Bryant 116B User Manual

116B Legacyt Line 16 Air Conditioner with Puronr Refrigerant 1--1/2 to 5 Nominal Tons
Product Data
the environmentally sound refrigerant
Bryant’s Air Conditioners with Puronr refrigerant provide a collection of features unmatched by any other family of equipment. The 116B has been designed utilizing Bryant’s Puron refrigerant. The environmentally sound refrigerant allows you to make a responsible decision in the protection of the earth’s ozone layer.
This product has been designed and manufactured to meet Energy Starr criteria for energy efficiency when matched with appropriate coil components. Refer to the combination ratings in the Product Data for system combinations that meet Energy Starr guidelines.
NOTE: Ratings contained in this document are subject to change at any time. Always refer to the AHRI directory (www.ahridirectory.org) for the most up--to--date ratings information.
INDUSTRY LEADING FEATURES / BENEFITS
Efficiency
14 -- 16.5 SEER/11.0-- 13.5 EER
S S Microtube Technologyt refrigeration system S Indoor air quality accessories available
Sound
Sound level as low as 76 dBA
S S Sound level as low as 74 dBA with accessory sound
blanket
Comfort
System supports Edger Thermidistatt or standard
S
thermostat controls
Reliability
Puronr refrigerant -- environmentally sound, won’t
S
deplete the ozone layer and low lifetime servce cost.
S Scroll compressor S Internal pressure relief valve S Internal thermal overload S Filter drier S Balanced refrigeration system for maximum reliability
Durability
DuraGuardt protection package:
S Solid, durable sheet metal construction S Dense wire coil guard standard S Baked--on, complete outer coverage, powder paint
Applications
Long--line -- up to 250 feet (76.20 m) total equivalent
S
length, up to 200 feet (60.96 m) condenser above evaporator, or up to 80 ft. (24.38 m) evaporator above condenser (See Longline Guide for more information.)
S Low ambient (down to --20_F/--28.9_C)) with
accessory kit

MODEL NUMBER NOMENCLATURE

12345678910111214 N N N A A/N N N N N A/N A/N N A
116BNA03600 00
Prod-
uct
Famil y
1=AC
Tier SEER
1=
Legacy
6=16 SEER B=Puron
RNC
Major
Series
Vol tag e
N=
208--- 230--- 1
or
208/230--- 1
Grille
Vari at ion s
A=Dense
ISO 9001:2000
Cooling Capacity
Open Open Open Series
0=Not
Defined
0=Not
Defined
0=Not
Defined
116B
the environmentally sound refrigerant
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org.
REGISTERED
This product has been designed an d manuf actured t o meet Energy S tar® criteria for energy eff iciency when matched with appropriate coi l components. However, proper refrigerant charge and proper air flow are crit ical to achieve rated capacity and efficiency. Installation of this product should follow all manufacturing refrigerant charging and air flow instructions. Failure to confirm
proper charge and air flow may reduce energy efficiency and shorten equipment l ife.

STANDARD FEATURES

Feature 018 024 030 036 042 048 / 049 060 / 061
Puron Refrigerant X X X X X X X
Maximum SEER * 16.0 16.0 16.5 16.5 16.0 16.0 16.0
Scroll Compressor X X X X X X X
FieldInstalledFilterDrier X X X X X X X
Fron t Seating Service Valv es X X X X X X X
Internal Pressure Relief Valve X X X X X X X
Internal Thermal Overload X X X X X X X
Long Line capability X X X X X X X
Low Ambient capability with Kit X X X X X X X
Dense Grille X X X X X X X
* With approved combinations X=Standard

PHYSICAL DATA

UNIT SIZE ---VOLTAGE, SERIES 018 -- -B 024--- A 030 -- -A 036--- A 042 --- A 048- -- B 049--- A 060--- A 061--- A
Operatin g Weight lb (kg)
Shipping Weight lb (kg)
Compressor Type Scroll REFRIGERANT Puron® (R --- 410A)
Control TXV (Puron® Hard Shutoff)
Charge lb (kg)
COND FAN Propeller Type, Direct Drive
Air Discharge Vertical Vertical Air Qty (CFM) 1881 2614 2614 3223 3810 4046 4046 4046 4046 Motor HP 1/12 1/10 1/10 1/12 1/5 1/4 1/4 1/4 1/4 Motor RPM 1100 1100 1100 800 800 800 800 800 800
COND COIL
Face Area (Sq ft) 11.50 15.10 17.20 17.60 25.15 25.15 25.15 30.15 30.15 Fins per In. 25 25 25 25 25 20 20 20 20 Rows 1 1 1 1 1 2 1 2 2 Circuits 3 4 4 4 6 7 7 8 8
VALVECONNECT.(In.ID)
Vapor 3/4 3/4 3/4 7/8 7/8 7/8 7/8 7/8 7/8 Liquid 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
REFRIGERANT TUBES (In. OD)
Rated Vapor* 3/4 7/8 1 --- 1 / 8 Max Liquid Line { 3/8
* Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
Note: See unit Installation Instruction for proper installation.
{ See Liquid Line Sizing For Cooling Only Systems with Puron Refrigerant tables.
125
(56.7)
154
(69.9)
4.60
(2.09)
147
(66.5)
183
(82.8)
6.00
(2.72)
153
(69.3)
188
(85.2)
6.81
(3.09)
165
(74.8)
204
(92.5)
7.00
(3.18)
213
(96.4)
254
(115.2)
8.62
(3.91)
264
(119.7)
317
(143.8)
13.0
(5.90)
231
(104.8)
269
(222.0)
9.00
(4.08)
272
(123.4)
310
(140.6)
14.50 (6.58)
272
(123.4)
310
(140.6)
14.50 (6.58)
2

REFRIGERANT PIPING LENGTH LIMITATIONS

Liquid Line Sizing and Maximum Total Equivalent Lengths
The maximum allowable length of a residential split system depends on the liquid line diameter and vertical separation between indoor and outdoor units.
See Table below for liquid line sizing and maximum lengths :
Maximum Total Equivalent Length Outdoor Unit BELOW Indoor Unit
Liquid
Size
18000
AC with
Puron
24000
AC with
Puron
30000
AC with
Puron
36000
AC with
Puron 42000
AC with
Puron
Liquid Line
Connection
3/8
3/8
3/8
3/8
3/8
Line
Diam.
w/ TXV
(0--- 1.5)
1/4 150 150 125 100 100 75 --- --- --- --- --- --­5/16 250* 250* 250* 250* 250* 250* 250* 225* 150 3/8 250* 250* 250* 250* 250* 250* 250* 250* 250*
1/4 75 75 75 50 50 --- --- --- --- --- --- --- --­5/16 250* 250* 250* 250* 250* 225* 175 125 100 3/8 250* 250* 250* 250* 250* 250* 250* 250* 250* 1/4 30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --­5/16 175 225* 200 175 125 100 75 --- --- --- --­3/8 250* 250* 250* 250* 250* 250* 250* 250* 250*
5/16 175 150 150 100 100 100 75 --- --- --- ---
3//8 250* 250* 250* 250* 250* 250* 250* 250* 250*
5/16 125 100 100 75 75 50 --- --- --- --- --- ---
3/8 250* 250* 250* 250* 250* 250* 250* 250* 150
48000
AC with
Puron
3/8 3/8 250* 250* 250* 250* 250* 250* 230 160 --- ---
49000
AC with
Puron
3/8 3/8 250* 250* 250* 250* 250* 250* 230 160 --- ---
60000
AC with
Puron
3/8 3/8 250* 250* 250* 225* 190 150 110 --- --- --- ---
61000
AC with
Puron
3/8 3/8 250* 250* 250* 225* 190 150 110 --- --- --- ---
* Maximum actual length not to exceed 200 ft (61 m) { Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
--- --- = o u t s i d e a c c e p t a b l e r a n g e
Liquid
Size
18000
AC with
Puron
24000
AC with
Puron
30000
AC with
Puron
36000
AC with
Puron 42000
AC with
Puron
Liquid Line
Connection
3/8
3/8
3/8
3/8
3/8
Line
Diam.
w/ TXV
1/4 175 250* 250* 250* 250* 250* 250* 250*
5/16 250* 250* 250* 250* 250* 250* 250* 250*
3/8 250* 250* 250* 250* 250* 250* 250* 250* 1/4 100 125 175 200 225* 250* 250* 250*
5/16 250* 250* 250* 250* 250* 250* 250* 250*
3/8 250* 250* 250* 250* 250* 250* 250* 250* 1/4 30 --- --- --- --- --- --- --- --- --- --- --- --- --- --­5/16 250* 250* 250* 250* 250* 250* 250* 250* 3/8 250* 250* 250* 250* 250* 250* 250* 250*
5/16 225* 250* 250* 250* 250* 250* 250* 250*
3/8 250* 250* 250* 250* 250* 250* 250* 250*
5/16 175 200 250* 250* 250* 250* 250* 250*
3/8 250* 250* 250* 250* 250* 250* 250* 250*
48000
AC with
Puron
3/8 3/8 250* 250* 250* 250* 250* 250* 250* 250*
49000
AC with
Puron
3/8 3/8 250* 250* 250* 250* 250* 250* 250* 250*
60000
AC with
Puron
3/8 3/8 250* 250* 250* 250* 250* 250* 250* 250*
61000
AC with
Puron
3/8 3/8 250* 250* 250* 250* 250* 250* 250* 250*
* Maximum actual length not to exceed 200 ft (61 m) { Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
--- --- = o u t s i d e a c c e p t a b l e r a n g e
AC with Puron Refrigerant Maximum Total Equivalent Length{: Outdoor unit BELOW Indoor
0 --- 5
6 --- 1 0
(1.8--- 3.0)
11--- 20
(3.4--- 6.1)
Maximum Total Equivalent Length
Outdoor Unit ABOVE Indoor Unit
AC with Puron Refrigerant Maximum Total Equivalent Length{: Outdoor unit ABOVE Indoor
25
(7.6)
26--- 50
(7.9--- 15.2)
{
for Cooling Only Systems with Puronr Refrigerant:
Vertical Separation ft (m)
21--- 30
(6.4--- 9.1)
31--- 40
(9.4--- 12.2)
41--- 50
(12.5--- 15.2)
51--- 60
(15.5--- 18.3)
Vertical Separation ft (m)
51--- 75
(15.5--- 22.9)
76--- 100
(23.2--- 30.5)
101--- 125
(30.8--- 38.1)
126--- 150
(38.4--- 45.7)
61--- 70
(18.6--- 21.3)
151--- 175
(46.0--- 53.3)
71--- 80
(21.6--- 24.4)
176--- 200
(53.6--- 61.0)
116B
3
REFRIGERANT CHARGE ADJUSTMENTS
Liquid Line Size Puron Charge oz/ft
3/8
5/16 0.40
1/4 0.27
(Factory charge for lineset = 9 oz)
0.60
Units are factory charged for 15 ft (4.6 m) of 3/8” liquid line. The factory charge for 3/8” lineset 9 oz. When using other length or diameter liquid lines, charge adjustments are required per the chart above.
Charging
Formula:
[(Lineset oz/ft x total length) – (factory charge for lineset)] = charge adjustment Example 1: System has 15 ft of line set using existing 1/4“ liquid line. What charge adjustment is required?
Formula: (.27 oz/ft x 15ft) – (9 oz) = (-4.95) oz. Net result is to remove 4.95 oz of refrigerant from the system
Example 2: System has 45 ft of existing 5/16” liquid line. What is the charge adjustment?
Formula: (.40 oz/ft. x 45ft) – (9 oz.) = 9 oz. Net result is to add 9 oz of refrigerant to the system

LONG LINE APPLICATIONS

An application is considered Long Line, when the refrigerant level in the system requires the use of accessories to maintain acceptable
116B
refrigerant management for systems reliability. See Accessory Usage Guideline table for required accessories. Defining a system as long line depends on the liquid line diameter, actual length of the tubing, and vertical separation between the indoor and outdoor units.
For Air Conditioner systems, the chart below shows when an application is considered Long Line.
AC WITH PURONr REFRIGERANT LONG LINE DESCRIPTION ft (m)
Beyond these lengths, long line accessories are required
Liquid Line Size Units On Same Level Outdoor Below Indoor Outdoor Above Indoor
1/4
5/16 120 (36.6) 50 (15.2) 120 (36.6)
3/8 80 (24.4) 35 (10.7) 80 (24.4)
Note: SeeLongLineGuidelinefordetails
No accessories needed within al l owed lengths
No accessories needed within al l owed lengths
175 (53.3)

VAPOR LINE SIZING AND COOLING CAPACITY LOSS

Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line diameters shown in the chart below are acceptable for AC systems with Puron refrigerant:
Unit
Nominal
Size (Btuh)
18000 1Stage AC with
Puron
24000 1Stage AC with
Puron
30000 1Stage AC with
Puron
36000 1Stage AC with
Puron
42000 1Stage AC with
Puron
48000,
49000 1Stage AC with
Puron
60000,
61000 1Stage AC with
Puron
Applications in this area may be long line and may have height restrictions. See the Residential Piping and Long Line Guideline.
Maximum
Liquid Line
Diameters
(In. OD)
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Vapo r Line
Diameters
(In. OD)
1/2 1 2 3 5 6 7 8 9 11
5/8 0 1 1 1 2 2 2 3 3
3/4 0 0 0 0 1 1 1 1 1
5/8 0 1 2 2 3 3 4 5 5
3/4 0 0 1 1 1 1 1 2 2
7/8 0 0 0 0 0 1 1 1 1
5/8 1 2 3 3 4 5 6 7 8
3/4 0 0 1 1 1 2 2 2 3
7/8 0 0 0 0 1 1 1 1 1
5/8 1 2 4 5 6 8 9 10 12
3/4 0 1 1 2 2 3 3 4 4
7/8 0 0 0 1 1 1 1 2 2
3/4 0 1 2 2 3 4 4 5 6
7/8 0 0 1 1 1 2 2 2 3
11/8 0 0 0 0 0 0 0 0 0
3/4 0 1 2 3 4 5 5 6 7
7/8 0 0 1 1 2 2 2 3 3
11/8 0 0 0 0 0 0 0 1 1
3/4 1 2 4 5 6 7 9 10 11
7/8 0 1 2 2 3 4 4 5 5
11/8 0 0 0 1 1 1 1 1 1
26--- 50
(7.9--- 15.2)
51--- 80
(15.5--- 24.4)
81--- 100
(24.7--- 30.5)
Cooling Capacity Loss (%)
Total Equivalent Line Length ft. (m)
101--- 125
(30.8--- 38.1)
126--- 150
(38.4--- 45.7)
151--- 175
(46.0--- 53.3)
176--- 200
(53.6--- 61.0)
201--- 225
(61.3--- 68.6)
226--- 250
(68.9--- 76.2)
4

ACCESSORY THERMOSTATS

PAR T N UMBE R PROGRAM GAS ELECTRIC HEAT COOL
T 2 --- PA C 0 1 5 --- 2 D a y
T 2 --- N A C 0 1 NP
T2SNAC01 NP
THERMOSTAT ACCESSORIES
PAR T N UMBE R BRIEF DESCRIPTION THERMOSTATS USED WITH
TSTATXXCNV10
T X --- L B P 0 1 LargeDecorativeBackplate T 6 --- P x x , T 6 --- N x x , a n d T 2 --- P x x
T X --- M B P 0 1 Medium Decorative Backplate T 2 --- N x x a n d T 1 --- P x x
Thermostat Conversion Kit (4 to 5 wire) --- 10
pack
All Bryantr branded thermostats
1 1
1 1
1 1

ACCESSORIES

KIT NUMBER DESCRIPTION
KAAFT0101AAA FREEZE THERMOSTAT X X X X X X X X X
KAATD0101TDR TIME DELAY RELAY X X X X X X X X X
KSALA0301410 LOW AMBIENT PSW X X X X X X X X X
KSALA0601AAA{ MOTORMASTER 230V X X X X X X X X X
HC32GE234 MOTOR FAN BALL BEARING X
HC34GE240 MOTOR FAN BALL BEARING X X
HC32GE229 MOTOR FAN BALL BEARING X
HC38GE228 MOTOR FAN BALL BEARING X
HC40GE228 MOTOR FAN BALL BEARING X X X X
KSAHS1701AAA HARD START (CAP / RELAY) X X X X X X X X X
KSACY0101AAA CYCLE PROTECTOR X X X X X X X X X
KSASF0101AAA SUPPORT FEET X X X X X X X X X
KAACS0201PTC START ASSIST PTC X X X X X X X X X
KAALS0201LLS LIQUID LINE SOLENOID X X X X X X X X X
KAAWS0101AAA WINTER START X X X X X X X X X
KAACH1701AAA CRANKCASE HTR X X X X
KAACH1601AAA CRANKCASE HTR X S S S S
KSATX0201PUR TXV PURON HSO X X X
KSATX0301PUR TXV PURON HSO X
KSATX0401PUR TXV PURON HSO X X
KSATX0501PUR TXV PURON HSO X X X
KSASH0601COP SOUND HOOD X X X X X
KSASH2101COP SOUND HOOD X X X X
KAALP0401PUR LOW PRES SURE SWITCH X X X X X X X X X
KAAHI0501PUR HIGH PRESSURE SWITCH X X X X X X X X X
{ Required accessories include ball bearing fan motor, compressor start assist (CAP / Relay), crankcase heater, evaporator freeze stat, hard shut ---off TXV. X = Accessory / S --- Standard
018--- B 024--- A 030 --- A 036- -- A 042 --- A 048 ---B 049- -- A 060 --- A 061 ---A
Unit Sizes --- Series
116B
5

ACCESSORY USAGE GUIDELINE

REQUIRED FOR LOW---AMBI-
ACCESSORY
Ball Bearing Fan Motor Yes { No No
Compressor Start Assist Capacitor and Relay Yes Yes No
Crankcase Heater Yes Ye s No
Evaporator Freeze Thermostat Yes No No
H a r d S h u t --- O f f T X V Yes Yes Yes
Liquid Line Solenoid Valve No No No
Motor Master®Control or
L o w --- a m b i e n t P r e s s u r e S w i t c h
Support Feet Recommended No Recommended
* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split---System Longline
Application Guideline.
{ Required for Low --- Ambient Controller (full modulation feature) MotorMasterr Control.
Winter Start Control Yes No No
ENT COOLING APPLICATIONS
(Below 55°F/12.8_C)
Yes No No
Accessory Description and Usage (Listed Alphabetically)
1. Ball--Bearing Fan Motor
116B
A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.
Usage Guideline:
Required on all units when MotorMasterr is used.
2. Compressor Start Assist -- Capacitor and Relay
Start capacitor and relay gives a ”hard” boost to compressor motor at each start up.
Usage Guideline: Required for reciprocating compressors in the
following applications:
Long line Low ambient cooling Hard shut off expansion valve on indoor coil Liquid line solenoid on indoor coil
Required for single--phase scroll compressors in the following applications:
Long line Low ambient cooling
Suggested for all compressors in areas with a history of low voltage problems.
3. Compressor Start Assist — PTC Type
Solid state electrical device which gives a ”soft” boost to the compressor at each start--up.
Usage Guideline:
Suggested in installations with marginal power supply.
4. Crankcase Heater
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes the chance of liquid slugging.
Usage Guideline:
Required in low ambient cooling applications. Required in long line applications. Suggested in all commercial applications.
5. Cycle Protector
The cycle protector is designed to prevent compressor short cycling. This control provides an approximate 5--minute delay after power to the compressor has been interrupted for any reason, including power outage, protector control trip, thermostat jiggling, or normal cycling.
6. Evaporator Freeze Thermostat
An SPST temperature--actuated switch that stops unit operation when evaporator reaches freeze--up conditions.
7. Low--Ambient Pressure Switch Kit
A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure within normal operating limits (approximately 100 psig to 225 psig). The control will maintain working head pressure at low--ambient temperatures down to 0_F (--18_C) when properly installed.
Low--Ambient Controller must be used when cooling operation is used at outdoor temperatures below 55_F (12.8_C).
8. MotorMasterr Low--Ambient Controller
A fan--speed control device activated by a temperature sensor, designed to control condenser fan motor speed in response to the saturated, condensing temperature during operation in cooling mode only. For outdoor temperatures down to --20_F (--28.9_C), it maintains condensing temperature at 100_F ±10_F (37.8_C ±
5.5_C).
9. Outdoor Air Temperature Sensor
Designed for use with Bryant Thermostats listed in this publication. This device enables the thermostat to display the outdoor temperature. This device also
is required to enable special thermostat features such as auxiliary heat lock out.
REQUIRED FOR LONG
LINE
APPLICATIONS*
(Over 80 ft./24.38 m)
(Within2miles/3.22km)
Usage Guideline:
Required when low ambient kit has been added.
Usage Guideline:
A Low--Ambient Pressure Switch or MotorMasterr
Usage Guideline:
A MotorMasterr Low Ambient Controller or Low--Ambient Pressure Switch must be used when cooling operation is used at outdoor temperatures below 55_F (12.8_C).
Suggested for all commercial applications.
Usage Guideline:
Suggested for all Bryant thermostats listed in this publication.
REQUIRED FOR
SEA COAST
APPLICATIONS
6
Accessory Description and Usage (Listed Alphabetically) (Continued)
10. Sound Hood
Wraparound sound reducing cover for the compressor. Reduces the sound level by about 2 dBA.
Usage Guideline: Suggested when unit is installed closer than 15 ft (4.57 m) to
quiet areas, bedrooms, etc. Suggested when unit is installed between two houses less
than 10 ft (3.05 m) apart.
11. Support Feet
Four stick--on plastic feet that raise the unit 4 in. (101.6 mm) above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base, minimizing corrosion.
Usage Guideline: Suggested in the following applications: Coastal installations. Windy areas or where debris is normally circulating. Rooftop installations. For improved sound ratings.
12. Thermostatic Expansion Valve (TXV)
A modulating flow--control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator.
Kit includes valve, adapter tubes, and external equalizer tube. Hard shut off types are available.
NOTE: When using a hard shut off TXV with single phase reciprocating compressors, a Compressor Start Assist Capacitor and Relay is required.
Usage Guideline:
Required to achieve AHRI ratings in certain equipment
13. Time--Delay Relay
An SPST delay relay which briefly continues operation of indoor blower motor to provide additional cooling after the compressor cycles off.
NOTE: Most indoor unit controls include this feature. For those that do not, use the guideline below.
Usage Guideline:
For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to AHRI Unitary Directory.
14. Winter Start Control
This control is designed to alleviate nuisance opening of the low--pressure switch by bypassing it for the first 3 minutes of operation.
116B
combinations. Refer to combination ratings.
Hard shut off TXV or LLS required in air conditioner long line applications.
Required for use on all zoning systems.
7