Bryan Boilers BE-60, BE-75, BE-90, BE-105, BE-120 Specification

...
Bryan Electric
BE Series
Steam & Water Boilers
98,000 to 1,277,000 BTUH
30 to 390 KW
Form No. 3600
(Rev. 05/03)
Steam Boiler
BE-90-Q4T3
Water Boiler
Bryan electric hot water or steam boilers...
For commercial, institutional and industrial applications
Electric Element Bundle
Each element replaceable with hand tools. Incoloy sheathed, 75 watts/sq in
150 lb ANSI flange
Spacing disc for support and proper circulation around individual elements
Removable threaded fittings for ease of individual element replacement
Bryan Series BE electric hot water** or steam boilers are compact, completely packaged and wired units with automatic controls featuring long life Incoloy sheathed elements. Applications include hot water heating, steam heating, process heating, and supplemental heat for heat pump type equipment.
Efficiency
Bryan Electric Boilers are nearly 95% efficient at all load levels. Varying loads do not effect the efficiency since the resistive type heating elements are immersed and de­signed to heat the water directly. With a modulating step control only the elements that are required to heat the water to the desired temperature/pressure will be ener­gized in order to encourage a balanced load during operation.
Replaceable Hairpins
Each element hairpin is field replaceable with no welding, soldering, or brazing required. Each hairpin, as standard for all Bryan Electric Boilers, is Incoloy sheathed and industrial size 0.430 diameter. Elements are designed for 75 watts/sq. inch for long life (optional 50 W/D available). Elements are individually installed in a standard ANSI 150 lb. blind flange.
Steam Disengaging Area
Steam release area is near the middle of the horizontal vessel for maximum steam disengaging area for dry steam and stable water level.
Water Boiler Design
All Bryan Boilers are built in accordance with the requirements of the ASME boiler and pressure vessel code and are UL listed. Water boilers are 150 psig MAWP and steam boilers either 15 psig or 150 psig. Higher pressures are available.
Vessel is designed for proper circulation around individual elements to maximize heat transfer. High velocities, i.e. heat pump applications, are handled with very little pressure drop when using a horizontal tank for the pressure vessel. Supply and return nozzle sizes can be made larger to accommodate the flow requirements.
Bryan BE Series Boiler Specifications
Model
BE-30 30 98 3 104 (47) 84 73 47 37 31 800 (365) BE-45 45 147 4.5 155 (70) 126 109 69 55 46 825 (375) BE-60 60 196 6 207 (93) 168 146 92 73 61 850 (390) BE-75 75 245 7.5 259 (117) 209 182 115 91 76 875 (400) BE-90 90 294 9 311 (141) 251 218 138 109 91 1000 (455) BE-105 105 343 10.5 362 (164) 293 254 161 127 107 1050 (480) BE-120 120 393 12 414 (187) 334 290 184 146 122 1100 (500) BE-135 135 441 13.5 466 (211) 376 326 206 164 137 1300 (590) BE-150 150 491 15 518 (234) 418 362 229 182 152 1325 (600) BE-165 165 539 16.5 569 (258) 460 398 252 200 167 1350 (615) BE-180 180 589 18 621 (281) 501 435 275 218 182 1400 (635) BE-195 195 637 19.5 673 (305) 543 471 298 236 197 1450 (660) BE-210 210 687 `21 725 (328) 585 507 320 254 212 1950 (885) BE-240 240 786 24 828 (375) 668 579 366 290 242 2000 (910) BE-270 270 884 27 932 (422) 751 651 412 326 272 2450 (1115) BE-300 300 982 30 1035 (469) 835 724 457 362 303 2500 (1135) BE-330 330 1081 33 1139 (516) 918 796 503 398 333 2550 (1160) BE-360 360 1179 36 1242 (563) 1001 868 549 435 363 2600 (1180) BE-390 390 1277 39 1346 (610) 1085 940 594 471 393 2650 (1205)
NOTES: * Lbs. steam per hour from and at 212°F. ** Not intended for use as a principal heating source for living space of any individual residence.
Input Nominal Output Steam Output* Approximate Total Load Amps
KW MBH BHP lbs/hr (kg/hr) 208V 240V 380V 480V 575V
Shipping
Wt. lbs (kg)
Water boiler trim and controls
Steam boiler trim and controls
Probe type low water cutoff control
ASME relief valve
Drain
(2) High limit controls
Pressure and temperature gauges
Operating control
Control circuit transformer
Modulating step controller (units over 60 KW)
Control circuit on-off switch
Standard Equipment Supplied:
HOT WATER DESIGN BOILERS:
Model “W” (150# ASME Design)
Thermometer and pressure gauge, Operating immer­sion aquastat, 2 high limit aquastats, Low water cutoff, Relief valve, Metal jacket with 2 fiberglass, 75 W/D Incoloy sheathed elements with pressure connector power lugs. Control panel with Key lock, On/Off control switch, 120 volt control transformer (fused), Magnetic contactors with 120 volt coil, Individual circuit fusing, Step indicating lamps, First on/first off progressive step controller (3 thru 40 steps), National Board Inspection and UL Label.
Model “WT”
Includes items in Model “W” design, plus Indirect heat exchanger — Max. discharge, Heat exchanger relief valve, Expansion tank, Boiler fill and drain valves and Boiler drain cock. (See Form 4800)
Optional Equipment Available:
Power panel door electric interlock. Preheat
switch. Flow switch. Manual reset controls.
Manual blowdown valve. Automatic
blowdown with 24 hour time clock. Alarms.
Indicating lights. Larger connection for heat
pump applications.
Other Designs Available:
1) BH – Our upgrade to the BE Series (Form 3200)
2) WT – Indirect Hot Water Supply Heaters (Form 4800)
3) Energy Selector Boiler – Electric plus gas, oil or gas/oil. A boiler with multiple energy source choice (Form 3500)
ASME relief valve
Pressure gauge
Water level gauge glass
Low water cutoff and
Control circuit fuse
pump control
(2) High limit controls Blowdown
Standard Equipment Supplied:
STEAM DESIGN BOILERS:
Model “S” (15# ASME Design) Model “Q” (150# ASME Design)
Steam pressure gauge w/gauge clock, Operating pressure control, 2 high limit pressure controls, Combination low water cutoff and pump control, Auxiliary low water cutoff, Relief valve, Water glass set, Metal jacket with 2 fiberglass, 75 W/D Incoloy sheathed elements with pressure connector power lugs. Control panel with: Key lock, On/off control switch, 120 volt control transformer, Magnetic contactors with 120 volt coil, Individual circuit fusing, Step indicating lamps, First on/ first off progressive step controller (3 thru 40 steps), National Board Inspection and UL Label.
Standard Design Features
Louvered panel cover for proper cooling air circulation
Each branch circuit is fused individually
Elevated legs integral with structural frame and extended rails for positive support of both pressure vessel and heavy duty power panel cabinet.
Modulating step controller (units over 60 KW)
Single point connection entrance
Operating control
Heavy duty, 11 gauge power panel cabinet
Control circuit fuse
Control circuit on-off switch
Control circuit transformer
16 gauge jacketing all around structural frame; zinc coated, rust resistant primer, enamel finished
Hinged door for access to vessel, ASME and elements
Bryan BE Series Steam & Hot Water Boilers
PLAN VIEW
LEFT END VIEW FRONT VIEW
MODELS "W" WATER / "S" 15# STEAM Dimensions in (cm) MODEL "Q" 150# STEAM Dimensions in (cm)
KW
30
45
60
90
105
120
135
150
165
180
195
210
240
270
300
330
360
390
Specifications subject to change without notice. Consult factory to consult on other boiler options.
Boiler Dimensions Power Panel Dimensions
length width height 208-230/3/60 380,460-575
ABCDEDEFGABCDEDEFG H
48 20 32 30 36 20 24 2 2 43 20 32 30 36 20 24 1 2 30
(122) (51) (81) (76) (91) (51) (61) (5) (5) (109) (51) (81) (76) (91) (51) (61) (3) (5) (77)
48 20 32 30 36 20 24 2 2 43 20 32 30 36 20 24 1 2 30
(122) (51) (81) (76) (91) (51) (61) (5) (5) (109) (51) (81) (76) (91) (51) (61) (3) (5) (77)
48 20 32 30 36 20 24 2 2 43 20 32 30 36 20 24 1 2 30
(122) (51) (81) (76) (91) (51) (61) (5) (5) (109) (51) (81) (76) (91) (51) (61) (3) (5) (77)
48 25 40 30 36 20 30 3 3 43 28 40 30 36 20 30 1 3 30
(122) (71) (102) (76) (91) (51) (73) (8) (8) (109) (71) (102) (76) (91) (51) (76) (3) (8) (77)
48 28 40 30 48 20 30 3 3 43 28 40 30 48 20 30 1 3 30
(122) (71) (102) (76) (122) (51) (76) (8) (8) (109) (71) (102) (76) (122) (51) (76) (3) (8) (77)
48 28 40 30 48 20 30 3 3 43 28 40 30 48 20 30 1 3 30
(122) (71) (102) (76) (122) (76) (91) (8) (8) (109) (71) (102) (76) (122) (76) (91) (3) (8) (77)
48 28 40 30 66 30 36 3 3 43 28 40 30 66 30 36 1 3 30
(122) (71) (102) (76) (168) (76) (91) (8) (8) (109) (71) (102) (76) (168) (76) (91) (3) (8) (77)
48 28 40 30 66 30 36 3 3 43 28 40 30 66 30 36 1 3 30
(122) (71) (102) (76) (168) (76) (91) (8) (8) (109) (71) (102) (76) (168) (76) (91) (3) (8) (77)
48 28 40 30 66 30 36 3 3 43 28 40 30 66 30 36 1 3 30
(122) (71) (102) (76) (168) (76) (91) (8) (8) (109) (71) (102) (76) (168) (76) (91) (3) (8) (77)
48 28 40 30 66 30 36 3 3 43 28 40 30 66 30 36 1 3 30
(122) (71) (102) (76) (168) (76) (91) (8) (8) (109) (71) (102) (76) (168) (76) (91) (3) (8) (77)
48 28 40 30 66 30 48 3 3 43 28 40 30 66 30 48 1 3 30
(122) (71) (102) (76) (168) (76) (122) (8) (8) (109) (71) (102) (76) (168) (76) (122) (3) (8) (77)
76 28 40
(193) (71) (102) (76) (122) (8) (8) (193) (71) (102) (76) (122) (3) (8) (140)
76 28 40
(193) (71) (102) (76) (122) (8) (8) (193) (71) (102) (76) (122) (3) (8) (140)
76 28 40
(193) (71) (102) (76) (168) (8) (8) (193) (71) (102) (76) (168) (3) (8) (140)
76 28 40
(193) (71) (102) (76) (168) (8) (8) (193) (71) (102) (76) (168) (3) (8) (140)
76 28 40
(193) (71) (102) (76) (168) (8) (8) (193) (71) (102) (76) (168) (3) (8) (140)
76 28 40
(193) (71) (102) (76) (168) (8) (8) (193) (71) (102) (76) (168) (3) (8) (140)
76 28 40
(193) (71) (102) (76) (168) (8) (8) (193) (71) (102) (76) (168) (3) (8) (140)
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
30 48 3 3 76 28 40
30 48 3 3 76 28 40
30 66 3 3 76 28 40
30 66 3 3 76 28 40
30 66 3 3 76 28 40
30 66 3 3 76 28 40
30 66 3 3 76 28 40
Inlet Outlet
length width height 208-230/3/60 380,460-575
RIGHT END VIEW
Boiler Dimensions Power Panel Dimensions
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
30 48 1 3 55
30 48 1 3 55
30 66 1 3 55
30 66 1 3 55
30 66 1 3 55
30 66 1 3 55
30 66 1 3 55
Inlet Outlet
Element Removal
Clearance
Bryan Steam LLC Since 1916
783 N. Chili Ave., Peru, Indiana 46970 U.S.A. Phone: 765-473-6651 • Internet: www.bryanboilers.com
Fax: 765-473-3074
Form No. 3600-6 ©2003 Bryan Steam LLC Printed in USA
E-mail: bryanboilers@iquest.net
53-5082