Bryan Boilers K-350-S150-GI, K500-W-GI User Manual

Bryan “Flexible Water Tube”
K Series
Steam & Water Boilers
Atmospheric gas fired
Form No. 4950
(1/03)
Water Boiler
K500-W-GI
Steam Boiler
K-350-S150-GI
Originators of the “Flexible Water Tube” design
High efficiency hot water and steam boilers for commercial and industrial applications
Bryan flexible water tube boilers are ideally suited for both hot water and steam space heating systems as well as either high or low pressure process steam. In a range of sizes from 3,500,000 to 6,500,000 BTUH input, Bryan K series flexible tube boilers are ideal for many commercial, institutional and industrial appli­cations. These include healthcare facilities; schools; apartments; churches; office buildings; correctional facilities; airports; sewage treatment plants; golf, tennis and fitness clubs. Hospitals, dairies, restau­rants, laundries, dry cleaners, food processing, tire recapping and metal plating are just a few of the many applications.
All Bryan boilers are built in accor­dance with the requirements of the ASME Boiler and Pressure Vessel Code.
Efficient “Flexible Water Tube” design
The Bryan bent water tube provides rapid internal circulation — for maximum heat transfer and operating efficiency.
Easily replaceable tubes
Tubes are easily removable and replaceable without welding or rolling. Requires little service space.
No “Thermal Shock”
The flexibility of the bent water tube design elimi­nates all possible damage from "Thermal Shock" and from stresses caused by poor or unequal inter­nal circulation. This is particularly important with forced hot water heating systems designed for higher temperatures and greater temperature drops.
Steam Boilers:
Steam release area
Large, full-size steam drum provides for dry steam and stable water level.
High or low pressure construction
Boiler is constructed as standard for 15 psi or 150 psi maximum working pressure. Also available for higher pressures to 300 psi.
Water Boilers:
High or low pressure construction
Boiler is constructed as standard for 160 psi maximum working pressure at 230°F operating temperature and 250°F design temperature. Also available for higher pressures to 250 psi, at 285°F operating temperature and 300°F design tempera­ture.
Natural internal circulation
The water tube design and the large
downcomer legs provide adequate inter­nal circulation without concern over exterior pump­ing conditions. Low pressure drop through boiler.
Compact — minimum floor space
Requires less floor space than most boilers, and tubes can be removed and replaced from one side, further minimizing space needs.
Shipped completely assembled and wired. Units can also be shipped "Knocked Down" for on-site assembly.
Bryan K Series Boiler Specifications
BOILER INPUT
MODEL MBH (KW)
K-350 3,500 (1,025.5) 2,800 (840.4) 84 2,886 424 (39.4) 5,800 (2,636) K-400 4,000 (1,172.0) 3,200 (937.6) 96 3,298 480 (44.6) 6,410 (2,912) K-450 4,500 (1,318.5) 3,600 (1,054.8) 108 3,710 540 (50.2) 7,020 (3,188) K-500 5,000 (1,465.0) 4,000 (1,172.0) 120 4,122 600 (55.7) 7,630 (3,466) K-550 5,500 (1,611.5) 4,400 (1,289.2) 131 4,535 661 (61.4) 8,420 (3,825) K-600 6,000 (1,758.0) 4,800 (1,406.4) 143 4,947 717 (66.6) 8,850 (4,020) K-650 6,500 (1,904.5) 5,200 (1,523.6) 155 5,359 777 (72.2) 9,460 (4,298)
NOTES: * Lbs. steam per hour from and at 212°F.
NOMINAL OUTPUT STEAM HEATING APPROX.
OUTPUT SURFACE SHIP WT.
MBH (KW) BHP LBS/HR* SQ. FT. (M²) LBS. (KG)
Design and construction features that assure reliable performance
A. Heavy steel boiler frame, built and stamped in accordance with the ASME boiler code.
Hot water boilers constructed as standard for operating pressures to 160 psi. Also available for higher operating pressures. Steam boilers constructed as standard for operating pressures of 15 psi or 150 psi. Also available for higher operat­ing pressures. Large steam release area for dry steam.
B. Water leg downcomers to insure rapid
G
internal circulation and temperature equalization.
B
C. Bryan flexible water tubes, easily re-
placeable, requiring no welding or
C
A
rolling. Tubes installed from one side.
D. Boiler tube access panel bolted tightly
D
and sealed to boiler frame. Con­structed of 2" insul-wool high tem­perature insulation in steel framework. Tubes installed from one side for easy
E
accessible service and inspection.
E. Boiler jacket, heavy gauge zinc coated,
with attractive enamel finish. Boiler jacket insulated with 1½" fiberglass to insure cool jacket.
F. Atmospheric gas burner controls — alloy steel
atmospheric burner. Quiet electric ignition and operation. No moving parts or complicated adjustments.
G. All controls, gauges, relief valve(s) are factory installed and wired and easily
accessible for servicing.
H. Control panel: all controls installed and connected to terminal strip.
H
F
Bryan K Series Boilers Standard and Optional Equipment
STANDARD EQUIPMENT FURNISHED
Water Boiler
Combination thermometer and altitude gauge, ASME Code rated boiler relief valve, water temperature control (240°F max std.), high limit control, probe LWCO.
Steam Boiler
Combination low water cutoff and pump control, auxiliary low water cutoff with manual reset, high limit pressure con­trol, ASME-rated safety valve, water glass set.
Atmospheric equipment
Electronic combustion safety control, automatic operating gas valve, safety gas valve, pilot solenoid valve, electric ignition assembly, main manual gas shut-off valve, pilot shut-off valve,
pilot and main gas pressure regulators, barometric draft controller, all controls installed and wired standard voltage 120/1/60.
OPTIONAL EQUIPMENT, EXTRA COST:
1. Manual reset high limit control
2. Manual reset low water cutoff
3. Auxiliary low water cutoff (water)
4. Combination low water cutoff and feeder
5. Alarm bells or horns
6. UL, CSD-1, FM, IRI or other insurance approved control systems
7. Low fire start, Hi-Lo or modulation fire control
8. Indicating lights, as desired
9. Lead-lag systems for two or more boilers with or without outdoor reset control
10. Heat exchanger coils for domestic water
OPTIONAL CONSTRUCTION:
Steam boiler
Optional construction to ASME Power Boiler Code requirements for pressure exceeding 150 psi to maxi­mum of 300 psi design pressure.
Hot water boiler
Optional construction to ASME Power Boiler Code requirements for temperatures exceeding 240° F and/or pressure exceeding 160 psi to maximum of 285° F operat­ing and 300° F design tempera­ture and 250 psi.
When ordering, please specify:
1. Boiler size
2. Supply and return temperatures required
3. Boiler relief valve setting
4. Type of fuel: natural or LP
5. If gas, type, BTU content, specific gravity and pressure available
6. Optional extra equipment or construction
7. Special approvals required (UL, CSD-1, FM, or IRI)
8. Altitude
Bryan K Series Steam & Hot Water Boilers
STEAM BOILER DIMENSIONS—inches (cm)
ABCD E* F GH I J KL
BOILER Length MODEL Over
K-350-S
K-400-S
K-450-S
K-500-S
K-550-S
K-600-S
K-650-S
Jacket Jacket Clearance Barometric Jacket Nozzle
1071/
4
(272.42) (137.48) (50.80) (313.06) (6.35) (15.24) (10.16) (5.08) (137.16) (81.28) (271.15) (212.71) (224.16)
117 59 24 133 2
(297.13) (149.86) (60.96) (337.82) (6.35) (20.32) (15.24) (5.08) (137.16) (81.28) (281.31) (212.71) (224.16)
1293/
4
(329.57) (166.05) (60.96) (370.21) (5.08) (20.34) (15.24) (5.08) (137.16) (81.28) (281.31) (212.71) (224.16)
1421/
2
(361.95) (182.25) (60.96) (402.59) (5.08) (20.32) (15.24) (5.08) (137.16) (81.28) (281.31) (212.71) (224.16)
1551/
2
(394.97) (198.76) (60.96) (435.61) (6.35) (25.40) (15.24) (5.08) (137.16) (81.28) (281.31) (212.71) (224.16)
165 83 24 181 21/2 NPT 10 FLG 6 FLG 2 NPT 54 32 1103/
(419.10) (210.82) (60.96) (459.74) (6.35) (25.40) (15.24) (5.08) (137.16) (81.28) (281.31) (212.71) (224.16)
178 891/
(452.12) (277.33) (60.96) (492.76) (6.35) (25.40) (15.24) (5.08) (137.16) (81.28) (281.31) (212.71) (224.16)
Flue Flue Ov erall Gas Train
Location Size Length Connection
541/
8
20 1231/421/2 NPT 6FLG 4 FLG 2 NPT 54 32 1063/
1
/2 NPT 8 FLG 6 FLG 2 NPT 54 32 1103/
653/
8
713/
781/
24 1453/
4
24 1581/
4
24 1711/221/2 NPT 10 FLG 6 FLG 2 NPT 54 32 1103/
2
24 194 21/2 NPT 10 FLG 6 FLG 2 NPT 54 32 1103/
4
2 NPT 8 FLG 6 FLG 2 NPT 54 32 1103/
2
2 NPT 8 FLG 6 FLG 2 NPT 54 32 1103/
Supply Nozzle
15# 150#
Connect.
Wid t h Min. Tube Height He ig ht Floor to
Feed
Outside Removal Over Over Flow
4
833/
4
881/
4
4
833/
4
881/
4
4
833/
4
881/
4
4
833/
4
881/
4
4
833/
4
881/
4
4
833/
4
881/
4
4
833/
4
881/
4
WATER BOILER DIMENSIONS—inches (cm)
ABCDE*FGH I J KL
BOILER Length MODEL Over
K-350-W
K-400-W
K-450-W
K-500-W
K-550-W
K-600-W
K-650-W
NOTE: * Gas train and control location dimensinos will vary depending on job specifications and conditions.
Dimensions and specifications are subject to change without notice. Consult factory for certified dimensions.
Jacket Jacket Clearance Barometric Jacket Nozzle
1071/
(272.42) (137.48) (60.96) (313.06) (6.35) (10.16) (10.16) (122.56) (81.28) (247.65) (179.07) (186.89)
117 59 24 133 21/2 NPT 6 FLG 6 FLG 481/
(297.13) (149.86) (60.96) (337.82) (6.35) (15.24) (15.24) (122.56) (81.28) (247.65) (179.07) (186.89)
1293/
(329.57) (166.05) (66.04) (370.21) (5.08) (15.24) (15.24) (122.56) (81.28) (252.73) (179.07) (186.89)
1421/
(361.95) (182.25) (71.12) (402.59) (5.08) (15.24) (15.24) (122.56) (81.28) (257.81) (179.07) (186.89)
1551/
(394.97) (198.76) (76.20) (435.61) (6.35) (15.24) (15.24) (122.56) (81.28) (262.89) (179.07) (186.89)
165 83 30 181 21/2 NPT 6 FLG 6 FLG 481/
(419.10) (210.82) (76.20) (459.74) (6.35) (15.24) (15.24) (122.56) (81.28) (262.89) (179.07) (186.89)
178 891/
(452.12) (277.33) (76.20) (492.76) (6.35) (15.24) (15.24) (122.56) (81.28) (262.89) (179.07) (186.89)
Flue Flue Overall Gas Train Supply Return
Location Size Length Connection Nozzle Nozzle
4
541/
8
4
653/
8
2
713/
4
2
781/
4
2
24 1231/421/2 NPT 4 FLG 4 FLG 481/
26 1453/
28 1581/
4
2 NPT 6 FLG 6 FLG 481/
2
2 NPT 6 FLG 6 FLG 481/
30 1711/221/2 NPT 6 FLG 6 FLG 481/
30 194 21/2 NPT 6 FLG 6 FLG 481/
Bryan Steam LLC Leaders Since 1916
783 N. Chili Ave., Peru, Indiana 46970 U.S.A. Phone:765-473-6651 • Internet: www.bryanboilers.com
Fax: 765-473-3074
E-mail: bryanboilers@iquest.net
W i d t h Min. Tube He igh t He igh t Floor to
Outside Removal Over Over Flow
4
4
4
4
4
4
4
32 971/
32 971/
32 991/
32 1011/
32 1031/
32 1031/
32 1031/
2
2
2
2
2
2
2
701/
701/
701/
701/
701/
701/
701/
2
731/
2
731/
2
731/
2
731/
2
731/
2
731/
2
731/
2
2
2
2
2
2
2
Form No. 4950 ©2002 Bryan Steam LLC Printed in USA
13-4428