HUMIDITY SENSING RECESSED
FLUORESCENT FAN / LIGHT
READ AND SAVE THESE INSTRUCTIONS
MODEL 744SFL
Page 1
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC
SHOCK, OR INJURY TO PERSONS, OBSERVE
THE FOLLOWING:
1. Use this unit only in the manner intended by the
manufacturer. If you have questions, contact the
manufacturer at the address or telephone number
listed in the warranty.
2. Before servicing or cleaning unit, switch
power off at service panel and lock the service
disconnecting means to prevent power from
being switched on accidentally. When the service
disconnecting means cannot be locked, securely
fasten a prominent warning device, such as a tag,
to the service panel.
3. Installation work and electrical wiring must be
done by a qualified person(s) in accordance with
all applicable codes and standards, including
fire-rated construction codes and standards.
4. Sufficient air is needed for proper combustion
and exhausting of gases through the flue
(chimney) of fuel burning equipment to prevent
backdrafting. Follow the heating equipment
manufacturer’s guideline and safety standards
such as those published by the National Fire
Protection Association (NFPA), and the American
Society for Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE), and the local
code authorities.
5. When cutting or drilling into wall or ceiling,
do not damage electrical wiring and other
hidden utilities.
6. Ducted fans must always be vented to
the outdoors.
7. Never place a switch where it can be reached
from a tub or shower.
8. Do not use a dimmer switch to operate the light
in this unit.
9. Install this unit in a flat ceiling only.
10. For use in non fire rated installations only.
11. Not for use in environmental air handling spaces.
12. If this unit is to be installed over a tub or shower, it
must be marked as appropriate for the application
and be connected to a GFCI (Ground Fault Circuit
Interrupter) - protected branch circuit.
13. Do not install in a ceiling thermally insulated to a
value greater than R40.
14. This unit must be grounded.
CAUTION
1. For general ventilating use only. Do not use
to exhaust hazardous or explosive materials
and vapors.
2. To avoid motor bearing damage and noisy and/
or unbalanced impellers, use the cardboard
protector (provided) to keep drywall spray,
construction dust, etc. off power unit.
3. The fluorescent bulb used with this product
inserts straight into the bulb socket. Do not
attempt to insert or remove bulb by twisting it.
4. Please read specification label on product for
further information and requirements.
!
OPERATION
The light, fan and humidity control can be operated
together or independently using multi-function switch
wall controls.
• Use a 3-function control to independently operate
light, fan and humidity control.
• Use a 2-function control to independently operate
light and humidity control. For fan operation see
MANUAL ON WITH TIMED OFF section below.
• Use a 2-function control to independently operate
light and fan. Wire humidity control direct to insure
humidity control is always on.
See “Connect Wiring” section for various wiring options.
Do not use a dimmer switch control to operate
light, fan or humidity control.
SENSOR OPERATION
This humidity-sensing
moderate humidity increases and (b) humidity above
a 50%-100% relative humidity set-point. (a) and (b)
are set with “SENSITIVITY” adjustment. Fan may
occasionally turn on when environmental conditions
change. If the fan continuously responds to changing
environmental conditions, “SENSITIVITY” adjustment
may be required (see section below).
STATUS INDICATOR
This indicator can only be seen by looking directly at it.
Normal mode is 5-seconds on and off. If it blinks rapidly
for 5-seconds and then off, check sensor connections
on trim ring/baffle and fan housing.
MANUAL ON WITH TIMED OFF
For odor or vapor control, the fan can be energized
by cycling its wall-mounted switch if one is installed.
Once the fan has been turned on in this manner, it will
remain on for the set “TIMER” period.
To manually energize the fan:
1. Go to Step 2 if switch is already on; otherwise,
turn switch on for more than 1 second.
2. Switch off for less than 1 second.
3. Switch back on and fan will turn on.
SENSITIVITY ADJUSTMENT
“SENSITIVITY” has been factory set for most
shower applications. If the fan is in a tub area or is
used for dampness control, the “SENSITIVITY” may
need to be increased toward maximum (“MAX.”).
If the control is responding too often to changing
environmental conditions, adjustment toward less
(“MIN.”) “SENSITIVITY” may be required. To adjust
the “SENSITIVITY”:
1. Turn power off at electrical service panel.
2. Remove bulb.
3. Through trim ring/baffle, locate the “SENSITIVITY”
screwdriver slot.
4. Using a small, flat-blade screwdriver, carefully
rotate “SENSITIVITY” adjustment clockwise
toward “MAX.” or counterclockwise toward “MIN.”
5. Re-install bulb.
6. Turn power on and check operation by turning
on shower or other humidity source until fan
turns on.
7. Repeat above steps if necessary.
fan responds to: (a) rapid to
TIMER ADJUSTMENT
This humidity-sensing fan has a “TIMER”. It is useradjustable from 5 to 60 minutes and is factory-set
at 20 minutes. The “TIMER” controls how long the
fan remains on (a) after rise in humidity and (b)
humidity level are both below the user-adjustable
“SENSITIVITY” setting or after being energized by
cycling power switch.
To adjust the “TIMER”:
1. Disconnect power at electrical service panel.
2. Remove bulb.
3. Through the trim ring/baffle, locate the
“TIMER” screwdriver slot.
4. Using a small, flat-blade screwdriver, carefully
rotate “TIMER” adjustment clockwise
to increase time or counterclockwise to
decrease time.
5. Re-install bulb.
6. Turn power on and check operation by cycling
power switch as instructed under “MANUAL
ON WITH TIMED OFF” or by turning on a
humidity source until fan turns on.
7. Check “TIMER” setting with watch or clock
after turning humidity source off if it was
turned on it Step 6.
8. Repeat above steps if necessary.
CLEANING &
MAINTENANCE
To clean trim ring / baffle: Vacuum with a
soft brush attachment or remove trim ring /
baffle and clean with a soft cloth.
SENSOR CLEANING
The humidity sensor is mounted in the trim
ring/baffle. The sensor will operate most
reliably when cleaned occasionally as follows:
1. Disconnect power at service entrance.
2. Remove the trim ring/baffle. Use a dry
dustcloth, clean toothbrush, or lightly
vacuum to clean sensor and grille.
DO NOT USE ABRASIVE CLOTH,
STEEL WOOL PADS, OR SCOURING
POWDERS.
3. DO NOT USE cleaning sprays, solvents,
or water on or near the sensor!
To clean inside of housing: Remove trim
ring / baffle and vacuum inside of housing
with a soft brush attachment.
Motor is permanently lubricated. Do not oil or
disassemble motor.
See “Service Parts” section for a list and
illustrations of service parts.
Installer: Leave this manual
with the homeowner.
PLAN THE INSTALLATION
MODEL 744SFL
Page 2
INSTALLATION
CABLE
CEILING
JOIST
FINISHED CEILING
4" ROUND
DAMPER/DUCT
CONNECTOR &
4” ROUND
DUCTWORK
TRIM RING / BAFFLE
HOUSING
MOUNTING
BRACKET
Typical Installation
The unit can be installed anywhere between ceiling joists using
mounting brackets provided. Install in a flat ceiling only.
INSULATION
(Can be placed around and
over fan housing.)
ROOF
CAP
*
CARDBOARD PROTECTOR
1. Install mounting brackets.
Slide the adjustable mounting brackets into the bracket channels
on the housing.
Bend the tabs on the cardboard protector and insert protector
into opening in housing.
NOTE: The cardboard protector shields the inside of the housing
from drywall spray and construction dust. Do not remove it until
after construction is completed.
FAN
HOUSING
Purchase
*
separately
4-IN.
ROUND
DUCT
*
4-IN. ROUND
ELBOW(S)
*
WALL
CAP
*
Two of the most common ways to
connect ductwork to the unit.
The unit will operate most quietly and efficiently when located
where the shortest possible duct run and minimum number of
elbows will be needed.
Use a roof cap or wall cap that has a built-in damper to reduce
backdrafts.
Plan to supply the unit with proper line voltage and appropriate
power cable.
COOKING AREA
Do not install above or
inside this area.
NOT FOR USE IN
A COOKING AREA.
45
o
Cooking
Equipment
o
45
Floor
Do not install in a cooking area.
The unit must not be installed above or inside the cooking area shown.
1/8" GAP
2. Mark mounting location.
Position unit between joists and extend mounting brackets.
IMPORTANT: Position brackets so there will be an 1/8” gap
between bottom of housing and ceiling material. Mark the top
of keyhole slot on all four mounting brackets.
3. Pound in nails.
Remove unit temporarily, and pound nails partially into joists at
all four marked locations.
MODEL 744SFL
Page 3
4. Hang and secure housing.
Hang unit from nails. Check to make sure that there will be a 1/8”
gap between bottom of housing and ceiling material. Pound nails
tight. For wide joist centers: A #8 x 3/8 self-tapping screw can be
used to join extended brackets together and create a rigid mount.
To ensure a noise-free mount, crimp the bracket channels tightly
around mounting brackets.
FLUSH
manual mode (for odor control) by cycling ON/OFF switch.
– Allows fan to operate in automatic mode or
2-FUNCTION CONTROL
(ON/OFF)
FAN
(AUTO/OFF)
VAC
LINE
RED
GRD
ORG
FAN
WHTWHT
WIRING OPTION #2 – Allows fan to operate in automatic mode
or manual mode (for odor control) by cycling ON/OFF switch.
Fan always on with light.
MODEL 68W
2-FUNCTION CONTROL
(PURCHASE SEPARATELY)
FAN
(ON/OFF)
FAN
(AUTO/OFF)
120
VAC
LINE
GRD
WHT
BRNBLK
CONTROL
5. Attach damper/duct connector.
Snap the damper/duct connector onto housing. Make sure that
tabs on the connector lock in housing slots. (Top of damper/duct
connector will be flush with top of housing.) Install ductwork.
VERTICAL
POWER CABLE
CONNECTION
HORIZONTAL POWER CABLE
CONNECTION
6. Choose power cable direction.
Remove wiring plate. When re-attached, the wiring plate allows
the power cable to enter unit horizontally or vertically.
7. Connect wiring.
Unit can be wired from outside of housing as shown. Use UL
approved connectors to wire per local codes.
FINISHED
CEILING
MATERIAL
CLEARANCE
HOLE
HOUSING
COLLAR
8. Finish ceiling.
Cut an opening in finished ceiling material for housing collar.
SERVICE PARTS
1
2
4
3
9
MODEL 744SFL
Page 4
Humidity Control Assembly
must be removed to
service these parts.
5
6
9. Plug in wiring.
Plug wiring into the proper receptacles.
TRIM RING / BAFFLE
LAMP
BRACKET
SPRINGS
10. Attach trim ring / baffle to housing.
Remove the cardboard protector from inside the housing collar.
Use a pencil to insert one end of each spring into the holes on the
lamp bracket. Center trim ring / baffle in ceiling opening.
11. Install bulb.
CAUTION - RISK OF FIRE: Use only R30-shaped,
14W compact fluorescent lamp with GX24Q-1 base
(supplied). Replacement bulbs can be ordered from
Broan if not available locally (see service parts list).
CAUTION: Push bulb straight into bulb socket.
!
Do not twist bulb to install or remove.
15
8
11
13
12
KEY NO. PART NO. DESCRIPTION
1 97014185 Damper / Duct Connector
2 97016382 Housing Assembly
3 98003036 Mounting Bracket (4 req.)
4 98005512 Wiring Adaptor Plate
5 99524804 Blower Wheel *
6 99524805 Motor Bracket / Venturi *
7 99080557 Motor *
97016454 Motor / Motor Bracket Assembly
(includes Key Nos. 6 & 7) *
8 99770141 Lamp Wire Harness
9 99770143 Main Wire Harness
10 97018168 Humidity Control Assy.
(includes Lamp Bracket)
11 99271401 Ballast / Lampholder
12 97018169 Trim Ring / Baffle with Springs
& Humidity Sensor
13 99525160 Baffle Springs (2 req.)
14 97016848 Fluorescent Lamp
15 98010628 Electrical Box Cover
Order replacement parts by PART NO. - not by KEY NO.
* Humidity Control Assembly must be removed to service these parts.
10
14
WARRANTY
Broan-NuTone warrants to the original consumer purchaser of its products that
such products will be free from defects in materials or workmanship for a period of
one year from the date of original purchase. THERE ARE NO OTHER WARRANTIES,
EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, IMPLIED WARRANTIES
OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
During this one-year period, Broan-NuTone will, at its option, repair or replace, without
charge, any product or part which is found to be defective under normal use and service.
THIS WARRANTY DOES NOT EXTEND TO FLUORESCENT LAMP STARTERS AND
TUBES. This warranty does not cover (a) normal maintenance and service or (b) any
products or parts which have been subject to misuse, negligence, accident, improper
maintenance or repair (other than by Broan-NuTone), faulty installation or installation
contrary to recommended installation instructions.
The duration of an implied warranty is limited to the one-year period as specified for
the express warranty. Some states do not allow limitation on how long an implied
warranty lasts, so the above limitation may not apply to you.
BROAN-NUTONE’S OBLIGATION TO REPAIR OR REPLACE, AT BROAN-NUTONE’S
OPTION, SHALL BE THE PURCHASER’S SOLE AND EXCLUSIVE REMEDY UNDER
THIS WARRANTY. BROAN-NUTONE SHALL NOT BE LIABLE FOR INCIDENTAL,
CONSEQUENTIAL OR SPECIAL DAMAGES ARISING OUT OF OR IN CONNECTION WITH
PRODUCT USE OR PERFORMANCE. Some states do not allow the exclusion or limitation
of incidental or consequential damages, so the above limitation may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights, which
vary from state to state. This warranty supersedes all prior warranties.
To qualify for warranty service, you must (a) notify Broan-NuTone at the address or
telephone number stated below, (b) give the model number and part identification and
(c) describe the nature of any defect in the product or part. At the time of requesting
warranty service, you must present evidence of the original purchase date.
Broan-NuTone LLC Hartford, Wisconsin www.broan.com 800-558-1711
BROAN-NUTONE ONE YEAR LIMITED WARRANTY
99044499B
7