Bryan Boilers RV400-S, RV350-W, RV350-S, RV400-W, RV450-W Brochure & Specs

...
Bryan “Flexible Water Tube”
RV Series
Steam & Water Boilers
Forced draft gas, oil or dual fuel fi red
Form No. 5310
(Rev. 5/07)
BRYAN
Steam Boiler
RV350-S150-FDG
Water Boiler
RV800-W-FDGO
®
BOILERS
Originators of the “Flexible Water Tube” design
Low initial cost, reliable operating effi ciency deliver substantial return on investment
True “fl exible water tube” design
guaranteed shock free
F
High quality steam
for heat or process
A
Full fi ve sq ft of heating
surface per BHP
Quality construction features:
A. Water side or steam side interior ac cessible for
clean out and inspection, front and rear open ings, upper and lower drums.
B. Large volume water leg down comers promote rapid internal circulation, temperature equalization and effi cient heat transfer.
C. Boiler tube and furnace area access panels: heavy gauge steel casing with 2" high-temperature ceramic fi ber insulation, bolted and tightly sealed to boiler frame.
D. Flame observation port in access door at rear of boiler.
E. Single side access; combustion chamber, tubes and burner
head are completely accessible from one side simplifying maintenance and minimizing fl oor space.
F. Minimum sized fl ue vent.
G. Control panel: all controls installed with connections
to terminal strip.
H. Forced draft, fl ame retention head type burner. Effi cient combustion of oil or gas, plus quiet operation.
I. Heavy steel boiler frame, built and stamped in accordance with the appropriate ASME Boiler Code.
J. Heavy gauge steel boiler jacket with rust-resistant zinc coating and enamel fi nish, insulated with 1½" fi berglass to ensure exceptionally cool outer surface.
J
C
K
B
D
L
I
K. Bryan bent water tubes are fl exible, individually re­placeable without welding or rolling. Never more than two tube confi gurations.
L. Pressurized design fi rebox with internal water-cooled furnace with low heat release rate.
M. Steam boilers with extra large drum with high steam release area ensure stable water level and dry steam.
M
G
H
E
Bryan RV Series Boiler Specifi cations
BOILER INPUT MODEL
RV350-W 3,500 (1,026) 2,800 (820) 84 (820) 2,940 (861) 88 (861) 419 (38.9) 7,000 (3,175)
RV350-S 3,500 (1,026) 2,800 (820) 84 (820) 2,887 (1,309) 419 (38.9) 7,110 (3,225)
RV400-W 4,000 (1,172) 3,200 (937) 96 (937) 3,360 (984) 100 (984) 490 (45.5) 7,690 (3,488)
RV400-S 4,000 (1,172) 3,200 (937) 96 (937) 3,299 (1,496) 490 (45.5) 8,170 (3,705)
RV450-W 4,500 (1,319) 3,600 (1,054) 108 (1,054) 3,780 (1,107) 113 (1,107) 544 (50.6) 8,320 (3,774)
RV450-S 4,500 (1,319) 3,600 (1,054) 108 (1,054) 3,711 (1,684) 544 (50.6) 8,540 (3,873)
RV500-W 5,000 (1,465) 4,000 (1,172) 120 (1,172) 4,200 (1,230) 125 (1,230) 597 (55.5) 9,080 (4,118)
RV500-S 5,000 (1,465) 4,000 (1,172) 120 (1,172) 4,124 (1,871) 597 (55.5) 9,650 (4,377)
RV550-W 5,500 (1,612) 4,400 (1,289) 131 (1,289) 4,620 (1,353) 138 (1,353) 668 (63.9) 9,820 (4,454)
RV550-S 5,500 (1,612) 4,400 (1,289) 131 (1,289) 4,536 (2,058) 668 (63.9) 10,175 (4,615)
RV600-W 6,000 (1,758) 4,800 (1,406) 143 (1,406) 5,040 (1,476) 151 (1,476) 722 (67.1) 10,530 (4,776)
RV600-S 6,000 (1,758) 4,800 (1,406) 143 (1,406) 4,948 (2,245) 722 (67.1) 11,335 (5,141)
RV700-W 7,000 (2,051) 5,600 (1,640) 167 (1,640) 5,880 (1,722) 176 (1,722) 847 (78.7) 11,960 (5,425)
RV700-S 7,000 (2,051) 5,600 (1,640) 167 (1,640) 5,773 (2,619) 847 (78.7) 12,900 (5,851)
RV800-W 8,000 (2,344) 6,400 (1,875) 191 (1,875) 6,720 (1,968) 201 (1,968) 972 (90.3) 13,450 (6,100)
RV800-S 8,000 (2,344) 6,400 (1,875) 191 (1,875) 6,598 (2,993) 972 (90.3) 14,455 (6,556)
NOTES: (1) W = Water / S = Steam (2) Output and horsepower based on boiler industry standard of 80% of input. (3) Output and horsepower based on an average natural gas combustion effi ciency of 84% for hot water boiler. Actual combustion effi ciencies for oil will be higher. (4) Lbs. steam per hour from and at 212°F.
(1)
MBH (KW) MBH (KW) HP (KW) MBH (KW) HP (KW) LBS/HR (KG/HR) SQ. FT. (M²) LBS. (KG)
OUTPUT @ 80% EFFICIENCY
(2)
OUTPUT @ 84% EFFICIENCY
STEAM OUTPUT
(3)
(4)
HTG. SURFACE APPROX. SHIP
Guaranteed effi ciency and easy maintenance assure low cost operation
All Bryan RV Series boilers offer these operating and performance features
Guaranteed effi ciency
The breakthrough in water tube boiler design that pro­duced the RV Series provides operating effi ciency so reliable, we guarantee it to be 84% for hot water boilers and 82% - 15 psi / 80% - 150 psi or better for steam boilers.
The Bryan Flexible Tube
Bryan’s exclusive “Flexible Tube” design
eliminates the possibility of damage
from so-called “thermal shock.” Tubes are easily removable and replaceable, without welding or rolling, eliminating long, expensive downtime should repairs ever be required.
Water cooled furnace
The configuration of the
Water Boiler
water tubes provides a water cooled combustion
chamber. A high percentage of the heating surface is exposed to direct radiant heat, increasing water velocities and heat transfer.
Large steam drum
The steam drum has generous water volume and steam release area. This design, along with effective drum internal functions, results in a stable water level and produces extremely dry steam at all load conditions.
Accessibility of furnace and tube area
Inner panel provides easy and complete access to furnace and boiler tube area, as well as to burner head. All panels are heavily insulated and sealed to boiler frame. All access is from only one side.
Compact design, minimum fl oor space
With our compact water tube design, the overall size of the unit is less than most other types of boilers, yet maintains a full fi ve square feet of heating surface area per HP.
Needing only 32" for tube removal, and on only one side of the boiler, the RV Series boiler occupies very little space in the boiler room. This can result in considerable savings in building costs. Pressurized fi ring permits minimum sized breaching and vent.
Multi-pass fl ue gas travel
High velocity four-pass fl ue gas travel is obtained by a unique baffl ing system. This contributes to maximum fi re side heat transfer and overall high boiler effi ciencies.
Thermal blend water return
Bryan’s unique “thermal blend” return blends cold or cooler return water with warmer boiler water abridging it to design operating temperatures. An injector tube directs the “mixed” water fl ow through the downcomer to the lower header and heating surfaces at a temperature above possible condensing conditions. This reduces the possi­bility of “cold spots” and damage from corrosive condensation.
Steam
Boiler
Positive internal circulation
Each pass of the Bryan water tube slopes up­ward. This confi guration, along with the large vol­ume down-comer water legs, provides the extremely rapid natural thermal inter­nal circulation, promoting both high effi ciency of heat transfer and uniform temperature throughout the boiler. Eliminating stress damage caused by unequal temperature distribution is especially important for heating systems, particularly where intermittent or continuous low temperature water returns may be encountered.
Bryan RV Series Boilers Standard and Optional Equipment
STANDARD EQUIPMENT FURNISHED
Water Boiler
Combination thermometer and altitude gauge, ASME Code rated boiler relief valve, water temperature control (240°F max std.), high limit control, pro be LWCO.
Steam Boiler
Steam pressure gauge, steam pres­sure control, combination low water cutoff and pump control, auxiliary low water cutoff, high limit pressure control, ASME-rated safety valve, water glass set.
Straight gas fi red unit
Electronic combustion safety control, automatic operating gas valve, safety gas valve, pilot solenoid valve, pilot ignition assembly, main manual gas shut-off valve, pilot cock, pilot and main gas pressure regulators, air safety
switch, control panel, all controls installed and wired.
Straight oil fi red unit
Electronic combustion safety control, dual oil valves oil ignition transformer, two-stage fuel unit, gas pilot, oil nozzle assembly, control panel, all controls installed and wired.
Combination gas-oil unit
Electronic combustion safety control, automatic operating gas valve, safety gas valve, pilot solenoid valve, pilot ignition assembly, main manual gas shut-off valve, pilot cock, pilot and main gas pressure regulators, air safety switch, manual fuel selector switch, dual oil valves, oil ignition transformer, two-stage fuel unit, oil ignition and nozzle assembly, control panel, all controls installed and wired.
OPTIONAL EQUIPMENT, EXTRA COST
1. Manual reset high limit control
2. Manual reset low water cutoff
3. Auxiliary low water cutoff
4. Combination low water cutoff and feeder
5. Alarm bells or horns
6. UL, CUL, CSD-1, FM, IRI or other insurance approved
control systems
7. Indicating lights, as desired
8. Lead-lag systems for two or more boilers with or without outdoor reset control
9. Draft control system
10. Low NOx package
OPTIONAL CONSTRUCTION
Steam boiler
Optional construction to ASME Power Boiler Code requirements for pressure exceeding 150 psi to maximum of 300 psi design pressure.
Hot water boiler
Optional construction to ASME Power Boiler Code requirements for tempera­tures exceeding 240° F and/or pressure exceeding 160 psi to maximum of 285° F operating and 300° F design temperature and 250 psi.
When ordering, please specify:
1. Boiler size
2. Supply and return tempera­tures required
3. Boiler relief valve setting
4. Type of fuel: natural, LP, or other gas and/or No. 2 oil
5. If gas, type, BTU content, specifi c gravity and pressure available
6. Electric power voltage, phase and frequency
7. Optional extra equipment or construction
8. Special approvals required (UL, CUL, CSD-1, FM, or IRI)
9. Altitude
Bryan RV Series Steam & Hot Water Boilers
STEAM HEATING/PROCESSING BOILER DIMENSIONS in inches (cm) A B C D E F G H I J K L Boiler Length Gas
Model of Number Jacket
(248.92) (40.64) (40.64) (331.47) (6.35) (15.24) (10.16) (5.08) (139.70) (81.28) (121.92) (254.64) (266.1)
(281.94) (47.63) (40.64) (364.49) (6.35) (20.32) (15.24) (5.08) (139.70) (81.28) (121.92) (254.64) (266.1)
(306.07) (47.63) (40.64) (389.26) (6.35) (20.32) (15.24) (5.08) (139.70) (81.28) (121.92) (254.64) (266.1)
(330.84) (47.63) (40.64) (414.02) (6.35) (20.32) (15.24) (5.08) (139.70) (81.28) (121.92) (254.64) (266.1)
(363.83) (47.63) (40.64) (446.41) (6.35) (25.40) (15.24) (5.08) (139.70) (81.28) (121.92) (254.64) (266.1)
(387.99) (47.63) (40.64) (470.54) (6.35) (25.40) (15.24) (5.08) (139.70) (81.28) (121.92) (254.64) (266.1)
(445.14) (52.71) (50.80) (544.83) (6.35) (25.40) (15.24) (5.08) (139.70) (81.28) (121.92) (254.64) (266.1)
(502.29) (52.71) (50.80) (602.62) (6.35) (25.40) (15.24) (5.08) (139.70) (81.28) (121.92) (254.64) (266.1)
98 16 16 130½ 2½ 6 4 2 55 32 48 100¼ 104¾
RV350-S
111 18¾ 16 143½ 2½ 8 6 2 55 32 48 100¼ 104¾
RV400-S
120½ 18¾ 16 153¼ 2½ 8 6 2 55 32 48 100¼ 104¾
RV450-S
130¼ 18¾ 16 163 8 6 2 55 32 48 100¼ 104¾
RV500-S
143¼ 18¾ 16 175¾ 2½ 10 6 2 55 32 48 100¼ 104¾
RV550-S
152¾ 18¾ 16 185¼ 2½ 10 6 2 55 32 48 100¼ 104¾
RV600-S
175¼ 20¾ 20 214½ 2½ 10 6 2 55 32 48 100¼ 104¾
RV700-S
197¾ 20¾ 20 237¼ 2½ 10 6 2 55 32 48 100¼ 104¾
RV800-S
Flue Flue Overall
Location Size Length
Train Connection 15 psi 150 psi
Supply
Return
Nozzle
Width Min. Tube Clearance for Height Floor to
Conn.
Outside Removal Servicing Over Flow
Jacket Clearance Burner Jacket Nozzle
HOT WATER HEATING BOILER DIMENSIONS in inches (cm) A B C D E F G H I J K L Boiler Length Gas Width Min. Tube Clearance for Height Floor to
Model of Number Jacket
(248.92) (40.64) (40.64) (331.47) (6.35) (10.16) (10.16) (127.00) (81.28) (121.92) (222.25) (228.60)
(281.94) (47.63) (40.64) (364.49) (6.35) (15.24) (15.24) (127.00) (81.28) (121.92) (222.25) (228.60)
(306.07) (47.63) (40.64) (389.25) (6.35) (15.24) (15.24) (127.00) (81.28) (121.92) (222.25) (228.60)
(330.84) (47.63) (40.64) (414.02) (6.35) (15.24) (15.24) (127.00) (81.28) (121.92) (222.25) (228.60)
(364.49) (47.63) (40.64) (446.41) (6.35) (15.24) (15.24) (127.00) (81.28) (121.92) (222.25) (228.60)
(387.99) (47.63) (40.64) (470.54) (6.35) (15.24) (15.24) (127.00) (81.28) (121.92) (222.25) (228.60)
(446.41) (52.71) (50.80) (554.83) (6.35) (15.24) (15.24) (127.00) (81.28) (121.92) (222.25) (228.60)
(502.29) (52.71) (50.80) (602.62) (6.35) (15.24) (15.24) (127.00) (81.28) (121.92) (222.25) (228.60)
98 16 16 130½ 4 4 50 32 48 87½ 90
RV350-W
111 18¾ 16 143½ 6 6 50 32 48 87½ 90
RV400-W
120½ 18¾ 16 153¾ 6 6 50 32 48 87½ 90
RV450-W
130¼ 18¾ 16 163 6 6 50 32 48 87½ 90
RV500-W
143½ 18¾ 16 175¾ 6 6 50 32 48 87½ 90
RV550-W
152¾ 18¾ 16 185¼ 6 6 50 32 48 87½ 90
RV600-W
175¾ 20¾ 20 214½ 6 6 50 32 48 87½ 90
RV700-W
197¾ 20¾ 20 237¼ 6 6 50 32 48 87½ 90
RV800-W
Flue Flue Overall
Location Size Length
Train Connection
Supply Return Nozzle Nozzle
Outside Removal Servicing Over Flow Jacket Clearance Burner Jacket Nozzle
Specifi cations subject to change without notice. Consult factory to consult on other boiler options.