Bryan Boilers RV-KD User Manual

NOTES:
1. ALL DIMENSIONS ARE IN INCHES. THOSE IN PARENTHESES ARE CENTIMETERS.
2. LOCATION DIMENSIONS ARE ALL ±1/2".
3. GAS TRAIN, CONTROL AND BURNER CONFIGURATION WILL VARY DEPENDING ON JOB SPECIFICATIONS & CONDITIONS.
4. DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. CONSULT FACTORY FOR CERTIFIED DIMENSIONS.
5. ALL FLANGES ARE 150# UNLESS OTHERWISE NOTED, FLANGES TO STRADDLE CENTER LINE.
RV-KD SERIES FORCED DRAFT
WATER BOILERS (RV450-RV800)
6 1/2"
(16.5)
21 3/8"
(54.2)
50"
(127.0)
8 3/4"
(22.2)
A
PLAN VIEW
EFFECTIVE DATE:
REPLACES:
D
H
25 5/8"
(65.0)
B
(121.92)
48"
BURNER
SERVICE AREA
C
MINIMUM TUBE
32"
(81.3)
REMOVAL CLEARANCE
3/22/04
8/11/03
8
16
13
17
REAR VIEW
1. PROBE TYPE L.W.C.O.-
2. FORCED DRAFT BURNER
3. RELIEF VALVE'S
4. BURNER CENTER LINE
5. CONTROL TAPPINGS 3/4" NPT
G
RETURN
15
89 3/4"
(227.9)
87 9/16"
(222.4)
14
8
6. JACKET ACCESS PANELS
7. PRESS./TEMP. GAUGE
8. CLNOUT./INSP. OPNG.-1 1/2"NPT
9. ELEC. ENCLOSURE-
10. VENT CONNECTION 1" NPT
12
3
6
LEFT SIDE VIEW
5
7
11. OIL PUMP LOCATION
12. LIFTING LUGS
13. DRAIN CONNECTION 2" NPT
14. HEIGHT OVER JACKET
15. HEIGHT OVER SUPPLY
SUPPLY
33 1/2"
(85.1)
G
10
2
4
8
16. FLAME OBSERVATION PORT
17. COMB. CHAMBER DRAIN 1" NPT
1
9
11
FRONT VIEW
BOILER MODEL
A-LENGTH OVER JACKET
B-FLUE LOCATION
C-FLUE DIAMETER
D-LENGTH OVER BASE
G-SUPPLY / RETURN NOZZLE SIZE
H-BURNER EXTENSION
BRYAN BOILERS
RV450
141 3/4"
(360.0)
18 3/4"
(47.6)
16"
(40.6)
164 7/16"
(417.6)
6" FLG
(15.2)
RV500
151 3/8"
(384.4)
18 3/4"
(47.6)
16"
(40.6)
174 1/8"
(442.2)
6" FLG
(15.2)
18 3/4"
(47.6)
(40.6)
187"
(474.9)
6" FLG
(15.2)
16"
18 3/4"
(47.6)
16"
(40.6)
196 5/8"
(499.4)
6" FLG
(15.2)
CONSULT FACTORY FOR BURNER EXTENSION APPLICATIONS
783 NORTH CHILI AVE
PERU, INDIANA 46970
RV700
(498.7)
20 3/4"
(52.7)
20"
(50.8)
225 7/8"
(573.7)
6" FLG
(15.2)
:
.
O
R
E
D
R
O
ORDER REV. NO.:
FORM NO.:
2167
RV800RV600RV550
218 7/8"173 7/8"164 1/4" 196 3/8"
(555.9)(441.6)(417.1)
20 3/4"
(52.7)
(50.8)
247 1/2"
(628.7)
6" FLG
(15.2)
20"
BRYAN BOILERS
BOILER MODEL RV450 RV500 RV550 RV600 RV700 RV800
INPUT MBH 4,500 5,000 5,500 6,000 7,000 8,000
OUTPUT* MBH 3,780 4,200 4,620 5,040 5,880 6,720
BOILER HORSEPOWER* HP 113 125 138 151 176 201
TUBE DIAMETER INCHES 1.50 1.50 1.50 1.50 1.50 1.50
NUMBER OF TUBES 61 67 75 81 95 109
PRESSURE VESSEL
RV SERIES FORCED DRAFT
Form # >> 2167
Date >> 9/5/2003
KNOCKDOWN WATER BOILERS
(KW) 1,318.5 1,465.0 1,611.5 1,758.0 2,051.0 2,344.0
(KW) 1,107.5 1,230.6 1,353.6 1,476.7 1,722.8 1,968.9
(KW) 1,106.6 1,229.6 1,352.5 1,475.5 1,721.4 1,967.3
(CM) 3.81 3.81 3.81 3.81 3.81 3.81
VOLUME GAL 181 200 216 236 278 309
(L) 685.1 757.0 817.6 893.3 1,052.2 1,169.6
HEATING SURFACE SQ FT 544 597 668 722 847 972
(SQ M) 50.6 55.5 62.1 67.1 78.7 90.3
OPERATING WEIGHT LBS 9,979 10,897 11,771 12,648 14,428 16,176
(KG) 4,526.5 4,943.1 5,339.2 5,736.9 6,544.4 7,337.5
SHIPPING WEIGHT LBS 8,470 9,230 9,970 10,680 12,110 13,600
(KG) 3,842.0 4,186.7 4,522.4 4,844.4 5,493.1 6,169.0
RELIEF VALVE TYPICAL - 30 PSIG (206.8 KPA)
QUANTITY (2) 740 (2) 740 (2) 740 (2) 740 (2) 740 (2) 740
SIZE INCHES 1½ x 2 2 x 2½ 2 x 2½ 2 x 2½ 2 x 2½ 2 x 2½
(CM) 3.81 x 5.08 5.08 x 6.35 5.08 x 6.35 5.08 x 6.35 5.08 x 6.35 5.08 x 6.35
CAPACITY-TOTAL MBH 5,800 10,500 10,500 10,500 10,500 10,500
(KW) 1,699.4 3,076.5 3,076.5 3,076.5 3,076.5 3,076.5
RELIEF VALVE TYPICAL - 125 PSIG (861.8 KPA)
QUANTITY (1) 174A (1) 174A (2) 174A (2) 174A (2) 174A (2) 174A
SIZE INCHES 1½ x 1½ 1½ x 1½ 1¼ x 1¼ 1¼ x 1¼ 1¼ x 1¼ 1¼ x 1¼
(CM) 3.81 x 3.80 3.81 x 3.81 3.17 x 3.17 3.17 x 3.17 3.17 x 3.17 3.17 x 3.17
CAPACITY-TOTAL MBH 6,460 6,460 10,740 10,740 10,740 10,740
(KW) 1,892.8 1,892.8 3,146.8 3,146.8 3,146.8 3,146.8
* Output and Boiler HP based on an average natural gas combustion effiiciency.
Loading...