Briggs & Stratton Home Generator User Manual

Operator’s Manual
Questions? Help is just a moment away!
Call: Home Generator Helpline
(800) 743-4115 M-F 8-5 CT
BRIGGSandSTRATTON.COM
20000 / 18000
Home Generator
Manual No. 202827GS Rev. C (11/02/2007)
Thank you for purchasing this quality-built Briggs & Stratton home generator. We’re pleased that you’ve placed your confidence in the Briggs & Stratton brand. When operated and maintained according to the instructions in this manual, your Briggs & Stratton home generator will provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with home generator systems and how to avoid them. This home generator system is designed and intended only for use as an optional home standby system that provides an alternate source of electric power and to serve loads such as heating, refrigeration systems, and communication systems that, when stopped during any power outage, could cause discomfort or inconvenience. This product is not intended for any other purpose and does not qualify for emergency standby as defined by NFPA 70 (NEC).
This home generator requires professional installation before use. Refer to the separate Installation Manual for full information. Follow the instructions completely. Save these instructions for future reference.
Where to Find Us
You never have to look far to find Briggs & Stratton support and service for your generator. Consult your Yellow Pages. There are over 30,000 Briggs & Stratton authorized service dealers worldwide who provide quality service. You can also contact Briggs & Stratton Customer Service by phone at (800) 743-4115, or use the Service Center Locator at BRIGGSandSTRATTON.COM, which provides a list of Briggs & Stratton Authorized Dealers.
Date of Purchase
Generator
Model Number
Model Revision
Serial Number
Engine
Model Number
Briggs & Stratton Power Products Group, LLC 900 North Parkway Jefferson, WI 53549
Copyright © 2007 Briggs & Stratton Power Products Group, LLC. All rights reserved. No part of this material may be reproduced or transmitted in any form by any means without the express written permission of Briggs & Stratton Power Products Group, LLC.
Table of Contents
Safety Rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Owner Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Fuel Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Delivery Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Features and Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Home Generator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Automatic Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Setting Exercise Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Servicing the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Fault Detection System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Generator Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Engine Oil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Storage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Warranty. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
FrançaisEspañol
3
Save These Instructions
Safety Rules
The safety alert symbol ( ) is used with a signal word (DANGER, CAUTION, WARNING), a pictorial and/or a safety message to alert you to hazards. DANGER indicates a hazard which, if not avoided, will result in death or serious injury. WARNING indicates a hazard which, if not avoided, could result in death or serious injury. CAUTION indicates a hazard which, if not avoided, might result in minor or moderate injury. NOTICE indicates a situation that could result in equipment damage. Follow safety messages to avoid or reduce the risk of injury or death.
The manufacturer cannot possibly anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and the tags and decals affixed to the unit are, therefore, not all-inclusive. If you use a procedure, work method or operating technique that the manufacturer does not specifically recommend, you must satisfy yourself that it is safe for you and others. You must also make sure that the procedure, work method or operating technique that you choose does not render the generator system unsafe.
NOTE: Your generator is equipped with a spark arrester muffler. The spark arrester must be maintained in effective working order by the owner/operator. In the State of California, a spark arrester is required by law (Section 4442 of the California Public Resources Code). Other states may have similar laws. Federal laws apply on federal lands.
Hazard Symbols and Meanings
WARNING
Storage batteries give off explosive hydrogen gas during recharging.
Slightest spark will ignite hydrogen and cause explosion.
Battery electrolyte fluid contains acid and is extremely caustic.
Contact with battery contents will cause severe chemical burns.
A battery presents a risk of electrical shock and high short circuit current.
DO NOT dispose of battery in a fire.
• DO NOT allow any open flame, spark, heat, or lit cigarette
• during and for several minutes after charging a battery.
DO NOT open or mutilate the battery.
• Wear protective goggles, rubber apron, and rubber
• gloves.
Remove watches, rings, or other metal objects.
• Use tools with insulated handles.
WARNING
Running engine gives off carbon monoxide, an odorless, colorless, poison gas.
Breathing carbon monoxide can cause headache, fatigue, dizziness, vomiting, confusion, seizures, nausea, fainting or death.
Operate generator ONLY outdoors.
• Install a battery operated carbon monoxide alarm near the
Explosion
Toxic Fumes
Fire
Rotating Parts
Electrical Shock
Hot Surface
Chemical BurnExplosive PressureAuto Start
• bedrooms.
Keep exhaust gas from entering a confined area through
• windows, doors, ventilation intakes, or other openings.
WARNING
The engine exhaust from this product contains chemicals
known to the State of California to cause cancer, birth
defects, or other reproductive harm.
WARNING
WARNING
Generator produces hazardous voltage. Failure to properly ground generator can result
in electrocution. Failure to isolate generator from power utility
can result in death or injury to electric utility workers due to backfeed of electrical energy.
When using generator for backup power, notify utility
• company.
DO NOT touch bare wires or receptacles.
• DO NOT use generator with electrical cords which are
• worn, frayed, bare or otherwise damaged.
DO NOT handle generator or electrical cords while
• standing in water, while barefoot, or while hands or feet are wet.
If you must work around a unit while it is operating,
• stand on an insulated dry surface to reduce shock hazard.
DO NOT allow unqualified persons or children to operate
• or service generator.
In case of an accident caused by electrical shock,
• immediately shut down the source of electrical power and contact the local authorities. Avoid direct contact with
the victim.
Despite the safe design of the home generator, operating
• this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death.
Remain alert at all times while working on this
• equipment. Never work on the equipment when you are physically or mentally fatigued.
Before performing any maintenance on the generator,
• disconnect the battery cable indicated by a NEGATIVE, NEG or (-) first. When finished, reconnect that cable last.
After your home generator is installed, the generator
• may crank and start without warning any time there is a power failure. To prevent possible injury, always set the generator’s system switch to OFF, remove the service disconnect from the disconnect box AND remove the 15 Amp fuse BEFORE working on the equipment.
Propane and Natural Gas are extremely flammable and explosive.
Fire or explosion can cause severe burns or death.
Install the fuel supply system according to applicable
• fuel-gas codes.
Before placing the home generator into service, the fuel
• system lines must be properly purged and leak tested.
After the generator is installed, you should inspect the
• fuel system periodically.
NO leakage is permitted.
• DO NOT operate engine if smell of fuel is present or other
• explosive conditions exist.
DO NOT smoke around the generator. Wipe up any oil
• spills immediately. Ensure that no combustible materials are left in the generator compartment. Keep the area near the generator clean and free of debris.
WARNING
Contact with muffler area can result in serious burns.
Exhaust heat/gases can ignite combustibles or structures causing a fire.
DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• DO NOT install the generator closer than 5 feet (1.5m)
• from any combustibles or structures with combustible walls having a fire resistance rating of less than 1 hour.
Keep at least minimum distances shown in General
Location Guidelines to insure for proper generator cooling and maintenance clearances.
Code of Federal Regulation (CFR) Title 36 Parks, Forests,
• and Public Property require equipment powered by an internal combustion engine to have a spark arrester, maintained in effective working order, complying to USDA Forest service standard 5100-1C or later revision. In the State of California a spark arrester is required under section 4442 of the California Public resources code. Other states may have similar laws.
5
WARNING
Starter and other rotating parts can entangle hands, hair, clothing, or accessories.
NEVER operate generator without protective housing or
• covers.
DO NOT wear loose clothing, jewelry or anything that
• may be caught in the starter or other rotating parts.
Tie up long hair and remove jewelry.
CAUTION
Installing the 15A fuse could cause the engine to start.
Observe that the 15 Amp fuse has been removed from
• the control panel for shipping.
DO NOT install this fuse until all plumbing and wiring has
• been completed and inspected.
CAUTION
Excessively high operating speeds increase risk of injury and damage to generator.
Excessively low speeds impose a heavy load.
DO NOT tamper with governed speed. Generator supplies
• correct rated frequency and voltage when running at governed speed.
DO NOT modify generator in any way.
NOTICE
NOTICE
Improper treatment of generator can damage it and shorten its life.
Use generator only for intended uses.
• If you have questions about intended use, ask dealer or
• contact Briggs and Stratton.
Operate generator only on level surfaces.
• Adequate, unobstructed flow of cooling and ventilating air
• is critical to correct generator operation.
The Oil Fill, Oil Drain and the Control Panel doors must be
• installed whenever the unit is running.
DO NOT expose generator to excessive moisture, dust,
• dirt, or corrosive vapors.
Despite the safe design of the home generator, operating
• this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death.
Remain alert at all times while working on this
• equipment. NEVER work on the equipment when you are physically or mentally fatigued.
DO NOT start engine with air cleaner or air cleaner cover
• removed.
DO NOT insert any objects through cooling slots.
• DO NOT use the generator or any of its parts as a step.
• Stepping on the unit can cause stress and break parts. This may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
If connected devices overheat, turn them off and
• disconnect them from generator.
Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
Exceeding generators wattage/amperage capacity can damage generator and/or electrical devices connected to it.
See Essential Circuits.
• Start generator and let engine stabilize before connecting
• electrical loads.
Installation
We sincerely appreciate your patronage. For this reason, Briggs & Stratton has made every effort to provide for a safe, streamlined and cost-effective installation. Because each installation is unique, it is impossible to know of and advise the trade of all conceivable procedures and methods by which installation might be achieved. Neither could we know of possible hazards and/or the results of each method or procedure. For these reasons,
Only current licensed electrical and plumbing contractors
should attempt home generator system installations.
Installations must strictly comply with all applicable
codes, industry standards and regulations.
Your Briggs & Stratton home generator is supplied with this “Operator’s Manual” and a separate “Installation Manual”. These are important documents and should be retained by the owner after the installation has been completed.
For the Home Owner:
To help you make informed choices and communicate effectively with your installation contractor(s),
Read and understand Owner Orientation in this manual
before contracting or starting your home generator
installation.
To arrange for proper installation, contact the store at which you purchased your Briggs & Stratton home generator, your dealer, a licensed electrician or your utility power provider.
The home generator warranty is VOID unless the
system is installed by licensed electrical and plumbing
professionals.
The Emission Control System for this generator is warranted for standards set by the U.S. Environmental Protection Agency and by the California Air Resources Board (CARB).
For the Installing Dealer/Contractor:
For most applications, the Installation manual contains all the information required to properly install and start the home generator. This Operator’s Manual describes essential circuit selection, routine operation and owner maintenance procedures.
If you need more information, call (800) 743-4115, between 8:00 AM and 5:00 PM CT.
Owner Orientation
This section provides home generator owners with the information necessary to achieve the most satisfactory and cost effective installation possible.
The illustrations are for typical circumstances and are meant to familiarize you with the installation options available with your home generator. A thorough understanding of these options will provide fundamental control over the cost of your installation, as well as ensure your final satisfaction and security.
Federal and local codes, appearance, noise levels, fuel types, and distances are the factors that must be considered when negotiating with an installation professional. Remember that as the distance from the existing electrical service and gaseous fuel supply increases, and the number of 90 degree bends in the fuel supply increases; equal compensations in piping and wiring materials must be allowed for. This is necessary to comply with local codes and overcome electrical voltage drops and gaseous fuel pressure drops.
The factors mentioned above will have a direct affect on
the overall price of your home generator installation.
NOTE: In some areas you may need to acquire electrical
permits for installing the home generator, building permits for installing gas lines, and permits for noise allowances. Your installer should check your local codes AND obtain the permits before installing the system.
Fuel Factors
An important consideration affecting the entire installation is the type of fuel used by your home generator. The system was factory tested and adjusted using either natural gas or liquid propane (LP vapor). For proper engine function, factors that are inherent to each of these fuels, your location and the duration of possible utility interruptions are important considerations in the following fuel guidelines:
• Use clean, dry fuel, free of moisture or any particulate material. Using fuels outside the following recommended values may cause performance problems.
• In engines set up to run on propane (LP), commercial grade HD5 propane with a minimum fuel energy of 2500 BTUs/ft3 with maximum propylene content of 5% and butane and heavier gas content of 2.5% and minimum propane content of 90%.
WARNING
Propane and Natural Gas are extremely flammable and explosive.
Fire or explosion can cause severe burns or death.
The home generator is equipped with an automatic safety
• gas “fuel shut-off” valve.
DO NOT operate the equipment if the “fuel shut-off” valve
• is missing or inoperative.
Power Decrease at High Altitude or High Temperature
Air density is less at high altitudes, resulting in less available engine power. Specifically, engine power will decrease 3.5% for each 1,000 feet (300 meters) above sea level and 1% for each 10° F (5.6°C) above 77°F (25°C). Make sure you and your installer consider these factors when determining total generator load.
7
Generator Location
The actual physical location of your home generator has a direct affect on:
1. The amount of plumbing required to fuel your generator.
2. The amount of wiring required to control and connect your generator.
NOTE: Specific location guidelines are discussed in the Installation Manual. Acquaint yourself with that information and confer with your installer. Be sure to ask how your site might affect installation costs and compliance with local codes and standards.
Generator Clearances
The generator must be installed outdoors. DO NOT install generator where exhaust gas could accumulate and enter inside or be drawn into a potentially occupied building. Ensure exhaust gas is kept away from any windows, doors, ventilation intakes or other openings that can allow exhaust gas to collect in a confined area. Prevailing winds and air currents should be taken into consideration when positioning generator. See the Installation Manual for full details on safe generator location.
WARNING
Exhaust heat/gases can ignite combustibles or structures causing a fire.
DO NOT install the generator closer than 5 feet (1.5m)
• from any combustibles or structures with combustible walls having a fire resistance rating of less than 1 hour.
Keep at least minimum distances shown in General
Location Guidelines in Installation Manual to insure for proper generator cooling and maintenance clearances.
Essential Circuits
As a home generator owner, it is important that you clearly identify the circuits in your building that are “essential” to you.
It is also important that your installer understand which circuits you want to include as “Essential Circuits”. Depending on the power consumed by these circuits, most or all of them can be switched to the home generator for the duration of normal power interruption.
The wattage reference table that follows will assist you with your decision-making process. It provides the wattage used by many ordinary household devices. Use it as a guide when selecting your essential circuits. Review this information with your installer and ask about any technical considerations that might affect your installation. This chart serves as a guide only. For exact wattage use an appropriate wattage meter
Device
q
Air Conditioner (12,000 Btu)* 1700
q
Air Conditioner (24,000 Btu)* 3800
q
Air Conditioner (40,000 Btu)* 6000
q
Battery Charger (20 Amp) 500
q
Circular Saw (6-1/2”) 800 to 1000
q
Clothes Dryer (Electric)* 5750
q
Clothes Dryer (Gas)* 700
q
Clothes Washer* 1150
q
Coffee Maker 1750
q
Compressor (1 HP)* 2000
q
Compressor (1/2 HP)* 1400
q
Compressor (3/4 HP)* 1800
q
Curling Iron 700
q
Dehumidifier* 650
q
Electric Blanket 400
q
Electric Range (per element) 1500
q
Electric Skillet 1250
q
Freezer* 700
q
Furnace Fan (1/2 HP)* 800
q
Garage Door Opener* 500 to 750
q
Hair Dryer 1200
q
Hand Drill 250 to 1100
q
Iron 1200
q
Jet Pump* 800
q
Light Bulb 100
q
Microwave Oven 700 to 1000
q
Milk Cooler* 1100
q
Oil Burner on Furnace 300
q
Oil Fired Space Heater (140,000 Btu) 400
q
Oil Fired Space Heater (30,000 Btu) 150
q
Oil Fired Space Heater (85,000 Btu) 225
q
Radio 50 to 200
q
Refrigerator 700
q
Slow Cooker 200
q
Submersible Pump (1 HP)* 2000
q
Submersible Pump (1/2 HP)* 1500
q
Submersible Pump (1-1/2 HP)* 2800
q
Sump Pump* 800 to 1050
q
Table Saw (10”)* 1750 to 2000
q
Television 200 to 500
q
Toaster 1000 to 1650
Running Watts
*Allow three (3) times listed watts for starting device
Essential Circuit Selection
When selecting the essential circuits that will be switched to “Standby Power,” it is important that the sum of the combined circuit loads does not exceed the wattage/ amperage capacity of the generator. To help you with your selection of essential circuits, please consider the following:
• Add up the total wattage of all electrical devices to be
connected at one time. This total should NOT be greater than the generator’s wattage capacity.
The rated wattage of lights can be taken from light
bulbs. The rated wattage of tools, appliances and motors can usually be found on a data plate or decal affixed to the device.
• If the appliance, tool or motor nameplate does not list wattage, multiply volts times the ampere rating to determine watts (Volts x Amps = Watts).
Some electric motors (induction types) require about
three times more watts of power for starting than for running. This surge lasts for only a few seconds. Be sure you allow for this high starting wattage when selecting electrical devices that will be energized by the home generator:
• Figure the watts required to start the largest motor.
• Add that to the total running watts of all other
connected loads.
This Briggs & Stratton home generator complies with the following “stationary standby power rating”:
The standby power rating is applicable for supplying
power for the duration of normal power interruption. No sustained overload capability is available for this rating.
This rating is applicable to installations served by
a reliable normal utility source. This rating is only applicable to variable loads with an average load factor of 80% of the standby rating. The standby rating is only applicable for optional standby power where the generator set serves as the backup to the normal utility source.
Use the wattage reference table provided and mark those circuits you consider “critical” or “essential”. Make sure you and your installer consider the system’s altitude above sea level and the ambient temperature range when determining total generator load.
IMPORTANT: When using the 100 Amp or 200 Amp transfer switch with the home generator, you must turn off any non essential loads. Failure to turn off non essential loads could overload the generator causing it to shut down.
Some examples of non essential loads are as follows:
• Pool pump
• Hot tub
• Electric hot tub and/or pool heaters
• Central air conditioners
• Electric hot water heaters
• Electric range and/or oven
• Arc welder
• Non essential electric heaters
Delivery Inspection
Carefully inspect the home generator for any damage that may have occurred during shipment.
IMPORTANT: If loss or damage is noted at time of delivery, have the person(s) making delivery note all damage on the freight bill and affix his signature under the consignor’s memo of loss or damage. If loss or damage is noted after delivery, separate the damaged materials and contact the carrier and your installer for claim procedures. Missing or damaged parts are not warranted.
The home generator is supplied with:
• Home generator
• Pre-attached mounting pad
• UL569/CSA8.3-listed flexible fuel hook-up
• Installation and Start-up manual
• Operator’s manual
• Illustrated parts list manual
• Installation checklist
• Two access door keys
• Four lifting hole plugs
• Oil fill spout
• One spare 15A fuse
• 2 Pole connector (for 240V from house)
• 10 Pole connector (for sensing and control wires)
• Air intake engine cover
• Alternator cover
• Remote LED Indicator kit (red LED/plate/screws)
9
Features and Controls
Home Generator
Read this Operator’s Manual and Safety Rules before operating your generator.
Compare the illustrations with your generator to familiarize yourself with the locations of various controls and adjustments. Save this manual for future reference.
A
B
P
N
M
L
K
J
H
G
Generator is pictured with access doors removed for clarity A - Exhaust Port — High-performance muffler lowers engine
noise to comply with most residential codes.
B - Oil Dip Stick — Used to check the engine oil level. C - Oil Fill Cap — Remove to service the engine with
recommended oil.
D - Air Cleaner — Protects engine by filtering dust and
debris out of intake air.
E - Oil Filter — Filters engine oil to prolong system life. F - Oil Drain Hose — Provided to facilitate oil changing. G - Oil Drain Door opening — Provides access for engine
servicing.
H - Oil Fill Door opening — Provides access for engine
servicing.
C
D E F
J - Engine Label — Identifies engine model and type. K - Fuel Inlet — Fuel supply is connected here. L - Control Panel Door opening — Provides access to
control panel and battery.
M - Unit Data Decal (located on base) — Identifies unit by
serial number.
N - Battery — 12 Volt DC, 55 Amp-Hour sealed battery
provides power to start the engine.
P - Control Panel — Used for various test, operation and
maintenance functions. See System Control Panel on the next page.
System Control Panel
Compare this Control Panel illustration with your generator to familiarize yourself with the location of these important controls:
D
C
B
A
A - Set Exercise Switch — Used to set the exercise cycle
start time and day-of-the-week. Exercise cycle only occurs in AUTO mode.
B - Manual Over-Ride Switch — With system switch in
AUTO position, push the manual over-ride switch to start the generator. To turn off the generator, push and hold the manual over-ride switch again until engine stops.
C - System Switch — This two-position switch is the most
important control on the system and is used as follows:
• “AUTO” position is the normal operating position. If a utility power outage is sensed, the system will start the generator. When utility power is restored, AUTO lets the engine stabilize internal temperatures, shuts off the generator, and waits for the next utility power outage.
• “OFF” position turns off running generator, prevents unit from starting and resets any detected faults.
E
F
G
D - 15 Amp Fuse — Protects the home generator DC control
circuits. If the fuse has ‘blown’ (melted open) or was removed, the engine cannot crank or start. Replace the fuse using only an identical ATO 15A fuse.
E - Service Tool — For use by qualified service personnel
ONLY.
F - Digital Display — Displays the total number of hours
the generator has been running and fault codes. Used to schedule maintenance tasks and for troubleshooting operational problems with the home generator. All fault conditions are described in Fault Detection System.
G - Circuit Breaker — Protects the system from shorts and
other over-current conditions. Must be ON to supply power to the Automatic Transfer Switch.
11
Access Doors
The home generator is equipped with an enclosure that has three access doors, as shown below. The doors are named for a significant component located behind them, as follows:
A Control Panel door B Fuel Inlet Port (shown for reference) C Oil Fill door D Oil Drain door E Exhaust Port (shown for reference)
WARNING
Contact with muffler area can result in serious burns.
DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
Each home generator is equipped with two identical keys. These keys fit the locks that secure the access doors.
To Open an Access Door:
1. Insert key into lock of access door you wish to open and turn one quarter turn counterclockwise.
2. Grasp door’s handle and turn one quarter turn counterclockwise to open. Remove key.
To Close an Access Door:
1. Close door and turn doors handle one quarter of a turn clockwise.
2. Insert key into lock of access door and turn one quarter turn clockwise. Remove key.
E
C
A
B
D
Operation
Important Owner’s Considerations
Engine Oil
This engine is shipped from the factory filled with the recommended oil. Before starting the engine, check oil level and ensure that engine is serviced as described in the engine operator’s manual. See Engine Oil in Maintenance.
NOTICE
Any attempt to crank or start the engine before it has been properly serviced with the recommended oil will result in equipment failure.
Refer to Maintenance and engine manual for oil fill
• information.
Damage to equipment resulting from failure to follow this
• instruction will void engine and generator warranty.
Battery
The home generator is supplied with a sealed, lead-acid, rechargeable, 12 Volt DC 55 Amp-Hour, valve regulated battery. It is installed in the unit and the battery cables are connected at the factory.
With the battery installed, all wiring to transfer switch and home generator completed, utility power supplied to the Automatic Transfer Switch, and the unit in AUTO mode, the battery receives a trickle charge while the engine is not running. The trickle charge cannot be used to recharge a battery that is completely discharged.
15 Amp Fuse
The generator’s 15 Amp fuse was removed at the factory to prevent the unit from starting during shipping. Your installer will ensure the fuse is properly installed upon completion of the installation.
Automatic Operation
To select automatic operation, do the following:
1. Set the service disconnect or main distribution panel circuit breaker that sends utility voltage to the transfer switch to ON.
2. Set the generator’s main circuit breaker to its ON position.
3. Set the system switch to AUTO.
CAUTION
With the system switch set to AUTO, the engine may crank and start at any time without warning. Such automatic starting normally occurs when utility source voltage drops below a preset level or during the normal exercise cycle.
To prevent possible injury that may be caused by such
• sudden starts, always set the system switch to OFF.
Remove the 15 Amp fuse before working on or around
• the generator or transfer switch.
Checking Automatic Operation
To check the system for proper automatic operation, proceed as follows:
1. Turn OFF the service disconnect or main distribution
panel circuit breaker sending power to the automatic transfer switch.
The engine will crank and start when the utility voltage drops out and the sensor has timed out. Let the system go through its entire automatic operation sequence.
2. With the generator output supplying its loads, turn ON
the service disconnect or main distribution panel circuit breaker that supplies utility power to the Automatic Transfer Switch.
3. The automatic transfer switch will transfer loads back to the utility power after 5 minute minimum run time and utility is restored.
4. The generator will run for an additional one minute for engine cool down, then shut down.
NOTE: If utility is restored and generator does not shut down after 10 minutes, set system switch to OFF and contact your installer or local service center.
This completes the test procedures for automatic operation. The home generator will now start automatically when utility power is lost and will supply power to the transfer switch.
13
Setting Exercise Timer
The home generator is equipped with an exercise timer that will start and exercise the system once every seven days. During this exercise period, the unit runs for approximately 20 minutes and then shuts down. Electrical load transfer DOES NOT occur during the exercise cycle (unless a utility power outage occurs).
A button on the control panel is labeled “Set Exercise” (see System Control Panel). The specific day and the specific time of day this button is pressed is programmed into the control board memory. This date and time is then used to automatically initiate the system exercise cycle. The “SET EXERCISE” legend on the control panel will flash until the set exercise cycle is set.
To perform the Set Exercise procedure:
1. Choose the day and time you want your home generator to exercise.
2. On that day and time, press and hold down the “Set Exercise” button for three seconds.
NOTE: “SET EXERCISE” will flash until the button is pressed for three seconds, then “SET EXERCISE” will illuminate for 5 seconds, and finally turn off.
For example, if you press the “Set Exercise” button on Sunday morning at 10:00 AM, the unit will run an exercise cycle the following Sunday at 10:00 AM (+/- 1/2 hour).
NOTE: “Set Exercise” will only work if the unit is in the Automatic mode and this exact procedure is followed. The exerciser will need to be re-set if the 15 Amp fuse is removed or changed, or if the 12 Volt DC battery is disconnected.
If you want to change the day and time the unit exercises, simply perform the “Set Exercise” procedure at the exact weekday and time you want it to take place.
Maintenance
Servicing the System
To service system:
1. Set the system switch to OFF.
2. Set the generator’s main circuit breaker to its OFF
position.
3. Utility voltage is present. Disconnect power before servicing by removing the two 2 Amp fuses from the transfer switch.
Fault Detection System
The generator may have to run for long periods of time with no operator present. For that reason, the system is equipped with sensors that automatically shut down the generator in the event of potentially damaging conditions, such as low oil pressure, high oil temperature, over speed, and other conditions.
The generator’s control panel has a digital display that shows fault codes, like “FC_1”. The table below lists the detected fault, the fault code as displayed on the control panel, and the number of blinks seen on the remote LED indicator.
Fault Description Fault Codes LED Flashes
Low battery voltage FC_1 1 Low oil pressure FC_2 2 Low voltage FC_3 3 Engine fails to start FC_4 4 Low frequency FC_5 5 Engine overspeed FC_6 6 High temperature FC_7 7 Transfer switch fault FC_8 8
The remote LED indicator is installed at a convenient inside location. The LED will remain lit when the generator is in AUTO. The LED will turn on and off in a series of blinks that correspond to the fault detected in your home generator. The blink pattern is repeated with a brief pause between each series of blinks.
Reset Fault Detection System
The operator must reset the fault detection system each time it activates. To do so, place the system switch in the OFF position for 5 seconds or more. Remedy the fault condition, then return the home generator to service by placing the system switch in the AUTO position.
A description of each fault and suggested remedies are as follows:
No LED - Discharged Battery
If there is a detected fault condition but the LED is not blinking, this is because the battery is completely discharged. To remedy the problem, remove the 15 Amp fuse and disconnect the battery from the generator. Take the battery to a local battery store for analysis. Replace the battery after it has been fully recharged, connecting the NEGATIVE cable last. Then install the 15 Amp fuse in the control panel.
NOTE: With the battery installed, all wiring to transfer switch and home generator completed, utility power supplied to the Automatic Transfer Switch, and the unit in AUTO mode, the battery receives a trickle charge while the engine is not running. The trickle charge is not able to recharge a battery that is completely discharged. See Battery in Maintenance.
Low Battery Voltage
This fault is indicated by fault code FC_1 and one blink on the LED indicator. This condition occurs if the generator cannot start because the starting battery output power is below that needed to crank the engine. Causes for this problem may be a faulty battery or battery charge circuit.
To remedy the problem, contact your local service center to check the battery charge output. Remove the 15 Amp fuse and disconnect the battery from the generator. Take the battery to a local battery store for analysis.
Replace the battery after it has been fully recharged, connecting the NEGATIVE cable last. Then install the 15 Amp fuse.
Low Oil Pressure
This fault is indicated by fault code FC_2 and two blinks on the remote LED indicator. The unit is equipped with an oil pressure switch (A). The oil drain connection (B) is shown for identification.
The oil pressure switch uses normally closed contacts that are held open by engine oil pressure during operation. Should oil pressure drop below the 8 psi range, switch contacts close and the engine is shut down.
To remedy the low oil pressure condition, add the recommended oil to the FULL mark on the dipstick.
If the low oil pressure condition still exists, the engine will start, then shut down after about 20 seconds. The fault code will appear and the LED will flash. In this case, contact a Briggs & Stratton Authorized Dealer.
Low Voltage (Generator)
This fault is indicated by fault code FC_3 and three blinks on the LED indicator. This condition is caused by a restriction in the fuel flow, a broken or disconnected signal lead, a failed alternator winding, the control panel circuit breaker is open, or the generator is overloaded.
To remedy the problem, contact your installer or a Briggs & Stratton Authorized Dealer.
Engine Fail To Start
This fault is indicated by fault code FC_4 and four blinks on the LED indicator. This feature prevents the generator from damaging itself if it continually attempts to start in spite of another problem, such as no fuel supply. Each time the system is directed to start, the unit will crank for 10 seconds, pause for 10 seconds, and repeat. If the system does not begin producing electricity after approximately 2 minutes, the unit will stop cranking and the LED will blink.
Check to make sure the generator’s main circuit breaker is in the ON position in order for the sensing leads to verify that the unit is running.
The most likely cause of this problem is no fuel supply. Check the inside and outside fuel shut off valves to ensure they are fully open. Other causes could be failed spark plug(s), failed engine ignition, or the engine air filter is clogged. You may need to contact your installer for assistance if you can’t remedy these problems.
Low Frequency
This fault is indicated by fault code FC_5 and five blinks on the LED indicator. This feature protects devices connected
A
to the transfer switch by shutting the generator down if the engine runs slower than 55 Hz for three seconds. This condition is caused by a failed engine governor or by excessive loads on the generator. To remedy the problem, contact your installer or a Briggs & Stratton Authorized Dealer.
B
15
Engine Overspeed
This fault is indicated by fault code FC_6 and six blinks on the LED indicator. This feature protects devices connected to the transfer switch by shutting the generator down if the engine happens to run faster than the preset limit. The overspeed fault is detected as follows:
• If the generator output frequency is 65-70 Hz, after three seconds, the generator will shut down.
• If the generator output frequency is greater than 70 Hz, the generator will shut down immediately.
This condition is caused by a failed engine governor. To remedy the problem, contact your installer or a Briggs & Stratton Authorized Dealer.
High Temperature
This fault is indicated by fault code FC_7 and seven blinks on the LED indicator. The contacts of the temperature switch (A) are normally open. The Oil Drain connector (B) is shown for reference. If the engine oil temperature exceeds approximately 148.9°C (300°F), the fault is detected and the engine shuts down.
A
Generator Maintenance
The generator warranty does not cover items that have been subjected to operator abuse or neglect. To receive full value from the warranty, the operator must maintain the system as instructed in the engine operator’s manual.
All adjustments should be made at least once each season. Follow the requirements in the engine operator’s manual.
Generator maintenance consists of keeping the unit clean. Operate the unit in an environment where it will not be exposed to excessive dust, dirt, moisture or any corrosive vapors. Cooling air louvers on the enclosure must not become clogged with snow, leaves, or any other foreign material.
Check the cleanliness of the unit frequently and clean when dust, dirt, oil, moisture or other foreign substances are visible on its exterior/interior surface.
NOTE: DO NOT use direct spray from a garden hose to clean generator. Water can enter the engine and generator and cause problems.
Engine Oil
The system is filled with synthetic oil (API SJ/CF 5W-30W). This allows for system operation in the widest range of temperature and climate conditions.
NOTE: The use of synthetic oil does not alter the required oil change intervals described in the engine operator’s manual.
B
Common causes for this condition include running the unit with all access doors removed, obstructed air inlet or exhaust port, low oil level, or debris in the engine cylinder cooling fins.
To resolve the problem, let the engine cool down and remove any accumulated debris and obstructions. Ensure that the access doors are installed whenever the unit is running.
Transfer Switch Fault
This fault is indicated by fault code FC_8 and eight blinks on the LED indicator (if transfer switch is equipped with fault detection). The most likely cause of this fault is a blown fuse in the transfer switch.
To remedy the problem, contact your installer or a Briggs & Stratton Authorized Dealer.
Changing Engine Oil
• Place the oil drain tube into an approved container.
• Push in and rotate the oil drain fitting 1/4 turn counterclockwise. Slowly pull outward until oil starts draining. DO NOT pull the oil drain fitting off the engine.
• When the oil has drained, push the oil drain fitting in and rotate 1/4 turn clockwise until it locks in place.
• Slide the oil drain tube up into the clamp on the generator.
NOTICE
WARNING
Any attempt to crank or start the engine before it has been properly serviced with the recommended oil will result in equipment failure.
Refer to Maintenance and engine manual for oil fill
• information.
Damage to equipment resulting from failure to follow this
• instruction will void engine and generator warranty.
To fill your engine with oil:
Follow the synthetic oil grade recommendation and oil fill instructions given in the engine operator’s manual.
Battery
Charging the Battery
If it is necessary to charge the battery, proceed as follows:
1. Set generator’s system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Disconnect negative battery cable to negative battery
terminal (indicated by NEGATIVE, NEG, or (-).
NOTICE
Failure to disconnect negative battery cable will result in equipment failure.
DO NOT attempt to jump start the battery.
• Damage to equipment resulting from failure to follow this
• instruction will void warranty.
4. Charge battery with battery charger at 2 Amps until battery holds 12 Volts.
NOTE: DO NOT exceed 13.7 Volts charging.
Storage batteries give off explosive hydrogen gas during recharging.
Slightest spark will ignite hydrogen and cause explosion.
Battery electrolyte fluid contains acid and is extremely caustic.
Contact with battery contents will cause severe chemical burns.
A battery presents a risk of electrical shock and high short circuit current.
DO NOT dispose of battery in a fire.
• DO NOT allow any open flame, spark, heat, or lit cigarette
• during and for several minutes after charging a battery.
DO NOT open or mutilate the battery.
• Wear protective goggles, rubber apron, and rubber
• gloves.
Remove watches, rings, or other metal objects.
• Use tools with insulated handles.
NOTE: With the battery installed and utility power available to the transfer switch, the battery receives a trickle charge whenever the engine is not running. It may take up to 72 hours to fully charge a battery from 5 Volts with the trickle charge. The trickle charge is not able to recharge a battery that is completely discharged.
5. Connect negative battery cable to negative battery
terminal (indicated by NEGATIVE, NEG, or (-)).
6. Ensure hardware on both positive and negative battery terminals is secure.
7. Reinstall 15 Amp fuse in control panel.
CAUTION
Installing the 15A fuse could cause the engine to start.
DO NOT install this fuse until all plumbing and wiring has
• been completed and inspected.
8. Set generator’s system switch to AUTO.
17
Servicing the Battery
If it is necessary to service the battery, proceed as follows:
1. Open “Control Panel” access door.
2. Set generator’s system switch to OFF.
3. Remove 15 Amp fuse from control panel.
4. Service or replace battery as required.
5. Connect red battery cable to battery positive terminal
(indicated by POSITIVE, POS, or (+)).
6. Connect negative battery cable to negative battery
terminal (indicated by NEGATIVE, NEG, or (-).
7. Ensure hardware on both positive and negative battery terminals is secure.
8. Reinstall 15 Amp fuse in control panel.
9. Set generator’s system switch to AUTO.
10. Close “Control Panel” access door.
11. Reset excercise timer. See Setting Excercise Timer.
To Clean the Generator
NOTICE
Improper treatment of generator can damage it and shorten its life.
DO NOT expose generator to excessive moisture, dust,
• dirt, or corrosive vapors.
DO NOT insert any objects through cooling slots.
• Use a damp cloth to wipe exterior surfaces clean.
• Use a soft, bristle brush to loosen caked on dirt, oil, etc.
• Use a vacuum cleaner to pick up loose dirt and debris.
• Use low pressure air (not to exceed 25 psi) to blow away dirt. Inspect cooling air slots and openings on the generator. These openings must be kept clean and unobstructed.
When Calling the Factory
You must have the following information at hand if it is necessary to contact a local service center regarding service or repair of this unit:
1. Obtain the unit Model Number and Serial Number from the unit data decal. See Controls.
2. Obtain the engine Model/Type/Code numbers from the engine label. See Controls. Please note that the model number may vary slightly from that presented herein.
Storage
The Briggs & Stratton home generator is designed for continuous backup operational duty. As such, there is no need to take any storage precautions. However, if it becomes necessary to take the system out of service for an extended period, call Briggs and Stratton Technical Services at (800) 743-4115, between 8:00 AM and 5:00 PM CT for specific recommendations.
Troubleshooting
Problem Cause Correction
Engine is running, but no AC output is available.
Engine runs good at no-load but “bogs down” when loads are connected.
Engine will not start; or starts and runs rough.
Engine shuts down during operation.
Loss of power on essential circuits.
1. Circuit breaker open or defective.
2. Fault in generator.
3. Poor wiring connections or defective transfer switch.
1. Short circuit in a connected load.
2. Generator is overloaded.
3. Shorted generator circuit.
4. Fuel Pressure is incorrect.
5. Natural gas fuel mixture is incorrect.
6. Kinked fuel line between regulator and engine.
1. 15 Amp fuse missing or blown.
2. Fuel supply turned off or depleted.
3. Failed battery.
1. Fuel supply turned off or depleted.
2. Fault indicator blinking.
1. Generator circuit breaker is open.
2. Transfer switch problems.
1. Reset or replace circuit breaker.
2. Contact local service facility.
3. Check and repair.
1. Disconnect shorted electrical load.
2. See Essential Circuits.
3. Contact local service facility.
4. See Gaseous Fuel System in the Installation Manual.
5. See Gaseous Fuel System in the Installation Manual.
6. Remove kink in fuel line. Replace if necessary.
1. Install (new) 15 Amp fuse. See System Control Panel.
2. Open fuel valve(s); check propane tank.
3. Replace battery.
1. Check fuel valves, fill propane tank.
2. Count blinks and refer to Fault Detection System.
1. Reset circuit breaker.
2. See the transfer switch manual.
19
BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC 12KW, 15KW and 20KW HOME GENERATOR OWNER WARRANTY POLICY
Effective September 1, 2005 replaces all undated Warranties and all Warranties dated before September 1, 2005
LIMITED WARRANTY
Briggs & Stratton Power Products Group, LLC will repair or replace, free of charge, any part(s) of the equipment that is defective in material or workmanship or both. Transportation charges on product submitted for repair or replacement under this warranty must be borne by purchaser. This warranty is effective for the time periods and subject to the conditions stated below. For warranty service, find the nearest Authorized Service Dealer in our dealer locator map at BRIGGSandSTRATTON.COM.
THERE IS NO OTHER EXPRESS WARRANTY. IMPLIED WARRANTIES, INCLUDING THOSE OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED TO ONE YEAR FROM PURCHASE, OR TO THE EXTENT PERMITTED BY LAW. ANY AND ALL IMPLIED WARRANTIES ARE EXCLUDED. LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES ARE EXCLUDED TO THE EXTENT EXCLUSION IS PERMITTED BY LAW. Some states or countries do not allow limitations on how long an implied warranty lasts, and some states or countries do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation and exclusion may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from state to state or country to country.
WARRANTY PERIOD
Warranty
Consumer Use Commercial Use
The warranty period begins on the date of purchase by the first retail consumer or commercial end user, and continues for the period of time stated in the table above. “Consumer use” means personal residential household use by a retail consumer. “Commercial use” means all other uses, including use for commercial, income producing or rental purposes. Once equipment has experienced commercial use, it shall thereafter be considered as commercial use for purposes of this warranty.
NO WARRANTY REGISTRATION IS NECESSARY TO OBTAIN WARRANTY ON BRIGGS & STRATTON PRODUCTS. SAVE YOUR PROOF OF PURCHASE RECEIPT. IF YOU DO NOT PROVIDE PROOF OF THE INITIAL PURCHASE DATE AT THE TIME WARRANTY SERVICE IS REQUESTED, THE MANUFACTURING DATE OF THE PRODUCT WILL BE USED TO DETERMINE THE WARRANTY PERIOD.
An extended fourth year of Consumer Use warranty for the engine and alternator is available by completing the customer registration card and the installation checklist and returning both to Briggs & Stratton Power Products, LLC.
3 years or 1500 Hours, whichever comes first None
ABOUT YOUR WARRANTY
We welcome warranty repair and apologize to you for being inconvenienced. Any Authorized Service Dealer may perform warranty repairs. Most warranty repairs are handled routinely, but sometimes requests for warranty service may not be appropriate. For example, warranty service would not apply if equipment damage occurred because of misuse, lack of routine maintenance, shipping, handling, warehousing or improper installation. Similarly, the warranty is void if the manufacturing date or the serial number on the equipment has been removed or the equipment has been altered or modified. During the warranty period, the Authorized Service Dealer, at its option, will repair or replace any part that, upon examination, is found to be defective under normal use and service. This warranty will not cover the following repairs and equipment:
Normal Wear: Outdoor Power Equipment and engines, like all mechanical devices, needs periodic parts and service to perform well. This warranty does not cover repair when normal use has exhausted the life of a part or the equipment.
Installation and Maintenance: This warranty does not apply to equipment or parts that have been subjected to improper or unauthorized installation or alteration and modification, misuse, negligence, accident, overloading, overspeeding, improper maintenance, repair or storage so as, in our judgment, to adversely affect its performance and reliability. This warranty also does not cover normal maintenance such as adjustments, fuel system cleaning and obstruction (due to chemical, dirt, carbon, lime, and so forth).
Other Exclusions: This warranty excludes wear items such as oil gauges, o-rings, filters, fuses, or spark plugs, etc., or damage or malfunctions resulting from accidents, abuse, modifications, alterations, or improper servicing or freezing or chemical deterioration. Accessory parts are excluded from the product warranty. This warranty excludes failures due to acts of God and other force majeure events beyond the manufacturers control. Also excluded is used, reconditioned, and demonstration equipment; equipment used for prime power in place of utility power and equipment used in life support applications. 198181-E, Rev. C, 12/31/2006
BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC
JEFFERSON, WI, USA