Bryan Boilers RV350, RV400 User Manual

RV-KD SERIES FORCED DRAFT
WATER BOILERS (RV350-RV400) REVERSE CONSTRUCTION
D
H
25 5/8"
(65.0)
B
48" (121.9)
BURNER
SERVICE AREA
C
EFFECTIVE DATE:
REPLACES:
NOTES:
1. ALL DIMENSIONS ARE IN INCHES. THOSE IN PARENTHESES ARE CENTIMETERS.
2. LOCATION DIMENSIONS
A
6 1/2"
(16.5)
19 3/8"
(49.2)
50"
(127.0)
8 3/4"
(22.2)
ARE ALL ±1/2".
3. GAS TRAIN, CONTROL AND BURNER CONFIGURATION WILL VARY DEPENDING ON JOB SPECIFICATIONS & CONDITIONS.
4. DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. CONSULT FACTORY FOR CERTIFIED DIMENSIONS.
5. ALL FLANGES ARE 150# UNLESS OTHERWISE NOTED.
3/15/04
12/9/03
MINIMUM TUBE
REMOVAL CLEARANCE
1
9
FRONT VIEW
1. PROBE TYPE L.W.C.O.-
2. FORCED DRAFT BURNER
3. RELIEF VALVE'S
4. BURNER CENTER LINE
5. CONTROL TAPPINGS 3/4" NPT
32"
(81.3)
PLAN VIEW
3
G
10
SUPPLY
2
11
33 1/2"
(85.1)
8
6. JACKET ACCESS PANELS
7. PRESS./TEMP. GAUGE
8. CLNOUT./INSP. OPNG.-1 1/2"NPT
9. ELEC. ENCLOSURE-
10. VENT CONNECTION 1" NPT
4
RIGHT SIDE VIEW
5
7
11. OIL PUMP LOCATION
12. LIFTING LUGS
13. DRAIN CONNECTION 2" NPT
14. HEIGHT OVER JACKET
15. HEIGHT OVER SUPPLY
12
F
RETURN
15
89 3/4"
(227.9)
87 9/16"
(222.4)
14
6
8
16. FLAME OBSERVATION PORT
17. COMB. CHAMBER DRAIN 1" NPT
REAR VIEW
8
16
13
17
BOILER MODEL
A-LENGTH OVER JACKET
B-FLUE LOCATION
C-FLUE DIAMETER
D-LENGTH OVER BASE
G-SUPPLY / RETURN NOZZLE SIZE
H-BURNER EXTENSION
BRYAN BOILERS
RV350 RV400
119 1/8"
(302.5)
27 1/2"
(69.8)
16"
(40.6)
141 7/8"
(360.3)
4" FLG
(10.2) (15.2)
CONSULT FACTORY FOR BURNER EXTENSION APPLICATIONS
783 NORTH CHILI AVE
PERU, INDIANA 46970
:
.
O
N
R
E
D
R
O
ORDER REV. NO.:
FORM NO.:
1976
132"
(335.2)
30 1/8"
(76.5)
16"
(40.6)
156 1/8"
(396.5)
6" FLG
BRYAN BOILERS
RV SERIES FORCED DRAFT
KNOCKDOWN WATER BOILERS
REVERSE CONSTRUCTION
BOILER MODEL RV350 RV400
INPUT MBH 3,500 4,000
(KW) 1,025.5 1,172.0
OUTPUT* MBH 2,940 3,360
(KW) 861.4 984.5
BOILER HORSEPOWER* HP 88 100
(KW) 860.7 983.7
TUBE DIAMETER INCHES 1.50 1.50
(CM) 3.81 3.81
NUMBER OF TUBES 47 55
PRESSURE VESSEL
Form # >> 1976
Date >> 4/28/2004
VOLUME GAL 146 169
(L) 552.6 639.7
HEATING SURFACE SQ FT 419 490
(SQ M) 38.9 45.5
OPERATING WEIGHT LBS 8,367 9,249
(KG) 3,795.4 4,195.3
SHIPPING WEIGHT LBS 7,150 7,840
(KG) 3,243.2 3,556.2
RELIEF VALVE TYPICAL - 30 PSIG (206.8 KPA)
QUANTITY (1) 740 (1) 740
SIZE INCHES 2 x 2½ 2 x 2½
(CM) 5.08 x 6.35 5.08 x 6.35
CAPACITY-TOTAL MBH 5,250 5,250
(KW) 1,538.2 1,538.2
RELIEF VALVE TYPICAL - 125 PSIG (861.8 KPA)
QUANTITY (1) 174A (1) 174A
SIZE INCHES 1¼ x 1¼ 1¼ x 1¼
(CM) 3.17 x 3.17 3.17 x 3.17
CAPACITY-TOTAL MBH 5,370 5,370
(KW) 1,573.4 1,573.4
* Output and Boiler HP based on an average natural gas combustion effiiciency.