 46
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in improper unit
operation or failure of unit components.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation.
Step 1 — Introduction
GENERAL
These instructions are written as if the furnace is installed in an
upflow application. An upflow furnace application is where the
blower is located below the combustion and controls section of
the furnace, and conditioned air is discharged upward. Since this
furnace can be installed in any of the 4 positions shown in Fig. 4,
you must revise your orientation to component location
312A
accordingly.
ELECTRICAL CONTROLS AND
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
There may be more than one electrical supply to the
furnace. Check accessories and cooling unit for additional
electrical supplies that must be shut off during furnace
servicing.
The electrical ground and polarity for 115--v wiring must be
properly maintained. Refer to Fig. 24 for field wiring information
and to Fig. 58 for furnace wiring information.
NOTE: If the polarity is not correct, the STATUS LED on the
control will flash rapidly and prevent the furnace from heating.
The control system also requires an earth ground for proper
operation of the control and flame--sensing electrode.
The 24--v circuit contains an automotive--type, 3--amp. fuse
located on the control. (See Fig. 32.) Any shorts of the 24--v
wiring during installation, service, or maintenance will cause this
fuse to blow. If fuse replacement is required, use ONLY a 3--amp.
fuse. The control LED will display status code 24 when fuse
needs to be replaced.
Proper instrumentation is required to service electrical controls.
The control in this furnace is equipped with a Status Code LED
(Light--Emitting Diode) to aid in installation, servicing, and
troubleshooting. It can be viewed through the sight glass in
blower access door. The furnace control LED is either ON
continuously, rapid flashing, or a code composed of 2 digits. The
first digit is the number of short flashes, the second digit is the
number of long flashes.
For an explanation of status codes, refer to service label located
on blower access door or Fig. 57, and the troubleshooting guide
which can be obtained from your distributor.
See Fig. 62 for a brief Troubleshooting guide.
For Controls with an Amber
The stored status codes will NOT be erased from the control
memory, if 115-- or 24--v power is interrupted. The control will
store up to five (5) status codes.
1. To retrieve status codes, proceed with the following:
NOTE: NO thermostat signal may be present at control, and all
blower--OFF delays must be completed.
WIRING
LED
a. Leave 115--v power to furnace turned on.
b. Remove outer access door.
c. Look into blower access door sight glass for currentLED
status. Removing blower access door will open blower
access doorswitch and terminate 115--v power to control
so that status code is not displayed.
d. BRIEFLY remove insulated terminal wire from the draft
safeguard (DSS) switch until LED goes out, then
reconnect it.
NOTE: If wire to DSS is disconnected longer than 4 sec, main
blower starts, and retrieval request is ignored.
2. When above items have been completed, the LED flashes
status code 4 times. Record this status code for further
troubleshooting. After the LED flashes status code four
times, BRIEFLY remove wire again from DSS switch
until LED goes out, then reconnect it to retrieve previous
status code (if available). Repeat as needed for more
previous status codes or until Code 11 appears.
Step 2 — Care and Maintenance
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Never store anything on, near, or in contact with the
furnace, such as:
1. Spray or aerosol cans, rags, brooms, dust mops,
vacuum cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning
compounds, plastic or plastic containers, gasoline,
kerosene, cigarette lighter fluid, dry cleaning fluids,
or other volatile fluids.
3. Paint thinners and other painting compounds, paper
bags, or other paper products. Explosure to these
materials could lead to corrosion of the heat
exchanger.
For continuing high performance and to minimize possible
furnace failure, periodic maintenance must be performed on this
furnace. Consult your local dealer about proper frequency of
maintenance and the availability of a maintenance contract.
!
WARNING
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal
injury, death or property damage.
Turn off the gas and electrical supplies to the unit before
performing any maintenance or service. Follow the
operating instructions on the label attached to the furnace.
!
WARNING
CARBON MONOXIDE POISONING AND FIRE
HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Never operate unit without a filter or with filter access door
removed.
46
Page 47
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts and servicing furnaces.
The minimum maintenance on this furnace is as follows:
1. Check and clean air filter each month or more frequently if
required. Replace if torn.
2. Check blower motor and wheel for cleanliness each
heating and cooling season. Clean as necessary.
3. Check electrical connections for tightness and controls for
proper operation each heating season. Service as
necessary.
4. Inspect burner compartment before each heating season
for rust, corrosion, soot or excessive dust. If necessary,
have furnace and burner serviced by a qualified service
agency.
5. Inspect the vent pipe/vent system before each heating
season for rust, corrosion, water leakage, sagging pipes or
broken fittings. Have vent pipes/vent system serviced by a
qualified service agency.
6. Inspect any accessories attached to the furnace such as a
humidifier or electronic air cleaner. Perform any service or
maintenance to the accessories as recommended in the
accessory instructions.
If stat us code recall is needed, briefl y remove then reconnect one main limit wire to di splay last st ored status code. On RED LED boards do not remove power or blower door before init iating st atus code recall.
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WI TH THE FIRST DIGIT DETERMI NED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.
11 NO PR EVIOUS CODE - Stored status code is erased automatically af ter 72 hours.
On RED LED boards stored status codes can also be erased when power
(115 VAC or 24 VAC) to control is interrupted.
12 BLOWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for the
selected blower off-delay time, if unit is powered up during a call for heat
(R-W/W1 closed) or (R-W/W1) opens during blower on-delay.
13 LIMIT CIRCUIT LOCKOUT - Lockout occurs if a limit, dra ft safeguard, flame rollout,
or blocked vent switch (if used) is open longer than 3 minutes.
- Control will auto reset after three hours. - Refer to #33.
14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.
21 GAS H EATING LOCKOUT - Control will NOT auto reset.
Check for: - Mis-wired gas v alve - Defective control (valve relay)
22 ABNORMA L FLAME-PROVING SIGNAL - Flame is proved while gas v alve is de-
energized. Inducer will run until fault is cleared. Check for:
- Leaky gas valve - Stuck-open gas valve
23 PRES SURE SWITCH DID NOT OPEN Check for: - Obstructed pressure tubing
24 SECO NDARY VOLTAGE FUSE IS OPEN Check for: - Short circuit in secondary
voltage (24VAC) wiring.
31 HIGH-H EAT PRESSURE SWITCH OR RELAY DID NOT CLOSE OR REOPENED
Control relay may be defective, ref er to status code #32
COMPONENT TEST
To initiate the component test sequence, shut OFF the room thermostat or disconnect the
"R" thermostat lead. Briefly short the TEST/TWIN terminal to the "Com 24V" terminal.
Status LED will flash last status code and then turn ON the inducer motor. The inducer
motor will start in HIGH speed and remain on HIGH speed until the end of the test then
shift to LOW speed for 7 to 15 seconds. The hot s urface igniter, blower motor LO HEAT
speed, blower motor HI HEAT speed, and blower motor COOL speed will be turned ON for
10-15 seconds each. Gas Valve and Humidifier will not be turned on. When the blower is
turned OFF the inducer will be switched to low-speed for 10 seconds.
LED CODE
CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2.
CONTINUOUS ON - Control has 24VAC power.
RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions.
- Pressure switch stuck closed
STATUS
32 LOW-HEAT PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than
five minutes, inducer shuts off for 15 minutes before retry. If opens during blower on-delay
period, blower will come on for the selected blower off-delay. Check for:
- Excessive wind - Restricted vent - Defective inducer motor
- Inadequate combustion air supply - Low inlet gas pressure (if LGPS u sed)
- Disconnected or obstructed pressure tubing
33 LIMIT CIRCUIT FAULT - Indicates a limit, draft safeguard, flame rollout, or blocked vent
switch (if used) is open. Blower will r un for 4 minutes or until open switch remakes
whichever is longer. If open longer th an 3 minutes, code changes to lockout #13. If open
less than 3 minutes status code #33 continues to flash until blower shuts off. Flame rollout
switch and BVSS require manual reset. Check for: - Dirty filter or restricted duct system
- Defective blower motor or capacitor - Proper vent sizing - Restricted vent
- Inadequate combustion air supply (Flame Roll-out Switch open).
34 IGNITION PROVING FAILURE - Control wil l try three more times before lockout #14 occurs.
If flame signal lost during blower on-delay period, blower will come on for the selected
blower off-delay. Check for: - Oxide buildup on fla me sensor (clean with fine stee l wool)
- Mis-wired pressure switches - Low-heat pressure switch stuck open
- Low inlet gas pressure (if LGPS used)
45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour lockout due to;
- Gas valve relay stuck open - Flame sense circuit failure - Software check error
Reset power to clear lockout. Replace control if status code repeats.
Fig. 57 -- Service Label
327598-101 REV. C
SERVICE
312A
A04210
47
Page 48
312A
A07125
Fig. 58 -- Wiring Diagram
48
Page 49
CLEANING AND/OR REPLACING AIR FILTER
The air filter arrangement will vary depending on the application.
NOTE: If the filter has an airflow direction arrow, the arrow
must point towards the blower.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts and servicing furnaces.
Media cabinet filter procedures:
NOTE: Media Cabinet is included with two--stage furnace.
Table 17 – Filter size information (in.)
FURNACE
CASING
WIDTH
14--- 1/216 X 25 X 114 X 25 X 1Cleanable*
17--- 1/216 X 25 X 116 X 25 X 1Cleanable*
2116 X 25 X 120 X 25 X 1Cleanable*
2416 X 25 X 124 X 25 X 1Cleanable*
*Recommended
1. Turn off electrical supply to furnace before removing filter
access door.
2. Remove filter cabinet door.
3. Slide filter out of cabinet.
4. If equipped with permanent, washable 1--in filter, clean
filter by spraying cold tap water through filter in opposite
direction of airflow. Rinse filter and let dry. Oiling or
coating of the filter is not recommended. See Table 17 for
size information.
5. If equipped with factory--specified disposable media filter,
replace only with media filter having the same part
number and size. For expandable replacement media, refer
to the instructions included with the replacement media. If
equipped with accessory KGAFR0301ALL external filter
rack. See Table 17.
6. Slide filter into cabinet.
7. Replace filter cabinet door.
8. Turn on electrical supply to furnace.
BLOWER MOTOR AND
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Blower access door switch opens 115--v power to control.
No component operation can occur unless switch is closed.
Caution must be taken when manually closing this switch
for service purposes.
NOTE: The blower wheel should not be dropped or bent as
balance will be affected.
FILTER SIZE
Side Return
Bottom Re -
turn
WHEEL
WARNING
FILTER TYPE
The following steps should be performed by a qualified
service agency.
To ensure long life and high efficiency, clean accumulated dirt
and grease from blower wheel and motor annually.
The inducer and blower motors are pre--lubricated and require no
additional lubrication. These motors can be identified by the
absence of oil ports on each end of the motor.
Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Loosen the thumbscrew from outer door and remove outer
door.
3. For downflow or horizontal furnaces having vent pipes
within the furnace that pass in front of the blower access
door:
a. Disconnect vent connector from furnace vent elbow.
b. Disconnect and remove short piece of vent pipe from
within furnace.
4. Remove 2 screws from blower access door and remove
blower access door.
5. Disconnect blower leads from furnace control. Record
wire color and location for reassembly. All other factory
wires can be left connected, but field thermostat
connections may need to be disconnected depending on
their length and routing.
6. Remove 2 screws holding control box to blower shelf.
7. Hang control box from front of furnace casing and away
from blower compartment.
8. Remove 2 screws holding blower assembly to blower
deck and slide blower assembly out of furnace.
9. Clean blower wheel and motor using a vacuum with soft
brush attachment. Blower wheel blades may be cleaned
with a small paint or flux brush. Do not remove or disturb
balance weights (clips) on blower wheel blades.
10. Vacuum any loose dust from blower housing, wheel and
motor.
11. If a greasy residue is present on blower wheel, remove
wheel from the blower housing and wash it with an
appropriate degreaser. To remove wheel:
NOTE: Before disassembly, mark blower mounting arms, motor,
and blower housing so motor and each arm is positioned at the
same location during reassembly.
a. Disconnectcapacitorwires(ifequipped)and ground wire
attached to blower housing.
b. Remove screws securing cutoff plate and remove cutoff
plate from housing.
c. Loosen set screw holding blower wheel on motor shaft
(160+/--20 in.--lb. when reassembling).
d. Remove bolts holding motor to blowerhousing and slide
motorout of wheel (40+/--10 in.--lb. when reassembling).
e. Remove blower wheel from housing.
f. Clean wheel and housing.
12. Reassemble motor and blower by reversing steps 11e,
through 11a. Be sure to reattach ground wire to the blower
housing.
13. Verify that blower wheel is centered in blower housing
and set screw contacts the flat portion of the motor shaft.
Loosen set screw on blower wheel and reposition if
necessary.
14. Spin the blower wheel by hand to verify that the wheel
does not rub on the housing.
15. Reinstall blower assembly in furnace.
312A
49
Page 50
16. Reinstall control box assembly in furnace.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in shortened heat
exchanger life.
Heating fan speed(s) MUST be adjusted to provide proper
air temperature rise as specified on the rating plate.
Recommended operation is at the midpoint of the rise range
or slightly above. Refer to “SET TEMPERATURE RISE”
under START--UP, ADJUSTMENT, and SAFETY
CHECK.
NOTE: Refer to Table 13 for motor speed lead relocation if leads
were not identified before disconnection.
17. Reconnect blower leads to furnace control. Refer to
312A
furnace wiring diagram, and connect thermostat leads if
previously disconnected.
18. To check blower for proper rotation:
a. Turn on electrical supply.
b. Manually close blower access door switch.
NOTE: If thermostat terminals are jumpered at the time blower
access door switch is closed, blower will run for 90 sec before
beginning a heating or cooling cycle.
c. Perform component self--test as shown at the bottom of
the SERVICE label, located on the front of blower access
door.
d. Verify blower is rotating in the correct direction.
19. If furnace is operating properly, RELEASE BLOWER
ACCESS DOOR SWITCH. Remove any jumpers or
reconnect any disconnected thermostat leads. Replace
blower access door.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury, or death.
Blower access door switch opens 115--v power to furnace
control. No component operation can occur unless switch is
closed. Exercise caution to avoid electrical shock from
exposed electrical components when manually closing this
switch for service purposes.
them thoroughly. A build--up of soot and carbon indicates that a
problem exists which needs to be corrected, such as improper
adjustment of manifold pressure, insufficient or poor quality
combustion air, incorrect size or damaged manifold orifice(s),
improper gas, or a restricted heat exchanger. Action must be taken
to correct the problem.
If it becomes necessary to clean the heat exchangers because of
dust or corrosion, proceed as follows:
1. Turn OFF gas and electrical power to furnace.
2. Remove outer access door.
3. Disconnect vent connector from furnace vent elbow.
4. For downflow or horizontal furnace having an internal
vent pipe, remove internal vent pipe within the casing.
5. Disconnect wires to the following components. Mark
wires to aid in reconnection of (be careful when
disconnecting wires from switches because damage may
occur):
a. Draft safeguard switch.
b. Inducer motor.
c. Pressure switches.
d. Limit overtemperature switch.
e. Gas valve.
f. Hot surface igniter.
g. Flame--sensing electrode
h. Flame rollout switches.
6. Remove screws that fasten the collector box assembly to
the cell panel. Be careful not to damage the collector box.
Inducer assembly and elbow need not be removed from
collector box.
7. Disconnect gas line from gas manifold.
8. Remove the 5 screws that attach the burner assembly to
the cell panel. The gas valve and individual burners need
not be removed from support assembly. Remove NOx
baffles if installed.
NOTE: Be very careful when removing burner assembly to
avoid breaking igniter. See Fig. 59 and 60 for correct igniter
location.
9/32˝
5/16˝
20. Downflow or horizontal furnaces with vent pipe through
furnace only:
a. Install and connect short pieceof vent pipe inside furnace
to existing vent.
b. Connect vent connector to vent elbow.
21. Turn on gas supply and cycle furnace through one
complete heating and cooling cycle. Verify the furnace
temperature rise as shown in Adjustments Section. Adjust
temperature rise as shown in Adjustments Section. If
outdoor temperature is below 70_F, turn off circuit breaker
to outdoor unit before running furnace in the cooling
cycle. Turn outdoor circuit breaker on after completing
cooling cycle.
CLEANING HEAT
The following steps should be performed by a qualified
service agency:
NOTE: If the heat exchangers get a heavy accumulation of soot
and carbon, they should be replaced rather than trying to clean
EXCHANGER
A05025
Fig. 59 -- Igniter Position--Side View
9. Using field--provided 25-- caliber rifle cleaning brush,
36--in. long 1/4” diameter steel spring cable, a variable
speed, reversible electric drill, and vacuum cleaner, clean
cells as follows:
50
Page 51
a. Remove metal screw fitting from wire brush to allow
insertion into cable.
b. Insert the twisted wire end of brush into end of spring
cable, and crimp tight with crimping tool or crimp by
striking with ball--peen hammer. TIGHTNESS ISVERY
IMPORTANT.
NOTE: The materials needed in item 9 can usually be purchased
at local hardware stores.
(1.) Attach variable--speed, reversible drill to the end of
spring cable (end opposite brush).
(2.) Insert brush end of cable into the outlet opening of
cell and slowly rotate with drill. DO NOT force
cable. Gradually insert cable into upperpass of cell.
(See Fig. 61.)
(3.) Work cable in and out of cell 3 or 4 times to obtain
sufficient cleaning. DO NOT pull cable with great
force. Reverse drill and gradually work cable out.
(4.) Insert brush end of cable in burner inlet opening of
cell, and proceed to clean 2 lower passes of cell in
same manner as upper pass.
(5.) Repeat foregoing procedures until each cell in
furnace has been cleaned.
(6.) Using vacuum cleaner, remove residue from each
cell.
(7.) Using vacuum cleaner with soft brush attachment,
clean burner assembly.
(8.) Clean flame sensor with fine steel wool.
(9.) Install NOx baffles (if removed.)
(10.) Reinstall burner assembly. Center burners in cell
openings.
10. Remove old sealant from cell panel and collector box
flange.
11. Spray releasing agent on the heat exchanger cell panel
where collector box assembly contacts cell panel.
NOTE: A releasing agent such as cooking spray or equivalent
(must not contain corn or canola oil, aromatic or halogenated
hydrocarbons or inadequate seal may occur) and RTV sealant
(G.E. 162, 6702, or Dow--Corning 738) are needed before
starting installation. DO NOT substitute any other type of RTV
sealant. G.E. 162 (P771--9003) is available through RCD in 3--oz.
tubes.
12. Apply new sealant to flange of collector box and attach to
cell panel using existing screws, making sure all screws
are secure.
13. Reconnect wires to the following components (Use
connection diagram on wiring label, if wires were not
marked for reconnection locations.):
a. Draft safeguard switch.
b. Inducer motor.
c. Pressure switches.
d. Limit overtemperature switch.
e. Gas valve.
f. Hot surface igniter.
g. Flame--sensing electrode.
h. Flame rollout switches.
14. Reinstall internal vent pipe, if applicable.
15. Reinstall vent connector on furnace vent elbow. Securely
fasten vent connector to vent elbow with 2 field--supplied,
corrosion --resistant, sheet metal screws located 180_ apart.
1-7/8”
A01026
Fig. 60 -- Igniter Position -- Top View
A91252
Fig. 61 -- Cleaning Heat Exchanger Cell
16. Replace blower access door only, if it was removed.
17. Set thermostat above room temperature and check furnace
for proper operation.
18. Verify blower airflow and speed changes between heating
and cooling.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,
death and/or property damage.
Never use a match or other open flame to check for gas
leaks. Use a soap--and--water solution.
19. Check for gas leaks.
20. Replace outer access door.
Step 3 — Sequence of Operation
NOTE: Furnace control must be grounded for proper operation
or control will lockout. Control is grounded through green wire
connected to gas valve and burner bracket screw. Using the
schematic diagram in Fig. 58, follow the sequence of operation
through the different modes. Read and follow the wiring diagram
very carefully.
NOTE: If a power interruption occurs during a call for heat
(W/W1 or W/W1--and--W2), the control run the blower for the
selected blower off--delay period two seconds after power is
restored and if the thermostat is still calling for gas heating. The
LED light will flash code 12 during this period, after which the
LED will be ON continuous, as long as no faults are detected.
After this period, the furnace will respond to the thermostat
normally.
The blower door must be installed for power to be conducted
through the blower door interlock switch ILK to the furnace
312A
51
Page 52
control CPU, transformer TRAN, inducer motor IDM, blower
motor BLWM, hot--surface igniter HSI, and gas valve GV.
1. Two--StageHeating(Adaptivemode)with
Single--Stage Thermostat
(See Fig. 24 or 33 for thermostat connections)
NOTE: The low--heat only switch (LHT) selects either the
low--heat only operation mode when ON, (see item 2. below) or
the adaptive heating mode when OFF in response to a call for
heat. (See Fig. 34.) When the W2 thermostat terminal is energized
it will always cause high--heat operation when the R to W circuit
is closed, regardless of the setting of the low--heat only switch.
This furnace can operate as a two--stage furnace with a
single-- stage thermostat because the furnace control CPU includes
a programmed adaptive sequence of controlled operation, which
selects low--heat or high--heat operation. This selection is based
upon the stored history of the length of previous gas--heating
periods of the single--stage thermostat.
The furnace will start up in either low-- or high--heat. If the
furnace starts up in low--heat, the control CPU determines the
312A
low--heat on--time (from 0 to 16 minutes) which is permitted
before switching to high--heat.
If the power is interrupted, the stored history is erased and the
control CPU will select low--heat for up to 16 minutes and then
switch to high--heat, as long as the thermostat continues to call for
heat. Subsequent selection is based on stored history of the
thermostat cycle times.
The wall thermostat “calls for heat”, closing the R to W circuit.
The furnace control performs a self--check, verifies the low--heat
and high--heat pressure switch contacts LPS and HPS are open,
and starts the inducer motor IDM in high--speed.
a. Inducer Prepurge Period
(1.) If the furnace control CPU selects low--heat
operation the inducer motor IDM comes up to
speed, the low--heat pressure switch LPS closes, and
the furnace control CPU begins a 15--second
prepurge period. After the low--heat pressureswitch
re--closes the furnace control CPU will begin a
15--second prepurgeperiod,and continue to run the
inducer motor IDM at high--speed.
(2.) If the furnace control CPU selects high--heat
operation, the inducer motor IDM remains running
at high--speed, and the high--heat pressure switch
relay HPSR is de--energized to close the NC contact.
When sufficient pressure is available the high--heat
pressure switch HPS closes, and the high--heat gas
valve solenoid GV--HI is energized. The furnace
control CPU begins a 15--second prepurge period
after the low--heat pressure switch LPS closes. If the
high--heatpressure switch HPS fails to close and the
low-- heat pressure switch LPS closes, the furnace
will operate at low--heat gas flow rate until the
high--heat pressure switch closes for a maximum of
2 minutes after ignition.
b. Igniter Warm--Up--At the end of the prepurge period,
the (Hot Surface Igniter) HSI is energized for a
17--second igniter warm--up period.
c. Trial--for--IgnitionSequence--Whentheigniter
warm--up period is completed the main gas valve relay
contacts GVR--1 and --2 close to energize the gas valve
solenoid GV--M, the gas valve opens, and 24 vac power
is supplied for a field--installed humidifier at the HUM
terminal.The gas valve solenoidGV--M permitsgasflow
to the burners whereitis ignitedby the HSI. Five sec after
the GVR closes, a 2--sec flame proving period begins.
The HSI igniter will remain energized until the flame is
sensed or until the 2--sec flame proving period begins. If
the furnace control CPU selects high--heat operation, the
high--heat gas valve solenoid GV--HI is also energized.
d. Flame--Proving--When theburner flameis proved at the
flame--proving sensor electrode FSE, the inducer motor
IDM switches to low--speed unless running at
high--speed, and the furnace control CPU begins the
blower--ON delay period and continues to hold the gas
valve GV--M open. If the burner flame is not proved
within two seconds, the control CPU will close the gas
valve GV--M,and thecontrol CPU will repeatthe ignition
sequence for up to three more Trials-- For--Ignition before
going to Ignition-- Lockout. Lockout will be reset
automatically after three hours, by momentarily
interrupting 115 vac power to the furnace, or by
interrupting 24 vac power at SEC1 orSEC2 to thefurnace
controlCPU (not atW/W1, G, R,etc.). If flame is proved
when flame should not be present, the furnace control
CPU will lock out of Gas--Heating mode and operate the
inducermotor IDM on highspeed until flameisno longer
proved.
e. Blower--ON Delay --If the burner flame is proven the
blower--ON delay for low--heat and high--heat are as
follows:
Low--Heat--45 seconds after the gas valve GV--M is
energized the blower motor (BLWM) is energized at LO
HEAT speed.
High--Heat--25 seconds after the gas valve GV--M is
energized the BLWM is energized at HI HEAT speed.
Simultaneously, the electronic air cleaner (EAC--1)
terminal isenergized and remains energized as long asthe
BLWM is energized.
f. Switching from Low--to High--Heat--If the furnace
control CPU switches from low--heat to high--heat, the
furnace control CPU will switch the inducer motor IDM
speed from low to high. The high--heat pressure switch
relay HPSR is de--energized to close the NC contact.
When sufficient pressure is available the high--heat
pressure switch HPS closes, and the high--heat gas valve
solenoid GV--HI is energized. The blower motor BLWM
will switch to HI HEAT speed five seconds after the
furnace control CPU switches from low--heat to
high--heat.
g. Switching from High-- to Low--Heat--The furnace
control CPU will not switch from high--heat to low--heat
while thethermostat R--to--W circuit is closed when using
a singlestage thermostat.
h. Blower--OFF Delay--When thethermostatis satisfied, the
R to W circuit is opened, de--energizing the gas valve
GV--M, stopping gas flow to the burners, and
de--energizing the humidifier terminal HUM. The
inducer motor IDM will remain energized for a5--second
post--purge period. The blower motor BLWM and air
cleaner terminal EAC--1 will remain energized for 90,
120, 150, or 180 seconds (depending on selection at
blower--OFF delay switches). The furnace control CPU
is factory--set for a 120--second blower--OFF delay.
2. Two-- Stage Thermostat and Two--Stage Heating (See Fig.
32 for thermostat connections)
NOTE: In this mode the LHT must be ON to select the low--heat
only operation mode in response to closing the thermostat
R--to--W1 circuit. Closing the thermostat R--to--W1--and--W2
circuits always causes high--heat operation, regardless of the
setting of the low--heat--only switch.
The wall thermostat “calls for heat”, closing the R--to--W1 circuit
for low--heat or closing the R--to--W1 and--W2 circuits for
high--heat. The furnace control performs a self--check, verifies the
52
Page 53
low-- heat and high--heat pressure switch contacts LPS and HPS
are open, and starts the inducer motor IDM in high--speed.
The start up and shut down functions and delays described in
item 1. above apply to the 2--stage heating mode as well, except
for switching from low-- to high--Heat and vice versa.
a. Switching from Low-- to High--Heat--If the thermostat
R--to-- W1 circuit is closed and the R--to--W2 circuit
closes, the furnace control CPU will switch the inducer
motor IDM speed from low to high. The high--heat
pressure switch relay HPSR is de--energized to close the
NC contact. When sufficient pressure is available the
high--heat pressure switch HPS closes,and the high--heat
gas valve solenoid GV--HI is energized. The blower
motorBLWM willswitch to HI HEAT speed five seconds
after the R--to--W2 circuit closes.
b. Switching from High-- to Low--Heat--If the thermostat
R--to--W2 circuitopens, and theR--to--W1 circuitremains
closed, the furnace control CPU will switch the inducer
motor IDM speed from high to low. The high--heat
pressure switch relay HPSR is energized to open the NC
contact and de--energizethehigh--heatgasvalvesolenoid
GV--HI.When the inducer motor IDM reduces pressure
sufficiently, the high-- heat pressure switch HPS will
open. The gas valve solenoid GV--M will remain
energized as long as the low--heat pressure switch LPS
remains closed. The blower motor BLWM will switch to
LO HEAT speed five seconds after the R--to--W2 circuit
opens.
3. Cooling Mode--The thermostat “calls for cooling.”
a. Single--Speed Cooling--
(See Fig. 28 for thermostat connections)
The thermostat closes the R--to--G--and--Y circuits. The
R--to-- Y circuit starts the outdoor unit, and the
R--to--G--and--Y/Y2 circuits start the furnace blower
motor BLWM on COOL speed.
The electronic air cleaner terminal EAC--1 is energized
with 115 vac when theblower motor BLWM isoperating.
When the thermostat is satisfied, the R--to --G and--Y
circuits are opened. The outdoor unit will stop, and the
furnace blower motor BLWM willcontinue operatingon
the COOL speed for an additional 90 seconds. Jumper
Y/Y2 to DHUM to reduce the cooling off--delay to 5
seconds. (See Fig. 25.)
b. Single--Stage Thermostat and Two--Speed Cooling
(Adaptive Mode)
(See Fig. 33 for thermostat connections)
This furnace can operate a two --speed cooling unit with
a single--stage thermostat because the furnace control
CPU includes a programmed adaptive sequence of
controlled operation, which selects low--cooling or
high--cooling operation. This selection isbased upon the
stored history of the length of previouscooling period of
the single--stage thermostat.
NOTE: The air conditioning relay disable jumper ACRDJ must
be connected to enable the adaptive cooling mode in response to
a call for cooling. (See Fig. 34.) When ACRDJ is in place, the
furnace control CPU can turn on the air conditioning relay ACR
to energize the Y/Y2 terminal and switch the outdoor unit to
high--cooling.
The furnace control CPU can start up the cooling unit in either
low-- or high--cooling. If starting up in low--cooling, the furnace
control CPU determines the low--cooling on--time (from 0 to 20
minutes) which is permitted before switching to high--cooling. If
the power is interrupted, the stored history is erased and the
furnace control CPU will select low--cooling for up to 20 minutes
and then energize the air conditioning relay ACR to energize the
Y/Y2 terminal and switch the outdoor unit to high--cooling, as
long as the thermostat continues to call for cooling. Subsequent
selection is based on stored history of the thermostat cycle times.
The wall thermostat “calls for cooling”, closing the
R--to--G--and--Y circuits. The R--to--Y1 circuit starts the outdoor
unit on low--cooling speed, and the R--to--G--and--Y1 circuits
starts the furnace blower motor BLWM at low--cool speed (same
speed as LO HEAT).
If the furnace control CPU switches from low--cooling to
high--cooling, the furnace control CPU will energize the air
conditioning relay ACR. When the air conditioning relay ACR is
energized the R--to--Y1--and--Y2 circuits switch the outdoor unit
to high--cooling speed, and the R--to--G--and--Y1--and--Y/Y2
circuits switch the furnace blower motor BLWM to COOL speed.
NOTE: When transitioning from low--cooling to high--cooling
the outdoor unit compressor will shut down for 1 minute while
the BLWM continues to run at low--cool speed (same speed as
LO--HEAT) until the outdoor unit compressor comes back on at
high speed.
The electronic air cleaner terminal EAC--1 is energized with 115
vac whenever the blower motor BLWM is operating. When the
thermostat is satisfied, the R--to--G--and--Y circuit are opened.
The outdoor unit stops, and the furnace blower BLWM and
electronic air cleaner terminal EAC--1 will remain energized for
an additional 90 seconds. Jumper Y1 to DHUM to reduce the
cooling off--delay to 5 seconds. (See Fig. 34.)
c. Two--Stage Thermostat and Two--Speed Cooling (See
Fig. 32 for thermostat connections)
NOTE: The air conditioning relay disable jumper ACRDJ must
be disconnected to allow thermostat control of the outdoor unit
staging. (See Fig. 34.)
The thermostat closes the R--to--G--and --Y1 circuits for
low--cooling or closes the R--to--G--and--Y1--and--Y2 circuits for
high--cooling. The R--to--Y1 circuit starts the outdoor unit on
low--cooling speed, and the R--to--G--and--Y1 circuit starts the
furnace blower motor BLWM on low-- cool speed (same speed as
LO HEAT). The R--to--Y1--and--Y2 circuits start the outdoor unit
on high--cooling speed, and the R--to--G--and-- Y/Y2 circuits start
the furnace blower motor BLWM on COOL speed. The
electronic air cleaner terminal EAC--1 is energized with 115 vac
whenever the blower motor BLWM is operating. When the
thermostatissatisfied,theR-- to-- G--and--Y1or
R--to--G--and--Y1--and--Y2 circuits are opened. The outdoor unit
stops, and the furnace blower BLWM and electronic air cleaner
terminal EAC--1 will remain energized for an additional 90
seconds. Jumper Y1 to DHUM to reduce the cooling off--delay to
5 seconds. (See Fig. 34.)
4. Thermidistat Mode
(See Fig. 27 -- 29 for Thermidistat connections) The
dehumidification output, DHUM on the Thermidistat
should be connected to the furnace control thermostat
terminal DHUM. When there is a dehumidify demand, the
DHUM input is activated, which means 24 vac signal is
removed from the DHUM input terminal. In other words,
the DHUM input logic is reversed. The DHUM input is
turned ON when no dehumidify demand exists. Once 24
vac is detected by the furnace control on the DHUM input,
the furnace control operates in Thermidistat mode. If the
DHUM input is low for more than 48 hours, the furnace
control reverts back to non --Thermidistat mode.
The cooling operation described in item 3. above also
applies to operation with a Thermidistat. The exceptions
are listed below:
a. Low cooling -- When the R--to--G--and--Y1 circuit is
closed and there is a demand for dehumidification,the
furnace blower motor BLWM will continue running at
low-- cool speed (same speed as LO HEAT).
312A
53
Page 54
312A
b. High cooling --When the R-- to--G--and--Y/Y2 circuit is
closed and there is a demand for dehumidification,the
furnace blower motor BLWM will drop the blower speed
from COOL to HI HEAT for a maximum of 10 minutes
before reverting back to COOL speed. If there is still a
demand for dehumidification after 20 minutes, the
furnace control CPU will drop the blower speed back to
HI HEAT speed. This alternating 10--minute cycle will
continue as long as there is a call for cooling.
c. Cooling off--delay -- When the gcall for coolingh is
satisfied and there is a demand for dehumidification, the
cooling blower--off delay is decreased from 90 seconds
to 5 seconds.
5. Continuous Blower Mode
When the R--to--G circuit is closed by the thermostat, the
blower motor BLWM will operate on continuous--blower
speed (can be set to LO HEAT, HI HEAT, or COOL
speed). Factory default is LO HEAT speed. Terminal
EAC--1 is energized as long as the blower motor BLWM is
energized. During a call for heat, the blower BLWM will
stop during igniter warm--up (17 seconds), ignition (7
seconds), and blower--ON delay (45 seconds in low--heat,
and 25 seconds in high--heat), allowing the furnace heat
exchangers to heat up more quickly, then restarts at the
end of the blower--ON delay period at LO HEAT or HI
HEAT speed respectively. The blower motor BLWM will
revert to continuous--blower speed after the heating cycle
is completed. In high--heat, the furnace control CPU will
hold the blower motor BLWM at HI HEAT speed during
the selected blower--OFF delay period before reverting to
continuous--blower speed.
When the thermostat “calls for low--cooling”, the blower
motor BLWM will switch to operate at low--cool speed
(same speed as LO HEAT). When the thermostat is
satisfied, the blower motor BLWM will operate an
additional 90 seconds on low--cool speed before reverting
back to continuous--blower speed.
When the thermostat “calls for high--cooling”, the blower
motor BLWM will operate at COOL speed. When the
thermostat is satisfied, the blower motor BLWM will
operate an additional 90 seconds on COOL speed before
reverting back to continuous--blower speed.
When the R--to--G circuit is opened, the blower motor
BLWM will continue operating for an additional 5
seconds, if no other function requires blower motor
BLWM operation.
Continuous Blower Speed Selection from Thermostat
To select different continuous--blower speeds from the
room thermostat, momentarily turn off the FAN switch or
pushbutton on the room thermostat for 1--3 seconds after
the blower motor BLWM is operating. The furnace control
CPU will shift the continuous--blower speed from the
factory setting of LO HEAT to HI HEAT speed.
Momentarily turning off the FAN switch again at the
thermostat will shift the continuous--blower speed from HI
HEAT to COOL. Repeating the procedure will shift the
continuous--blower speed from COOL to LO HEAT
speed. The selection can be changed as many times as
desired and is stored in the memory to be automatically
used following a power interruption.
NOTE: If the blower--off delay is set to the maximum, the
adjustable continuous--fan feature is locked (i.e., fan speed cannot
be changed from its current setting).
6. Heat Pump
(See Fig. 28 through 31 for thermostat connections)
When installed with a heat pump, the furnace control
automatically changes the timing sequence to avoid long
blower off times during demand defrost cycles. When the
R--to-- W/W1--and--Y1 or R--to--W/W1--and--Y1--and--G
circuits are energized the furnace control CPU will switch
to or turn on the blower motor BLWM at low--cool speed
(same speed as LO HEAT), and begin a low-- heat cycle.
The blower motor BLWM will remain on until the end of
the prepurge period, then shut off for 24 seconds then
come back on at LO HEAT speed. When the W/W1 input
signal disappears, the furnace control begins a normal
inducer post--purge period and the blower remains running
at LO HEAT speed. If the R--to-- W/W1--and--Y1--and--G
signals disappear at the same time, the blower motor
BLWM will remain on for the selected blower-- OFF delay
period. If the R--to--W/W1--and--Y1 signals disappear,
leaving the G signal, the blower motor BLWM will remain
on for the selected blower--OFF delay period then switch
to continuous--blower speed.
When the R--to--W/W1--and--Y/Y2, R--to--W/W1--and-Y / Y 2 --a n d -- G ,R -- t o -- W / W 1 -- a n d -- Y 1 -- a n d -- Y / Y 2 ,o r
R--to--W/W1--and-- Y1--and--Y/Y2--and--G circuits are
energized the furnace control CPU will switch to or turn
on the blower motor BLWM at COOL speed, and begin a
high--heat cycle. The blower motor BLWM will remain on
until the end of the prepurge period, then shut off for 24
seconds then come back on at HI HEAT speed. When the
W/W1 input signal disappears, the furnace control begins
a normal inducer post--purge period and the
blower switches to COOL speed after a 3 second delay. If
t h e R -- t o -- W / W 1 -- a n d -- Y / Y 2 -- a n d -- G o r R -- t o -- W / W 1 -- a n d
--Y1--and-- Y/Y2--and--G signals disappear at the same
time, the blower motor BLWM will remain on for the
selected blower--OFF delay period. If the R--to--W/W1-a n d -- Y / Y 2 o r R -- t o -- W / W 1 -- a n d -- Y 1 -- a n d -- Y / Y 2 s i g n a l s
disappear, leaving the G signal, the blower motor BLWM
will remain on for the selected blower-- OFF delay period
then switch to continuous--blower speed.
Step 4 — Wiring Diagrams
Refer to wiring diagram, Fig. 58.
Step 5 — Troubleshooting
Refer to the service label. (See Fig. 57—Service Label.) The
Troubleshooting Guide can be a useful tool in isolating furnace
operation problems. Beginning with the word “Start,” answer
each question and follow the appropriate arrow to the next item.
The Guide will help to identify the problem or failed component.
After replacing any component, verify correct operation
sequence.
54
Page 55
A02107A
NO
Is door switch closed?
NO
YES
Is door switch closed?
NO
YES
TROUBLESHOOTING GUIDE
Is circuit breaker closed?
NO
Is there 115V going to switch?
NO
YES
Check for continuity in wire from circuit
breaker to furnace.
YES
Replace door switch.
YES
Is 24V present at W/W1, W2, Y1, Y/Y2 or G
thermostat terminals on the furnace control?
NO
Does the control respond to W/W1, W2, Y1,
Y/Y2, and G (24V) thermostat signals?
NO
YES
Disconnect all the thermostat wires from the
furnace control.
YES
Run system through a low-heat, high-heat,
or cooling cycle to check operation. Status
NO
The thermostat is not compatible with the
furnace control. Either install a ballast resistor,
connect the Com24V thermostat terminal to
Does the problem repeat when using a
jumper wire?
YES
codes are erased after 72 hours. On RED
LED boards stored status codes can also be
erased whenever (115V or 24V) is interrupted.
Replace furnace control.
the thermostat, or replace the thermostat.
312A
NO
Close circuit breaker and go back to START.
Replace transformer.
Check room thermostat or
interconnecting cable.
Fig. 62 -- Troubleshooting Guide 2--Speed
Is there 115V at L1 and L2?
NO
START
Is LED status light on?
Is there 24V at SEC-1 and SEC-2?
YES
Replace furnace control.
Check for correct line voltage polarity. If
units are twinned, check for proper low-
voltage (24V) transformer phasing.
YES
NO
Is LED status light blinking rapidly
without a pause?
To recall status code briefly remove and reconnect one RED wire from the
draft safeguard switch to display stored status code. On RED LED control do
not remove power or blower access panel before initiating status code recall.
You can also recall the previous status code by momentarily shorting the
TEST/TWIN terminal to Com24V terminal until the LED goes out. LED will
flash the status code of the previous fault or status code #11 (1 short and 1
long flash) if there was no previous fault. After the control repeats the code
4 times, the control will start the component test sequence. Once indicated
the control will turn ON at HI HEAT speed. The inducer will run for the entire
component test. The HSI, blower motor LO HEAT speed, HI HEAT speed, and
COOL speed will run for 10 – 15 seconds each. Gas valve and humidifier will
not be turned on. When the blower motor is turned OFF the inducer will be
switched to low-speed for 10 seconds.
NO
YES
Is LED status light blinking ON/OFF slowly
with a combination of short and long flashes?
Determine status code. The status code is a
2 digit number with the first digit determined
by the number of short flashes and the second
digit by the number of long flashes?
55
Was there a previous status code other
than #11?
YES
Go to section below for the status code that
was flashed.
Page 56
reset after 1 hour lockout due to:
45 CONTROL CIRCUITRY LOCKOUT Auto-
- Flame circuit failure.
- Gas valve relay stuck open.
- Software check error.
Reset power to clear lockout. Replace
control if code repeats.
Check for continuity in the harness and igniter.
Replace furnace control.
Replace defective component.
Check connections. If OK, replace control.
Check that all gas valves are turned on.
Replace valve.
Check for:
- Inadequate flame carryover or rough
ignition.
- Low inlet gas pressure.
- Proper firing rate.
(.045” nominal)
- Blocked or incorrect carry- over gap.
Allow blower to come on and repeat test to
check for intermittent operation.
Check connections and retry. If current is
near typical value (4.0-6.0 nominal) and
burners will not stay on, repeat check in high-
heat. If burners will still not stay on replace
control. If burners operate in high-heat then
switch to low-heat, check manifold pressure.
If OK, check burner carryover and flame
sensor location.
A05001
Replace electrode.
Replace furnace control.
312A
NO
tube.
WHILE HIGH-HEAT PRESSURE
SWITCH IS CLOSED - Check for:
- Low-heat pressure switch stuck open.
- Disconnected or obstructed pressure
- Miswired pressure switches.
- Low inlet gas pressure (if LGPS used).
43 LOW-HEAT PRESSURE SWITCH OPEN
NOT CLOSE OR REOPENED – If open
longer than 5 minutes, inducer shuts off
for 15 minutes before retry. If opens
during blower on-delay period, blower
will come on for the selected blower off-
delay. Check for:
- Proper vent sizing.
- Low inlet gas pressure (if LGPS used).
- Low inducer voltage (115V).
- Inadequate combustion air supply.
32 LOW-HEAT PRESSURE SWITCH DID
YES
Unplug igniter harness from control and
initiate another component test sequence.
Check for 115V between pin 1 and
NEUTRAL-L2 on the control. Was 115V
present for the 15 second period?
tubing.
- Disconnected or obstructed pressure
- Defective inducer motor.
- Defective pressure switch.
- Excessive wind.
- Restricted vent.
NO
YES
Reconnect the R thermostat lead and set
thermostat to call for heat. Connect voltmeter
across gas valve connections. Does gas
valve receive 24V?
Blower will run for 4 minutes or until
limit, draft safeguard, flame rollout, or
blocked vent shutoff switch* (if used) is
open.
open switch remakes whichever is longer.
If open longer than 3 minutes, code
33 LIMIT CIRCUIT FAULT – Indicates the
NO
YES
Does gas valve open and allow gas to flow?
changes to lockout #13. If open less
than 3 min. status code #33 continues
to flash until blower shuts off. Flame
rollout switch and BVSS requires manual
NO
YES
Do the main burners ignite?
reset. Check for:
- Dirty filter or restricted duct system.
- Defective blower motor or capacitor.
- Loose blower wheel.
- Defective switch or connections.
YES
NO
Do the main burners stay on?
(flame rollout switch open).
- Restricted vent.
- Inadequate combustion air supply
- Proper vent sizing.
- Excessive wind.
NO
YES
Repeat call for heat and check flame sensor
current during trial for ignition period. Is the
DC microamps below 0.5?
Clean flame sensor with fine steel wool and
recheck current. Nominal current is 4.0 to
6.0 microamps.
NO
is not sensed during the trial for ignition
period, the control will repeat the ignition
sequence 3 more times before lockout
#14 occurs. If flame signal is lost during
the blower on-delay period, blower will
come on for the selected blower off-delay.
Check the following items first before
34 IGNITION PROVING FAILURE – If flame
NO
Is current near typical value?
to furnace sheet metal.
proceeding to the next step.
- Gas valve turned off.
- Green/Yellow wire MUST be connected
- Flame sensor must not be grounded.
- Manual shut-off valve.
NO
YES
YES
Will main burners ignite and stay on?
YES
To determine whether the problem is in
the gas valve, igniter, or flame sensor
the system can be operated in the
component test mode to check the igniter.
First remove the R thermostat connection
from the control and initiate the
Fixed.
component test sequence. Does the
igniter glow orange/white by the end of
the 15 second warm-up period?
Fig. 63 -- Troubleshooting Guide 2--Speed
* Blocked vent shutoff switch used in Chimney Adapter Kit
are erased after 72 hours. On RED LED
boards stored status codes can also be
erased whenever power (115V or 24V)
is interrupted. Run system through a
low-heat, high-heat, or cooling cycle to
check system.
(115V OR 24V) – Normal operation.
Blower runs for the selected blower off-
11 NO PREVIOUS CODE – Stored codes
12 BLOWER ON AFTER POWER UP –
delay, if unit is powered up during a call
for heat (R-W/W1 closed) or when (R-
W/W1 opens) during the blower on-delay
period.
occurs if the limit, draft safeguard, flame
rollout, or blocked vent switch* (if used)
is open longer than 3 minutes. Control will
auto-reset after 3 hours. See code 33.
13 LIMIT CIRCUIT LOCKOUT – Lockout
ignite gas and prove flame in 4 attempts.
14 IGNITION LOCKOUT – System failed to
Control will auto-reset after 3 hours. See
status code 34.
control.
power and wait 5 minutes to retry.
Check for:
- Stuck closed gas valve relay on
- Miswire or short to gas valve wire.
Flame is proved while gas valve is de-
energized. Inducer will run until fault is
cleared. Check for:
- Stuck open or leaky gas valve.
Check for:
- Obstructed pressure tube.
- Pressure switch stuck closed.
21 GAS HEATING LOCKOUT – Tur n off
22 ABNORMAL FLAME-PROVING SIGNAL
23 PRESSURE SWITCH DID NOT OPEN
(24V) wiring including thermostat
OPEN Check for:
- Short circuit in secondary voltage
24 SECONDARY VOLTAGE FUSE IS
leads. Disconnect thermostat leads
to isolate short circuit.
RELAY DID NOT CLOSE OR
31 HIGH-HEAT PRESSURE SWITCH OR
REOPENED - Check for:
- Control relay may be defective.
- Gas valve is miswired.
- See status code 32.
56
Page 57
57
Page 58
E2007 B ryant Heating & Cooling Systems 7310 W. Mo rris St. Indianapolis, IN 46231Printed in U.S.A.Edition Date: 02/07
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
58
Catalog No. II312A--- 4 5 --- 8
Replaces: II312A--- 45--- 7
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.