Model 1 13A
Legacy--RNC Series Air Conditioner wit h Pu ronr
Produc t Data
the environmentally sound refrigerant
Bryant’s Air Conditioners with Puron r refrigerant provide a
collection o f features u nm atched b y an y oth er family of
equipment. The 113A has been designe d utilizing Bryant’s Puron
refrigerant. The environmentally sound refrigerant allows you to
make a responsible decision in the protection of the earth’s ozone
layer. Bryant’s air conditioning system with Puron refrigerant
meets the Energy Starr guidelines for energy efficiency.
A05233
INDUSTRY LEADING
FEATURES / BENEFITS
Efficiency
13 SEER/11 EER
S
S
Microtube Technologyt refrigeration system
S
Indoor air quality accessories available
Sound
Sound level as low as 76 dBA
S
Comfort
System supports Thermidistatt or standard thermostat
S
controls
Reliability
S
Puronr refrigerant -- environmentally sound, won’t
deplete the ozone layer and low lifetime servce cost.
S
Front--seating service valves
S
Scroll compressor
S
Internal pressure relief valve
S
Internal thermal overload
S
Filter drier
S
Balanced refrigeration system for maximum reliability
Durability
DuraGuardt protection package:
S
Solid, Durable sheet metal construction
S
Dense wire coil guard
S
Baked--on, complete coverage, powder paint
Applications
Long--line -- up to 250 feet total equivalent length, up
S
to 200 feet condenser above evaporator, or up to 80 ft.
evaporator above condenser (See Longline Guide for
more information.)
S
Low ambient (down to --20_F) with accessory kit
Warranty
5 year limited compressor warranty
S
S
5 year limited parts warranty
MODEL NUMBER NOMENCLATURE
12345678910111214
NNNAA/NNNNNA/NA/NNA
113ANA 036 0000
Prod-
uct
Famil y
TierSEERMajor Ser iesVoltageVariations
Cooling Capacity
OpenOpenOpenSeries
N=
113A
1=AC1=Legacy
RNC
3=13 SE ERA=Puron
the environmentally sound refrigerant
208---230 ---1
or
208/230---1
C
R
E
R
U
T
C
A
F
U
N
A
M
A
R
A=Standard
T
O
D
E
A
I
R
F
I
I
T
R
E
A
I
R
C
O
Y
R
A
T
I
N
U
E
T
Q
N
U
E
I
P
M
I
S
D
T
A
R
N
A
D
0=Not
Defined
A
S
C
O
M
P
L
N
D
Y
I
T
I
N
I
O
G
N
I
N
W
G
I
T
H
0
1
2
ISO 9001:2000
REGISTERED
As an Energy Star® Partn er , Carrier
Corporation has determined that this
product meets the ENERGY STAR®
guidelines for energy efficiency
0=Not
Defined
0=Not Defined
STANDARD FEATURES
Feature18243036424860
Puron RefrigerantXXXXXXX
13 SEERXXXXXXX
Scroll CompressorXXXXXXX
DenseWireCoilGuardXXXXXXX
FieldInstalledFilterDrierXXXXXXX
Front Seating Service ValvesXXXXXXX
Internal Pressure Relief ValveXXXXXXX
Internal Thermal OverloadXXXXXXX
Long Line capabilityXXXXXXX
Low Ambient capability with KitXXXXXXX
A=
Original
Series
2
PHYSICAL DATA
UNIT SIZE SERIES018 ---A024---A030---A036---A042 ---A048---A060 ---A
Operating Weight (lb)125125134152189210236
Shipping Weight (lb)146146155175218235270
Compressor TypeScroll
REFRIGERANTPuron® (R---410A)
ControlTXV (Puron® Hard Shutoff)
Charge (lb)4.254.354.755.256.28.358.75
COND FANPropeller Type, Direct Drive
Air DischargeVertical
Air Qty (CFM)1880220022002950317033654050
Motor HP1/121/101/101/41/51/41/5
Motor RPM110011001100110011001100825
COND COIL
Face Area (Sq ft)9.859.8511.4914.7717.2521.5625.15
* For tubing sets between 80 and 200 ft. horizontal or 20 ft. vertical differential, consult the Longline Guideline.
Note: See unit Installation Instruction for proper installati on.
113A
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
PURON 1--STAGE AIR CONDITIONER APPLICATIONS
LONG LINE APPLICATION: An application is considered
”Long line” when the total equivalent tubing length exceeds 80 ft
or when there is more than 20 Ft vertical separation between
indoor and outdoor units. These applications require additional
accessories and system modifications for reliable system
operation. The maximum allowable total equivalent length is
250Ft. The maximum vertical separation is 200 Ft when outdoor
Standard ApplicationLong Line Application Requires Accessories
25508080+100125150175200225250
Standard Length = 80 Ft or less total equivalvent length
Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines
Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See
Long Line Application Guidelines
unit is above indoor unit, and up to 80 Ft when the outdoor unit
is below the indoor unit. Refer to Accessory Usage Guideline
below for required accessories. See Long--Line Application
Guideline for required piping and system modifications. Also,
refer to the table below for the acceptable vapor tube diameters
based on the total length to minimize the cooling capacity loss.
Cooling Capacity Loss (%)
Total Equivalent Line Length (ft)
3
ACCESSORY THERMOSTATS
THERMOSTAT / SUBBASE PKG.DESCRIPTION
TSTATBBPRH01 ---BThermidistat Control --- Programmable / Non ---Programmable Thermostat with Humidity control
TSTATBBPAC01--- BT h e r m o s t a t --- A u t o C h a n g e o v e r, 7 --- D a y P r o g r a m m a b l e , _F/_C, 1 --- S t a g e H e a t , 1 --- S t a g e C o o l
TSTATBBNAC01 ---CT h e r m o stat --- A u t o C h a n g e o v e r, N o n --- P r o g r a m m a b l e , _F/_C , 1 --- S t a g e H e a t , 1 --- S t a g e C o o l
TSTATBBBAC01 --- BBuilder’s Thermostat --- Manual Changeover, Non---Programmable, _F/_C , 1 --- S t a g e H e a t , 1 --- S t a g e C o o l
TSTATBBSEN01 ---BOutdoor Air Temperature Sensor
TSTATXXBBP01Backplate for Builder’s Thermostat
TSTATXXNBP01Backplate for Non ---Programmable Thermostat
TSTATXXPBP01Backplate for Programmable Thermos tat
TSTATXXCNV10Thermostat Conversion Kit (4 to 5 wires) --- 10 Pack
Compressor Start Assist Capacitor and RelayYesYesNo
Motor Master®Control or Low --- ambient
Pressure Switch
YesNoNo
Support FeetRecommendedNoRecommended
Liquid Line Solenoid ValveNo
S e e L o n g --- L i n e A p -
plication Guideline
Ball Bearing Fan MotorYes{NoNo
* For tubing line sets between 80 and 200 ft. and/or 20 ft. vertical differntial, refer to Residential Split ---System Longline Application Guideline.
{ Required for Low---Ambient Controller (ful l modulation feature) and MotorMasterr Control only.
4
REQUIRED FOR
SEA COAST
APPLICATIONS
(Within 2 miles)
No
Accessory Description and Usage (Listed Alphabetically)
1. Ball-- Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction
while maintaining bearing lubrication.
Usage Guideline:
Required on all units when MotorMasterr —
2. Compressor Start Assist -- Capacitor and Relay
Start capacitor and relay gives a ”hard” boost to compressor
motor at each start up.
Usage Guideline:
Required for reciprocating compressors in the
following applications:
Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil
Required for single--phase scroll compressors in the
following applications:
Long line
Low ambient cooling
Suggested for all compressors in areas with a history of
low voltage problems.
3. Compressor Start Assist — PTC Type
Solid state electrical device which gives a ”soft” boost to the
compressor at each start--up.
Usage Guideline:
Suggested in installations with marginal power supply.
4. Crankcase Heater
An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles.
Improves compressor lubrication on restart and minimizes the
chance of liquid slugging.
Usage Guideline:
Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.
5. Cycle Protector
The cycle protector is designed to prevent compressor short
cycling. This control provides an approximate 5--minute delay
after power to the compressor has been interrupted for any
reason, including power outage, protector control trip, thermostat
jiggling, or normal cycling.
6. Evaporator Freeze Thermostat
An SPST temperature--actuated switch that stops unit operation
when evaporator reaches freeze--up conditions.
Usage Guideline:
Required when low ambient kit has been added.
7. Low--Ambient Pressure Switch Kit
A long life pressure switch which is mounted to outdoor unit
service valve. It is designed to cycle the outdoor fan motor in
order to maintain head pressure within normal operating limits
(approximately 100 psig to 225 psig). The control will maintain
working head pressure at low--ambient temperatures down to 0_F
when properly installed.
Usage Guideline:
A Low--Ambient Pressure Switch or MotorMasterr
Low--Ambient Controller must be used when cooling operation is
used at outdoor temperatures below 55_F (12.8_C).
8. MotorMasterr Low--Ambient Controller
A fan--speed control device activated by a temperature sensor,
designed to control condenser fan motor speed in response to the
saturated, condensing temperature during operation in cooling
mode only. For outdoor temperatures down to --20_F (--28.9_C),
it maintains condensing temperature at 100_F ±10_F (37.8_C ±
-- 1 2 _C).
Usage Guideline:
A MotorMasterrLow Ambient Controller or
Low--Ambient Pressure Switch must be used when
cooling operation is used at outdoor temperatures
below 55_F (12.8_C).
Suggested for all commercial applications.
9. Outdoor Air Temperature Sensor
Designed for use with Bryant Thermostats listed in this
publication. This device enables the thermostat to display the
outdoor temperature. This device also
is required to enable special thermostat features such as auxiliary
heat lock out.
Usage Guideline:
Suggested for all Bryant thermostats listed in this
publication.
10. Sound Hood
Wraparound sound reducing cover for the compressor. Reduces
the sound level by about 2 dBA.
Usage Guideline:
Suggested when unit is installed closer than 15 ft to
quiet areas, bedrooms, etc.
Suggested when unit is installed between two houses less
than 10 ft apart.
11. Support Feet
Four stick--on plastic feet that raise the unit 4 in. above the
mounting pad. This allows sand, dirt, and other debris to be
flushed from the unit base, minimizing corrosion.
Usage Guideline:
Suggested in the following applications:
Coastal installations.
Windy areas or where debris is normally circulating.
Rooftop installations.
For improved sound ratings.
12. Thermostatic Expansion Valve (TXV)
A modulating flow-- control valve which meters refrigerant liquid
flow rate into the evaporator in response to the superheat of the
refrigerant gas leaving the evaporator.
Kit includes valve, adapter tubes, and external equalizer tube.
Hard shut off types are available.
NOTE: When using a hard shut off TXV with single phase
reciprocating compressors, a Compressor Start Assist Capacitor
and Relay is required.
Usage Guideline:
Required to achieve ARI ratings in certain equipment
combinations. Refer to combination ratings.
Hard shut off TXV or LLS required in air conditioner
long line applications.
Required for use on all zoning systems.
13. Time--Delay Relay
An SPST delay relay which briefly continues operation of indoor
blower motor to provide additional cooling after the compressor
cycles off.
NOTE: Most indoor unit controls include this feature. For those
that do not, use the guideline below.
Usage Guideline:
For improved efficiency ratings for certain
combinations of indoor and outdoor units. Refer to
ARI Unitary Directory.
113A
5
Accessory Description and Usage (Listed Alphabetically) (Continued)
14. Winter Start Control
This control is designed to alleviate nuisance opening of the
low-- pressure switch by bypassing it for the first 3 minutes of
operation.
ELECTRICAL DATA
UNIT
SIZE
18
2458.313.50.7517.61414454325
3064.012.80.7516.81414474525
3677.014.11.419.01212666330
42112.017.91.123.51212535140
48109.019.91.426.21010767340
60134.026.41.234.288918650
* Permissible limits of the voltage ran ge at which the unit will operate satisfactorily
113A
{ If wire is applied at ambient greater than 30˚ C(86˚ F), consult table 310 --- 16 of the NEC (ANSI/NFPA 70). The ampacity of non --- metallic ---sheathed cable
(NM), trade name ROMEX, shall be that of 60˚ C (140˚ F) conditions, per the NEC (ANSI/NFPA 70) Article 336 ---26. If other than uncoated (no ---plated), 60
or 75˚ C (140 or 167˚ C) ins ulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, cons ult applicable tables
of the NEC (ANSI/NFPA 70).
}Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time---Delay fuse.
FLA --- Ful l L o ad A mps
LRA --- L o c ke d R o tor A mps
MCA --- Minimu m Circuit Amps
RLA ---RatedLoadAmps
NOTE: Control circuit is 24 ---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
V/PH
208/230/1253197
All motors/compressors contain internal overload protection.
OPER
VOLTS*
MAXMINLRARLAFLA60° C75° C60° C75° C
COMPRFAN
MCA
48.09.00.511.71414676415
MIN WIRE
SIZE{
MIN WIRE
SIZE{
MAX
LENGTH
(FT)}
MAX
LENGTH
(FT)}
A--WEIGHTED SOUND POWER (DBA)
UNIT
STANDARD
SIZE
187652.061.067.070.567.563.556.5
247656.564.067.569.567.065.060.5
307655.063.569.072.069.064.559.5
367658.564.068.069.566.062.555.0
427857.565.071.073.070.567.562.5
487859.567.072.573.070.067.062.5
607853.561.067.574.568.562.561.0
RATING
1252505001000200040008000
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
MAX
FUSE**
or CKT
BRK
AMPS
A--WEIGHTED SOUND POWER (DBA) WITH ACCESSORY SOUND HOOD
UNIT
SIZE
STANDARD
RATING
187450.061.564.566.564.061.054.5
247558.065.569.070.568.065.059.0
307656.564.069.571.569.064.558.0
367658.564.568.569.567.063.558.5
427757.565.070.572.070.067.062.0
487759.567.072.072.069.566.562.0
607753.061.066.573.066.060.557.5
1252505001000200040008000
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE --- VOLTAGE & SERIESREQUIRED SUBCOOLING (_F)
018---A8
024---A13
030---A16
036---A16
042---A10
048---A17
060---A11
6
113A
1. Allow 30” clearance to service side of unit, 48” above unit, 6” on one side, 12”
on remaining side, and 24” between units for proper airflow.
2. Minimum outdoor operating ambient in cooling mode is 55 _F, max. 125_ F.
3. Se ries designation is the 13th positio n of the unit model numbe r.
(Professional Engineer), if required.
4. Center of gravity
5. For hurricane tie downs, contact distributor for detai ls and PE Certificatio n
* Tested combination
{ In most cases, only 1 method should be used to achieve TDR function. Using more than 1 method in a system may cause degradation in performance. Use
either the accessory Time ---Delay Relay KAATD0101TDR or a furnace equipped with TDR. Most Bryant furnaces are equipped with TDR.
EER — Energy Efficiency Ratio
SEER — Seasonal Energy Efficiency Ratio
TDR — T i me --- D e la y R ela y
TXV — Thermostatic Expansion Valve
NOTES:
1. Ratings are net values reflecting the effects of circulating fan motor heat. Supplemental electric heat is not included.
2. Tested outdoor/indoor combinations have been tested in accordance with DOE test procedures for central air conditioners. Ratings for other
combinations are determined under DOE computer simulation procedures.
3. Determine actual CFM values obtainable for your system by referring to fan performance data in fan coil or furnace coil literature.
4. Do not apply with capillary tube coils as performance and reliability are significantly affected.
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240 --- 94. If additional tubing length and/or
indoor unit is located above outdoor unit, a slight variation in ca pacity may occur.
** Total system kW is total of indoor and outdoor unit kilowatts.
{ Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
} Sensible capacities shown are based on 80˚F(27˚C) entering air a t the indoor coil. For sensible capacities at other than 80˚F(27˚C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80˚F(27˚C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of in door coil air
per degree above 80˚F(27˚C).
When the required data fall between the published da ta, interpolation may be performed.
CSPH*6012A**0.980.97315(A,J)AV066155
CONDENSER ENTERING AIR TEMPERATURES deg F
To ta l
System
KW**
Capacity
MBtuh{
To ta l
Sys-
tem
KW**
Capacity
MBtuh{
To ta l
Sys-
tem
KW**
Capacity
MBtuh{
To ta l
Sys-
tem
KW**
Capacity
MBtuh{
To ta l
Sys-
tem
KW**
113A
21
GUIDE SPECIFICATIONS
GENERAL
System Description
Outdoor--mounted, air--cooled, split--system air conditioner
unit suitable for ground or rooftop installation. Unit consists
of a hermetic compressor, an air--cooled coil, propeller--type
condenser fan, and a control box. Unit will discharge supply
air upward as shown on contract drawings. Unit will be used
in a refrigeration circuit to match up to a packaged fan coil
or coil unit.
Quality Assurance
— Unit will be rated in accordance with the latest edition
of ARI Standard 210.
— Unit will be certified for capacity and efficiency, and
listed in the latest ARI directory.
— Unit construction will comply with latest edition of
ANSI/ ASHRAE and with NEC.
— Unit will be constructed in accordance with UL
standards and will carry the UL label of approval.
113A
Delivery, Storage, and Handling
Warranty (for inclusion by specifying engineer)
Unit will have c--UL approval.
— Unit cabinet will be capable of withstanding Federal
Tes t
Method Standard No. 141 (Method 6061) 500--hr salt
spray test.
— Air--cooled condenser coils will be leak tested at 150
psig and pressure tested at 450 psig.
— Unit constructed in ISO9001 approved facility.
— Unit will be shipped as single package only and is
Factory assembled, single piece, air--cooled air conditioner
unit. Contained within the unit enclosure is all factory wiring,
piping, controls, compressor, refrigerant charge Puronr
(R--410A), and special features required prior to field start--up.
Unit Cabine
t
— Unit cabinet will be constructed of galvanized steel,
bonderized, and coated with a powder coat paint.
AIR--COOLED, SPLIT--SYSTEM AIR CONDITIONER
1--1/2 TO 5 NOMINAL TONS
Fans
— Condenser fan will be direct--drive propeller type,
discharging air upward.
— Condenser fan motors will be totally enclosed,
1--phase type with class B insulation and permanently
lubricated bearings. Shafts will be corrosion resistant.
— Fan blades will be statically and dynamically
balanced.
— Condenser fan openings will be equipped with coated
steel wire safety guards.
Compresso
Condenser Coil
Refrigeration Component
Operating Characteristics
Electrical Requirements
Special Features
r
— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration
isolators.
— Condenser coil will be air cooled.
— Coilwillbeconstructedofaluminumfins
mechanically bonded to copper tubes which are then
cleaned, dehydrated, and sealed.
s
— Refrigerationcircuitcomponentswillinclude
liquid--line shutoff valve with sweat connections,
vapor--line shutoff valve with sweat connections,
system charge of Puronr (R--410A) refrigerant, and
compressor oil.
— Unit will be equipped with high--pressure switch, low
pressure switch and filter drier for Puron refrigerant.
— The capacity of the unit will meet or exceed _____
Btuh at a suction temperature of _____ _F. The power
consumption at full load will not exceed _____ kW.
— Combinationoftheunitandtheevaporatororfancoil
unit will have a total net cooling capacity of _____
Btuh or greater at conditions of _____ CFM entering
air temperature at the evaporator at _____ _Fwetbulb
and _____ _F dry bulb, and air entering the unit at
_____ _F.
— The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
— Nominal unit electrical characteristics will be _____ v,
single phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v
to _____ v.
— Unit electrical power will be single point connection.
— Control circuit will be 24v.
— Refer to section of this literature identifying
accessories and descriptions for specific features and
available enhancements.
113A
EBryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231Printed in U.S.A.Edition Date: 12/05
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
22
Catalog No. PDS 113A.18.1
Replaces: NEW
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.