Broan 576, 676 User Manual

Page 1
!
!
To register this product visit
HOUSING
CEILING
JOIST
OR WALL STUD
MOUNTING TABS
GRILLE
CEILING OR WALL
MATERIAL
POWER CABLE
HOUSING
2 x 4
CEILING JOIST or
TRUSS
MOUNTING
TABS
GRILLE
CEILING
MATERIAL
POWER CABLE
ADDITIONAL
FRAMING
2 x 4 CEILING JOIST or
TRUSS
HOUSING
MOUNTING
TABS
GRILLE
CEILING
MATERIAL
POWER CABLE
ADDITIONAL
FRAMING
"I"
JOIST
"I"
JOIST
HOUSING
MOUNTING
TABS
CEILING
MATERIAL
POWER CABLE
ADDITIONAL
FRAMING
"I"
JOIST
"I"
JOIST
GRILLE
MOUNTING
TAB
GRILLE
SUSPENDED
CEILING MATERIAL
POWER
CABLE
4" ROUND
DUCT
HOUSING
www.broan.com
CEILING / WALL VENTILATORS/VENTILADORES DE CIELO RASO / PARED
MODELS / MODELOS 576 • 676 • 684
TYPICAL INSTALLATION
LEA Y CONSERVE ESTA
READ AND SAVE
THESE INSTRUCTIONSS
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number listed in the warranty.
3. Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and standards.
4. Sufficient air is needed for proper combus­tion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the Ameri­can Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
5. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. If this unit is to be installed in the ceiling over a tub or shower, it must be marked as appropriate for the application and be connected to a GFCI (Ground Fault Circuit Interrupter) - protected branch circuit.
8. Never place a switch where it can be reached from a tub or shower.
9. This unit must be grounded.
CAUTION
1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
2. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.
3. Please read specification label on product for further information and requirements.
Installer: Leave this manual with the homeowner. Homeowner: Use and Care information
on page 4.
HOUSING MOUNTED DIRECTLY TO
CEILING JOIST OR WALL STUD
2x6 (or larger) Discharge parallel to joists or studs.
*
*
HOUSING MOUNTED TO 2x4 TRUSS
Requires additional framing for mounting tabs.
Discharge parallel to joists.
*
HOUSING MOUNTED TO “I” JOIST
Requires additional framing for mounting tabs.
Discharge parallel to joists.
*
HOUSING MOUNTED IN
ANY LOCATION BETWEEN JOISTS
Requires additional framing for mounting tabs.
* Additional framing must be a 2x6 (minimum height).
SUSPENDED CEILINGS
Housing hung with wires - 3-point mount.
INSTRUCCIONES
ADVERTENCIA
PARA REDUCIR EL RIESGO DE INCENDIO, DES­CARGA ELÉCTRICA O LESIONES PERSONALES, OBSERVE LO SIGUIENTE:
1. Utilice esta unidad solamente de acuerdo con las instrucciones del fabricante. Si tiene preguntas comuníquese con el fabricante a la dirección o al número telefónico que se indica en la garantía.
2. Antes de dar servicio o limpiar la unidad, interrumpa el suministro de energía en el panel de servicio y bloquee los dispositivos de desconexión para evitar la reinstalación accidental de la energía. Cuando no se puedan bloquear los dispositivos de desconex­ión, fije seguramente en el panel de servicio un medio de advertencia que sea visible, como por ejemplo una etiqueta.
3. Una persona o personas calificadas deben realizar el trabajo de instalación y el cableado eléctrico, de acuerdo con todos los códigos y normas aplicables, inclusive los códigos y normas de construcción para evitar incendios.
4. Se necesita suficiente aire para que se realice la combustión y la descarga de gases adecuadas a través de la chimenea del equipo para quemar combustible a fin de evitar las corrientes de inver­sión. Observe los lineamientos del fabricante del equipo de calefacción y las normas de seguridad, como por ejemplo las publicadas por la Asociación Nacional de Protección contra Incendios (National Fire Protection Association: NFPA), y la Sociedad Americana de Ingenieros en Calefacción, Refrig­eración y Sistemas de Acondicionamiento de Aire (American Society for Heating, Refrigeration and Air Conditioning Engineers: ASHRAE), y los códigos locales.ditioning Engineers (ASHRAE), and the local code authorities.
5. Cuando corte o perfore la pared o el cielo raso, tenga cuidado de no dañar el cableado eléctrico ni otras conexiones de servicios que se encuentren ocultas.
6. Los ventiladores con conductos siempre deben tener salida hacia el exterior.
7. Si se va a instalar esta unidad en el cielo raso sobre una tina o ducha, debe marcarse que es apropiada para esta aplicación y conectarse a un GFCI (inter­ruptor accionado por pérdida de conexión a tierra) en un circuito de derivación protegido.
8. Nunca coloque el interruptor en un lugar en donde se pueda alcanzar desde la tina o ducha.
9. Esta unidad debe conectarse a tierra.
PRECAUCIÓN
1. Esta unidad debe usarse solamente para venti­lación general. No la utilice para la descarga de materiales ni vapores peligrosos o explosivos.
2. Para evitar causar daño a los cojinetes del motor y pistones impulsores ruidosos y/o no balancea­dos, mantenga los aerosoles para pirca, el polvo de construcción, etc. lejos del motor.
3. Por favor consulte la información y los re­querimientos adicionales contenidos en la etiqueta de especificaciones que se encuentra en el producto.
A la persona que realiza la instala­ción: Deje este manual con el dueño de la casa. Al dueño de la casa: Las instrucciones de operación y limpieza se encuentran
en la página 4.
Page 2
MOUNTING
TAB
GRILLE
SUSPENDED
CEILING MATERIAL
POWER
CABLE
4" ROUND
DUCT
HOUSING
ALETA DE MONTAJE
REJILLA
MATERIAL DEL
TECHO SUSPENDIDO
CABLE
DE ALIMENTACIÓN
CONDUCTO
REDONDO DE
4" (10.2 CM)
CUBIERTA
5/8
1
1-1/4
ALETA DE MONTAJE
REJILLA
MATERIAL DEL
TECHO SUSPENDIDO
CABLE
DE ALIMENTACIÓN
CONDUCTO
REDONDO DE
4" (10.2 CM)
CUBIERTA
INSTALACIONES TÍPICAS
CUBIERTA
VIGUETA
DEL
TECHO
O PARED
ALETAS DE
MONTAJE
REJILLA
MATERIAL DEL
TECHO O PARED
CABLE
DE ALIMENTACIÓN
CUBIERTA
ALETAS DE
MONTAJE
REJILLA
MATERIAL
DEL TECHO
CABLE
DE ALIMENTACIÓN
ESTRUCTURA
ADICIONAL*
VIGUETA O
VIGA DE
2x4 DE CIELO
RASO
VIGUETA O
VIGA DE
2x4 DE
CIELO RASO
CUBIERTA
CABLE DE ALIMENTACIÓN
VIGUETA
"
I
"
ALETAS DE
MONTAJE
MATERIAL
DE CIELO RASO
ESTRUCTURA
ADICIONAL
REJILLA
VIGUETA
"
I
"
CUBIERTA
CABLE DE ALIMENTACIÓN
VIGUETA
"
I
"
ALETAS DE
MONTAJE
MATERIAL
DEL TECHO
ESTRUCTURA
ADICIONAL*
REJILLA
VIGUETA
"
I
"
TYPICAL INSTALLATIONS
INSTALACIONES TÍPICAS
CUBIERTA MONTADA
DIRECTAMENTE EN LA VIGUETA
2x6 (o más grande). Descarga paralela a las viguetas.
*
CUBIERTA MONTADA EN UNA VIGA DE 2x4
Se requiere una estructura adicional para las aletas
de montaje. Descarga paralela a las viguetas.
*
CUBIERTA MONTADA EN UNA VIGUETA “I”
Se requiere una estructura adicional para las aletas
de montaje. Descarga paralela a las viguetas.
*
CUBIERTA MONTADA EN CUALQUIER
LUGAR ENTRE LAS VIGUETAS
Se requiere una estructura adicional
para las aletas de montaje.
* La estructura adicional debe ser un tramo de 2x6 (altura mínima).
Housing hung with wires - 3-point mount.
SUSPENDED CEILINGS
INSTALL THE HOUSING
THE FOLLOWING INSTALLATION ILLUSTRATIONS SHOW 2 X 6 JOISTS OR STUDS. IF YOU HAVE A TRUSS OR “I”-JOIST INSTALLATION, MOUNT THE VENTILATOR TO THE ADDITIONAL FRAMING IN THE SAME MANNER. (Additional framing must be a 2x6 (minimum height).
1. Choose the location for your fan in the ceil­ing or wall. For best possible performance, use the shortest possible duct run and a minimum number of elbows.
2. Position mounting brackets against joist or stud so that bottom edge of housing will be flush with finished ceiling or wall.
Additional positioning
feature for 5/8”, 1”, & 1-1/4” thick ceiling or
wall material:
Holes in corners of housing are labeled with
various ceiling or wall material thicknesses. Position housing so bottom edge of joist is visible through a matched set of holes. The housing is now in the proper position for that ceiling or wall material thickness.
Additional positioning feature for 1/2” thick
ceiling or wall material:
Bend two tabs, on side of housing,
Lift housing until tabs contact underside of joist or stud.
Mark the keyhole slot on both mounting
brackets.
3. Set housing aside and drive nails partially into joist or stud at the top of both keyhole marks.
- PLEASE NOTE -
New Construction
HOLES
OROFICIOS
TAB
ALETA
BOTTOM EDGE OF JOIST
BORDE INFERIOR DE LA VIGUETA
900 outward.
Cubierta montada con cables. Montaje de tres puntos.
TECHOS SUSPENDIDOS
INSTALACIÓN DE LA CUBIERTA
LAS SIGUIENTES ILUSTRACIONES DE LA INSTALACIÓN MUESTRAN VIGUETAS O MONTANTES DE 2 X 6. SI LA INSTALACIÓN ES EN UNA VIGA O EN UNA VIGUETA EN “I”, MONTE EL VENTILADOR EN LA ESTRUCTURA ADICIONAL DE LA MISMA MANERA. (La estructura adicional debe ser un tramo de 2x6 (altura mínima).
1. Seleccione la ubicación del ventilador con lámpara en el cielo raso o pared. Para obtener el mejor rendimien­to posible, utilice un tramo de conductos lo más corto
en las esquinas de la cubierta están marcados con varios espesores del material del cielo raso o pared. Coloque la cubierta de manera que el borde inferior de la vigueta sea visible a través del conjunto de orificios que coinciden. Ahora la cubierta se encuentra en la posición adecuada para ese espesor del material del cielo raso o pared.
Característica adicional para la colocación en material
de cielo raso o pared de ½” (1.3 cm):
Doble a 90º y hacia afuera las dos aletas que se encuen-
tran a los costados de la cubierta. Levante la cubierta hasta que las aletas entren en contacto con la cara inferior de la vigueta or montante.
Marque el orificio con forma de cerradura de ambas
abrazaderas de montaje.
- POR FAVOR NOTE -
Construcción nueva
Construcción nueva
posible y un número mínimo de codos.
2. Coloque las abrazaderas de montaje contra la vigueta o montante, de manera que el borde inferior de la cubierta quede al ras del cielo raso o pared terminado.
Característica adicional para la
colocación en material de cielo
raso o pared de 5/8” (1.6 cm), 1” (2.5 cm) y 1 ¼” (3.2 cm):
Los orificios que se encuentran
3. Coloque la cubierta a un lado e introduzca parcialmente los clavos en la vigueta o mon­tante, en la parte superior de ambas marcas de los orificios en forma de cerradura.
Cubierta montada con cables. Montaje de tres puntos.
TECHOS SUSPENDIDOS
4. Hang housing from nails and pound nails tight. To ensure a noise-free mount, pound another nail through the top hole of each mounting tab.
2
4. Suspenda la cubierta con los clavos e introduzca los clavos completamente. Para asegurar un montaje sin ruido, coloque otro clavo en el orificio superior de cada aleta de montaje.
Page 3
INSTALL THE HOUSING
SWITCH BOX
ON / OFF SWITCH
(purchase separately)
WHITE
BLACK
GROUND (bare)
WIRING
PLATE
120 VAC
LINE IN
RECEPTACLE
CAJA DE INTERRUPTOR
INTERRUPTOR
ENCENDIDO /
APAGADO
(se vende por
separado)
BLANCO
NEGRO
TIERRA (desnudo)
PLACA
DE CONEXIONES
LÍNEA DE ENTRADA
DE 120 VCA
RECEPTÁCULO
BLK
BLK
WHT
WHT GRD
UNIT
SWITCH BOX
ON / OFF
SWITCH
LINE
IN
BLK
WHT GRD
M
NEG
NEG
BLC
BLC TRA
UNIDAD
CAJA DE
INTERRUPTOR
INTER-
RUPTOR
ENCENDIDO/
APAGADO
LÍNEA
DE
ENTRADA
NEG
BLC TRA
M
INSTALACIÓN DE LA CUBIERTA
Existing Construction
1. Choose the location for your fan in the ceiling or wall. For best possible performance, use the shortest possible duct run and a minimum number of elbows.
2. In attic or behind wall, position mounting brackets against joist. Trace outline of housing on ceiling or wall material.
3. Set housing aside and cut ceiling or wall opening slightly larger than marked.
4. Place housing in opening so that its bottom edge is flush with finished ceiling or wall. Nail to joist through keyhole on both sides. To ensure a noise-free installation, drive another nail through the top hole of each mounting bracket.
5. Additional mounting holes are provided for installations where access from above is inconvenient or not possible. Nail or screw housing directly to joists, studs or framing.
INSTALL THE DUCTWORK
1. Snap the damper/duct connector onto housing. Make sure that tabs on the connector lock into slots in housing. Top of damper/duct connector should be flush with top of housing.
2. Connect 4” round duct to damper/duct connector and extend duct to outside through a roof or wall cap. Check damper to make sure that it opens freely. Tape all duct connections to make them secure and air tight.
CONNECT THE WIRING
1. Wire unit following diagram. Run electrical cable as direct as possible to unit. Do not allow cable to touch sides or top of unit after installation is complete.
ATTACH THE GRILLE
1. Squeeze grille springs together and insert springs into slots in motor plate.
NOTE: If desired, rotate grille 90o and move springs to
optional tabs.
2. Push grille against ceiling or wall.
ADDITIONAL MOUNTING HOLES
ORIFICIOS DE MONTAJE ADICIO-
NALES
FLUSH AL RAS
Construcción existente
1. Seleccione la ubicación del ventilador en el cielo raso o pared. Para obtener el mejor rendimiento posible, utilice un tramo de conductos lo más corto posible y un número mínimo de codos.
2. En el entretecho o detrás de la pared, coloque las abrazaderas de montaje contra la vigueta. Trace el perímetro de la cubierta en el material del techo o pared.
3. Coloque la cubierta a un lado y haga una abertura en el techo o pared ligeramente más grande que el perímetro marcado.
4. Coloque la cubierta en la abertura de manera que su borde inferior quede al ras del cielo raso o pared terminado. Clave la cubierta en la vigueta a través del orificio en forma de cerradura, en ambos lados. Para asegurar un montaje sin ruido, coloque otro clavo en el orificio superior de cada aleta de montaje.
5. En la cubierta se pueden encontrar orificios de montaje adicio­nales para aquellas instalaciones en las que es inconveniente o imposible el acceso desde arriba. Clave o atornille la cubierta directamente en las viguetas, montantes o el armazón.
INSTALACIÓN DEL SISTEMA DE CONDUCTOS
1. Conecte a presión el conector del regulador de tiro/conducto en la cubierta. Asegúrese de que las aletas del conector queden fijas en las ranuras de la cubierta. La parte superior del conector del regulador de tiro/conducto debe quedar al ras de la parte superior de la cubierta.
2. Conecte el conducto redondo de 4” (10.2 cm) en el conector del regulador de tiro/conducto y extienda el conducto hasta el exterior a través de una tapa de techo o de pared. Revise el regulador de tiro para asegurarse de que abre libremente. Coloque cinta en todas las conexiones de los conductos para asegurarlas y hacerlas herméticas.
CONEXIÓN ELÉCTRICA
1. Conecte la unidad de acuerdo con este diagrama. Extienda el cable eléctrico a la unidad tan directamente como sea posible. No permita que el cable toque los costados ni la parte superior de la unidad después de que la instalación esté terminada.
CONEXIÓN DE LA REJILLA
1. Apriete los resortes de la rejilla y métalos en la place del motor.
NOTA: Si lo desea, haga girar la rejilla 90o y mueva los resortes
a las orejetas opcionales.
2. Presione la rejilla contra el cielo raso o pared.
OPTIONAL TABS
OREJETAS
OPCIONALES
SLOT IN MOTOR PLATE
RANURA EN EL PLACA DEL MOTOR
SPRING TABS
OREJETAS
DEL RESORTES
GRILLE SPRING RESORTE DE LA
REJILLA
3
Page 4
USE AND CARE
INSTRUCCIONES DE OPERACIÓN Y LIMPIEZA
WARNING: DISCONNECT ELECTRICAL POWER SUPPLY AND LOCK OUT SERVICE PANEL BEFORE CLEANING OR SERVICING THIS UNIT.
MOTOR LUBRICATION
The motor is permanently lubricated. Do not oil or disassemble motor.
CLEANING
TO CLEAN GRILLE: CAUTION: Plastic parts can be cleaned with mild, soapy water (use a mild detergent, such as dishwashing liquid) and dried with a soft cloth. Do not use abrasive cloth, steel wool pads, or scouring powders.
TO CLEAN FAN ASSEMBLY:
Unplug fan assembly. To remove motor plate: Find the single tab on the motor plate (located next to the receptacle). Push up near motor plate tab while pushing out on side of housing. Or insert a straight-blade screwdriver into slot in housing (next to tab) and twist screwdriver. Gently vacuum fan, motor and interior of housing. METAL AND ELECTRICAL PARTS SHOULD NEVER BE IMMERSED IN WATER.
WARRANTY
Broan-NuTone warrants to the original consumer purchaser of its products that such products will be free from defects in materials or workmanship for a period of one year from the date of original purchase. THERE ARE NO OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
During this one-year period, Broan-NuTone will, at its option, repair or replace, without charge, any product or part which is found to be defective under normal use and service.
THIS WARRANTY DOES NOT EXTEND TO FLUORESCENT LAMP STARTERS, TUBES, HALOGEN AND INCANDESCENT BULBS, FUSES, FILTERS, DUCTS, ROOF CAPS, WALL CAPS AND OTHER ACCESSORIES FOR DUCTING. This warranty does not cover (a) normal maintenance and service or (b) any products or parts which have been subject to misuse, negligence, accident, improper maintenance or repair (other than by Broan­NuTone), faulty installation or installation contrary to recommended installation instructions.
The duration of any implied warranty is limited to the one-year period as specified for the express warranty. Some states do not allow limitation on how long an implied warranty lasts, so the above limitation may not apply to you.
BROAN-NUTONE’S OBLIGATION TO REPAIR OR REPLACE, AT BROAN-NUTONE’S OPTION, SHALL BE THE PURCHASER’S SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY. BROAN-NUTONE SHALL NOT BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES ARISING OUT OF OR IN CONNECTION WITH PRODUCT USE OR PERFORMANCE. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights, which vary from state to state. This warranty supersedes all prior warranties.
To qualify for warranty service, you must (a) notify Broan-NuTone at the address or telephone number below, (b) give the model number and part identification and (c) describe the nature of any defect in the product or part. At the time of requesting warranty service, you must present evidence of the original purchase date.
Broan-NuTone LLC, 926 W. State Street, Hartford, Wisconsin 53027 www.broan.com 800-558-1711
BROAN-NUTONE ONE YEAR LIMITED WARRANTY
SERVICE PARTS/PIEZAS DE SERVICO
KEY
No. PART NO. CLAVE No. PIEZA. DESCRIPTION/DESCRIPCIÓN
1 97013576 Grille/Rejilla 2 97018310 Motor Plate/Placa del motor (576) 97014926 Motor Plate/Placa del motor (676, 684) 3 99080656 Motor (576) 99080517 Motor (676) 99080518 Motor (684) 4 99020300 Impeller/Pistón impulsor (576) 99020276 Impeller/Pistón impulsor (676, 684) 5 99260425 Motor Nut (2 req.)/Tuerca del motor (se req. 2) * 97018554 Blower Assembly (576) (includes Key Nos. 2 thru 5) Conjunto del ventilador (576) (incluye Clave Nos. 2 de a 5) * 97015157 Blower Assembly (676) (includes Key Nos. 2 thru 5) Conjunto del ventilador (676) (incluye Clave Nos. 2 de a 5) * 97015159 Blower Assembly (684) (includes Key Nos. 2 thru 5) Conjunto del ventilador (684) (incluye Clave Nos. 2 de a 5) 6 99270982 Receptacle/Receptáculo 7 98009611 Wire Panel/Panel del cableado * 97015170 Wire Panel Assembly (includes Key Nos. 6 & 7) Conjunto del panel de cableado (incluye Clave No. 6 & 7) 8 97014922 Housing/Cubierta 9 97003932 Damper/Duct Connector/Conector del regulador de tiro/conducto 10 98008868 Wiring Plate/Placa de conexiones 11 99150245 Screw, #8-18 x .375/Tornillo, #8-18 x .375 12 99150471 Ground Screw/Tornillo de conexión a tierra
* Not shown assembled. Order replacement parts by “PART NO.” - not by “KEY NO.”
* No ilustrado ensamblado. Pida piezas de servicio dando como referencia el No. DE PIEZA, no el No. DE CLAVE.
ADVERTENCIA: ANTES DE LIMPIAR O DAR SERVICIO ESTA UNIDAD, DESCONECTE EL SUMINISTRO DE ENERGÍA Y BLOQUEE EL PANEL DE SERVICIO .
LUBRICACIÓN DEL MOTOR
El motor está permanentemente lubricado. No lubrique ni desmonte el motor.
LIMPIEZA
PARA LIMPIAR LA REJILLA: PRECAUCIÓN: Las piezas de plástico se pueden limpiar con una solución suave
de agua y jabón (use un detergente suave, como por ejemplo líquido para lavar vajilla) y séquelas con un paño suave. No use tela abrasiva, almohadillas de estropajo de acero ni polvos desengrasadores.
PARA LIMPIAR EL CONJUNTO DEL VENTILADOR:
Desenchufe el conjunto del ventilador. Para quitar la placa del motor: Localice la aleta de la placa del motor (se encuentra junto a el receptáculo). Empuje hacia arriba la aleta de la placa del motor mientras empuja hacia afuera el costado de la cubierta. O bien, introduzca un destornillador de punta recta en la ranura de la cubierta (junto a la aleta) y haga girar el destornillador. Con una aspiradora limpie suavemente el ventilador, e motor y el interior de la cubierta. NUNCA DEBE SUMERGIR EN AGUA LAS PIEZAS METÁLICAS NI LAS ELÉCTRICAS.
GARANTIA
Broan-NuTone garantiza al consumidor comprador original de sus productos que dichos productos carecerán de defectos en materiales o en mano de obra por un período de un año a partir de la fecha original de compra. NO EXISTEN OTRAS GARANTÍAS, EXPLICITAS O IMPLÍCITAS, INCLUYENDO, ENTRE OTRAS, GARANTÍAS IMPLÍCITAS DE COMERCIALIZACIÓN O APTITUD PARA UN PROPÓSITO PARTICULAR.
Durante el período de un año, y a su propio criterio, Broan-NuTone reparará o reemplazará, sin costo alguno, cualquier producto o pieza que se encuentre defectuosa bajo condiciones normales de servicio y uso.
LA PRESENTE GARANTÍA NO CUBRE LOS TUBOS FLUORESCENTES NI SUS ARRANCADORES, BOMBILLAS DE HALÓGENO E INCANDESCENTES, FUSIBLES, FILTROS, CONDUCTOS, TAPONES DE TECHO O PAREDES Y DEMÁS ACCESORIOS PARA CONDUCTOS. Esta garantía no cubre (a) mantenimiento y servicio normales o (b) cualesquiera productos o piezas que hayan sido utilizados de forma errónea, negligente, que hayan causado un accidente, o que hayan sido reparados o mantenidos inapropiadamente (por otras compañías que no sean Broan-NuTone), instalación defectuosa, o instalación contraria a las instrucciones de instalación recomendadas.
La duración de cualquier garantía implícita se limita a un período de un año como se especifica en la garantía expresa. Algunos estados no permiten limitaciones en cuanto al tiempo de vencimiento de una garantía implícita, por lo que la limitación antes mencionada puede no aplicarse a usted.
LA OBLIGACIÓN DE BROAN-NUTONE DE REPARAR O REEMPLAZAR, SIGUIENDO EL CRITERIO DE BROAN­NUTONE, DEBERÁ SER EL ÚNICO Y EXCLUSIVO RECURSO LEGAL DEL COMPRADOR BAJO ESTA GARANTÍA. BROAN-NUTONE NO SERÁ RESPONSABLE POR DAÑOS INCIDENTALES, CONSECUENTES, O POR DAÑOS ESPECIALES QUE SURJAN A RAÍZ DEL USO O DESEMPEÑO DEL PRODUCTO. Algunos estados no permiten la exclusión o limitación de daños incidentales o consecuentes, por lo que la limitación antes mencionada puede no aplicarse a usted.
Esta garantía le proporciona derechos legales específicos, y usted puede también tener otros derechos, los cuales varían de estado a estado. Esta garantía reemplaza todas las garantías anteriores.
Para calificar para la garantía de servicio, usted debe (a) notificar a Broan-NuTone al domicilio o al número de teléfono que se menciona abajo, (b) dar el número del modelo y la identificación de la pieza, y (c) describir la naturaleza de cualquier defecto en el producto o la pieza. En el momento de solicitar servicio cubierto por la garantía, usted debe de presentar un comprobante con la fecha original de compra.
Broan-NuTone LLC, 926 W. State Street, Hartford, Wisconsin 53027 www.broan.com 800-558-1711
Replacement parts can now be ordered on our
website. Please visit
us at www.Broan.com
1
GARANTÍA BROAN-NUTONE LIMITADA POR UN AÑO
10
11
7
6
2
4
3
Las piezas de recambio
se pueden ahora pedir en
5
nuestro Web site. Visítenos
9
12
8
por favor en
www.Broan.com
99043689D
Loading...